EXHIBIT D FY26 1 Appendix A - Const Specs - Production Offices FINAL 2025-10-27.pdf
PDF 10 MB Posted
- Attached to
- Military Recruiting Lease for office space 5, 300 to 5, 800 SF required Federal contract opportunity
- Solicitation number
- DACA455270014200
About this file
This is a Construction & Security Specifications document for Military Recruiting Facilities Production Offices (Leased Premises). It serves as Exhibit D, Appendix A to a government lease agreement and establishes detailed requirements for constructing and outfitting military recruiting offices.
The document mandates that lessors provide shell components and build-out services including HVAC systems designed to ASHRAE Standard 62.1 with temperature control (70-76°F), mechanical/electrical/plumbing systems fully enclosed within walls, and commissioning verification prior to occupancy. All construction must comply with federal, state, and local building codes, with the most stringent standard applying when conflicts arise. Lessor deliverables include architectural/engineering (AE) drawings in PDF and DWG formats, all permits, Certificate of Occupancy, and a commissioning plan submitted 60 days before space acceptance. The specifications require specific mechanical systems (VAV boxes, MERV 8+ filters, programmable thermostats), potable water supply with hot water at 105°F, and restroom facilities (one unisex or two facilities for six or more recruiters). Electrical requirements include 20-amp minimum circuits, quadplex outlets at 8-foot spacing in offices, LED lighting at 50+ foot-candles, and emergency lighting with 1-hour battery backup. Communications infrastructure includes color-coded CAT 6 wiring (blue for military services voice/data, yellow for entry control, red for CCTV, gray for roller shades), dedicated communication cabinets per military service, and security/communications boards within secure closets. All exterior windows and doors require laminated glass or fragment retention film (3M Safety & Security Film), and exterior doors must have Grade 1 hardware with concealed hinge pins. Interior doors are flush panel solid core wood with red chestnut stain and polyurethane finish. Finishes include Level 5 drywall throughout, suspended 2'x4' acoustical ceiling tiles (NRC .65+), porcelain tile in entries/hallways/restrooms with non-slip surfaces, and paint schedules specifying Sherwin Williams colors (Worldly Gray SW 7043 for common areas and restrooms). The document explicitly prohibits equipment from People's Republic of China, Huawei Technologies, ZTE Corporation, Hytera Communications, Hikvision, or Dahua Technology per 2019 N.D.A.A. requirements, with written certification required pre-installation and re-certification upon acceptance. The contractor must notify the Corps of Engineers representative at least five working days before commencing work, and no construction shall begin without official Notice to Proceed (NTP).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| EXHIBIT A USACE RERUITING FORM L100.pdf | ||
| EXHIBIT E SAMPLE FLOOR PLAN.pdf | ||
| EXHIBIT I Recruiting Agency Agreement - Authorization for Property Manager to act on behalf of Owner FINAL 2020-10-16.pdf | ||
| EXHIBIT B General Clauses.pdf | ||
| EXHIBIT C Rental Proposal Worksheet 10.23.2023.pdf | ||
| EXHIBIT F FY26 1 Construction Specifications Bid Proposal Worksheet FINAL 2022-10-19.xlsx | XLSX spreadsheet | |
| EXHIBIT H Certificate of Authorization Corporate-LLC-Partnership FINAL 2020-10-16.pdf | ||
| TAOC Recruiting Request for Lease Proposal Template R100 FINAL 2020-10-16.pdf | ||
| EXHIBIT G FY26 1 Appendix D - Janitorial Service Guidance All Facilities --FINAL-- 2023-11-15.pdf | ||
| EXHIBIT G FY26 1 Appendix D - Janitorial_Checklist --FINAL-- 2023-11-15.xlsx | XLSX spreadsheet | |
| EXHIBIT J Seismic Offer Forms A - F.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 1 of 85
CONSTRUCTION & SECURITY SPECIFICATIONS
Military Recruiting Facilities ~ Production Offices
(CPP’s ~APPENDIX “A”)
VERSION: FY 26.1
(Leased Premises Address)
(Date / Revised Date)
GENERAL STANDARDS (GS)
A. General Guidance:
Each designated Military Service to be located at this recruiting facility will have their specific standards included in the following General Standards (GS), enclosures and attachments. Any significant departure from either the intent of these construction specifications or the approved Chief Architect floor plan will require prior approval of the Corps of Engineers (COE); Representative / P.O.C.:___________________ phone #:_______________, email:________________________.
IMPORTANT: NOTHING IN THESE SPECIFICATIONS WILL PROHIBIT THE SUBSTITUTION,
WITH PRIOR APPROVAL OF THE COE, OF AN EQUIVALENT PRODUCT, SERVICE OR FINISH
(TO INCLUDE ALL LICENSING, SOFTWARE, HARDWARE PARTS, COMPONENTS, ETC.
MEETING THE SPECIFIED REQUIREMENTS HEREIN). LESSOR / CONTRACTOR(S) TO
PROVIDE WRITTEN CERTIFICATION OF EQUIVALENCY TO COE REPRESENTATIVE PRIOR
TO APPROVAL / INSTALLATION.
REQUIRED BY LAW: For all supplied communication requirements and electronic security applications (see paragraph K below), the Lessor (or their contractors) are PROHIBITED (2019 N.D.A.A. law and any subsequent modifications) from providing to the Government any such equipment or services as a substantial or essential component, or critical technology as part of any system. These PROHIBITED security / telecommunications products are from any of the following source entities, any subsidiary or affiliate of such source entities: 1) The
People’s Republic of China; 2) Huawei Technologies Company; 3) ZTE Corporation; 4) Hytera Communications
Corporation, Hangzhou Hikvision Digital Technology Company; 5) or Dahua Technology Company. Lessor (or contractors) must certify the equipment is not from any of these sources and provide written confirmation to the COE Representative prior to installation. Upon acceptance of the premises, the Lessor or Contractor must re-certify in writing what equipment has been installed, and that all components comply with the 2019
N.D.A.A. requirements.
1. Drawings, Plans and Permits: The Lessor is responsible for all permits (including low voltage), drawings, constructing, operating, maintaining, and obtaining a Certificate of Occupancy for the leased premises in accordance with the lease / solicitation requirements. Any changes on the build out of the leased premises should be addressed directly to the COE representative. The recruiters for the subject office(s) are NOT authorized to change or modify anything related to the construction of the office.
The attached conceptual drawing / Chief Architect floor plan provided by the COE representative will be used for design, planning, and bid purposes.
a. Required Lessor deliverables for Architectural / Engineering (AE) drawings:
1. The Lessor is responsible for coordinating with the COE in the development of these plans.
2. Lessor’s AE drawings must be created and provided to COE representative prior to scheduling the pre-construction “kickoff” meeting.
3. COE representative to review and approve all Lessor provided AE drawings prior to starting construction activities or premises alterations. No construction shall start until the COE representative provides an official Notice to Proceed (NTP) for construction.
4. IMPORTANT: Conceptual drawings / floor plans and/or AE drawings in draft or final form shall
NOT be posted online or provided to third parties for security reasons.
5. AE Drawing sets to include at a minimum (but not limited to) the following:
i. Architectural cover sheet, site, and parking plan with all measurements / details / abbreviations / symbols.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 2 of 85
ii. Leased premises with all room dimensions to include square foot allocations, wall, door, window, structural columns, key notes, etc.
iii. Mechanical, Electrical and Plumbing (MEP) Engineering Drawings:
• Including low voltage communications / wiring / hardware / and controls.
• Aiphone, CCTV, roller shade controls and security system components.
iv. Interior design drawings for walls, ceilings, and floor finish plan with schedules.
v. Interior / Exterior elevations with graphics and signage details / schedules, etc.
vi. Interior / Exterior door and window hardware schedules and finish details, etc.
vii. IMPORTANT: Once finalized and approved by local municipalities, FINAL AE drawings shall be provided to the COE in the following electronic formats to serve as a basis to resolve any issues of variance which may arise:
• PDF file(s) in 11” x 17” page format.
• Electronic DWG file(s).
2. Codes and Standards: The leased premises must comply with all Federal, State and local construction standards, building codes and all other applicable laws. Any variance must have prior approval by the authority having jurisdiction. Where conflicts between standards arise, the build-out of the recruiting office must comply with the most stringent requirements.
3. Only Energy Star labeled components and natural resource conserving / recyclable products shall be installed.
4. Number of Recruiters: For the purposes of determining the number of restrooms, keys, or desk-tenant stations
(Video Intercom Entry Control – referenced hereafter as “EC”) per Military Service, the following number (#) of recruiters for each Military Service is provided:
Army _______; Navy _______; Air Force _______; Marines _______;
Air Force Reserve _______; Air National Guard _______; Army National Guard ________.
5. Alternate Pricing Integrators: These are different companies that have the Armed Forces Specifications that can be used to purchase components from multiple distributors and product lines for potential better pricing.
• Wesco – Matt Ridgeway: Matt.Ridgeway@anixter.com
• IML Security Supply – Angi Strrubing: angi.struebing@imlss.com
Mike Donohue: Mike.donohue@imlss.com
• ADI Global – Aaron Waters: governmentsales@adiglobal.com
6. General Notes:
a. These specifications do not preclude common sense considerations / solutions to any issues that may arise during the build-out of the leased premises. Any variation, deviation or departure from this specification must be approved in writing, by the COE Representative listed above.
b. To minimize potential misunderstanding, on-site meetings between the Lessor, Contractor, and COE to be scheduled for pre-bid meetings (if necessary) & kick-off meetings prior to commencement of construction.
c. The contractor is required to notify the COE representative and Lessor at least five (5) working days prior to commencement of work on the site.
B. Mechanical:
1. Plumbing / electrical / HVAC and mechanical service lines / facilities, if located within the leased premises, shall be enclosed within wall cavities. Exposed ducts, piping, wiring, and/or conduit runs are not permitted in the offices or common areas of the leased premises. If there are Lessor / building mechanical rooms / space accessed from within the Government controlled premises, this enclosed space may NOT, under any circumstances, be considered part of the Government leased premises or co-used for any other purposes.
2. Heating, Ventilation and Air Conditioning (HVAC) - Lessor Required SHELL Components
(subparagraphs a thru f):
a. HVAC systems shall be installed and operational, including, as appropriate, main and branch lines, VAV boxes, dampers, flex ducts, and diffusers, for an open office layout, including all building common areas.
The Lessor shall provide conditioned air through medium pressure duct work at a rate of .75 cubic feet per minute per square foot and systems shall be designed with sufficient systems capacity to meet all requirements in this Lease.
b. The HVAC system design shall conform to applicable temperature standards and operating practices (in accordance with ASHRAE Standard 62.1). HVAC system will be balanced to accommodate the mailto:Matt.Ridgeway@anixter.com mailto:angi.struebing@imlss.com mailto:Mike.donohue@imlss.com mailto:governmentsales@adiglobal.com
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 3 of 85 approved floor plan / AE drawing and operational needs of each Military Service. If not otherwise stipulated, the HVAC equipment shall be capable of maintaining a minimum temperature of 70 degrees
Fahrenheit during the heating season and a maximum of 76 degrees Fahrenheit during the cooling season regardless of outside temperature. Areas affected by solar radiation (either excessive heat gain or loss) shall be accounted for by the Lessor within the design of the HVAC system.
c. Ventilation to the leased premises shall be provided in the most energy efficient and cost-effective manner. It will meet or exceed all applicable building code standards and local ordinances.
d. Restrooms & Security Closets: Shall have their own supply and return vents installed for adequate ventilation (minimum of 10 air changes per hour) for appropriate air flow heat dispensation.
e. HVAC Filters: To be placed in ceiling return vents for easy access / replacement by janitorial service staff. Locations to be noted on the A/E drawings. Where practicable, the Lessor is encouraged to use a
MERV 8 (or greater) air filter.
f. For energy efficiency requirements:
1. When required by the State (e.g. - California Title 24) – all 5 ton or greater HVAC units / systems to incorporate:
i. Air-to-Air exchanger / economizer (if not already present).
ii. A “residential” style HVAC system with zoning / dampers to heat or cool specific areas as needed. Avoiding ductless / split HVAC systems if possible.
iii. Smart thermostat in each individual Military Service’s office.
iv. Stand-alone HVAC system: **NO** connection to Government networks, internet, routers, or
WiFi is allowed.
g. The HVAC system, will be designed and provide temperature controlled thermostats in each individual
Military Service office. The contractor will coordinate with the COE on the determination of acceptable thermostat(s). A digital, 7-day programmable, code-protected thermostat shall be utilized. Thermostat’s to be mounted in each individual Military Service “open office” areas.
3. SYSTEMS COMMISSIONING: The Lessor shall incorporate commissioning requirements to verify that the installation and performance of energy consuming systems meet the Government’s requirements. These systems include, at a minimum, heating, ventilating, air conditioning (HVAC) systems and associated controls, lighting controls, and domestic hot water systems. In instances involving minimal improvements including system reconfiguration, recommissioning is required to ensure that the systems are operating properly.
a. The Lessor shall submit a written commissioning plan to the COE representative at least 60 days prior to
Space acceptance. The plan shall include:
1. A schedule of systems commissioning; and
2. A description of how commissioning requirements will be met and confirmed.
b. Results of the system commissioning plan will be provided to the COE representative immediately following the test of the systems.
c. Indoor Air Quality: HVAC flush-out shall commence after construction ends and the leased space has been completely cleaned. All interior finishes, such as millwork, doors, paint, carpet, and acoustic tiles must be installed, and major volatile organic compound (VOC) punch list items must be finished. Prior to occupancy, all supply / return vents to be cleaned and free of construction debris / dust. Lessor shall install new filtration media and perform a building flush-out by supplying outdoor air to flush out
VOC’s.
C. Plumbing:
1. Potable water shall be provided to the leased premises. The Lessor shall verify the existing water supply meets all potable water standards. If deficient, the Lessor will be responsible for providing an acceptable, alternate water supply. The water heating system shall produce and maintain a hot water temperature of 105 degrees for restrooms and the janitorial mop service sink. All water heater systems must be secured from public view / access.
2. Restrooms: At a minimum, a unisex restroom will be provided. Recruiting offices with six (6) or more authorized recruiters shall require two (2) restrooms. Lessor will confirm number of restroom facilities required at this location as _________. Restrooms shall contain, at a minimum, the following plumbing fixtures and approximate square footage:
a. Unisex / Men's: 100 sq. ft., 1 commercial toilet, 1 urinal, 1 sink, stainless steel partitions / urinal screens as required.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 4 of 85
b. Women's (if required): 64 sq. ft., 1 commercial toilet, 1 sink.
c. Restroom Fixtures & Accessories: See para. G.8.
d. If existing, restrooms to be updated with all appropriate paint, tile, fixtures, etc.
3. Drinking Fountain - Water Cooler: The Lessor to install a stainless steel drinking fountain equal to Elkay
EZ Series, EZS8WSSK, non-filtered electric water cooler, with an attached EZH20 bottle filling station.
Location as shown on the approved floor plan / AE drawing.
4. Janitorial Closet: shall contain 1-floor mounted mop sink and service faucet with a hot and cold water supply.
5. Pantry (Wet): See each Military Services attachment for details.
D. Electrical:
1. Electrical Distribution: Each electrical circuit shall be 20 amp rated or greater as defined by the National
Electrical Code (NEC). All power distribution equipment shall be required to handle the actual specified and projected loads with 10 percent spare load capacity. All electrical panels servicing the Government leased premises should be located within the leased premises. When located outside the leased premises (inside or outside the building) the panel(s) must be secured (locked).
a. Outlets, Switches and Faceplates: Installation to be at industry standard height unless otherwise specified.
1. Minimum Requirements: All power outlets in offices, storage / test rooms, and conference rooms
(where applicable) shall be Quadplex’s with a maximum of 8-foot spacing unless otherwise specified. All foyers / hallways and common areas shall have Duplex outlets with a maximum of 16 feet spacing.
2. Installation at desktop or countertop level (as required) will be as specifically referenced on the approved floor plan / AE drawings.
3. These items shall be color coordinated in standard white, unless otherwise specified or referenced differently within each Military Services’ Attachment (for appropriate color variation).
4. Ceiling and floorport outlets may be required in open office areas as identified on the approved floor plan / AE drawing.
b. Specific Electrical Requirements:
1. Restroom Fixtures (paragraph G.8.).
2. Janitorial closet: outlet mounted 42” above finished floor (AFF); as shown on the approved floor plan / AE drawing.
3. Single / dual roller shades (paragraph G.9.a.1).
4. Pantry (Wet or Dry): See each Military Services attachment for details.
c. Communication / Commo Board Cabinets for EACH Military Service & Security Board Cabinet:
See paragraph E and K.1 for more details.
1. Quadplex outlets to be flush mounted on the fire-retardant treated plywood backboard(s), and installed at the back of each 12U Cabinet at the lower left corner, as shown on ENCLOSURE
#1c and 1d.
2. Isolated copper grounding plate on each Commo / Security Board(s) connected to a green #6 ground wire will be attached to the building ground or grounding rod in accordance with code standards. An equivalent standard for isolated electrical ground installation is acceptable.
d. Conference / Multi-Purpose Rooms (if present): Power outlets as shown on the approved floor plan
/ AE drawing to include one (1) recessed Legrand RFB4 floor box with brushed aluminum finish
FloorPort Activation Covers. Configured with two (2) electrical duplex outlets, two (2) BLUE voice
/ data port jack outlets, one (1) HDMI female port, and with HDMI wire run to the non-CCTV television (TV) / monitor mounting pole (in the room). Floor box location to be confirmed with
COE representative.
e. Required wiring / data port jack colors: All data port jacks and straight-through (T568B) CAT 6 wiring shall be color coordinated, and labeled. All wiring shall be contained in appropriate conduit in walls and the ceiling interstitial / plenum space to be arranged in a tight compact arrangement / appearance in raceways.
1. Military Services Comms (Voice & Data):
i. Two (2) CAT 6 wiring & data port jacks color = BLUE.
2. EC Systems (paragraph K.3):
i. CAT 6 wiring & data port jack color = YELLOW.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 5 of 85
3. CCTV / NVR systems (paragraph K.4) & Mounted TV / Monitors (paragraph D.4):
i. CAT 6 wiring & data port jack color = RED.
4. Roller Shades (single or dual):
i. CAT 6 wiring = GRAY.
2. Interior Lighting: UL listed light fixtures shall be capable of producing and maintaining a uniform lighting level of a minimum of 50 foot-candles of illumination at working surface height in all office spaces. All other non-working areas will have a minimum of 30 foot-candles of illumination at floor level.
a. LED: Lighting in all office, hallways, display areas and test rooms will be a minimum of 2 x 4 flat panel, 4300 lumens, 4000k temperature, dimmable, energy efficient, LED light fixtures, with a minimum lifespan of 60,000 hours. In restrooms, mechanical rooms, security closets, janitorial closets and other smaller areas may require fixtures, similar 2x2 energy efficient, recessed LED fixtures will be provided.
Note: If existing light fixtures differ from those specified, the Lessor will consult with the COE on their acceptability. If existing fixtures are used, LED ballast bypass lamps to be installed. Interior office spaces and test rooms to have wall mounted on-off switch with full range dimmers. All other areas to use standard commercial grade switches without dimmers.
b. Emergency Lighting: Shall be built into the LED ceiling light fixtures, with an emergency driver component in order to maintain illumination throughout the means of egress. Light fixtures with emergency drivers are to be hardwired to maintain an adequate charge on battery pack to provide at least
1-½ hours of power to light as per NFPA 101. Each fixture to have a “test light indicator” (LED Combo
Test Switch – (LCTS)) installed next to the fixture. The LCTS light color is preferred to be green
(indicating the light and battery backup is in good working order). LCTS cover shall be white to match ceiling tiles.
3. Exterior Lighting:
a. The Lessor will ensure building egress doors and designated government parking areas use energy efficient lighting with a minimum illumination of 5 foot-candles / square foot at ground level (or as required to adequately support CCTV operations).
b. Front entrances: Where possible, install overhead recessed and/or flush lighting fixture located directly above facility front entrance (exterior) door(s).
c. Secondary Egress: If not already present, an exterior security light shall be installed by the Lessor.
Light fixture to be LED, equivalent to 150 watts or greater, with ‘dusk-to-dawn’ light sensor with manual override.
4. Mounted Monitors:
a. CCTV Monitors: See CCTV system specifications in paragraph K.4.
b. Service Specific Use / Non-CCTV Monitors (conference rooms, open area offices, etc.): Duplex power, and communications outlet boxes (with BLUE CAT 6 wire) to be installed and concealed above ceiling tiles directly above Monitor mounting location as indicated on the approved floor plan / AE drawing, with CAT 6 routed to the Military Service’s Commo Board / Cabinet. Mounting height to be 8’-6” AFF for top edge of Monitor. See paragraph K.4 notes for more details regarding Monitor mounting pole requirements.
E. Communications:
1. Outlets, Switches and Faceplates: See “Electrical” paragraph D.
2. Security Closet:
a. Security Board: Within the Security Closet, Lessor to wall mount a ¾” thick, 4’-0” W x 8’-0” H fire-retardant treated plywood backboard, at 2’-0” AFF (top edge of backboard to be trimmed 6” below drop ceiling if necessary). The security board location must have 36” of front clearance to facilitate access. See paragraph D for electrical requirements, and paragraph K.1 and ENCLOSURE #1c for Security Board diagram requirements / layout.
b. Communications Board / Commo Board: Within the Security Closet, Lessor to wall mount a ¾” thick, 4’ to 8’ W x 8’-0” H fire-retardant treated plywood backboard, at 2’-0” AFF (top edge of backboard to be trimmed 6” below drop ceiling if necessary). The Comm Board location must have 36” of front clearance to facilitate access. See paragraph D. for electrical requirements and an overall layout as shown on
ENCLOSURE #1a and 1d.
1. A wall mounted Comms cabinet (Tripp Lite Model #SRW12UDP) to be installed as a dedicated comms cabinet for each Military Service.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 6 of 85
2. Lower row of comms cabinet (s) to be mounted directly on the Commo Board. Top of cabinet to be at 48” AFF with 12” of clearance between cabinets on all sides (horizontal and vertical) for airflow.
3. Upper row of Comms Cabinet (s) to be aligned and mounted with bottom of cabinet at 60” AFF.
4. Comm Cabinets to be uniquely keyed with each Service(s) receiving 3 keys.
3. Demarc Requirements: The building demarcation point provided by the Lessor must be secured from public access.
a. If required, mitigation to secure the demarcation point shall be coordinated with the COE.
b. Appropriately sized communications conduit to be installed from the building demarc point to the
Military Service(s) Commo Board. Two (2) pull strings are required for each Military Service, and used by their respective communications provider. See ENCLOSURE #1a and 1b.
4. Low Voltage / Communications (See ENCLOSURE #1a, 1b, 1c and 1d for a diagram of requirements / layout):
a. Outlets / Wiring: These voice / data port outlets will be vertically aligned and installed within 2” horizontally on each office space electrical outlet, so the tops of both outlets measure to the same height
AFF, or as identified on the approved floor plan. Required 1” conduit terminating 12” above finished wall height. See Paragraph A.1. Permits.
1. Security and Communications Cabinet wiring requirements:
i. Each Military Service will have straight-through BLUE data CAT 6 wires from their
Communications Cabinet into their office space.
ii. Ceiling access points (BLUE data CAT 6 wires) to be covered with a blank standard white faceplate.
iii. The Security Cabinet will have yellow data CAT 6 wires into each Military Service’s office space for the Aiphone desk-tenant stations.
• Aiphone Desk-Tenant Station Outlets: Routed from the Security Cabinet PoE+ Switch(s) to designated wall location. These straight through CAT 6 yellow wire(s) labeled on both ends with a female RJ45 cover plate at the wall location.
• With an 8’ yellow patch wire from wall outlet to the desk-tenant station.
iv. Each labeled wall plate (destination end) shall be equipped with a three (3) port female RJ45 plate. All data port jacks, and straight-through CAT 6 wire (T568B) will be color coordinated and labeled with identification number at both ends. Two BLUE data port jacks & BLUE wires will be routed to the Commo Board and one yellow data port jack & yellow wire routed to the Security Board PoE+ Switch(s).
v. The RJ45 connector can then be connected to a modem, router, switch, adaptive security appliance, etc., which may be installed by the Military Service’s telecom provider.
vi. All Communications faceplates will be color coordinated with the electrical faceplates. See each Military Service Attachment for specific color requirements for faceplates.
vii. Required wiring / data port jack colors: All data port jacks and straight-through (T568B)
CAT 6 wiring shall be color coordinated and labeled. All wiring shall be contained in appropriate conduit in walls and the ceiling interstitial / plenum space to be arranged in a tight compact arrangement / appearance in raceways.
• Military Services Comms (Voice & Data):
a. Two (2) CAT 6 wiring & data port jacks color = BLUE.
• EC Systems (paragraph K.3):
a. CAT 6 wiring & data port jack color = YELLOW.
• CCTV / NVR systems (paragraph K.4) & Mounted TV / monitors (paragraph D.4):
a. CAT 6 wiring & data port jack color = RED.
• Roller Shades (single or dual):
a. CAT 6 wiring = GRAY.
viii. All wiring for Commo / Security Board Cabinets components shall be color coordinated, labeled with Military Service and Port Identification numbers at both ends, have a minimum of three (3) feet of slack, contained in a horizontal or vertical organizer / enclosure (similar to
Legrand Model #SHMC2RU) and in an organized manner. All wires shall be labeled referencing port numbers and Military Service as follows:
• Air Force = “USAF”.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 7 of 85
• Air Force Reserve = “AFR”.
• Army = “USA”.
• Navy = “USN”.
• Marine Corps = “USMC”.
• Air National Guard = “ANG”.
• Army National Guard = “ARNG”.
b. Conduit / Raceways: Conduit capable of handling all data wires, access sized to fit ALL Military
Services requirements (minimum of 1” conduit for two (2) Military Services at a location), as follows:
1. Building Demarcation point to each Military Service commo board, with two (2) pull strings per Military Service along with necessary junction box(s) for easy access. See paragraph E.3.
2. Voice and data wall / ceiling / floor outlet box conduit runs to the commo board shall terminate 12” above finished wall height. Note: See paragraphs D & K.
3. Wiring above ceiling (interstitial / plenum space) shall be contained in a raceway, if not installed in conduit.
c. Military Services Responsibilities & Equipment: Military Services are responsible for all other remaining communications requirements (not identified) via their service provider (e.g. – Verizon, AT&T, etc.). The telecom provider will typically install (but not limited to), the following:
1. Any equipment / wiring / terminations required from the building demarcation point and/or junction box to the commo board, including equipment required to install service at the building demarc point and/or at the commo board such as modems, routers, PBX’s, network switches, intermediate distribution frames, main distribution frames, distribution frames of any kind, patch panels, punch blocks, etc.
2. Any patch wires to connect their equipment.
3. All communications services (internet, Wi-Fi, cable TV if applicable (not part of the CCTV system), signal repeaters, etc.).
4. It is each Military Service’s / telecom providers responsibility to coordinate with the Lessor, and to install or contract for all remaining installation requirements.
5. This would include any additional low voltage communications permits as required.
F. Safety and Fire Equipment:
1. The Lessor shall be responsible for any required remediation of the fire protection system for fire code compliance.
2. Exit Signs: Shall be placed at exit ways from each Military Service office and leased premises. Signs shall be hardwired, UL listed, have 6” H lettering with backup batteries which shall provide at least 1-1/2 hours of power to light as per NFPA 101. Mounting: Must be capable of ceiling, wall, or end mounting; either single or double faced as required. The sign must utilize long-life LED lamps and self-diagnostics.
3. One, 10-lb. ABC Dry-Chemical Fire Extinguisher with Semi-Recessed Protective White Cabinet: Shall be installed towards the rear of each Military Service’ office, and in the rear common area. Location of these units will be coordinated with the COE representative. Mounting height of protective cabinet should be 48” to 52” AFF (or as dictated by local building code regulations) with maximum travel distance to fire extinguisher of 75 feet.
4. Dual Sensor Photoelectric / Ionization Smoke and Fire Detector-Alarm: The Lessor shall ensure the location and installation of all smoke detectors are in accordance with manufacturer’s recommendations for coverage area. At a minimum, at least one hardwired, 120-volt smoke detector with lithium battery backup and test function shall be installed, visible in each military recruiting office and common area, The alarm will be UL approved and capable of emitting an audible alarm of at least 85 dB at 10 feet.
5. Fire Dept. Access Lockbox: Where required for rapid emergency access, COE and Lessor shall coordinate to provide access keys to Government leased premises.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 8 of 85
G. Architectural Finishes-Fixtures-Supplies: Ceilings / Walls to be finished according to the following standards for the required Level 5 finish on all visible surfaces:
1. Drywall: Gypsum Association GA-214 Standards.
2. Painting & Decorating Contractors of America (PDCA / PCA) Standard P1.
3. Ceilings: Office ceilings shall be 9 feet or no more than 11 feet, from floor to lowest obstruction. All ceilings shall be installed on a level plane in each room.
a. Existing: It will be the Lessor’s responsibility to consult with the COE on the acceptability of the buildings existing ceiling system. If found acceptable, all ceiling tiles that are damaged, stained or sagging shall be replaced. If matching tiles cannot be found, or if replacement exceeds 50%, then all ceiling tiles shall be replaced and meet the standard for new ceilings.
b. New: A suspended ceiling system with acoustical tile panels shall be installed. It will be a 2’ x 2’ revealed pattern on an exposed 2’ x 4’ grid with 2’ x 4’ ceiling tile (tegular-revealed) panels. The ceiling panels and grid to be white. All panels shall have a noise reduction coefficient (NRC) of not less than
.65 in accordance with ASTM C-423.
c. Restrooms: Ceiling to be ⅝” drywall, taped and sanded, with a Level 5 finish.
4. Walls:
a. Demising Walls, Janitorial and Mechanical Rooms: Walls separating government leased premises from adjacent tenants and the interior walls enclosing janitorial / mechanical facilities will be erected from floor to building understructure. It shall be constructed with 3-⅝” metal studs, 16” o.c., ⅝” Type
“X” drywall, taped and sanded, with a Level 5 finish below finished ceiling line.
1. Demising Wall - Option #1: Steel chain link or expanded metal mesh fence may be substituted for drywall wall sections above the finished ceiling line.
2. Demising Wall - Option #2: Open, 3-⅝”, 25ga. (minimum) studding, 6” o.c., reinforced horizontally @ 24” o.c. maybe used without chain link fence or drywall installation above finished ceiling line.
b. Separation of Individual Military Service Office(s): Walls separating collocated Military Service offices and common areas shall extend from finished floor to 12” above finished ceiling. Construction shall be of 3-⅝” metal studs 16” o.c. with ⅝” drywall, taped and sanded, with a Level 5 finish. See paint schedule for wall colors.
c. Standard Interior Office Partitions: Walls shall extend from finished floor to finished ceiling.
Construction shall be of 3-⅝” metal studs 16” o.c. with ⅝” drywall, taped and sanded, with a Level 5 finish. See paint schedule for wall colors.
d. Soundproofing: Sound attenuating batts with a minimum Sound Transmission Class (STC) of 45, when tested in accordance with ASTM E-336, shall be inserted in all demising and internal walls.
e. Porcelain Wainscot Wall Tile (Restroom): Wall tiles shall be installed per ENCLOSURE #2, including ordering instructions, typical wainscot pattern, including tile, transitions, and grout color designations.
f. Fiberglass Wall Panels (Janitorial Closet): Shall be installed to from floor to ceiling (full-wall-height) on all janitorial closet walls. Panels to be standard white, Class C, Fiberglass Reinforced Plastic (FRP).
Panel performance to comply with ASTM E-84.
g. Accent Walls: Will be as specified on the approved floor plan / AE drawing and as referenced on the specific Military Service paint-finish schedule. Wall mounted fixtures such as thermostats, wall switches, light sensors, emergency lighting etc., should be placed free and clear of all Military Service accent walls.
PAINT SCHEDULE
General Painting Notes:
- See GS paragraph G for requirements, inspect drywall finish prior to painting to ensure a Level 5 finish.
- For individual Military Service requirements, see the specific Military Service Attachment-Paint Schedule.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 9 of 85
COMMON AREA & RESTROOMS PAINT SCHEDULE
Mfr: Color Name: Color #: Product: Coats: Finish: Area:
Sherwin
Williams
PRIMER
ProMar 200
White (see Note 1) B28W02600 2
Latex:
Acrylic Primer
All Walls / All
Painted Trim
Sherwin
Williams Common Area & Restroom Walls
Worldly Gray
SW 7043
Worldly Gray B20W12651 2 Latex: Eg-Shel
Walls (Restroom &
Common Areas)
Sherwin
Williams Common Areas & Restrooms Trim
Worldly Gray
SW 7043
Worldly Gray B31W2651 2 Latex: Semi-Gloss
Trim (Restroom &
Common Areas)
Sherwin
Williams Common Area Chair Rail
Mega Greige
SW 7031
Mega Greige B31W2651 2 Latex: Semi-Gloss
Chair Rail
(Common Areas)
Sherwin
Williams Standard Ceiling Finish
White
Standard White
Ceiling Finish Standard 2 Latex: Eg-Shel
Ceiling
(Restroom)
Note 1: ProMar 200 Primer to be tinted to match the applicable wall color for all walls, and all painted trim.
Note 2: For individual Military Service paint-finish schedule, see specific Military Service Attachment-Paint Schedule.
Note 3: Chair Rail to be: Mega Greige SW 7031.
Note 4: Restrooms to be: Worldly Gray SW 7043.
Note 5: Drywall Ceilings (where applicable) to be: Standard White Ceiling Finish.
Note 6: If selected, contractor should request Sherwin Williams’ colors as listed above for common areas.
Formulas to these colors are available on Sherwin Williams’ National Accounts Database.
5. Flooring - General parameters: All floor areas will be of a common level, finished in a specified material and have a minimum live-load capacity of 50 pounds per square foot.
a. Porcelain Tiles: See ENCLOSURE #2, including ordering instructions, for a typical floor tile pattern, including tile color / name, grout color / name, and tile transition designations. See specific Military
Service Attachment for their requirement.
1. Entry Tiles for Separate or Shared Entrances (Lobby / Front / Rear Exterior Exits as necessary):
Porcelain tile with unpolished, non-slip surface shall be installed at the interior side of exterior / exit entrance doors for recruiting offices located in a 4-season climate zone. Military Service facility front entrance areas shall have tile to be centered on the width of the door opening plus a foot on each side, with a minimum of approximately 4’ L x 5’ W, see the approved floor plan / AE drawings where applicable.
2. Common Hallway / Corridor / Security Closets and Restroom Areas: Porcelain tile with unpolished, non-slip surface shall be installed in the hallways, corridors, security closets, and restroom area floors.
b. Storage areas: Vinyl Composition Tile (VCT) with base cove shall be installed in storage areas. Note:
See specific Military Service Attachment for requirements.
c. Base Cove (for VCT & Carpet only): Note: See specific Military Service Attachment for requirements.
d. Janitorial-Mechanical room(s): Exposed concrete with non-slip floor sealer.
Base Cove: Johnsonite / Tarkett (https://distributor.tarkett.com), Rubber; Color: #40, Black, 4” H.
e. Carpet Schedule by Military Service (Office, test room and related areas): For individual Military
Service requirements, see the specific Military Service Attachment’s Carpet Schedule.
6. Windows:
a. Exterior: Windows shall be weather tight and if operable, shall be equipped with lock assemblies.
Window unit(s) that cannot be secured must be replaced.
1. Existing Laminated Glass - IMPORTANT: Lessor will confirm that all glass meets the following minimum requirements. A nominal ¼” thick laminated glass pane fabricated from two pieces of nominal ⅛” thick glass bonded together with a minimum 0.030” polyvinyl butyral (PVB) interlayer.
If the window contains an insulating glass unit (IGU), the innermost lite must be the laminated glass noted above and the outer lite may be monolithic glass. If the Lessor is unable to provide written confirmation that the existing glass meets this requirement, then glass fragment retention film must be installed as indicated below. With written confirmation from the Lessor / contractor stating laminated glass is present (on ALL windows / doors that are on the perimeter of the Government’s
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 10 of 85 leased premises, regardless of the window being to the outside air or a shared common space with other tenants) and meets the required standards above, fragment retention film is not required.
2. Glass Fragment Retention Film: IMPORTANT: Without written confirmation of laminated glass installed, all glass in exterior windows and doors shall have fragment retention film applied to the interior (room) side in accordance with manufacturer's instructions by a certified installer. Fragment retention film can be either optically clear or, if approved by Lessor, with a light gray tint or a reflective surface. Film shall be 3M Safety & Security Window Film, series type Ultra S800 or Ultra
Prestige S50. Film may be substituted that meets or exceeds the specified films (along with manufacturer’s structural silicone adhesive anchoring systems) , with prior approval of COE. Film shall be attached to the interior frame on all four (4) sides using an anchoring system in accordance with the manufacturer’s instructions. The anchoring system shall use the 3M Impact Protection
Adhesive structural silicone adhesive. Under NO circumstances are standard sealant or caulk compounds to be utilized for adhesive anchoring of the film . Note: The structural silicone adhesive color shall complement existing framing system. The adhesive shall be applied only after the window has been masked with 1” blue “safe release tape” applied to both film and window frame to assure a clean, gasket-like appearance when tape is removed. For ‘wooden window / door frame systems’, an anchoring system need not be applied to glass fragment retention film edges (daylight application). If selected, for installation, government pricing-expedited delivery is available from;
Window Film Depot, P.O.C. Jeff Franson, 866-933-3456; email: jeff@windowfilmdepot.com.
3. Mini-Blinds: NOT TO BE INSTALLED ON ANY EXTERIOR WINDOWS OR DOORS.
4. Roller Shades: See Para. G.9.a.1. (below).
5. Perforated Window Wraps: See Para. G.9.b.
b. Interior:
1. Windows: A 3’-0” H x 4’-0” W fixed, glass window set in metal frame shall be installed in interior walls of hallways and recruiter-in-charge office(s). Top of window frames to align with top of door frames. Note: Ganged windows along hallways are acceptable. These windows shall meet all safety code requirements and be equipped with mini-blinds that meet standards referenced below.
2. Window Frames: Interior window frames to match style and color of door frames (Timely manufactured steel Classic S-Series) with factory applied Alumatone finish (not painted). With ¼” tempered glass and ½” glass stop (TA-14 in Alumatone finish).
3. Test Room(s): Except for the Marine Corps, test rooms shall have an individual window(s) as indicated on the approved floor plan / AE drawing. Mini-blinds are not to be installed for these windows or doors.
4. Mini-Blinds (interior windows / doors only, except test rooms): All interior windows and glass doors (except test rooms) shall be equipped with mini-blinds having non-corroding mechanisms and synthetic tapes. Each window shall have its own individual mini-blind. Mini-blinds shall be Hunter
Douglas Riviera Commercial Aluminum Horizontal Blinds (cordless), Color: Brushed Aluminum #
G8-034, with 1” wide aluminum horizontal slat with beveled steel profile or approved equal. Test and Interview room windows DO NOT have mini-blinds. Note: To prevent swaying, mini-blinds that are installed on interior doors must be secured at the bottom of the door with metal clips.
7. Doors:
a. Exterior – Main Entrance(s): Lessor Shell Requirements / Exterior Door Health Survey: Exterior door openings to the Government controlled space shall be surveyed to ensure a healthy, weather tight and fully functional door unit (door, frame, glass, and hardware). Door opening / swing to be outswing only, fail secure with Grade 1 hardware and no mail slots allowed. Existing mail slots in exterior doors shall be removed. Survey / coordinate hardware requirements on existing doors / frames to be re-used.
Clean, repair or replace as necessary - advise COE representative if existing door / hardware needs to be replaced. All exterior door hinge pins (exposed to the outside exterior of the office premises) will be secured / replaced with concealed / non-removable pins.
1. Fragment Retention Film: The Lessor will confirm and provide written confirmation that the existing glass in exterior glass doors meets the minimum laminated glass requirements identified in
Para. G.6.a above or fragment retention film must be installed.
2. Secondary Egress Doors: Steel doors and frames are required unless building aesthetics / standards only allow glass / other door types.
mailto:jeff@windowfilmdepot.com
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 11 of 85
b. Interior Doors: Shall be a flush panel solid core wood door with maple veneer and Grade 2 hardware or better.
1. Frames / Glass / Finish:
i. Interior door and window frames to be Timely manufactured steel Classic S-Series (445) frames with factory applied Alumatone finish (not painted).
ii. Door color to be stained MinWax, Red Chestnut #232 (on all sides) with two (2) coats of polyurethane matte finish to be applied to stained areas.
iii. Doors requiring a full length glass inset (low profile lite kit [24” x 60”] with ¼” tempered glass), shall color match the Timely manufactured steel frames (factory applied Alumatone color SC108) or brushed stainless steel finish.
c. The following door opening hardware schedule and specifications shall apply: A Certified
Integrator / Installer per manufacturer is required for extended warranty periods and trouble-free installations for Aiphone, Hanwha (Certified Video Professional / Wisenet Certified Professional
(WCP)), ASSA ABLOY, and most other listed equipment manufacturers.
Door Openings (Doors / Hardware) Schedule & Specifications
EXTERIOR:
Application: Model / Skew #’s: Description: Size: Finish: Qty: Set Codes: Notes:
Primary Entrance Door
Single Aluminum:
N/A
Building Standard w/Glass Door 1-¾” x 36” x
84” Match Building
Standard N/A E1, E2 Notes 1, 3 and 4
Primary Entrance Door
Double Aluminum:
N/A
Building Standard w/Glass Door 1-¾” x 36” x
84” (Ea)
Match Building
Standard N/A E8 Notes 1, 3 and 4
Secondary Egress Single
Door(s):
N/A Hollow Metal Core
1-¾” x 36” x 84”
See Paint Schedule
N/A E3, E4 Notes 1, 3 and 4
Secondary Egress Double
Door(s):
N/A Hollow Metal Core
1-¾” x 36” x
84” (Ea)
See Paint
Schedule N/A
Similar to:
E8, E9 or E10 Notes 1, 3 and 4
Adjust as needed.
INTERIOR:
Application: Model / Skew #’s: Description: Size: Finish: Qty: Set Codes: Notes:
Military entrance / egress, commander’s office, conference / multi-purpose room, test / interview
N/A Wood Door w-Full Length
Glass Inset 1-¾” x 36” x
80” See Notes N/A
I1, I2, I3, I4, and I5, Notes 2, 3, and 4
General Door (service to internal common area, restroom, storage, janitorial, mechanical)
N/A Wood Door 1-¾” x 36” x
80” See Notes N/A
I6, I8, I9, and I10 Notes 2, 3, and 4
Security Closet Door N/A Wood Door (Options):
Solid ~ Louvered Inset ~ Pocket Door
1-¾” x 36” x
80” See Notes N/A
I7a, I7b, and I7c Notes 2, 3, and 4
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 12 of 85
HARDWARE SET DESCRIPTIONS:
EXTERIOR:
Application: Model / Skew #’s: Description: Size: Finish: Qty: Set Codes: Notes:
Single Aluminum
Exterior Door
8801EL36-24 Adams Rite - Rim Exit Device 2-5/8” x 36” Satin Aluminum 1
E1
55-56-PE8504F
NEL (at stiles less than 4.5”)
55-56-PE8804F
WEL (at stiles
4.5” or more)
Sargent – Rim Exit Device with Motorized Latch
Retraction
Nightlatch, key retracts latch.
Select model by verifying stile width.
36” wide
Other widths available.
Satin Stainless
Steel
PE80 for secondary egress w/ keypad
A620-626 Yale – Cylinder Housing &
Interchangeable Core (7-Pin) N/A Satin Chrome 1
MS4043-00-130 Adams Rite - Guard Ring N/A Clear Anodized 1
4612-1 Adams Rite - Power Transfer N/A Chrome 1
BF158-630 Rockwood - Door Pull 1” x 12” Satin SS 1 Match Existing building color
3531-689 Yale - Automatic Door Closer 2-1/8” x 12” Aluminum 1
BLP-210
(outswing)
DON-JO - Security Latch
Guard (Anti-Pry Plate) 10” x 3.25” (outswing)
Match Existing 1
Conform to existing door configuration (e.g., offset, door handle, etc.)
DPS-M-GY
Securitron - Door Position
Switch (Magnetic) ¾” Gray 1
Only required for shared / common area egress doors.
IXG-DM7-
HIDA
Aiphone - IXG System
Door-Entrance Station
13-11/16” H x 7-3/16” W x 2” D
SS 1
(with mounting bracket)
SBX-IXGDM7
Aiphone - Surface Mount
Box, Includes Rain Hood
13-3/4” H x
7-5/16” W x
3-1/16” D
SS 1
DK-26
Securitron - Keypad with
CPU Board/Controller
1-1/2” W x
7” H x 7/8”
D
SS 1
Optional Rear
Egress Only w/o
Public Access
FPO250-
C8D8E2
LSP - Power Supply
(hardwired on security board) 12” W x 14” H x 4.5” D
Black 1 8 Door / 8 Lock, 20A, 12VDC
Single Aluminum
Exterior Door
Emergency Egress
ONLY. No door pull.
* - NOT the standard
Secondary Egress.
PE8510F (at stiles less than
4.5”)
PE8810F (at stiles 4.5” or more)
Sargent – Rim Exit Device
Exit only no outside trim or key override
Select model by verifying stile width.
36” wide Other widths available.
Satin Stainless
Steel
E2
If exterior inswing door consult with
COE.
A620-626 Yale – Cylinder Housing &
Interchangeable Core N/A Satin Chrome 1
MS4043-00-130 Adams Rite - Guard Ring N/A Clear Anodized 1
3531-689 Yale - Automatic Door
Closer 2-1/8” x 12” Aluminum 1
BLP-210
(outswing)
DON-JO - Security Latch
Guard (Anti-Pry Plate) 10” x 3.25”
(outswing) Match Existing 1
Conform to existing door configuration
(e.g., offset, door handle, etc.)
DPS-M-GY
Securitron - Door Position
Switch (Magnetic) ¾” Gray 1
Only required for shared / common area egress doors.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 13 of 85
Single Hollow
Metal/Wood Exterior
Door
8701EL36-24 Adams Rite - Rim Exit Device 2-5/8” x 36” Satin Aluminum 1
E3
3701-36 for fire rated doors
55-56-PE8504F
NEL (at stiles
WEL (at stiles
4.5” or more)
Sargent – Rim Exit Device with Motorized Latch
Retraction
Nightlatch, key retracts latch.
Include shim kits as needed for glass moldings.
Select model by verifying stile width.
36” wide Other widths available.
Satin Stainless
Steel
PE80 for secondary egress w/ keypad
A620-626 Yale – Cylinder Housing &
Interchangeable Core N/A Satin Chrome 1
MS4043-00-130 Adams Rite - Guard Ring N/A Clear Anodized 1
4612-1 Adams Rite - Power Transfer N/A Chrome 1
BF158-630 Rockwood - Door Pull 1” x 12” Satin SS 1 Match Existing building color
3531-689 Yale - Automatic Door Closer 2-1/8” x 12” Aluminum 1
BLP-210
(outswing)
DON-JO - Security Latch
Guard (Anti-Pry Plate) 10” x 3.25”
(outswing) Match Existing 1
Conform to existing door configuration
(e.g., offset, door handle, etc.)
DD01-180ULSN
NuK3y - Peephole (220º
Viewing Angle)
1-1/16” x
1-3/8” ~ 2-
1/4”
Satin Nickel 1 9/16” Hole
Install height @
5'-0" AFF
DPS-M-GY
Securitron - Door Position
Switch METAL (Magnetic) ¾” Gray 1
DPS-W-GY for
Wood Doors. Only required for shared / common area egress doors.
IXG-DM7-HIDA
Aiphone - IXG System
Door-Entrance Station
13-11/16” H x 7-3/16” W x 2” D
SS 1
(with mounting bracket)
SBX-IXGDM7
Aiphone - Surface Mount
Box, Includes Rain Hood
13-3/4” H x
7-5/16” W x 3-1/16” D
SS 1
DK-26
Securitron - Keypad with
CPU Board/Controller
1-1/2” W x
7” H x 7/8”
D
SS 1
Optional Rear
Egress Only w/o
Public Access
FPO250-C8D8E2
LSP - Power Supply
(hardwired on security board) 12” W x 14” H x 4.5” D
Black 1 8 Door / 8 Lock, 20A, 12VDC
Single Hollow
Metal/Wood Exterior
Door Emergency Egress
ONLY. No door pull.
* - NOT the standard
Secondary Egress.
PE8510F (at stiles less than
4.5”)
PE8810F (at stiles
4.5” or more)
Sargent – Rim Exit Device
Exit only no outside trim or key override.
Include shim kits as needed for glass moldings.
Select model by verifying stile width.
36” wide Other widths available
Satin Aluminum 1
E4
A620-626 Yale – Cylinder Housing &
Interchangeable Core N/A Satin Chrome 1
MS4043-00-130 Adams Rite - Guard Ring N/A Clear Anodized 1
3531-689 Yale - Automatic Door Closer 2-1/8” x 12” Aluminum 1
DD01-180ULSN
NuK3y - Peephole (220º
Viewing Angle)
1-1/16” x
1-3/8” ~ 2- 1/4”
Satin Nickel 1 9/16” Hole
Install height @
5'-0" AFF
BLP-210
(outswing)
DON-JO - Security Latch
Guard (Anti-Pry Plate) 10” x 3.25”
(outswing) Match Existing 1
Conform to existing door configuration
(e.g., offset, door handle, etc.)
DPS-M-GY
Securitron - Door Position
Switch METAL (Magnetic) ¾” Gray 1
DPS-W-GY for
Wood Doors Only required for shared / common area egress doors.
LEASE NO. DACAXX5XXXXXXXXX EXHIBIT X Page 14 of 85
Double Aluminum
Exterior Door (both active leaf’s, one electrified)
8801EL36-24
Adams Rite - Rim Exit
Device 2-5/8” x 36” Satin Aluminum 1
E8
8801-36 Adams Rite - Rim Exit
Device 2-5/8” x 36” Satin Aluminum 1
55-56-PE8504F
NEL x PE8510F x L980A mullion (at stiles
WEL x PE8810F x L980S mullion
(at stiles 4.5” or more)
Sargent – Pair of Rim Exit
Device with Motorized Latch
Retraction one leaf.
Nightlatch, key retracts latch at active leaf. Exit only inactive. Keyed removable mullion.
Select model by verifying stile width.
36” wide
Other widths available
Satin Stainless Steel
PE80 for secondary egress w/ keypad
A620-626 Yale – Cylinder Housing &
Interchangeable Core N/A Satin Chrome 2
4612-1 Adams Rite - Power Transfer N/A Chrome 1
BF158-630 Rockwood - Door Pull 1” x 12” Satin SS 1 On electrified door.
Match Existing building color
3531-689 Yale - Automatic Door
Closer 2-1/8” x 12” Aluminum 2
MS4043-00-130 Adams Rite - Guard Ring N/A Clear Anodized 2
3890-10-628
Adams Rite – Removable
Mullion for 8800 Series Exit
Devices
N/A Clear Anodized 1
DPS-M-GY
Securitron - Door Position
Switch (Magnetic) ¾” Gray 2
Only required for shared / common area egress doors.
IXG-DM7-HIDA
Aiphone - IXG System
Door-Entrance Station
13-11/16” H x 7-3/16” W x 2” D
SS 1
(with mounting…
This is the start of the file's text. The full file is on GovTribe.