DESCRIPTION
GEOTHERMAL HEAT PUMP SCHEDULE (PHASE II)
TAG HP-1 HP-2 HP-3 HP-4
AREA SERVED
NOMINAL TONNAGE 15 6 15 15
MAKE MAMMOTH MAMMOTH MAMMOTH MAMMOTH
MODEL G180VLF G072VLB G180VLF G180VLF
TYPE VARIABLE VOL. VARIABLE VOL. VARIABLE VOL. SINGLE ZONE VAV
CFM 5100 2000 5100 5700
ESP 2 0.65 2 2
COOLING CAPACITY MBH
EAT 80/67 80/67 80/67 80/67
LAT 58/55 57/55 59/55 60/57
TOTAL CAPACITY 181714 74095 181714 184804
HEATING CAPACITY
EAT 60 60 60 60
LAT 93.3 91.1 93.3 91.2
TOTAL CAPACITY 120011 31004 120011 120870
WATER FLOW
FLUID 30% PROP. GLYCOL 30% PROP. GLYCOL 30% PROP. GLYCOL 30% PROP. GLYCOL
GPM 39 20 39 39
WPD 29.2 31 29.2 29.2
EWT / LWT HEATING 37/32.9 37/33.9 37/32.9 37/32.8
EWT / LWT COOLING 60/71 60/68.6 60/71 60/71.2
EER 14.3 19.1 14.3 14
COP 2.6 3.1 2.6 2.6
ELECTRICAL
VOLTAGE 460/3/60 460/3/60 460/3/60 460/3/60
MCA 37.2 15.9 37.2 37.2
MAX FUSE 45 25 45 45
DIMENSIONS
LXWXH 100x35x76 31x29x81 100x35x76 100x35x76
WEIGHT 2440 770 2440 2440
NOTES:
1. DIRECT DRIVE PLENUM FANS, BELTS NOT ALLOWED
2. DIGITAL SCROLL COMPRESSOR WITH SUCTION PRESSURE DEMAND LIMITS
3. COMPRESSOR BLANKETS SOUND ATTENUATION
4. FULL MICROPROCESSOR SAFETY AND TEMPERATURE CONTROLS WITH EPIC DDC CONTROLLER
5. DISCHARGE AIR CONTROL
6. FULL UNIT BREAKDOWN TO FIT THROUGH 36" DOOR, CONTROL PANEL MOUNTING, FILTER RACK
MOUNTING BY CONTRACTOR: IF NECESSARY TO REMOVE
7. LOW TEMPERATURE PACKAGE WITH FULLY INSULATED SUCTION LINES
8. BRAZED PLATE HEAT EXCHANGER ON SIZE 180 AND ABOVE
9. DISCHARGE AIR TEMP CONTROL CONTROL
10. 2" FILTER RACKS WITH HINGED DOORS
11. WATER TEMPERATURE SWITCHES BY MANUFACTURER
12. VFD FOR SUPPLY FAN WITH DUCT STATIC PRESSURE CONTROL
13. CONFIGURABLE DISCHARGE AIR ORIENTATION VIA PLENUM FAN OPENING RELOCATION
PUMP SCHEDULE
TAG P-5/6
MAKE BELL & GOSSETT
SERIES 1510
MODEL 2AC
STYLE BASE MOUNTED
GPM 133
FT-HEAD 40
MOTOR HP 3
BHP 2.09
VOLTS/PH 460/3
RPM 1750
CONTROL VFD
NOTES:
1. COORDINATE WITH DIV 26 FOR ELECTRICAL
2. VFD SHALL BEOF SAME MAKE AND MODEL AS PHASE I
CONSTRUCTION AND ALSO BE COMPATIBLE WITH NEW BAS.
SINGLE DUCT TERMINAL UNIT SCHEDULE
TAG HP ROOM MODEL SIZE CFM STATIC PRESSURE NC LEVELS ELECTRIC HEAT COIL UNIT
INFORMATIONTAG UNIT OUTLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM KW VOLTS/PH. STEPS EAT LAT
VAV-01 HP-2 OFFICE 109/STORAGE 117 DESV 06 12x8 100 50 1 0.25 0.01 - - 110 1.5 120/1 S 55 98.1 RH VAV-02 HP-1 OFFICE 108 DESV 06 12x8 225 115 1 0.25 0.04 14 13 225 3 120/1 S 55 97.1 RH VAV-03 HP-1 OPEN OFFICE 110 DESV 12 16x15 920 460 1 0.25 0.06 18 23 500 6.5 480/3 S 55 96.1 RH VAV-04 HP-1 OPEN OFFICE 110 DESV 12 16x15 920 460 1 0.25 0.06 18 23 500 6.5 480/3 S 55 96.1 RH VAV-05 HP-1 TEAM LEADER 111 DESV 08 12x10 300 150 1 0.25 0.01 14 18 300 4 120/1 S 55 97.1 RH VAV-06 HP-1 OFFICE 112 DESV 06 12x8 110 55 1 0.25 0.01 - - 110 1.5 120/1 S 55 98.1 RH VAV-07 HP-1 OFFICE 113 DESV 06 12x8 110 55 1 0.25 0.01 - - 110 1.5 120/1 S 55 98.1 RH VAV-08 HP-1 RECEPT 115/ WORKRM 114 DESV 06 12x8 230 115 1 0.25 0.04 14 13 230 3 120/1 S 55 96.2 RH VAV-09 HP-1 FOCUS TEACHING 120 DESV 10 14x13 560 280 1 0.25 0.05 18 20 250 3.5 120/1 S 55 99.2 RH VAV-10 HP-1 OPEN OFFICE 110 DESV 12 16x15 1130 565 1 0.25 0.09 20 24 750 9.5 480/3 S 55 95 RH VAV-11 HP-2 OFFICE 149/OFFICE 150 DESV 06 12x8 100 50 1 0.25 0.01 - - 100 1 120/1 S 55 86.6 RH VAV-12 HP-2 TRAVELING EXHIBIT 119/LOBBY156A DESV 10 14x13 480 240 1 0.25 0.04 17 18 240 3 120/1 S 55 94.5 RH VAV-13 HP-2 BOOKSTORE 121 DESV 10 14x13 650 325 1 0.25 0.06 19 22 400 5.5 480/3 S 55 98.5 RH VAV-14 HP-3 LOADING/STORAGE 100 DESV 10 14x13 425 215 1 0.25 0.03 16 17 240 3 120/1 S 55 94.5 RH VAV-15 HP-3 VOLUNTEERS 145 DESV 06 12x8 200 100 1 0.25 0.03 13 11 200 2.5 120/1 S 55 94.5 RH VAV-16 HP-3 MULTI-PURPOSE 141 DESV 10 14x13 650 325 1 0.25 0.06 19 22 400 5.5 480/3 S 55 98.5 RH VAV-17 HP-3 MULTI-PURPOSE 141 DESV 12 16x15 735 370 1 0.25 0.04 17 22 500 6.5 480/3 S 55 96.1 RH VAV-18 HP-3 RESOURCE 148 DESV 10 14x13 480 240 1 0.25 0.04 17 18 240 3 120/1 S 55 94.5 RH VAV-19 HP-3 CONFERENCE 138 DESV 10 14x13 480 240 1 0.25 0.04 17 18 240 3 120/1 S 55 94.5 RH VAV-26 HP-2 CORRIDOR 153 DESV 06 12x8 110 55 1 0.25 0.01 - - 110 1.5 120/1 S 55 98.1 RH
NOTES: 1. SELECTIONS ARE BASED ON TITUS AS MANUFACTURER.
2. ALL PERFORMANCE BASED ON TESTS CONDUCTED IN ACCORDANCE WITH ASHRAE 130-2008 AND AHRI 880-2008.
3. ALL NC LEVELS DETERMINED USING AHRI 885-2008 APPENDIX E.
4. ALL AIRFLOW, PRESSURE LOSSES AND HEATING PERFORMANCE VALUES HAVE BEEN CORRECTED FOR ALTITUDE.
5. UNITS OF MEASURE: DIMENSIONS (IN), AIRFLOW (CFM), WATER FLOW (GPM), AIR PRESSURE (IN WG), WATER HEAD LOSSES (FT) AND TEMPERATURES (°F).
6. IN THE "STEPS" COLUMN, CODE "S" DENOTES A MODULATING SCR HEATER.
7. THE MINIMUM SUPPLY CIRCUIT AMPACITY (MCA) AND MAXIMUM OVERCURRENT PROTECTION (MOP) RATINGS WERE CALCULATED IN ACCORDANCE WITH UL
STANDARDS BASED ON MOTOR AND ELECTRIC COIL FULL LOAD CURRENT RATINGS