ESBD_510890_1777408097042_G.6 Scope of Work.pdf
PDF 4 MB Posted
- Attached to
- Camp Bowie Classroom HVAC
- Solicitation number
- TMD26-CFMO-0044411
- Issued by
- Burleson County, Texas
About this file
This Scope of Work document pertains to HVAC supplemental cooling system installation at Camp Bowie Readiness Center in Brownwood, Texas, managed by the Texas Military Department Construction & Facilities Management Office. The project involves furnishing and installing a supplemental variable refrigerant flow (VRF) HVAC system to address insufficient cooling in first- and second-floor classrooms. The system includes a Daikin RXYA120AATJA outdoor condenser unit (or approved equal) with ceiling-mounted indoor fan coil units, refrigerant piping, condensate drain piping, controls, and all required accessories. Electrical work includes installation of a 60-ampere, 3-pole disconnect in a NEMA 3R enclosure, a 45-ampere, 3-pole breaker in Panel LP1, relocation of existing breakers, new conduit and conductors, and panel directory updates. The contractor must provide system startup, testing, and commissioning to verify classroom temperatures maintain 75 degrees Fahrenheit or below under occupied conditions during peak summer design conditions, with all work performed in accordance with Garver recommendations and applicable codes.
The scope of work encompasses comprehensive specifications for mechanical, electrical, and control system components in accordance with Division 23 (HVAC Systems) and Division 26 (Electrical Systems) standards. The work requires installation of six indoor fan coil units (five FXFA18AAVJU cassettes and one FXFA24AAVJU cassette), refrigerant isolation valves, specialized branch piping kits, six navigation remote controllers, and six decorative panels. Equipment pads, wall and ceiling penetrations, firestopping, and finish repairs are included. Contractor qualifications require ISO 9001 and ISO 14001 certification, with installer personnel needing manufacturer certification valid for the project duration. The manufacturer provides a five-year warranty on compressors and parts from Substantial Completion. Field quality control includes refrigerant tubing pressure testing at 1.2 times operating pressure (minimum 600 psig) for 24 hours, evacuation testing to 500 microns for one hour, system refrigerant charge verification witnessed by manufacturer representative, and startup service documentation including at least two hours of continuous operation recording with all available system parameters.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Provide all labor, materials, equipment, and supervision necessary to furnish and install a supplemental HVAC system at the Camp Bowie Readiness Center to address insufficient cooling in the first- and second-floor classrooms.
The work shall include installation of a system consistent with the basis of design (Daikin RXYA120AATJA or approved equal), including ceiling-mounted indoor fan coil units, refrigerant piping, condensate drain piping, controls, and all required accessories for a complete and operational system.
Provide all electrical work required to support the new system, including installation of a 60A, 3-pole disconnect in a NEMA 3R enclosure, a 45A, 3-pole breaker in Panel LP1, relocation of existing breakers as required, installation of new conduit and conductors, and updating the panel directory.
Provide equipment pads, wall and ceiling penetrations, and required firestopping. Patch and repair all disturbed finishes to match existing conditions.
All work shall be performed in accordance with the attached Garver recommendations with provided selections from Daikin VRV Selection Project Report, drawings (including Sheets E-801, E-104, and E-501), and specifications (including specifications from Division 23 and Division 26), and shall comply with applicable codes and manufacturer requirements.
The contractor shall provide system startup, testing, and commissioning, including verification that the system maintains classroom temperatures at or below 75°F under occupied conditions during peak summer design conditions consistent with local criteria.
Attachment G.6 - Scope of Work Page 1 of 97
Camp Bowie RC Classroom HVAC Scope of Work
Camp Bowie RC MM 14 August 2025
ISSUE:
Garver was informed by Mr. Gary Bonner that cooling in first and second floor Classrooms was insu%icient to maintain temperatures below 78 degrees when fully occupied.
RESEARCH/FINDINGS:
Garver investigated the issue and found that the HVAC load for this area was insu%icient for a fully occupied classroom as noted by Mr. Gary Bonner.
RECOMMENDATIONS:
It is recommended that additional cooling be added to supplement the additional personnel that will be in the space.
Mechanical: It is estimated the spaces need a 114 MBH unit to provide additional cooling.
The proposed unit is a Daikin RXYA120AATJA (see attached VRV Selection Project Report
Product/Data Cut Sheets). This will utilize ceiling-mounted fan coil units and an independent outdoor condenser. Refer to attached sheets E-801 & E-104.
Electrical: Provide power to new unit. Install 60A/3-pole disconnect in NEMA 3R enclosure on exterior wall beside unit. Ensure there is a minimum 36” of clearance in front of disconnect and 30” of horizontal clearance. Refer to sheet E-501 for clearance details.
Indoor unit shall be powered through outdoor unit. Provide 45A/3-pole breaker and install in
Panel LP1-49,51,53. Relocate existing 20A/1-pole breakers to Panel ‘T1’. New conductor and conduit size: 1"C-3#6, 1#10(G). Print a new typed panel directory for Panel ‘LP1’.
Site: Locate new 10-ton condenser and pad adjacent to the sidewalk outside Door 107A.
Refer to sheet E-801.
ATTACHMENTS:
VRV Product Selection Report (Product Data Cut Sheets)
Drawings:
• E-801 – First Floor Electrical (with markups & details)
• E-104 – Second Floor Electrical (with markups)
• E-501 – Electrical Details
Specifications:
• 23 81 29 – Variable Refrigerant Flow HVAC Systems
• 26 28 16 - Enclosed Switches and Circuit Breakers
• 26 05 19 - Low-Voltage Electrical Power Conductors and Cables
• 26 05 26 - Grounding and Bonding for Electrical Systems
• 26 05 29 - Hangers and Supports for Electrical Systems
• 26 05 33 - Raceways and Boxes for Electrical Systems
• 26 24 16 – Panelboards
### END OF REPORT; SEE ATTACHED DOCUMENTATION ###
Attachment G.6 - Scope of Work Page 2 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 1
VRV Selection Project Report
Report details
Produced on: 6/30/2025
Application version: 2025.6.25.1
Project details
Project name: Camp Bowie
Solution name: r32
Client Name:
Customer reference:
Quotation reference: Camp Bowie VRV
Project number: 713062/911528
Selection parameters of the indoor units can be found in the Engineering Data Books Selection parameters of the outdoor units can be found in the Engineering Data Books Only the data published in the data book are correct. This program uses close approximations of these data.
Attachment G.6 - Scope of Work Page 3 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 2
Material list
Model Quantity Description RXYA120AATJA 1 VRV EMERION (208-230V 3ph)
FXFA18AAVJU 5 FXFA_AA - Round Flow Sensing Cassette
FXFA24AAVJU 1 FXFA_AA - Round Flow Sensing Cassette
KHRP26A22TA 2 Refnet branch piping kit
KHRP26A33TA 2 Refnet branch piping kit
KHRP26M72TUA 1 Refnet branch piping kit
BRC1NRV71 6 Navigation Remote Controller
BYCQ54GEFU 6 Standard Decorative Panel
Remarks
Note: Upon depletion of inventory of current REFNET models, order of current REFNET models will be substituted with the new upgraded -A models with no additional fee.
Attachment G.6 - Scope of Work Page 4 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 3
Indoor unit details
Table of abbreviations
Abbreviation Description Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Max SC Available sensible cooling capacity
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Sound Sound pressure level low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
WxHxD WidthxHeightxDepth
Weight Weight of the device
Mrel Maximum Refrigerant Amount that can be released. Equals the total refrigerant charge in the system when there are no shut-off valves.
Attachment G.6 - Scope of Work Page 5 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 4
HRU- 1 - RXYA120AATJA
Capacity data at conditions and connection ratio (94) as entered
Name FCU Cooling Tmp C Rq TC Max TC Rq SC Tevap Max SC
°F
(DBT/WBT)
BTU/h BTU/h BTU/h °F BTU/h
FC- 1 FXFA24AAVJU 78.8/65.5 n/a 22,957 n/a 42.8 16,270
FC- 2 FXFA18AAVJU 78.8/65.5 n/a 17,165 n/a 42.8 13,208
FC- 3 FXFA18AAVJU 78.8/65.5 n/a 17,165 n/a 42.8 13,208
FC- 4 FXFA18AAVJU 78.8/65.5 n/a 17,165 n/a 42.8 13,208
FC- 5 FXFA18AAVJU 78.8/65.5 n/a 17,165 n/a 42.8 13,208
FC- 6 FXFA18AAVJU 78.8/65.5 n/a 17,165 n/a 42.8 13,208
Name FCU Heating Tmp H Rq HC
Max HC
Min coil Max coil
°F BTU/h BTU/h in³ in³ FC- 1 FXFA24AAVJU 68.0 n/a 27,932 n/a n/a
FC- 2 FXFA18AAVJU 68.0 n/a 20,840 n/a n/a
FC- 3 FXFA18AAVJU 68.0 n/a 20,840 n/a n/a
FC- 4 FXFA18AAVJU 68.0 n/a 20,840 n/a n/a
FC- 5 FXFA18AAVJU 68.0 n/a 20,840 n/a n/a
FC- 6 FXFA18AAVJU 68.0 n/a 20,840 n/a n/a
Name FCU Room Sound PS MCA MOP WxHxD Weight dBA A inch lbs
FC- 1 FXFA24AAVJU 28 - 36 208-230V 1ph 0.5 15 A 33.1 x 9.7 x 33.1 51.0
FC- 2 FXFA18AAVJU 28 - 36 208-230V 1ph 0.4 15 A 33.1 x 9.7 x 33.1 42.0
FC- 3 FXFA18AAVJU 28 - 36 208-230V 1ph 0.4 15 A 33.1 x 9.7 x 33.1 42.0
FC- 4 FXFA18AAVJU 28 - 36 208-230V 1ph 0.4 15 A 33.1 x 9.7 x 33.1 42.0
FC- 5 FXFA18AAVJU 28 - 36 208-230V 1ph 0.4 15 A 33.1 x 9.7 x 33.1 42.0
FC- 6 FXFA18AAVJU 28 - 36 208-230V 1ph 0.4 15 A 33.1 x 9.7 x 33.1 42.0
Remarks
Reduced operational load
The sum of the required indoor unit capacities is 108,781BTU/h for cooling and 132,133BTU/h for heating. However, the outdoor unit selection uses reduced load values for cooling of 108,781BTU/h (=100%) and for heating of 111,000BTU/h
(=84%). Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear and tear.
Outdoor vs. indoor position
Outdoor unit placed at the same level as the indoor units.
Required room measures
Note that this design is incomplete due to missing pipe lengths.
Attachment G.6 - Scope of Work Page 6 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 5
Outdoor unit details
Table of abbreviations
Abbreviation Description Name Logical name of the device
Model Device model name
CR Connection ratio
Tmp C Outdoor conditions in cooling
WFR per module Water flow per outdoor unit module
CC Available cooling capacity
Rq CC Required cooling capacity
PIC Power input in cooling mode
InC Water inlet temperature in cooling mode
OutC Water outlet temperature in cooling mode
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
PIH Power input in heating mode
InH Water inlet temperature in heating mode
OutH Water outlet temperature in heating mode
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (16.4ft actual piping length) excluding extra refrigerant charge. For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
FLA Fan Motor Input
FCIDI Fan Compressor Inverter Drive Input
RLA Nominal Running Amps
WxHxD WidthxHeightxDepth
Weight Weight of the device
EER EER value at nominal condition
EER2 EER2 value at nominal condition
IEER IEER value at nominal condition
COP47 COP value at nominal condition and at ambient temperature of 47°F
COP17 COP value at nominal condition and at ambient temperature of 17°F
Attachment G.6 - Scope of Work Page 7 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 6
Outdoor details
Name Model CR Cooling Heating Piping Tmp C CC Rq CC Tmp H HC Rq HC
% °F BTU/h BTU/h °F
(DBT/WBT)
BTU/h BTU/h ft
HRU- 1 RXYA120AATJA 94.2 84.2 112,510 108,781 32.0/30.7 111,229 24.6
Name Model PS MCA MOP WxHxD Weight A A inch lbs
HRU- 1 RXYA120AATJA 208V - 230V
3ph
39.9 45.0 48.8 x 65.4 x 30.1 725.3
Attachment G.6 - Scope of Work Page 8 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 7
Sound Data
Name Model Sound Power Sound Pressure
Cooling Heating Cooling Heating dBA dBA dBA dBA
HRU- 1 RXYA120AATJA - - 61 -
Refrigerant information
Name Model Refrigerant type GWP
Base charge lbs
Extra charge lbs
Total refrigerant charge lbs
Total CO2 equivalent tonnes
HRU- 1 RXYA120AATJA R32 675 25.35 unknown unknown 7.76
The system(s) contain fluorinated greenhouse gases.
When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2 equivalent.
For some outdoor units, piping lengths were not entered manually causing the determination of refrigerant amounts to be inaccurate.
HRU- 1 - RXYA120AATJA
Model Quantity Description RXYA120AATJA 1 VRV EMERION (208-230V 3ph)
FXFA18AAVJU 5 FXFA_AA - Round Flow Sensing Cassette
FXFA24AAVJU 1 FXFA_AA - Round Flow Sensing Cassette
KHRP26A22TA 2 Refnet branch piping kit
KHRP26A33TA 2 Refnet branch piping kit
KHRP26M72TUA 1 Refnet branch piping kit
BRC1NRV71 6 Navigation Remote Controller
BYCQ54GEFU 6 Standard Decorative Panel
Refrigerant information
Refrigerant type GWP Base charge lbs
Extra charge lbs
Total refrigerant charge lbs
Total CO2 equivalent tonnes R32 675 25.35 unknown unknown 7.76
The system(s) contain fluorinated greenhouse gases.
Attachment G.6 - Scope of Work Page 9 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 8
When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2 equivalent.
Piping lengths were not entered manually causing the determination of refrigerant amounts to be inaccurate.
Pipe capacities
Maximum Connection Index Diameters
71.9 3/8"x3/4"
95.9 3/8"x7/8"
119.9 1/2"x7/8"
251.9 1/2"x1 1/8"
259.9 5/8"x1 1/8"
379.9 5/8"x1 3/8"
> 379.9 3/4"x1 5/8"
Main pipe size up 5/8"x1 1/4"
Piping limitations
Description Value Maximum total length 3,280.8ft
Maximum longest actual length 541.3ft
Maximum longest equivalent length 623.4ft
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 131.2ft
Maximum length first branch to indoor unit 295.3ft
Maximum length of indoor units to nearest branch 131.2ft
Maximum length difference between longest and shortest distance to indoor units 131.2ft
Maximum height difference, outdoor unit below indoor units 295.3ft
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 295.3ft
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 295.3ft
Maximum height difference in technical cooling, outdoor unit above indoor units 295.3ft
Maximum height difference between indoor units 131.2ft
Connection ratio range 50.0% - 200.0%
Refrigerant pipe diameters 5/8" (liquid) x 1 1/4" (gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 295.3ft
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Attachment G.6 - Scope of Work Page 10 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 9
Attachment G.6 - Scope of Work Page 11 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 10
Piping diagrams
Piping HRU- 1
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required.
Attachment G.6 - Scope of Work Page 12 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 11
Attachment G.6 - Scope of Work Page 13 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 12
Wiring diagrams
Wiring HRU- 1
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT = AWG 18-2 is required - however always refer to local code for further information
Note:
Attachment G.6 - Scope of Work Page 14 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 13
Attachment G.6 - Scope of Work Page 15 of 97
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 14
Attachment G.6 - Scope of Work Page 16 of 97
UP
UP
J
J
J
OC
OC
OC
DL
OC
OC
OC OC
OC OC
CLASSROOM
CONFERENCE
CORRIDOR
107B
OFFICE
OFFICE
OFFICE
STORAGE
OFFICE
OFFICE
RH-3
RH-2
RH-1 RH-6
RH-5
RH-4
HVLS-1
HVLS-2
LP3-18LP3-20
LP3-21 LP3-17 LP3-19
BID OPTION #1
BID OPTION #5
BID OPTION #6
BID OPTION #7
TV
WP
TV
GFIGFI
TV
WP
GFIGFIGFI
GFI
GFI
GFI
GFI
GFIGFIGFIWP
WP
WP
WP
AC/GFI
AC/GFI
AC/GFI
AC/GFI
AC/GFI
AC/GFI
GFI
GFI
GFI GFI
WP
WP
TV
TV
WP
WP
EWC
TV
LP1-11
LP1-10
TV TV
LP1-19
LP1-20
LP1-36
M-21 M-22
M-23,25
M-24,26
CONNECT EXISTING
OVERHEAD DOOR TO
NEW PANEL 'LP1'.
SEE SHEET E-103
FOR CIRCUIT.
LV
A3 A3 A3
A1
A1
A1
A1
A1
A1
LV LV LV
LVLV
D
A1
A1A1
A1
(5
-6
W
T
H S
T R
E E
T F
A X
-1
A U
S T
IN
T E
X A
S
T E
X A
S M
IL
IT
A R
Y D
E P
A R
T M
E N
T C
O N
S T
R U
C T
IO
N
F
A C
IL
IT
IE
S
M A
N A
G E
M E
N T
O F
F
IC
E -C
F M
O
REVIEWED BY:
DRAWN BY:
PROJECT NO.
ISSUE DATE:
PROJECT ARCHITECT:
TXARNG CFMO
DESIGNED BY:
This Record Drawing is a combination of the sealed architectural/engineering contract drawings for this project, modified by information furnished by the contractor reflecting changes in the Project made during construction.
The original sealed drawings are on file at the offices of
GARVER, LLC
RECORD DRAWINGS PREPARED
ON: 02/28/2025
THE SEAL THAT ORIGINALLY APPEARED
ON THIS DOCUMENT WAS AUTHORIZED
BY:
TEXAS NO: __________________ ON:
09/30/2022_________
ALTERATION OF A SEALED DOCUMENT
WITHOUT PROPER NOTIFICATION OF
THE RESPONSIBLE ENGINEER IS AN
OFFENSE UNDER THE TEXAS
ENGINEERING PRACTICE ACT.
E-801
FIRST FLOOR
ELECTRICAL
C A
M P
B O
W
IE
S. FEEZOR
G. FREY
J. JOYCE
02/28/2025 (RD)
R E
D
IN
E S
S C
E N
T E
R M
A J O
R M
A
IN
T E
N A
N C
E
48170030
3/32" = 1'-0"
ELECTRICAL FIRST FLOOR
BID OPTION NOTES
BID OPTION 1
THIS WORK ITEM INVOLVES THE EXPANSION OF
CONFERENCE ROOM 108 AND THE ENCLOSING OF
THE CLASSROOM AREA IN ADMINISTRATION 107 TO
HOUSE 40 PERSONS UTILIZING THE EXISTING
DESKS.
BID OPTION 5
THIS WORK INCLUDES THE INSTALLATION OF A
CANOPY AT THE MAIN ENTRANCE. A FLAT (LOW
SLOPE) CANOPY WOULD BE INSTALLED AT THE
SECOND-FLOOR LEVEL AT THE ENTRANCE, EXTEND
THE WIDTH OF THE STOREFRONT AND
APPROXIMATELY 10 FEET FROM THE BUILDING
FACE. THE CANOPY ROOF WOULD BE
TRANSLUCENT PANELS AND BE SET ON STEEL
COLUMNS AND CONCRETE FOUNDATIONS.
BID OPTION 6
THE WORK INCLUDES THE INSTALLATION OF TWO
HVLS CEILING FANS, THE REPLACEMENT OF THE
OVERHEAD SECTIONAL DOOR WITH A COILING
DOOR, AND THE REPLACEMENT OF EXISTING
HEATING SYSTEMS FOR THE ASSEMBLY HALL.
BID OPTION 7
THE WORK INVOLVES THE CONVERSION OF
WOMEN'S LOCKER ROOM 137 INTO FIVE NEW
OFFICES AND A SMALL STORAGE ROOM. THE NEW
OFFICE CORRIDOR WILL CONNECT TO THE NORTH
WITH CORRIDOR 132 TO THE ASSEMBLY HALL AND
TO THE WEST WITH CORRIDOR 138 AND THE
ADMINISTRATION AREA.
BAR SCALE
SCALE: 3/32" = 1'-0"
4' 8' 20' 32'
NORTH
SAM FEEZOR
113619
Mechanical: It is estimated the spaces need a 114 MBH unit to provide additional cooling.
The proposed unit is a Daikin RXYA120AATJA (see attached cut-sheet). This will utilize ceiling-mounted fan coil units and an independent outdoor condenser.
Electrical: Provide power to new unit. Install 60A/3-pole disconnect in NEMA 3R enclosure on exterior wall beside unit. Ensure there is a minimum 36” of clearance in front of disconnect and 30” of horizontal clearance. Refer to sheet E-501 (attached for reference) for clearance details. Indoor unit shall be powered through outdoor unit. Provide 45A/3-pole breaker and install in Panel LP1-49,51,53. Relocate existing 20A/1-pole breakers to Panel ‘T1’. New conductor and conduit size: 1"C-3#6, 1#10(G). Print a new typed panel directory for Panel ‘LP1’.
SCOPE
WP
GRADE
COMPACTED SUBGRADE
8"
12"
TWO #4 REBAR - 5" FROM EDGE OF PAD
6" THICKNESS
6/6 WWF (TYPICAL) 2" FROM EDGE
NOT TO SCALE:
HVAC EQUIPMENT PAD DETAIL
10 ton outdoor condenser and pad
Indoor ceiling-mount fan coil unit
LP1-49,51,53
FIGURE 1
SECURE TO ROOF JOIST. SEE DETAIL
SHEET M- (TYP)
VIBRATION ISOLATOR. SEE SCHEDULE
AND DETAILS SHEET M- (TYP)
3/8"∅ THREADED
ROD (TYP)
HANGING BRACKETS (TYP)
INDOOR UNIT
SA
24V LEAD TO ROOM. T'STAT
PROVIDED BY UNIT MFGR.
4 WAY SUPPLY
AIR DISCHARGE. CENTER
RA GRILLE
CONTROL
CONNECTIONS
WEATHERPROOF FUSED
DISCONNECT. MOUNT
ADJACENT TO UNIT.
SECURE UNIT TO SLAB
SA
DUCTLESS MINI SPLIT CEILING CASSETTE INSTALLATION
NOT TO SCALE
Attachment G.6 - Scope of Work Page 17 of 97
DN DN
MEETING /
CLASSROOM
MEETING /
CLASSROOM
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
TELECOM
206DFC-4-1
DFC-4-2
DFC-4-3 DFC-4-4
DFC-5-1
DFC-6-1
DFC-6-2DFC-6-3
PANEL 'T2'
STORAGE
LP3-16
LP3-15
LP3-11
LP3-12
LP3-10LP3-9
LP3-8
TV TVTVTVTV
LP3-1
LP3-2
LP3-13
LP3-6
LP3-4
LP3-5
LP3-3
E-104
1 1 1 1
PANEL 'T2'
DFC-5-1
T2-3
T2-5
T2-1
T2-6,8
T2-2,4
L6-30R
REFER TO DETAIL
1 ON SHEET T-501
DFC-9-1
T1-7
T1-5
PANEL 'T1' T1-3T1-1
T1-2,4 T1-6,8
T1-14,16 T1-10,12
L6-30R
REFER TO DETAIL
1 ON SHEET T-501
(TYP.)
(5
-6
W
T
H S
T R
E E
T F
A X
-1
A U
S T
IN
T E
X A
S
T E
X A
S M
IL
IT
A R
Y D
E P
A R
T M
E N
T C
O N
S T
R U
C T
IO
N
F
A C
IL
IT
IE
S
M A
N A
G E
M E
N T
O F
F
IC
E -C
F M
O
REVIEWED BY:
DRAWN BY:
PROJECT NO.
ISSUE DATE:
PROJECT ARCHITECT:
TXARNG CFMO
DESIGNED BY:
This Record Drawing is a combination of the sealed architectural/engineering contract drawings for this project, modified by information furnished by the contractor reflecting changes in the Project made during construction.
The original sealed drawings are on file at the offices of
GARVER, LLC
RECORD DRAWINGS PREPARED
ON: 02/28/2025
THE SEAL THAT ORIGINALLY APPEARED
ON THIS DOCUMENT WAS AUTHORIZED
BY:
TEXAS NO: __________________ ON:
09/30/2022_________
ALTERATION OF A SEALED DOCUMENT
WITHOUT PROPER NOTIFICATION OF
THE RESPONSIBLE ENGINEER IS AN
OFFENSE UNDER THE TEXAS
ENGINEERING PRACTICE ACT.
E-104
SECOND FLOOR
ELECTRICAL
C A
M P
B O
W
IE
S. FEEZOR
G. FREY
J. JOYCE
02/28/2025 (RD)
R E
D
IN
E S
S C
E N
T E
R M
A J O
R M
A
IN
T E
N A
N C
E
48170030
1/8" = 1'-0"
SECOND FLOOR POWER PLAN
BAR SCALE
SCALE: 1/8" = 1'-0"
4' 8' 16' 24'
GENERAL NOTES
1. PROVIDE NEW ELECTRICAL PANELS, STEP-
DOWN TRANSFORMERS, AND OTHER
INFRASTRUCTURE REQUIRED FOR A COMPLETE
NEW ELECTRICAL DISTRIBUTION SYSTEM.
REFER TO SHEET E-601 ONE-LINE DIAGRAM FOR
MORE INFORMATION.
2. PROVIDE NEW FEEDERS AND DISCONNECT
SWITCHES FOR NEW MECHANICAL EQUIPMENT.
3. EXISTING CONDUIT MAY BE CLEANED AND
REUSED WHERE IN GOOD CONDITION AND
SUITABLY LOCATED FOR NEW INSTALLATION
WORK PERIOD IF CONDUIT IS NOT SUITABLE FOR
REUSE, CONTRACTOR SHALL REMOVE AND
REPLACE WITH NEW.
4. PROVIDE NEW LIGHTNING PROTECTION SYSTEM
ON STRUCTURE, MEETING NFPA 70, 780, AND 96.
SYSTEM SHALL BE CONSTRUCTED TO MAINTAIN
ROOF WARRANTY AND CERTIFIED WITH UL
MASTER LABEL.
5. PROVIDE RIGID GALVANIZED STEEL FOR ANY
AREAS SUBJECT TO PHYSICAL DAMAGE,
INCLUDING SURFACE MOUNTED CONDUIT
INSTALLED BELOW 8FT IN DRILL HALL OR
TRAINING BAY.
KEYED NOTES
PROVIDE AN ACCESSIBLE ELECTRICAL
DISCONNECT AT EACH SPLIT SYSTEM INDOOR
UNIT. PROVIDE 208V/1PH CONNECTION TO
DFC UNITS REQUIRED FOR DCU 1 THROUGH 9.
REFER TO SHEET E-602 FOR CIRCUIT
LOCATIONS.
MOUNT RECEPTACLE ADJACENT TO TV
OUTLET AT 84" AFF.
SCALE: 1/4" = 1'-0"
2' 4' 8' 12
NORTHNORTH
1/4" = 1'-0"
COMM RM 206 - ENLARGED
1/4" = 1'-0"
COMM RM 144 - ENLARGED
SAM FEEZOR
113619
Indoor ceiling-mount fan coil unit
Attachment G.6 - Scope of Work Page 18 of 97
WORKING
SPACE
DEDICATED
ELECTRICAL
SPACE
WIDTH OF EQUIPMENT
(MINIMUM 30")
6'-6" MINUMUM
6'-0" MINUMUM
SPRINKLER PIPE
PERMITTED
DUCTWORK PERMITTED
DEPTH PER NEC
TABLE 110.26(A)(1)
WORKING
SPACE WORKING
SPACE
SIDE
VIEW
FRONT
VIEW
SIDE
VIEW
FRONT
VIEW
LUMINAIRE
PERMITTED
STRUCTURE
(TYP)
DEDICATED
ELECTRICAL
SPACE
DEDICATED
ELECTRICAL
SPACE
SUSPENDED
CEILING (TYP) SPRINKLER
PIPING (TYP)
ELECTRICAL
PANEL (TYP)
36"
DEPTH
6' -6
H
E
IG
H T
6' -6
H
E
IG
H T
30"
WIDTH DEPTH OF PANEL
PANEL
WIDTH OF
PANEL PANEL PANEL
30"
MINIMUM WIDTH
30"
MINIMUM WIDTH
30"
MINIMUM WIDTH
ELECTRICAL
ROOM
WORKING SPACE MAY BE MEASURED FROM
THE PANEL EDGE FOR ELECTRICAL
EQUIPMENT MOUNTED CLOSE TO WALLS
WORKING SPACE FOR PANELS MAY
OVERLAP THE WORKING SPACE
MASONRY BLOCK WALL
1-HOUR & 2-HOUR
GYPSUM WALL
BOARD
UL 1479 FIRE STOP
PUTTY FLUSH WITH
SURFACE
MINERAL WOOL
TYPICAL CONDUIT
1" MAXIMUM OPENING
AROUND CONDUIT
EL
EC
2X 4" MOUSE HOLES
BOX
COVER
EXTENSION
BOXES USED TO ROUTE FIRE ALARM & BUILDING MANAGEMENT
SYSTEM CONTROLS SHALL BE PROVIDED WITH COVERS THAT
INDICATE SERVICE.
3/8-16 UNIC HEX HEAD BOLT W/ TWO
WASHERS
1/2" X 4" PULL SLOT
.5 SKID RESISTANT
SURFACE
BOXES SHALL HAVE GASKETED HEAVY
DUTY BOLT DOWN COVER, AND OPEN
BOTTOM. PROVIDE A MINIMUM 12"
AGGREGATE BASE BELOW ALL BOXES.
IN-GRADE PULL BOXES SHALL BE PROVIDED ALONG
THE LENGTH OF ALL BELOW GRADE CIRCUITS.
SPACING SHALL BE SUCH THAT PULLING TENSION
REQUIRED IS WITHIN MANUFACTURER'S SPECIFIED
LIMITS. MAXIMUM SPACING BETWEEN PULL PULL
POINTS SHALL BE 150'. MINIMUM BOX SIZE SHALL BE
18"X24".
BOXES INSTALLED INSTALLED IN AREAS
THAT MAY RECEIVE VEHICULAR TRAFFIC
SHALL BE PROVIDED WITH TRAFFIC
RATED COVERS.
EXAMPLE
PANEL HEA
480/277V, 3 PHASE, 4 WIRE
EMERGENCY SYSTEM
FED BY HEDA-3, (100A/3P)
PANELBOARD COVER
PANEL IDENTIFICATION NOTES:
1.
2.
SIMILAR FOR DISCONNECTS, MOTOR CONTROLLERS, TRANSFORMERS, LIGHTING CONTROL PANEL, AUTOMATIC TRANSFER SWITCHES, ETC.
PROVIDE PANEL IDENTIFICATION FOR ALL NEW PANELS AND FOR ALL EXISTING REWORKED PANELS
THAT DO NOT CURRENTLY HAVE IDENTIFICATION TAGS IN PLACE.
I.D. NAMEPLATE WITH THE
FOLLOWING INFORMATION:
1. EQUIPMENT I.D. ABBREVIATION
2. VOLTAGE, PHASE, WIRES
3. EMERGENCY OR NORMAL SYSTEM
4. POWER SOURCE ORIGINATION AND
OVERCURRENT DEVICE SIZE.
H W
P
IP
E
GROUNDING ELECTRODE
CONDUCTOR SIZE PER
NEC 250.66
BONDING JUMPER
SIZE PER NEC 250.66
M E
TA
L
G A
S P
IP
E
M E
TA
L
A
IR
P
IP
E
S P
R
IN
K
LE
R P
IP
E
M E
TA
L
D R
A
IN
P
IP
E M
E
TA
L V
E N
T P
IP
E
BRANCH CIRCUIT EQUIPMENT GROUND
CONDUCTOR WHICH SUPPLIES ELECTRICAL
EQUIPMENT CONNECTED TO PIPING. SIZE PER
NEC 250.122 TO COMPLY WITH NEC 250.104 3B OR
CONNECT TO SERVICE GROUND
NOTE:
ALL BONDING CONNECTIONS SHALL BE MADE AT ACCESSIBLE LOCATIONS. USE
EXOTHERMIC CONNECTIONS WHERE CONNECTED TO BUILDING STEEL, RE-BAR,
AND GROUND RODS. USE CLAMP CONNECTIONS FOR PIPING SYSTEMS.
COPPER CONDUCTOR TO
BE INSULATED WHERE IN
CONTACT WITH CONCRETE
REINFORCED CONCRETE FOOTING
4"
DOM. COLD WATER
EFFECTIVELY GROUNDED
METAL BUILDING FRAME
EXOTHERMIC WELD
CONNECTION TYPICAL
1" OR LARGER METAL COLD WATER PIPING 10' MINIMUM,
UNDERGROUND IN DIRECT CONTACT WITH EARTH AND
ELECTRICALLY CONTINUOUS, BONDING CONNECTION
SHALL BE IN AN ACCESSIBLE LOCATION
4"6" 3/4" X 10' COPPER-CLAD STEEL
GROUNDING ROD NUMBER AS REQUIRED
#4 REBAR, 20' - 0" MINIMUM
TOTAL LENGTH - LOCATE
AS NEAR TO BOTTOM OF
FOOTING AS POSSIBLE
CADWELD "GEM" OR EQUAL
(BELOW VAPOR BARRIER)
NEUTRAL BUS
REFER TO POWER RISER
EQUIPMENT GROUND BUS
SERVICE DISCONNECT/CIRCUIT BREAKER
GROUNDING BUSHING WITH BONDING CONDUCTOR SAME
SIZE AS GROUNDING ELECTRODE CONDUCTOR
1" CONDUIT
M
E
TA
L H
V A
C D
U C
TS
BURNDY #GAR OR EQUAL (LOCATE WITHIN 5'-0" OF WATER SERVICE)
GROUNDING ELECTRODE
CONDUCTOR SIZE PER NEC 250.66
MAIN POWER GROUND BUS BAR CONNECTED TO GROUNDING TRIAD, BUILDING
STEEL, COLD WATER PIPE, LIGHTNING PROTECTION, GROUND RING CONNECTION,
ENCASED ELECTRODES, AND TELECOMMUNICATIONS TMGB.
BOND EXISTING METALLIC SERVICE PIPING TO NEW BUILDING GROUND.
24"MIN
3"
3"
3"
TYP.
600 VOLTS OR LESS
TYPICAL DITCHING DETAIL
SELECT COMPACT
BACKFILL LESS THAN 2"
SIEVE (TYPICAL)
SELECT COMPACT BACKFILL
LESS THAN 1" SIEVE
1" MIN.
SCH. 40 PVC
FINISH GRADE SOD WHERE
GRASS CONCRETE WHERE
CONCRETE (TYPICAL) TRENCH TAPE
(TYPICAL)
THIS UNDERGROUND CONDUIT
DETAIL APPLIES TO LOW
VOLTAGE SITE ELECTRICAL
ONLY. REFER TO ENTERGY
STANDARDS FOR
UNDERGROUND CONDUIT
REQUIRMENTS FOR UTILITY
OWNED CABLING.
#4 HORIZONTAL BAR @
9" CENTERS (TYPICAL)
TRENCH TAPE
FINISHED GRADE
1" BEVEL
BASE COVER
GROUT SHALL BE PACKED UNDER POLE
BASE TO INSURE FULL CONTACT WITH
FOUNDATION - PROVIDE DRAIN HOLE
THRU GROUTING
INSTALL GROUND LUG
AND #6 SDBC TO REBAR
INSTALL BELL TYPE
NYLON BUSHINGS
(TYPICAL)
INSTALL RIGID GAL.
STEEL ELBOWS
(TYPICAL)
SCHEDULE 80 PVC
#4 VERTICAL BAR @
9" CENTERS (TYPICAL)
THREADED ANCHOR BOLT PER
MANUFACTURER'S REQUIRMENTS.
THE FIRST AND LAST LIGHTING
STANDARDS SHALL HAVE A SPARE
CONDUIT STUBBED OUT 4' BEYOND
BASE FOR FUTURE EXTENSION.
LENGTH
"L"
DIAMETER
"W"
18"
24"
24"
18"
4'-0"
5'-0"
6'-0"
4'-6"
MAX. POLE
HEIGHT
30'-0"
20'-0"
15'-0"
10'-0"
36"
24"
"L"
"W"
ROUND
(5
-6
W
T
H S
T R
E E
T F
A X
-1
A
U S
T
IN
T
E X
A S
T E
X A
S M
IL
IT
A R
Y D
E P
A R
T M
E N
T C
O N
S T
R U
C T
IO
N
F
A C
IL
IT
IE
S
M A
N A
G E
M E
N T
O F
F
IC
E -C
F M
O
REVISED ISSUE DATES:
REVIEWED BY:
DRAWN BY:
PROJECT NO.
ISSUE DATE:
PROJECT ARCHITECT:
TXARNG CFMO
DESIGNED BY:
E-501
ELECTRICAL DETAILS
C A
M P
B O
W
IE
S. FEEZOR
G. FREY
J. JOYCE
09/30/22 (IFC)
R E
D
IN
E S
S C
E N
T E
R M
A J O
R M
A
IN
T E
N A
N C
E
21F00095
N.T.S.
ELECTRICAL CLEARANCE DETAIL
N.T.S.
ELECTRICAL PANEL CLEARANCE
N.T.S.
ELECTRICAL WORKING SPACE
N.T.S.
FIRE WALL PENETRATION
N.T.S.
IN-GRADE PULL BOX DETAIL
N.T.S.
PANEL IDENTIFICATION DETAIL
N.T.S.
SERVICE GROUNDING DETAIL
N.T.S.
UNDERGROUND CONDUIT DETAIL
1/8" = 1'-0"
LIGHTING POLE BASE DETAIL
9/30/2022
SHT. 128 OF 140
Attachment G.6 - Scope of Work Page 19 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 1
SECTION 238129 - VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes: VRF HVAC systems.
1. Indoor, suspended, ceiling-mounted units.
2. Outdoor, air-source heat-pump units.
3. Heat recovery control units (HRCUs).
4. System controls.
5. System refrigerant and oil.
6. System condensate drain piping.
7. System refrigerant piping.
8. Metal hangers and supports.
9. Metal framing systems.
10. Fastener systems.
11. Miscellaneous support materials.
12. Piping and tubing insulation.
13. System control cable.
1.2 DEFINITIONS
A. Air-Conditioning System Operation: System capable of operation with all zones in cooling only.
B. Heat-Pump System Operation: System capable of operation with all zones in either heating or cooling, but not with simultaneous heating and cooling zones that transfer heat between zones.
C. Heat Recovery System Operation: System capable of operation with simultaneous heating and cooling zones that transfer heat between zones.
D. HRCU: Heat Recovery Control Unit. HRCUs are used in heat recovery VRF HVAC systems to manage and control refrigerant between indoor units to provide simultaneous heating and cooling zones. "Heat Recovery Control Unit" is the term used by ASHRAE for what different manufacturers term as branch circuit controller, branch selector box, changeover box, flow selector unit, mode change unit, and other such terms.
E. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control, signaling power-limited circuits.
F. Plenum: A space forming part of the air distribution system to which one or more air ducts are connected. An air duct is a passageway, other than a plenum, for transporting air to or from heating, ventilating, or air-conditioning equipment.
G. Three-Pipe System Design: One high pressure refrigerant vapor line, one low pressure refrigerant vapor line, and one refrigerant liquid line connect a single outdoor unit or multiple
Camp Bowie RC Major Maintenance TMD PN 48170030 Brownwood, Texas HVAC ADDITIONS
Attachment G.6 - Scope of Work Page 20 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 2
manifold outdoor units in a single system to associated system HRCUs. One liquid line and refrigerant vapor line connect HRCUs to associated indoor units.
H. Two-Pipe System Design: One refrigerant vapor line and one refrigerant liquid line connect a single outdoor unit or multiple manifold outdoor units in a single system to associated system
HRCUs. One refrigerant liquid line and refrigerant vapor line connect HRCUs to associated indoor units. HRCUs used in two pipe systems act as an intermediate heat exchanger and include diverting valves and gas/liquid separators to move high and low pressure refrigerant between indoor units.
I. VRF: Variable refrigerant flow.
1.3 ACTION SUBMITTALS
A. Product Data: For VRF HVAC system components.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for indoor and outdoor units and for HRCUs.
2. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
3. Include operating performance at design conditions and at extreme maximum and minimum outdoor ambient conditions.
4. Include description of system controllers, dimensions, features, control interfaces and connections, power requirements, and connections.
5. Include system operating sequence of operation in narrative form for each unique indoor-and outdoor-unit and HRCU control.
6. Include description of control software features.
7. Include total refrigerant required and a comprehensive breakdown of refrigerant required by each system installed.
8. Include refrigerant type and data sheets showing compliance with requirements indicated.
9. For system design software.
10. Indicate location and type of service access.
B. Shop Drawings: For VRF HVAC systems.
1. Include plans, elevations, sections, and mounting details.
2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
3. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment. Include adjustable motor bases, rails, and frames for equipment mounting.
4. Include diagrams and details of refrigerant piping and tubing showing installation requirements for manufacturer-furnished divided flow fittings.
5. Include diagrams for power, signal, and control wiring.
C. Delegated Design Submittals:
1. Include design calculations for selecting vibration isolators and for designing vibration isolation bases.
Attachment G.6 - Scope of Work Page 21 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 3
2. Include design calculations with corresponding diagram of refrigerant piping and tubing sizing for each system installed.
3. Include design calculations with corresponding floor plans indicating that refrigerant concentration limits are within allowable limits of ASHRAE 15 and governing codes.
4. Include calculations showing that system travel distance for refrigerant piping and controls cabling are within horizontal and vertical travel distances set by manufacturer.
Provide a comparison table for each system installed.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For VRF HVAC systems to include in emergency, operation, and maintenance manuals.
B. Software and Firmware Operational Documentation:
1. Software operating and upgrade manuals.
2. Program Software Backup: On CD or DVD, USB media, or approved cloud storage platform, complete with data files.
3. Device address list.
4. Printout of software application and graphic screens.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Nationally recognized manufacturer of VRF HVAC systems and products.
2. Shipped VRF HVAC systems with similar requirements to those indicated for a continuous period of five years within time of bid.
3. VRF HVAC systems and products that have been successfully tested and in use on at least three completed projects.
4. Having complete published catalog literature, installation, and operation and maintenance manuals for all products intended for use.
5. Having full-time in-house employees for the following:
a. Product research and development.
b. Product and application engineering.
c. Product manufacturing, testing, and quality control.
d. Technical support for system installation training, startup, commissioning, and troubleshooting of installations.
e. Owner training.
B. Factory-Authorized Service Representative Qualifications:
1. Authorized representative of, and trained by, VRF HVAC system manufacturer.
2. Demonstrated past experience with products being installed for period within three consecutive years before time of bid.
3. Demonstrated past experience on five projects of similar complexity, scope, and value.
a. Each person assigned to Project shall have demonstrated past experience.
Attachment G.6 - Scope of Work Page 22 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 4
4. Staffing resources of competent and experienced full-time employees that are assigned to execute work according to schedule.
5. Service and maintenance staff assigned to support Project during warranty period.
6. Product parts inventory to support ongoing system operation for a period of not less than five years after Substantial Completion.
7. VRF HVAC system manufacturer's backing to take over execution of Work if necessary to comply with requirements indicated. Include Project-specific written letter, signed by manufacturer's corporate officer, if requested.
C. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by VRF HVAC system manufacturer.
1. Each employee shall be certified by manufacturer for proper installation of systems, including, but not limited to, equipment, piping, controls, and accessories indicated and furnished for installation.
2. Installer certification shall be valid and current for duration of Project.
3. Retain copies of Installer certificates on-site and make available on request.
4. Each person assigned to Project shall have demonstrated past experience.
a. Demonstrated past experience with products being installed for period within three consecutive years before time of bid.
b. Demonstrated past experience on five projects of similar complexity, scope, and value.
D. ISO Compliance: System equipment and components furnished by VRF HVAC system manufacturer shall be manufactured in an ISO 9001 and ISO 14001 facility.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver and store products in a clean and dry place.
B. Comply with manufacturer's written rigging and installation instructions for unloading and moving to final installed location.
C. Handle products carefully to prevent damage, breaking, denting, and scoring. Do not install damaged products.
D. Protect products from weather, dirt, dust, water, construction debris, and physical damage.
1. Retain factory-applied coverings on equipment to protect finishes during construction and remove just prior to operating unit.
2. Cover unit openings before installation to prevent dirt and dust from entering inside of units. If required to remover coverings during unit installation, reapply coverings over openings after unit installation and remove just prior to operating unit.
E. Replace installed products damaged during construction.
Attachment G.6 - Scope of Work Page 23 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 5
1.7 WARRANTY
A. Manufacturer's Warranty: Manufacturer agrees to repair or replace equipment and components that fail(s) in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures.
b. Faulty operation.
c. Deterioration of metals, metal finishes, and other materials beyond normal weathering and use.
2. Warranty Period:
a. For Compressor: Five year(s) from date of Substantial Completion.
b. For Parts, Including Controls: Five year(s) from date of Substantial Completion.
c. For Labor: Five year(s) from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 VRF HVAC SYSTEMS
A. Source Limitations: Obtain products from single source from single manufacturer including, but not limited to, the following:
1. Indoor and outdoor units, including accessories.
2. Controls and software.
3. HRCUs.
4. Refrigerant isolation valves.
5. Specialty refrigerant pipe fittings.
2.2 SYSTEM DESCRIPTION
A. Direct-expansion (DX) VRF HVAC system(s) with variable capacity in response to varying cooling and heating loads. System shall consist of multiple indoor units, HRCUs, outdoor unit(s), piping, controls, and electrical power to make complete operating system(s) complying with requirements indicated.
1. Two-pipe system design.
2. System(s) operation, heat pump or heat recovery as indicated on Drawings.
3. Each system with one refrigerant circuit shared by all indoor units connected to system.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. AHRI Compliance: System and equipment performance certified according to AHRI 1230.
D. ASHRAE Compliance:
Attachment G.6 - Scope of Work Page 24 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 6
1. ASHRAE 15: For safety code for mechanical refrigeration.
2. ASHRAE 62.1: For indoor air quality.
3. ASHRAE 135: For control network protocol with remote communication.
4. ASHRAE/IES 90.1 Compliance: For system and component energy efficiency.
E. UL Compliance: Comply with UL 1995.
2.3 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional specialist, as defined in Section 014000
"Quality Requirements," to design complete and operational VRF HVAC system(s) complying with requirements indicated.
1. Provide system refrigerant calculations.
a. Refrigerant concentration limits shall be within allowable limits of ASHRAE 15 and governing codes.
b. Indicate compliance with manufacturer's maximum vertical and horizontal travel distances. Prepare a comparison table for each system showing calculated distances compared to manufacturer's maximum allowed distances.
2. Include a mechanical ventilation system and gas detection system as required to comply with ASHRAE 15 and governing codes.
3. System Refrigerant Piping and Tubing:
a. Arrangement: Arrange piping to interconnect indoor units, HRCUs, and outdoor unit(s) in compliance with manufacturer requirements and requirements indicated.
b. Routing: Conceal piping above ceilings and behind walls to maximum extent possible.
c. Sizing: Size piping system, using a software program acceptable to manufacturer, to provide performance requirements indicated. Consider requirements to accommodate future change requirements.
4. System Controls:
a. Network arrangement.
b. Network interface with other building systems.
c. Product selection.
d. Sizing.
B. Service Access:
1. Provide and document service access requirements.
2. Locate equipment, system isolation valves, and other system components that require service and inspection in easily accessible locations. Avoid locations that are difficult to access if possible.
3. Where serviceable components are installed behind walls and above inaccessible ceilings, provide finished assembly with access doors or panels to gain access. Properly size the openings to allow for service, removal, and replacement.
Attachment G.6 - Scope of Work Page 25 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 7
4. If less than full and unrestricted access is provided, locate components within an 18-inch reach of the finished assembly.
5. Where ladder access is required to service elevated components, provide an installation that provides for sufficient access within ladder manufacturer's written instructions for use.
6. Comply with OSHA regulations.
C. System Design and Installation Requirements:
1. Design and install systems indicated according to manufacturer's recommendations and written instructions.
2. Where manufacturer's requirements differ from requirements indicated, contact Architect for direction. The most stringent requirements should apply unless otherwise directed in writing by Architect.
D. Isolation of Equipment: Provide isolation valves to isolate each HRCU, indoor unit and outdoor unit for service, removal, and replacement without interrupting system operation.
E. System Capacity Ratio: The sum of connected capacity of all indoor units shall be within the following range of outdoor-unit rated capacity:
1. Not less than 60 percent.
2. Not more than 100 percent.
3. Range acceptable to manufacturer.
F. System Turndown: Stable operation down to 20 percent of outdoor-unit capacity.
G. System Auto Refrigerant Charge: Each system shall have an automatic refrigerant charge function to ensure the proper amount of refrigerant is installed in system.
H. Outdoor Conditions:
1. Suitable for outdoor ambient conditions encountered.
a. Design equipment and supports to withstand wind loads of governing code.
I. Sound Performance: Sound levels generated by operating HVAC equipment shall be within requirements indicated.
1. Indoor: Within design guidelines of "2015 ASHRAE HANDBOOK- HVAC
Applications.
2. Outdoor: Within ordinance of governing authorities.
J. Thermal Movements: Allow for controlled thermal movements from ambient, surface, and system temperature changes.
K. Capacities and Characteristics: As indicated on Drawings.
Attachment G.6 - Scope of Work Page 26 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 8
2.4 INDOOR, SUSPENDED, CEILING-MOUNTED UNITS
A. Description: Factory-assembled complete unit with components, piping, wiring, and controls required for mating to piping, power, and controls field connections.
B. Cabinet:
1. Material: Painted steel, or coated steel frame covered by a plastic cabinet, with an architectural acceptable finish suitable for tenant occupancy on exposed surfaces.
2. Insulation: Manufacturer's standard internal insulation to provide thermal resistance and prevent condensation.
3. Mounting: Manufacturer-designed provisions for field installation.
4. Internal Access: Removable panels of adequate size for field access to internal components for inspection, cleaning, service, and replacement.
C. DX Coil Assembly:
1. Coil Casing: Aluminum, galvanized, or stainless steel.
2. Coil Fins: Aluminum, mechanically bonded to tubes, with arrangement required by performance.
3. Coil Tubes: Copper, of diameter and thickness required by performance.
4. Expansion Valve: Electronic modulating type with linear or proportional characteristics.
5. Internal Tubing: Copper tubing with brazed joints.
6. Internal Tubing Insulation: Manufacturer's standard insulation, of thickness to prevent condensation.
7. Field Piping Connections: Manufacturer's standard.
8. Factory Charge: Dehydrated air or nitrogen.
9. Testing: Factory pressure tested and verified to be without leaks.
D. Drain Assembly:
1. Pan: Non-ferrous material, with bottom sloped to low point drain connection.
2. Condensate Removal: Gravity.
a. If a floor drain is not available at unit, provide unit with field-installed condensate pump accessory.
3. Field Piping Connection: Non-ferrous material.
E. Fan and Motor Assembly:
1. Fan(s):
a. Direct-drive arrangement.
b. Single or multiple fans connected to a common motor shaft and driven by a single motor.
c. Fabricated from non-ferrous components or ferrous components with corrosion protection finish.
d. Wheels statically and dynamically balanced.
2. Motor: Brushless dc or electronically commutated with permanently lubricated bearings.
Attachment G.6 - Scope of Work Page 27 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 9
3. Motor Protection: Integral protection against thermal, overload, and voltage fluctuations.
4. Speed Settings and Control: Two (low, high), three (low, medium, high), or more than three speed settings or variable speed with a speed range of least 50 percent.
5. Vibration Control: Integral isolation to dampen vibration transmission.
F. Filter Assembly:
1. Access: Front, to accommodate filter replacement without the need for tools.
2. Washable Media: Manufacturer's standard filter with antimicrobial treatment.
G. Discharge-Air Grille Assembly: Mounted in front of unit cabinet.
1. Discharge Pattern: One-way throw.
H. Return-Air Grille Assembly: Manufacturer's standard.
I. Outdoor Air Ventilation Connection: Sheet metal knockout for optional connection to outdoor air ventilation duct.
J. Unit Accessories:
1. Remote Room Temperature Sensor Kit: Wall-mounted, hardwired room temperature sensor kit for use in rooms that do not have room temperature measurement.
2. Condensate Pump: Integral reservoir and control with electrical power connection through unit power.
K. Unit Controls:
1. Enclosure: Manufacturer's standard, and suitable for indoor locations.
2. Factory-Installed Controller: Configurable digital control.
3. Factory-Installed Sensors: Unit inlet air temperature.
4. Field-Customizable I/O Capability:
a. Digital Inputs: Two for use in customizable control strategies.
b. Digital Outputs: Two for use in customizable control strategies.
5. Features and Functions: Self-diagnostics, time delay, auto-restart, auto operation mode]
[, manual operation mode.
6. Communication: Network communication with other indoor units and outdoor unit(s).
7. Cable and Wiring: Manufacturer's standard with each connection labeled and corresponding to a unit-mounted wiring diagram.
8. Field Connection: Manufacturer's standard with each connection labeled and corresponding to a unit-mounted wiring diagram.
L. Unit Electrical:
1. Enclosure: Manufacturer's standard, and suitable for indoor locations.
2. Field Connection: Single point connection to power entire unit and integral controls.
3. Disconnecting Means: Factory-mounted circuit breaker or switch, complying with
NFPA 70.
4. Control Transformer: Manufacturer's standard. Coordinate requirements with field power supply.
Attachment G.6 - Scope of Work Page 28 of 97
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS 238129 - 10
5. Wiring: Manufacturer's standard with each connection labeled and corresponding to a unit-mounted wiring diagram.
6. Raceways: Enclose line voltage wiring in [metal ]raceways to comply with NFPA 70.
2.5 OUTDOOR, AIR-SOURCE HEAT-PUMP UNITS
A. Description: Factory-assembled and -tested complete unit with components, piping, wiring, and controls required for mating to piping, power, and controls field connections.
1. Specially designed for use in systems with either all heating or all cooling demands, but not for use in systems with simultaneous heating and cooling.
2. Systems shall consist of one unit, or multiple unit modules that are designed by variable refrigerant system manufacturer for field interconnection to make a single refrigeration circuit that connects multiple indoor units.
3. All units installed shall be from the same product development generation.
B. Cabinet:
1. Galvanized steel and coated with a corrosion-resistant finish.
a. Coating with documented salt spray test performance of 1000 hours according
ASTM B117 surface scratch test (SST) procedure.
2. Mounting: Manufacturer-designed provisions for field installation.
3. Internal Access: Removable panels or hinged doors of adequate size for field access to internal components for inspection, cleaning, service, and replacement.
C. Compressor and Motor Assembly:
1. One or more positive-displacement, direct-drive and hermetically sealed scroll compressor(s) with inverter drive and turndown to 15 percent of rated capacity.
2.…
This is the start of the file's text. The full file is on GovTribe.