Existing Door Alarm Support Hardware Submittal.pdf
PDF 469 KB Posted
- Attached to
- Z2DA--Replace H2 Wood doors Federal contract opportunity
- Solicitation number
- 36C25922Q0401
About this file
This solicitation package includes a statement of work for replacing existing wood doors with steel doors in a Veterans Affairs medical center mental health unit. The scope of work calls for removing thirty-seven existing wood patient room doors and replacing them with steel wicket doors to improve durability and mitigate risks of patient self-harm. Thirty-two doors are located in the inpatient mental health ward and five doors are in the emergency department. Requirements specify steel cores with a minimum 16-gauge thickness for the replacement doors. Contractor must also remove and reinstall existing over-the-door patient tampering alarms on twenty-five doors and confirm the system functions after installation. The period of performance is ninety calendar days from notice to proceed.
The solicitation requires adherence to all applicable safety standards and regulations. The contractor must submit for approval a site-specific safety plan, construction schedule, and documentation of personnel qualifications and training. Infection control risk assessments are also required due to work in an occupied patient area. The contractor must provide all necessary labor, materials, equipment, and supervision to complete the door replacements in accordance with specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 08 71 00-16 - IBS - Mental Health Interior Door Hardware_Redacted.pdf | ||
| 08 71 00-16R1 - IBS - Mental Health Interior Door Hardware FOR RECORD_Redacted.pdf | ||
| S05 - QNA (Replace H2 Wood doors).pdf | ||
| 36C25922Q0401_1 0001.docx | DOCX document | |
| Combined Spec (updated 06.17.22).pdf | ||
| Existing Door Alarm Switch Submittal.pdf | ||
| Combined Spec.pdf | ||
| Existing Door Alarm Electrical Components Submittal.pdf | ||
| Past Performance Questionnaire.docx | DOCX document | |
| Existing Door Photos.docx | DOCX document | |
| Existing Wood Door Submittal.pdf | ||
| Combined Drawings.pdf | ||
| 36C25922Q0401_1.docx | DOCX document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEYSWITCH - SINGLE GANG
USER’S GUIDE
1 Mounting Installation
75.1020.05.EN 20140103 - SEE OTHER SIDE FOR JAMB KEYSWITCH - Page 1 of 1
2 Precautions Shut off all power before attempting any wiring procedures.
Maintain a clean & safe environment when working in public areas.
Constantly be aware of pedestrian traffic around the area.
Always stop pedestrian traffic when performing tests that may result in unexpected reactions.
ESD electrostatic discharge: Circuit boards are vulnerable to damage by electrostatic discharge.
Before handling any board ensure you dissipate your body’s charge.
Always check placement of all wiring before powering up to insure that moving parts will not catch any wires and cause damage to equipment.
Ensure compliance with all applicable safety standards (i.e. ANSI A156.10 / A156.19) upon completion of installation.
DO NOT attempt any internal repair. All repairs and/or component replacements must be performed by BEA, Inc. Unauthorized disassembly or repair:
1. May jeopardize personal safety and may expose one to the risk of electrical shock.
2. May adversely affect the safe and reliable performance of the product will result in a voided product warranty.
3 Company Contact
MOMENTARY / ON-OFF SPDT KEYSWITCH
Corbin Russwin® #ML2200, Schlage® #B520-233 or Equivalent
SINGLE GANG KEYSWITCH
(10KEYSWITCHMOM / 10KEYSWITCHONF)
Adjust height of switch on bracket until cam triggers positively when rotated.
4.
0”
3.
0” 0.
5”
3.000”
1.500”
0.
0”
SWITCH BRACKET
CYLINDER LOCK
FACE
PLATE
SWITCH
3A @ 250VAC
YELLOW- NO
WHITE - COM
RED - NC
6A @ 125VAC
1 1/8”
MORTISE
CYLINDER
Select shape of cam shown for no. of switches used (specify when ordering cylinder).
Schlage® #B520-256, Yale® #2160, Arrow® #004, Sargent® #13-0660 or Equivalent
Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please call BEA, Inc. If you must wait for the following workday to call BEA, leave the door inoperable until satisfactory repairs can be made. Never sacrifice the safe operation of the automatic door or gate for an incomplete solution.
The following numbers can be called 24 hours a day, 7 days a week. For more information, visit www.beasensors.com.
East:
Canada and Texas:
1-866-249-7937 1-866-836-1863
Central:
West:
1-800-407-4545 1-888-419-2564
Plain Horn Strobes, Speaker Strobes, and Strobes SpectrAlert® Advance Plain Notification Appliances
SpectrAlert Advance plain horn strobes, speaker strobes, and strobes were designed to reduce installation time and meet a wide variety of Mass Notification and Emergency Communication applications. All of the plain notification appliances carry the same product specifications as the “FIRE” marked products. Compatible with our colored lenses and decal kits to provide distinctive visual signaling during and emergency. Model numbers with a “K” suffix are outdoor rated products that are listed to UL 1638 and UL 1480 and are rated from -40° F to 151° F (-40° C to 66° C) and have a NEMA 4X rating. The outdoor models ship with the plastic outdoor back box.
Plain Ceiling-Mount Speaker Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor — SPSCW-P Standard None Clear lens
— SPSCWV-P Standard None High volume dB, Clear lens
— SPSCWH-P High None Clear lens
Outdoor — SPSCWHK-P High None Clear lens
Plain Wall-Mount Speaker Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor SPSR-P SPSW-P Standard None Clear lens
— SPSWH-P High None Clear lens
Outdoor SPSRK-P SPSWK-P Standard None Clear lens
Plain Ceiling-Mount Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor — SCW-P Standard None Clear Lens
Plain Wall-Mount Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor SR-P SW-P Standard None Clear lens
— SWH-P High None Clear lens
Outdoor SRK-P SWK-P Standard None Clear lens
SRHK-P SWHK-P High None Clear lens
Notes:
• Standard Candela settings: 15, 15/75, 30, 75, 95, 110, and 115
• High Candela settings: 135, 150, 177, and 185
• -P denotes plain devices with no markings.
• *Compatible with DECAL-R and DECAL-RC for white devices (red letters) and DECAL-W or DECAL-WC for red devices (white letters).
Ceiling-Mount Horn Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor PC2R-P PC2W-P Standard None 2-Wire, Clear Lens
— PC2WH-P High None 2-Wire, Clear Lens
Wall-Mount Horn Strobes Location Red Model No. White Model No. Candela Marking* Description
Indoor P2R-P P2W-P Standard None 2-Wire, Clear Lens
— P2WH-P High None 2-Wire, Clear Lens
P4R-P P4W-P Standard None 4-Wire, Clear Lens
Outdoor P2RK-P P2WK-P Standard None 2-Wire, Clear Lens
P2RHK-P P2WHK-P High None 2-Wire, Clear Lens ayacoub Rectangle ayacoub Rectangle
SpectrAlert Advance devices can be adapted to nearly any application with the appropriate accessory. Our mounting options allow our strobes, speakers, horns, chimes, and strobe combinations to be placed in new or existing construction with professional results.
Audible Visible Accessories
Ceiling-Mount Back Boxes Location Red Model No. White Model No. Description
Indoor SBBCR SBBCW Surface-mount back box for ceiling-mount horns, strobes, horn strobes, speakers, and speaker strobes
Outdoor SA-WBBC SA-WBBCW Metal outdoor back box for ceiling-mount horns, strobes, and horn strobes
— MWBBCW Metal weatherproof back box for speakers and speaker strobes
Wall-Mount Back Boxes Location Red Model No. White Model No. Description
Indoor SBBR SBBW Surface-mount back box for wall-mount horns, strobes, and horn strobes
SBBSPR SBBSPW Surface-mount back box for wall-mount speakers and speaker strobes
Outdoor SA-WBB SA-WBBW Metal outdoor back box for wall-mount horns, strobes, and horn strobes
MWBB MWBBW Metal outdoor back box for speakers and speaker strobes
Colored Lenses - For use with plain (non-FIRE marked) strobe devices.
Ceiling Model No. Wall Model No. Color Description
LENS-AC LENS-A Amber Lens attachment for all SpectrAlert Advance plain (non-FIRE marked) indoor or outdoor, ceiling- or wall-mounted strobesLENS-BC LENS-B Blue
LENS-GC LENS-G Green
LENS-RC LENS-R Red
Decal Kits - For use with plain (non-FIRE marked) devices.
Mounting Model No. Color Description
Ceiling DECAL-RC Red Letters 60 decals* for up to 5 white devices (3 decals are required per device)
DECAL-WC White Letters 60 decals* for up to 5 red devices (3 decals are required per device)
Wall DECAL-R Red Letters 40 decals* for up to 5 white devices (2 decals are required per device)
DECAL-W White Letters 40 decals* for up to 5 red devices (2 decals are required per device)
*All decals include labels “AGENT, EVAC, ALERT and FIRE” for up to 5 devices.
Back Box Skirts Mounting Red Model No. White Model No. Description
Wall — BBS-SP201W Wall-mount back box skirt for ExitPoint Directional Sounder
— SEP-BBSW Strobe expander plate back box skirt for Dual Strobe Expander Plates
— SPSEP-BBSW Speaker strobe expander plate back box skirt for Dual Strobe Expander Plates
Optional Lens Colors ayacoub Rectangle ayacoub Rectangle ayacoub Rectangle
Specifications and Ratings
UL Max. Strobe Current Draw (mA RMS)
Candela
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
Standard Candela Range 15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High Candela Range 135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
UL Max. Horn Current Draw (mA RMS)
Sound Pattern dB
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-Temporal High 57 56 69 75
Non-Temporal Medium 42 50 60 69
Non-Temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50
Horn Output (dBA) in UL Reverberant Room
Switch Position Sound Pattern dB
8–17.5 Volts** 16–33 Volts**
24 Volt Nominal Measurements
Reverberant Anechoic
DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 75 75 80 80 86 85 96 96
3 Temporal Low 71 71 76 76 81 79 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 89 98 98
6 Non-Temporal Low 73 74 81 81 86 84 96 92
7* Coded High 82 82 88 88 93 92 101 101
8* Coded Medium 78 78 85 85 90 89 97 98
9* Coded Low 74 75 81 81 85 83 96 92 *Horn & 4-wire Horn Strobe only. **Minimum dB rating for Operational Voltage Range per UL 464.
Mini-Horn Output (dBA)
Pattern Output Level 8–17.5 VDC 8–17.5 VFWR Nominal
12 VDC
Nominal
12 VFWR 16–33 VDC
16–33
VFWR
Temporal High 68 67 71 70 78 76
Temporal Low 66 65 69 68 76 75
Continuous High 72 71 75 74 80 79
Continuous Low 70 69 73 72 78 77
UL Max. Mini-Horn Current Draw (mA RMS)
Sound Pattern Volume
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
Temporal High 12 10 17 15
Temporal Low 10 9 14 13
Non-Temporal High 22 17 29 25
Non-Temporal Low 17 13 21 19
21systemsensor.com/av
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
DC Input
8–17.5 Volts 16–33 Volts
15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
DC Input
16–33 Volts
FWR Input
16–33 Volts
135 150 177 185 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Rotary Horn and Horn Strobe Switch Settings
Setting Repetition Rate dB Level
1 Temporal Horn High
2 Temporal Horn Medium
3 Temporal Horn Low
4 Normal Horn High
5 Normal Horn Medium
6 Normal Horn Low
7* Externally Coded High
8* Externally Coded Medium
9* Externally Coded Low
*Horn and 4-wire horn strobe only.
UL Max. Chime Current Draw (mA RMS)
Sound Pattern dB
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
1 Second Chime High 34 50 58 51
1 Second Chime Low 30 51 51 54
¼ Second Chime High 34 51 50 50
¼ Second Chime Low 31 51 50 52
Temporal Chime High 30 50 48 54
Temporal Chime Low 30 47 50 51
5 Second Whoop High 32 52 34 54
5 Second Whoop Low 30 40 34 52
One Test Chime/coded High 48 49 50 50
Specifications and Ratings
ExitPoint™ Current Draw Measurements and Sound Output Guide
Speed Selection Maximum DC Operating Current
(mA RMS) (16 to 33 V)
Audibility (dBA) (16 to 33 V)
Note 1
Audibility (dBA) (16 to 33 V)
Note 2Speed
DIP
Switch
Selection Power Setting
Fast (Exit) 10 High 185 98 75
Fast (Exit) 10 Med-High 131 95 72
Fast (Exit) 10 Med 78 92 69
Fast (Exit) 10 Med-Low 76 89 66
Fast (Exit) 10 Low 64 86 63
Med-Fast 9 High 170 98 74
Med-Fast 9 Med-High 124 95 71
Med-Fast 9 Med 75 93 68
Med-Fast 9 Med-Low 73 90 65
Med-Fast 9 Low 62 87 62
Med-Slow 8 High 135 97 73
Med-Slow 8 Med-High 104 95 70
Med-Slow 8 Med 67 92 67
Med-Slow 8 Med-Low 65 89 64
Med-Slow 8 Low 57 87 61
Slow 7 High 120 98 72
Slow 7 Med-High 92 95 69
Slow 7 Med 62 92 66
Slow 7 Med-Low 61 89 63
Slow 7 Low 54 86 60 Note 1: Sound output data peak dB measured in ULC anechoic room at 10 feet.
Note 2: Sound output measured in a reverberant room at 10 feet.
Low Frequency Sounder Output (dBA) in Reverberant (UL**) and Anechoic Room:
Switch Position Sound Pattern 8–17.5 Volts** 16–33 Volts**
24 V Nominal Measurements
Reverberant Anechoic
DC FWR DC FWR DC FWR DC FWR
1 Temporal 76 76 76 76 76 76 86 86 2 Continuous 80 80 80 80 80 80 90 90 3* Coded 80 80 80 80 80 80 90 90
*Sounder ratings provided are for continuous voltage as provided by the NAC.
** Minimum dB rating for Operational Voltage Range as per UL 464.
Sound Pattern 16–33 Volts DC 16–33 Volts FWR
135 cd 150 cd 177 cd 185 cd 135 cd 150 cd 177 cd 185 cd
Temporal 277 292 325 344 296 309 343 351
Continuous 337 362 387 417 393 395 432 433
Low Frequency Sounder/Strobe Current Draw (mA) for P2H-LF High Candela Range Series:
Low Frequency Sounder Current Draw (mA) for H-LF Series:
Position Sound Pattern 8–17.5 Volts 16–33 Volts
DC FWR DC FWR
1 Temporal 191 262 138 166 2 Continuous 292 384 138 208 3 Coded 292 388 153 205
NOTE: In position 3, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the sounder output will remain constantly on. Coded ratings provided are for continuous voltage.
Position 3 is not available on 2-wire low frequency sounder/strobe products.
23systemsensor.com/av
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
K Series Operating Temperature –40°F to 151°F (–40°C to 66°C)
Humidity Range 10% to 93% non-condensing (indoor products)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated
24 DC/FWR1
Operating Voltage Range2
8 V to 17.5 V (12 V nominal) or 16 V to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 AWG to 18 AWG
Ceiling-Mount Dimensions (including lens)
6.8 in Dia. × 2.5 in H (173 mm Dia. × 64 mm H)
Wall Weatherproof Back Box Dimensions
5.7 in L × 5.1 in W × 2.0 in D (145 mm L × 130 mm W × 51 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is an unfiltered, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
3. To calculate current draw for 4-wire horn strobes, combine horn and strobe current draws from the tables at left.
Specifications
Indoor Speaker and Speaker Strobe Sound Output
UL Reverberant (dBA @ 10 ft.) 2 W 1 W ½ W ¼ W
Wall- and Ceiling-Mount SP Series 86 83 80 77
Wall- and Ceiling-Mount SPV Series 90 87 84 81
Wall- and Ceiling-Mount SPS Series 85 82 79 76
Wall- and Ceiling-Mount SPSV Series 89 86 83 80
Outdoor Speaker and Speaker Strobe Sound Output
UL Reverberant (dBA @ 10 ft.) 2 W 1 W ½ W ¼ W
Wall- and Ceiling-Mount Speaker K Series 90 87 84 81
Wall- and Ceiling-Mount Speaker Strobe K Series 89 86 83 80
Candela Measurements, Amber Lens Strobe
Candela On-Axis Rating (UL 1638)
Standard Candela Range 15 15
15/75 15/75
30 30
75 75
95 95
110 110
115 115
High Candela Range 135 135
150 150
177 177
185 185
File details come from the government source that posted it. Updated .