ESBD_File_331667_Exhibit 6 BEC MEP.xlsx

XLSX spreadsheet 1012 KB Posted

Attached to
Facility Operation and Utility Complex (BEC and MEP) - Baylor University
Solicitation number
RFP2023-0253
Issued by
Mclennan County, Waco City, Texas

About this file

This document is a Request for Proposal (RFP) issued by Baylor University to solicit proposals from qualified and experienced firms to provide facility operations and maintenance services related to the Baylor Energy Complex (BEC) and campuswide Mechanical, Electrical, and Plumbing (MEP) services. The RFP covers the jurisdictions of McLennan County and the City of Waco, Texas. The requested services include maintaining the BEC and providing MEP services across the Baylor University campus. The RFP does not specify quantities, but does provide details on response due dates, bidder site visits, and the contract term, which appears to be for an initial period with renewal options.

The RFP does not provide specifics on pricing terms, set asides, incumbents, funding requirements, or funding sources. However, it indicates that the University is seeking qualified and experienced firms to provide the requested facility operations and maintenance services for the BEC and campus-wide MEP.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Summary

Exhibit 6 - BEC Annual Work Order Summary
BEC WO Types
Row LabelsCount of WO Type Description
Corrective547
Inspection1496
PM1217
Grand Total3260
BEC Trades
Row LabelsCount of Type-Description
1000 - Administrative5
1500 - Carpentry3
2000 - Electrical2
4000 - HVAC4
6000 - Mechanical526
7000 - Painting1
8500 - Plumbing6
9500 - Safety/Security82
I - zInspection1319
P - zPlanned1312
Grand Total3260

Export

WO #RequestedTask ClosedFinish DateEst. CompletionClientBuildingAreaDepartmentTask Code-DescriptionType-DescriptionTag #DescriptionItem TypeShopTradeSupervisorPriorityContractorStatusProjectProject NameRequestDue DateWO Type DescriptionWO Task Posted HoursChargeableItem SubLocationTask Comments
0263-61377705/01/2022 07:0005/11/2022 14:0205/11/2022 14:0205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P2007 - Baylor Energy Complex UPSP - zPlanned18267UPSEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompleted and ClosedBaylor Energy Complex UPS05/01/2022 07:00PM0.18FALSERoger Fowler-Checked for cleanliness, damage, and proper operation.
0263-61379405/01/2022 07:0005/09/2022 15:4005/09/2022 15:4005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16494(NEW TOWERS) FAN 11EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury on motor. Checked for leaks, damage, volts, amps, and proper operation.
0263-61379605/01/2022 07:0005/09/2022 15:0705/09/2022 15:0705/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16495(NEW TOWERS) FAN-10EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.26FALSERoger Fowler-Performed augury on motor. Checked for leaks, damage, volts, amps, and proper operation.
0263-61379705/01/2022 07:0005/09/2022 14:4605/09/2022 14:4605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16496(NEW TOWERS) FAN-9EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.05FALSERoger Fowler-Tower 9 fan vfd is down for replacement.
0263-61379805/01/2022 07:0005/09/2022 14:3105/09/2022 14:3105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16497(CERAMIC) Tower FAN-6EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.23FALSERoger Fowler-Performed augury on motor. Also checked amps, volts, for leaks, damage, and proper operation.
0263-61379905/01/2022 07:0005/26/2022 13:0005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned16556Chiller-4EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.97FALSEJohn Charette-performed augury on motor and compressor, submitted reading for diagnosis, waiting for results from augury

checked for leaks from all valves and flanges on condenser and chilled water supply and returns to and from chiller checked oil level- no oil added checked for any signs of visible damage to chiller and all valves verified proper operation of chiller John Charette-received results from augury, updated on results page

0263-61380005/01/2022 07:0005/09/2022 14:1405/09/2022 14:1405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16498(CERAMIC) Tower FAN-5EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.23FALSERoger Fowler-Performed augury on motor. Checked amps, volts, for damage, leaks, and proper operation.
0263-61381205/01/2022 07:0005/09/2022 11:1005/09/2022 11:1005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16466CHWP-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury on pump. Checked volts, amps, leaks, damage, and proper operation.
0263-61381305/01/2022 07:0005/09/2022 10:5605/09/2022 10:5605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16467CHWP-7EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.35FALSERoger Fowler-Performed augury on pump. Checked for leaks, damage, volts, amps, and proper operation.
0263-61381505/01/2022 07:0005/26/2022 13:0805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16478CWP-12EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompleted and ClosedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.25FALSEJohn Charette-this pump is used only if needed , in need of replacement motor and pump

checked oil level

0263-61381605/01/2022 07:0005/05/2022 13:1005/05/2022 13:1005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16480CWP-15EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.27FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation.
0263-61381705/01/2022 07:0005/05/2022 14:1805/05/2022 14:1805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16482CWP-14EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.28FALSERoger Fowler-Performed augury, checked for leaks, damage, and proper operation.
0263-61381805/01/2022 07:0005/05/2022 14:1504/28/2022 14:1505/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16484CWP-13EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.00FALSERoger Fowler-VFD's for tower 9 and CWP 13 are down for repair.
0263-61381905/01/2022 07:0005/17/2022 14:0105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned16406Chiller-1EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM1.00FALSEJohn Charette-performed augury on both motors and compressors, summited reading for diagnosis, waiting for results from augury

checked for leaks from condenser and evaporator chambers checked for leaks from valves and flanges from condenser and evaporator water piping checked oil level verified proper operation of chiller took temp readings on chiller checked for any signs of visible damage John Charette-received results from augury, updated on results page

0263-61385705/01/2022 07:0005/09/2022 13:4405/09/2022 13:4405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16503(BAC) Tower FAN-8EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.21FALSERoger Fowler-Performed augury on motor. Checked for leaks, damage, volts, amps, and proper operation.
0263-61385805/01/2022 07:0005/09/2022 13:3805/09/2022 13:3805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16504(BAC) Tower FAN-7EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury on motor. Checked volts, amps, for leaks, damage, and proper operation.
0263-61385905/01/2022 07:0005/09/2022 13:2905/09/2022 13:2905/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16516(CERAMIC) Tower FAN-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.22FALSERoger Fowler-Performed augury on motor. Also checked amps, volts, damage, leaks, and proper operation.
0263-61386005/01/2022 07:0005/09/2022 13:2105/09/2022 13:2105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned16517(CERAMIC) Tower FAN-3EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.26FALSERoger Fowler-Performed augury on motor. Also checked amps, volts, oil leaks, damage, and proper operation.
0263-61386105/01/2022 07:0005/09/2022 13:0405/09/2022 13:0405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned18243(CERAMIC) Tower FAN-1EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.22FALSERoger Fowler-Performed augury on motor. I checked the amps, volts, for leaks, and proper operation.
0263-61389105/01/2022 07:0005/05/2022 14:1205/05/2022 14:1205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16488CWP-7EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.22FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation.
0263-61389205/01/2022 07:0005/05/2022 13:4205/05/2022 13:4205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16486CWP-11EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.21FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation.
0263-61389305/01/2022 07:0005/05/2022 13:3005/05/2022 13:3005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned18249CWP-8EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.24FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation
0263-61389605/01/2022 07:0005/17/2022 13:5805/17/2022 13:5805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4104 - Baylor Energy Complex Boiler MonthlyP - zPlanned16543Boiler-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Boiler05/01/2022 07:00PM0.26FALSERoger Fowler-Performed augury on boiler blower motor. Checked for leaks, damage, proper operation, and anything unusual.
0263-61390905/01/2022 07:0005/03/2022 08:2705/03/2022 08:2705/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4127 - Baylor Energy Complex Steam HeaderP - zPlanned16336Campus Steam HeaderEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Steam Header05/01/2022 07:00PM0.56FALSERoger Fowler-Inspected header for leaks, damage, other any other issues
0263-61391005/01/2022 07:0005/02/2022 10:0505/02/2022 10:0505/31/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4120 - Baylor Energy Complex Chill Water Make-UpP - zPlanned16335Chill Water Make-Up Feed SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Make-Up05/31/2022 07:00PM0.78FALSERoger Fowler-Inspected chill water make up for leaks, damage, or any other issues.
0263-61391105/01/2022 07:0005/05/2022 13:0105/12/2022 13:0105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P8507 - Baylor Energy Complex Chemical SumpP - zPlanned16334Sump Pump OUTSIDEEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Chemical Sump05/01/2022 07:00PM0.24FALSERoger Fowler-Inspected sump pump foe cleanliness, damage, and proper operation.
0263-61391205/01/2022 07:0005/02/2022 09:3405/02/2022 09:3405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P1523 - Baylor Energy Complex StructureP - zPlanned16333TCC StructureEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedBaylor Energy Complex Structure05/01/2022 07:00PM1.58FALSERoger Fowler-Inspected structure for damage, leaks, and any other structural issues
0263-61391305/01/2022 07:0005/02/2022 15:1205/02/2022 15:1205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P1524 - Baylor Energy Complex Storm TrenchP - zPlanned16346Trench Pit south sideEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Storm Trench05/01/2022 07:00PM0.26FALSEnear south tunnelRoger Fowler-Inspected trench for cleanliness and any other issues.
0263-61391405/01/2022 07:0005/02/2022 14:1005/02/2022 14:1005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P8508 - Baylor Energy Complex Sump PumpP - zPlanned16345Sump Pump South TunnelEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Sump Pump05/01/2022 07:00PM0.24FALSERoger Fowler-Inspected sump pump for cleanliness, damage, and proper operation.
0263-61391505/01/2022 07:0005/02/2022 12:1405/02/2022 12:1405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P8508 - Baylor Energy Complex Sump PumpP - zPlanned16341Sump Pump North TunnelEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Sump Pump05/01/2022 07:00PM0.26FALSERoger Fowler-Inspected sump pump for cleanliness, damage, and proper operation.
0263-61391605/01/2022 07:0005/02/2022 13:5705/02/2022 13:5705/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P2003 - Baylor Energy Complex LightingP - zPlanned16339Inside Lighting/Receptacles/Circuit BreakersEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Lighting05/29/2022 07:00PM0.62FALSETim Massie-Checklist completed for lights and breakers
0263-61391705/01/2022 07:0005/05/2022 07:1005/05/2022 07:1005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P2003 - Baylor Energy Complex LightingP - zPlanned16337Outside LightingEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompleted and ClosedBaylor Energy Complex Lighting05/01/2022 07:00PM5.95FALSEBoiler 3 area has a light out. Please replace.
0263-61391805/01/2022 07:0005/02/2022 10:2405/02/2022 10:2405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P1524 - Baylor Energy Complex Storm TrenchP - zPlanned16340Trench Pit MainEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Storm Trench05/01/2022 07:00PM0.31FALSERoger Fowler-Inspected trench for cleanliness and any other issues.
0263-61391905/01/2022 07:0005/17/2022 13:4605/17/2022 13:4605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4104 - Baylor Energy Complex Boiler MonthlyP - zPlanned16541Boiler-1EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Boiler05/01/2022 07:00PM0.52FALSERoger Fowler-Performed augury on boiler blower motor. Also inspected boiler for leaks, damage, anything unusual, and proper operation.
0263-61393705/01/2022 07:0005/04/2022 13:5505/04/2022 13:5505/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned16407Chiller-6EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.38FALSEJohn Charette-Performed augury on chiller motors. Also checked for leaks, damage, and proper operation.
0263-61393905/01/2022 07:0005/03/2022 08:1305/03/2022 08:1305/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4102 - Baylor Energy Complex Air DryerP - zPlanned16490Air Dryer-1EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Air Dryer05/01/2022 07:00PM0.20FALSERoger Fowler-Air dryer is brand new
0263-61394005/01/2022 07:0005/09/2022 10:5105/09/2022 10:5105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16468CHWP-3EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.37FALSERoger Fowler-Performed augury on pump. Also checked for leaks, damage, volts, amps, and proper operation.
0263-61394105/01/2022 07:0005/09/2022 10:3405/09/2022 10:3405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16469CHWP-4EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.41FALSERoger Fowler-Performed augury on pump. Also checked for damage, leaks, volts, amps, and proper operation.
0263-61394205/01/2022 07:0005/09/2022 10:0605/09/2022 10:0605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16470CHWP-5EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.46FALSERoger Fowler-Performed augury on pump. Also checked for signs of damage, for leaks, amps, volts, and proper operation.
0263-61394305/01/2022 07:0005/09/2022 09:4605/09/2022 09:4605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16471CHWP-1EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.46FALSERoger Fowler-Performed augury on pump. Also checked for leaks, signs of damage, volts, amps, and proper operation.
0263-61394405/01/2022 07:0005/09/2022 09:1605/09/2022 09:1605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned16472CHWP-VFD #6EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.42FALSERoger Fowler-Performed augury on pump. Also checked for leaks, signs of damage, volts, amps, and proper operation.
0263-61394805/01/2022 07:0005/11/2022 14:0405/11/2022 14:0405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P2048 - Energy Management Server MaintenanceP - zPlanned18268EMSEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompleted and ClosedEnergy Management Server Maintenance05/01/2022 07:00PM0.22FALSERoger Fowler-Checked for damage, cleanliness, and proper operation.
0263-61395205/01/2022 07:0005/13/2022 13:3005/19/2022 13:3005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4117 - Baylor Energy Complex Condensate Return TankP - zPlanned16427*Condensate Return SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompleted and ClosedBaylor Energy Complex Condensate Return Tank05/01/2022 07:00PM0.21FALSERoger Fowler-Inspected tank for leaks, signs of damage, and for anything unusual.
0263-61395305/01/2022 07:0005/17/2022 13:4305/17/2022 13:4305/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P1520 - Baylor Energy Complex D-A TankP - zPlanned16430D-A Tank SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex D-A Tank05/01/2022 07:00PM0.85FALSERoger Fowler-Performed augury on all feed water pumps, checked for leaks, damage, and proper operation.
0263-61402105/01/2022 07:0005/03/2022 08:1105/03/2022 08:1105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4102 - Baylor Energy Complex Air DryerP - zPlanned16523Air Dryer-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Air Dryer05/01/2022 07:00PM0.21FALSERoger Fowler-Air dryer is brand new
0263-61403405/01/2022 07:0005/17/2022 14:1205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned16524Chiller-3EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM1.00FALSEJohn Charette-performed augury on motor and compressor, submitted reading for diagnosis, waiting for results from augury

checked for leaks from condenser and evaporator chambers checked for leaks from valves and flanges on evaporator and condenser water piping checked oil level took temp reading on chiller verified proper operation of chiller checked for any signs of visible damage John Charette-received results from augury, updated on results page

0263-614351 05/01/2022 07:00 05/02/2022 09:56 05/29/2022 07:00 Baylor University Baylor Energy Complex-Zone 2-1070 B014 0263P1535 - Storage Tank Checklist 9500 - Safety/Security 00055 Used Oil Storage Tank Equipment Baylor Energy Complex-0263 Baylor Energy Complex-BEC Mike Landolt 1 Emergency-24h-Tier 1 PM Completed Storage Tank Checklist 05/29/2022 07:00 PM 0.25 FALSE John Charette-there is no used oil kept onsite, all used oil is taken to mechanic shop for proper recycling this shed is now used for tool and hose storage

0263-61436205/01/2022 07:0005/17/2022 13:4005/17/2022 13:4005/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4104 - Baylor Energy Complex Boiler MonthlyP - zPlanned16568Boiler-3EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Boiler05/01/2022 07:00PM0.28FALSERoger Fowler-Performed augury on boiler blower motor. Also checked for leaks, unusual noises, and proper operation
0263-61439205/01/2022 07:0005/02/2022 15:2205/02/2022 15:2205/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P1517 - BEC Diesel Storage Tank Checklist9500 - Safety/Security221829Storage TankEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBEC Diesel Storage Tank Checklist05/29/2022 07:00PM0.22FALSEabove ground dieselRoger Fowler-Inspected tank for leaks, cleanliness, and any other issues.
0263-61458705/01/2022 07:0005/17/2022 14:0905/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned271816Chiller-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.25FALSEJohn Charette-received results from augury, updated on results page
0263-61461705/01/2022 07:0005/09/2022 09:1405/09/2022 09:1405/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned272058CHWP-8EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury on pump. Also checked amps, volts, for leaks, for signs of damage, and proper operation.
0263-61461805/01/2022 07:0005/09/2022 08:4605/09/2022 08:4605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned272059CHWP-9EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury on pump. Also checked volts, amps, for leaks, for signs of damage, and proper operation.
0263-61461905/01/2022 07:0005/05/2022 14:0305/05/2022 14:0305/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned272065CWP-16EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.26FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation
0263-61462005/01/2022 07:0005/05/2022 14:0105/05/2022 14:0105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4121 - Baylor Energy Complex Chill Water PumpP - zPlanned272066CWP-17EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Chill Water Pump05/01/2022 07:00PM0.23FALSEJohn Charette-Performed augury, checked for leaks, damage, and proper operation.
0263-61462105/01/2022 07:0005/04/2022 12:1105/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned272076Chiller-8EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.75FALSEJohn Charette-performed augury on motor and compressor, submitted reading for diagnosis

checked for leaks from condenser and evaporator chambers checked for leaks from valves and flanges on evaporator and condenser water piping checked oil level took temp readings on motor and compressor verified proper operation of chiller verified all psi gauges are functional checked for any signs of visible damage

0263-61506505/01/2022 07:0005/05/2022 13:5905/05/2022 13:5905/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16476CWP-9EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.26FALSERoger Fowler-Performed augury, checked for damage, leaks, and proper operation.
0263-61506605/01/2022 07:0005/05/2022 13:5705/05/2022 13:5705/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4115 - Baylor Energy Complex Condenser Water PumpP - zPlanned16327CWP-10EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedBaylor Energy Complex Condenser Water Pump05/01/2022 07:00PM0.24FALSERoger Fowler-Performed augury, checked for damage, leaks, and proper operation.
0263-61506805/01/2022 07:0005/17/2022 13:4805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned18231Chiller-7EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.25FALSEJohn Charette-chiller is no longer in service, in process of being de-commissioned
0263-61506905/01/2022 07:0005/17/2022 13:4605/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4109 - Baylor Energy Complex Centrifugal ChillerP - zPlanned18229Chiller-5EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Centrifugal Chiller05/01/2022 07:00PM0.25FALSEJohn Charette-chiller is OOS at this time
0263-61507305/01/2022 07:0005/26/2022 13:0205/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned273509(SPX) Tower Fan-13EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompleted and ClosedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.75FALSEJohn Charette-performed augury on motor and fan gearbox, submitted reading for diagnosis, waiting for results from augury

while towers were being cleaned, motors and fan gearboxes was checked for any signs of damage checked oil level on gearbox-- no oil added checked for leaks from from cell tower checked for any signs of visible damage to motor and fan gearbox checked for leaks from valves and flanges removed LOTO and energized unit John Charette-received results from augury, updated on results page 0263-615074 05/01/2022 07:00 05/26/2022 13:04 05/01/2022 07:00 Baylor University Baylor Energy Complex-Zone 2-1070 B014 0263P4119 - Baylor Energy Complex Cooling Tower Unit P - zPlanned 273510 (SPX) Tower Fan-14 Equipment Baylor Energy Complex-0263 Baylor Energy Complex-BEC Mike Landolt 1 Emergency-24h-Tier 1 PM Completed and Closed Baylor Energy Complex Cooling Tower Unit 05/01/2022 07:00 PM 0.75 FALSE John Charette-performed augury on motor and fan gearbox, submitted reading for diagnosis, waiting on results from augury checked for leaks on exterior of cooling tower from valves and flanges after cleaning was done a visual inspection was done inside tower to check, motor and fan gearbox checked oil level-- no oil added checked for any signs of visible damage on the inside and outside of cooling tower removed LOTO and energized cooling tower fan John Charette-received results from augury, updated on results page

0263-61507505/01/2022 07:0005/09/2022 11:2805/09/2022 11:2805/01/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P4119 - Baylor Energy Complex Cooling Tower UnitP - zPlanned273508Ceramic Cooling Tower #5EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Cooling Tower Unit05/01/2022 07:00PM0.29FALSERoger Fowler-I performed the augury on the pump. I also checked for leaks, damage, volts, amps, and proper operation.
0263-61514605/01/2022 07:0006/06/2022 15:0005/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-Z20263P9035 - DAILY/HOURLY ROUTES OF OPERATIONS ,CHECKING EQUIPMENT FOR LEAKS PROPER OPERATION CHECKING GAUGES PSI, OIL LEVELS AND FOR ANY NOISES AND REPORT ANY ISSUES IN W.O. AS NEEDEDP - zPlannedBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedDAILY/HOURLY ROUTES OF OPERATIONS ,CHECKING EQUIPMENT FOR LEAKS PROPER OPERATION CHECKING GAUGES PSI, OIL LEVELS AND FOR ANY NOISES AND REPORT ANY ISSUES IN W.O. AS NEEDED05/29/2022 07:00Inspection331.18FALSE
0263-61514705/01/2022 07:0005/03/2022 07:5705/03/2022 07:5705/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9036 - Check Polisher for proper operation and for any issues.P - zPlanned16557*Condensate Polisher SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedCheck Polisher for proper operation and for any issues.05/29/2022 07:00Inspection0.21FALSERoger Fowler-No leaks. Polisher is out of service
0263-61514805/01/2022 07:0005/03/2022 07:5805/03/2022 07:5805/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9037 - Check Softener for proper operation and for any issues.P - zPlanned16437(Water treatment) Softener SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedCheck Softener for proper operation and for any issues.05/29/2022 07:00Inspection0.24FALSERoger Fowler-Inspected water softener for leaks, cleanliness, and proper operation
0263-61514905/01/2022 07:0005/03/2022 08:0005/03/2022 08:0005/29/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070BEC-1070-BoilRMB0020263P9038 - Check Dealkalizer for proper operation and for any issues.P - zPlanned16436(Water Treatment) - DE alkalizer systemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedCheck Dealkalizer for proper operation and for any issues.05/29/2022 07:00Inspection0.23FALSERoger Fowler-Inspected dealkalizer for leaks, cleanliness, and proper operation.
0263-61515305/01/2022 07:0005/02/2022 13:1405/02/2022 13:14Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9040 - Blow out all open starter Motors(chill water pump motors) with air. Clean all dust build up on windings.P - zPlannedBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedBlow out all open starter Motors(chill water pump motors) with air. Clean all dust build up on windings.05/11/2022 07:00Inspection0.79FALSERoger Fowler-Checked motor starters for cleanliness and any other issues
0263-61526005/02/2022 07:0005/07/2022 02:0905/07/2022 02:0905/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP03-1070 - Chemical Building Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChemical Building Area Routine Cleaning05/09/2022 07:00Inspection0.88FALSEKnocked down cobwebs in chemical pumping room

Sweep all rooms in chemical building

0263-61526105/02/2022 07:0005/07/2022 22:5505/07/2022 22:5505/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP04-1070 - Electrical Panels Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompleted and ClosedElectrical Panels Area Routine Cleaning05/09/2022 07:00Inspection0.93FALSESweep floors and take up garbage from area.
0263-61526205/02/2022 07:0005/08/2022 12:5405/08/2022 12:5405/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP07-1070 - Chiller-1 and North Tunnel Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-1 and North Tunnel Area Routine Cleaning05/09/2022 07:00Inspection0.81FALSE
0263-61526305/02/2022 07:0005/07/2022 03:0005/07/2022 07:5905/07/2022 03:59Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP08-1070 - Chiller-3 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-3 Area Routine Cleaning05/09/2022 07:00Inspection1.00FALSE
0263-61526405/02/2022 07:0005/05/2022 01:0805/05/2022 01:0805/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP09-1070 - Chiller-5 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompleted and ClosedChiller-5 Area Routine Cleaning05/09/2022 07:00Inspection0.55FALSEDust and swept floor and remove insect and webs.
0263-61526505/02/2022 07:0005/09/2022 08:5405/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP10-1070 - Chiller-4 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-4 Area Routine Cleaning05/09/2022 07:00Inspection0.15FALSERoger Fowler-cleaned ans swept
0263-61526605/02/2022 07:0005/08/2022 11:4005/08/2022 11:4005/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP11-1070 - Chiller-6 and Chiller-7 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-6 and Chiller-7 Area Routine Cleaning05/09/2022 07:00Inspection0.34FALSECleaned up around chillers dusted
0263-61526705/02/2022 07:0005/11/2022 15:5605/11/2022 15:5605/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP12-1070 - Boiler-1 and Boiler-2 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompleted and ClosedBoiler-1 and Boiler-2 Area Routine Cleaning05/09/2022 07:00Inspection2.16FALSEBeware of the skunk around the boilers.
0263-61526805/02/2022 07:0005/06/2022 16:0405/06/2022 16:0405/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP13-1070 - Boiler-3 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedBoiler-3 Area Routine Cleaning05/09/2022 07:00Inspection0.56FALSESwept boiler 3 bay and rearranged cleaning area.
0263-61526905/02/2022 07:0005/08/2022 09:0705/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP15-1070 - Second Level Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedSecond Level Area Routine Cleaning05/09/2022 07:00Inspection0.88FALSE
0263-61528305/02/2022 07:0005/06/2022 13:4905/06/2022 13:4905/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP33-1070 - Chiller-8 & 9 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-8 & 9 Area Routine Cleaning05/09/2022 07:00Inspection0.85FALSERoger Fowler-Cleaned and swept around chiller 8. Emptied all trash cans
0263-61528505/02/2022 07:0005/08/2022 00:3905/08/2022 00:3905/09/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP99-1070 - Chiller-2 Area Routine CleaningI - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedChiller-2 Area Routine Cleaning05/09/2022 07:00Inspection1.72FALSESweep up dirt and removed garbage.
0263-61528605/02/2022 07:0005/08/2022 10:5805/08/2022 10:58Baylor UniversityBaylor Energy Complex-Zone 2-1070B0140263P8506 - Baylor Energy Complex Eye Wash Checklist9500 - Safety/SecurityBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedBaylor Energy Complex Eye Wash Checklist05/03/2022 07:00PM0.34FALSECheck eyewash stations ok
0263-61528805/02/2022 07:0005/08/2022 03:0005/08/2022 03:1505/08/2022 03:15Baylor UniversityBaylor Energy Complex-Zone 2-1070B014INSP81-1070 - Cleaning our Red Shed ( storage and parts area ) needs to be swept out and straighten up weekly with any Trash taken out.I - zInspectionBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt3 Recurring Services-28d-Tier 3 PMCompletedCleaning our Red Shed ( storage and parts area ) needs to be swept out and straighten up weekly with any Trash taken out.05/08/2022 07:00Inspection0.15FALSE
0263-61529705/02/2022 07:0005/08/2022 14:4005/08/2022 14:4005/08/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9033 - DA-Tank Level Sight Glass/Gauge Blow DownP - zPlanned16430D-A Tank SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt1 Emergency-24h-Tier 1 PMCompletedDA-Tank Level Sight Glass/Gauge Blow Down05/08/2022 07:00PM0.25FALSEBlowdown was successful
0263-61529805/02/2022 07:0005/08/2022 15:0105/08/2022 15:0105/08/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9032 - Condensate Tank
(North Tunnel) Level Sight Glass/Gauge Blow DownP - zPlanned16427*Condensate Return SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedCondensate Tank
(North Tunnel) Level Sight Glass/Gauge Blow Down05/08/2022 07:00PM0.34FALSEBlowdown was successful
0263-61529905/02/2022 07:0007/07/2022 14:1605/08/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070B0180263P9034 - Inspect tools, organize, clean and inventory ToolroomP - zPlannedBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedInspect tools, organize, clean and inventory Toolroom05/08/2022 07:00Inspection0.36FALSETools and equipment in good condition
0263-61530005/02/2022 07:0005/07/2022 05:1705/07/2022 05:17Baylor UniversityBaylor Energy Complex-Zone 2-1070B0180263P9883 - Test water at the BEC. Chemical Testing on Boilers and City water and report any issues.P - zPlannedBEC-1070Baylor Energy Complex-Zone 2-1070BuildingBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedTest water at the BEC. Chemical Testing on Boilers and City water and report any issues.05/12/2022 07:00Inspection15.99FALSECollected and tested all plant water

Blowdown all operating boilers Calibrated boiler e controller Manually fed Trasar into ceramic tower Entered data into the computer Collected and tested all plant water Calibrated boiler e controller Assisted Nalco in ceramic e controller repair Entered data into the computer Collected and tested all plant water Calibrated boiler e controller controller Entered data into the computer Collected and tested all plant water Blowdown all operating boilers Calibrated boiler e controller Entered data into the computer Collected and tested all plant water Calibrated boiler e controller Calibrated blue pen conductivity meter Entered data into the computer

0263-61530105/02/2022 07:0005/06/2022 13:5205/06/2022 13:5205/30/2022 07:00Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC0263P9039 - Clean out " Y " Strainers and flush out lines, A and B side.P - zPlanned16427*Condensate Return SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt2 Urgent-48h-Tier 2 PMCompletedClean out " Y " Strainers and flush out lines, A and B side.05/30/2022 07:00PM0.74FALSERoger Fowler-Isolated strainers, removed strainers, cleaned strainers, reinserted strainers, opened the valves, and checked for leaks.
0263-61534005/02/2022 08:0510/12/2022 08:47Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC6004-1070 - Misc BEC Jobs6000 - Mechanical16492Boiler FWP-2EquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedpump seal is leaking and needs to be replaced05/12/2022 08:05Corrective1.83FALSEtook pump OOS, turned power to pump off on control box and locked out

cut valves off to and from pump and isolated each, locked out all necessary valves John Charette-getting quote from brandt to replace expansion joint and replace pump seal and stack kit John Charette-contractor came and replaced pump stack kit and pump seal, contractor pointed out at completion of rebuild, that wiring to motor from DA control panel are burnt and needs to be replaced before wiring motor back up, contractor not able to check for proper rotation or seal leak until repair to wires are made waiting on expansion joint to be replaced as well John Charette-reopening work order, having contractor come back out for start up of pump to make adjustments if needed checked pump shaft and seal, found that during installation of new stack kit and shaft seal, contractor apparently didn't torque down shaft collar bolts to specs. collar screws were only socket tight. removed all 4 collar screws and lifted stack shaft up and put spacer back in place., put shaft collar back in place and started tightening screws to keep collar in place. tightened all shaft screws and torqued to specs of 63ftlb., turned electricity back on to pump and removed shaft spacer. started motor and pump shaft collar stayed in place and shaft stayed spaced as called for in specs.

LOTO has been removed and pump is now back in service and can be ran when needed John Charette-pump was torn down and rebuilt by contractor, after pump was rebuilt new wiring was pulled from control cabinet to motor and was put back in service

0263-615431 05/02/2022 11:51 05/04/2022 13:36 05/04/2022 13:36 Baylor University Baylor Research and Innovation Collaborative-Zone 2-1070 263SER-Z2 4000 - General HVAC Repair 4000 - HVAC BRIC-1070 Baylor Research and Innovation Collaborative-Zone 2-1070 Building Baylor Energy Complex-0263 Baylor Energy Complex-BEC Michael Heroux 4 Routine-10d Completed and Closed KIPSU

BRIC CHWP-1 needs a post repair Augury vibration test and analysis performed. Please assign to John Charrette, thanks 05/12/2022 11:51 Corrective 0.85 FALSE Drove from BEC to the BRIC Made contact with Aaron Performed augury on chilled pump #1, submitted readings for diagnosis.

Waiting on results from augury and will pass results to Don Fearing as well as Aaron Pierce Drove back to the BEC form BRIC

0263-61557905/03/2022 11:5410/12/2022 09:52Baylor UniversityBaylor Energy Complex-Zone 2-1070263SER-BEC6004-1070 - Misc BEC Jobs6000 - Mechanical16430D-A Tank SystemEquipmentBaylor Energy Complex-0263Baylor Energy Complex-BECMike Landolt4 Routine-10dCompletedEmergency Steam Outage on 5/1/22 .. Feed-water line had a pipe rupture, had call out extra personal and Vendor to Help mitigate the issue and repairs.05/13/2022 11:54Corrective0.15FALSEJoel Amick-work has been completed and PO issued