Exhibit C - Plans and Spec.pdf
PDF 3 MB Posted
- Attached to
- FIRE SUPPRESSION MODIFICATION
- Solicitation number
- ITB-13347
- Issued by
- Leon County, Florida
About this file
This document is a hydraulic analysis report for fire protection renovations at the Caldwell Building, located at 107 E. Madison St. in Tallahassee, Florida. The project involves a comprehensive hydraulic evaluation for an Ordinary Group I fire sprinkler system, with multiple hydraulic calculations and system demand analyses performed across six different groups and multiple routes. The analysis was conducted using AutoSPRINK 2020 software, with a job number of 2308 and multiple evaluation dates in July 2023.
The hydraulic summary indicates a fire protection system with a design flow rate of 5.6 K-Factor at 7.000, targeting a total area of approximately 1,500 square feet. The water supply analysis shows a static pressure of 80 PSI, with a required flow of 250 gallons per minute. The system includes 14-18 sprinklers across different nodes, with total demand ranging between 492-551 gallons per minute and safety margins between 12-19 PSI. The analysis covers detailed hydraulic graphs for water supply, pressure curves, and node-specific evaluations, ensuring the fire protection system meets necessary performance and safety standards for the Caldwell Building's attic area.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .