This document is a Special Requirements specification (2TN0993) detailing specific facility requirements for a government lease space, likely for a garage or specialized storage area. The key requirements include two motorized 12'-0" x 14'-0" roll-up doors with safety features and heavy-duty slide bolts, a pedestrian door with a 3-point latching device and access control keypad, and a minimum 16'-0" vertical clearance with no ceiling. The space must provide 120V and 240V power and meet government standards for fire safety, accessibility, seismic, and sustainability.
The HVAC specifications mandate continuous 24/7 operation with precise environmental controls during the cooling season, maintaining a dry-bulb temperature between 55°F and 78°F and relative humidity between 40% and 60%. The HVAC systems must also comply with the latest ASHRAE Standard 62 for ventilation, with outside air intakes located in inaccessible or secured areas to prevent contaminant insertion. Additionally, the offered space must not be located in a 1-percent or 0.2-percent annual chance floodplain, and a fully serviced lease is required.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2TN0993 – SPECIAL REQUIREMENTS
Additional Requirements:
• Two (2) Motorized 12'-0" W x 14'-0" H roll-up doors. Roll-up doors must be provided with all safety features and with heavy-duty slide bolts at the bottom of the door on both sides.
• One (1) pedestrian door must be provided leading to the exterior (adjacent to roll-up door) with hardware function 7 (3-point latching device) with access control keypad provided (including all
5/11 conduits and power). The hardware, conduits, and power are the responsibility of lessor, but
Tenant will provide the keypad.
• No ceiling required (16'-0" minimum vertical clearance).
• Ability to provide 120V and 240V.
• Offered space must meet Government requirements for fire safety, accessibility, seismic, and sustainability standards per the terms of the Lease. A fully serviced lease is required. Offered space shall not be in the [1-percent-annual chance/0.2-percent-annual chance] floodplain (formerly referred to as [“100-year”/“500-Year”] floodplain).
• HVAC systems serving garage areas must operate continuously 24 hrs/day, 365 days/yr to maintain the following indoor environment (during cooling season, only). HVAC serving this room must be fed from normal power:
o DB Temperature: 130 C (550 F) to 270 C (780 F) o RH: 40% to 60%
• HVAC systems must provide ventilation in accordance with the latest edition of ASHRAE Standard
62, "Ventilation for Acceptable Indoor Air Quality." Outside air intakes must be located in an inaccessible location or secured to inhibit direct insertion of contaminants.
File details come from the government source that posted it. Updated .