ESBD_358316_1715117823151_IW181539 Drawings.pdf
PDF 657 KB Posted
- Attached to
- PROCUREMENT AND INSTALLATION OF A MONITORED PULSE FENCE DETECTION SYSTEM AT THE TDCJ MCCONNELL UNIT.
- Solicitation number
- IW181539
- Issued by
- Bastrop County, Texas
About this file
This document appears to be a set of engineering drawings and specifications for the installation of a Monitored Pulse Fence Detection System at the McConnell Unit of the Texas Department of Criminal Justice. The project includes the installation of a perimeter security system, control panels, and associated electrical infrastructure across the facility grounds. The drawings provide detailed site plans, electrical schematics, and zoning information for the planned pulse fence system. The engineering work is being performed by Eduardo F. Viana, a licensed professional engineer in the state of Texas. The project is designated as MWR #04822003 and is currently in the construction phase, with a targeted completion date of December 21, 2023.
The specifications indicate that all electrical work must comply with the current edition of the National Electrical Code and Texas Department of Criminal Justice standards. The pulse fence system will be divided into 14 distinct zones, ranging from 270 to 490 feet in length. The drawings also reference an existing stun fence system around the 12 main buildings, which will be integrated with the new monitored pulse fence. No information is provided regarding pricing, funding sources, or procurement processes in the reviewed documentation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FO
A X
S E
A
T H
E S
HUNTSVILLE, TEXAS
FACILITIES DIVISION
THE TEXAS DEPARTMENT OF CRIMINAL JUSTICE
ENGINEERING SERVICES
E
DRAWING INDEX
COVER SHEET
MWR. NO. 04822003
TYLER
HUNTSVILLE
AUSTIN
SAN ANTONIO
HOUSTON
DALLAS
LUBBOCK
AMARILLO
EL PASO
LAREDO
FT. WORTH
INSTALL MONITORED PULSE FENCE
T T
T
McCONNELL UNIT
E1 UNIT SITE PLAN - POWER
E2 PULSE FENCE SITE PLAN
WORK SITE VIEW
PROJECT LOCATION
REGIONAL VIEW
STATE-WIDE VIEW
DETECTION SYSTEM - PERIMETER
SHEET 1 OF 3
N
McCONNELLN
B - WING
A - WING
McCONNELL
UNIT
BEE COUNTY
SITE LOCATION
BEEVILLE, TEXAS
McCONNELL UNIT
28.3723 N / -97.7170 W
BLDG. 1
BLDG. 2
BLDG. 3
BLDG. 4
BLDG. 5
BLDG. 6
BLDG. 19
BLDG. 18
BLDG. 17
BLDG. 14
BLDG. 15
BLDG. 7
BLDG. 8
BLDG. 9
BLDG. 10
BLDG. 11
BLDG. 12A
BLDG. 12B
BLDG. 12C
PROJECT
LOC. STUN
FENCE
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text o
AutoCAD SHX Text p
AutoCAD SHX Text o
AutoCAD SHX Text o
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text p
AutoCAD SHX Text o
AutoCAD SHX Text o
AutoCAD SHX Text
CHASE FIELD
AutoCAD SHX Text
BEEVILLE
AutoCAD SHX Text
S. WASHINGTON
AutoCAD SHX Text
BYPASS
AutoCAD SHX Text
AutoCAD SHX Text
BUS.
AutoCAD SHX Text
US 181
AutoCAD SHX Text
CHRISTI
AutoCAD SHX Text
CORPUS
AutoCAD SHX Text
WEST
AutoCAD SHX Text
BYRD ST.
AutoCAD SHX Text
MOREHOUSE RD.
AutoCAD SHX Text
OFFSITE RD.
AutoCAD SHX Text
ENTERPRISE ST.
AutoCAD SHX Text
CONSTITUTION ST.
AutoCAD SHX Text
KING ST.
AutoCAD SHX Text
ESSEX ST.
AutoCAD SHX Text
JOHN ROGERS
AutoCAD SHX Text
INDEPENDENCE ST.
AutoCAD SHX Text
ELLYSON ST.
AutoCAD SHX Text
ESSEX ST.
AutoCAD SHX Text
MC CAIN RD.
AutoCAD SHX Text
HALSEY
AutoCAD SHX Text
EAST
AutoCAD SHX Text
GARZA
AutoCAD SHX Text
WEST
AutoCAD SHX Text
GARZA
BLDG. 1
BLDG. 2
BLDG. 3
BLDG. 4
BLDG. 5
BLDG. 6
BLDG. 19
BLDG. 18
BLDG. 17
BLDG. 14
BLDG. 15
BLDG. 7
BLDG. 8
BLDG. 9
BLDG. 10
BLDG. 11
BLDG. 12A
BLDG. 12B
BLDG. 12C
PARKING LOT
ENTRY
SALLY PORT
A
N O
D
AT
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
PR
O
JE
C
T N
AM
E:
D
ES
C R
IP
TI
O N
R
EV
IS
IO
N
1 2 3 4 5 1 2
IS
SU
ED
F
O R
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
TITLE:
M W
R
U N
IT
EN
G
IN
EE
R
D R
AW
N
B Y:
D
AT
E:
SC
AL
E:
A S
SH
O
W N
D
AT
E
SHEET OF
E1
IN
ST
AL
L
M O
N
IT
O R
ED
P
U
LS
E
FE
N C
E D
ET
EC
TI
O
N S
YS
TE
M
- P
ER
IM
ET
ER
ED
U
AR
D
O F
. V
IA
N A
/0
2/
M cC
O N
N
EL
L
ED
U
AR
D
O F
. V
IA
N A
UNIT SITE PLAN
- POWER
C O
N
ST
R U
C
TI
O N
/2
1/
2 3
D R
AW
IN
G P
AT
H
J:
\D
EP
TI
N
FO
\E ng in ee rin g\ En gi ne er in g G ro up
\E N
G \A
C
AD
L
IB
R
AR
Y\ Pr oj ec t D ra w in g D at ab as e\
M cC on ne ll (0
)\0
In st al l M on ito re d
Pu ls e Fe nc e
D et ec tio n Sy st em
Pe rim et er \0
In st al l M on ito re d
Pu ls e Fe nc e
D et ec tio n Sy st em
Pe rim et er .d w g
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE
TYPE AND QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR
MANUFACTURER NAMES SHALL BE INTERPRETED TO INCLUDE THE LANGUAGE "OR
A/E APPROVED EQUAL". ANY BRAND OR MANUFACTURER MEETING SPECIFICATIONS
WILL BE CONSIDERED, IRRESPECTIVE OF THE LANGUAGE "OR A/E APPROVED EQUAL"
APPEARING IN CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
UNIT SITE PLAN - POWER
Scale: NTS1
NOTES :
1. PROJECT SPECIFIC REQUIREMENTS AS PER TDCJ SPECS, SECTION 01 00 00.10
2. ALL ELECTRICAL CONDUITS, CIRCUITRY, AND GROUNDING SHALL BE
INSTALLED PER THE CURRENT EDITION OF THE N.E.C.
2. CONDUIT IS DEPICTED DIAGRAMMATICALLY, CONTRACTOR TO ROUTE AS
NECESSARY.
3. ALL CIRCUIT CONDUCTORS SHALL BE OF COPPER THWN-2.
4. All CONDUITS SHALL COMPLY WITH TDCJ SPECS, SECTION 26 05 33.
12/21/2023
PNL. 1EL1
CENTRAL CONTROL ROOM. A 120VAC/20A
EMERGENCY CIRCUIT SHALL BE RUN TO THIS
LOCATION FOR CONTROL EQUIPMENT POWER.
KEYED NOTES:
1 RUN ONE 3 4" CONDUIT WITH 2#10 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL 1EL1 IN BLDG 1 ELECT. ROOM #01-127 TO CENTRAL CONTROL AND
INSTALL A 120V, 20A RECEPTACLE ON A 120V, 20A CKT.
2 RUN ONE 1 12" CONDUIT WITH 2#6 +1#12 GND THWN2 CONDUCTORS FROM
PANEL13EL1 IN BLDG 13 ELECT. ROOM #13-104 TO CONTROL CABINET ON 1-
120V, 20A CKT.
3 RUN ONE 1 12" CONDUIT WITH 2#6 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL CEL1 IN PICKET TOWER-C TO CONTROL CABINET ON 1-120V, 20A CKT.
4 RUN ONE 1 12" CONDUIT WITH 2#6 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL CEL1 IN PICKET TOWER-C TO CONTROL CABINET ON 1-120V, 20A CKT.
5 RUN ONE 1 12" CONDUIT WITH 2#6 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL BEL1 IN PICKET TOWER-B TO CONTROL CABINET ON 1-120V, 20A CKT.
6 RUN ONE 1 12" CONDUIT WITH 2#6 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL BEL1 IN PICKET TOWER-B TO CONTROL CABINET ON 1-120V, 20A CKT.
7 RUN ONE 1 12" CONDUIT WITH 2#4 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL AEL1 IN PICKET TOWER-A TO CONTROL CABINET ON 1-120V, 20A CKT.
8 RUN ONE 1 12" CONDUIT WITH 2#10 + 1#12 GND THWN2 CONDUCTORS FROM
PANEL AEL1 IN PICKET TOWER-A TO CONTROL CABINET ON 1-120V, 20A CKT.
LEGEND
SERVER & FIBER/DATACOM HEAD-END
CONTROL PANEL / NEMA 3R, 120VAC/20A, 1PH
PULL BOX
DOPPLER DETECTION SYSTEM
EMERGENCY ELECT. PNL 208/120VAC
FIBER OPTIC (1 12" UNDERGROUND CONDUIT)
120VAC/20A CKT (1 12" UNDERGROUND CONDUIT)
PNL. 13EL1
PERIMETER SECURITY
PICKET TOWER - B
PERIMETER SECURITY
PICKET TOWER - C
PNL. BEL1
PERIMETER SECURITY
PICKET TOWER - A
PNL. CEL1
PNL. AEL1
EXISTING STUN FENCE
AROUND 12 BLDG. PERIMETER.
EXISTING FENCE CONTROLLER
FOR STUN FENCE 12 BLDG.
EXISTING FENCE CONTROLLER
FOR STUN FENCE 12 BLDG.
AutoCAD SHX Text
NORTH
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text J
AutoCAD SHX Text T
AutoCAD SHX Text 129756
AutoCAD SHX Text
EDUARDO FIERRO VIANA
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
D
BLDG. 1
BLDG. 2
BLDG. 3
BLDG. 4
BLDG. 5
BLDG. 6
BLDG. 19
BLDG. 18
BLDG. 17
BLDG. 14
BLDG. 15
BLDG. 7
BLDG. 8
BLDG. 9
BLDG. 10
BLDG. 11
BLDG. 12A
BLDG. 12B
BLDG. 12C
PARKING LOT
ENTRY
SALLY PORT
A
N O
D
AT
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
PR
O
JE
C
T N
AM
E:
D
ES
C R
IP
TI
O N
R
EV
IS
IO
N
1 2 3 4 5 1 2
IS
SU
ED
F
O R
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
TITLE:
M W
R
U N
IT
EN
G
IN
EE
R
D R
AW
N
B Y:
D
AT
E:
SC
AL
E:
A S
SH
O
W N
D
AT
E
SHEET OF
E2
IN
ST
AL
L
M O
N
IT
O R
ED
P
U
LS
E
FE
N C
E D
ET
EC
TI
O
N S
YS
TE
M
- P
ER
IM
ET
ER
ED
U
AR
D
O F
. V
IA
N A
/0
2/
M cC
O N
N
EL
L
ED
U
AR
D
O F
. V
IA
N A
PULSE FENCE
SITE PLAN
C O
N
ST
R U
C
TI
O N
/2
1/
3 3
D R
AW
IN
G P
AT
H
J:
\D
EP
TI
N
FO
\E ng in ee rin g\ En gi ne er in g G ro up
\E N
G \A
C
AD
L
IB
R
AR
Y\ Pr oj ec t D ra w in g D at ab as e\
M cC on ne ll (0
)\0
In st al l M on ito re d
Pu ls e Fe nc e
D et ec tio n Sy st em
Pe rim et er \0
In st al l M on ito re d
Pu ls e Fe nc e
D et ec tio n Sy st em
Pe rim et er .d w g
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE
TYPE AND QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR
MANUFACTURER NAMES SHALL BE INTERPRETED TO INCLUDE THE LANGUAGE "OR
A/E APPROVED EQUAL". ANY BRAND OR MANUFACTURER MEETING SPECIFICATIONS
WILL BE CONSIDERED, IRRESPECTIVE OF THE LANGUAGE "OR A/E APPROVED EQUAL"
APPEARING IN CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
NOTES :
1. PROJECT SPECIFIC REQUIREMENTS AS PER TDCJ SPECS, SECTION 01 00 00.10
2. ALL ELECTRICAL CONDUITS, CIRCUITRY, AND GROUNDING SHALL BE
INSTALLED PER THE CURRENT EDITION OF THE N.E.C.
12/21/2023
LEGEND
CONTROL PANEL / NEMA 3R, 120VAC/20A, 1PH
PULSE FENCE SITE PLAN
Scale: NTS1
DOPPLER DETECTION SYSTEM
PULSE FENCE
ZONE 2
275 FT.
ZONE 3
470 FT.
ZONE 4
300 FT.
ZONE 5
420 FT.
ZONE 6
480 FT.
ZONE 7
270 FT.
ZONE 9
370 FT.
ZONE 10
490 FT.
ZONE 11
420 FT.
ZONE 12
325 FT.
ZONE 13
295 FT.
ZONE 1
275 FT.
ZONE 8
270 FT.
ZONE 14
295 FT.
EXISTING STUN FENCE
AROUND 12 BLDG. PERIMETER.
EXISTING FENCE CONTROLLER
FOR STUN FENCE 12 BLDG.
EXISTING FENCE CONTROLLER
FOR STUN FENCE 12 BLDG.
AutoCAD SHX Text
NORTH
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text J
AutoCAD SHX Text T
AutoCAD SHX Text 129756
AutoCAD SHX Text
EDUARDO FIERRO VIANA
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
D
| 04822003 Install Monitored Pulse Fence Detection System - Perimeter-COVER |
| Sheets and Views |
| COVER |
| 04822003 Install Monitored Pulse Fence Detection System - Perimeter-E1 |
| Sheets and Views |
| E1 |
| 04822003 Install Monitored Pulse Fence Detection System - Perimeter-E2 |
| Sheets and Views |
| E2 |