Exhibit Q Unit Spec sheet.pdf

PDF 11 MB Posted

Attached to
Replace EOL HVAC Unit ITE 38
Solicitation number
ISD-348339-SM
Issued by

About this file

This exhibit specification sheet outlines the technical requirements for replacing end-of-life HVAC units at Fermi National Accelerator Laboratory. The Department of Energy solicitation seeks to procure new HVAC units to replace aging ITE 38 equipment. Bidders must meet the minimum specifications for the new units detailed in the 11MB exhibit, including product dimensions, cooling and heating capacities, electrical requirements, controls, warranties and certifications. The replacement project aims to upgrade the laboratory's climate control infrastructure in a cost-effective manner while maintaining continuity of operations. Responses to the solicitation are due by the specified deadline to allow for completion of installation prior to extreme temperature conditions.

View the file

Other files

File Type Posted
Amendment 01.pdf PDF
Amendment 02.pdf PDF
Exhibit A..a - Proposal Form.doc DOC document
Exhibit Q Table 50. Unit wiring with electric heat (continued).pdf PDF
Exhibit D 010010_General_Requirements_3_2022_7.docx DOCX document
Exhibit C 2 022 Construction Insurance Requirements.pdf PDF
Exhibit L Statement and Acknowledgment SF1413.pdf PDF
Exhibit J Payment Bond FL-42 (Rev. 12-12-2022) SF25A (Rev 8-2016).pdf PDF
1.0 RFP Instructions to Offerors.docx DOCX document
Exhibit Q Unit Specs without Heat.png PNG image
Exhibit M PUR-466_Proposal Certifications.pdf PDF
Exhibit G Section 014100 Quality Requirements - March 2022.pdf PDF
Exhibit I Bid Bond FL-41 (Rev. 12-12-2022) SF24.pdf PDF
Exhibit B RFP FRA General Terms and Conditions for Construction (05-2023).pdf PDF
Exhibit O Director Safety Letter.pdf PDF
Exhibit A SOW_WO921094_NLE_EOL_HVAC_REPLACEMENT.docx DOCX document
Exhibit H Fermilab Subcontractor Safety Information Questionnaire.pdf PDF
Exhibit Q General Decision Number IL20230020 5-12-2023.docx DOCX document
Exhibit F 013100_ESH_Requirements_3-2022_8.docx DOCX document
Exhibit E 013300_Submittals_3.docx DOCX document
Exhibit N SARC_Subcontractor Annual RepsCerts Rev 3.pdf PDF
Exhibit K Performance Bond FL-40 (Rev. 12-12-2022) SF25 (Rev 8-2016).pdf PDF
Exhibit Q breaker for NLE.jpg JPG image
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

May 2023 RT-PRC096C-EN

Product Catalog Packaged Rooftop Air Conditioners Precedent™ Cooling and Electric Heat Standard Efficiency 6 to 25 Tons — 60 Hz

©2023 Trane RT-PRC096C-EN

Introduction Packaged Rooftop Air Conditioners

Trane’s customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Precedent™.

Precedent™ features cutting edge technologies: reliable compressors, Trane engineered Symbio controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Precedent™ products are built to meet your needs.

The Precedent product is designed for comfort cooling, mixed air applications. If the product is being considered for other types of applications, such as process cooling, dedicated outdoor air, indoor agriculture, etc. Consult with your local Trane Sales Representative. Applying the units in an unintended application could result in inadequate performance and/or premature component failures.

Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionize this design concept.

Symbio control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.

With its sleek, compact cabinet, Precedent™ continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.

Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

• Corrected airflow values for 17.5 and 20 tons tables in Reheat Temperature Rise chapter.

• Updated Unit wiring and Unit wiring with electric heat tables in Electric Data chapter.

• Updated Model weights, corner weights (lbs) and center of gravity dimensions table in Weights chapter.

RT-PRC096C-EN 3

Features and Benefits Features Control Options Accessories Key Benefits

Model Number Description

General Data

Gross Cooling Capacities

Reheat Temperature Rise

Evaporator Fan Performance 6 to 10 Ton Units — Downflow 6 to 10 Ton Units — Horizontal

12.5 Ton Units — Downflow

12.5 Ton Units — Horizontal

15 to 25 Ton Units — Downflow 15 to 25 Ton Units — Horizontal

Fan Performance

Heating Performance

Controls Enhanced BAS Integration and Connectivity Secure Remote Connectivity with Trane Connect Serviceability Flexibility Economizer Controls Zone Sensors Air-Fi Wireless Communicating Zone Sensors Thermostats Humidity Control (HGRH)

Electrical Data

Dimensional Data

Weights

Table of Contents

4 RT-PRC096C-EN

Mechanical Specifications General Casing Coils Coil Guards Compressors Filters Frostat™ Indoor Fan Powered or Unpowered Convenience Outlet Stainless Steel Drain Pan Through-the-Base Electrical with Circuit Breaker Through-the-Base Electrical with Disconnect Switch Economizer (Standard) Electric Heaters Manual Outside Air Damper Motorized Outside Air Damper Powered Exhaust Roof Curb Ventilation Override Operation

Table of Contents

RT-PRC096C-EN 5

Features and Benefits Features Table 1. Precedent™ features – standard and optional

Standard Features

Options

Factory Installed Factory or Field

Installed Field

Installed 3-year Limited Parts Warranty X

5-year Limited Compressor Warranty X

2 inch Filter X

2 inch MERV 8 Filters X

2 inch MERV 13 Filters X

Access Doors X

Access Door (Control Box) X

Access Panels X

Anti-Short Cycle Timer (Standard with Symbio) X

Barometric Relief X

CO2 Sensor X

Clogged Filter Switch(a) X

Coil guards X

CompleteCoat™ Condenser Coil X

Condensate Overflow Switch(b) X

Convertible Airflow(c) X

Colored and Numbered Wiring X

Crankcase Heaters X

Humidity Control (HGRH) X

Direct Drive Plenum Fan X

Discharge Air Temperature Sensing Kit — MZVAV, SZVAV, Economizer X

Discharge Air Temperature Sensing Kit — Standard (Multispeed) X

Economizer: Low Leak — Downflow (6 to 25 Tons)(a) X

Economizer: Low Leak — Horizontal (6 to 25 Tons)(d) (a) X

Economizer: Standard — Convertible (6 to 12.5 Tons)(a) X

Economizer: Standard — Downflow (15 to 25 Tons)(a) X

Economizer: Standard — Horizontal (15 to 25 Tons)(a) X

Electric Heater(b) X

Expansion Modules(e) X

Fault Detection and Diagnostics (FDD)(f) X

Filter Removal Tool X

Foil-Faced and Edge Protected Insulation X

Frostat™ X

High Pressure Control X

High Static/Oversized Motor X

High Temperature Sensor X

IAQ Dual Sloped Composite Drain Pan X

Liquid Line Refrigerant Drier X

Low Ambient Cooling to 0°F X

Low Ambient Cooling to 40°F X

Low Pressure Control X

Manual Outside Air Damper X

6 RT-PRC096C-EN

Table 1. Precedent™ features – standard and optional (continued)

Standard Features

Options

Factory Installed Factory or Field

Installed Field

Installed Microchannel Coils X

Motorized Outside Air Damper X

Multispeed Direct Drive Motors X

Multiple Zone VAV (Variable Air Volume) X

Operating Charge of R-410A X

Phase Balance/Loss/Reversal Protection X

Phase Monitor X

Powered Exhaust X

Powered or Unpowered Convenience Outlet X

Quick Adapt Curbs X

Reference or Comparative Enthalpy X

Roof Curb X

Single Point Power X

Single Side Service X

Smoke Detector - Return(a) X

Smoke Detector - Supply(b) X

Stainless Steel Drain Pan X

Standardized Components X

Symbio Controls X

Thermal Expansion Valve X

Through-the-Base Condensate(g) X

Through-the-Base Electrical Access X

Through-the-Base Electrical with Circuit Breaker X

Through-the-Base Electrical with Disconnect Switch X

Variable Air Flow (SZVAV)/Variable Air Flow (MZVAV) X

Ventilation Override(h) X

(a) Includes Symbio Fresh Air Options Module.

(b) Includes Symbio Indoor Options Module.

(c) Factory ships in downfllow. For TSJ180-300 units where horizontal airflow is required, FIAHZDC001* (Horizontal Conversion Panel) is required. No conversion kit required on

TSJ072-150 units.

(d) Provided by third party.

(e) Requires Tracer TU and utilizes TGP2 software.

(f) Fault Detection and Diagnostics (FDD) requires Advanced Controller (either Digit 21=1 for BACnet or 21=3 for Air-Fi).

(g) 6-12.5 tons only.

(h) Requires FIASCCM001 accessory.

Control Options Table 2. Precedent™ control options — standard and optional

Standard Features

Options

Factory Installed

Factory or Field Installed

Field Installed

Dual Thermistor Remote Zone Sensor X

Symbio Service and Installation App X

Symbio 700 Advanced Module(a) X

Humidity Sensor/Humidistat X

Thermostat X

RT-PRC096C-EN 7

Table 2. Precedent™ control options — standard and optional (continued)

Standard Features

Options

Factory Installed

Factory or Field Installed

Field Installed

Wireless Zone Sensor X

Zone Sensor X

LonTalk® Communication Interface (LCI)(b) X

Trane® Air-Fi® Wireless Communication Interface (WCI)(b) X

Note: For more information, reference the Controls chapter.

(a) Symbio 700 Advanced Module includes BACnet MS/TP or IP communication protocols.

(b) Requires Symbio 700 Advanced Module (MOD03103).

Accessories FIA KIT #S DESCRIPTION Used With Cabinets Used With Models

FIAEHTB309*(a) 9kW, 208-230V Electric Heater B TSJ072A3-102A3

FIAEHTB318*(a) 18kW, 208-230V Electric Heater B TSJ072A3-120A3

FIAEHTB327*(a) 27kW, 208-230V Electric Heater B TSJ072A3-120A3

FIAEHTB336*(a) 36kW, 208-230V Electric Heater B TSJ072A3-120A3

FIAEHTB354*(a) 54kW, 208-230V Electric Heater B TSJ120A3

FIAEHTB409*(a) 9kW, 460V Electric Heater B TSJ072A4-102A4

FIAEHTB418*(a) 18kW, 460V Electric Heater B TSJ072A4-120A4

FIAEHTB427*(a) 27kW, 460V Electric Heater B TSJ072A4-120A4

FIAEHTB436*(a) 36kW, 460V Electric Heater B TSJ072A4-120A4

FIAEHTB454*(a) 54kW, 460V Electric Heater B TSJ120A4

FIAEHTBW09*(a) 9kW, 575V Electric Heater B TSJ072AW-102AW

FIAEHTBW18*(a) 18kW, 575V Electric Heater B TSJ072AW-120AW

FIAEHTBW27*(a) 27kW, 575V Electric Heater B TSJ072AW-120AW

FIAEHTBW36*(a) 36kW, 575V Electric Heater B TSJ072AW-120AW

FIAEHTBW54*(a) 54kW, 575V Electric Heater B TSJ120AW

FIAEHTC318*(a) 18kW, 208-230V Electric Heater C TSJ150A3

FIAEHTC327*(a) 27kW, 208-230V Electric Heater C TSJ150A3

FIAEHTC336*(a) 36kW, 208-230V Electric Heater C TSJ150A3

FIAEHTC354*(a) 54kW, 208-230V Electric Heater C TSJ150A3

FIAEHTC418*(a) 18kW, 460V Electric Heater C TSJ150A4

FIAEHTC427*(a) 27kW, 460V Electric Heater C TSJ150A4

FIAEHTC436*(a) 36kW, 460V Electric Heater C TSJ150A4

FIAEHTC454*(a) 54kW, 460V Electric Heater C TSJ150A4

FIAEHTCW18*(a) 18kW, 575V Electric Heater C TSJ150AW

FIAEHTCW27*(a) 27kW, 575V Electric Heater C TSJ150AW

FIAEHTCW36*(a) 36kW, 575V Electric Heater C TSJ150AW

FIAEHTCW54*(a) 54kW, 575V Electric Heater C TSJ150AW

FIAEHTD318*(a) 18kW, 208-230V Electric Heater D TSJ180A3

FIAEHTD336*(a) 36kW, 208-230V Electric Heater D TSJ180A3-300A3

FIAEHTD354*(a) 54kW, 208-230V Electric Heater D TSJ180A3-300A3

FIAEHTD372*(a) 72kW, 208-230V Electric Heater D TSJ210A3-300A3

FIAEHTD418*(a) 18kW, 460V Electric Heater D TSJ180A4

FIAEHTD436*(a) 36kW, 460V Electric Heater D TSJ180A4-300A4

FIAEHTD454*(a) 54kW, 460V Electric Heater D TSJ180A4-300A4

8 RT-PRC096C-EN

FIA KIT #S DESCRIPTION Used With Cabinets Used With Models

FIAEHTD472*(a) 72kW, 460V Electric Heater D TSJ210A4-300A4

FIAEHTDW18*(a) 18kW, 575V Electric Heater D TSJ180AW

FIAEHTDW36*(a) 36kW, 575V Electric Heater D TSJ180AW-300AW

FIAEHTDW54*(a) 54kW, 575V Electric Heater D TSJ180AW-300AW

FIAEHTDW72*(a) 72kW, 575V Electric Heater D TSJ210AW-300AW

FIABARM002* Barometric Relief B/C TSJ072A-150A

FIABARM003* Barometric Relief D TSJ180-300A

FIAC02K001* CO2 (DCV) Wall Mounted Sensor ALL TSJ072A-300A

FIAC02K002* CO2 (DCV) Duct Mounted Sensor ALL TSJ072A-300A

FIACURB402* 14-inch Full Perimeter Knockdown Curb B TSJ072A-120A

FIACURB403* 14-inch Full Perimeter Knockdown Curb C TSJ150A

FIACURB404* 14-inch Full Perimeter Knockdown Curb D TSJ180A-300A

FIACLFS001*(b) Clogged Filter Switch B/C TSJ072A-150A

FIACLFS002*(b) Clogged Filter Switch (MERV13) B/C TSJ072A-150A

FIACLFS003*(b) Clogged Filter Switch D TSJ180A-300A

FIACLFS004*(b) Clogged Filter Switch (MERV13) D TSJ180A-300A

FIADAST003* Discharge Air Sensing Tube Kit T/W Models B TSJ072A-120A

FIADAST005* Discharge Air Sensing Tube Kit T/W Models C TSJ150A

FIADAST008* Discharge Air Sensing Tube Kit T/W Models D TSJ180A-300A

FIADFDB001*(b) Differential Dry Bulb Economizer Control ALL TSJ072A-300A

FIADMPR002* Manual Damper B/C TSJ072A-150A

FIADMPR003* Manual Damper D TSJ180A-300A

FIADMPR102* Motorized Damper B/C TSJ072A-150A

FIADMPR103* Motorized Damper D TSJ180A-300A

FIAECON002*(b) Dry Bulb Economizer B/C TSJ072A-150A

FIAECON102*(b) Dry Bulb Downflow Low Leak B/C TSJ072A-150A

FIAECON003*(b) Dry Bulb Downflow Economizer D TSJ180A-300A

FIAECON303*(b) Dry Bulb Horizonal Economizer D TSJ180A-300A

FIAECON103*(b) Dry Bulb Downflow Low Leak D TSJ180A-300A

FIAECON203*(b) Dry Bulb Horizontal Low Leak D TSJ180A-300A

FIAENTH001* Reference Enthalpy Economizer Control ALL TSJ072A-300A

FIAENTH002* Comparative Enthalpy Economizer Control ALL TSJ072A-300A

FIAHTST001* High Temperature (Fire) Duct Mounted Stat ALL TSJ072A-300A

FIAHZDC001* Horizontal Conversion Panel D TSJ180A-300A

FIALOAM001* Low Ambient ALL TSJ072A-300A

FIALTCI001* LonTalk Communication Interface ALL TSJ072A-300A

FIAOPTN001* Indoor Options Module ALL TSJ072A-300A

FIAOPTN002* Fresh Air Options Module ALL TSJ072A-300A

FIAOVFL001*(a) Condensate Overflow Switch ALL TSJ072A-300A

FIAPWRX302* Power Exhaust 230V B/C TSJ072A3-150A3

FIAPWRX402* Power Exhaust 460V B/C TSJ072A4-150A4

FIAPWRXW02* Power Exhaust 575V B/C TSJ072AW-150AW

FIAPWRX303* Power Exhaust 230V D TSJ180A3-300A3

FIAPWRX403* Power Exhaust 460V D TSJ180A4-300A4

FIAPWRXW03* Power Exhaust 575V D TSJ180AW-300AW

FIAQACB026* Adapter Curb, Existing BAYCURB026 to New C Cabinet (FIACURB403A) C TSJ150A

FIAQACB027* Adapter Curb, Existing BAYCURB027 to New C Cabinet (BAYCURB403A) C TSJ150A

FIAQACB044* Adapter Curb, Existing BAYCURB044 to New B Cabinet (BAYCURB402A) B TSJ072A-120A

RT-PRC096C-EN 9

FIA KIT #S DESCRIPTION Used With Cabinets Used With Models

FIASCCM001*(c) , (d) Symbio Customer Connection Module ALL TSJ072A-300A

FIAXMOD030*(d), (e) Symbio 700 XM30 Expansion Module ALL TSJ072A-300A

FIAXMOD032*(d), (e) Symbio 700 XM32 Expansion Module ALL TSJ072A-300A

(a) Requires Symbio Indoor Options Module.

(b) Requires Symbio Fresh Air Options Module.

(c) Provides Ventilation Override, External Auto/Stop, Alarm Indicator, Remote Min Position.

(d) Requires Symbio Advanced Controller (digit 21=1 or 3).

(e) Requires Tracer TU and Utilizes TGP2 Software (programming knowledge required).

Key Benefits Direct Drive Plenum Fan

Supply Air Smoke Detector

Options Module

Return Air Smoke Detector

Electric HeatDrain Pan

Foil Faced Edge Captured Insulation

Compressors

Direct Drive Condenser Fan

XM30 and 32 Control Modules

Layered Control Box

Condenser Coil

Evaporator Coil

Airflow Distribution Airflow is outstanding. Precedent™ can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.

Cabinet Integrity For added water integrity, Precedent™ has a raised 1 inch lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.

10 RT-PRC096C-EN

Coil Guards Coil guards protect condenser coil during shipping as well as hail, vandals, wind, etc. Toolless design lends itself to ease of maintenance in cleaning coils.

CO2 Sensor — Demand Control Ventilation (DCV) Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (carbon dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed accessory and wires directly to the Symbio 700 controller.

CompleteCoat™ Condenser Coil This optional coated coil provides excellent corrosion resistance as well as uniformity of coverage and coating thickness.

Controls — Symbio™ Enhanced BAS Integration and Connectivity

• Open standard communications

– BACnet®over Zigbee (Air-Fi Wireless)

– BACnet MS/TP

– BACnet IP

– Modbus™ RTU

– Modbus TCP/IP

– LonTalk®

• Securely access, troubleshoot, and monitor equipment from anywhere via Trane Connect™

Serviceability

• Wireless mobile app interface (iPhone and Android) to simplify startup/service

• On-board user interface

• Data Trending

• Real-time, clear language diagnostics

• Historical alarm logs

• Backup and Restore functionality to reduce commissioning and service time

Flexibility

• Future-ready upgradable software, supporting changing codes and new sequences of operation

• Standard, consistent pre-engineered applications that meet industry standards

RT-PRC096C-EN 11

• Built-in Schedules (requires Tracer® TU)

• Expandable inputs and outputs (requires Tracer TU)

• Ability to add custom programmed sequences (requires Tracer TU)

Accessibility Control box consists of a multilevel design with Symbio Controls located on hinged panels which provide protection from high voltage components for ease of servicing.

Convenience Outlet This option is GFCI, 120V/15A, 2 plug, convenience outlet powered or GFCI, 120V/20A, 2 plug convenience outlet unpowered. This option can be ordered when through the base electrical with either the disconnect switch or circuit breaker option is ordered.

Convertible Units Units ship in a downflow configuration and can be easily converted to horizontal by simply removing two panels. Optional field accessory kits required for 15 to 25 ton units.

12 RT-PRC096C-EN

Direct Drive Plenum Fans All 6 to 25 tons units are equipped with a direct drive plenum fan design with the following features.

• Backward-curved fan wheel

• External rotor direct drive variable speed indoor motor

• Variable speed adjustment available in Symbio controller

• Designed to slide out for ease of maintenance

Drain Pan Every Precedent™ unit has an easy-to-clean, composite removable dual-sloped drain pan (IAQ). On units with B or C (6 to 12.5T) size cabinets, the drain pan is reversible, allowing installation of the draining trap on either side of the unit.

Fault Detection and Diagnostics (FDD) This offering meets the mandatory requirement of CATitle 24 of fully configurable diagnostics allowing fault history and reading fault codes at the unit via Symbio™ 700 board or app. This feature provides detection of the following faults: Air temperature sensor failure/fault and notification of acceptable economizer mode. The FDD system shall be certified by the Energy Commission as meeting the requirements.

Flexibility Precedent™ offers ultimate flexibility. Units are built to order in our standard ship cycle time.

RT-PRC096C-EN 13

High Efficiency Filtration Precedent™ units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2 inches throwaway filters.

High Static Motor Available on 10 and25 ton models, this high static motor option extends beyond the capability of the standard motor.

Hinged Access Doors These doors permit easy access to the filter, fan and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.

Humidity Control (HGRH) All 12.5 to 25 tons Precedent units can be ordered with a factory installed modulating humidity control system designed to provide year around comfort by improving indoor air quality while controlling humidity levels.

Humidity Sensor/Humidistat The humidity sensor/humidistat, when used in conjunction with our dehumidification (hot gas reheat) units will provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted. The humidity deadband can be set between 40% and 60% relative humidity.

Low Ambient Cooling All Precedent™ units have cooling capabilities down to 40°F. Factory installed option or field installed accessory extends operation down to 0°F.

Low Leak Economizer This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CATitle 24 standards (4 cfm/ ft2@1" wg exterior air/return air). This option allows 100% outdoor air supply from 0 to 100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. This option can be paired with or without fault detection and diagnostics (FDD) to meet current mandatory CATitle 24 requirements.

The economizers come with four control options, dry bulb, reference enthalpy, comparative enthalpy, or differential dry bulb.

14 RT-PRC096C-EN

Note: Downflow low leak economizer is available as a factory installed option. Horizontal low leak economizer option is only available as a field installed option.

Microchannel Coils Microchannel coils are all-aluminum coils with fully-brazed construction. This design reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer.

Microchannel all-aluminum construction provides several additional benefits:

• Light weight (simplifies coil handling)

• Easy to recycle

• Minimize galvanic corrosion

Multi-Speed Indoor Fan System This system incorporates a multi-speed fan control to change the speed of the fan to 66% of full airflow based off of compressor stages.

Multiple-Zone VAV Control A multiple-zone VAV (MZVAV) system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a VAV terminal unit that varies the quantity of air delivered to maintain the desired temperature in that zone. The rooftop unit controller varies the speed of the indoor fan to maintain the static pressure in the supply ductwork at a setpoint, ensuring that all zones receive the necessary quantity of air. In addition, cooling capacity is cycled to maintain the supply air temperature at the desired setpoint.

For decades, Trane has been an industry leader in rooftop VAV systems. Now, multiple-zone VAV control is available in the light commercial rooftop platform (6 to 25 tons).

RT-PRC096C-EN 15

Other Benefits

• Cabinet design ensures water integrity

• Ease of Service, Installation and Maintenance

• Mixed model build enables “fastest in the industry” ship cycle times

• Outstanding Airflow Distribution

• Symbio Controls

Quick Adapt Curbs Enables easy upgrade of existing Voyager™ 6 to 25 tons units to Precedent™ units on replacement jobs.

Rigorous Testing All of the Precedent™ designs were rigorously rain tested at the factory to ensure water integrity.

Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging design. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.

Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.

We perform a 100% coil leak test at the factory. The assembled unit is leak tested to 465 psig.

All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.

Every unit receives a 100% unit run test before leaving the production line to make sure it meets rigorous requirements.

Single Zone VAV (SZVAV) SZVAV is fully integrated into the control system. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic boards and sensors are factory installed and tested to ensure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for field installed sensors, boards, etc. SZVAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider -Trane.

Building system modeling in energy simulation software such as TRACE is recommended to evaluate performance improvements for your application.

Supply/Return Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or the return air stream, the air velocity entering the smoke detector unit must be between 500 to 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance table. Supply and/or return smoke detectors may not be used with the plenum smoke detector.

16 RT-PRC096C-EN

Through-the-Base Condensate 6 to 12.5 tons unit includes provisions for through-the-base condensate drain connections. This allows the drain to be connected through the roof curb instead of a roof penetration.

Through-the-Base Electrical Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through-the-base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

Ventilation Override Ventilation override allows the unit to be set to transition to up to three different pre-programmed sequences for smoke purge, pressurization, and exhaust. The transition occurs when a binary input on the Customer Connection Module is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The Customer Connection module that allows ventilation override is available as a field installed accessory (FIASCCM001). For more information on functionality, refer to Symbio™ 700 Controller with Precedent™ Packaged Rooftop Air-Conditioners Application Guide (ACC-APG002*-EN).

RT-PRC096C-EN 17

Model Number Description

Digit 1 — Unit Function

T = DX Cooling

Digit 2 — Cooling Efficiency

S = Standard Efficiency

Digit 3 — Refrigerant

J = R-410A

Digit 4,5,6 — Nominal Gross Cooling Capacity (MBh) 072 = 6 Ton 090 = 7.5 Ton 102 = 8.5 Ton 120 = 10 Ton 150 = 12.5 Ton 180 = 15 Ton 210 = 17.5 Ton 240 = 20 Ton 300 = 25 Ton

Digit 7 — Design Sequence

Digit 8 — Voltage Selection

3 = 208–230/60/3 4 = 460/60/3 W = 575/60/3

Digit 9 — Unit Controls

S = Symbio™ 700

Digit 10 — Heat Type

0 = Base Model (None or Electric)

Digit 11 — Heating Capacity1

0 = No Heat C = 9 kW Electric Heat G = 18 kW Electric Heat K = 27 kW Electric Heat N = 36 kW Electric Heat P = 54 kW Electric Heat R = 72 kW Electric Heat

Digit 12, 13 — Service Sequence

** = Factory Assigned

Digit 14 — Fresh Air Selection

0 = No Fresh Air A = Manual Outside Air Damper 0–50% B = Motorized Outside Air Damper 0–50% C = Economizer, Dry Bulb 0–100% without Barometric Relief2 D = Economizer, Dry Bulb 0–100% with Barometric Relief2 E = Economizer, Reference Enthalpy 0–100% without Barometric Relief2 F = Economizer, Reference Enthalpy 0–100% with Barometric Relief2 G = Economizer, Comparative Enthalpy 0–100% without Barometric Relief2 H = Economizer, Comparative Enthalpy 0–100% with Barometric Relief2 K = Downflow Low Leak Economizer, Dry Bulb with Barometric Relief2 M = Downflow Low Leak Economizer, Reference Enthalpy with Barometric Relief2 P = Downflow Low Leak Economizer, Comparative Enthalpy with Barometric Relief2 R= Downflow Low Leak Economizer, Differential Dry Bulb with Barometric Relief2

Digit 15 — Supply Fan/Motor

0 = Multi-Speed Motor 1 = Optional Oversized/High Static Motor 2 = Single Zone Variable Air Volume with Standard Motor 3 = Single Zone Variable Air Volume with Oversized/High Static Motor 4 = Multiple Zone Variable Air Volume with Standard Motor 5 = Multiple Zone Variable Air Volume with Oversized/High Static Motor

Digit 16 — Hinged Access/Filters

0 = Standard Panels/Standard Filters A = Hinged Access Panels/Standard Filters B = Standard Panels/2 inch MERV 8 Filters C = Hinged Access Panels/2 inch MERV 8 Filters D = Standard Panels/2 inch MERV 13 Filters E = Hinged Access Panels/2 inch MERV 13 Filters

Digit 17 — Coil Protection

0 = Standard Coil 1 = Condenser with CompleteCoat™

Digit 18 — Through-the-Base Provisions

0 = No Through-the-Base Provisions A = Through-the-Base Electric

Digit 19 — Disconnect/Circuit Breaker (three-phase only) 0 = No Disconnect/No Circuit Breaker 1 = Unit Mounted/Non-Fused Disconnect 2 = Unit Mounted Circuit Breaker

Digit 20— Convenience Outlet

0 = No Convenience Outlet A = Unpowered 20A Convenience Outlet B = Powered 15A Convenience Outlet (three-phase only)

Digit 21— Communications Options

0 = No Communications Interface 1 = Advanced Controller with BACnet® Communications Interface 2 = Advanced Controller with LonTalk® Communications Interface 3 = Advanced Controller with Air-Fi® Communications Interface

Digit 22— Refrigeration System Option

0 = Standard Refrigeration System A = Dehumidification Option1, 3

Digit 23— Controls Expansion Module

0 = None 1 = XM-30 Expansion Module 2 = XM-32 Expansion Module 3 = XM-30 and XM-32 Expansion Module 4 = XM–30 Expansion Module (Qty 2) 5 = XM–32 Expansion Module (Qty 2)

Digit 24— Smoke Detector

0 = No Smoke Detector A = Return Air Smoke Detector2 B = Supply Air Smoke Detector1 C = Supply and Return Air Smoke Detectors1, 2

18 RT-PRC096C-EN

Digit 25— System Monitoring Controls

0 = No Monitoring Control 1 = Clogged Filter Switch2 2 = Condensate Overflow Switch1 3 = Discharge Air Sensing Tube 4 = Clogged Filter Switch and Condensate Overflow Switch1, 2 5 = Clogged Filter Switch and Discharge Air Sensing Tube2 6 = Condensate Overflow Switch and Discharge Air Sensing Tube1 7 = Clogged Filter Switch, Condensate Overflow Switch and Discharge Air Sensing Tube1, 2

Digit 26— Not Used

Digit 27— Hardware Enhancements

0 = No Enhancements 1 = Stainless Steel Drain Pan

Digit 28— Short Circuit Current Rating

0 = Standard (5k) SCCR Marking A = Tier 2 (=65K) SCCR Marking

Digit 29— Low Ambient4

0 = None A = Low Ambient Cooling to 0°F

Model Number Notes Notes:

1. Includes Symbio™ Indoor Module.

2. Includes Symbio™ Fresh Air Module.

3. Includes Symbio™Customer Connection Module.

4. Standard Low Ambient Cooling Limit is 40°F.

Model Number Description

RT-PRC096C-EN 19

General Data Table 3. General data— 6 to 12.5 tons— standard efficiency

6 Tons 7.5 Tons 8.5 Tons 10 Tons 12.5 Tons

TSJ072 TSJ090 TSJ102 TSJ120 TSJ150

Cooling Performance

Gross Cooling Capacity 73000 91000 104000 122000 155000

EER 11.2 11.2 11.2 11.2 11.0

Nominal cfm/AHRI Rated cfm 1860 2475 2975 3700 5000

AHRI Net Cooling Capacity 72000 90000 102000 120000 150000

IEER (2-Speed) 14.8 14.8 14.8 14.8 14.2

IEER (SZVAV/MZVAV) 15.3/15.3 15.3/15.3 15.3/15.3 15.3/15.3 14.7/14.7

System Power (kW) 6.55 8.18 9.27 10.91 13.70

Compressor

Number/Type 2/Manifold Scroll 2/Manifold Scroll 2/Manifold Scroll 2/Manifold Scroll 2/Manifold Scroll

Percent Capacity (Stage 1–Stage 3) 32/68/100 33/67/100 32/68/100 28/72/100 32/68/100

Sound

Outdoor Sound Rating (dBA) 86 86 86 86 89

Outdoor Coil

Type Microchannel Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face Full Face

Tube Size (in.) 0.7 0.7 1.0 1.0 1.0

Face Area (sq. ft.) 21.64 21.64 21.64 21.64 28.32

Rows/FPI (Fins per inch) 1/23 1/23 1/21 1/21 1/23

Indoor Coil

Type Microchannel Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face Full Face

Tube Size (in.) 1.0 1.0 1.0 1.0 1.0

Face Area (sq. ft.) 11.84 11.84 11.84 11.84 14.27

Rows/FPI (Fins per inch) 2/18 2/18 2/18 2/18 2/18

Refrigerant Control TXV TXV TXV TXV TXV

Drain Connection No./Size (in.) NPT 1/0.75 1/0.75 1/0.75 1/0.75 1/0.75

Reheat Coil

Type Microchannel Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face Full Face

Tube Size (in.) 0.6 0.6 0.6 0.6 0.6

Face Area (sq. ft.) 9.04 9.04 9.04 9.04 11.82

Rows/FPI (Fins per inch) 1/23 1/23 1/23 1/23 1/23

Outdoor Fan

Type Propeller Propeller Propeller Propeller Propeller

No. Used/Diameter (in.) 1/26 1/26 1/26 1/26 1/30

Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 Direct/1

CFM 5900 5900 5900 6700 8200

Motor HP 0.70 0.70 0.70 0.75 1.00

Motor RPM 1100 1100 1100 1100 1100

Indoor Fan

Type BC Plenum BC Plenum BC Plenum BC Plenum BC Plenum

20 RT-PRC096C-EN

Table 3. General data— 6 to 12.5 tons— standard efficiency (continued)

6 Tons 7.5 Tons 8.5 Tons 10 Tons 12.5 Tons

TSJ072 TSJ090 TSJ102 TSJ120 TSJ150

No. Used/Diameter (in.)/Width (in.) 1/23x6 1/23x6 1/23x6 1/23x6 1/23x6

Drive Type/No. Speeds/RPM Direct/Variable Direct/Variable Direct/Variable Direct/Variable Direct/Variable

Motor HP (Standard/Oversized) 3.0/ – 3.0 / – 3.0 / – 3.0 / 4.6 4.6 / –

Max Motor RPM 1850 1850 1850 1850 / 1940 1940

Filters(a)

Type Furnished Throwaway Throwaway Throwaway Throwaway Throwaway

Number Size Recommended

(2) 18 x 24 x 2

(3) 24 x 16 x 2

(2) 18 x 24 x 2

(3) 24 x 16 x 2

(2) 18 x 24 x 2

(3) 24 x 16 x 2

(2) 18 x 24 x 2

(3) 24 x 16 x 2

(3) 18 x 18 x 2

(3) 24 x 18 x 2

Refrigerant Charge lbs of R-410A 9.0 9.0 9.5 10.1 11.4 lbs of R-410A, Hot Gas Reheat 10.3 9.6 10.1 10.7 11.6

Cabinet

Cabinet Size B0 B0 B0 B0 C0

(a) Outdoor sound rating shown is tested in accordance with AHRI 370-2015. For additional information reference the outdoor sound power level data in the performance section.

Table 4. General data— 15 to 25 tons— standard efficiency

15 Tons 17.5 Tons 20 Tons 25 Tons

TSJ180 TSJ210 TSJ240 TSJ300

Cooling Performance

Gross Cooling Capacity 185000 214000 246000 281000

EER 11.0 11.0 10.0 10.0

Nominal cfm/AHRI Rated cfm 5250 6650 8000 10000

AHRI Net Cooling Capacity 182000 210000 240000 271000

IEER (2-Speed) 14.2 14.2 13.2 13.2

IEER (SZVAV/MZVAV) 14.7/14.7 14.7/14.7 13.7/13.7 13.7/13.7

System Power (kW) 16.55 19.09 24.00 27.10

Compressor

Number/Type 2/Manifold Scroll 2/Manifold Scroll 2/Manifold Scroll 2/Manifold Scroll

Percent Capacity (Stage 1 - Stage 4) 33/67/100/NA 33/67/100/NA 24/36/64/100 25/37/63/100

Sound

Outdoor Sound Rating (dBA) 87 91 91 93

Outdoor Coil

Type Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face

Tube Size (in.) 0.71 0.71 1.0 1.0

Face Area (sq. ft.) 33.90 33.90 33.89 33.89

Rows/FPI (Fins per inch) 1/23 1/23 1/21 1/21

Indoor Coil

Type Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face

Tube Size (in.) 1.0 1.0 1.0 1.0

Face Area (sq. ft.) 23.93 23.93 23.93 23.93

Rows/FPI (Fins per inch) 2/18 2/18 2/18 2/18

RT-PRC096C-EN 21

Table 4. General data— 15 to 25 tons— standard efficiency (continued)

15 Tons 17.5 Tons 20 Tons 25 Tons

TSJ180 TSJ210 TSJ240 TSJ300

Refrigerant Control TXV TXV TXV TXV

STD. Drain Connection No./Size (in.) 1/1.00 PVC Socket 1/1.00 PVC Socket 1/1.00 PVC Socket 1/1.00 PVC Socket

Stainless Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT

Reheat Coil

Type Microchannel Microchannel Microchannel Microchannel

Configuration Full Face Full Face Full Face Full Face

Tube Size (in.) 0.6 0.6 0.6 0.6

Face Area (sq. ft.) 21.83 21.83 21.83 21.83

Rows/FPI (Fins per inch) 1/23 1/23 1/23 1/23

Outdoor Fan

Type Propeller Propeller Propeller Propeller

No. Used/Diameter (in.) 2/26x3 2/26x4 2/26x4 2/28x4

Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1

CFM 11520 14660 14220 16600

Motor HP 2/0.50 2/1.0 2/1.0 2/1.0

Motor RPM 1125 1125 1125 1125

Indoor Fan

Type BC Plenum BC Plenum BC Plenum BC Plenum

No. Used/Diameter (in.)/Width (in.) 2/23x6 2/23x6 2/23x6 2/23x6

Drive Type/No. Speeds/RPM Direct/Variable Direct/Variable Direct/Variable Direct/Variable

Motor HP (Standard/Oversized) 3.0 / – 3.0 / – 3.0 / – 3.0 / 4.6

Max Motor RPM 1850 1850 1850 1850 / 1940

Filters(a)

Type Furnished Throwaway Throwaway Throwaway Throwaway

Number Size Recommended (8) 20 x 24 x 2 (8) 20 x 24 x 2 (8) 20 x 24 x 2 (8) 20 x 24 x 2

Refrigerant Charge lbs of R-410A 14.5 14.2 16.6 16.9 lbs of R-410A, Hot Gas Reheat 15.8 15.0 17.2 17.7

Cabinet

Cabinet Size D0 D0 D0 D0

(a) Outdoor sound rating shown is tested in accordance with AHRI 370-2015. For additional information reference the outdoor sound power level data in the performance section.

22 RT-PRC096C-EN

Gross Cooling Capacities Table 5. Gross cooling capacities — 6 tons

CFM

Ent DB (°F)

Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) 61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC Ambient Temperature 85°F Ambient Temperature 95°F Ambient Temperature 105°F

75 67.7 54.1 77.4 43.1 85.4 30.6 63.6 51.8 72.8 40.9 79.9 28.7 59.3 49.4 67.9 38.5 73.9 26.4 80 67.6 63.1 77.3 52.8 85.7 40.6 63.5 60.8 72.8 50.6 80.4 38.2 59.2 58.3 67.9 48.2 74.6 35.7 85 69.1 69.1 77.1 62.3 85.9 50.7 65.9 65.9 72.7 60.4 80.8 48.3 62.4 62.4 67.9 55.3 75.0 45.8 90 76.9 71.5 76.9 71.5 85.9 60.5 70.2 70.2 72.5 69.2 80.8 58.2 66.5 66.5 67.7 66.7 75.1 55.7

75 70.1 58.8 79.8 46.1 87.1 29.2 65.8 56.2 75.0 43.6 81.3 28.9 61.1 52.5 69.8 41.1 74.8 27.1 80 69.7 68.8 79.7 57.2 87.5 42.8 65.5 65.5 75.0 54.9 81.9 40.5 61.5 61.5 69.8 52.4 75.8 38.0 85 73.2 73.2 79.5 67.4 87.8 54.4 69.7 69.7 74.8 63.4 82.3 52.0 65.9 65.9 69.6 62.9 76.1 49.4 90 77.7 77.7 79.1 78.2 87.9 65.8 74.1 74.1 74.5 74.5 82.4 63.4 70.1 70.1 70.2 70.2 76.3 60.8

75 71.5 61.3 81.4 48.1 88.1 31.6 67.1 57.0 76.4 45.7 82.4 29.2 62.1 56.8 71.1 43.2 75.9 28.3 80 71.1 71.1 81.3 60.6 88.6 44.7 67.6 67.6 76.3 58.2 82.9 42.2 63.7 63.7 71.0 55.7 76.7 39.8 85 75.9 75.9 80.8 72.1 88.9 57.3 72.3 72.3 75.9 69.6 83.1 54.8 68.2 68.2 70.5 66.9 76.7 52.2 90 80.6 80.6 80.7 80.7 89.0 69.9 76.7 76.7 76.8 76.8 83.3 67.5 72.3 72.3 72.4 72.4 77.0 63.0

75 72.5 65.1 82.7 50.2 89.3 32.2 67.9 62.6 77.6 47.8 83.3 30.1 62.9 59.9 72.1 45.2 76.8 28.2 80 73.4 73.4 82.5 63.8 89.6 46.3 69.7 69.7 77.4 61.4 83.9 43.9 65.6 65.6 71.9 58.8 77.4 41.2 85 78.3 78.3 81.8 76.0 89.7 60.1 74.4 74.4 76.7 73.5 83.8 57.6 70.2 70.2 71.2 71.2 77.3 55.0 90 83.0 83.0 83.0 83.0 89.9 73.1 78.8 78.8 78.9 78.9 84.0 67.8 74.0 74.0 74.1 74.1 77.1 67.8

75 73.3 68.2 83.8 52.2 90.3 32.8 68.6 65.6 78.5 49.8 84.2 30.4 63.6 62.9 72.8 47.1 77.5 28.8 80 75.3 75.3 83.5 67.0 90.5 47.9 71.5 71.5 78.3 64.0 84.4 45.4 67.3 67.3 72.7 59.4 78.1 42.8 85 80.4 80.4 82.5 79.9 90.4 62.9 76.3 76.3 77.3 77.3 84.3 60.4 71.8 71.8 71.9 71.9 78.0 57.8 90 84.9 84.9 85.0 85.0 90.3 76.9 80.5 80.5 80.5 80.5 84.1 74.2 75.2 75.2 75.3 75.3 77.4 71.3

Ambient Temperature 115°F Ambient Temperature 125°F

75 54.6 46.8 62.6 35.9 67.5 23.2 49.5 42.4 56.8 33.1 60.5 21.3 80 54.6 54.6 62.6 45.6 68.1 33.0 50.4 50.4 56.8 42.9 61.1 30.2 85 58.5 58.5 62.6 53.5 68.6 43.0 54.3 54.3 56.8 52.1 61.3 40.0 90 62.5 62.5 62.5 62.5 68.7 52.9 57.8 57.8 57.8 57.8 61.4 49.9

75 56.1 50.9 64.3 38.5 68.8 23.7 50.7 48.0 58.1 35.7 61.7 20.9 80 57.5 57.5 64.3 49.8 69.2 35.3 53.1 53.1 58.1 47.0 62.3 32.3 85 61.7 61.7 64.0 60.2 69.3 46.5 57.0 57.0 57.8 57.2 62.2 43.7 90 65.5 65.5 65.6 65.6 69.5 57.1 60.0 60.0 60.0 60.0 62.2 54.4

75 57.0 54.1 65.3 40.5 69.5 24.3 51.5 51.1 58.9 37.6 62.2 21.8 80 59.5 59.5 65.2 53.1 70.1 36.8 54.9 54.9 58.9 48.6 62.8 33.9 85 63.7 63.7 64.7 64.1 70.1 49.4 58.6 58.6 58.6 58.6 62.8 46.5 90 67.2 67.2 67.3 67.3 69.9 61.2 60.8 60.8 60.9 60.9 62.5 58.1

75 57.7 57.1 66.1 42.5 70.0 26.4 52.1 52.1 59.5 39.5 62.9 20.2 80 61.3 61.3 66.0 54.4 70.7 38.5 56.3 56.3 59.2 52.5 63.3 35.5 85 65.4 65.4 65.4 65.4 70.7 52.2 59.8 59.8 59.8 59.8 63.3 48.4 90 68.3 68.3 68.4 68.4 70.3 64.8 61.9 61.9 61.9 61.9 62.8 61.7

75 58.2 58.2 66.7 44.4 70.8 25.8 53.4 53.4 60.0 41.4 63.1 23.3 80 62.7 62.7 66.3 58.3 71.3 40.1 57.5 57.5 59.5 55.2 63.7 37.1 85 66.7 66.7 66.7 66.7 71.2 55.1 60.6 60.6 60.6 60.6 63.7 50.3 90 69.1 69.1 69.2 69.2 70.5 68.4 62.8 62.8 62.9 62.9 62.9 62.9

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NETcooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total gross capacity

3. SHC = Sensible heat capacity

RT-PRC096C-EN 23

Table 6. Gross cooling capacities — 7.5 tons

CFM

Ent DB (°F)

Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC Ambient Temperature 85°F Ambient Temperature 95°F Ambient Temperature 105°F

75 84.6 68.9 96.3 54.7 106.0 40.1 79.7 66.3 90.8 52.1 100.3 34.2 74.5 63.6 84.8 49.4 92.8 34.2 80 84.2 80.1 96.1 67.0 106.7 51.5 79.4 77.5 90.6 64.5 100.5 48.9 74.2 74.2 84.7 61.7 93.6 46.1 85 86.6 86.6 95.8 79.5 107.0 64.2 82.8 82.8 90.4 76.8 100.7 61.6 78.6 78.6 84.5 72.0 93.8 58.8 90 95.3 90.5 95.3 90.5 106.8 76.8 87.9 87.9 90.0 87.9 100.6 74.2 83.5 83.5 84.1 84.1 93.8 71.5

75 86.7 73.5 98.5 57.6 107.9 40.8 81.6 69.7 92.7 54.6 101.5 37.2 76.1 65.0 86.5 51.8 94.4 34.1 80 86.0 86.0 98.3 71.3 108.7 53.8 81.0 81.0 92.6 68.6 102.1 51.2 76.6 76.6 86.4 65.8 95.0 48.4 85 90.3 90.3 97.9 83.1 108.8 68.0 86.3 86.3 92.1 81.6 102.3 65.3 81.8 81.8 85.9 78.6 95.2 62.4 90 95.8 95.8 97.2 97.0 108.7 82.1 91.6 91.6 91.7 91.7 102.3 79.5 86.8 86.8 86.9 86.9 95.2 76.6

75 88.3 75.0 100.4 59.9 109.4 39.7 82.8 74.2 94.4 57.2 102.7 38.0 77.1 71.2 88.0 54.4 95.2 35.1 80 87.8 87.8 100.1 75.3 110.3 56.1 83.6 83.6 94.1 72.7 103.5 53.4 79.1 79.1 87.8 69.8 96.3 50.9 85 93.5 93.5 99.3 89.3 110.4 71.6 89.2 89.2 93.4 86.5 103.6 68.9 84.5 84.5 87.0 83.5 96.3 66.0 90 99.2 99.2 99.3 99.3 110.2 87.2 94.6 94.6 94.7 94.7 103.6 84.0 89.5 89.5 89.6 89.6 96.3 77.8

75 89.3 80.8 102.0 62.5 110.6 41.8 83.9 78.0 95.8 59.7 103.8 37.9 78.0 74.9 89.2 56.8 96.0 35.8 80 90.4 90.4 101.5 79.3 111.7 58.3 86.1 86.1 95.4 76.6 104.8 55.4 81.3 81.3 88.8 72.8 97.3 52.4 85 96.3 96.3 100.4 94.1 111.6 75.1 91.8 91.8 94.2 94.2 104.7 72.4 86.8 86.8 87.7 87.7 97.1 69.5 90 102.0 102.0 102.1 102.1 111.4 89.0 97.2 97.2 97.3 97.3 104.3 88.3 91.7 91.7 91.8 91.8 96.6 85.0

75 90.3 84.5 103.2 64.9 111.4 43.3 84.6 84.6 96.9 62.1 104.6 36.0 78.6 78.6 90.1 59.2 96.7 36.0 80 92.7 92.7 102.6 83.2 112.8 60.1 88.2 88.2 96.4 78.4 105.7 57.4 83.3 83.3 89.4 76.4 98.0 54.3 85 98.8 98.8 101.1 101.1 112.6 78.6 94.0 94.0 94.9 94.9 105.5 75.9 88.7 88.7 88.8 88.8 97.8 72.9 90 104.5 104.5 104.6 104.6 111.9 95.6 99.4 99.4 99.4 99.4 104.7 92.6 93.5 93.5 93.6 93.6 96.8 89.3

Ambient Temperature 115°F Ambient Temperature 125°F

75 68.9 59.4 78.3 46.3 85.3 32.3 62.6 57.1 71.4 43.2 77.3 26.0 80 69.2 69.2 78.3 58.9 86.1 43.3 64.3 64.3 71.4 55.8 78.0 40.2 85 74.0 74.0 78.1 70.5 86.4 55.8 68.8 68.8 71.1 67.2 78.1 52.6 90 78.6 78.6 78.7 78.7 86.4 68.5 73.0 73.0 73.1 73.1 78.2 63.7

75 70.1 64.3 79.9 48.9 86.7 28.5 63.7 61.0 72.7 45.7 77.9 26.8 80 71.9 71.9 79.8 62.9 87.4 45.6 66.7 66.7 72.6 59.8 79.1 42.0 85 76.8 76.8 79.3 75.5 87.4 59.4 71.3 71.3 72.0 72.0 78.9 56.1 90 81.5 81.5 81.6 81.6 87.5 71.6 75.3 75.3 75.4 75.4 78.7 69.2

75 71.0 68.1 81.1 51.3 87.3 29.8 64.5 64.5 73.7 48.1 78.4 27.3 80 74.2 74.2 80.9 66.6 88.4 47.3 68.7 68.7 73.4 62.0 79.7 44.0 85 79.2 79.2 80.1 80.1 88.2 62.9 73.3 73.3 73.3 73.3 79.4 60.1 90 83.8 83.8 83.8 83.8 87.9 77.3 77.0 77.0 77.0 77.0 78.8 73.6

75 71.7 71.7 82.1 53.7 87.8 30.3 65.5 65.5 74.4 50.4 78.8 27.8 80 76.2 76.2 81.6 69.7 89.1 49.3 70.4 70.4 73.8 66.2 80.1 45.8 85 81.2 81.2 81.3 81.3 88.9 66.3 74.8 74.8 74.9 74.9 79.9 62.3 90 85.5 85.5 85.6 85.6 88.1 81.6 78.1 78.1 78.1 78.1 78.8 77.9

75 72.5 72.5 82.9 56.0 88.3 34.4 66.9 66.9 75.1 52.7 79.8 33.0 80 77.9 77.9 82.1 73.0 89.6 51.1 71.8 71.8 74.2 69.5 80.5 47.7 85 82.9 82.9 82.9 82.9 89.4 69.7 76.1 76.1 76.2 76.2 80.1 64.6 90 86.8 86.8 86.9 86.9 88.2 85.8 78.8 78.8 78.8 78.8 78.9 78.9

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NETcooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total gross capacity

24 RT-PRC096C-EN

Table 7. Gross cooling capacities — 8.5 tons

CFM

Ent DB (°F)

Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC Ambient Temperature 85°F Ambient Temperature 95°F Ambient Temperature 105°F

75 96.6 77.8 108.7 61.2 118.4 42.4 91.0 74.8 102.2 58.3 110.4 39.0 85.1 71.6 95.1 54.9 101.9 35.6 80 96.0 90.3 108.5 75.2 118.6 57.0 90.5 87.2 102.0 72.1 110.7 53.7 84.6 83.9 95.0 68.8 102.1 50.1 85 97.9 97.9 108.2 87.5 118.9 71.7 93.5 93.5 101.8 82.6 111.2 68.0 88.5 88.5 94.9 80.8 102.6 64.4 90 107.6 101.4 107.6 101.4 118.8 85.4 98.8 98.8 101.2 98.2 111.1 82.1 93.4 93.4 94.2 94.2 102.6 78.6

75 98.9 82.8 111.0 64.5 120.1 43.1 93.1 79.5 104.2 61.4 111.8 39.7 86.9 75.2 96.8 57.5 103.5 36.4 80 98.0 96.2 110.8 79.8 120.5 59.5 92.2 92.2 104.0 76.6 112.3 56.1 86.6 86.6 96.7 73.2 103.6 52.9 85 102.0 102.0 110.4 93.2 120.8 75.3 97.1 97.1 103.5 91.1 112.7 71.9 91.8 91.8 96.1 87.5 103.7 68.3 90 107.7 107.7 109.4 108.4 120.7 91.2 102.4 102.4 102.7 102.7 112.6 87.8 96.5 96.5 96.6 96.6 103.7 84.2

75 100.7 85.7 112.9 67.0 121.5 43.8 94.5 83.5 105.8 63.7 113.3 40.6 87.9 80.0 98.2 60.2 104.7 35.0 80 99.5 99.5 112.6 84.3 122.1 62.2 94.5 94.5 105.6 81.0 113.6 58.8 89.2 89.2 97.9 77.6 105.0 55.3 85 105.4 105.4 111.8 99.9 122.3 79.3 100.2 100.2 104.7 96.4 113.8 75.8 94.4 94.4 97.0 92.7 104.9 72.2 90 111.1 111.1 111.2 111.2 122.2 96.8 105.5 105.5 105.5 105.5 113.8 92.8 98.9 98.9 99.0 99.0 104.5 88.5

75 101.8 91.0 114.5 69.8 122.9 41.6 95.5 87.7 107.2 66.4 114.6 41.4 88.8 84.1 99.3 62.8 105.6 38.4 80 102.2 102.2 114.1 88.6 123.5 64.4 97.1 97.1 106.8 85.3 115.1 60.7 91.5 91.5 99.0 81.0 106.0 57.1 85 108.3 108.3 112.8 105.1 123.5 83.2 102.8 102.8 105.5 101.6 114.8 79.7 96.6 96.6 97.5 97.5 105.8 76.1 90 114.0 114.0 114.1 114.1 123.4 98.9 107.9 107.9 108.0 108.0 114.4 97.3 100.8 100.8 100.9 100.9 105.0 93.4

75 102.8 95.0 115.8 72.4 124.2 45.4 96.3 91.6 108.3 69.0 115.7 42.1 89.4 88.0 100.1 65.4 106.6 38.7 80 104.7 104.7 115.3 92.9 124.8 66.4 99.3 99.3 107.8 87.6 115.9 62.8 93.4 93.4 99.4 84.7 107.0 59.3 85 110.8 110.8 113.5 110.1 124.5 87.0 105.0 105.0 106.0 106.0 115.5 83.4 98.4 98.4 98.4 98.4 106.6 79.9 90 116.4 116.4 116.5 116.5 123.8 105.9 109.9 109.9 109.9 109.9 114.6 102.0 102.3 102.3 102.3 102.3 105.4 98.2

Ambient Temperature 115°F Ambient Temperature 125°F

75 78.7 67.7 87.4 51.5 93.2 32.1 71.7 61.7 79.0 47.3 83.5 26.7 80 78.3 78.3 87.4 65.2 93.5 46.9 72.4 72.4 78.9 61.4 83.9 43.2 85 83.0 83.0 87.1 78.3 93.6 60.7 76.4 76.4 78.5 74.1 84.0 56.9 90 87.2 87.2 87.3 87.3 93.5 74.9 79.6 79.6 79.7 79.7 84.0 69.5

75 80.0 72.2 88.8 53.9 94.2 33.6 72.5 68.3 80.0 49.9 84.1 29.3 80 81.1 81.1 88.7 69.6 94.8 49.4 74.7 74.7 79.8 65.6 85.1 45.1 85 85.7 85.7 88.0 83.6 94.8 64.7 78.4 78.4 79.0 79.0 84.9 60.8 90 89.6 89.6 89.6 89.6 94.7 77.4 81.3 81.3 81.3 81.3 84.5 75.4

75 80.9 76.3 89.9 56.5 95.2 34.4 73.2 72.3 80.7 52.5 85.2 30.0 80 83.3 83.3 89.7 73.7 95.9 51.3 76.5 76.5 80.4 68.3 85.8 47.3 85 87.8 87.8 88.6 88.6 95.7 68.6 79.9 79.9 80.0 80.0 85.5 64.4 90 91.3 91.3 91.3 91.3 95.1 84.6 83.0 83.0 83.0 83.0 84.8 80.3

75 81.6 80.3 90.7 59.0 96.2 34.4 73.8 73.8 81.3 54.9 85.5 28.1 80 85.2 85.2 90.2 77.0 96.7 53.4 77.9 77.9 80.6 72.6 86.4 49.4 85 89.4 89.4 89.5 89.5 96.5 72.0 81.0 81.0 81.0 81.0 86.1 67.8 90 92.8 92.8 92.9 92.9 95.5 89.4 84.3 84.3 84.3 84.3 84.9 84.9

75 82.0 82.0 91.4 61.5 96.8 35.6 75.1 75.1 81.8 57.4 86.2 31.2 80 86.8 86.8 90.6 80.6 97.4 55.5 79.0 79.0 80.8 76.1 86.9 51.4 85 90.8 90.8 90.8 90.8 97.1 76.0 82.0 82.0 82.1 82.1 86.2 71.2 90 94.4 94.4 94.4 94.4 95.7 94.2 85.3 85.3 85.4 85.4 85.4 85.4

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NETcooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total gross capacity

RT-PRC096C-EN 25

Table 8. Gross cooling capacities — 10 tons

CFM

Ent DB (°F)

Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC Ambient Temperature 85°F Ambient Temperature 95°F Ambient Temperature 105°F

75 113.3 91.6 127.5 72.0 138.4 47.1 106.8 88.1 119.9 68.7 129.2 43.6 99.8 84.5 111.7 64.9 119.2 41.7 80 112.4 106.2 127.2 88.5 138.7 66.8 105.9 102.5 119.7 85.0 129.5 63.4 99.0 99.0 111.6 81.1 119.5 59.0 85 114.8 114.8 126.8 105.0 139.0 84.2 109.6 109.6 119.4 101.5 130.1 80.0 103.9 103.9 111.3 95.1 120.1 75.8 90 125.9 119.3 125.9 119.3 138.9 100.5 115.9 115.9 118.5 115.5 130.1 96.7 109.6 109.6 110.4 110.4 120.2 92.6

75 115.9 97.5 130.2 75.8 140.2 50.4 109.1 93.6 122.2 72.2 130.5 46.5 101.8 87.1 113.6 67.9 120.9 42.7 80 114.6 114.6 129.8 93.9 140.7 69.7 107.9 107.9 122.0 90.3 131.2 65.9 101.5 101.5 113.4 87.6 121.1 62.1 85 119.4 119.4 129.3 109.2 141.1 88.4 113.9 113.9 121.3 107.2 131.7 84.6 107.7 107.7 112.7 103.0 121.3 80.4 90 126.1 126.1 127.8 127.3 141.0 107.1 120.1 120.1 120.2 120.2 131.7 103.3 113.3 113.3 113.4 113.4 121.4 99.1

75 117.9 100.4 132.3 78.8 141.6 51.1 110.6 98.2 124.1 75.0 132.2 47.4 103.0 94.1 115.2 71.0 122.2 43.6 80 116.4 116.4 131.9 101.1 142.8 73.7 110.8 110.8 123.7 95.4 132.6 68.6 104.7 104.7 114.9 91.4 122.6 65.2 85 123.4 123.4 130.7 117.4 142.6 93.0 117.4 117.4 122.6 113.4 132.9 89.1 110.8 110.8 113.6 113.6 122.5 84.9 90 130.1 130.1 130.2 130.2 142.6 113.7 123.6 123.6 123.7 123.7 133.0 108.1 116.0 116.0 116.1 116.1 122.1 104.0

75 119.1 106.9 134.1 82.0 143.1 52.0 111.8 103.0 125.6 78.2 133.6 48.3 103.9 98.8 116.4 74.0 123.3 44.4 80 119.6 119.6 133.5 104.2 143.8 75.7 113.8 113.8 125.1 100.4 134.1 71.2 107.3 107.3 116.0 94.7 123.8 67.1 85 126.7 126.7 131.8 123.4 143.9 97.6 120.4 120.4 123.3 123.3 133.9 93.6 113.3 113.3 114.1 114.1 123.5 89.5 90 133.4 133.4 133.5 133.5 143.8 117.8 126.4 126.4 126.4 126.4 133.5 114.3 118.2 118.2 118.2 118.2 122.5 109.6

75 120.1 111.6 135.5 85.1 144.4 52.9 112.5 112.5 126.8 81.2 134.7 49.2 104.5 104.5 117.3 77.0 124.3 45.3 80 122.5 122.5 134.8 109.1 145.2 77.7 116.3 116.3 126.2 101.9 135.0 73.6 109.5 109.5 116.5 99.6 124.8 69.7 85 129.6 129.6 132.4 132.4 145.0 102.0 122.9 122.9 123.8 123.8 134.8 97.4 115.3 115.3 115.4 115.4 124.4 94.0 90 136.1 136.1 136.2 136.2 144.1 124.1 128.6 128.6 128.7 128.7 133.7 119.7 119.7 119.7 119.8 119.8 122.7 122.7

Ambient Temperature 115°F Ambient Temperature 125°F

75 92.4 79.7 102.8 60.9 109.0 37.7 84.2 75.7 92.9 56.0 97.6 33.3 80 91.9 91.9 102.7 77.0 109.4 55.0 85.3 85.3 92.8 71.9 98.2 51.0 85 97.5 97.5 102.3 92.3 109.5 71.5 90.0 90.0 92.3 87.5 98.4 67.1 90 102.5 102.5 102.6 102.6 109.4 88.2 93.8 93.8 93.9 93.9 98.4 81.3

75 93.8 85.0 104.3 63.6 110.3 38.6 85.3 80.6 94.0 59.1 97.8 36.7 80 95.2 95.2 104.2 82.8 110.8 57.9 88.0 88.0 93.9 77.6 99.5 53.2 85 100.7 100.7 103.3 98.5 110.8 76.2 92.4 92.4 92.9 92.9 99.3 71.7 90 105.2 105.2 105.3 105.3 110.6 93.5 95.4 95.4 95.4 95.4 98.8 88.8

75 94.8 89.9 105.5 66.7 111.4 39.5 86.0 86.0 94.8 62.0 99.3 35.0 80 97.9 97.9 105.3 86.6 112.0 60.3 90.0 90.0 94.5 81.4 100.2 55.7 85 103.1 103.1 103.9 103.9 111.8 82.3 94.0 94.0 94.1 94.1 99.8 74.7 90 107.1 107.1 107.2 107.2 111.1 99.4 97.2 97.2 97.3 97.3 99.1 94.5

75 95.5 95.5 106.4 69.7 112.2 40.3 86.8 86.8 95.5 64.9 99.9 35.8 80 100.0 100.0 105.8 90.7 112.9 62.8 91.7 91.7 94.7 85.6 100.6 57.3 85 105.0 105.0 105.1 105.1 112.6 83.0 95.1 95.1 95.2 95.2 100.6 79.2 90 108.6 108.6 108.7 108.7 111.5 105.0 98.7 98.7 98.7 98.7 99.2 99.2

75 96.1 96.1 107.2 72.6 112.9 41.1 88.3 88.3 96.0 67.8 100.5 36.7 80 101.9 101.9 106.2 94.8 113.8 66.2 93.0 93.0 94.8 94.8 101.2 61.1 85 106.5 106.5 106.5 106.5 113.3 88.0 96.1 96.1 96.2 96.2 100.6 83.7 90 110.3 110.3 110.4 110.4 111.6 110.6 99.8 99.8 99.8 99.8 99.9 99.9

Notes:

1. All capacities shown are gross and have not considered indoor fan heat. To obtain NETcooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2. MBh = Total gross capacity

26 RT-PRC096C-EN

Table 9. Gross cooling capacities — 12.5 tons