EXHIBIT B Page 1 of 3
RLP NO. 36C24422R0162
LEASE NO. 36C24423L0002
Indiana Agency Specific Requirements (ASR)
List – 11-08-2022
ITEM HOW
MANY
DESCRIPTION
Ambulance Entrance 1 A Nonpublic access should be created which enters into the clinic in a nonpublic area. The entrance should have a minimum width of 76 inches and have two doors with no post between.
The doors will have to be secured when not in use. This entrance shall also have an intercom system installed in order to communicate with individuals outside.
Audiology Booth
1 Lessor shall provide an Audiology Booth with all the appropriate data and electrical equipment to make it functional.
Industrial Acoustics Double Wall Suite. OD 16’6” X 10’2” X 8’ 1 ¼” and inside dimension of 8’-2” W x 6’-9”L X 6’6 ¾” H with a 36” clear opening width doors. Conduit for Fire Strobes, data and data drop for thermostat in suite. Closure plate on all side closures edges. Floor of booth to be flush with floor.
See Audiology and Speech Pathology Design Guide at:
https://www.cfm.va.gov/til/dGuide/dgAudio-spchPath.pdf
EN-09- Exterior Nonilluminated Dimensional Building Identification Letters
EN-09- Exterior Nonilluminated Dimensional Building Identification Letters:
Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf
Section – Exterior Signs – Dimensional Building Identification Letters (4-7-52) Message Layout:
Logo/Signature: Horizontal Sign Format (page 4-7-52)
Wall Mounted Monumental Signage: Sign to be appropriate size or ease of viewing. Facility exterior Architectural Entrance Sign to span minimum full width of door entrance opening of facility or as needed to be scaled in proportion to facility frontage.
Mounting – (page 4-9-17 through 4-10-11)
Sign Type EN-14 – Building Entrance Door Identification
Sign Type EN-14 – Building Entrance Door Identification Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf
EXHIBIT B Page 2 of 3
LEASE NO. 36C24423L0002
Section – Exterior Signs – Dimensional Building Identification Letters (page 4-7-61 through 4-7-63)
Sign Type Interior Signs Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf
Section – Interior Signs – Dimensional Building Identification Letters (starts on page 9-1-1)
Nurse Call
1 The Lessor shall provide a Nurse Call alarm system that reports to the central operation area and provides an illuminated light outside of the area alarmed. The following rooms shall be equipped with the nurse call alarm.
All restrooms – Restrooms shall have at a minimum a pull chord alarm to include the gynecology restroom and provider restrooms.
The lab room – Lab shall have push buttons located at the place of the blood draw are /chair
ASC-NGGTWY2-H/STATION GATEWAY II,
ASC-NUDL4S-H/DOME LIGHT 4 SECTIONS, SPEECH AND
BUZZER, and ASC-NUDUTY/DUTY STATION or approved equal.
Security Surveillance Television and Security Alarms
A Security Surveillance Television (SSTV) system shall be provided to monitor assigned areas.
The lessor shall allow the government to install an intrusion detection alarm system which detects entry into the room and which broadcasts a local alarm of sufficient volume to induce an illegal entrant to abandon a burglary attempt. The Intrusion detectors with have the following:
AA internal, automatic charging DC standby Power supply and a primary AC power operation.
A remote, key operated activation/deactivation switch Installed outside the rooms and adjacent to the room entrance door frame.
An automatic reset capability following an intrusion detection.
A local alam1 level of 80 dB (min) to 90 dB (max) up to 100 feet [30.48 m] from the protected room.
An Integral c:apability for the attachment of wiring for remote alarm and intrusion indicator equipment (visual or audio).
Intrusion detector equipment which operates on the principle of narrow beam interception, microwave, or photo eclectic eye is unacceptable.
EXHIBIT B Page 3 of 3
LEASE NO. 36C24423L0002
A locally sounding alarm should not be Installed in a room which is close to a cardiac care or other special treatment area where a loud alarm would have an injurious effect on patients.
Intrusion detector alarms will be remotely monitored by a commercial security alarm monitoring firm, a local police department, or a security office charged with building security.
The remoted alarms will be in addition to locally broadcast alarms in the protected areas.
Vending Facilities
1 Provide data, power and space for three vending machines.