Exhibit_C_M4.1.3__STATION_3_HEATING_AND_VENTILATION_SCHEDULES_Rev.2.pdf
PDF 226 KB Posted
- Solicitation number
- FY2027-ITB-215
- Issued by
- Champaign County, Illinois
About this file
This document is a heating and ventilation schedules exhibit for Fire Station No. 3 located at 1205 W Bradley Avenue, Urbana, Illinois, prepared by FGM Architects Inc. in coordination with Clark Dietz, Inc., RME Rubinos & Mesia Engineers, and JSD Inc. as part of a construction project for the City of Urbana. The exhibit provides comprehensive mechanical system specifications for Station 3, including detailed schedules for nine water source heat pumps ranging from 360 to 1,480 CFM capacity, nine exhaust fans with capacities between 75 and 1,900 CFM, multiple circulation and heating water pumps, two gas-fired condensing boilers each rated at 145,000 to 155,000 BTU/H input, a dedicated outdoor air system with 1,100 CFM capacity, radiant heating panels, air compressor, air-cooled condensing units, louver intake and exhaust systems, and various HVAC terminal devices including grilles, diffusers, and dampers. The document also includes specifications for support systems such as air separators, expansion tanks, glycol feeders, an air conditioning unit for IT space, infloor heating manifolds with multiple circuits, and electric unit heaters, along with roof-mounted exhaust hoods and air filtration units.
The schedules specify equipment manufacturers including ClimateMaster for heat pumps, Greenheck for exhaust fans and louvers, Lochinvar for boilers, Taco for pumps and expansion tanks, Bell & Gossett for secondary pumps and air separators, and various other HVAC component suppliers. All specified equipment operates on 208-volt single or three-phase electrical service at 120 volts for certain components, with motor power ratings ranging from 0.01 to 5.0 horsepower. The system utilizes R-454B refrigerant and 30 percent propylene glycol for freeze protection in infloor heating applications. The document was issued for construction on May 31, 2024, following several revisions issued for bid, permit, and construction coordination purposes, with the most recent revision noted on February 17, 2025. The specifications reflect a comprehensive HVAC design incorporating water source heat pump technology with dedicated outdoor air handling and multiple redundant heating sources suitable for a modern fire station facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JOB NO.
SHEET NO.
© 2023 FGM Architects Inc.
C o p y ri g h t
F G
M A
R C
H
IT
E C
T S
I N
C
1815 S Meyers Rd, STE 470
Oak Brook Terrace, IL 60181
630.413.4130 (O) 217.373.8923(F)
IL STATE CERTIFICATE OF AUTHORITY
NO. 184-000450
CLARK DIETZ, INC.
CIVIL
1400 E TOUHY AVE, STE 215
DES PLAINES, IL 60018
312.644.3379 (O) XXX.XXX.XXXX(F)
XXX STATE CERTIFICATE OF AUTHORITY
NO. XXXXXXXXXX
JSD INC.
LANDSCAPE
200 S MICHIGAN AVE, STE 1500
312.663.5879 (O) 312.663.1473 (F)
XXX STATE CERTIFICATE OF AUTHORITY
NO. XXXXXXXXXX
RME | RUBINOS & MESIA ENGINEERS, INC.
STRUCTURAL
1815 S Meyers Rd, STE 470
Oak Brook Terrace, IL 60181
630.413.4130 (O) 217.373.8923(F)
IL STATE CERTIFICATE OF AUTHORITY
NO. 184-000450
CLARK DIETZ, INC.
MECH, PLUMBING, & FIRE PROTECTION
1815 S Meyers Rd, STE 470
Oak Brook Terrace, IL 60181
630.413.4130 (O) 217.373.8923(F)
IL STATE CERTIFICATE OF AUTHORITY
NO. 184-000450
CLARK DIETZ, INC.
ELECTRICAL
F
IR
E S
T A
T
IO
N S
N O
N
O
C
IT
Y
O F
U R
B A
N A
N O
.2
E M
U M
F O
R D
D R
U
R B
A N
A
IL
N O
W
B R
A D
LE
Y
A V
E
U R
B A
N A
IL
/1
/2
:0
:5
P M
P
F
F
G M
U rb a n a
F ir e S ta ti o n s\ D e si g n
\C A
D \M o d e ls
\R e v it
\U p g ra d e d M o d e l
\J A
W \F
S
T A
T
IO
N
C D
C E
N T
R A
L M
O D
E L
R d e ta ch e d
.r v t
M4.1.3 22-3456.02
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
STATION 3 HEATING AND
VENTILATION SCHEDULES
WATER SOURCE HEAT PUMP SCHEDULE
TAG
LOCATION
SERVICE TYPE ARRANGEMENT
FAN
OUTSIDE AIR
(CFM)
EVAPORATOR COOLING COIL HEAT REJECTION CONDENSER
WPD (FT
H2O)
CONDENSER HEATING COIL
REFRIGERANT
TYPE
VOLT
(V) PH NOTES MANUFACTURER MODELNAME
DESIGN
AIRFLOW
(CFM) ESP (IN W.G)
AIRSIDE SOURCE: CONDENSER WATER
CAP
(BTU/H)
AIRSIDE
EAT, DB
(°F)
EAT, WB
(°F)
LAT, DB
(°F)
LAT, WB
(°F)
DESIGN FLOW
(GPM)
EWT
(°F)
LWT
(°F)
EAT, DB
(°F)
LAT, DB
(°F)
3HP-1 CORRIDOR BUNK ROOMS HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
360 0.50 40 80.0 67.0 61.0 56.0 1.9 60 52 1.4 7500 70.0 89.3 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-006
3HP-2 CORRIDOR
RESTROOMS/
BUNK ROOMS
HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
420 0.50 50 80.0 67.0 61.0 56.0 2.5 60 52 3.7 10000 70.0 92.0 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-009
3HP-3 CORRIDOR BUNK ROOMS HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
320 0.50 40 80.0 67.0 61.0 56.0 1.9 60 52 1.4 7500 70.0 91.7 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-006
3HP-4 KITCHEN
KITCHEN/DINI
NG
HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
1480 0.50 330 80.0 67.0 61.0 56.0 5.4 60 52 7.8 21500 70.0 83.5 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-018
3HP-5 FITNESS FITNESS HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
650 0.50 225 80.0 67.0 61.0 56.0 3.4 60 52 7.0 13500 70.0 89.2 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-012
3HP-6 CORRIDOR
RESTROOMS/
OFFICES
HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
760 0.50 120 80.0 67.0 61.0 56.0 5.4 60 52 7.8 21500 70.0 96.2 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-018
3HP-7 CORRIDOR LOBBY HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
180 0.50 20 80.0 67.0 61.0 56.0 1.9 60 52 3.7 7500 70.0 108.6 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-006
3HP-8 CORRIDOR OFFICES HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
1000 0.50 150 80.0 67.0 61.0 56.0 5.9 60 52 6.0 23600 70.0 91.9 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-024
3HP-9 CORRIDOR
CONFERENCE
ROOM
HORIZONTAL
LEFT RETURN/
RIGHT
DISCHARGE
900 0.50 125 80.0 67.0 61.0 56.0 5.9 60 52 6.0 23600 70.0 94.3 R-454B/NOTE 1 208 1 CLIMATE MASTER TC-TR-024
EXHAUST FAN SCHEDULE
TAG
LOCATION
SERVICE TYPE ARRANGEMENT
FAN UNIT
WEIGHT
(LB)
VOLT
(V) PH NOTES MANUFACTURER MODELNAME
DESIGN
AIRFLOW (CFM) ESP (IN W.G) RPM
DRIVE
TYPE
MOTOR
POWER (HP)
3EF-1 MEZZ
APPARATUS B
AY
INLINE HORIZONTAL 1900 1.00 1419 DIRECT 0.75 80 120 1 1 GREENHECK SQ-140
3EF-2 BAY STORAGE
DECON/LAUND
RY
INLINE HORIZONTAL 400 0.25 1550 DIRECT 0.10 49 120 1 GREENHECK SQ-95
3EF-3
TURNOUT
GEAR/STORM
SHELTER
STORM
SHELTER
INLINE HORIZONTAL 360 0.50 1550 DIRECT 0.25 49 120 1 GREENHECK SQ-95
3EF-4 BAY STORAGE
TRAINING
STORAGE
INLINE HORIZONTAL 360 0.25 1550 DIRECT 0.25 49 120 1 GREENHECK SQ-95
3EF-5 CORRIDOR
HOUSE
RESTROOMS
INLINE HORIZONTAL 380 1.00 1140 DIRECT 0.25 56 120 1 GREENHECK SQ-100
3EF-6 HOSE TOWER HOSE TOWER SIDEWALL HORIZONTAL 300 0.25 681 DIRECT 0.25 60 120 1 GREENHECK AER-20-VG
3EF-7 ROOF
MECHANICAL
ROOM
ROOF
MOUNT
UPFLOW 150 0.25 1050 DIRECT 0.03 40 120 1 GREENHECK CUE-090
3EF-8 ROOF
ELECTRICAL
ROOM
ROOF
MOUNT
UPFLOW 150 0.25 1050 DIRECT 0.03 40 120 1 GREENHECK CUE-090
3EF-9 TOILET
BAY
RESTROOM
CEILING ROUND OUTLET 75 0.25 900 DIRECT 0.01 12 120 1 GREENHECK SP-A90
PUMP SCHEDULE
TAG
LOCATION
TYPE
PUMP MOTOR
VOLT
(V) PH NOTES MANUFACTURER MODELNAME
FLOW
HEAD
(FT)
SPEED
(RPM)
POWER
(HP)
DESIGN
(GPM)
3BP-1 INLINE 15.0 15.0 3250 0.13 120 1 TACO IL0011
3BP-1 INLINE 15.0 15.0 3250 0.13 120 1 TACO IL0011
3HWP-1
MECH. ROOM
INLINE 15.0 65.0 1725 1.50 208 3 1 TACO 133
3HWP-2
MECH. ROOM
INLINE 15.0 65.0 1725 1.50 208 3 1 TACO 133
3P-1
MECH. ROOM
END SUCTION 39.0 100.0 3150 5.00 208 3 BELL & GOSSETT E-1510 1.25BC
3P-2
MECH. ROOM
END SUCTION 39.0 100.0 3150 5.00 208 3 BELL & GOSSETT E-1510 1.25BC
RADIANT PANEL SCHEDULE
TAG LOCATION TYPE SIZE
# OF PANELS
HEATING
LOAD (BTU/H)
VOLT
(V) PH NOTES MANUFACTURER MODEL
3RP-1 TRAINING ROOM
CEILING
MOUNT
24" X 48" 10 2300 208 1 THERMA-RAY AS2448-675-208
DEDICATED OUTDOOR AIR SYSTEM SUMMARY SCHEDULE
TAG
LOCATION
TYPE ARRANGEMENT
VENTILATION SUPPLY FAN
HEATING CAP
(MBH)
COOLING CAP
(MBH)
VOLT
(V) PH
UNIT
WEIGHT
(LB) NOTES MANUFACTURER MODELNAME OA %
DESIGN
AIRFLOW
(CFM) ESP (IN W.G) RPM
DRIVE
TYPE
MOTOR
QTY POWER (HP)
3DOAS-1 MECH. ROOM INLINE Horizontal 100 1100 1.77 1200 DIRECT 1 0.75 100 30.6 208 3 1174 GREENHECK MSX-P116-H12-D1
GAS-FIRED BOILER SCHEDULE
TAG
LOCATION
TYPE CAP (BTU/H)
GAS-FIRED HEAT EXCHANGER
THERMAL
EFF VOLT PH NOTES MANUFACTURER MODELNAME NO.
GAS BURNER WATERSIDE
INPUT
(BTU/H)
FUEL FLOW
EWT (°F) LWT (°F)TYPE PRESS AVAIL (PSI) DESIGN (GPM)
3B-1 MECH. ROOM 134 CONDENSING 145000 155000 NG 2.0 11.0 110 140 95% 120 1 LOCHINVAR KHBWHB-Sub-0
3B-2 MECH. ROOM 134 CONDENSING 145000 155000 NG 2.0 11.0 110 140 95% 120 1 LOCHINVAR KHBWHB-Sub-0
LOUVER SCHEDULE
TAG
LOCATION
QTY MATERIAL FINISH TYPE
DESIGN
AIRFLOW
(CFM)
FREE
AREA (SF)
FREE AREA
VELOCITY
(FPM)
DUTY
TYPE
DIMENSIONS UNIT
WEIGHT
(LB) NOTES MANUFACTURER MODELNAME WIDTH HEIGHT
3EL-1 APPARATUS BAY 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1900 3.8 500 EXHAUST 30" 36" 29 GREENHECK ESD-635
3EL-2 BAY LAUNDRY 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
500 1.0 500 EXHAUST 18" 18" 16 GREENHECK ESD-635
3EL-3 APPARATUS BAY 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1900 3.8 500 EXHAUST 30" 36" 29 GREENHECK ESD-635
3EL-4
TURNOUT
GEAR/STORM
SHELTER
1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
360 0.8 450 EXHAUST 18" 18" 16 GREENHECK ESD-635
3EL-5
TURNOUT
GEAR/STORM
SHELTER
1 ALUMINUM ENAMEL
ICC500 STORM
SHELTER
LOUVER
360 0.8 450 EXHAUST 18" 18" 16 GREENHECK AFL-501
3IL-1 APPARATUS BAY 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1900 3.8 504 INTAKE 30" 36" 29 GREENHECK ESD-635
3IL-2 FITNESS 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
3000 5.8 517 INTAKE 20" 20" 29 GREENHECK ESD-635
3IL-3 FITNESS 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1100 2.3 472 INTAKE 30" 24" 19 GREENHECK ESD-635
3IL-4 APPARATUS BAY 1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
760 2.8 275 INTAKE 28" 28" 29 GREENHECK ESD-635
3IL-5
TURNOUT
GEAR/STORM
SHELTER
1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
360 0.8 450 INTAKE 18" 18" 16 GREENHECK ESD-635
3IL-6
TURNOUT
GEAR/STORM
SHELTER
1 ALUMINUM ENAMEL
ICC 500 STORM
SHELTER
LOUVER
360 0.8 450 INTAKE 18" 18" 16 GREENHECK AFL-501
AIR SEPARATOR SCHEDULE
TAG
LOCATION
SYSTEM TYPE ARRANGEMENT
DESIGN
FLOW
(GPM)
MAX
FLOW
(GPM)
PIPE
SIZE ASME NOTES MANUFACTURER MODELNAME
3AS-1 MECH. ROOM
HEATING
WATER
TANGENTIAL HORIZONTAL 22.0 56.0 2" Yes BELL & GOSSETT R-2N
3AS-2 MECH. ROOM
HEATING
WATER
TANGENTIAL HORIZONTAL 32.0 56.0 2" Yes SPIROTHERM VJR200TM
EXPANSION TANK SCHEDULE
TAG
LOCATION
SYSTEM TYPE ARRANGEMENT VOL (GAL)
ACCEPTANCE
VOL
PRECHARG
E PRESS
UNIT DIMENSIONS UNIT WEIGHT
(LB)
ASME NOTES MANUFACTURER MODEL
NAME NO. DIAMETER HEIGHT
3ET-1 MECH. ROOM 134 HEATING WATER BLADDER VERTICAL 8.0 5.3 gal 12 psi 14" 22 1/2" 45 Yes TACO CX30-125
3ET-2 MECH. ROOM 134 HEATING WATER BLADDER VERTICAL 8.0 5.3 gal 12 psi 14" 22 1/2" 45 Yes TACO CX30-125
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
TAG DESCRIPTION FACE SIZE NECK SIZE MATERIAL
MOUNTING
SURFACE CFM RANGE NOTES MANUFACTURER MODEL
A1
SQUARE PLAQUE CEILING
DIFFUSER
24" X 24" 6"
STAINLESS
STEEL
LAY-IN 0-150 1,2 PRICE SPD
A2
SQUARE PLAQUE CEILING
DIFFUSER
24" X 24" 8"
STAINLESS
STEEL
LAY-IN 151-200 1,2 PRICE SPD
A3
SQUARE PLAQUE CEILING
DIFFUSER
24" X 24" <varies>
STAINLESS
STEEL
LAY-IN <varies> 1,2 PRICE SPD
A4
SQUARE PLAQUE CEILING
DIFFUSER
24" X 24" 12"
STAINLESS
STEEL
LAY-IN 301-450 1,2 PRICE PDS
E1 CEILING EXHAUST GRILLE 24" X 24" 8"
STAINLESS
STEEL
LAY-IN - 1,2 TITUS 350RL
E2
DUCT MOUNTED EXHAUST
GRILLE
14" X 6" N/A
STAINLESS
STEEL
DUCT - 1,2 TITUS S300FS
E3
DUCT MOUNTED EXHAUST
GRILLE
12" X 6" N/A
STAINLESS
STEEL
DUCT - 1,2 TITUS S300FS
E4
DUCT MOUNTED EXHAUST
LOUVER
32" X 20" N/A
STAINLESS
STEEL
DUCT - 1,2 TITUS 300RS
R1
CEILING SQUARE RETURN
GRILLE
24" X 24" <varies>
STAINLESS
STEEL
LAY-IN <varies> 1,2 PRICE 80
R2
CEILING SQUARE RETURN
GRILLE
24" X 24" 6"
STAINLESS
STEEL
LAY-IN 0-150 1,2 PRICE 80
R3
CEILING PLENUM RETURN
GRILLE
24" X 24" <varies>
STAINLESS
STEEL
LAY-IN <varies> 1,2 PRICE 80
R4
CEILING SQUARE RETURN
GRILLE
24" X 24" 12"
STAINLESS
STEEL
LAY-IN 301-450 1,2 PRICE 80
T1
TRANSFER AIR GRILLE 45
DEGREE DOUBLE DEFLECTION
14" X 6" N/A
STAINLESS
STEEL
DUCT - PRICE 600
GLYCOL FEEDER SCHEDULE
TAG
LOCATION
TYPE
PUMP UNIT
VOL
(GAL)
UNIT
WEIGHT
(LB)
VOLT
(V) PH NOTES MANUFACTURER MODELNAME NO.
FLOW
(GPM)
DISCHARGE PRESS
(PSI)
3GF-1 MECH. ROOM 134 30% PG 1.0 50.0 55.0 50 120 1 AXIOM SF100
3GF-2 MECH. ROOM 134 30% PG 1.0 50.0 55.0 50 120 1 AXIOM SF100
AIR COMPRESSOR SCHEDULE
TAG
LOCATION
TYPE
FREE AIR
DELIVERY
CFM
MAX
WORKING
PRESSURE
(PSIG)
FAN
UNIT
WEIGHT
(LB)
VOLT
(V) PH NOTES MANUFACTURER MODELNAME NO.
MOTOR
POWER (HP)
AC-1 MEZZ 201
SINGLE STAGE
RECIPROCATING
HORZ. TANK MT.
17.4 125 5.00 770 208 3
PROVIDE AIR FILTER AND
REGULATOR ON COMPRESSOR
DISCHARGE.
QUINCY QR-25 F325
AIR COOLED CONDENSING UNIT
TAG
LOCATION COMPRESSOR
AMBIENT
TEMP (F) CAP (MBH) SEER EER NO. COMPRS. NO. CIRCUITS FLA HZ MCA VOLT (V) PH NOTES MANUFACTURER MODELNAME
REFRIGERANT
TYPE
3CU-1
FENCED
AREA
R-454B/NOTE 1 95.0 18 18.5 9.9 1 1 15 60 11 208 1
COORDINATE ELECTRICAL
DISCONNECT WITH ELECTRICAL
CONTRACTOR.
MITSUBISHI TRUYA0181KA70NA
3CU-2
FENCED
AREA
R-454B/NOTE 1 95.0 60 17 0 1 1 0.93 60 19 208 1
COORDINATE ELECTRICAL
DISCONNECT WITH ELECTRICAL
CONTRACTOR.
TRANE 4TTR6036B1000A
AIR CONDITIONING UNIT SCHEDULE
TAG
LOCATION AIRFLOW
(CFM)
FAN MOTOR
FLA
SENSIBLE
(BTU/HR)
TOTAL
(BTU/HR) HZ MCA MOCP
VOLT
(V) PH NOTES MANUFACTURER MODELNAME NO.
3CRAC-1 I.T. 133 425 0.33 12240 18000 60 1 15 208 1
PROVIDE UNIT WITH MANUFACTURER'S UNIT DISCONNECT
SWITCH. PROVIDE UNIT WITH BACNET COMM CAPABLE WITTH BAS
SYSTEM. COORDINATE WITH CONTROLS CONTRACTOR.
MITSUBISHI
TPKA0A0181HA
70A
INFLOOR HEATING MANIFOLD SCHEDULE
TAG
LOCATION
TYPE
# OF
CIRCUITS FLOW (GPM) EWT (F) MAX TD (F) PD (FT H2O)
TOTAL LOAD
(BTU/H) PIPE DIA. TUBE DIA
TUBE
SPACING GLYCOL TYPE GLYCOL % NOTES
MANUFACTUR
ER MODELNAME
3MF-1 APPARATUS BAY CABINET 9 4.8 117 20 7.4 45325 1 1/4" 1/2" 9" PG 30
LEGEND
VALVE
M-8330
3MF-2 APPARATUS BAY CABINET 8 4.54 117 20 4 47860 1 1/4" 1/2" 9" PG 30
LEGEND
VALVE
M-8330
3MF-3 BAY LAUNDRY-1 CABINET 3 1.45 117 20 3.6 14451 1 1/4" 1/2" 9" PG 30
LEGEND
VALVE
M-8330
3MF-4
TURNOUT
GEAR/STORM
SHELTER
CABINET 2 1.14 117 20 5 11326 1 1/4" 1/2" 9" PG 30
LEGEND
VALVE
M-8330
3MF-5 TRAINING STOR. CABINET 2 0.8 117 20 2.1 7949 1 1/4" 1/2" 9" PG 30
LEGEND
VALVE
M-8330
ELECTRIC UNIT HEATER SCHEDULE
TAG
LOCATION
AIRFLOW
PATTERN
FAN ELECTRIC COIL
MOUNTIN
G HEIGHT
(FT)
VOLT
(V) PH NOTES MANUFACTURER MODELNAME
DESIGN
AIRFLOW
(CFM)
MOTOR
CAP
(BTU/H)
AIRSIDE
QTY
POWER
(HP) EAT, DB (°F) LAT, DB (°F)
3UH-1
MECHANICAL
ROOM
HORIZONTAL 380 1 0.03 10200 55.0 79.9 8 120 1 MODINE HER30
3UH-2
ELECTRICAL
ROOM
HORIZONTAL 380 1 0.03 10200 55.0 79.9 8 120 1 MODINE HER30
ROOF HOOD SCHEDULE
TAG
LOCATION
SERVICE
DESIGN
AIRFLOW
(CFM)
MAX
VELOCITY
(FPM)
THROAT DIA.
(IN) INLET W (IN) INLET L (IN) NOTES MANUFACTURER MODELNAME
3RH-1 ROOF
KITCHEN
HOOD
600 730 N/A 22 22 GREENHECK GRSR-12
3RH-2 ROOF
HOUSE
RESTROOMS
800 572 16 N/A N/A GREENHECK GRS-16-QD
AIR FILTRATION UNIT SCHEDULE
TAG
LOCATION
# OF MOTORS HP VOLT (V) PH NOTES MANUFACTURER MODELNAME
3AFU-1 APPARATUS BAY 1 1 208 1 AIRHAWK 3000 XL
3AFU-2 APPARATUS BAY 1 1 208 1 AIRHAWK 3000 XL
NOTES:
1. PROVIDE WITH MANUFACTURER'S VARIABLE FREQUENCY DRIVE.
NOTES:
1. FOR ALL AREAS WITH DRYWALL CEILING, GRILLE AND DIFFUSER SHALL BE PROVIDED WITH BUILT-IN BALANCING DAMPERS.
2. ALL GRILLES AND DIFFUSERS PROVIDED IN WET AREAS (TOILETS, LOCKER ROOMS, JANITOR CLOSETS, LAUNDRY, DECONTAMINATION AREAS) SHALL BE
NON CORROSIVE ALLUMINUM CONSTRUCTION.
MOTORIZED DAMPER SCHEDULE
TAG LOCATION SERVICE
DAMPER
WIDTH
DAMPER
HEIGHT
BLADE
CONFIGURATION
TYPE
NOTES
3DMP-1
APPARATUS
BAY
IL-1 36" 6" PARALLEL TWO-POSITION
3DMP-2
APPARATUS
BAY
IL-1 36" 16 1/12" PARALLEL TWO-POSITION
3DMP-3
APPARATUS
BAY
IL-1 36" 7 1/2" PARALLEL TWO-POSITION
3DMP-4
APPARATUS
BAY
IL-4 28" 28" PARALLEL TWO-POSITION
3DMP-5
DECON/LAUN
DRY
EL-1 30" 36" PARALLEL TWO-POSITION
3DMP-6 MECH. ROOM IL-3 28" 28" PARALLEL TWO-POSITION
3DMP-7
STORM
SHELTER
IL-5 18" 18" PARALLEL TWO-POSITION
NOTES:
1. USE REFRIGERANT TYPE BASED ON AVAILABILITY AND WHAT IS ALLOWED TO BE USED.
NOTES:
1. USE REFRIGERANT TYPE BASED ON AVAILABILITY AND WHAT IS ALLOWED TO BE USED.
NOTES:
1. USE REFRIGERANT TYPE BASED ON AVAILABILITY AND WHAT IS ALLOWED TO BE USED.
NOTES:
1. PROVIDE WITH MANUFACTURER'S VARIABLE FREQUENCY DRIVE. ISSUANCE
NO DATE DESCRIPTION
0 03/04/24 ISSUED FOR BID & PERMIT
1 04/01/24 REVISION #1
2 04/08/24 REVISION #2
3 05/03/24 ISSUED FOR PERMIT
REVISIONS
4 05/17/24 ISSUED FOR PERMIT
REVISIONS
5 05/31/24 ISSUED FOR CONSTRUCTION
10 02/17/25 PR-006
File details come from the government source that posted it. Updated .