ESBD_File_341194_Addendum 3.pdf

PDF 3 MB Posted

Attached to
Frank Garrett HVAC Project
Solicitation number
152-11-2024-01
Issued by
Bexar County, San Antonio City, Texas

About this file

This document is an addendum related to a project called the Frank Garrett HVAC Project for the city of San Antonio, Texas. The project involves the renovation of the Frank Garrett Community Center, including the replacement of the HVAC system. The addendum provides changes and clarifications to the original bid documents, such as adding additional drawings, responding to questions about site visits, the existing chiller, pipe sizes, and permitting. The bid opening is scheduled for December 5, 2023 at 2:00 PM CT, and a non-mandatory pre-bid meeting was held on November 13, 2023. The deadline for questions is November 20, 2023 at 4:00 PM CT.

The addendum also includes detailed specifications for the new HVAC system, including a control sequence for the chilled water system, pipe sizing details, and electrical one-line diagrams. The project is funded by the city of San Antonio and Bexar County, and the successful contractor will be required to comply with all applicable state and local laws and regulations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum #3, Frank Garrett HVAC Project No. 35-00282-02-03 Form09/22/2021AM Page 1 | 2

ADDENDUM 3

PROJECT NAME: Frank Garrett HVAC Project

DATE: 11/27/2023

PROJECT NO: 35-00282-02-03

This addendum is separated into sections for convenience; however, all respondents, bidders, contractors, subcontractors, material men, and other parties must be responsible for reading the entire addendum. The failure to list an item or items in all affected sections of this addendum does not relieve any party affected from performing as per instructions, providing that the information is set forth one time any place in this addendum. These documents will be attached to and will become part of the Contract Documents for this project. The respondent/bidder is required to acknowledge the receipt of this addendum.

GENERAL:

1. The following changes and/or additions to the Contract Documents, via this addendum, must apply to proposals made for and to the execution of the various parts of the work affected thereby.

2. Careful note of the Addendum must be taken by all interested parties and all trades affected must be fully advised in their performance of the work involved.

3. This Addendum is hereby made part of the project requirements and contract documents for the above reference project.

Ensure to acknowledge this Addendum in CivCast when downloading this Addendum. Acknowledgement of this Addendum is a requirement in order to submit bid in CivCast. This addendum consists of the items and their associated attachments as listed below:

A. ADMINISTRATIVE CHANGES TO BID DOCUMENTS:

1. Adding additional drawings to the bid documents.

B. CHANGES TO PLANS / SPECIFICATIONS:

1.

C. QUESTIONS & RESPONSES:

Question #1: Will there be an opportunity to walk the site?

Answer: A Site Visit was held on 11/13/2023.

Question #2: Is the existing chiller operational? At what point will the temporary chiller be needed and for what duration?

Answer: Yes. The temporary chiller will only be required while the existing chiller play is being replaced.

Question #3: The current lead time on the Trane Scroll chiller is 30 weeks (210 calendar days). Would like a time extension from the granted 210 days to account for submittal review, installation, commissioning for an additional 60 days (270 total calendar days from NTP).

Addendum #3, Frank Garrett HVAC Project No. 35-00282-02-03 Form09/22/2021AM Page 2 | 2

Answer: A split NTP will be provided to allow for the long lead time of the chiller.

Question #4: Will a building permit be required or just trade permits? if a building permit is required, who is paying for the permit review and building permit?

Answer: Trade permit only.

Question #5: Will COSA be providing lab testing for the new chiller pad?

Answer: Yes.

Question #6: Pipe sizes for the domestic cold water and sanitary sewer are the only pipe sizes shown.

Pipe sizes for the domestic hot water and hot water return are not shown. In order to price these systems, all pipe sizes will be required, and site visit is not enough time for us to do this.

Answer: See Addendum #3 drawings for pipe sizes.

Question #7: What are the pipe sizes to all new chilled water piping? Not shown on drawings.

Answer: See Addendum #3 drawings for pipe sizes.

SIGNED AND SEALED BY CONSULTANT (Engineer/Architect of Record) By signing and sealing this addendum, the Engineer/Architect of Record acknowledges that the sign/seal is only for changes/clarifications to the items associated with the Engineer’s/Architect’s work referenced in this addendum.

END OF ADDENDUM NO. 3

Date: 11/27/2023

Client: MARMONMOK ARCHITECTURE

Project Name: FRANK GARRETT COMMUNITY CENTER RENOVATION–PACKAGE 2

Project Number: 23002

This addendum is generally separated into sections for convenience; however, all contractors, subcontractors, material men and other parties shall be responsible for reading the entire addendum. The failure to list an item or items in all affected sections of this addendum does not relieve any part affected from performing as per instructions, providing that the information is set forth one time any place in this addendum. These documents shall be attached to and become part of the Contract Documents for this project.

PLAN ITEMS

RE: Plan Sheet M101:

Item 1: Added keyed notes.

Item 2: Added demolition work.

Item 3: Added new work.

RE: Plan Sheet M201:

Item 1: Added note

RE: Plan Sheet E102:

Item 1: Added keyed notes 9, 10, and 11.

Item 2: Revised floor plan, as indicated.

RE: Plan Sheet E103:

Item 1: Added keyed notes 6, and 7.

Item 2: Revised One-line diagram, as indicated.

RE: Plan Sheet E202:

Item 1: Revised floor plan, as indicated.

RE: Plan Sheet E302:

Item 1: Added keyed note 2.

Item 2: Revised One-line diagram, as indicated.

Alderson & Associates, Inc. | Consulting Engineers | TBPE Firm No. F1008

7700 Torino, Suite 101 | San Antonio, TX 78229 | (210) 614-1110 | www.alderson-inc.com

4"

4"

4"

1"

1"

4"

4"

LDR2 HV1

MDPL

1"

1"

1"

4"

4" 4" 4"

4" 4"

4"

M101

MECHANICAL NEW

WORK & DEMOLITION

ENLARGEMENT

E

D

C

B

A

654321

Drawn Checked Date Project No.

Revisions

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

23002 10/13/23

MEB

PEP

11-27-2023 Addendum #03

M201

MECHANICAL

SCHEDULES

E

D

C

B

A

654321

Drawn Checked Date Project No.

Revisions

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

MEB

PEP

PIPE CLAMPS PER

P-4000 UNISTRUT

3/8" THREAD ROD,

SECURE FROM BLDG.

STRUCTURE

STRUT USE

INSULATION PROTECTION

GRINNEL FIG. #167

WHERE INSULATION

IS IN CONTACT WITH

ALLOW ROOM FOR

FUTURE PIPE ADDITION

PIPE HANGER DETAIL

NO SCALE

OR EQUAL

SPECS, TYP.

SPECS AT UN-INSULATED

PROVIDE DIELECTRIC

SEPARATION PER

COPPER PIPING

ROD, CUT TO

PIPE HANGER

INSULATION

CLEVIS TYPE

LENGTH

THREADED

SHEET METAL SHIELD

FOR INSULATION - MIN.

HANGER POINT

LENGTH 1.5 TIMES

INSULATED PIPE DIAMETER

PROVIDE A SECTION

INSULATION AT EACH

OF INCOMPRESSABLE

PIPE

CARRIER

STRAP SADDLES WITH

ZIP TIES

STAINLESS STEEL

PUMPMOTOR

(NON-SLAM TYPE)

MANUAL AIR VENT

CONCENTRIC REDUCER

BALL VALVE (TYP.)

PRESSURE GAUGE

CHECK VALVE

BUTTERFLY VALVE W/

BASE

PUMP INERTIA

GROUTABLE)

(STEEL &

DRIP RIM BASE

PER SPECIFICATIONS

VIBRATION ISOLATION

ELBOW DOWN VALVE

Y-STRAINER W/ ELBOW

FLEXIBLE PIPE

CONNECTION (TYP.)

FLOOR

DISCHARGE SUCTION

MEMORY STOP (TYP.)

(TYP.)

ECCENTRIC REDUCER

SUCTION DIFFUSER

END SUCTION PUMP DETAIL

(N.O.) FLEXIBLE HOSE

3/4" DRAIN VALVE (N.C.)

FLOOR DRAIN

1" DRAIN TO

NO SCALE

KEEPING PAD

3-1/2" HOUSE-

SITE

FLOW

METER

FILTER/FEEDER

TANK

TO PUMP

SUCTION

FROM PUMP

DISCHARGE

1" PIPE

BALL VALVE

(TYP.)

3/4 " TO

FLOOR

DRAIN

3-1/2" TALL

HOUSEKEEPING

PAD

1" PIPE

FUNNEL

AIR DIRT SEPERATOR

LOCATE DRAIN VALVE FOR

EASY ACCESS FROM FLOOR

(WITHOUT LADDER).

1/2" AIR VENT

TO FLOOR

DRAIN

SUSPEND FROM STRUCTURE

OVERHEAD (PROVIDE ANGLE

BETWEEN JOISTS TO

DISTRIBUTE LOAD) (PROVIDE

SPRING VIBRATION ISOLATOR

HANGERS)

BUTTERFLY VALVE (TYP.)

AIR/DIRT SEPARATOR DETAIL

NO SCALE

FILTER FEEDER DETAIL

NO SCALE

ROUTE TO NEAREST

FLOOR DRAIN

ECCENTRIC TRANSITION,

(TOP FLAT, TYPICAL)

3 4

DOMESTIC

MAKEUP PIPING

CHECK BFP ASSY

DBL

DIGITAL FLOW METER W/

PULSE OUTPUT CAPABILITY.

CONNECT TO BAS FOR

MONITORING PURPOSES.

TO EXPANSION

TANK FEED

LINE

BALL VALVE

(N.C.)

3/4"

3/4"

BALL VALVE

(N.O.)

PRESSURE REDUCING

VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE

3/4"3/4"

TO DRAIN

MAKE-UP WATER PIPING DETAIL

NO SCALE

4" CHWR

4" CHWS

FLEX

CONNECTOR,

(TYP.)

HOUSEKEEPING PAD

PRESSURE

GAUGE W/ COCK

(TYP.)

FLOW

SWITCH

P/T PORT (TYP.)

THERMOMETER (TYP.)

BUTTERFLY

VALVE

P

PFS

P

CONTROL SEQUENCE FOR CHILLED WATER SYSTEM:

1. SYSTEM DESCRIPTION: THE CHILLED WATER SYSTEM CONSISTS OF ONE AIR COOLED SCROLL

CHILLER AND TWO VFD CONTROLLED CHILLED WATER PUMPS PIPED IN PARALLEL FOR

LEAD/STAND BY OPERATION. LEAD/STAND-BY STATUS SHALL BE ROTATED BY THE BAS

WEEKLY FOR THE PUMPS.

2. CHILLER START: UPON CHILLER ENABLE, THE BAS SHALL ENABLE (SOFT START) THE LEAD

PUMP, RAMP THE SPEED OF THE PUMP TO THE DESIGN FLOW RATE AND MONITOR STATUS

VIA CURRENT SENSOR. ONCE CHILLED WATER FLOW IS PROVEN VIA THE FLOW SWITCH, THE

BAS SHALL ENABLE THE CHILLER. THE BAS SHALL MONITOR THE CHILLER VIA BACNET MS/TP

AND ALARM IF THE CHILLER FAILS. THE CHILLER'S FACTORY CONTROLS SHALL MAINTAIN

THE LEAVING WATER TEMPERATURE SET POINT OF 44F (ADJ.). THE BAS SHALL ENABLE THE

STAND-BY PUMP IN THE EVENT OF A LEAD PUMP FAILURE. THE BAS SHALL ALARM IN THE

EVENT OF EQUIPMENT FAILURE.

3. CHILLER STOP: WHEN THE CHILLER IS COMMANDED TO STOP, THE BAS SHALL DISABLE THE

CHILLER AND DISABLE THE CHILLED WATER PUMP.

4. FREEZE PROTECTION: IN THE EVENT OF AN EVAPORATOR LOW TEMPERATURE ALARM, THE

BAS SHALL ENABLE THE CHILLED WATER PUMP AND OPERATE IT AT THE DESIGN FLOW

RATE.

CH-1

BACnet MS/TP

(CONNECT TO BAS)

P-1

BUILDING LOAD

AHUS WITH

EXISTING 3-WAY

CHILLED WATER

CONTROL VALVES

AIR COOLED

CHILLER

S/S

STATUS

ALARM TS

TS

TS

BI

BI

BO

P-2

T

CHW RETURN

TEMP

AI IMMER

T

CHW SUPPLY

TEMP

AI IMMER

FS

CHW FLOW

BI DPS

S/S TS

STATUS TS

SPEED TS

CHILLED WATER

PUMP (2 THUS)

VFD

VFD

THE NEW CHILLER SYSTEM SHALL BE

INTEGRATED INTO THE EXISTING

TRANE TRACER SUMMIT BUILDING

AUTOMATION SYSTEM

CONNECT

NEW MAKEUP

WATER PIPING

TO EXISTING

ISOLATION

VALVE.

'MSB'

CH-1

CHP-1 CHP-2

B-1

MOTOR

STARTERS

XFMR 'T-LDR2'

EXISTING CPS

TRANSFORMER

WATER VALVES &

BACKFLOW PREV

UTILITY YARD

WIREWAY

PULLBOX

LDR2 HV1

MDPL

GND

T-MDPL

CENTRAL PLANT

CONTROLLER

AHU CONTROLLER

HVAC CONTROLS

SEC 1 SEC 2

EXISTING CPS

TRANSFORMER

UTILITY YARD

MOTOR

STARTERS

LDR2 HV1

B-1

'MSB'

'MSB'

MDPL

GND

SEC 1 SEC 2

T-MDPL

CENTRAL PLANT

CONTROLLER

AHU CONTROLLER

HVAC CONTROLS

CH-1

CHP-1 CHP-2

1. PROVIDE NEW ELECTRICAL EQUIPMENT, AS INDICATED. REFER TO ELECTRICAL ONE-LINE

DIAGRAM ON SHEET E103 FOR ADDITIONAL INFORMATION.

2. REMOVE AND RELOCATE EXISTING CPS METER. SALVAGE ASSOCIATED FEEDERS FOR

RECONNECTION. REFER TO DETAIL 2 ON THIS SHEET AND ELECTRICAL ONE-LINE DIAGRAM

ON SHEET E103 FOR ADDITIONAL INFORMATION.

3. PROVIDE GALVANIZED ELECTRICAL RACK FOR MOUNTING OF ELECTRICAL EQUIPMENT.

REFER TO ELECTRICAL ONE-LINE DIAGRAM ON SHEET E103 FOR ADDITIONAL INFORMATION.

4. NEW LOCATION OF SALVAGED CPS METER.

5. EXTEND PAD PER CPS STANDARD TO ALLOW FOR THE INSTALLATION OF NEW TAP BOX.

6. RECONNECT SALVAGED FEEDERS, AS INDICATED. EXTEND FEEDERS TO CONNECT TO

DISCONNECT, AS INDICATED.

7. PROVIDE CONDUIT, AS INDICATED. FIELD COORDINATE ROUTING WITH EXISTING

CONDITIONS. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON SHEET E103 FOR ADDITIONAL

INFORMATION.

8. PROVIDE NEW FEEDERS TO EXISTING DISCONNECT TO FEED NEW 'MSB'. REFER TO

ELECTRICAL ONE-LINE DIAGRAM ON SHEET E103 FOR ADDITIONAL INFORMATION.

9. PROVIDE FUSED DISCONNECT AND ASSOCIATED LINE-SIDE FEEDER FOR CONNECTION TO

TEMPORARY CHILLER. COORDINATE FUSE SIZE WITH TEMPORARY CHILLER PROVIDER

PRIOR TO INSTALLATION.

10. REMOVE EXISTING AHU CONTROLLER. SALVAGE ASSOCIATED CIRCUITRY AND CONTROL

WIRING.

11. NEW LOCATION OF AHU CONTROLLER. RECONNECT SALVAGE CIRCUITRY AND CONTROL

WIRING. EXTEND WIRING AS REQUIRED FOR A COMPLETE FUNCTIONAL SYSTEM.

KEYED NOTES: (APPLIES TO THIS SHEET)

1. COMPLETE WORK IN ACCORDANCE WITH APPLICABLE CODES, ORDINANCES, AND

INTERPRETATIONS OF AHJ.

2. COORDINATE WORK WITH OTHER TRADES AS REQUIRED TO PROVIDE COMPLETE SYSTEMS

AND AVOID CONFLICTS.

3. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE THE

GREATEST POSSIBLE CLEARANCE FOR PLUMBING AND MECHANICAL EQUIPMENT BOTH

CURRENT AND FUTURE. CONDUITS SHALL BE KEPT TIGHT TO STRUCTURE OR ROUTED

THROUGH STRUCTURAL TRUSSES WHEREVER POSSIBLE.

4. COORDINATE LOCATION OF ALL DISCONNECT SWITCHES TO ENSURE THAT ALL NEC

MINIMUM WORKING CLEARANCES ARE MAINTAINED.

5. SINGLE HOMERUNS ARE SHOWN FOR CIRCUIT IDENTIFICATION ONLY. CIRCUITS MAY BE

GROUPED UP TO THREE (3) PHASE CONDUCTORS PER RACEWAY, UNLESS NOTED

OTHERWISE.

6. HOMERUNS AND RUNS BETWEEN JUNCTION BOXES SHALL BE MINIMUM OF 3/4" CONDUIT

AND SHALL INCLUDE #10 (MINIMUM) CONDUCTORS AND INSULATED GROUNDING

CONDUCTOR. CIRCUIT SHALL EXTEND FROM OCPD TO A JUNCTION BOX IN THE AREA OF

THE RECEPTACLES OR UTILIZATION EQUIPMENT. DROPS TO INDIVIDUAL 20-AMP WIRING

DEVICES SHALL INCLUDE #12 (MINIMUM) CONDUCTORS.

7. VOLTAGE DROP TO LAST DEVICE ON BRANCH CIRCUIT SHALL NOT EXCEED 3 PERCENT

FROM PANEL. INCREASE BRANCH CIRCUIT CONDUCTOR SIZES AS REQUIRED TO ALLOW

FOR CIRCUIT LENGTH.

8. FMC OR LFMC SHALL BE USED FOR CONNECTIONS TO VIBRATION PRODUCING EQUIPMENT,

SUCH AS MOTORS, TRANSFORMERS, AND HVAC EQUIPMENT. LFMC SHALL BE USED IN DAMP

AND WET LOCATIONS.

9. PROVIDE UL LISTED FIRE STOP SYSTEMS AT ALL PENETRATIONS THROUGH RATED

PARTITIONS.

10. WIRING DEVICES SHALL BE SPECIFICATION-GRADE DEVICES, LISTED AND LABELED BY A

NRTL.

11. ALL FEEDER AND BRANCH CIRCUIT WIRING SHALL BE COPPER.

12. MARK JUNCTION BOX COVERS USING PERMANENT MARKER INDICATING THE PANEL AND

CIRCUIT NUMBERS SERVING THE JUNCTION BOX.

(APPLIES TO ALL ELECTRICAL SHEETS)

GENERAL

POWER NOTES:

E102

ENLARGED

ELECTRICAL FLOOR

PLANS - PHASE 1

SCALE:

NORTH

1 ENLARGED ELECTRICAL PLAN - MECH RM - STEP 1 - PHASE 1

1/4" = 1' - 0"

1. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF TELEPHONE OUTLETS, DATA

OUTLETS, FLOOR OUTLETS, RECEPTACLES, AND ELECTRICAL CONNECTIONS TO BE REMOVED.

FIELD VERIFY LOCATION AND QUANTITY OF ITEMS TO BE REMOVED, AS NO ALLOWANCE WILL BE

MADE BECAUSE OF UNFAMILIARITY WITH THESE DETAILS.

2. EXISTING CIRCUITS INDICATED WERE OBTAINED FROM AS-BUILT DRAWINGS AND MAY NOT BE

CORRECT. IDENTIFY AND LOCATE EXISTING BRANCH CIRCUITRY.

3. REMOVE BRANCH CIRCUITS SERVING EQUIPMENT, RECEPTACLES, LIGHT FIXTURES, MOTORS, AND OTHER ITEMS SHOWN TO BE REMOVED BACK TO OCPD IN SWITCHBOARD, PANEL, LOAD

CENTER, OR J-BOX GRID SYSTEM, EXCEPT AS OTHERWISE REQUIRED BY NOTES BELOW.

3.1. BRANCH CIRCUIT: CONDUCTORS, RACEWAYS, BOXES, WIREWAYS, WIRING DEVICES,

COVERPLATES, DISCONNECTING MEANS, STARTERS, CONTROLLERS, AND SUPPORTS.

3.2. OCPD SHALL REMAIN AS AN INTEGRAL PART OF EXISTING SWITCHBOARD, PANEL, OR LOAD

CENTER, AND IF NOT BEING REUSED, SHALL BE LABELED AS SPARE.

3.3. CONDUITS IN INACCESSIBLE AREAS: REMOVE CONDUCTORS AND ABANDON IN PLACE,

CAPPED AND SEALED. IN A FINISHED SPACE, REMOVED CONDUIT TO BELOW FINISHED

SURFACE, FILL VOID WITH NON-SHRINKING GROUT, AND RESURFACED TO MATCH

SURROUNDING SURFACES.

4. MAINTAIN INTEGRITY OF BRANCH CIRCUITS WITH A PORTION OF THE LOAD REMOVED. REMOVE

PORTION OF BRANCH CIRCUIT ASSOCIATED WITH REMOVED DEVICE TO A POINT AS NECESSARY

TO SERVE REMAINING LOAD.

5. EXTEND BRANCH CIRCUITS WHERE INDICATED TO SERVE NEW LOADS OR TO RECONNECT

RELOCATED EQUIPMENT. RUN CONDUIT CONCEALED WHERE POSSIBLE, AND ROUTE TO AVOID

INTERFERENCE WITH EQUIPMENT OR AESTHETICS. REPLACE WITH NEW CONDUCTORS FROM

OCPD TO LOAD.

6. INCLUDE IN BID COSTS RESULTING FROM OVERTIME, EVENING, AND WEEKEND WORK.

COORDINATE WITH OWNER ON OPERATION SCHEDULES AND ASSOCIATED REQUIREMENTS.

7. SALVAGED ITEMS AND MATERIALS SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL

BE DELIVERED TO OWNER’S DESIGNATED STORAGE FACILITY.

8. REMOVE FROM PROJECT SITE DEMOLISHED MATERIALS AND EQUIPMENT. DISPOSE OF IN

ACCORDANCE WITH APPLICABLE ENVIRONMENTAL LAWS AND REGULATIONS. REMOVE PCB

CONTAINING BALLASTS AND DISPOSE OF THROUGH AUTHORIZED DISPOSAL FACILITY.

9. PROVIDE CLOSURE CAPS IN EXISTING CORE DRILLED HOLES. FILL IN REMAINING HOLES WITH

FLOOR STONE CEMENT FLUSH WITH SURROUNDING AREA.

10. SEAL OPENINGS IN FIRE RESISTANCE RATED PARTITIONS TO PRESERVE RATING OF PARTITION.

11. DAMAGE CAUSED BY THE WORK, WHICH IS NOT CONCEALED BY NEW CONSTRUCTION, SHALL BE

REPAIRED TO MATCH EXISTING SURFACES.

12. IDENTIFY AND LOCATE EXISTING UTILITIES THAT MAY CONFLICT WITH NEW WORK, AND INCLUDE

IN BID COSTS NECESSARY TO COORDINATE THE INSTALLATION OF THE NEW WORK WITH THE

EXISTING UTILITIES.

13. COORDINATE AND VERIFY ACTUAL LENGTHS AND ROUTES OF CONDUIT AND FEEDER RUNS

WITH ENGINEERED DRAWINGS AS WELL AS EXISTING SITE CONDITIONS PRIOR TO SUBMISSION

OF BID OR PROPOSAL.

14. COORDINATE AND SCHEDULE ELECTRICAL AND COMMUNICATION SERVICE OUTAGES TO

EXISTING FACILITIES WITH OWNER IN ADVANCE OF OUTAGE.

15. PERFORM WORK IN A MANNER TO MINIMIZE INTERRUPTION OF SERVICES TO OCCUPIED SPACES

AND TO MAINTAIN SERVICE TO ROOMS NOT UNDERGOING ACTIVE CONSTRUCTION.

16. PRIOR TO BID, VISIT THE PROJECT SITE, BECOME FAMILIAR WITH THE CONDITIONS AS THEY

EXIST, AND CONFIRM LOCATIONS, SIZES, AND QUANTITIES OF MATERIALS AND ITEMS TO BE

REMOVED OR INSTALLED. LOOK ABOVE CEILINGS IN AREAS TO BE RENOVATED, AND IDENTIFY

QUANTITIES MATERIALS TO BE REMOVED.

(APPLIES TO ALL ELECTRICAL SHEETS)

GENERAL ELECTRICAL

DEMOLITION NOTES:

E

D

C

B

A

654321

Drawn Checked Date Project No.

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

LME

TJS

23002 10/13/23

SCALE:

NORTH

2 ENLARGED ELECTRICAL PLAN - MECH RM - STEP 2 - PHASE 1

1/4" = 1' - 0"

Revisions 1 11-27-2023 Addendum #03

1 1

/2

7/

FEEDER SCHEDULE

3 PHASE, 4 WIRE

TAG CONDUIT PHASE CONDUCTORS NEUTRAL CONDUCTORS GROUND CONDUCTORS

1000N (3)3" EACH WITH (3)#400 KCMIL (1)#400 KCMIL (1)# 2/0 GND.

400N (1)4" EACH WITH (3)#600 KCMIL (1)#600 KCMIL (1)# 3 GND.

3 PHASE, 3 WIRE

TAG CONDUIT PHASE CONDUCTORS NEUTRAL CONDUCTORS GROUND CONDUCTORS

175 (1)1-1/2" EACH WITH (3)2/0 AWG NA (1)#3 GND.

NOTES:

1. CONDUIT SIZES ARE FOR CONDUIT INDICATED WITH THHN, THWN INSULATED COPPER CONDUCTORS WITH MAXIMUM 40% FILL. CONTRACTOR SHALL ADJUST CONDUIT SIZE AS REQUIRED PER NEC APPENDIX C, CONDUIT FILL TABLES FOR ALL OTHER CONDUIT AND INSULATION TYPES.

2. REFER TO SPECIFICATIONS FOR ADDITIONAL CONDUIT APPLICATION AND INSTALLATION REQUIREMENTS.

3. PROVIDE LUGS AS REQUIRED FOR FEEDERS INDICATED.

E103

ELECTRICAL

ONE - LINE DIAGRAM

PHASE 1

200A

125AF

200A

200AF

200A

125AF

200A

175AF

400A

300AF

200A

200AF

G N

75 kVA

XFMR

T-LC

CHILLER

CH-1

T-LDR2

15kVA XFMR

1000A

1000AF

30A

30AF

30A

30AF

400A

225AF

75 kVA

XFMR

T-LB

400A

225AF

400A

350AF

112.5 kVA

XFMR

T-LA

EMERG

LIGHTS

MAIN SWITCHBOARD 'MSB', 480/277V, 1000A, 3PH, 4W

200A

200AF

EXISTING

PANEL

'LC'

225A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'LC'

100A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'HA'

225A MLO

480/277V

3PH, 4W

N1

EXISTING

PANEL

'LB'

225A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'LA'

400A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'LD'

225A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'HV1' SEC1

200A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'HV1' SEC 2

200A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'LDR2'

100A MLO

208/120V

3PH, 4W

N1

NOTE TO CONTRACTOR:

PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE

AND SCHEDULE ELECTRICAL SERVICE OUTAGES TO EXISTING

FACILITIES WITH OWNER IN ADVANCE OF OUTAGE.

E

D

C

B

A

654321

Drawn Checked Date Project No.

Revisions

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

LME

TJS

23002 10/13/23

112.5 kVA

XFMR

T-MDPL

NEW

PANEL

'MDP'

400A MLO

208/120V

3PH, 4W

N1

CAP

BANK

400N

1000N

1000N

11-27-2023 Addendum #03

400N

400A

400AF

/2

7/

CHILLER - SEE MECH

'MSB'

CH-1

CHP-1 CHP-2

B-1

MOTOR

STARTERS

XFMR 'T-LDR2'

EXISTING CPS TRANSFORMER

WATER VALVES & BACKFLOW PREV

XFMR

SEC DISC

XFMR 'T-LC'

(ABOVE)

UTILITY YARD

WIREWAY

PULLBOX

LDR2 HV1

LE

LC

5 'MSB'

MDPL

GND

SEC 1 SEC 2

T-MDPL

CENTRAL PLANT

CONTROLLER

AHU CONTROLLER

HVAC CONTROLS

AHU

CONTROLLER

XFMR

SEC DISC

XFMR 'T-LB'

(ABOVE)

3 LB

HA

LD

XFMR 'T-LA'

(ABOVE CEILING)

XFMR

SEC DISC

LA

CU-1 4

1. REMOVE EXISTING TRANSFORMER, ASSOCIATED DISCONNECT AND FEEDERS BACK TO

SOURCE PANELBOARD.

2. EXISTING TRANSFORMER TO BE ABANDONED IN PLACE. REMOVE ASSOCIATED DISCONNECT

AND FEEDERS BACK TO SOURCE PANELBOARD.

3. REMOVE EXISTING PANELBOARD. ASSOCIATED BRANCH CIRCUITRY TO REMAIN FOR

RECONNECTION.

4. REMOVE POWER AND MAKE SAFE. REMOVE FEEDERS BACK TO SOURCE PANEL.

5. REMOVE EXISTING MSB AND ASSOCIATED BRANCH CIRCUITRY, UNLESS NOTED

OTHERWISE. REFER TO ONE-LINE DIAGRAM ON SHEET RE:1/E203 FOR ADDITIONAL

INFORMATION.

KEYED NOTES: (APPLIES TO THIS SHEET)

E202

ENLARGED

ELECTRICAL FLOOR

PLANS - PHASE 2

SCALE:

NORTH

1 GIRLS DRESSING ROOM - PHASE 2

ENLARGED ELECTRICAL PLAN - MECH RM AND

1/4" = 1' - 0"

SCALE:

NORTH

3 WORK ROOM - PHASE 2

ENLARGED ELECTRICAL PLAN -

1/4" = 1' - 0" SCALE:

NORTH

4 JANITOR CLOSET - PHASE 2

ENLARGED ELECTRICAL PLAN -

1/4" = 1' - 0"SCALE:

NORTH

2 AND STORAGE - PHASE 2

ENLARGED ELECTRICAL PLAN - MECH RM

1/4" = 1' - 0"

E

D

C

B

A

654321

Drawn Checked Date Project No.

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

LME

TJS

23002 10/13/23

NOTE TO CONTRACTOR:

PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE

AND SCHEDULE ELECTRICAL SERVICE OUTAGES TO EXISTING

FACILITIES WITH OWNER IN ADVANCE OF OUTAGE.

SCALE:

NORTH

5 ENLARGED ROOF PLAN - PHASE 2

1/4" = 1' - 0"

Revisions 1 11-27-2023 Addendum #03

/2

7/

MOTOR

STARTERS

EXISTING CPS TRANSFORMER

WATER VALVES & BACKFLOW PREV

UTILITY YARD

WIREWAY

LDR2 HV1

LE

LC

EF-2 EF-1

B-1

FD

FD

AS-1

CH-1

CHP-1

CHP-2

VFD-1

VFD-2

'MSB'

MDPL

GND

SEC 1 SEC 2

T-MDPL

CENTRAL PLANT

CONTROLLER

AHU CONTROLLER

HVAC CONTROLS

HV1-56,58,60

HV1-55,57,59

MSB-7 3

AHU

CONTROLLER

LB

HA 1

LD

LA

1. PROVIDE NEW PANELBOARD, AS INDICATED. RECONNECT BRANCH CIRCUITRY SALVAGED

DURING DEMOLITION. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION.

2. PROVIDE POWER CONNECTION TO HVAC EQUIPMENT, AS INDICATED. REFER TO PANEL

SCHEDULES FOR ADDITIONAL INFORMATION.

3. PROVIDE POWER CONNECTION TO CHILLER WITH INTEGRAL DISCONNECT.

KEYED NOTES: (APPLIES TO THIS SHEET)

E302

ENLARGED

ELECTRICAL FLOOR

PLANS - PHASE 3

SCALE:

NORTH

1 GIRLS DRESSING ROOM - PHASE 3

ENLARGED ELECTRICAL PLAN - MECH RM AND

1/4" = 1' - 0"

SCALE:

NORTH

3 WORK ROOM - PHASE 3

ENLARGED ELECTRICAL PLAN -

1/4" = 1' - 0" SCALE:

NORTH

4 JANITOR CLOSET - PHASE 3

ENLARGED ELECTRICAL PLAN -

1/4" = 1' - 0"SCALE:

NORTH

2 AND STORAGE - PHASE 3

ENLARGED ELECTRICAL PLAN - MECH RM

1/4" = 1' - 0"

E

D

C

B

A

654321

Drawn Checked Date Project No.

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

LME

TJS

23002 10/13/23

Revisions 1 11-27-2023 Addendum #03

/2

7/

E303

ELECTRICAL

ONE - LINE DIAGRAM

PHASE 3

E

D

C

B

A

654321

Drawn Checked Date Project No.

Revisions

2023 Marmon Mok, LLP Unauthorized reproduction is prohibited.

c

SHEET TITLE

SHEET NO.

Fi le

P at h

2/ 8/

:3

4:

P M

FR

AN

K G

AR

R

ET

T

C O

M M

U N

IT

Y

C

EN

TE

R

R

EN

O

VA

TI

O

N

PA

C

KA

G

E

N W

8t h St

Sa n An to ni o, T

X

LME

TJS

23002 10/13/23

CHILLER

CH-1

T-LDR2

15kVA XFMR

112.5 kVA

XFMR

T-MDPL

NEW

PANEL

'LC'

125A MLO

208/120V

3PH, 4W

N1

NEW

PANEL

'HA'

225A MLO

480/277V

3PH, 4W

N1

NEW

PANEL

'LB'

225A MLO

208/120V

3PH, 4W

N1

NEW

PANEL

'LE'

125A MLO

208/120V

3PH, 4W

N1

NEW

PANEL

'LD'

100A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'HV1' SEC1

200A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'HV1' SEC 2

200A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'LDR2'

100A MLO

208/120V

3PH, 4W

N1

EXISTING

PANEL

'MDPL'

400A MCB

208/120V

3PH, 4W

N1

FEEDER SCHEDULE

3 PHASE, 4 WIRE

TAG CONDUIT PHASE CONDUCTORS NEUTRAL CONDUCTORS GROUND CONDUCTORS

1000N (3)3" EACH WITH (3)#400 KCMIL (1)#400 KCMIL (1)# 2/0 GND.

400N (1)4" EACH WITH (3)#600 KCMIL (1)#600 KCMIL (1)# 3 GND.

225N (1)3" EACH WITH (3)#4/0 AWG (1)#4/0 AWG (1)# 4 GND.

125N (1)2" EACH WITH (3)#1 AWG (1)#1 AWG (1)# 6 GND.

100N (1)2" EACH WITH (3)#3 AWG (1)#3 AWG (1)# 8 GND.

3 PHASE, 3 WIRE

TAG CONDUIT PHASE CONDUCTORS NEUTRAL CONDUCTORS GROUND CONDUCTORS

175 (1)1-1/2" EACH WITH (3)2/0 AWG NA (1)#3 GND.

NOTES:

1. CONDUIT SIZES ARE FOR CONDUIT INDICATED WITH THHN, THWN INSULATED COPPER CONDUCTORS WITH MAXIMUM 40% FILL. CONTRACTOR SHALL ADJUST CONDUIT SIZE AS REQUIRED PER NEC APPENDIX C, CONDUIT FILL TABLES FOR ALL OTHER CONDUIT AND INSULATION TYPES.

2. REFER TO SPECIFICATIONS FOR ADDITIONAL CONDUIT APPLICATION AND INSTALLATION REQUIREMENTS.

3. PROVIDE LUGS AS REQUIRED FOR FEEDERS INDICATED.

400N

225N

NEW

PANEL

'LA'

225A MLO

208/120V

3PH, 4W

N1

225N 225N 125N 125N

100N

11-27-2023 Addendum #03

400N

400A

400AF

/2

7/

Addendum 3
2023-11-27 - Frank Garrett Package 2 - Add 04 - Narrative
2023-11-27 - Frank Garrett Package 2 - Add 04 - MP Drawings
Sheets and Views
23002 - M201 - Mech Schedules & Details-30x42 M201
2023-11-27 - Frank Garrett Package 2 - Add 04 - E Drawings
Sheets and Views
30x42 E102
30x42 E103
30x42 E202
30x42 E302
30x42 E303

File details come from the government source that posted it. Updated .