ESBD_506851_1778880382611_IW244389 - Amendment No. 1.pdf
PDF 6 MB Posted
- Attached to
- TDCJ - Plane Unit - Duct Heater Package
- Solicitation number
- IW244389
- Issued by
- Liberty County, Texas
About this file
This is Amendment No. 1 to an Invitation for Bid (IFB) issued by the Texas Department of Criminal Justice (TDCJ), Contracts and Procurement Department, for the replacement of 34 duct heating units at the Plane Unit in Dayton, Texas. The amendment addresses clarifications regarding the scope of work, which involves procuring and installing variable air volume (VAV) boxes and fan-powered boxes (FPB) rather than standard duct heaters, along with associated controls, disconnects, and installation services. The original bid opening date of May 18, 2025, at 3:00 PM has been revised to May 27, 2026, at 3:00 PM. The amendment provides responses to eleven bidder questions concerning equipment specifications, including duct inlet sizes, box voltages, kilowatt ratings, primary and heating airflows, motor sizes for fan-powered units, and heat sizes for all 34 boxes. The TDCJ specifies that new controls will be required (not existing controls), new electrical disconnects will be installed with WIP lines, and the terminal units consist of a mixture of single-duct and fan-powered boxes, with some containing motors and others without. Bidders must acknowledge receipt of this amendment with their bid submission to receive consideration.
The amendment references attached technical drawings and photographs that provide detailed specifications for duct sizes and equipment configurations for the medical and education buildings. All questions and answers provided in the amendment are directly tied to engineering specifications and equipment compatibility, indicating the TDCJ has clarified technical requirements to enable accurate bid preparation. Bidders are required to reference the attached documentation to understand equipment requirements fully. The contract requires commercial general liability insurance of $1 million general aggregate with $500,000 per occurrence limits and automobile liability coverage of $500,000 combined single limit, with a payment bond required for bids exceeding $25,000. The project timeline extends from a June 28, 2026, commencement date to an October 11, 2026, completion deadline. No specific budget amount is disclosed in the amendment, and no Historically Underutilized Business (HUB) subcontracting set-asides are available for this procurement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Our mission is to provide public safety, promote positive change in offender behavior, reintegrate offenders into society, and assist victims of crime.
2 Financial Plaza, Suite 703
Huntsville, Texas 77340
(936) 437-3885 www.tdcj.texas.gov
T e x a s D e p a r t m e n t o f C r i m i n a l J u s t i c e
Bobby Lumpkin Executive Director
Contracts and Procurement Department
AMENDMENT No. 1
BID NO.: IW244389
PURCHASER / CONTRACT SPECIALIST: Teria Godwin-Pierce BID OPENING DATE & TIME: 05/18/2025 at 03:00 PM REVISED BID OPENING DATE & TIME: 05/27/2026 at 03:00 PM
The purpose of this amendment is to provide answers to questions.
Reference attached pages of this amendment.
IN THE SUBMISSION OF BID, BIDDER MUST ACKNOWLEDGE RECEIPT OF THIS
AMENDMENT; OTHERWISE, THE BID MAY NOT BE GIVEN CONSIDERATION.
BIDDER MAY ACKNOWLEDGE RECEIPT ON FACE OF BID OR BY RETURNING
ONE COPY OF THIS NOTICE.
SIGNED:
BIDDER
COMPANY NAME:
(936) 437-3885 www.tdcj.texas.gov
Amendment No. 1 Bid No.: IW244389
Question
No.
Question
Answer
1 We need a better list of the VAV units because they are typically made to order depending on each duct
Also need to know if we are going to reuse existing controls and what type they are.
Please see the attachments and the pictures below.
2 Solicitation shows to be duct heaters, but they are VAV's and FPB's. Please provide list box size, voltage, and KW. For each box.
Please see the attachments and the pictures below.
3 Please provide Drawings showing duct size.
Please see the attachments and the pictures below.
4 Will the controls for the boxes be stand alone or will they tie into a BAS system?
New Controls.
5 Confirm there are existing disconnects and that they are to be reused.
New with WIP Lines.
6 The solicitation is requesting duct heaters, but the example model numbers are describing VAV boxes. Is this is the case? Confirm if these are all single duct terminal units, all fan powered, or a mixture of the two.
Some with motors and some without.
7 Are there any schedules that can be provided for all (34) of the boxes?
Please see the attachments and the pictures below.
8 What are the duct inlet sizes of all boxes? Please see the attachments and the pictures below.
9 What are the primary airflows of all boxes? What are the heating airflow for all the boxes?
Please see the attachments and the pictures below.
10 If there are fan powered boxes, what are the motor sizes?
Please see the attachments and the pictures below.
11 What are the heat sizes for all boxes? Please see the attachments and the pictures below.