Exhibit C Attachment A Discharge Limits and Monitoring Requirements.pdf

PDF 119 KB Posted

Attached to
NCC WTP Operations and Maintenance
Solicitation number
RFP FAAA 2027000059 2
Issued by
Garfield County, Colorado

About this file

This document is Exhibit C Attachment A to the North Clear Creek Water Treatment Plant (NCCWTP) Operations and Maintenance Scope of Work, establishing discharge limits and monitoring requirements for the facility's operations. The scope of work addresses the monitoring and operational management of the NCCWTP, which treats influent with predicted flow rates between 80 and 600 gallons per minute and contaminant levels including cadmium, copper, iron, manganese, zinc, and sulfate. The operator is responsible for continuous monitoring of three distinct outfalls: Outfall 001 (treated effluent), Outfall 002 (untreated bypass when storage capacity is exceeded), and Outfall 003 (diverted flow through bypass storm drain). Effluent monitoring requirements for Outfall 001 include continuous flow recording and daily pH monitoring, with weekly composite sampling for parameters such as total suspended solids, total recoverable iron, and various dissolved metals, and quarterly composite sampling for total dissolved solids and sulfate. Annual acute toxicity testing is required for Pimephales promelas and Ceriodaphnia dubia organisms.

Bypass monitoring through Outfalls 002 and 003 is triggered when flow continues for at least two hours and includes weekly grab sampling for pH, cadmium, copper, iron, lead, manganese, nickel, silver, and zinc with continuous flow recording. Influent monitoring is required regardless of discharge occurrence across four collection points: the influent vault (300I), Gregory Incline manhole (400I), Gregory Gulch collection trench (500I), and National Tunnel flume (600I). Quarterly monitoring of the influent vault includes continuous flow recording and grab sampling for pH, total dissolved solids, hardness, and dissolved metals. The three additional influent locations require semi-annual grab sampling during high flow periods in June and low flow periods in December for the same parameters. The document does not specify pricing, contract term, renewal options, set-asides, incumbent information, or funding sources.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NCCWTP Operations and Maintenance Scope of Work Attachment A

Discharge Limits and Monitoring Requirements

1. Predicted Influent

Parameter Predicted Influent Flow (gallons per minute) 80 – 600 pH (standard units) 4.1 – 6.4 Cadmium, dissolved (mg/L) 0.002 – 0.01 Copper, dissolved (mg/L) 0.05 - 1.3 Iron, total recoverable (mg/L) 25 - 150 Manganese, dissolved (mg/L) 8 - 28 Zinc, dissolved (mg/L) 2 - 9 Sulfate, total (mg/L) 900 - 1600

2. Effluent Monitoring and Limitations

The North Clear Creek WTP Operator (Operator) shall monitor all effluent parameters at the frequencies and sample types listed below.

Outfall Description 001 Outfall 001 is the outfall from the North Clear Creek Water Treatment

Plant prior to contact or commingling with any surface or ground water. Outfall 001 will be monitored at the overflow of the V-Notch weir located in the facility effluent vault (TK-400).

002 Outfall 002 is the outfall from the bypass structure which passively discharges untreated influent when the influent vault (TK-050) water level exceeds storage capacity. Outfall 002 will be monitored from the vault door adjacent to the 12” bypass pipe.

003 Outfall 003 is the outfall from the bypass structure which diverts flow from the source conveyance pipeline through the bypass storm drain (BPST) around the North Clear Creek Water Treatment Plant. Outfall 003 will be monitored from Manhole 18, located upstream of the influent vault.

Table 1 - Outfall 001 – Effluent Monitoring Requirements

Effluent Parameter

Effluent Limitations Maximum Concentrations

Monitoring Requirements

30-Day Average Daily Maximum Frequency Sample

Type

Effluent Flow (MGD) 0.65 Report Continuous Recorder pH (su) -- 6.5-9.0 Daily Grab TSS, effluent (mg/l) 30 45 Weekly Composite Oil and Grease (visual) -- Report Weekly Visual Oil and Grease (mg/l) 10 Contingent Grab TDS (mg/l) -- Report Quarterly Composite Hardness as CaCO3 (mg/l) -- Report Weekly Composite Cd, PD (µg/l) 0.61 1.5 Weekly Composite Cu, PD (µg/l) 64 -- Weekly Composite

Effluent Parameter

Effluent Limitations Maximum Concentrations

Monitoring Requirements

30-Day Average Daily Maximum Frequency Sample

Type

Fe, TR (µg/l) 5400 -- Weekly Composite Pb, PD (µg/l) 2.0 51 Weekly Composite Mn, PD (µg/l) 1531 2772 Weekly Composite Ni, PD (µg/l) 43 388 Weekly Composite Ag, PD (µg/l) 0.05 1.4 Weekly Composite Zn, Dis (µg/l) 740 -- Weekly Composite Sulfate (mg/l) -- Report Quarterly Composite LC50 Statre 96Hr Acute Pimephales promelas -- LC50 ≥100%

(daily min) Annual Grab

LC50 Statre 48Hr Acute Ceriodaphnia dubia -- LC50 ≥ 100%

(daily min) Annual Grab

Bypass Monitoring

In the event that any flow is bypassed through Outfall 002 or Outfall 003 and continues for at least 2-hours, the following samples shall be collected.

Table 2 - Outfall 002 and Outfall 003 - Bypass Monitoring

Parameter Monitoring Requirements Frequency Sample Type

Flow (MGD) Continuous Recorder pH (su) Daily Grab Cd, PD (µg/l) Weekly Grab Cu, PD (µg/l) Weekly Grab Fe, TR (µg/l) Weekly Grab Pb, PD (µg/l) Weekly Grab Mn, PD (µg/l) Weekly Grab Ni, PD (µg/l) Weekly Grab Ag, PD (µg/l) Weekly Grab Zn, PD (µg/l) Weekly Grab

3. Influent Monitoring

Regardless of whether or not an effluent discharge occurs, the Operator shall monitor influent parameters at the following required frequencies.

Influent Description

300I Influent 300I is the influent vault (TK-050) located at the North Clear Creek Water Treatment Plant.

400I Influent 400I is the Gregory Incline manhole where flow is continuously recorded.

500I Influent 500I is the collection trench were Gregory Gulch is diverted into the conveyance pipeline.

600I Influent 600I is the National Tunnel flume located under the pedestrian bridge at Mill Street.

Table 3 – Influent 300I - Monitoring

Parameter Monitoring Requirements

Frequency Sample Type Flow (MGD) Continuous Recorder pH (su) Quarterly Grab

TDS (mg/l) Quarterly Grab

Hardness as CaCO3 (mg/L) Quarterly Grab

Cd, PD (µg/l) Quarterly Grab

Cu, PD (µg/l) Quarterly Grab

Fe, TR (µg/l) Quarterly Grab

Pb, PD (µg/l) Quarterly Grab

Mn, PD (µg/l) Quarterly Grab

Ni, PD (µg/l) Quarterly Grab

Ag, PD (µg/l) Quarterly Grab

Zn, PD (µg/l) Quarterly Grab

Sulfate (mg/L) Quarterly Grab

Table 4 - Influent 400I, Influent 500I and Influent 600I - Monitoring

Parameter Monitoring Requirements

Frequency Sample Type Flow (MGD) Continuous Recorder pH (su) Semi-annually Grab

Cd, PD (µg/l) Semi-annually Grab

Cu, PD (µg/l) Semi-annually Grab

Fe, TR (µg/l) Semi-annually Grab

Pb, PD (µg/l) Semi-annually Grab

Mn, PD (µg/l) Semi-annually Grab

Ni, PD (µg/l) Semi-annually Grab

Ag, PD (µg/l) Semi-annually Grab

Zn, PD (µg/l) Semi-annually Grab

Semi-annual sampling to occur during high flow (June) and low flow (December)

File details come from the government source that posted it. Updated .