This document is a comprehensive elevator modernization specification for Volusia County's S. James Foxman Justice Center, prepared by Lerch Bates Inc. The project involves modernizing four elevators: Passenger Elevator 1 and 2, Prisoner Elevator, and Judges Elevator. The scope includes complete engineering, equipment, labor, and permit requirements for a full elevator modernization. The contract includes 12 months of preventive maintenance, service, testing, and parts replacement following final acceptance, in accordance with a Portfolio Master Elevator Service Agreement. The specification covers detailed requirements for equipment replacement, installation procedures, performance standards, and quality assurance, with a focus on maintaining code compliance and operational efficiency.
The project requires a contractor with at least 5 years of local market experience within 50 miles of the project site, who must hold all necessary licenses. The specification mandates specific technical requirements for hydraulic elevator components, including machine room equipment, hoistway components, car equipment, and signaling systems. Notably, the project involves selective replacement and refurbishment of existing elevator infrastructure, with particular attention to the Judges and Prisoner elevators, which require more specialized features like stainless steel interior finishes, communication systems, and specific operating panel configurations. The contractor will be responsible for comprehensive installation, testing, and validation of the elevator systems, with strict performance guarantees and a detailed acceptance review process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LERCH BATES INC. HYDRAULIC ELEVATOR
Elevator Consulting Group MODERNIZATION
SECTION 14250
TABLE OF CONTENTS
PART 1 GENERAL
1.01 WORK INCLUDED
1.02 RELATED WORK
1.03 DEFINITIONS
1.04 QUALITY ASSURANCE
1.05 DOCUMENT AND SITE VERIFICATION
1.06 SUBMITTALS
1.07 PERMIT, TEST AND INSPECTION
1.08 MAINTENANCE
PART 2 EQUIPMENT
2.01 MATERIALS
2.02 CAR PERFORMANCE
2.03 OPERATION
2.04 MACHINE ROOM EQUIPMENT
2.05 HOISTWAY EQUIPMENT
2.06 HOISTWAY ENTRANCES
2.07 CAR EQUIPMENT
2.08 CAR ENCLOSURE
2.09 HALL CONTROL STATIONS
2.10 SIGNALS
PART 3 EXECUTION
3.01 SITE CONDITION INSPECTION
3.02 PRODUCT DELIVERY, STORAGE, AND HANDLING
3.03 INSTALLATION
3.04 FIELD QUALITY CONTROL
3.05 ADJUSTMENTS
3.06 CLEANUP
3.07 PAINTING
3.08 ACCEPTANCE REVIEW AND TESTS
14250 - 1 Volusia County / S James Foxman Justice Center
SECTION 14250
HYDRAULIC ELEVATOR MODERNIZATION
PART 1 GENERAL
1.01 WORK INCLUDED
A. Location and Elevators: S James Foxman Justice Center
1. Passenger Elevator 1 and 2, Prisoner Elevator, Judges Elevator
B. All engineering, equipment, labor, and permits required to satisfactorily complete elevator modernization required by Contract Documents.
C. Applicable conditions of General, Special, and Supplemental Conditions, Division 1, and all sections listed in Contract Documents “Table of Contents.”
D. Project Costs shall be inclusive of Preventive Maintenance, Service, Testing and parts replacement for the 12 Month Warranty Period following Final Acceptance of the modernization in accordance with the Portfolio Master Elevator Service Agreement.
E. Cartage and Hoisting: All required staging, hoisting and movement to, on, and from the site including new equipment, reused equipment, or dismantling and removal of existing equipment.
F. Unless specifically identified as “Reuse,” “Retain,” or “Refurbish,” provide new equipment.
G. Protective barriers between cars in normal operation and adjacent cars in the modernization process. Full depth and height of hoistway.
H. Hoistway, pit, and machine room barricades as required.
1.02 RELATED WORK
A. As part of this Elevator Modernization Contract, all associated building related work will be included in the scope of work and the responsibility of the Elevator Contractor. The elevator Contractor may utilize any Certified and Licensed General
14250 - 2 Volusia County / S James Foxman Justice Center
Contractor, Electrician, and other subcontractors necessary to perform the Building Related Work
B. The following building related work shall be performed as noted below. Should additional work be required that is foreseen in the review of the project site, the Elevator Contractor shall make Volusia County and Consultant aware of it immediately in writing so an Addendum can be issued, otherwise it shall be the Elevator Contractor’s responsibility for providing as part of their bid submittal. Work applies to all elevators unless explicitly stated otherwise.
1. MACHINE ROOM:
a. Provide/confirm air conditioning for machine room. Provide all electrical, engineering, permitting and vandal resistant lockable cage for exterior condenser that shall be wall mounted in a preapproved location by Facility Management. Per A17.1 do not locate HVAC equipment over Elevator or Electrical equipment. Locate in a serviceable location and install in accordance with local codes and manufacturer installation requirements.
Provide full manufacturer’s standard warranty, parts and labor.
b. Provide 110VAC GFCI outlets in machine room.
c. Provide auxiliary contacts for mainline disconnects and applicable signal wiring for battery lowering feature.
d. Provide Standby single-phase power to controller, and car lighting, car top fan and emergency signaling device.
e. Provide New Three-phase mainline copper power feeder to terminals of each elevator controller in the machine room. Provide New Heavy Duty Electrical Disconnect
f. Provide New Single-phase copper power feeder to each elevator controller for car lighting and exhaust blower. Provide in solid conduit.
g. Provide Emergency telephone line to each individual elevator control in elevator machine room.
h. Verify/Provide 3 fire initiation signaling to elevator equipment in machine room and all applicable related work. Main, Secondary, Fire Hat.
i. Connect Fire Initiating Devices to elevator controller and provide all tests for proper operation. Testing shall be performed prior to each elevator being turned over for public use after being modernized. Replace non-operational fire signalization devices.
j. Seal all static vents and penetrations in machine room enclosure to ensure proper fire rating and ensure efficient use of HVAC.
k. Provide a minimum of 200lx of LED lighting at machine room floor. Provide light switch at strike side of machine room entry.
2. HOISTWAY/PIT/LANDINGS/CAR
a. Provide NEMA 4 guarded light and switch in each pit (Minmium10 foot candles throughout entire pit areas).
b. Provide 110VAC GFCI protected outlet in pit.
c. Where existing sump pumps are located, replace with new rated for 3000gph and provide a dedicated non-gfci outlet receptacle for power.
d. All stop switches and pit light switches should be located minimum 18 inches above the landing floor, accessible from outside the hoistway, clearly labeled and not installed behind pit ladder rungs.
e. Verify and provide proper operation of fire initiation devices currently in hoistway.
f. Verify/Provide 3 fire initiation signaling to elevator equipment in machine room and all applicable related work. Main, Secondary, Fire Hat.
1) Fire Alarm initiation devices shall be designed and installed without being impacted by external air, wind, dust considerations.
14250 - 3 Volusia County / S James Foxman Justice Center
2) Replace devices that are not operational, not adequate for reuse and or are not located in a code compliant functional location.
3) Provide all engineering, permitting, labor, installation and inspection services.
1.03 DEFINITIONS
A. Terms used are defined in the latest edition of the Safety Code for Elevators and Escalators, ASME A17.1.
B. Reference to a device or a part of the equipment applies to the number of devices or parts required to complete the installation.
C. The provisions of this specification are applicable to all elevators unless identified otherwise.
D. Substantial Completion is the stage in the progress of the Work when the project is sufficiently complete in accordance with the Contract Documents so that the Owner can use the elevators for their intended use. This shall be at a minimum a time when all elevators in the project have passed all mandated safety code inspections.
1.04 QUALITY ASSURANCE
A. Bidding Contractor’s must be in business for a minimum of 5 years in the local market, defined as within 50 miles of the project there must be an official business address. The Contractor must hold all the necessary licenses required to perform their business, to include any subcontractor’s being utilized.
B. To be furnished with your bid, provide general information as follows:
1. Within 50 Miles of this project, provide the following about your company:
a. Dedicated Modernization Mechanics: _______
b. Dedicated Modernization Supervisors: _______
c. Dedicated Repair Teams: _______
d. Dedicated Maintenance Mechanics: _______
e. Number of Maintenance Routes: _______
f. How many elevators on service within 50 miles of this project._______
2. Physical Branch Office Address _______________________________
3. Years in Business _______ (Minimum of 5 years licensed in State of Florida)
4. Quantity of Elevators Modernized in the past 5 years out of local Branch Office
C. Compliance with Regulatory Agencies: Comply with most stringent applicable provisions of following Codes, laws, and/or Authorities, including revisions and changes in effect:
1. Safety Code for Elevators and Escalators, ASME A17.1
2. Guide for Inspection of Elevators, Escalators, and Moving Walks, ASME A17.2
3. Elevator and Escalator Electrical Equipment, ASME A17.5
4. All Applicable National Electrical Code
5. All Applicable NFPA Code Requirements
6. Americans with Disabilities Act, ADA/ADAAG
7. Local Fire Authority Requirements
8. Florida Building Code, Administrative Code and Statutes
9. Uniform Federal Accessibility Standard, UFAS
D. Warranty:
14250 - 4 Volusia County / S James Foxman Justice Center
1. Material and workmanship of installation shall comply in every respect with Contract Documents. Correct defective material or workmanship which develops within one
(1) year from date of final acceptance of all work to satisfaction of Purchaser and Consultant at no additional cost, unless due to ordinary wear and tear, or improper use or care by Purchaser. Perform maintenance in accordance with terms and conditions indicated in the Preventive Maintenance Agreement.
2. Defective is defined to include, but not be limited to: operation or control system failures, car performance below required minimum, excessive wear, unusual deterioration, or aging of materials or finishes, unsafe conditions, the need for excessive maintenance, abnormal noise, or vibration, and similar unsatisfactory conditions.
3. Retained Equipment: All retained components, parts, and materials shall be cleaned, checked, modified, repaired or replaced, so each component and its parts are in like new operating condition. Retained equipment must be compatible for integration with new systems. All retained equipment shall be covered under the warranty provisions of the Contract Documents. No perorations of equipment or parts shall be allowed on preventive maintenance contract.
4. Make modifications, requirements, adjustments, and improvements to meet performance requirements of the Construction Documents.
1.05 DOCUMENT AND SITE VERIFICATION
A. In order to discover and resolve conflicts or lack of definition which might create problems, Contractor must review Contract Documents and site conditions for compatibility with its product prior to submittal of quotation. Review existing structural, electrical provisions, and mechanical provisions for compatibility with Contractor's products. Purchaser will not pay for change to structural, mechanical, electrical, or other systems required to accommodate Contractor’s equipment.
B. Failure of providing thorough review of site conditions shall not result in additional costs to the Purchaser. This is inclusive of both specified and non-specified building related work Contractors.
1.06 SUBMITTALS
A. To be furnished with bid, provide a PDF Microsoft Word Schedule with specific dates itemizing minimum installation tasks for each elevator with the tentative start date of the schedule being 60 days after the required bid due date. Include the following tasks in no specific order:
1. Equipment Fabrication
2. Equipment Delivery
3. Elevator Modernization Commencement (removed from public beneficial usage)
4. Jobsite Safety Tasks
5. Machine Work
6. Controller Work
7. Car Door Work
8. Hoistway Door Work
9. Wiring
10. Hall Fixtures
11. Car Fixtures
12. Pit Work
13. Fire Command Panel
14. Building Electrical Work
15. Building HVAC Work
16. Building Fire System Work
14250 - 5 Volusia County / S James Foxman Justice Center
17. Testing
18. Cleaning/Painting
19. Turn Over for Public Use
20. Note when elevator work will be performed outside of 6:00am-6:00pm M-F hours.
At contract signing or issuance of Purchase Order, resubmit schedule with revised dates as needed to adjust for front end award/contracting process should the original dates not be accurate. Durations of tasks shall not change from original schedule submitted with bid just as long as scope of work did not change.
B. Payment schedule of values shall be in accordance with Volusia County’s payment standards and procedures.
C. Within 10 calendar days after award of contract and before beginning equipment fabrication submit shop drawings, and required material samples for review. Allow 10 days for response to initial submittal.
1. Scaled or Fully Dimensioned Layout: Plan of pit, hoistway, and machine room indicating equipment arrangement, elevation section of hoistway, details of car enclosures, and car/hall signal fixtures.
2. Design Information: Indicate equipment lists, reactions, and design information on layouts.
3. Power Confirmation Information: Design for existing conditions.
4. Fixtures: Cuts, samples, or shop drawings.
5. Finish Material: Submit 3" x 12" samples of actual finished material for review of color, pattern, and texture. Compliance with other requirements is the exclusive responsibility of the Contractor. Include, if requested, signal fixtures, lights, graphics, Braille plates, and detail of mounting provisions.
6. Design Information: Provide calculations verifying the following:
a. Adequacy of existing electrical provisions.
b. Adequacy of retained equipment relative to code requirements if car weight increased by more than 5%.
c. Machine room heat emissions in B.T.U.H.
d. Adequacy of existing retained elevator machine beams.
e. Adequacy of existing car platform structure for intended loading.
7. Written Maintenance Control Program (MCP) specifically designed for the equipment included under this contract. Include any unique or product specific procedures or methods required to inspect or test the equipment. In addition, identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other required equipment tests.
D. Submittal review shall not be construed as an indication that submittal is correct or suitable or that the work represented by submittal complies with the Contract Documents.
Compliance with Contract Documents, Code requirements, dimensions, fit, and interface with other work is Contractor’s responsibility.
E. Acknowledge and/or respond to review comments within 10 calendar days of return.
Promptly incorporate required changes due to inaccurate data or incomplete definition so that delivery and installation schedules are not affected. Identify and cloud drawing revisions including Contractor elective revisions on each re-submittal. Contractor’s revision response time is not justification for equipment delivery or installation delay.
F. At the completion of the project: Provide 3 sets of neatly bound and 2 electronic sets written information necessary for proper maintenance, testing, repair, diagnostic and adjustment of equipment within 30 days following final acceptance. Final retention will be
14250 - 6 Volusia County / S James Foxman Justice Center withheld until data is received by Purchaser and reviewed by Consultant. Include the following as minimums:
1. Straight-line wiring diagrams of “as-installed” elevator circuits, with index of location and function of components. Provide one set reproducible master. Mount one set wiring diagrams on panels, racked, or similarly protected, in elevator machine room.
Provide remaining set rolled and in a protective drawing tube. Maintain all drawing sets with addition of all subsequent changes. These diagrams are Purchaser’s property. A legend sheet shall be furnished with each set of drawings to provide the following information:
a. Name and symbol of each relay, switch, or other apparatus.
b. Location on drawings, drawing sheet number and area, and location of all contacts.
c. Location of apparatus, whether on controller or on car.
2. Written Maintenance Control Program (MCP) specifically designed for the equipment included under this contract. Include any unique or product specific procedures or methods required to inspect or test the equipment. In addition, identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other required equipment tests.
3. Printed instructions explaining all operating features.
4. Complete software documentation for all installed equipment.
5. Lubrication instructions, including recommended grade of lubricants.
6. Parts catalogs listing all replaceable parts including Contractor’s identifying numbers and ordering instructions.
7. Four sets of keys for all switches and control features properly tagged and marked.
8. Diagnostic test devices together with all supporting information necessary for interpretation of test data and troubleshooting of elevator system, and performance of routine safety tests.
9. The elevator installation shall be a design ( MCE ) which can be maintained by any licensed elevator maintenance company employing journeymen mechanics, without the need to purchase or lease additional diagnostic devices, special tools, or instructions from the original equipment Manufacturer.
a. Provide on site capability to diagnose faults to the level of individual circuit boards and individual discreet components for the solid state elevator controller.
b. Provide a separate, detachable device, as required to the Purchaser as part of this installation if the equipment for fault diagnosis is not completely self-contained within the controller. Such device shall be in possession of and become property of the Purchaser.
c. Installed equipment not meeting this requirement shall be removed and replaced with conforming equipment at no cost to the Purchaser.
10. Provide upgrades and/or revisions of software during the progress of the work, warranty period and the term of the ongoing maintenance agreement between the Purchaser and Contractor.
G. Preventive Maintenance Contract: Furnish properly executed contract for continuing, preventive maintenance at the direction of the Purchaser.
H. Acceptance of such records by Purchaser/Consultant shall not be a waiver of any Contractor deviation from Contract Documents or shop drawings or in any way relieve Contractor from his responsibility to perform work in accordance with Contract Documents.
1.07 PERMIT, TEST AND INSPECTION
A. Obtain and pay for permit, license, and inspection fee necessary to complete installation.
14250 - 7 Volusia County / S James Foxman Justice Center
B. Perform test required by governing authority in accordance with procedure described in ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving Walks in the presence of Authorized Representative.
C. Supply personnel and equipment for final review by Consultant.
1.08 MAINTENANCE
A. INTERIM AND WARRANTY MAINTENANCE
1. Furnish preventive maintenance service on elevators in accordance with the current service agreement standards in place for the facility (see separate document) effective the 1st of the month in which Construction will occur through the completion of the 12 month Warranty Period. The cost for Interim and Warranty Maintenance shall be included in the lump sum cost of the Contractor’s bid.
2. All service calls shall be included at no additional charge during this period, to include overtime, holiday, weekends.
3. Use competent personnel, acceptable to Purchaser, employed and supervised by the Contractor.
4. Provide all Code Mandated Testing that is mandated to ensure the elevators maintain a current certificate of operation.
5. Perform services in accordance with the Service Agreement referenced.
6. At the conclusion of all elevators being modernized in this contract, provide preventive maintenance and 24-hour emergency callback service for one year commencing on date of final acceptance by Purchaser. Perform this service in accordance with the terms and conditions of the Service Agreement. This service will not have a monthly service charge.
7. Provide all Code Mandated Testing that is mandated to ensure the elevators maintain a current certificate of operation.
8. Use competent personnel, acceptable to the Purchaser, supervised and employed by Contractor.
9. The warranty maintenance period above shall be extended one (1) month for each three (3) month period in which equipment related failures average more than .25 per unit per month.
B. CONTRACT PREVENTIVE MAINTENANCE
1. Upon Completion of the Warranty Period, the elevator(s) will revert back to the incumbent service provider should the incumbent service provider not be the Modernization awardee.
PART 2 EQUIPMENT
2.01 MATERIALS
A. Materials and finishes that are specified in this contract, they shall meet the below requirements at a minimum and ensure aesthetic compatibility with adjacent or nearby finishes of the same metal types, both new and retained.
B. Steel:
1. Sheet Steel (Furniture Steel for Exposed Work): Stretcher-leveled, cold-rolled, commercial quality carbon steel, complying with ASTM A366, matte finish.
2. Sheet Steel (for Unexposed Work): Hot-rolled, commercial quality carbon steel, pickled and oiled, complying with ASTM A568/A568M-03.
3. Structural Steel Shapes and Plates: ASTM A36.
14250 - 8 Volusia County / S James Foxman Justice Center
C. Stainless Steel: Type 302 or 304 complying with ASTM A240, with standard tempers and hardness required for fabrication, strength and durability. Apply mechanical finish on fabricated work in the locations shown or specified, Federal Standard and NAAMM nomenclature, with texture and reflectivity required. Protect with adhesive paper covering.
1. No. 4 Satin: Directional polish finish. Graining in vertical dimension.
D. Aluminum: Extrusions per ASTM B221; sheet and plate per ASTM B209.
E. Plastic Laminate: ASTM E84 Class A and NEMA LD3.1, Fire-Rated Grade (GP-50), Type 7, 0.050" ±.005" thick, color and texture as follows:
1. Exposed Surfaces: Color and texture selected by Purchaser.
2. Concealed Surfaces: Contractor’s standard color and finish.
F. Fire-Retardant Treated Particle Board Panels: Minimum 3/4" thick backup for natural finished wood and plastic laminate veneered panels, edged and faced as shown, provided with suitable anti-warp backing; meet ASTM E84 Class “I” rating with a flame-spread rating of 25 or less, registered with Local Authorities for elevator finish materials.
G. Paint: Low Fume Water Based Paint. (All Painting shall be performed after normal business hours of the facility and vented properly.
2.02 CAR PERFORMANCE
A. Car Speed: ± 5% of contract speed under any loading condition.
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. 2.0-2.5 seconds (center open doors)
2. 2.5-3.0 seconds (side open doors)
E. Door Closing Time: Seconds from start of closing to fully closed:
1. 2.5-3.0 seconds (center open doors)
2. 4.0-4.5 seconds (side open doors)
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open for center opening doors and 1/2 open for side opening doors and car level and stopped at next successive floor under any loading condition or travel direction. Based on 12’ floors, add or deduct .2 seconds per foot deviation:
1. 14.0-15.0 seconds (center open doors)
2. 16.5-17.5 seconds (center open doors)
G. Pressure: Fluid system components shall be designed and factory tested for 500 p.s.i.
Maximum operating pressure shall be 400 p.s.i.
H. Car Ride Quality:
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than 3 feet/second² with an initial ramp between 0.5 and 0.75 second.
3. Sustained Jerk: Not more than 6 feet/second³.
14250 - 9 Volusia County / S James Foxman Justice Center
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO 18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
I. Noise and Vibration Control
1. Airborne Noise: Measured noise level of elevator equipment and its operation shall not exceed 55 dBA inside car under any condition including door operation and car ventilation exhaust blower on its highest speed. Limit noise level in the machine room relating to elevator equipment and its operation to no more than 80 dBA. All dBA readings to be taken 3'-0" off the floor and 3'-0" from the equipment using the “A” weighted scale.
2. Vibration Control: All elevator equipment provided under this contract, including power unit, controller, oil supply lines, and their support shall be mechanically isolated from the building structure and electrically isolated from the building power supply and to each other to minimize the possibility of objectionable noise and vibrations being transmitted to occupied areas of the building.
2.03 OPERATION ALL CARS
A. Approved Controller System Manufacturers
1. Motion Control Engineering (MCE)
B. Simplex Collective Microprocessor Based:
1. Operate car without attendant from pushbuttons in car and located at each floor.
When car is available, automatically start car and dispatch it to floor corresponding to registered car or hall call. Once car starts, respond to registered calls in direction of travel and in the order the floors are reached.
2. Do not reverse car direction until all car calls have been answered, or until all hall calls ahead of car and corresponding to the direction of car travel have been answered.
3. Slow car and stop automatically at floors corresponding to registered calls, in the order in which they are approached in either direction of travel. As slowdown is initiated for a hall call, automatically cancel hall call. Cancel car calls in the same manner. Hold car at arrival floor an adjustable time interval to allow passenger transfer.
4. Answer calls corresponding to direction in which car is traveling unless call in the opposite direction is highest (or lowest) call registered.
5. Illuminate appropriate pushbutton to indicate call registration. Extinguish light when call is answered.
C. Other Items:
1. Low Oil Control: In the event oil level is insufficient for travel to the top floor, provide controls to return elevator to the main level and park until oil is added.
2. Independent Service: Provide controls for operation of each car from its pushbuttons only. Close doors by constant pressure on desired destination floor button or door close button. Open doors automatically upon arrival at selected floor.
D. Firefighters’ Service: Provide equipment and operation in accordance with code requirements.
E. Automatic Car Stopping Zone: Stop car within 1/4" above or below the landing sill.
Maintain stopping zone regardless of load in car, direction of travel, distance between landings.
14250 - 10 Volusia County / S James Foxman Justice Center
F. Motion Control: AC type with unit valve suitable for operation specified and capable of providing smooth, comfortable car acceleration and retardation. Limit the difference in car speed between full load and no load to not more than ±5% of the contract speed in either direction of travel.
G. Door Operation: Automatically open doors when car arrives at main floor. At expiration of normal dwell time, close doors. Reopen doors when car is designated for loading. Provide “heavy door/variable air pressure” feature for consistent specified door operation within appropriate speed and inertia limits.
H. Standby Lighting and Alarm: Car mounted battery unit with solid-state charger to operate alarm bell and car emergency lighting. Battery to be rechargeable with minimum 5-year life expectancy. Include required transformer. Provide constant pressure test button in service compartment of car operating panel.
1. Battery Standby Power Transfer: Upon loss of normal power, provide controls to automatically lower the car(s) to the nearest lower landing. Upon arrival at the nearest landing, the elevator doors shall open automatically and remain open until regular door time has expired. The elevator shall then become deactivated. The standby power source shall be provided via 12-volt D.C. battery units installed in machine room, including solid-state charger and testing means mounted in a common metal container. Battery to be rechargeable lead acid or nickel cadmium with a 10-year life expectancy.
2. Upon restoration of normal power, the elevator shall automatically resume normal operation
2.04 MACHINE ROOM EQUIPMENT ALL CARS
A. Arrange equipment in existing machine room spaces.
B. Pump Unit: Provide New. Assembled unit consisting of positive displacement pump, induction motor, master-type control valves combining safety features, holding, direction, bypass, stopping, manual lowering functions, shut off valve, oil reservoir with protected vent opening, oil level gauge, outlet strainer, MEI SILENCER, all mounted on isolating pads.
Design unit for heavy duty 24/7 type use, minimum 80 up starts per hour. ALL
ELEVATORS
C. Landing Systems: Shall be designed and installed with not be negatively impacted, degrade in quality or functionality due to the exposure of humid air, direct UV light and temperatures in excess of 100 degrees. The application shall be appropriate for garage hoistway that has a glassback hoistway that receives direct sunlight and has corridor space that does not have humidity or temperature control provisions. - ALL ELEVATORS
D.
E. Controller: UL/CSA labeled. - ALL ELEVATORS
1. Compartment: Securely mount all assemblies, power supplies, chassis switches, relays, etc., on a substantial, self-supporting steel frame. Completely enclose equipment with covers. Provide means to prevent overheating.
2. Relay Design: Magnet operated with contacts of design and material to insure maximum conductivity, long life, and reliable operation without overheating or excessive wear. Provide wiping action and means to prevent sticking due to fusion.
Contacts carrying high inductive currents shall be provided with arc deflectors or suppressors.
3. Microprocessor-Related Hardware
14250 - 11 Volusia County / S James Foxman Justice Center
a. Provide built-in noise suppression devices which provide a high level of noise immunity on all solid-state hardware and devices.
b. Provide power supplies with noise suppression devices.
c. Isolate inputs from external devices, such as pushbuttons, with opto-isolation modules.
d. Design control circuits with one leg of power supply grounded.
e. Safety circuits shall not be affected by accidental grounding of any part of the system.
f. System shall automatically restart when power is restored.
g. System memory shall be retained in the event of power failure or disturbance.
h. Equipment shall be provided with Electro Magnetic Interference (EMI) shielding within FCC guidelines.
4. Wiring: CSA labeled copper for factory wiring. Neatly route all wiring interconnections and securely attach wiring connections to studs or terminals.
5. Permanently mark components, relays, fuses, PC boards, etc., with symbols shown on wiring diagrams.
6. Controller shall be designed to include brownout protection circuitry, surge protection circuitry and shall be clearly labeled for visual inspection and validation from Consultant.
F. Muffler: Provide MEI Silencer. Properly charge system and leave service instruction manual in machine room. - - ALL ELEVATORS
G. Piping and Oil: Provide New. Provide necessary piping, connections and oil for the system.
All pipe shall have support hangers or stands that are isolated from building structure. A minimum of two (2) sound isolation couplings shall be provided between the pump unit and oil line and the oil line and jack unit. Pipe shall be painted flat black and labeled every 6 feet “Elevator Hydraulic Line” a minimum of 2” letters in typed and laminated signage affixed to pipe for areas that are within general public spaces. All penetrations for oil line in building structure shall be backfilled with appropriate grade fire putty to maintain fire rating.
Oil line shall not come in direct contact with any building structure that could result in the emission of noise or vibration. Judge and Prisoner car oil lines shall be new. Abandoned oil lines to be cut off flush and filled. - ALL ELEVATORS
H. Shutoff Valve: Provide New. Manual valve in line adjacent to pump unit as well as adjacent to hydraulic cylinder. No special tools shall be required to operate. - ALL ELEVATORS
2.05 HOISTWAY EQUIPMENT - ALL ELEVATORS
A. Guide Rails: Retain main guide rails in place.
1. Clean rails and brackets. Remove all rust.
2. Check all rail and bracket fastenings and tighten.
3. Realign rails as required to provide smooth car ride.
4. Provide supplemental rail brackets and/or backing as required by code or to enhance car ride quality.
B. Buffers Retain existing. Clean and Paint
C. Pit Ladder: Verify/Provide Code Compliant Pit ladder.
D. Hydraulic Jack Assembly: Retain existing.
1. Cylinders: Retain existing. Provide New Packing Seal. Thoroughly clean hydraulic piston and if required due to poor surface condition, temporarily install sanding collar to smooth our any piston abnormalities. Contractor is responsible for ensure the jack
14250 - 12 Volusia County / S James Foxman Justice Center assembly is plumb and provides operation that does not have any knocks, grinding or cause accelerated packing seal replacements and loss of oil.
E. Terminal Stopping: Provide normal and final devices. Provide emergency terminal speed limiting devices.
F. Electrical Wiring and Wiring Connections:
1. Conductors and Connections: Copper throughout with individual wires coded and connections on identified studs or terminal blocks. Use no splices or similar connections in wiring except at terminal blocks, control compartments, or junction boxes. Provide 10% spare conductors throughout. Run spare wires from car connection points to individual elevator controllers in the machine room. Provide applicable spare shielded communication wires in addition to those required to connect specified items. Tag spares in machine room.
2. Conduit: Retain existing conduit where feasible. Al other times provide galvanized steel conduit, EMT, or duct. Conduit size, 1/2". Flexible heavy-duty service cord may be used between fixed car wiring and car door switches for door protective devices.
3. Traveling Cables: Flame and moisture-resistant outer cover. Prevent traveling cable from rubbing or chafing against hoistway or equipment within hoistway.
4. Auxiliary Wiring: Connect fire alarm initiating devices, emergency two-way communication system in each car controller in machine room.
G. Entrance Equipment: Provide GAL Door Package with moisture resistant GAL door operator.
1. Door Hangers: Provide New
2. Door Tracks: Provide New.
3. Door Interlock Assemblies: Provide New.
4. Door Closers: Smart Tork Spirators on each door.
5. Hoistway Door Unlocking Device: Provide New.
6. Relating Mechanism: Provide New.
7. .
H. Hoistway Access Switches: Mount at terminal landings with engraved position labels.
2.06 HOISTWAY ENTRANCES – ALL ELEVATORS
A. Door Panels: Provide New. Fully enclosed 16-gauge steel, sandwich construction without binder angles. Provide leading edges of center-opening doors with rubber astragals.
Provide a minimum of two (2) gibs per panel, one at leading and one at trailing edge with gibs in the sill groove entire length of door travel. Construct door panels with interlocking, stiffening ribs. Architectural metal of 316 stainless cladding shall wrap around leading and trailing edge of panel and return a minimum of 1/2" on rear side of leading edge of panel.
Provide new sight guards with matching finish and new strike bumpers for side opening doors or rubber astragals for center opening doors. Note : Retain Passenger #1 and #2 main landing hoistway doors.
B. Door Retainers: Provide at top and bottom of doors in accordance with code requirements.
C. Sight Guards: Provide new, matching material and finish as doors.
D. Fascia, Toe Guards, and Hanger Covers: Paint Flat Black.
14250 - 13 Volusia County / S James Foxman Justice Center
E. Hoistway Entrance Jambs: Wrap jambs in 316 stainless cladding. Note : Retain existing jambs and finishes Passenger #1 and #2.
2.07 CAR EQUIPMENT
A. Frame: Retain Existing. Check and tighten all fastenings. Paint entire frame flat black.
Provide new cab enclosure steadying isolation. ALL CARS
B. Platform: Retain existing. Reinforce if required. Check and tighten all fastenings. There should be adequate isolation between piston platen plate and piston such that there is not any vibration transmission to cab floor in the up direction. ALL CARS
C. Platform Apron: Provide new extended platform apron per code. Minimum 14-gauge steel, reinforced and braced to car platform for all car openings. ALL CARS
D. Guide Shoes: Provide New, utilizing appropriate design and manufactured by ELSCO. ALL
CARS
E. Sills: Provide New Aluminum Sill. Prepare the existing area properly prior to installing new sill. Utilize security type fasteners. Prisoner and Judges Cars Only
F. Doors: Provide New. 16 gauge steel, sandwich construction without binder angles.
Construct door panels with interlocking, stiffening ribs. Doors should be of a solid and robust fabrication. Door panels should not flex or be of inferior quality. Provide Satin Stainless Finish. Doors shall not have integral hanger assemblies. Prisoner and Judges Car Only
G. Door Hangers: Provide New. GAL. Two-point hanger roller with neoprene roller surface and suspension with eccentric upthrust roller adjustment. All Cars
H. Door Track: Provide New. GAL. Bar or formed, cold-drawn removable steel track with smooth roller contact surface. All Cars
I. Door Header: If new door equipment requires, provide new 12 gauge steel, shape to provide stiffening flanges. Otherwise retain existing and modify as needed. All Cars
J. Door Electrical Contact: GAL. Prohibit car operation unless car door is closed. All Cars
K. Door Clutch: Provide New. GAL. Heavy-duty clutch, linkage arms, drive blocks and pickup rollers or cams to provide positive, smooth, quiet door operation. Design clutch so car doors can be closed, while hoistway doors remain open. All Cars
L. Restricted Opening Device: Provide New. GAL. Provide means for restricting door opening per code requirements if existing means cannot be retained. Plunger type restrictors not acceptable. All Cars
M. Door Operator: Provide New. High speed, heavy-duty door operator capable of opening doors at no less than 2-1/2 f.p.s. Accomplish reversal in no more than 2-1/2" of door movement. Provide solid-state door control with closed loop circuitry to constantly monitor and automatically adjust door operation based upon velocity, position, and motor current. .
Provide a minimum of four (4) controller-activated motion profiles, per floor, per door, to maintain consistent, smooth, and quiet door operation at all floors, regardless of door weight or varying air pressure. Acceptable closed-loop door operators: All Cars
1. GAL MOVFRII Moisture Resistant Grade (W).
14250 - 14 Volusia County / S James Foxman Justice Center
N. Door Control Device: All Cars
1. Infrared Reopening Device: New black fully enclosed device with full screen infrared matrix or multiple beams extending vertically along leading edge of each door panel to minimum height of 7'-0" above finished floor. Device shall prevent doors from closing and reverse doors at normal opening speed if beams are obstructed while doors are closing, except during nudging operation. In event of device failure, provide for automatic shutdown of car at floor level with doors open.
2. Nudging Operation: After beams of door control device are obstructed for a predetermined time interval (minimum 20.0 - 25.0 seconds), warning signal shall sound and doors shall attempt to close with a maximum of 2.5 foot pounds kinetic energy. Activation of the door open button shall override nudging operation and reopen doors.
3. Interrupted Beam Time: When beams are interrupted during initial door opening, hold door open a minimum of 3.0 seconds. When beams are interrupted after the initial 3.0 second hold open time, reduce time doors remain open to an adjustable time of approximately 1.0 - 1.5 seconds after beams are reestablished.
4. Differential Door Time: Provide separately adjustable timers to vary time that doors remain open after stopping in response to calls.
a. Car Call: Hold open time adjustable between 3.0 and 5.0 seconds.
b. Hall Call: Hold open time adjustable between 5.0 and 8.0 seconds. Use hall call time when car responds to coincidental calls.
O. Car Operating Panel: Judges and Prisoner Car Only
1. Provide Innovation with PB72 LED Blue Buttons.
2. Single car operating panel with faceplates, consisting of a metal box containing vandal resistant operating fixtures, mounted behind the car stationary front return panel. Faceplates shall be hinged and constructed of stainless steel, satin finish.
3. Suitably identify floor buttons, alarm button, door open button, door close button with SCS, Visionmark, or Entrada cast tactile symbols recessed flush mounted. Configure plates per local building code accessibility standards including Braille. Locate operating controls no higher than 48" above the car floor; no lower than 35" for emergency push-to-call button and alarm button.
4. Provide minimum 3/4" diameter flush floor pushbuttons which illuminate to indicate call registration.
5. Provide alarm button to ring bell located on car. Illuminate button when actuated.
6. Provide keyed stop switch at bottom of car operating panel in locked car service compartment. Mark device to indicate “run” and “stop” positions.
7. Provide “door open” button to stop and reopen doors or hold doors in open position.
8. Extended Door Hold Open Button: Provide button to extend normal door hold open period up to 30 seconds. Cancel extended time by registration of car call or actuation of door close button. When activated, illuminate the door hold open button and the door close button. Cancel the hold open time when the door close button is activated. If a hall call is entered at another floor, sound a buzzer to indicate call waiting is activated.
9. Provide “door close” button to activate door close cycle. Cycle shall not begin until normal door dwell time for a car or hall call has expired, except firefighters’ operation.
10. Provide firefighters' locked box as required by code.
11. Provide firefighters’ Phase II key switch with engraved instructions filled red. Include light jewel, audible signal, and call cancel button.
12. Provide lockable service compartment with recessed flush door. Door material and finish shall match car return panel or car operating panel faceplate. Inside surface of door shall contain an integral flush window for displaying the elevator operating permit.
13. Include the following controls in lockable service cabinet with function and operating positions identified by permanent signage or engraved legend:
14250 - 15 Volusia County / S James Foxman Justice Center
a. Inspection switch.
b. Light switch.
c. Three-position exhaust blower switch.
d. Independent service switch.
e. Constant pressure test button for battery pack emergency lighting.
f. 120-volt, AC, GFCI protected electrical convenience outlet.
g. Stop switch.
h. Switch to select either floor voice annunciation, floor passing tone, or chime.
14. Provide black paint filled (except as noted), engraved, or approved etched signage as follows with approved size and font:
a. Phase II firefighters’ operating instructions on main operating panel above corresponding keyswitch filled red.
b. Car number
c. “No Smoking” with symbol
d. Car capacity in pounds
P. Car Top Control Station: Provide New with ENABLE function. Mount to provide safe access and utilization while standing in an upright position on car top. All Cars
Q. Car Top Railing: Provide Retain , New if required.
R. Work Light and Duplex Plug Receptacle: Provide New All Cars
1. GFCI protected outlet at top and bottom of car for Elevator Technician use
2. GFCI protected outlet at top of car for future security camera installation on a dedicated circuit.
3. Provide a minimum of 10 foot candle of lighting on entire car top.
4. Include on/off switch and lamp guard.
S. Car Top Ventilation Fan: Provide New. Provide three-speed fan sized appropriately for the elevator cab size. All Cars
T. Communication System: Judges and Passenger Car Only
1. “Push to Call,” two-way communication instrument in car with automatic dialing, tracking, and recall features with shielded wiring to car controller in machine room.
Provide dialer with automatic rollover capability with minimum two numbers.
a. “Push to Call” button or adjacent light jewel shall illuminate and flash when call is acknowledged. Button shall match car operating panel pushbutton design.
Provide uppercase “PUSH TO CALL” “HELP ON THE WAY” engraved signage adjacent to button.
b. Provide “Push to Call” button tactile symbol, engraved signage, and Braille adjacent to button mounted integral with car front return panel.
2. Provide emergency phone line operability detection system with audible tone and visual signal as required by code. Locate in most cost effective location.
3. PROGRAM PHONE PER THE DIRECTION OF THE PURCHASER. ALL CARS.
2.08 CAR ENCLOSURE : JUDGE AND PRISONER CAR ONLY
A. Car Enclosure: Provide complete as specified herein. Provide the following features.
1. Shell: Retain existing.
2. Canopy: Retain existing.
3. Front Return Panels, Transom, Strike Jamb, Entrance Columns: Re-clad in satin stainless and provide cutouts for signal and car operating fixtures. Delaminate surfaces as needed to ensure proper adhesion of new cladding and proper clearance and fitment.
4. Base: Provide New Stainless steel with concealed ventilation cutouts.
14250 - 16 Volusia County / S James Foxman Justice Center
5. Interior Side Wall Finish: Provide new flat laminate. Wilsonart® HD® with Antimicrobial Protection and Enhanced Scratch & Scuff-Resistant AEON™ Technology. Color to be approved by Facility. All material to be treated to meet Flame Spread and Smoke Density code requirements. Judges Car
6. Interior Walls Rear and Sides : 316 Stainless Steel Textured Panels. Prisoner Car
7. Lighting: Provide LED fixtures with wiring and hookup. Lighting shall shut off after adjustable period (60 – 180 seconds) of no elevator demand. Lighting shall achieve code compliant foot candles and be protected from breakage. Judges and Prisoner Car
8. Suspended Ceiling: 316 Stainless Steel Drop Ceiling. Each section to contain an individual light fixture. Each section to contain an individual light fixture. Each fixture to contain a black trim bezel and Eye Beam LED bulbs to comply with code. Edge to be painted black to match ceiling reveals. Included is a low voltage driver unit to be mounted on car top. Emergency escape hatch shall be incorporated into ceiling based on existing location of escape hatch in elevator canopy and shall have hairline joints in ceiling finish. Edge of ceiling to be held approximately 1” from transom & centered between side walls. Judges and Prisoner Car
9. Handrails: Minimum 1-1/4" diameter stainless steel flat grab bar with returned ends across rear and side walls. Provide standoffs with threaded set pins. Judges and Prisoner Car
10. Flooring: Remove existing flooring taking all measures to prevent damage to existing subflooring. Furnish and install rubber coin style sheet flooring. Prisoner Car Furnish and install equivalent type flooring. Judges Car Color to be approved by Facility.
B. Elevator Contractor to provide all door adjustment for proper clearances. All Cars
2.09 HALL CONTROL STATIONS ALL CARS
A. Approved Provider: Innovation Industries
B. Provide 1 riser with surface mounted faceplate. Include pushbuttons for each direction of travel which illuminate to indicate call registration.
1. Provide Satin Stainless Innovation Fixture with Blue PB35 Buttons.
2. Fixture must cover existing fixture hole and be constructed out of 316 #4 stainless steel.
3. Note : Passenger #1 and #2 Lobby fixture color matched to existing lobby entrances.
C. Provide all applicable Fire Recall, Emergency Phone Line Monitoring Device and Emergency Signage integral with Lobby Fixture.
1. Emergency Use Exist Stair Flame shall be directly above pushbuttons to separate pushbuttons from the rest of the code mandated features and functions.E
2. Elevator access key switch to be located in terminal fixtures.
2.10 SIGNALS
A. Car Direction Lantern: Provide flush-mounted digital car lantern in existing fixture locations.
Illuminate BLUE up or down digital lights and sound electronic tone once for up and twice for down direction travel as doors open. Sound tone once for up direction and twice for down direction. Sound level shall be adjustable from 0 - 80 dBA measured at 5'-0" in front of hall control station and 3'-0" off floor. Provide adjustable car door dwell time to comply with ADA requirements relative to hall call notification time. Fixture must be vandal resistant. Judge and Prisoner Cars Only
14250 - 17 Volusia County / S James Foxman Justice Center
B. Car Position Indicator: Alpha-numeric digital indicator containing floor designations and direction arrows a minimum of 2" high to indicate floor served and direction of car travel.
Locate fixture in car operating panel. When a car leaves or passes a floor, illuminate indication representing position of car in hoistway. Illuminate proper direction arrow to indicate direction of travel. Illumination should be blue. Judge and Prisoner Cars Only
C. Faceplate Material and Finish: #4 Stainless Steel, 316 grade. Judge and Prisoner Car Only
D. Provide electronic device with easily reprogrammable message and male voice to announce car direction, floor, emergency exiting instructions, etc. Judge and Prisoner Car Only
E. Contractor to coordinate installation, wiring and testing of card readers as applicable.
PART 3 EXECUTION
3.01 SITE CONDITION INSPECTION
A. Prior to beginning installation of equipment, examine hoistway and machine room areas.
Verify no irregularities exist which affect execution of work specified.
B. Do not proceed with installation until work in place conforms to project requirements.
3.02 PRODUCT DELIVERY, STORAGE, AND HANDLING
A. Deliver material in Contractor’s original, unopened protective packaging.
B. Store material in original protective packaging. Prevent soiling, physical damage, or moisture damage.
C. Protect equipment and exposed finishes from damage and stains during transportation, erection, and construction.
3.03 INSTALLATION
A. Install all equipment in…