Well & Well Pump Information

This Information was updated on: July 8, 2013

Well Log: DESC 5743

• Pitless Adapter was installed in 2008.

Elevations:

• 4498’ Ground Elevation

• 4495.5’ 3” Galvanized Steel Pipe Outlet Elevation

• 4495.0’ Pitless Adapter Welded to Well Casing

• 4093.5’ Approximate Water Surface. (23.5’ above the pump)

• 4072’ Pressure Transducer

• 4071’ Submersible Well Pump (427’ below finished ground).

• 4071’ Top of Shroud attached to well pump

• 4071’ End of air hose, attached to drop pipe at top of pump.

• 4059’ Bottom of well pump shroud. (Shroud is 12’ long.)

Water Level Gauge & Air Hose

• Air hose for water level gauge was installed with new pump in 2013.

• One end of the air hose is located inside the transducer control box. The other end is attached just above the pump, at 427’ below grade.

Pump Shroud

• The existing pump shroud was cleaned and reinstalled with the pump in 2008.

• 8” diameter x 12’ long.

• 0.40 screen opening.

• Plate welded to bottom of screen.

Pump Info

• Pump Installed in June 2013.

o Pump Manufacturer: Goulds Pumps o Pump Model: 95L20 o Pump Serial#: 102G05980 o Franklin Motor Model: 2366148120

20HP, 3ph., 460/380V

• Well pump test, in June 2013, found that:

o The flow through pump-to-waste was 80 GPM.

o Well water level at start of test was 23.60’ above pump.

o Well water level, after 4 hours of pumping at 80 GPM, was 23.46’ above pump.

History & Notes

• In 2008, the water system was replaced. This included the pitless adapter, submersible well pump, drop pipe, waterline from the well to the well house, well house plumbing & controls, waterline from well house to the connection just outside of the Visitor Center building & waterline outside of the VC building, and control cables from the well house to the VC building. The project demolished the buried concrete reservoir tank, located just adjacent to the well house. This project did NOT replace the well house pressure tank; and did NOT replace the waterline that supplies the RV/trailer area.

• The well pump that was installed in 2008 (Red Jacket Water Products, model 20HP 16ST6 16MB6) failed and was replaced in 2013.

• In 2013, a new submersible well pump was installed. Goulds Pump, model 95L20; 20HP, 3ph., 460/380V; capable of pumping 80 GPM.