Exhibit_A-2_Plans.pdf
PDF 8 MB Posted
- Solicitation number
- 0000036375
- Issued by
- Trinity County, California
About this file
These are construction and engineering drawings for a Synthetic Natural Gas (SNG) Plant project for the California Department of Corrections and Rehabilitation (CDCR), with bid number C5612927-D Re-Bid 1. The plans detail a comprehensive site layout for a liquefied petroleum gas (LPG) system, including a 30,000-gallon LPG storage tank, flare stack, air blend mixer, liquid supply pump, and associated piping and safety systems. The drawings provide technical specifications for equipment installation, including seismic safety controls, emergency shut-off stations, fire protection systems, and detailed pneumatic and control system configurations.
The project drawings include extensive technical details such as material lists, valve specifications, piping diagrams, and safety signage requirements. Key safety features include emergency shut-off valves, fire extinguisher locations, alarm stations, and seismic detection systems. The design incorporates multiple redundant safety mechanisms, including pneumatic controls, bypass valves, and fail-safe systems for the LPG infrastructure. The plans are approved by both the California Department of Corrections and Rehabilitation Access Compliance Review and the California State Fire Marshal, indicating compliance with state regulatory standards for industrial gas system installations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum_2.pdf | ||
| Exhibit_A-1_SPECS.pdf | ||
| Exhibit_B-1-Public_Works_Rate_Sheet.xlsx | XLSX spreadsheet | |
| IFB_Package_C5612927-D__Re-Bid_1_8-8-2025.pdf | ||
| Addendum_1.pdf | ||
| Addendum_3.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
-0
, 507 i
1. . ' t ·· • l • i j
'0'!f ' • ~"""" ' ':
~• H
) i i;
' ~ . . l ._ .
' ; \, > i; '.': .. ;
·. l '·
' i r
' '·; ... 24 ·•···• ,, \ 1·.• .·•·. '• . . · . c:~.:,,_, ;"\. : L - .
~ -w., .. -
POC (E) 1-1/4"M~-,...-
.l ~ •
V:\1842\active\184200751\civil\drawings\C1_0_0.dwg, 11/19/201910:23:36 AM, ijosifek
\ i
I
FIRE PROTECT~
SYSTEM POC i '
SEE DWG P2.0.0
I .
\ I \ I l\ ' \
GENERAL NOTES
1.
2.
REFER TO SHEET CO.O FOR CIVIL ABBREVIATIONS, NOTES AND SYMBOLS.
THE UNDERLYING SCANNED IMAGES OF ORIGINAL AS-BUILT SITE
DRAWINGS CONTAIN ADDITIONAL INFORMATION ABOUT THE PROJECT
SITE THAT IS FOR REFERENCE ONLY. OVERLAID NEW CONTENT
SPECIFIES NEW WORK THAT IS PART OF THE CURRENT PROJECT AND
CONTRACT, ; · .. ··.
I i i • \
I ' I
• . "•.J
' ! f
' !' I I . .
NOTE: SHEET C1 .0.0 IS PART OF THE
SYNTHETIC NATURAL GAS PLANT DRAWING
SET AND COVERS THE SAME AREA AS C1.19
AS SHOWN ON THE KEY PLAN
KEY PLAN ' ., ·-~
' ' 1--~-------~-------1 ' i
' I .
' t ;
I .
C1.11 tl'.
w z
[Z Cl
8~ en N
I
:z
C
...I (.) -. 10 ,.._ N .,,.
co -tl'.
LU
i Cl
TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 Exhibit A-2
N
1 o· -o"
8' HIGH CHAIN LINK FENCE
WI BARRIER WIRES (TYP.)
62'-10"
15' -0" 15' -0" 9' -8"
. 0.2%
SITE GRADING
SCALE: N.TS.
5' J'
15'
6" AB
(TYP)
58'
CONG TANK FOUNDATION,
SEE STRUCTURAL DETAIL
@·, SITE GRADING
~ SCALE: N.T.S.
'20/
X
130.6
AB
1 ______ ,
30.000 GALLON~'\".~.;:::><:;::::--, 5"-0"
. TANK. ii;;
\--=--_-_=--:_:l @-y\--
GENERAL NOTES
I I
NEW GRADE, FILL
TOE OF SLOPE
(SEE NOTE 5)
15' -Q"
·•.-· f '.
6" AB
1. SEE PLUMBING DRAWINGS FOR SYNTHETIC NATURAL GAS PIPING AND EQUIPMENT PLAN AND DETAILS.
8'-2"' 5'-0"
6"AB
(TYP)
8'
6" CONG/ 6' AB --'
8' HIGH CHAIN LINK FENCE
WI BARRIER WIRES (TYP.)
<.·1
12' (E)EP
·1 I
. 2.0,; I
(E~ ~~R~ICE ROAO 7
r-- 8' HIGH CHAIN LINK FENCE
/ _ ;':R~:E~
' 130.42 .
AB
2. ALL CONSTRUCTION SHALL CONFORM TO. AT A MINIMUM, THE CBC 2016, CMC 2016, CFC 2016 AND ALL APPLICABLE ADA CODES.
3. REFER TO SHEET CO.O FOR CIVIL ABBREVIATIONS. NOTES AND SYMBOLS.
4. SEE SHEET E2.0.0 FOR BOLLARD DETAIL 4/E2.0.0 AND BOLLARD PLACEMENT.
5. HYDROSEED WITH NATIVE OR NONINVASIVE SPECIES APPROPRIATE TO THAT SPECIFIC LOCATION TO INACTIVE CONSTRUCTION AREAS (PREVIOUSLY GRADED AREAS INACTIVE FOR 10 DAYS OR MORE). HYDROSEE MIX TO BE APPROVED BY THE ENGINEER.
. //:7 / I '
,. ; · ·•,if' UJ ciwo ,...< / iN5 N. (\, i i' ,_.._ l i ! 1' / I ' •• i ! {
- r'-J_ :, I ;i st n.
Ii I J NO ' I .-
/ /jy, ! 1" W I i/ w
I I I /; ~ i--
/ /1 ;· I 11ro o Jill_ ow
NO
,- I-
I i:/ ' I . I j ;
l / ;.: '
'v (\j
!t
I
' /I
[ill]
(J') ()J ·o
~z ,-0
X
SCALE:
I n i rn I st i.J ~1 I
. ' I I I I I
I I I !
I 1 i :
I , t / I
/ .ro ~ / ,/ ✓/ ciCL
I r .- ~o ! i (0 .-1- , I N .
·/ ci CL : r00 I __ ,_
. I I I
1 I ! : . k
- - ··----- -·---- _, ..... - - --·- ----- ----- i
' 7 .-, -- '
- ' --. ' -. • F ✓ -- -
PIPING BELOW GROUND
· · SEE PLUMBING PLAN
V) ·o -z ::, (.'.)
X
4" CHAIN LINK SWING GATE W/
BARRIER WIRES @ ~
C2.6.0 vi§;! .
-Cl
(j \ 0.. ·.
- ,., Q
I -~·· j.
~\ I
C)
I I
I C)
I I g
I I I I
··1
42'-4" __:X::,___ __ ___;~--1
131.)
MATC1 EX
___ i __ ~_j I
, o
C)
-----(E) GAS SERVICE UNDER
GRADE FROM UTILITY.
(E) UTtTY POLE AND GUY WIRE
\ PROTE\T IN PLACE
I (l.
i
Q
_\1\ /1 .
(E) FENCE
Q.
I N u
"' '-' z i u
N ...
00 -
I r----(E) GAS PRY
□ \ &METER :r------WL\-( CATHODIC
!--- 8' HIGH CHAIN LINK FENCE
WI BARRIER WIRES (TYP.)
VARIES 42' -4" TO 44' -0"
GB
.VARIES VARIES.,
132.6
MATCH EX
EXISTING FENCE --
MATCH EXISTING GRADE
(SEE PlJ\N) SEE PlAN)
- .~~~!""!~.,.,,,..,~~:,-i\~.,~c-~, !"/~. ~Y!s.~~~"';'c~~~"i'.":,.(z,"',~""''\'• ~~~~~":l"f!:3~':!.!", ~~.!!',;.,,'s', ~7~·
EXISTING GROUND 6' AB
(TYP)
SITE GRADING
SCALE: N.T.S.
P OTECTION PANEL,
S E SHEET E1.19
-WAY BYPASS
ALVE ASSEMBLY,
EE SHEET P2.0.0
KEY PLAN
APPROVALS
CALIFORNIA DEPARTMENT OF CORRECTIONS
AND REHABILITATION ACCESS COMPLIANCE
REVIEW
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE OR
APPROVE ANY OMISSION OR DEVIATION FROM THE
APPLICABLE REGULATIONS.
TRACKING NUMBER: lib! DATE: l·'"T·Zou:>
REVIEWER: ~ 44¥4'1I.
CALIFOR~\;RE MARSHAL.
APPROVED
FIRE AND PANIC ONLY
0:: . w z Q en w z '.3 Q.
0:: w i iii
0 -' !
w..J (.)~"'
~en~ eno fll 1---f:;,
- z ~ '-q~ g ..Joo~ ...... a: <...-i .. .. a.. Cl co !s ~ .9-...., ..,. O'> . ,;:I z wc5co · t- _<D ~ ~~~ ~ ~ ?i 0 >"en >- <t o w " >- OU Lll u :r: ~fisui ·ffi g ~ w Z.,:....J ~ C
~ ~ ~ ~ ~ .,0.. .!
a.. -oo · - -~ ~o<C tn ~ \ '"'- oN> a ... ........ ___ ..__..._ .... _~
APPROVAL or THIS Pl.All DOES NOT AUTHORIZE SHEET NUMBER O
OR APPROVE ANY OMISSION OR DEVIATION FROM ;ij
THE APPLICABLE REGULATIONS. FINAL APPROVAL :;-
IS SUBJECT TO FIELD INSPECTION. ONE SET or C 2· Q Q ~ APPROVED PLANS SHALL BE AVAILABLE AT TliE j
PROJECT SITE AT IILL TIMES. ■ ■ N :; ~L _________________________________________________________________________________________________________________________________ L_·~RE~v~1t:w~to~~:'~#~::::S~J=A=N=0=2::::::W:20:._.~o:F_!*_~s:H:E:E~Ts:Jt
TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 co 0 .. --co -0 N
N co
PERMANENTLY WELD
(E) M.AN HOLE COVER
(E) STEAM UG PIPING
TO BE ABANDON~D
IN PLACE
DEMOLISH ALL VALVES FLOATS,
PIPING AND ACCESORIES
DEMOLISH (E) VENTS
AND REPAIR EXISTING
MANHOLE COVER.
COMPLETELY FILL PIT
Z,,,7,W~WITH SAND
CAP PIPING AT PENETRATION
NATIVE SAND, IMPORTED LOW EXPANSION
POTENTIAL MATERIAL OR CLASS 2 AB
AC PAVING TO MATCH EXIST THICKNESS
ADD OVERLAY
ENTIRE WIDTH .
IN EXISTING
PAVED AREAS
z Q !- (/) C
~ (.) V> :;, <( ..J"' L,J
ma. zb
:. ::, z
SAWCUT
CLASS2AB 8 L,J
z 0 .... "' () 0 <(
0, a.
NOTES:
t() i!:
9"THICK MIN 3/4" x 1-112" _../
CRUSHED ROCK
WRAPPED WITH
GEOTEXTILE FABRIC,
12" MINIMUM WRAP
OVERLAP, SEE NOTE 2
INSIDE OUTSIDE
ROADWAY ROADWAY
9"MIN
(TYP)
PIPE 00+24"
DETECTABLE MARKING TAPE
18" DEEP IN NON ROAD AREA,
24" DEEP IN ROAD AREAS
TRENCH EXCAVATION
BACKFILL MATERIAL
CAP PIPING AT PENETRATION
1. TRENCH SHEILD SHALL NOT DISTURB BEDDING BELOW TOP OF PIPE, TRENCH SHALL BE "BENCHED"
FOR SHEILD.
@ ~~:1~:L STEAM PIT DEMOLITION
90e BEND ti' g ff p,:., '<' it & "' ref &
6" 11 1/4° 1,108 1 1 22 112· 2,207' 1 2 45• 4,328 2 3 90• 7,996 2 4
PLUG 5655 2 3
8"
I:
45° BEND
REACTION BEARING AREAS FOR
HORIZONTAL WATER PIPE BENDS
BASED ON TEST PRESSURE OF 200psi
1 1 1 1 2 1 1 1 3 1 1 2 5 1 1 2 4 1 1 2
TEE INTERSECTION
2 1 3 1 5 1 8 1
2. TO BE USED WHERE TRENCH BOTTOMS ARE DISTURBED BY CONTRACTOR'S TRENCHING OR PIPE
INSTALLATION PROCEDURES OR WHERE EXCAVATION OCCURS BELOW GROUND WATER TABLE.
NOTES:
1. REACTION BEARING AREAS ARE IN
SQUARE FEET MEASURED IN AVERTlCAL
PLANE IN THE TRENCH SIDE AT AN
ANGLE OF 90' TO THE THRUST VECTOR.
2. CONCRETE SHALL BE 2500psi OR CLASS
C CONCRETE.
3. CONCRETE SHALL NOT CONTACT BOLTS,
GLANDS OR ENDS OF MJ FITTINGS.
4. TRENCHES SHALL CONFORM TO STANDARD
DETNL. (SEE DETAIL THIS SHEEn.
5. ALL BENDS AND INTERSECTIONS SHALL
HAVE CONCRETE THRUST BLOCKING.
PROVIDE POLYETHYLENE PLASTIC SHEET
BETWEEN THRUST BLOCK AND FITTING.
6. SEE e•, 90" BEND VALVE FOR HYDRANTS
FOR ADDITIONAL SAFETY FACTOR.
TYPICAL PIPE TRENCH SECTION
SCALE: NTS
AC OR CONG
BROOKS METER BOX
W / H20 COYER OR
EQUAL SIZE AS REQD
PIPE RISER SHALl
BE 4", UNLESS
NOTED OTHERWISE
AB OR DIRT
' g•
·. i' 11 1, 11 l;
24"x36~ QUAZITE UTILITY BOX, PART NO. PG2436B818 OR
APPROVED EQUAL. STACK BOXES
TO OBTAINED REQUIRED DEPTH.
QUAZITE TRAFFIC BEARING COVER,
PART NO. PG2436HA0009
OR APPROVED EQUAL.
1WO WAY 4" x 2-1/2~
FIRE DEPT. CONNECTION,
THREADS TO MEET BASE
STANDARDS. PAINTFED. ·
COLOR #20050.
!---,,+--COVER SLEEVE. PAINT
~ - FED. COLOR #20050.
~-,-- IDENTIFICATION PLATE
.. ,',,RADE ,, __ """""' """'"" '""""' '"' .• ,, .. '"""""""'
•• • • .. .. .J •• '
LANGED
FITTING
MECHANICAL
COUPLING7
36n SQUARE x 6" THICK
CONCRETE GRADE PAD
REINFORCED WI
6x6xW1 .2xW1 .2 W.W.F ..
p.,-.;,.;,=-4• MECHANICAL
i. MEGALUG
RETAINING GLAND
18" MIN#67 STONE
THRUST BLOCKING, (SEE
DETAIL THIS SHEET).
FM-UL LISTED
SWING CHECK VALVE
W/ BALL DRIP
. ' 90', BENO - .
·· DUCTILE IRON
. •t THR~:;:~:::~:~~:~ING
DETAIL THIS SHEET).
FIRE DEPARTMENT CONNECTION
GFCI RECEPTACI.
FOR HEATER
ANCliORAll!GLES-\ TO CoNCRET~ \ SlAS TVP!CAL SUPPUt'D WiUNIT fROMWATt':R
SUPPLY MAIN
6"-1"
PROI/IOE INSUI.AT£D ENC.l.OSURE FOR
/!,I3CJVC.. GROUND BACK FLOW PREVENTER.
ENCLOSURE SHAU. BE CONSTRUCTED Of STUCCO AUJt.!INUM/INSULATION SANDWICH PANELS, 8ACl<FLOW .PREVENTER · SHALL BE
ACCESSIBLE THROUGH DOORS OR
REM0VA13LE PANELS: ENct.,OSURE; To EIE
EQUIPPED W/ MANUFACTURER'S STANDARD
HEATER PACKAGE -, 1500W/120V/!•;
COORDINATE CONNECTION -W/ E.C ••
RO\IIOE RPZ STYLE BACK FLOW
PREVENTER ASSEMBLY AS INOICATEO, _ WITH
SPRING CHECKS, O.S.&Y. GATE V'AL\iES, AND TEST COCKS. ENCLOSURE TO HAVE
OPENING TO PIPE REI..IEF VALVE DRAIN -TO
GAAOE OUTSIDE ENCLOSURE. Pi:1-0VIOE AIR ~ nmNG FOR REI..IEF VAL.'tl'E" ORAIN.
· /iROVIOE S4"X78"X6• TI·UCK CONCRETE ' SLAB Win{ 12" TURNED DOWN EOOE, - --
RE-!NFORCE WITH W.W.F. MAT. SLAB TO -
. SE 'J~ A80v'E ;..""tJRROU"NDiNG GRAW.
NOTE: SIZE OF PAO MAY VARY WITH
ENCLOSlJRE MANUFACT\JREft
TWO 3/i' CONDUITS FOR Al.ARMS ~ND
KEATER. -
NOTES:
6'-1"
1. LOCATION OF STREET TAP Nro BACK Fl.OW PREVENiER SHA1.L BE COORDINAlID W/ WATER UTIUTY. CONJAACTOR SIW.L PAY WAlER TAP· FEES.
FIRE l'fiOTECTlON 2. PROVIDE TAMPER SWITCl-lES. ON BOTH OS&Y VALVES. At.SQ SUPl'lYTOBLOO. PRCN1DE A¾• CONDUIT fOR ALARM WIRING TO 8LOO F"ACP.
SPRlNK!.l:RSYSTlJ! 3. AU. PIPING SHALL eE Cl.ASS 51 C£MOlT UNEO DUCTILE
'"""· 4. PIPING FROM -UNDERGROUND MAIN -TO 8ACKf'l.OW PREV£NTER SHALL BE MECHANICAL JOINT DUCTlLE IRON W/ MEGALUGS OR RESlltA»-IED . JOINT OIJCTII..E IRON. PROVIDE TliRUST BLOCKS AT UNDERGROI.INI) a80WS.
FIRE SUPPRESSION BACKFLOW PREVENTER ENCLOSURE DETAIL
SCALE: 1f2"" 1'-0"
FIRE SUPPRESSION
BACKFLOW PREVENTER
SCALE: NTS SCALE: NTS
! 5" MIN / 8" MAX
CALDER CPLG & PLUG
FOR NON-PRESSURE
LINES. BLIND FLANGE
FOR PRESSURE LINES
PLACE BOX ON
BRICKS ALL
AROUND
......... s
A
30"
5•
VARIES
A
NOTES:
1. THIS INSTAUATION SHALL BE USED ON
EXISTING MANHOLES ONLY WHERE THE
DIFFERENCE IN ELEVATION BETWEEN THE
TOP OF THE OUTLET PIPE AND THE
INVERT OF THE FEEDER OR CCLLECTOR
SEWER EXCEEDS 24".
2. BAND COUPLER SHALL BE A MISSION
SHIELDED TRANSITION COUPLER, MODEL
NUMBER MR02-44 OR APPROVED EQUAL
BAND SHALL HAVE A MINIMUM OF 3
LOCKING BAND STRAPS.
3. PVC OR ABS PIPE SHALL BE USED
INSIDE MANHOLE.
EXISTING
MANHOLE
OPEN END
(TEE TOBE
CUT AT 45°)
WATER $EENOTE2 '
TIGHT SEAL
SEENOTE3
' N
I ' "' 0 I
' "' I
111/4° 1,970 1 1 2 1 1 22 1/2° 3,922 1 2 3 1 1
1 2 1 1 4 1
7. THRUST BLOCK FOR TEE INTERSECTION
SAME AS FOR 90" BEND.
MAINLIN 45" LONG RADIUS
BEND z
STAINLESS STELL
BANOS ANCHORED 24" MIN
45• 7,694 2 4 5 1 1 2 8 1 90" 14,215 4 8 9 2 2 4 15 2
PLUG 10 053 3 5 6 2 2 3 10 1
10" 111/4° 4,433 2 3 3 1 1 2 5 1 22 112· 8,826 3 5 6 2 2 3 9 1 45" 17,312 5 9 11 3 3 5 18 2
MAINLINE
rLoW I SLOPE goo 31 ,983 8 16 19 4 4 8 32 4
PLUG 22 619 6 12 14 3 3 6 23 3
@ ?c~~~~ARD THRUST BLOCKING CLEANOUT
SCALE: NTS
WYE OR BEND
IF AT END OF
LINE
• WITH STAINLESS
60"
;;; STELL BOLTS TO
WALL 24" O.C. (TWO
BANDS MIN.)
SECTIONA•A
t r i'.-¼:~
SEE NOTE 6
SECTION B-B
INSIDE SANITARY SEWER
@ ~A~,O~s CONNECTION
APPROVALS
CALIFORNIA DEPARTMENT OF CORRECTIONS
AND REHABILITATION ACCESS COMPLIANCE
REVIEW
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE OR
APPROVE ANY OMISSION OR DEVIATION FROM THE
APPLICABLE REGULATIONS.
TRACKING NUMBER: -~/-7-U,20
REVIEWER: 4#/111 ;,
CALIF'ORNIA STATE FIRE MARSHAL
APPROVED
FIRE AND PANIC ONLY
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE
OR APPROVE ANY OMISSION OR DEVIATION FROM
THE APPLICABLE REGULATIONS. FINAL APPROVAL
IS SUBJECT TO FIELD INSPECTION. ONE SET OF
APPROVED PLANS SHALL BE AVAILABLE AT THE
PROJECT ITE AT ALL TIMES.
REVIEWED BY:
i ~ ~ Q l!!
z (/) ::c z > u :z
0 a ~ s I- = z (I) w c:, ~ co w <C (!) Cl ::i:: <C :z LU z ~ 0:: <C en
<C Cl :::r;; c:, z z a :z: (/)
0:: <C z <C LIJ 0 <C en (.)
LL (/) ll.l
::J z z u <C 0 0 5':: w u I- I- ll.l (/)
LL u (.) en z 0 w :::> _..J (!) 0:: a::: ~ w 0:: I- Cf)
~ 0 (/) :z w (.) z ll.l Cl
0 :a;;
(/) LL :z
0 (.) 0 I- -a:::
(!) -z z> w _z ~ z u.J
!i: z Cl <C ~ if --' CL :z:
w >- <.9 a I- en
::J LU
c:, <C
LL
"' <O
·2 "' ·-J~ 0"' o ...
0, ~ ~ " _, ·- - < -; ;j 0 .,, - " - 0 m~g co "'i' ~ oO-
t) =a ii <O (.() :-t u a E ..-..-c::
0, a, " *Ue:! "ti .s:28~ -xi Cl) I() (/) CJ) ;! tE • w t;;
(J) a.
z 0 a::
J::
w
:5 a.
w a::
0 z :5 (J) z a:: .
a::
w z (J) w Cl a_ 0 "' w<"' I- 0 f:8 < a:: "' t;; 5 c3 < 0 .
Z CD~ a::: <( _,J ow-
u. [l_ ~
::JO(.)
UN>
I-w w ::c
II)
ti) ..I
Cl
Cl
• -I
IO
(I) z
0::
Cl
_J
-It) .
I", 0 .
N ...,. .
00 -w j::
N ...,.
!3 00 Lit 'II""'
0 . -.
'1>
"' c1;
;j z ..
"' -0 N
<6 -et: w a:, I-
SHEET NUMBER
C6.1
OF # SHEETS
·a :g E g ---
53- " ~ .. • 0 -:,.
"' J, '" v "' / • .> -u '" v
TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 Exhibit A-2 matthew.vanatta Rectangle matthew.vanatta Rectangle
-r a..
0 ..., N
N
If';/ / , .. /! ;;-I / / l/ I I ,4
!/ / / ;J f / / / f
!111 f I I I I
I I I , / / i
I / /
/ rv-.. :
I I , /
,. I I / I /;>/~
11 l/1 , f I I
I / I /_ I / I 1 < , , '
I I I i I ·,-~ i / /1 / / .' / I / / I
' // if r1 I I I I
I
I I I
I
I
If ,/ /-- / / // --- - - -------------------~, 2 5- -------~-----
-- __ , ___ -·-·- --- ; L- '
I I / --- / ' -I I I I/.: ==-----_ ----- -=-:::::::::_:11-_;;_;0IJ.:·:_--____ --____ 1_::2--=9--=---=--=--------
, I; 1//r v)
(E) GRADE ------
I I I I
I' / / , I , , /;
• I ' I ( fi , r , • _ r
1 I I
I I I I I I I I I/ I I ! I /1
I i I I ,/ I / 1
I ! ! I
• 1 ! / Ii
I I I I 1/ I I i I I Ii I / i I I I I
I / . I i ' i I I I ! !
i I ' , i I' I I I I I
I Ii I I I I I ! I :
I
I i
: I
I I I I 1
I i 1
11 I
I I I i 1 Ii I i 11
I ' I I r
' I
I I I
I I I r
"/ / \ ,I -~ ( )
-- MANUAL RELEASE / / _
STATION / - /
r-1- 8" FIRE LINE REFER TO
CIVIL DWG FOR CONT.
I
52'-10"
OIL SEPARATOR
1" DRAINS TO
DRYWELL
CONC. PAD (TYP) (
- 1~' I _, AM
DRY WELL
g "ti G)
I la
GENERAL NOTES
1. DISTANCE AROUND AND BETWEEN STORAGE TANKS SHALL BE PER NFPA 58 SECTION
6.3.1. AND CFC TABLE 6104.3.
2. PROVIDE KNOX BOX FOR THE PROPOSED 8 FT FENCE AND GATES FOR EMERGENCY
INGRESS TO THE SITE.
3. PROVIDE FIRE EXTINGUISHER WITH MINIMUM 18 POUND B:C DRY CHEMICAL
EXTINGUISHER. 4A:40B:C
4. REFER TO SHEET P2.3.0 FOR EQUIPMENT SCHEDULE AND SHEET P2.5.0 FOR PIPING
5.
6, 7.
8.
DIAGRAM AND SIZES.
NOT USED
REFER TO SHEET P2.5.0 FOR SIGNAGE DETAILS.
SEE DETAIL 7, SHEET P2.6.0 FOR SIGN POST INSTALLATION.
REFER TO SHEET P0.0 FOR PLUMBING ABBREVIATIONS, NOTES AND SYMBOLS.
- ---------- 9. SEE SHEET E2.0.0 FOR BOLLARD DETAIL 4/E2.0.0 AND BOLLARD PLACEMENT.
(E) GAS SERVICE UNDER
GRADE FROM UTILITY. ---~ I
(E) FENCE J
(E) FENCE
-I _ J I
I ---- .:--.,.--1,-\
KEY PLAN
N
APPROVALS
- CALIFORNIA DEPARTMENT OF CORRECTIONS
AND REHABILITATION ACCESS COMPLIANCE
REVIEW
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE OR
APPROVE ANY OMISSION OR DEVIATION FROt.t THE
APPLICABLE REGULATIONS.
TRACKING NUMBER: 1114\ - DATE: f·1·2<>Z<>
REVIEWER: ~ ~'ftf
CALIFORNIA STATE FIRE MARSHAL
APPROVED
FIRE AND PANIC ONLY
APPROVAL or THIS PLAN DOES NOT AUTHORIZE
OR APPROVE ANY OMISSION OR DEVIATION FROM
THE APPLICABLE REGULATIONS. f'lNAL APPROVAL IS SUBJECT TO FIELD INSPECTION. ONE SET or
APPROVED PLANS SHALL BE AVAILABLE AT THE
PROJECT SITE AT ALL TIMES.
REVIEWED BY:
_....-::r.~N O 2 2020
"' ~ " z z
! i!i li5 z i "Ill o Ill "" " -"., zi! "'~ ;a ii! ;"' " ~ ; .!, "' w
" "' §~ ~i u a, ..a C ta ..a
V)
::;; z
::i w I-
0 "' i:i "' 0.. z
0 0 0 "' 1i: ..I (.) a.. Cl <O z w <( 0)
..... 0 f8 ~ <( 0:: 0)
0 t; >- <( Cl U >-::c: <( 0 .
-a,W w z cii ..I 0 0:: ..I
::i 0 0.. >
LL. 0 <(
0..
~oU w
0:: u N :;
Y,l z !l i!i ism "-ii !il .!, z 0.
w I-iii
CJ
:ii!:
m ..J a..
CJ
..J
!t z Iii ::c I-z
"' " z !l i!i .,_ 0 ::l "-1!
i~ tO -w I-
N
,:I ...,.
;;!tO ... _ 0 .. ·-<> >
0 z I-w --, 0:: a..
w I-z
0::
i Cl
"' c';
..l, -..
0 z ..
"' -0
"' <D
0::
w
ID -
0 ..
!c
SHEET NUMBER
P2.0.0
OF # SHEETS
m C
" • u
E
N N ci -m
"-m m , u □, o, N m .S • 0 C
" 0 c 0 •
Ci N " 0
N
TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 r a, -0 - N
N -
ID# IMAGE SPECIFICATION GENERAL NOTES
1. REFER TO SHEET PO.O FOR PLUMBING ABBREVIATIONS, NOTES AND SYMBOLS.
f(QANGE~
MATERIAL: 0.40" ALUMINUM
SAFETYSIGN.COM ITEM#: J1630
CODE REFERENCE: 2014 NFPA 58
SECTION 5.2.8.4 (2)
NATURAL GAS TO SITE
/ DISTRIBUTION SYSTEM
BUILDING BRANCH LINE
(TYP)
PRESSURE RELIEF--------------!:'.!
VALVE (TYP)
AIR COMPRESSOR -460V/3PHl60HZ
AIR COMPRESSOR
CONTROL PANEL
MULTI-PORT PRESSURE
::,,--- RELIEF VALVES, SPRING
LOADED (TYP)
ROTARY GAUGE
D-1
V
N-1
N-2
'NO SMOKING
FLAMMABLE GAS
8 i ·:-r:;·
Fl E E X T I N G u I s H E R
V
2 0
8 +
I
COLORS: RED "DANGER" SYMBOL, WHITE
BACKGROUND, BLACK LETTERING
MOUNTING DETAILS: BOLTED
FURNISHED BY: CONTRACTOR
INSTALLED BY: CONTRACTOR
MATERIAL: 0.40" ALUMINUM
GRAINGER ITEM #: 9WLM4
CODE REFERENCE: OSHA 29 CFR
1910.157(C)(1)
COLORS: WHITE LETTERS ON RED
BACKGROUND
MOUNTING DETAILS: BOLTED
FURNISHED BY: CONTRACTOR
INSTALLED BY: CONTRACTOR
MATERIAL: OUTDOOR VINYL
SAFETYSIGN ITEM #: M3357
CODE REFERENCE: 2012 NFPA 704
SECTION 4.1.1
COLORS: BLACK TEXT; BACKGROUNDS:
2:BLUE, 4:RED, O:YELLOW
MOUNTING DETAILS:
FURNISHED BY: CONTRACTOR
INSTALLED BY: CONTRACTOR
I---Oo(J-L--1-J SHUT-OFF VALVE --, (TYP)
0..
[ii" -
FLARE STACK- -----------1
WI CAPACITY= 69,000 MMBTUH
PILOT
COUPLING
(POL YETHELENE
TO STEEL) 1------ 114"
PRESSURE GAUGE ~
(TYP) . ~
- - 120Vl1PHl60HZ
, ---- FLARE STACK CONTROL
PANEL
o--- 3"
PRESSURE SWITCH
--+- ISOLATION
FLANGE
,=~---- BLIND FLANGES
~- SHUT-OFF
VALVE
1------ 3" FLARE STACK
BUTTERFLY VAVE WI
,,,.-J1-- PNEUMATIC ACTUATOR
(FAIL CLOSED)
NC
SURGE TANK
ffi
... PRESSURE RELIEF
VALVE
PRESSURE REGULATOR
VALVE (SET@ 35 PSIG)
PRESSURE SENSING PORT
ffi LIQUID LEVEU
PRESSURE GAUGE .___,,.._ ____ _.,
REFRIGERANT -460Vl3PH/60~HZ DRYER ___ _j
UNION
FLOAT GAUGE
(TYP)
t---- FILTER (TYP)
.,..._.., TO DRYWELL
THERMOMETER
(TYP)
AIR RECEIVER
ffi i----2"
CONDENSATE
OIL-WATER
SEPARATOR
~ STRAINER SOLENOID VAL VE
/ (TYP)
SOLENOID VA. WI
CYCLE TIMER
-120V/1PH/50HZ
~---,---1 TO DRYWELL
~ CONDENSATE DRAIN
I - -120Vl1PHl60HZ
I VAPORIZER -----
CONTROL PANEL
I GLYCOLWATERFILLW/ \
CAP
I MIXER
DIFFERENTIAL BYPASS VALVE --
CHECK VALVE (TYP) -
GLOBE VALVEWI ~
HYDROSTATIC RELIEF
r -460V/3PH/60HZ
I I I
I CONTROL PANEL ,------------,
(TYP)
460Vl3PHl60HZ
PUMP If\
NC \J:::,7
MIXER
460Vl3PH/60HZ ITO PUMP STARTER!
I I
VAPORIZER
ffi
SEE DETAIL 2/P2.5.0
(TYP)
30,000 GALLON
LPG STORAGE TANK
~ INTERNAL VALVE WI
PNEUMATIC ACTUATOR
~ SEE DETAIL 9 / P2.6.0 (TYP)
, ~ GLOBEVALVEW/
-~ HYDROSTATIC RELIEF
(TYP)
UNION (TYP)
FLEX. CONN. (TYP)
1-.-t~ --t-----t---------t- LIQUID WITHDRAW
1------t-----if---------t- LIQUID FILL
-~-2"
N-3
~MERGENCY SHUT-OFF
VALVE FOR VAPOR
RETURN
MATERIAL: 0.40" ALUMINUM
GRAINGER ITEM #: CUSTOM
CODE REFERENCE: 2014 NFPA 58
SECTION 6.12.10(1)
COLORS: RED LETTER ON WHITE
BACKGROUND
5• l
SPECIFIC GRAVITY TEST
PORT
GLOBE VALVE W/
HYDROSTATIC RELIEF
2" LPG VAPOR GLOBE VALVE WI
HYDROSTATIC RELIEF ,_____---+----+-- VAPOR RETURN
N-4 i V + -
EMERGENCY
FUEL
SHUTOFF , ________ _
SIGNAGE DETAIL
SCALE: NONE
MOUNTING DETAILS: BOLTED
FURNISHED BY: CONTRACTOR
INSTALLED BY: CONTRACTOR
MATERIAL: 0.40" ALUMINUM
GRAINGER ITEM #: 3NY30
CODE REFERENCE: 2014 NFPA 58
SECTION 6.12.10(1)
COLORS: RED LETTER ON WHITE
BACKGROUND
MOUNTING DETAILS: BOLTED
FURNISHED BY: CONTRACTOR
INSTALLED BY: CONTRACTOR
DRAIN LU
THREE-WAY BYPASS VALVE
(NORMAL POSITION IS WHEN
SYNTHETIC GAS IS NOT BEING USED)
SHUT-OFF
VALVE
PRESSURE REGULATOR
VALVE
4"
ISOLATION FLANGE PRESSURE GAUGE (TYP)~
COUPLING
(POLYETHYLENE TO STEEL)
SHUT-OFF VALVE (TYP) ~
FLEX (TYP) - -----
UNION (TYP) - ------~~
ISOLATION FLANGE
COUPLING
(POLYETHYLENE TO STEEL)
NITROGEN STORAGE
CYLINDERS
LU
GLYCOL WATER DRAIN J
1/2" STAINLESS STEEL
PNEUMATIC TUBING ~
112" NITROGEN TUBING
u::
N --' W
I ~~ ~ (J) (J)
0.. ::;; ::;;
/ PRESSURE REGULATOR
STRAINER
(TYP)
NITROGEN TUBING
SEISMIC DETECTION SYSTEM
MOUNTED ON CONCRETE PAD
(NORMAL POSITION IS WHEN
SEISMIC VALVE IS NOT
ACTIVATED, NORMAL
OPERATING CONDITIONS.)
ffi
NO
COM
THREE-WAY BYPASS SOLENOID
VALVE (NORMAL POSITION IS
WHEN ENERGIZED)
THREE-WAY BYPASS
SOLENOID VALVE SWITCH --~
I I
ON
OFF
ffi
~ PUMP BYPASS
BACK PRESSURE REGULA TOR
PNEUMATIC ACTUATOR -~
MANIFOLD (TYP)
30,000 GALLON
LPG STORAGE TANK
2•--1---- ---i
1-114" - --, ANGLE VALVE - ------f
EMERGENCY SHUT-OFF ~
VALVE ~
1/ ANGLE VALVE WI
HYDROSTATIC
RELIEF
/ VALVE
1----tHDIO--{XI--L--fr ¼ -M- - -(E)MPG- - - -< GAS SERVICE 110,933 CFH 1 t 0
~ UNION (TYP)
~ BACK CHECK
VALVE
-~na~ i.N~.
~41~
Pttitm't~ ~ Alt '
~IIU!II-~ v_-~ ~ ~ r~ Vii\OON ~
~r~ ~---00 2,t\f
~ Air UM
~6""Une
Eloollill~
AC 110 V 60 Hz (USA) Grawfume1~ 1------ GraviBlend™-3 Vent
AC 220 V 50 Hz (Export)
Power Suppiy. PLC. PCV --·-------- Operator Interface, Terminal Str ip (inst.;lll in hon-hazardous area) I·
---------- - - --- ------- -~p1 · p f ... .,,- ___.._ =-' _ , _ _ __ ·-• _ _ -·- -·· _ ~ -· _ ~-- .,_,. " .cJI. os,on roo I 1·- - '"- - ·~· -· ·•·• -- .. Elecirical Box I - - . L ___ ___, LPG VaporlnleC I I ' 2" • 300# Flange_ ,.' .
- ----IL)--,---'-----~~s...l'~ 7-- 7~::::::;:r-,---:~fir--=fj.T-+ . y' 7 -r -r =""" l .- PCV I I
I I l
-- l. 1l I I g - l j
II .,..,...,"-
. .,. f'b,;:~
1'9 ,.._, . DIM~YM
~ -...-,.,,, bl .,,__
D """"" 1 ..... ,,,.., ... .._
PGA ·
1. I l I I l
PCV
I J_ lr-E~-,___,__..,..c....• ·---1· 1. i \J'!:>C---.. 11 -r
I Mli<.d Ga< Ornlei !
~!t~9} .i
POM-40'. .,. I
PQl,l:6P; '6'' l l I ! Blenders wilti discharge pressures above 80 • psi(5,6ba-f are equipped with a•CQotrol valve !
_ _ _ __ 1::rn~a.i~d~in~:a!ct~~~gu!;Of _: _____ _.. _ ,_ __ .-= _ ~~ ·~• ~~ ,_ _ ~ --= _J
AIR BLEND MIXER DIAGRAM
SCALE: NONE
15 PSI NATURAL GAS
SITE DISTRIBUTION SYSTEM
SEISMIC VALVE--~
GAS SERVICE PROVIDED BY THE GAS EMERGENCY SHUT-OFF
STATION COMPANY
, 1 '
1J>2.s.o.., 0 0 0 0 120V, 1PH, 60 Hz - - - - - -- - - - - -- - - - -
EMERGENCY PUSHBUTTON EMERGENCY PUSHBUTTON EMERGENCY PUSHBUTTON EMERGENCY PUSHBUTTON
ALARM STATION #4 ALARM STATION #3 ALARM STATION #1 ALARM STATION #2
EXCESS FLOW VALVE
HOSE COUPLING ~
WI 2-114" ACME CAP_/
"Y" STRAINER
------ HOSE COUPLING
WI 3-114" ACME CAP
LPG TRUCK UNLOADING STATION
STANDBY SYSTEM (SYNTHETIC NATURAL GAS)
SCALE: NONE
NOTES:
1. REGULATORS FOR OUTDOOR INSTALLATION ARE
REQUIRED TO BE DESIGNED, INSTALLED, OR
PROTECTED SO THEIR OPERATION WILL NOT BE
AFFECTED BY THE ELEMENTS AS NOTED ON
NFPA 58 - 6.8.1.5
2.
3.
4.
5.
PIPING AND TUBING SHALL BE IDENTIFIED IN
ACCORDANCE WITHASME A13.1 TO INDICATE THE
MATERIAL CONVEYED AS REQUIRED BY CFC
5003.2.2.1 (2)
PROVIDE MARKING ON VAPORIZER CONFORMING
TO ASME CODE. E.G. MAXIMUM VAPORIZING
CAPACITY IN GALLONS PER HOUR, RATED HEAT
INPUT IN BRITISH THERMAL UNITS PER HOUR AND
NAME OR SYMBOL OF THE MANUFACTURER.
CONTROL VALVES ARE REQUIRED TO COMPLY
WITH ANSI/UL 125.
CHECK VAL VE SHALL BE INSTALLED NO MORE
THAN 12" FROM THE HOSE FILL CONNECTION.
APPROVALS
CALIF'ORNIA DEPARTMENT OF CORRECTIONS
AND REHABILITATION ACCESS COMPLIANCE
REVIEW
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE OR
APPROVE ANY OMISSION OR DEVIATION FROM THE
APPLICABLE REGULATIONS.
TRACKING NUMBE~~ DATE: 1·'7-UZd REVIEWER: /l YI Af'!e 4-'i I
CALIFORNIA STATE FIRE MARSHAL
APPROVED
FIRE AND PANIC ONLY
APPROVAL Of THIS PLAN DOES NOT AUTHORIZE
OR APPROVE ANY OMISSION OR DEVIATION FROM
THE APPLICABLE REGULATIONS. FINAL APPROVAL
IS SUBJECT TO FIELD INSPECTION. ONE SET Of
APPROVED PLANS SHALL BE AVAILABLE AT THE
PROJEC SITE AT A~<MES.
REVIEWED BY: •
.N1112'.2m z ii:
ii
" el w ,-.
Cl)
>-Cl) a..
...J u z Cl I w
5 a.. w a::
"' " z
~i!
is El ~:i s~
~ il' _., z ::5 Cl) z Cl) a::
w z Cl) w C
"' " z
~i!
is El ~ il' _., 8:0<0 w <( 0, ,-. 0 18 <( a:: 0, ,-. >- <( cncu <( 0 -
- CCI W z<C-' ~w~ u..a.~ ::J8U
c) N ::;
"' " z
~i!
isEj ~2
B~ en
...J u.
en ...J
~ z u I-w J:
I-z >-en
"' " z ~i!
is El ~:i x~ ~ il' -"'
~ I
I N a..
z
C
...J z I uJ ::::E co -ci z u w u w
0 1-.._ __ __..__ ..... _ ;ii
SHEET NUMBER
P2.5.0 t 5-
OF # SHEETS :;-
TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 Exhibit A-2
Oval
::I:
Q.
N ..
N - · a, -0 N
a) -,,, 30'·0"
120V/1PH/60HZ
POWER
1··
RAIN CAP
(SEE NOTE #1)
_,.---FLARE STACK
(SEE NOTE #1)
~-------PILOT
(SEE NOTE #1)
r--SHUT-OFFVALVE
(SEE NOTE #1)
LL.~~-- 3" LPG (SEE NOTE #1 )
LJl-----CONTROL PANEL (NEMA 4)
W/ TRANSFORMER, PILOT
MOMENTARY SWITCH.
(SEE NOTE #1)
SHUT-OFF VALVE (TYP)
UNION
~..._INSULATING FLANGE
GUY WIRES TYP. OF 4
WITH ANCHORS, SEE 9 I S2.6.0
FOR DEADMAN FOOTING.
AND CA THOOIC PROTECTION
J:ri'd.lJnt-!2) 3" 150# BLIND FLANGES
(SEE NOTE#1)
I CONCRETE FOUNDATION
11 r3"LPG
~ = = ::J w DIA.MIN.
NOTE:
1, PROVIDED BY FLARE STACK
MANUFACTURER
FLARE STACK DETAIL
SCALE: N.T.S.
NOTE:
120V SEE
ELECTRICAL
DRAWINGS
FURNISH & INSTALL (2) COLOR PLASTIC
ENGRAVED TAGS 2"X2' WITH 3/18" HIGH
LETTERS STATING "LP. VAPOR RETURN &
L.P. LIQUID INLET' AND POSITION TO MATCH
PIPING, FASTEN TAGS PER MFG. RECOMMEN•
DA TIONS FOR OUTDOOR INSTALLATION
SEE SHEET P2.0.0
FOR CONT. OF
REMOTE SHUT-OFF.
TO TANK .
LIQUID
MANIFOLD
18\------1'
MATERIAL UST
TO TANK
LIQUID /
MANIFOLD_,,,..-
0 2" BACK CHECK VALVE
@ 1-114" EMERGENCY SHUTOFF VALVE
@ 2• 400#ANGLEVALVE
01-1/4" 400#ANGLEVALVE
@ 1-1/4" EXCESS FLOW VALVE
@ 1-1/4" HYDROSTATIC RELIEF VALVE
(j) 2" 300# F.S. UNION
© 1-1/4" 300# F.S. UNION
@ 2" NIPPLE SCH. 80
@ 2" NIPPLE SCH. 80
@ 2" NIPPLE SCH. 80
@ 2" NIPPLE SCH. 80
@ 1-1/4" NIPPLE SCH. BO
@ 1-1/4" NIPPLE SCH. BO
@ 1-1/4" NIPPLE SCH. BO
@ 1-1/4" NIPPLE SCH. 80
@ 1-1/4" NIPPLE SCH. BO
@ 2" ELL. 2000# FORGED STEEL
@ 1-1/4" ELL. 2000# FORGED STEEL
@ CAP 3-114" ACME, METAL, W/CHAIN
@ CAP 2-1/4" ACME, NYLON, W/CHAIN
@ 1-1/4" 3000# F.S. COUPLING (WELD TO CHANNEL)
@ ADAPTER 3-114" M. ACME x 2" MNPT
@ADAPTER 2-114" M. ACME x 1-1/4" MNPT
LIQUID INLET
/ VAPORRETURN
I'----@
1~8 l
SEE SHEET S2.6.0
FOR TRUCK UNLOAD
STATION SUPPORT
@ TRUCK UNLOADING STATION BULKHEAD SUBASSEMBLY
BY LPG SYSTEM MANUFACTURER
@ 2" 3000# F.S. FULL COUPLING {WELD TO CHANNEL)
@ 2" TRUCK GROUNDING SOLENOID VALVE.
ELECTRICAL DRAWINGS
TRUCK UNLOADING STATION
SCALE: N.T.S.
RETURN TO
STORAGE TANK
\ INLET
SEE ELECTRICAL DRAWINGS
FOR STARTER LOCATION
~OV/3PH/60HZ
POWER
::t'
~TO PRESSURE
SWITCH
2· / LG
ETURNTO ~ TYP. I
2" LIQUID LINE FROM '·:4 I
/ STORAGE TANK
2" LIQUID
STORAGE TANK 0--1
LIQUID SUPPLY PUl';IP MATERIAL LIST
0 ,,.-..., IB
PUMP W/ORIVE
LPG LIQUID PUMP ELECTRIC MOTOR, CLASS 1, GROUP 0, DIV, 2
STARTER AT MCC-D
2" 400 WOG DUCTILE IRON STRAINER
0-300 LIQUID FILLED PRESSURE GAUGES
2" GLOBE VALVE
114" RELIEF VALVE
LIQUID SUPPLY PUMP
SCALE: N.T.S.
TO VAPORIZER
2" DIFFERENTIAL BYPASS VALVE
2" 400 WOG CHECK VALVE
2• BACK PRESSURE REGULATOR
UNION
FLEX.CONN.
PRESSURE SWITCH
PUMP SKID ON CONCRETE PAD,
SEE 8/S2.6.0 !
, .. .-----·TO TANK DELUGE SYSTEM
TO WET PILOT BRANCHES ~
' DELUGE VALVE WI WET PILOT TRIM-, ••
AND MANUAL RELEASE •• NOTE: CONNECT ALARM DEVICES TO
FIRE ALARM CONTROL PANEL
A ,-
112" NPT
SSSWAGELOK
FlmNG(TYP)
114"SSTUBE
TO ACTUATORS
112" LINE BORE
TOP VIEW
SS SWAGELOK ___ ../
FlmNG
END VIEW
1-112" SS BAR
STOCK (12" LONG)
SSPLUG
1/2" NPT
114" NPT
1/4" SS TUBE
TO ACTUATORS
...--- 1-112" SS BAR
STOCK
---- SSPLUG
PNEUMATIC MANIFOLD - STORAGE TANK
SCALE: N.T.S.
~ SEE BACK BRACE
. DETAILS.
SECTION A-A
MAX WIDTH RECT SIGN= 48" '
K - r_-, ---------1 ·-, ---- I I I I I I I I I •· I I I ' I ' I I I ' ll>C-----1=•=1-----
FRONT VIEW
TTACHSIGNTOPOST .c--~--J""'t-A
WI THBOLTSATTOP,
ENTER AND BOTTOM C
A
- SIGN PANEL------7
END VIEW
4 '
,_f'2.6.0_, " <O
GENERAL NOTES
1. REFER TO SHEET PO.O FOR PLUMBING ABBREVIATIONS, NOTES AND SYMBOLS.
RIGID CALCIUM
SILICATE & SHIELDS.
INSERT AT ALL
SUPPORTS (TYP) ----~
STRUT CHANNEL
SUPPORT, SEE
STRUCT.
SEISMIC
BRACE (TYP) ----.Jl.-jj., NOTES:
I I I I I I
CONCRETE SLAB
AS REQUIRED,
SEESTRUCT.
1iS2.6.0.
PIPE CLAMP
(TYP)
PIPING (TYP)
INSULATION
FINISH GRADE
PLATE SECURED
TO CONCRETE
SLAB AS
REQUIRED
1. SEE SPECIFICATIONS FOR MAXIMUM SUPPORT SPACING
2. PAINT WELDS WI ZINC RICH PAINT BEFORE PAINTING W/ COLOR COAT.
TYPICAL PIPE SUPPORT-GROUND MOUNTED
SCALE: NONE
-::-:-:-::::-r,,-&..\,..,..------~-3/16" STEEL PLATE TUBE CAP (TYP) 3116" -,----,~:::::t=====· 1/2" DIA. $ST BOLT WI HEX NUT AND LOCK WASHER (TYP)
2"X2"X3/16" SQ TS, WELD TD POST AND
EXTEND TO SIDES OF F.E. CABINETW/ TUBE
CAP (BOTH SIDES) r---- FIRE EXTINGUISHER CABINET WI 18 LB MIN.
B:C DRY CHEMICAL EXTINGUISHER
'A'--_J -----EMERGENCY PUSHBUTTON ALARM SWITCH
-,---- , 1-r\.....---- .,,----12" SO. SIGN W/ 1-112" LETTERS "EMERGENCY
:.JV ALARM SWITCH'
I ,,---2"X2'X3/16" SQ. TUBE STEEL (TS) (TYP)
<> <> z z ~z ~is ~o z oBJ ~"' o,,, e,- e,- ~ zai zai iia ~~ !~ c., i~ l:l C
!l il' ~il' a'"' -"'
<:. ~ t i
<> z ~is 1s Bi e,-i~
!!l
"' <> z ~i'i 1s Bl o,-
;g;~ ,le"' i~ a.
<:> z
..J z L,,J
::E
DO -
···--8" OSY VALVE WI
TAMPER SWITCH
4"x4"POST 2" 12" 12" 2R
~~....,..~--! ! 11 I ,,..---(4) 1/2" DIA. TYPE 316 SST ANCHORS.
GRADE
,..,/MANIFOLD DRAINS
/ TOGETHER AND SPILL
OJ ON SPLASH BLOCK.
_ ___..- -- Bfl INCOMING DUCTILE
IRONPIPEW/
RESTRAINING RODS.
DELUGE VALVE DETAIL
SCALE: NONE
PRESSURE REGULATOR
WIPRESSURE GAUGES (TYP)
STAINLESS STEEL
PNEUMATIC TUBING.
(TYP)
SITE GAS DISTRIBUTION ---~
SYSTEM
~1-~(;l--;;1:-'-, SEISMIC BUTTERFLY VALVE L ---;i, I (PNEUMATIC)FAILCLOSED.
)5.-i+r--SOV (TYP)
;--H+- FLEX (TYP) (---,=~..L..;
RETAINER I
J
REMOTE ON-OFF ---L-1
SWITrC"-H'----~ I
..--1--,iw ~' "' .'IC COl,I'-~
RELIEF
l ___ J
,. 7 '
~2.6.0.,.
LPG TANK INTERNAL
PNEUMATIC VA. (N.C.)
TYP. OF 3 ON EACH
TANK, SEE 1/P2.6.1.
VALVES SHALL FAIL
CLOSED.
L..--.---TANKSUPPORT
FOOTING AND PIER
.,,,.- LPG TANK INTERNAL
PNEUMATIC VA. (N.C.)
TYP. OF 3 ON EACH
TANK, SEE1/P2.6.1.
VALVES SHALL FAIL
CLOSED.
L.----TANK SUPPORT
FOOTING AND PIER
SEISMIC
DUMP VA.
NITROGEN CYLINDERS (ONE STAND-BY)
WITH SEISMIC RESTRAINTS IN RACK
MOUNTED ON CONCRETE PAD, SEE
31S2.6,0 AND 5/2.6.0
3-WAY SOLENOID VA.
~- SEISMIC DETECTION
SYSTEM MOUNTED
ON CONCRETE PAD
PNEUMATIC MANIFOLD
(TYP) SEE 3/P2.6.0
'~., - INDICATED NORMAL
POSITION IS WHEN NOT
ENERGIZED.
NOTES:
1. USE STAINLESS STEEL TUBING TO CONNECT
THE TANK ISOLATION VALVES TO THE
NITROGEN CYLINDERS AND EARTHQUAKE
VALVE. PROVIDE AN 18-INCH PIGTAIL FOR
CONNECTIONS THAT REQUIRE MOVEMENT.
PNEUMATIC SAFETY CONTROL
SCALE: N.T.S.
PLAN
1"
3/8"1 HOLE FOR 1/4"1
HEX HEAD BOLT WITH
AAT WASHERS, FIBER
WASHER NUT AND JAM
NUT.
GRADE
00 ..,.
l;> ., 3116"
"' GRADE
;&= l..::==d:=:=,,,,..
3/8" x 3/4" SLOT FOR
1/4"1 HEX HEAD BOLT
WITH AAT WASHERS,
FIBER WASHER NUT
• : ?-~~=>---:::-.12' DIA, (MIN,) CONCRETE FOUNDATION
NOTE: SANO BLAST AND POWDERCOAT ALL
SUPPORT STEEL MEMBERS.
ELEVATION AND JAM NUT. POST EMBEDMENT
BACK BRACE DETAILS
SINGLE POST INSTALLATION-SIGN FIRE EXTINGUISHER CABINET AND ALARM
u a, SCALE: NONE
1/2" SST-EMBED
IN CONCRETE \
2" TUBE STEEL POST
SEE DETAIL 8/P2.6.0
STAINLESS STEEL
CABLE
SCALE: N.T.S.
L----SIGN ON BOTH SIDES OF 2•1NCH SQUARE POST
"EMERGENCY SHUT-OFF VALVE FOR VAPOR
RETURN" • 18" SQ. W/2" LETTERS.
,r:::._....:_:::,._,,,-- 5/8"0 X 4" LG
S.S. EYE BOLT
...--11---- 1 LB LEAD WEIGHT
J::j<-:;;,E:31--- 4" TEE HANDLE
1-t.-==------'I--- CABLE -1/16" S.S.6X7
WELD TO POST
TO VALVE}
ACTUATOR
• .d. . .,, .
6" -~-
L ,•· ... L. ~-~ _ • .'; • ---, ~ .<i ;
I· 10" -I
CROSS SECTION
6"x8"/W1.4xW1.4 W.W.M.
1----__,I I I I Ii STAINLESS STEEL
~ -'\,--~~\,---~PULLEY WITH GUIDE
' 10 "I EMERGENCY SHUTOFF STATION DETAIL
P2.6.0 SCALE: N.T.S.
APPROVALS
CALIFORNIA DEPARTMENT OF CORRECTIONS .
AND REHABILITATION ACCESS COMPLIANCE
REVIEW
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE OR
APPROVE ANY OMISSION OR DEVIATION FROM THE
APPLICABLE REGULATIONS.
TRACKING NUMBER: U!,,t DATE: 1•7•-zn,:, REVIEWER: JidtjJ!f/ 4½e 4~1
CALIFORNIA STATE FIRE MARSHAL
APPROVED·
FIRE AND PANIC ONLY
C ta .., V)
0::
w z
CJ
Cl
N _,.
0 z I-w .., 0::
0..
w I-z <f)
E
"' N
I-..L.-----...a.--1 /i:'
APPROVAL OF THIS PLAN DOES NOT AUTHORIZE S EET N R ~
OR APPROVE ANY OMISSION OR DEVIATION FROM H UMBE ;:;
THE APPLICABLE REGULATIONS. FINAL APPROVAL :;;-
. IS SUBJECT TO FIELD INSPECTION. ONE SET OF p 2 6 0 ]
APPROVED PLANS SHALL BE AVAILABLE AT THE 5-
PROJEC SITE AT ALL MES. • • N
REVIEWED BY:,--1.L"J.+."'-~1-JA_N_0:._2 _2 ___ 02~0 OF /I SHEETS f ---------------------------------------------------------------------------------------------------------------------------------''--------u-----------''---------__, TBB
California Department of Corrections and Rehabiliation (CDCR) Plans
Bid Number C5612927-D Re-Bid 1 Exhibit A-2 matthew.vanatta Rectangle
Rectangle
File details come from the government source that posted it. Updated .