This document is a Room Data Matrix (RDM) Excel spreadsheet detailing interior construction specifications for a VA medical facility, encompassing comprehensive design requirements for multiple departments and room types. The matrix provides exhaustive technical specifications for approximately 100 distinct room categories, including exam rooms, laboratories, imaging services, pharmacy, and administrative spaces, with detailed parameters for floor and wall finishes, door hardware, electrical and mechanical systems, lighting, power requirements, and environmental conditions such as temperature, humidity, and air exchange rates.

The RDM serves as a technical design guide, specifying precise requirements for each room's construction and operational characteristics, including specific technical notes for different functional areas like Audiology, Dental Services, Imaging, Mental Health, and Pharmacy. Each room entry includes standardized information such as floor and wall finishes, ceiling heights, sound isolation ratings, door and hardware specifications, electrical outlets, lighting configurations, HVAC parameters, and specialized environmental control requirements, which would be critical for contractors bidding on the St. Louis County VA Clinic replacement lease project (Solicitation Number: 36C25525R0080).

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RDM Org

ROOM DATA MATRIXINTERIOR CONSTRUCTIONDOORS AND HARDWAREMECHANICALELECTRICALIT
ROOM IDENTIFICATIONFLOORWALLSCEILINGNOTESNote: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise.POWERLIGHTING
Functional AreaDEPARTMENTROOM NAMEROOM NAMES (VA)FGI EQUIVALENT FOR ASHRAE 170FGI EQUIVALENT FOR TABLE 1.2-5 Minimum Sound IsolationFloor FinishBaseWall FinishWainscot MaterialWainscot HeightSTCCeiling FinishHeightNotesSize (Width)TypeMaterialGlazingRatingHardware GroupHardware NotesIndoor Temperature
Cooling FIndoor Temperature
Heating FIndoor Relative Humidity
% RH MaxIndoor Relative Humidity
% RH MinMinimum Total ACHMinimum OA ACHRoom Air Return
Gen. Exh G Spec Exh SMaximum Noise
Level NCRoom Air BalanceHVAC Notes# Duplex Receptacles# Quad ReceptaclesPower - NotesFixture TypeControlsLighting - Special RequirementsLighting - Notes# Data Outlets (standard density WAO)IT -

Special Requirements 0 General Rooms/Spaces Exam Room PACT Exam EXAM EXAMINATION RFT RB P -- -- SEE FGI AT 9'-0" 10 3'-0"

3'-6"FlushWood__12 SE381Multilevel Switching, Dimming & OccupancyMulti-level switching or manual dimmingN/A3
0General Rooms/SpacesExam RoomExam Room - Multi-Specialty, Exam / Treatment, Exam - Consult, Consult Room - PACT, Exam/Consult Room (Mental Health/Social Work), Exam Room EMG/EEG, Exam Room-Cardiology, Exam/Consult, Nurse Practitioner, Women's Health Exam, Tele-Health Exam, Optometry Exam Treatment Room, Eye Lane, Tele-Retinal, TECHS, Applicance Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment RoomEXAMEXAMINATIONRFTRBP----SEE FGIAT9'-0"103'-6"FlushWood__12 S81Multilevel Switching, Dimming & OccupancyMulti-level switching or manual dimmingN/A3
0General Rooms/SpacesConsult RoomConsult Room, Audiology Rehabilitation Counceling Room, Dental Consult RoomCONSULTATIONCPTRBP----SEE FGIAT9'-0"--3'-6"FlushWood__12 S_757060-42Return40NR6Multilevel Switching, Dimming & OccupancyMulti-level switching or manual dimmingN/A1
0General Rooms/SpacesProcedure RoomProcedure Room, General, Urology, Gynecology, Specialty Care, Multi-Specialty Care, Cast RoomPROCEDURETREATMENTWSFWSFEPRWC4'-0"SEE FGIAT9'-0"33'-0"
3'-6"FlushWood----12 SE37P13Multilevel Switching, Dimming & OccupancyWall mounted exam lightN/A2
0General Rooms/SpacesLaboratoryLaboratory (Typical)LABORATORY WORKROOM__WSFWSFEP----40AT-SP9'-0"33'-0"FlushWood__15 AG46P3, P4Multilevel Switching, Dimming & OccupancyN/AN/A5
0General Rooms/SpacesConference RoomConference Room, Multi-Purpose Room, Group Room, Shared Medical Appointment Room, Education Room, Staff Training Room, Classroom__CPTRBPRWC4'-0"40AT9'-0"173'-6"FlushWood__15 S_M28P14Multilevel Switching, Dimming & OccupancyProvide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections.N/A4Floor data for table
0General Rooms/SpacesTOILETGeneral Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family Assist, Specimen Collection ToiletTOILET ROOMTOILET ROOMPTPTPCT7'-0"SEE FGIAT9'-0"1,23'-6"FlushWood__11_1Downlights/Mirror or vanityOccupancy SensorN/AN/A
0General Rooms/SpacesOFFICEAny Office--CONSULTATIONCPTRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 CS41Multilevel Switching, Dimming & OccupancyN/AN/A2
0General Rooms/SpacesWAITINGWaiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6 People, Waiting-GeneralEXAM - PUBLIC SPACECPTRBP----SEE FGIAT9'-0"10, 17M4----Multilevel Switching, Dimming & OccupancyN/AN/A1
0General Rooms/SpacesRECEPTIONReception, Information Desk, Travel Window, Reception - Accessible----RFTRBP------AT9'-0"--3'-0"Flush w/ narrow visionWood__12 CG3M411Downlights, pendants, decorative, and accentMultilevel Switching, Dimming & OccupancyN/AN/A10Data/phone feeds to systems furniture
0General Rooms/SpacesCOPY ALCOVECopy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room----RFTRBP------AT9'-0"6______63Multilevel Switching, Dimming & OccupancyN/AN/A3
0General Rooms/SpacesCLEAN UTILITYClean Utility, Clean Supply, Clean Workroom, Clean Linen, Sterile Storage, CBOC Steril Supply Storage Room, Clean Scope, Dental Clean Cart, Central Sterile----RFTRBPRWC4'-0"--AT9'-0"--3'-0"FlushWood--45 MIN121 AG_667555304(+)1Occupancy SensorN/AN/A
0General Rooms/SpacesSOILED UTILITYSoiled Utility Room, Recycled Material, Soiled Holding, Soiled Linen, Soiled Workroom, Soiled Supply, Soiled CartSOILED HOLDING / SOILED WORK ROOM--WSFWSFPRWC4'-0"--AT9'-0"33'-0"FlushWood--45 MIN121 AG_2--Occupancy SensorN/AN/A--
0General Rooms/SpacesSTORAGEStorage - Medical Equipment, Storage - Shared Medical Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage - Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area, Buld Storage, General Storage, Secure Storage,CLEAN WORKROOM/CLEAN SUPPLYRFTRBP------AT9'-0"3'-0"FlushWood----35 AG1 per wall, not to exceed 12' spacing--Surface or chain mounted 1' x 4'Occupancy SensorN/AN/A
0General Rooms/SpacesJANITOR'S CLOSETHousekeeping Aides Closet (HAC)ENVIRONMENTAL SERVICES ROOM--CSRBPFRP4'-0"--AT9'-0"3'-0"FlushWood----34 A_1--Occupancy SensorN/AN/A--
0General Rooms/SpacesKITCHENETTESocial Activities Space/ Kitchen----RFTRBP------AT9'-0"173'-0"FlushWood----15 A_4--Multilevel switching/dimming/occupancyN/AN/A--
0General Rooms/SpacesEQUIPMENT ALCOVEAED Alcove, Height and Weight Alcove, Scale Alcove, Stretcher Alcove, Med Alcove, Portable Patient Lift Alcove, Wheelchair Alcove, My Health eVet, Kiosk,----Match AdjacentMatch AdjacentMatch AdjacentRWC4'-0"--ATMatch Adjacent3----------61--Multilevel Switching, Dimming & OccupancyN/AN/A--
0General Rooms/SpacesSTAFF LOUNGEStaff Lounge----RSFRBP----40AT9'-0"43'-0"Flush w/ narrow visionWood----13_Exh. (G)(-)8--P7
Multilevel Switching, Dimming & OccupancyN/AN/A2
0General Rooms/SpacesMEDICATION ROOMMedication RoomMEDICATION ROOM--RFTRBP------AT9'-0"3'-0"FlushWood----3451Multilevel Switching, Dimming & OccupancyN/AN/A1
0General Rooms/SpacesLACTATION ROOMEmployee Wellness, Lactation Room, Quiet Room----RFTRBP----50AT9'-0"103'-0"FlushWood----12 CS4--Multilevel Switching, Dimming & OccupancyN/AN/A1
0General Rooms/SpacesLOCKER ROOMLocker Room, Locker Room (Male/ Female) Locker - Staff Personal Property, Locker Room - Staff----RFTRBP----40AT9'-0"3'-0"FlushWood----Push/PullExh. (G)(-)4--Multilevel Switching, Dimming & OccupancyN/AN/A--
0General Rooms/SpacesOFFICE, CUBICLE, Open OfficeCubicle - Administrative, Data Processing, Workstation - Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical,----CPTRBP------AT9'-0"2 per workstation--Multilevel Switching, Dimming & OccupancyN/AN/A1
0General Rooms/SpacesSUB-WAITINGSub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-Zone 2----CPTRBP------AT9'-0"10, 17-----------6M44--Multilevel Switching, Dimming & OccupancyN/AN/A--
0General Rooms/SpacesVENDINGVending Machine AreaRFTRBP------AT9'-0"------------6M48--Multilevel Switching, Dimming & OccupancyN/AN/A4
0General Rooms/SpacesTOILET/SHOWER ROOMToilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male StaffTOILET ROOMTOILET ROOMPTPTCT----SEE FGIGWB/P9'-0"2, 193'-6"FlushWood----11 G2--Multilevel Switching, Dimming & OccupancyN/AN/A
0General Rooms/SpacesCHANGING ROOMDressing roomRFTRBP----40AT9'-0"3'-6"FlushWood----11 K757060-42ReturnNRNR1--Multilevel Switching, Dimming & OccupancyN/AN/A
2Primary Care, Specialty Care, PACTPACT TEAM WORK SPACEPACT Team Work Space, Team Work Area- Home Based Primary Care--CPTRBP--AT9'-0"--_____14 MP6M32 per workstation--Multilevel Switching, Dimming & OccupancyProvide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.N/A1 per workstation
2Primary Care, Specialty Care, PACTEXAM ROOM, AIRBORNE INFECTION ISOLATIONExam, Isolation, Negative PressureAII RoomEXAMINATIONWSFWSFP----SEE FGIGWB:P9'-0"3,73'-6"FlushWood----12 S6--Multilevel Switching, Dimming & OccupancySealed fixture, flat lens surface on exteriorN/A1
5Audiology and SLPAUDIOLOGY HEARING AID TESTINGHearing Aid Lab, Hearing Aid Processing, Hearing Aid Repair--RFTRBP----40AT9'-0"--3'-0"FlushWood__15 S_757060-Exh. (G)(-)70P4Multilevel Switching, Dimming & OccupancyN/AN/A2
5Audiology and SLPAUDIOLOGY HEARING AID FITTINGAudiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology Assistive Technology Romm, Speech Language Pathology Voice Treatment RoomEXAM--CPTRBP----60AT9'-0"--3'-6"FlushWood__12 S_6Multilevel Switching, Dimming & OccupancyN/AN/A2
5Audiology and SLPAUDIOMETRIC EXAM BOOTHAudiometric Exam Suite, Exam - Audiometric Booth, Aud: Suite - Audiometric Exam, Hearing/Diagnostics, Booth, 1-PersonEXAM--Pre-FabPre-FabPre-Fab----SEE EQUIP LIST

tc={DA07BD7C-343C-4CA6-BD5F-166A5EACAEF6}: [Threaded comment]

Your version of Excel allows you to read this threaded comment; however, any edits to it will get removed if the file is opened in a newer version of Excel. Learn more: https://go.microsoft.com/fwlink/?linkid=870924

Comment:

find out how booths are specified and what is the min requirement for VA. Pre-Fab 8'-0" -- 3'-0"

3'-6"Pre-FabPre-Fab__12,49P1Typically pre-packaged unit including lighting and switchingN/AL15
5Audiology and SLPELECTROPHYSIOLOGYElectrophysiology, Posturography, VestibulographyEXAMTREATMENTRFTRBP----SEE FGIAT9'-0"--3'-6"FlushWood__12 S_6P2, P3, P14Multilevel Switching, Dimming & OccupancyN/AN/A3
6Dental ServiceSPECIALTY EQUIPMENT MECHANICAL ROOMDental Equipment Mech. Room, Mechanical Rooms - Electrical----CS--P----60EXP9'-0"3'-6"FlushWood----14 SExh. (G)(-)2--P3Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A1
6Dental ServiceDENTAL PROSTHETICS LABORATORYLaboratory, Dental Prosthetics--WSFWSFP------AT9'-0"3'-0"FlushWood----15 AG7570602062Return

Exh. (G)

45(-)M137--Multilevel Switching, Dimming & OccupancyN/AN/A5
6Dental ServiceDENTAL TREATMENT ROOMDental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, BariatricEXAMTREATMENTWSFWSFP----SEE FGIAT9'-0"3'-6"FlushWood----12 CS(+)7--Multilevel Switching, Dimming & OccupancyN/AN/A1
6Dental ServiceDENTAL X-RAY ROOMX-Ray Room, Panoramic / Cephalometric (Cone Beam)CLASS 1 IMAGING ROOMTREATMENTRFTRBP----SEE FGIAT9'-0"53'-6"FlushWood--LEAD LINED17 AGL87--P3Multilevel Switching, Dimming & OccupancyN/AN/A1
7OptometryFITTING & DISPENSING, EYEGLASSESFitting & Dispensing, Eyeglasses--RFTRBP------AT9'-0"--3'-6"FlushWood__12 S6757060-42Return40NR2Downlights and accent/displayMultilevel Switching, Dimming & OccupancyN/AN/A2
7OptometryLOW VISION EXAM/ THERAPY/ TRAININGLow Vision Exam/ Therapy/ TrainingEXAMEXAMINATIONRFTRBP----SEE FGIAT9'-0"--3'-6"FlushWood__12 S_6Multilevel Switching, Dimming & OccupancyProvide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.N/A3
7OptometryPRE-TESTING/ INTAKEPre-Testing/ IntakeEXAMEXAMINATIONRFTRBP----SEE FGIAT9'-0"--3'-6"FlushWood__12 S_61Multilevel Switching, Dimming & OccupancyProvide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.N/A2
7OptometryVISUAL FIELDS ROOMVisual Fields Room, Photography Room, Ultrasound Room, Tomography Room, Imaging Room, OCT LaserEXAMEXAMINATIONRFTRBP----SEE FGIAT9'-0"--3'-6"FlushWood__12 S_7Multilevel Switching, Dimming & OccupancyProvide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting.N/A2
8Mental HealthQUIET ROOMQuiet Room for PatientsEXAMTREATMENTCPTRBP----SEE FGIAT9'-0"3'-6"FlushWood----35 S4--Multilevel Switching, Dimming & OccupancyN/AN/A1
8Mental HealthBIOFEEDBACK TREATMENT ROOMBiofeedback Treatment RoomEXAMTREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----15 S4--Multilevel Switching, Dimming & OccupancyN/AN/A2
9Specialty Care ServicesPULMONARY FUNCTION ROOMPulmonary Function - AnalysisEXAMTREATMENTWSFRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 G6--Multilevel Switching, Dimming & OccupancyN/AN/A2
9Specialty Care ServicesTREADMILL ROOMTreadmill RoomEXAMTREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 MS6--P9Multilevel Switching, Dimming & OccupancyN/AN/A2
9Specialty Care ServicesEKG TESTING ROOMEKG Testing RoomEXAMEXAMINATIONRFTRBP----SEE FGIAT9'-03'-6"FlushWood----12 SOne per wall--Multilevel Switching, Dimming & OccupancyN/AN/A2
9Recreation TherapyGROUP THERAPY ROOM, MUSICCreative Arts - Group Therapy Room - Music--TREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 CG8--Multilevel Switching, Dimming & OccupancyN/AN/A1
9Recreation TherapyGROUP THERAPY ROOM, ARTCreative Arts - Group Therapy Room - Large--TREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 CG8--Multilevel Switching, Dimming & OccupancyN/AN/A1
9Recreation TherapyWEIGHT ROOM, SMALLRecreation Therapy Exercise / Weight Room - Small--TREATMENTRFRBP----SEE FGIAT9'-0"3'-6"FlushWood----34 AG12--Multilevel Switching, Dimming & OccupancyN/AN/A--
10PHYSICAL THERAPYPHYSICAL THERAPY GYMTreatment Exercise Area (includes workstations therapists)EXAMTREATMENTRFRBP----SEE FGIAT9'-0"3'-6"FlushWood----14 S14--P14Multilevel Switching, Dimming & OccupancyN/AN/A4
10PHYSICAL THERAPYActivities Daily Living (ADL) TrainingADL Evaluation and Training Center, Toilet, Tub, Bed, Kitchen, LaundryEXAMTREATMENTRFTRBP----SEE FGIAT9'-03'-6"FlushWood----15 S4--Multilevel Switching, Dimming & OccupancyN/AN/A
13Imaging ServicesRADIOLOGYRadiology, ES: General Purpose Radiology RoomCLASS 1 IMAGING ROOMTREATMENTWSFRBP----SEE FGIAT9'-0"54'-0"FlushWood--LEAD LINED15 LS85P3, P13Fully dimmable, occupancy sensorN/AL22
13Imaging ServicesC.T. CONTROL ROOMCT Control Area, X-Ray - Computed Tomography - ControlTREATMENTWSFWSFP----SEE FGIAT9'-0"53'-0"FlushWood--LEAD LINED12 LS45M146--P3Multilevel Switching, Dimming & OccupancyN/AN/A4
13Imaging ServicesC.T. EQUIPMENT ROOMCT Equipment Room, X-Ray - Computed Tomography - Indep View Console--WSFWSFP------AT9'-0"56'-0"FlushWood----45 AG750M147--P3, P13Multilevel Switching, Dimming & OccupancyN/AN/A2
13Imaging ServicesC.T. SCAN ROOMCT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography - ScannerCLASS 1 IMAGING ROOMTREATMENTWSFWSFP----SEE FGIAT9'-0"54'-0"FlushWood--LEAD LINED15 ALG7--P3, P13Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesMAMMOGRAPHY SCAN ROOMMammo - X-ray, Mammography RoomCLASS 1 IMAGING ROOMTREATMENTRFTRBP----SEE FGIAT9'-0"53'-6"FlushWood--LEAD LINED12 LS7--P3Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesRADIOGRAPHIC / FLOURO SCAN ROOMRadiographic / Fluoroscopic (R/F) RoomCLASS 1 IMAGING ROOMTREATMENTWSFWSFP--SEE FGIAT9'-0"53'-6"FlushWood--LEAD LINED15 AGL7--P3, P13Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesULTRASOUND SCAN ROOMUltrasound RoomCLASS 1 IMAGING ROOMTREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----12 S
7--P3, P13Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesPACS SERVER ROOMX-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System (PACS)--RFTRBP---AT9'-0"3'-0"FlushWood----15 GK504--P3, P13Multilevel Switching, Dimming & OccupancyN/AN/A4
13Imaging ServicesMRI CONTROL ROOMMRI Control Room, X-Ray - Magnetic Resonance - Control, MRI Zone 3CLASS 1 IMAGING ROOMEXAM - MRIRFTRBP----40AT9'-0"3'-0"FlushWood----12 GS45M146--P3Multilevel Switching, Dimming & OccupancyN/AN/A4
13Imaging ServicesMRI EQUIPMENT ROOMMRI System Component Room, X-Ray - Magnetic Resonance - System ComponentTREATMENTRFTRBPRWC4'-0"AT9'-0"114'-0"FlushWood----35 AG4050M147--P3Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesMRI FERROMAGNETIC DETECTIONX-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI Zone 2, MRI Viewing RoomEXAM - MRIRFTRBP----SEE FGIAT9'-0"11, 164'-0"FlushWood----15 G75706040122Return40NR1--P3Multilevel Switching, Dimming & OccupancyN/AN/A1
13Imaging ServicesMRI SCAN ROOMMRI Scanning, X-Ray - Magnetic Resonance - Scanner,EXAM - MRIWSFRBP----SEE FGIATVARIES11,13,164'-0"FlushWood--R/F Shielded175706040122Return
Exh. (S)50NRM172--P3Multilevel Switching, Dimming & OccupancyMRI rated fixturesN/A1
13Imaging ServicesREADING ROOMMRI Viewing Room, X-Ray - Magnetic Resonance - Viewing--CPTRBP----40AT9'-0"3'-0"FlushWood----12 GS406--P3Multilevel Switching, Dimming & OccupancyN/AN/A6
13Imaging ServicesBONE DENSITOMETRYBone DensitometerEXAMTREATMENTRFTRBP----SEE FGIAT9'-0"3'-6"FlushWood----35 S7--P3Multilevel Switching, Dimming & OccupancyN/AN/A2
14Pathology and Laboratory MedicineSPECIMEN COLLECTIONBlood Specimen Collection, Alcove - Specimen Collection Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory-Venipuncture, Blood DrawEXAM__WSFWSFEP------AT9'-0"3--_____64Multilevel Switching, Dimming & OccupancyMulti-level switching or manual dimmingN/A2
14Pathology and Laboratory MedicineSPECIMEN ACCESSIONING, PROCESSING & DISTRIBUTION ROOMSpecimen Accessioning, Processing & Distribution RoomLABORATORY WORK ROOM--WSFWSFEP------GYP/EP or AT-SP9'-03, 73'-6"Flush w/ Narrow VisionWoodNarrow Vision--15 AGOne per wall, 6' spacing, one adjacent to sinkOne at each workstationMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/AOne at each workstation
15Pharmacy ServicePHARMACYPharmacy, Pharmacy, PACT 3 (Controlled Substance) (w/3 AutoDispensing)PHARMACY--RFRBP------AT9'-0"--6'-0"FlushMetal--200 AS715P5Multilevel Switching, Dimming & OccupancyN/AN/A9
15Pharmacy ServicePHARMACY DISPENSING WINDOWDispense/Consult Window, Workroom, PharmacistPHARMACY--RFRBP------AT9'-0"--------OPEN12Multilevel Switching, Dimming & OccupancyN/AN/A5
15Pharmacy ServiceCLEAN ROOM, COMPOUNDINGPharmacy - Clean Room - Chemotherapy Compounding----RFRFP------GWB:P9'-0"37'-0"Single Slide Auto Sliding DoorAluminum/ GlassYes--85068686020302Exh. (S)55(-)M1214--P10
Multilevel Switching, Dimming & OccupancySealed fixture, flat lens surface on exteriorN/A5
15Pharmacy ServiceIV ADMIXTUREPharmacy - IV Admixture - Low Volume----RFRFP------GWB:P9'-0"37'-0"Single Slide Auto Sliding DoorAluminum/ GlassYes--85068686020302Return55(++)M1214--P10
Multilevel Switching, Dimming & OccupancySealed fixture, flat lens surface on exteriorN/A5
15Pharmacy ServicePRESCRIPTION DISPENSING AREAPrescription Dispensing Area - OmniCell Station----RFRFP------AT9'-0"3-----------68--Multilevel Switching, Dimming & OccupancyN/AN/A2
15Pharmacy ServiceSECURE STORAGE VAULTSecure Storage, VaultCLEAN WORK ROOM/ CLEAN SUPPLY--RFTRBPRWC4'-0"--GWB:P9'-0"3'-0"FlushHollow Metal----11--Multilevel Switching, Dimming & OccupancyN/AN/A--
15Pharmacy ServiceANTEROOMAnteroom, Compound Sterile Preparation--WSFWSFEP------GWB:SP9'-0"37'-0"Single Slide Auto Sliding DoorAluminum/ GlassYes--85068686020302Return55(+)M122--Multilevel Switching, Dimming & OccupancySealed fixture, flat lens surface on exteriorN/A--
17Business OfficeSECURE CASH ROOMSecure Money Handling Room--RFTRBP------AT9'-03'-0"Flush w/ 1-Way ViewerSteel----200 GV4--Multilevel switching/dimming/occupancyN/AN/A1
18EngineeringBIOMED. REPAIR SHOPRepair Shop, Biomedical Eng.----RFRBP------AT9'-0"3'-6"FlushWood----35 AGExh. (G)(-)M710--P4, P6Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A2
19LogisticsLOADING DOCKReceiving/ Shipping Dock----CSRBEP------EXP.--86'-0"FlushWood----44 APW7-60--Exh. (G)(+)M52--Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A2
19LogisticsMAIL ROOMSupport: Mail Room and Dist. Center, Mailing Room - Prosthetic Appliances----RFRBPRWC4'-0"--AT9'-0"3'-0"FlushWood----15 G4--Multilevel Switching, Dimming & OccupancyN/AN/A4
19LogisticsGAS CYLINDER STORAGEStorage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior----WSFRBPRWC4'-0"--AT9'-0"3'-0"FlushWood--45 MIN34 GExh. (S)
(-)1--Multilevel Switching, Dimming & OccupancyN/AN/A--
19LogisticsBIO-HAZARD STORAGEStorage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous WasteREGULATED WASTE--WSFWSFEPRWC4'-0"--GWB:SP9'-0"33'-6"FlushHollow Metal----34 G1--Multilevel Switching, Dimming & OccupancyN/AN/A--
19LogisticsSTORAGE WAREHOUSEBulk Storage, General Storage, WarehouseCLEAN WORKROOM/CLEAN SUPPLYCSRBP------Exp10'-0"6'-0"FlushWood----45 AGminimum, 1 per wall, not to exceed 12' spacing--Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A
19LogisticsBREAK DOWNBreak DownCLEAN WORKROOM/CLEAN SUPPLYRPTRBEP------AT9'-0"84'-0"FlushWood----34 AG1--Multilevel Switching, Dimming & OccupancyN/AN/A
20Police ServicePOLICE HOLDING ROOMHolding Room----CSRBP------GWB-PT9'-0"3,153'-6"FlushHollow MetalHalf Glass w/ Laminated Glass18 P0--Multilevel Switching, Dimming & OccupancyTamperproof fixture designN/A--
20Police ServiceOPERATIONS ROOMOperations RoomRFTRBP----40AT9'-0"3'-6"FlushHollow Metal----200 APSM1508Multilevel Switching, Dimming & OccupancyN/AN/A4
20Police ServiceSECURE STORAGESmall Arms Armory, Storage - SecureRFTRBP------AT9'-0"3'-0"FlushHollow Metal----200 P757060-42ReturnNRNR1--Multilevel Switching, Dimming & OccupancyN/AN/A1
21VCSRETAIL AREARetail AreaEXAM - PUBLIC SPACERFTRBP----SEE FGIAT9'-0176'-0"Flush w/ Full VisionWoodFull Vision47 KM7, 9M4One per wall, 6' spacing--Multilevel Switching, Dimming & OccupancyTrack or adjustable accent lighting for retail displays.L53
23OI&TTELECOMM.Telecommunications Room/ Closet, IT Telecommunications Room----RFTRBP------EXP.12'-0"3'-6"FlushWood----34 AS64755530----NR6--P15Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A--
23OI&TSERVER ROOMCentral Server Room----RFTRBP------EXP.12'-0"3'-6"FlushWood----34 AS7281606M810--P15Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A--
23OI&TI.T. WORKROOMIT Workroom, Equip. Configuration/ Repair----RFTRBP------AT9'-0"3'-0"FlushWood----35 AG10--P4, P6
Surface or chain mounted 1' x 4'Occupancy/vacancyN/AN/A8
24SPSANTEROOM, SOILED TRANSITIONAnteroom, Soiled Transition/Drop-OffDECONTAM
ROOM--RESRESEP------GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG667260301010Exhaust (G)40(-)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A2
24SPSDECONTAMINATION ROOMDecontamination Work Room, Scope Decontamination RoomDECONTAM
ROOM--RESRESEP--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG6672603066Exhaust (G)40(--)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A4
24SPSCart WashCart Wash--RESRESCT--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG70751010Exhaust (S)40(-)M18, M19One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A
24SPSWater Treatment Storage RoomWater Treatment Storage Room--RESRESEP--GYP-EP9'-03, 73'-6"FlushSteel--15 AG70751010Exhaust (G)40(-)M18, M19One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A1
24SPSREPROCESSING ROOM, SCOPEReprocessing Room, Scope--RESRESEP--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG6672603066Exhaust (G)40(-)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A2
24SPSInstrument AssemblyInstrument Assembly--WSFWSFEP--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG6672603044Exhaust (G)40(++)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A4
24SPSSterilization AreaSteam Sterilization Area, Low Temp Sterilization Area--RESRESEP--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG667560301010Exhaust (G)40(++)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A2
24SPSCooling AreaCooling Area--RESRESEP--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionSteelNarrow Vision--15 AG667560301010Exhaust (G)40(++)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A1
24SPSEquipment Room, Steam GeneratorEquipment Room, Steam Generator--RFTRBEP--ACT-SP9'-03, 73'-6"FlushSteel--15 AG851010Exhaust (G)45(-)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A--
24SPSClean DispatchClean Dispatch--RFTRBEP--ACT-SP9'-03, 77075603044Exhaust (G)40One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A1
24SPSSTORAGE, CLEAN SCOPEStorage, Clean ScopeCLEAN SUPPLY--RESRESEPRWC4'-0"--GYP-EP9'-03, 73'-6"Flush w/ Narrow VisionWoodNarrow Vision--15 AG667555304(+)One per wall--2 X 2 recessed lensedMultilevel Switching, Dimming & OccupancyGyp ceiling - lights to be sealed type/flange mountedN/A--

Interior Finishes Notes Interior Finishes Notes

General Notes
A.Hollow metal frames and doors to be painted.
B.Window sills to be solid surface fabrication.
C.Resilient base to be 4", unless otherwise noted.
D.Provide painted finishes only on inside of exterior walls (no wall covering).
E.Floor material transitions to occur at centerline of door, unless otherwise noted.
F.Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.
G.Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.
H.Coordinate height of wall protection with wall-mounted devices.
I.Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and
lobby/waiting areas.
J.Soffit above upper cabinets to be gypsum board.
K.Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.
L.Solid surface countertops to have sides and backsplash at walls.
Schedule Notes
1.CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.
2.Tile base to be coved.
3.Integral coved base 6" high tightly sealed to walls.
4.If sink is present, use hard suface flooring as noted.
5.Lead lined walls and control area view window.
6.Flooring and base to match adjacent area flooring material and base.
7.Use gasketed, clip down ACT/grid system
8.Use slip-retardant finish on floor material
9.Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.
10.Note that if wall saver designed chairs are used, no wall protection is required.
11.Extend all room partitions to structural deck.
12.CT above countertop on wall.
13.Ceiling height as required to acommodate equipment.
14.Cove QT base, 6" high.
15.No separate trim at top of base, use alternate method to seal to wall.
16.Ceiling suspension system should be fabricated from nonferromagnetic material.
17.Aesthetic specialty materials may be used as accents where the design and budget permits.
18.Ceiling tile to meet USDA regulations.
19.Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces
20.Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.
21.Wall CT and ceiling to meet building code light reflectancy standards.
22.Space may be room or area within a room. Coordinate finishes with adjacent spaces.
23.Provide 3/4" painted plywood where required by Telecommunications.
Finish Codes
ATAcoustical Ceiling Tile
AT-SPAcoustical Scrubbable Ceiling Tile (with sprayed plastic finish)
CPTCarpet Tile
CSConcrete, Sealed
CTCeramic Tile (Wall)
EPEpoxy Paint
EXPExposed Ceiling
MATModular Carpet Walk Off Mat
PPaint
PTPorcelain Tile
QTQuarry Tile
RBResilient Base
RESResinous Flooring and Base
RFRubber Flooring
RFTResilient Floor Tile
RSFResilient Sheet Flooring - Heterogeneous
RWCRigid Wall Covering (Wall Protection)
SDStatic Dissipative Tile
SSolid Surface Fabrication
WSFWelded Seam Sheet Flooring - Homogeneous

Doors and Hardware Notes Doors and Hardware Notes

General Notes
A.Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to
the group.
B.All doors to be 7'-0" high, unless otherwise noted.
C.Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix.
Schedule Notes
1.Hollow metal frame cased opening
2.Two door (in swing and swing out) acoustical door and frame assembly.
3.Two doors required at this room/space.
4.Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.
5.Provide STC 50 rated acoustical door.
6.No door in this room/space.
7.Equal leaf pair of doors.
8.Lead lined door and hardware.
9.Space may be a room or area within another room. Omit door if space is not a separate room.

Electrical Notes

ELECTRICAL NOTES

POWER NOTES LIGHTING NOTES

P1.Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.L1.EMI/RFI emissions to be controlled
P2.Receptacles on all wallsL2.Dimmable to 5 fc
P3.Coordinate electrical connections with equipment to be installed. Receptacles on all walls.L3.May not have ceiling - then use industrial fixture type
P4.Plug strip at 44" above countersL4.May not have ceiling. If no ceiling, use industrial fixture type
P5.Multiple receptacles above and below desk for device chargingL5.Treat like a store. Adjustable lighting, General lighting.
P6.Cord reel(s) for freestanding workbenchesL6.No ceiling in these rooms. No prescription for lighting.
P7.All outlets on dedicated circuits.
P8.Cord reel(s) for freestanding workbenches
P9.Treadmill on dedicated circuit
P10.Each hood on dedicated circuit
P11.Provide receptacles per equipment plan
P12.Electrical to review redundancy requirements with OIT guidelines.
P13.Receptacle above ceiling for overhead lift
P14.Recessed power quad floor box
P15.L21-20R receptical above each rack
P16.

Mechanical Notes

MECHANICAL HVAC NOTES

M1.Intentioanlly Left Blank
M2.Per ASHRAE 62 for ventilation, and FGI Guidelines for NC
M3.General Open Office area
M4.General Open/Public area
M5.Per ASHRAE 62 for ventilation if interior enclosed space.
M6.Comply with ASHRAE 15 if Special Refrigeration Systems are used
M7.If chemicals are used, provide specialized exhaust
M8.Data Center
M9.Transfer air to Food Prep Kitchen
M10.Intentioanlly Left Blank
M11.MEP Room
M12.See USP-797 and -800
M13.Counter-height specialized exhaust system required
M14.Provide air conditioning and ventilation per imaging manufacturer recommendations
M15.General Office Area
M16.Verify specific vendor/manufacturer requirements.
M17.Non-ferrous construction
M18.Provide cooling only air terminal unit to serve the manual equipment wash room.
M19.Provide a dedicated wet exhaust system