Q. What is the maximum & minimum flow (GPM) the load bank will see?

A. See Below

Q. What is the maximum & minimum pressure the load bank will see?

A. See Below

Q. What are the operating temperatures?

A. See Below

Description Supply PSI (Range) Flow Range (GPM) Operating Temps. Output Signals PAO Fluid 0-150 0-35 0 - 120 Deg F 4-20 mA EGW Fluid 0-160 0-50 0 - 120 Deg F 4-20 mA

Coolanol Fluid 0-160 0-10 0 - 180 Deg F 4-20 mA

Q. Do you require an output signal from the pressure & flow devices, if so will that be a current 4-20mA or voltage 0-10vdc ?

A. Exact pressure, flow and temperature sensor range can be discussed for clarification for resolution requirements

Q. I am assuming you would like this device to be mounted in a protective frame, if not please advise the orientation.

A. Mounting Configuration: Contractor shall provide a design sketch of device build, to include frame details. Example is on-site

Attachment 2 Questions and Answers