Exhibit C - Plans and Spec.pdf
PDF 3 MB Posted
- Attached to
- FIRE SUPPRESSION MODIFICATION
- Solicitation number
- ITB-13347
- Issued by
- Leon County, Florida
About this file
This document is a hydraulic analysis report for fire protection renovations at the Caldwell Building, located at 107 E. Madison St. in Tallahassee, Florida. The project involves a comprehensive hydraulic evaluation for an Ordinary Group I fire sprinkler system, with multiple hydraulic calculations and system demand analyses performed across six different groups and multiple routes. The analysis was conducted using AutoSPRINK 2020 software, with a job number of 2308 and multiple evaluation dates in July 2023.
The hydraulic summary indicates a fire protection system with a design flow rate of 5.6 K-Factor at 7.000, targeting a total area of approximately 1,500 square feet. The water supply analysis shows a static pressure of 80 PSI, with a required flow of 250 gallons per minute. The system includes 14-18 sprinklers across different nodes, with total demand ranging between 492-551 gallons per minute and safety margins between 12-19 PSI. The analysis covers detailed hydraulic graphs for water supply, pressure curves, and node-specific evaluations, ensuring the fire protection system meets necessary performance and safety standards for the Caldwell Building's attic area.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .