Exhibit_2_-_Concrete_Mow_Strip_Specification.pdf
PDF 155 KB Posted
- Solicitation number
- BPM050831
- Issued by
- Dorchester County, Capitol Heights Town, Maryland
About this file
This document is a technical specification exhibit from the Maryland Department of Health for the Eastern Shore Hospital Center Security Fence project, specifically detailing the concrete mow strip design. The exhibit provides a detailed technical drawing of a 2-foot wide concrete strip with precise construction specifications, including a 4-inch gravel bed, compacted subgrade, and a 4-inch reinforced air-entrained concrete slab with galvanized welded wire mesh. The specification calls for a 3/8-inch wide by 1-inch deep control joint placed at 6-foot intervals maximum, and is issued for pricing purposes with a date of 04.03.2025.
The technical drawing specifies the concrete mow strip shall be constructed using 3,000 PSI concrete with 6x6 - W1.4/W1.4 galvanized welded wire mesh reinforcement. The cross-section details minimum 4-inch dimensions for both the gravel bed and concrete slab, with a total width of 2 feet. The document is part of a larger project for a security fence at the Eastern Shore Hospital Center, prepared by RFCD (likely the design firm), and represents a technical specification exhibit intended to provide precise construction guidelines for the concrete mow strip component of the project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Exhibit_4_-_ESHC_Fencing_Specifications_Revised.pdf | ||
| Exhibit_4_-_ESHC_Fencing_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2 CONCRETE MOW STRIP
Scale: 1" = 1'-0"
2'-0"
4" GRAVEL BED
NOTES:
1. PROVIDE A 3/8" WIDE X 1" DEEP CONTROL JOINT @ 6'-0" O.C. (MAX.)
OR TOOL JOINT.
COMPACTED
SUBGRADE
4"
MIN.
4"
MIN.
4" REINFORCED AIR
ENTRAINED CONCRETE
SLAB (3,000 PSI),
6 x 6 - W1.4 / W1.4, GALVANIZED W.W.M.
PROJECT :
DETAIL TITLE :
COMM. NO. :
DRAWN BY :
CHECKED BY :
DATE :
SHEET
NUMBER:
AS2CONCRETE MOW STRIP
EASTERN SHORE HOSPITAL CENTER - SECURITY FENCE
RFCD
RFCD
04.03.2025
ISSUED FOR: PRICING
MARYLAND
DEPTARTMENT OF HEALTH
Exhibit # 2