This document contains a comprehensive hydraulic analysis report for fire protection renovations at the Caldwell Building, located at 107 E. Madison St. in Tallahassee, Florida. The report, prepared by M.E.P.CAD, Inc. using AutoSPRINK 2020 software, details the hydraulic calculations for an Ordinary Group I fire sprinkler system with a design area of 1,500 square feet. The analysis covers multiple water supply scenarios, examining water flow, pressure, and distribution across various nodes and routes within the building's fire protection system.
The hydraulic summary indicates a water supply flow of 250 gallons per minute with a static pressure of 80 pounds per square inch. The report provides detailed hydraulic graphs and node analyses for different water supply routes, demonstrating the system's performance under various flow conditions. The calculations include specific details such as friction loss, pipe velocities, and pressure variations across different system components. The analysis appears to be part of a comprehensive fire protection design review, ensuring the sprinkler system meets safety and performance standards for the Caldwell Building's attic renovation project.