1. The 120/240 panel they want to use to power the Fans and 2 small machines, does not have enough room for all the new circuit breakers, do they want to add a sub-panel?
-Yes
1. They want to keep the existing plug for one of the machines, the machine is 220v but the plug is 380-415v rated, that is not allowed.
-Change plug to match machine specifications
1. The existing disconnect they want to keep does not have enough clearance, code requires 3 feet in front of disconnect.
-Relocate disconnect to be within 3 feet clearance
1. What type of air-line do they want, what material, and what size?
-Hardline to hose reels. 3/8 ID/300 PSI
1. Will CE require that any design changes/materials the vendor uses (building 61685 61686) be in accordance with a certain color/color scheme for the power upgrade for air compressor ?
-Yes, paint match to existing lines