Exhibit 1-HVAC Equipment and Task List .xlsx
XLSX spreadsheet 14 KB Posted
- Attached to
- HVAC Preventative Maintenance MDOT Grand Region
- Solicitation number
- RFP 591 260000002109 2
- Issued by
- Michigan
About this file
This is an HVAC Equipment and Task List exhibit for a preventative maintenance contract with the Michigan Department of Transportation (MDOT) Grand Region. The document specifies equipment inventory and corresponding maintenance requirements across multiple HVAC systems. The facility contains one Lochinvar boiler requiring annual inspection of valves, piping, burner cleaning, heat exchanger disassembly and cleaning, boiler flushing, condensate drain filter changes, and low water cutoff testing. Two QMark electric unit heaters require annual cleaning and inspection. Six Mitsubishi mini-split units and six corresponding condensing units require semi-annual maintenance in April and September, including evaporator coil inspection and cleaning, filter cleaning, and mechanical and electrical system inspections. Five rooftop units manufactured by Carrier and Trane require six-month service intervals including economizer filter inspection and replacement, refrigerant component inspection, lubrication of moving parts, condenser coil cleaning, and belt inspection or replacement. Two Greenheck exhaust fans require annual cleaning, lubrication, and electrical component inspection.
The exhibit provides specific equipment identifiers including make, model, and serial numbers for all units, enabling precise tracking and maintenance documentation. The preventative maintenance schedule is organized by frequency, with annual tasks assigned to boiler, electric heaters, and exhaust fans, semi-annual tasks for mini-split units and condensing units, and six-month intervals for rooftop units. This comprehensive equipment listing and task breakdown establishes the scope of work for the MDOT Grand Region HVAC preventative maintenance contract, allowing bidders to understand the full extent of maintenance responsibilities and develop accurate cost proposals based on the specified equipment and service frequencies.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - WHD 9917 Nov 2025.pdf | ||
| Attachment 2 - WHD 9918 Feb 2024.pdf | ||
| Attachment 3 - Prevailing Wage Rates Kent County 2026.pdf | ||
| Schedule B-Pricing Grand Region HVAC Revised.xlsx | XLSX spreadsheet | |
| Amendment 1 - RFP 260000002109.docx | DOCX document | |
| RFP 26-2109 Proposal Instructions VQW Contract Terms Schedule A Schedule B Revised.docx | DOCX document | |
| Amendment 2- Q & A RFP 26-2109.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| EXHIBIT 1 | HVAC EQUIPMENT AND TASK LIST | ||||
| Equipment | Make | Model | Serial number | PM Task | Basis (frequency - schedule) |
| Boiler (1) | Lochinvar | FTX400N | #2220129514216 | Inspection of valves and piping. Test glycol and charge if needed. Disassemble and clean burners and heat exchanger. Valve off and flush the boiler. Change condesate drain filter media. Test low water cutoff test and reset. Clear obstrucions in vents and flues. | Annually |
| Controls | JCI | Niagara | Check Remote connection and reset passwords as needed. | As needed as part of PM review. | |
| Electric Unit heaters (2) | QMark | CU93505483BTB CU93505483BTB | 1200 008 1200 009 | Clean and inspect for proper operation | Annually |
| Mini Split (6) | Mitsubishi | PKA-A24FA PKA-A24 PKA-A24FA PKA-A12LA PKA-12LA PKA-A18HA6 | 82A02182B 82A02145B 82A02177B 25M00808 25M00803 64A09413C | Inspect and clean evaporator coils. Clean filters. Clean condenser unit. Inspect all mechanical and electrical systems. Inspect/clean blower. | April & Sept |
| Mini Split Condensing Unit (6) | Mitsubishi | PUY-A12NKA7 PUY-A12NKA7 PUY-A24NHA2 PUY-A24NHA3 PUY-A18NHA6 PUY-A24NHA2 | 13U27833B 13U27948B 81U02954B 66U01529C 66U07478C 73U01249B | Clean condenser coils & fan. Clear any obstructions. Inspect mechanical and electrical components. Inspect/lube fan motor if applicable. | April & Sept |
| Roof Top Units (5) | Carrier Trane Trane Trane Trane | 48TCEA07A2A5A0A0A0 YHD240G4RVD19K8C1A1B60000A0000000000000 YZD210F4RVE19KGC1A1B60000A00001000000000 YZD180F4RVE19KHC1A1B60000A00001000000000 YHD240G4RVD19K8C1A1B60000A00000000000000 | 281C81768 223410278D 223310617D 223310387D 223410279D | Clean and inspect econimizer filter. Replace filters. Inspect electrical, mechanical, refrigerant components. Lubrication of moving parts. Clean condesing coils and fan blades. Inspect shives / change belts. Inspect/clean air grills. | 6 Months |
| Exhaust Fans (2) | Greenheck | 6B-180-10-1-30-X | 21471823 | Clean fan. Lubricate fan and motor if applicable. Inspect electrical connections and components. | Annually |