Erie VAMC Expand Emergency Power Phase 3 - Drawings.pdf
PDF 29 MB Posted
- Solicitation number
- VA-25-00073838
About this file
These are comprehensive electrical engineering drawings for the Erie VA Medical Center's Emergency Power Phase 3 Project (Contract No. 562-21-708), detailing a significant electrical infrastructure upgrade across multiple buildings. The project involves expanding and modernizing emergency power systems, including installing a new 600kW/750kVA bi-fuel generator in Building #11, replacing existing electrical panels, modifying switchgear, and updating electrical distribution infrastructure across Building #1 and associated facilities.
Key technical scope includes removing existing generators and electrical equipment in Buildings #11 and #12, installing new emergency transfer switches, redistributing electrical loads, replacing Federal Pacific panels with Square D panels, and extending/modifying existing electrical conduits and feeders. The project involves precise electrical system modifications across basement, first, second, third, fifth, sixth, seventh, eighth, and ninth floors, with careful coordination required to minimize facility disruptions. The solicitation indicates proposals are due on July 23, 2025 by 10:00am EST, with no additional site visits or time extensions permitted.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24425R0093 0001.pdf | ||
| Transformer Name Plate.JPG | JPG image | |
| 36C24425R0093_1.pdf | ||
| Erie EEPG3 Site Visit 6-24-25.pdf | ||
| Erie VAMC Expand Emergency Power Phase 3 - Specifications.pdf | ||
| 36C24425R0093 0002.pdf | ||
| As Built for Building 12.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
SITE
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
COVER SHEET &
DRAWING INDEX
GI001
DRTH
CO
W
W W
W
W
W
S
T
E
E
CO
CO
W
W W
W
W
W
S
T
E
E
E
T
CIVIL
PROPOSED CONDITIONS SITE PLAN
CS101
DJLJRS
562-21-708
2023-07-12
KEYPLAN
BLDG 8
BLDG 14
BLDG 18
EAST 38th STREET
BL
D
G
BL
DG
6BL
D
G
BLDG 1
O
LD
F
RE
NC
H
RO
AD
BL
DG
SITE
AREA OF
WORK
AREA OF
WORK
PROPOSED SITE PLANEXISTING SITE PLAN
NO. DESCRIPTION DATE
VA FORM 08-6231
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
321 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
A
C
D
E
F
Civil Engineering:
PENNTERRA ENGINEERING, INC.
AutoCAD SHX Text
TANK
AutoCAD SHX Text F
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text Fire
AutoCAD SHX Text Fire
AutoCAD SHX Text
NO PARKING
AutoCAD SHX Text Fire
AutoCAD SHX Text Shed
AutoCAD SHX Text Fire
AutoCAD SHX Text Conn
AutoCAD SHX Text
%%UPARKING
AutoCAD SHX Text H
AutoCAD SHX Text Salt
AutoCAD SHX Text (Location Approximate)
AutoCAD SHX Text Trans- former
AutoCAD SHX Text Ex. Building 11
AutoCAD SHX Text Ex. Pump House
AutoCAD SHX Text Ex. Building 6
AutoCAD SHX Text Underground Storm Water Retention Area
AutoCAD SHX Text Ex Window Well Not Field Verified
AutoCAD SHX Text Ex. Enclosed Structure Not Field Verified
AutoCAD SHX Text
PROPOSED GENERATOR (REFER TO ELECTRICAL PLANS)
AutoCAD SHX Text
PROPOSED ELECTRIC LINE FOR NEW GENERATOR (REFER TO ELECTRICAL PLANS)
AutoCAD SHX Text
PROPOSED 12' GATE ENTRANCE
AutoCAD SHX Text
CONNECT NEW FENCE TO EXISTING
AutoCAD SHX Text
CONNECT NEW FENCE TO EXISTING
AutoCAD SHX Text 850.97
AutoCAD SHX Text 850.32
AutoCAD SHX Text 851.20
AutoCAD SHX Text 851.32
AutoCAD SHX Text 850.82
AutoCAD SHX Text
1,512 S.F. ASPHALT EXPANSION AREA
AutoCAD SHX Text N
AutoCAD SHX Text
MAGNETIC
AutoCAD SHX Text
TANK
AutoCAD SHX Text F
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text Fire
AutoCAD SHX Text Fire
AutoCAD SHX Text
NO PARKING
AutoCAD SHX Text Fire
AutoCAD SHX Text Shed
AutoCAD SHX Text Fire
AutoCAD SHX Text Conn
AutoCAD SHX Text
%%UPARKING
AutoCAD SHX Text H
AutoCAD SHX Text Salt
AutoCAD SHX Text (Location Approximate)
AutoCAD SHX Text Trans- former
AutoCAD SHX Text Edge of conduit duct bank
AutoCAD SHX Text Ex. Water Line "3-5' Deep"
AutoCAD SHX Text Ex. Electric Line "5-7' Deep"
AutoCAD SHX Text Ex. Building 11
AutoCAD SHX Text Ex. Pump House
AutoCAD SHX Text Ex. Building 6
AutoCAD SHX Text Underground Storm Water Retention Area
AutoCAD SHX Text Ex. Communications Lines As Shown On VA Mapping (Not Field Verified)
AutoCAD SHX Text Ex. Generators
AutoCAD SHX Text Ex. Electric Line As Shown On VA Mapping (Not Field Verified)
AutoCAD SHX Text Ex. Gas Regulator Set
AutoCAD SHX Text Ex. Water Tank
AutoCAD SHX Text Ex. Storm Pipe As Shown On VA Plans (Not Field Verified)
AutoCAD SHX Text Ex. Gas Lines 1'-2' Deep
AutoCAD SHX Text
(TO BE REMOVED)
AutoCAD SHX Text Ex. Unknown Utility Lines (Assumed Electric)
AutoCAD SHX Text Ex. Generator Connection Cabinet
AutoCAD SHX Text Ex. Above Ground Gas Lines, Valves, Regulators and Generator Feeds
AutoCAD SHX Text Ex. Light Mast On Fence
AutoCAD SHX Text Ex. Water Line 3'-4' Deep
AutoCAD SHX Text Ex. Electric Line 5' Deep
AutoCAD SHX Text Ex. Electric Lines 1'-2' Deep
AutoCAD SHX Text Ex Window Well Not Field Verified
AutoCAD SHX Text Ex. Enclosed Structure Not Field Verified
AutoCAD SHX Text Seams In Pavement
AutoCAD SHX Text Seams In Pavement
AutoCAD SHX Text Ex. Unknown Utility Lines (Assumed Electric)
AutoCAD SHX Text Ex. Fuel Tank
AutoCAD SHX Text
(TO BE REMOVED)
AutoCAD SHX Text Ex. Trees
AutoCAD SHX Text
(TO BE PROTECTED WITH FILTREXX GROSOXX BERM DURING CONSTRUCTION)
AutoCAD SHX Text Ex. Building 12
AutoCAD SHX Text Ex. 8' Steel Slat Fence
AutoCAD SHX Text Ex. 8' Steel Slat Fence
AutoCAD SHX Text Ex. Gasline
AutoCAD SHX Text
(TO BE REMOVED)
AutoCAD SHX Text Ex. Electrical Duct Bank
AutoCAD SHX Text
(TO BE ABANDONED)
AutoCAD SHX Text Ex. Electrical Duct Bank
AutoCAD SHX Text Ex. Electrical Line
AutoCAD SHX Text
(TO BE REMOVED)
AutoCAD SHX Text Ex. Electrical Line
AutoCAD SHX Text
(TO BE REMOVED)
AutoCAD SHX Text Existing Underground Electric w/ Manhole
AutoCAD SHX Text Existing Underground Telephone
AutoCAD SHX Text Existing Waterline
AutoCAD SHX Text Existing Gas Line
AutoCAD SHX Text Existing Storm Sewer w/ Inlet
AutoCAD SHX Text S
AutoCAD SHX Text Existing Sanitary Sewer w/ Manhole
AutoCAD SHX Text Existing Fire Line w/ Fire Alarm Junction Box
AutoCAD SHX Text F
AutoCAD SHX Text Existing Overhead Utility Line w/ Pole
AutoCAD SHX Text Existing Underground Electric Ductbank
AutoCAD SHX Text Existing Sign
AutoCAD SHX Text Existing Fire Hydrant
AutoCAD SHX Text Existing Steam Line
AutoCAD SHX Text Existing Light Pole
AutoCAD SHX Text Existing Tree
AutoCAD SHX Text Existing Bush
AutoCAD SHX Text Existing Treeline
AutoCAD SHX Text Existing Building
AutoCAD SHX Text Existing Fenceline
AutoCAD SHX Text
EXISTING FEATURES LEGEND
AutoCAD SHX Text
PROPOSED FEATURES LEGEND
AutoCAD SHX Text Existing Property Line
AutoCAD SHX Text Existing Property Line Adjoiner
AutoCAD SHX Text
PROPOSED EDGE OF PAVEMENT
AutoCAD SHX Text
PROPOSED FENCE / TYPE
AutoCAD SHX Text PROPOSED MINOR CONTOURS W/ ELEVATION (1's & 2's)
AutoCAD SHX Text PROPOSED MAJOR CONTOURS W/ ELEVATION (5's & 10's)
AutoCAD SHX Text
EXISTING BUILDING TO BE REMOVED
AutoCAD SHX Text
DEMOLITION FEATURES LEGEND
AutoCAD SHX Text
18" FILTREXX GROSOXX TREE WELL PROTECTION BERM
AutoCAD SHX Text
EXISTING FENCELINE TO BE REMOVED
AutoCAD SHX Text
PROPOSED SPOT ELEVATION
AutoCAD SHX Text 69.87
AutoCAD SHX Text
EXISTING UNDERGROUND ELECTRIC LINE TO BE REMOVED
AutoCAD SHX Text
EXISTING GAS LINE TO BE REMOVED
AutoCAD SHX Text
PLAN ABBREVIATIONS LEGEND
AutoCAD SHX Text CO = CLEAN-OUT FOR UNDERGROUND PIPE DC = DEPRESSED CURB D.I.P. = DUCTILE IRON PIPE EX = EXISTING FFE = FINISHED FLOOR ELEVATION GM = GAS METER HDPEP = HIGH DENSITY POLYETHYLENE PIPE H.P. = HIGH POINT ELEVATION INV. = INVERT ELEVATION LF = LINEAR FEET MH = MANHOLE PR = PROPOSED RB = RECORD BOOK TBR = TO BE REMOVED TC = TOP OF CASTING TG = TOP OF GRATE
AutoCAD SHX Text 1 inch = 20 ft.
AutoCAD SHX Text
( IN FEET )
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text %%uGENERAL NOTES
AutoCAD SHX Text
1. All temporary Erosion and Sedimentation measures shall be in accordance with Sections 01 57 19, 31 20 00 All temporary Erosion and Sedimentation measures shall be in accordance with Sections 01 57 19, 31 20 00 and 32 90 00. 2. All site demolition shall be in accordance with sections 02 41 00 and 22 05 11 Para 3.6C. All site demolition shall be in accordance with sections 02 41 00 and 22 05 11 Para 3.6C. 3. Trench backfill compaction requirements shall be per section 31 20 00. Trench backfill compaction requirements shall be per section 31 20 00. 4. Contractor shall hand dig all excavation within six feet of any known utilities. Contractor shall hand dig all excavation within six feet of any known utilities. 5. All turf work shall be in accordance with sections 31 20 00 and 32 90 00. All turf work shall be in accordance with sections 31 20 00 and 32 90 00. 6. The contractor is fully responsible for verifying and locating all underground utilities within the work area and The contractor is fully responsible for verifying and locating all underground utilities within the work area and shall provide utility location service prior to construction. The contractor shall verify the locations of manholes, inlets, valves, inverts, etc. depicted upon these plans. The contractor (with prior VA approval) shall test pit existing utilities as deemed necessary within the limits of construction to verify the exact location and depth, as required. Any noted discrepancies shall be reported to PennTerra Engineering, Inc.
AutoCAD SHX Text
M-R PROJECT NO: 0517-0002
CIVIL
DETAILS
CS501
DJLJRS
562-21-708
SITE
NO. DESCRIPTION DATE
VA FORM 08-6231
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
321 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
A
C
D
E
F
Civil Engineering:
PENNTERRA ENGINEERING, INC.
2023-07-12
BID DOCUMENTS
NOT FOR CONSTRUCTION
Double gate Arrangement
16" [4.1mm]
TYPICAL
3" [76.2mm]
(Latch Clearance) Ameristar Standard
Leaf Widths 2" [50.8mm] (Hinge Clearance)
Over all Out to Out .2
2" [50.8mm] (Hinge Clearance)
4" [32.4mm]
16" [17.2mm]
7'
6'-6" Min.
Footing depth
2" [50.8mm]
2" [50.8mm]
Pale welded to rail
Gate Rail
Values shown are nominal and not to be used for installation purposes. See product specification for installation requirements.
Weld on Box Hinge
3" I-BEAM
Gate Upright 2" [50.8mm] x 12 ga.
Gate Rail 2" [50.8mm] x 12 ga.
4" [69.9mm] Pale
(.075 [1.69mm] wall)
8'
6'-6"
8' 7'
12" DIA. PIER
12" DIA. PIER
AutoCAD SHX Text
4 1/2" - SUPERPAVE WMA BASE COURSE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
1 1/2" - SUPERPAVE WMA WEARING COURSE
AutoCAD SHX Text
4 1/2" - NO. 2A STONE SUB-BASE
AutoCAD SHX Text
WELL COMPACTED SUBGRADE
AutoCAD SHX Text
WEARING SURFACE:
AutoCAD SHX Text
SUPERPAVE ASPHALT MIXTURE DESIGN, WMA WEARING COURSE
AutoCAD SHX Text
PG 64-22, < 0.3 MILLION ESAL'S, 9.5 MM MIX,
AutoCAD SHX Text
1-1/2" DEPTH, SRL-M
AutoCAD SHX Text
BASE COURSE SURFACE:
AutoCAD SHX Text
SUPERPAVE ASPHALT MIXTURE DESIGN, WMA BASE COURSE
AutoCAD SHX Text
PG 64-22, < 0.3 MILLION ESAL'S, 25.0 MM MIX,
AutoCAD SHX Text
4 1/2" DEPTH
AutoCAD SHX Text
STANDARD PAVEMENT SECTION
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
TEMPORARY E&S CONTROL - COMPOST FILTER SOCK DETAIL
AutoCAD SHX Text
WATER FLOW
AutoCAD SHX Text
PLAN VIEW
AutoCAD SHX Text
UPSLOPE
AutoCAD SHX Text
DOWNSLOPE
AutoCAD SHX Text
AREA TO BE PROTECTED
AutoCAD SHX Text
10' LINEAR SPACING (TYP.)
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
1. All material to meet EPA compost filter sock specifications. specifications. specifications. 2. Silt sock compost/soil/rock/seed fill to meet application requirements. 3. Silt socks depicted are for use on minimal slopes. Greater slopes may require larger silt socks per the Engineer. 4. Compost material to be dispersed on site, as determined by Engineer.
AutoCAD SHX Text
COMPOST FILTER SOCK
AutoCAD SHX Text
DISTURBED AREA
AutoCAD SHX Text
COMPOST FILTER SOCK
AutoCAD SHX Text
DISTURBED AREA
AutoCAD SHX Text
AREA TO BE PROTECTED
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text 3"-4"
AutoCAD SHX Text
(12" TYP.)
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
BLOWN/PLACED FILTER MEDIA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING CONTOUR
AutoCAD SHX Text 2"x2" WOODEN STAKE
AutoCAD SHX Text
PLACED 10' O.C.
AutoCAD SHX Text 2"x2" WOODEN STAKE
AutoCAD SHX Text
PLACED 10' O.C.
AutoCAD SHX Text Material Type
AutoCAD SHX Text Material Characteristics
AutoCAD SHX Text 3 mil HDPE
AutoCAD SHX Text 5 mil HDPE
AutoCAD SHX Text 5 mil HDPE
AutoCAD SHX Text Multi-Filament Polypropylene (MFPP)
AutoCAD SHX Text Heavy Duty Multi-Filament Polypropelene (HDMFPP)
AutoCAD SHX Text Photo- degradable
AutoCAD SHX Text Bio- degradable
AutoCAD SHX Text Photo- degradable
AutoCAD SHX Text Photo- degradable
AutoCAD SHX Text Photo- degradable
AutoCAD SHX Text Sock Diameters
AutoCAD SHX Text 12" 18"
AutoCAD SHX Text 12" 18" 24" 32"
AutoCAD SHX Text 12" 18" 24" 32"
AutoCAD SHX Text 12" 18" 24" 32"
AutoCAD SHX Text 12" 18" 24" 32"
AutoCAD SHX Text Mesh Opening
AutoCAD SHX Text 3/8"
AutoCAD SHX Text 1/8"
AutoCAD SHX Text 3/8"
AutoCAD SHX Text 3/8"
AutoCAD SHX Text 3/8"
AutoCAD SHX Text Tensile Strength
AutoCAD SHX Text 26 psi
AutoCAD SHX Text 26 psi
AutoCAD SHX Text 44 psi
AutoCAD SHX Text 202 psi
AutoCAD SHX Text Ultraviolet Stability % Original Strength (ASTM G-155)
AutoCAD SHX Text 23% at 1000 hr.
AutoCAD SHX Text 23% at 1000 hr.
AutoCAD SHX Text 100% at 1000 hr.
AutoCAD SHX Text 100% at 1000 hr.
AutoCAD SHX Text Minimum Functional Longevity
AutoCAD SHX Text 6 months
AutoCAD SHX Text 9 months
AutoCAD SHX Text 6 months
AutoCAD SHX Text 1 year
AutoCAD SHX Text 2 years
AutoCAD SHX Text Two-Ply Systems
AutoCAD SHX Text Inner Containment Netting
AutoCAD SHX Text HDPE biaxial net
AutoCAD SHX Text Continuously wound
AutoCAD SHX Text Fusion-welded junctures
AutoCAD SHX Text 3/4"x3/4" Max. aperture size
AutoCAD SHX Text Composite Polypropylene Fabric (Woven layer and non-woven fleece mechanically fused via needle punch)
AutoCAD SHX Text 3/16" Max. aperture size
AutoCAD SHX Text Sock fabrics composed of burlap may be used on projects lasting 6 months or less.
AutoCAD SHX Text TABLE 4.1 Compost Sock Fabric Minimum Specifications
AutoCAD SHX Text Outer Filtration Mesh
AutoCAD SHX Text Organic Matter Content
AutoCAD SHX Text Organic Portion
AutoCAD SHX Text pH
AutoCAD SHX Text Moisture Content
AutoCAD SHX Text Particle Size
AutoCAD SHX Text Soluble Salt Concentration
AutoCAD SHX Text 25%-100% (dry weight basis)
AutoCAD SHX Text Fibrous and elongated
AutoCAD SHX Text 5.5-8.5
AutoCAD SHX Text 30%-60%
AutoCAD SHX Text 30% - 50% pass through 3/8" sieve
AutoCAD SHX Text
5.0 dS/m (mmhos/cm) Maximum
AutoCAD SHX Text TABLE 4.2 Compost Standards
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
IMPASSE II ANTI-SCALE STEEL PANEL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
3" I-BEAM FOR 3R EXT 8'T IMPASSE II
AutoCAD SHX Text
M-R PROJECT NO: 0517-0002
AutoCAD SHX Text NOTES: 1. SOXX SHALL BE USED TO PROTECT EXISTING TREE TRUNKS FROM FILL PLACEMENT. 2. SOXX SHALL BE FILLED WITH FILTREXX ENGINEERED SOIL (OR EQUAL) AND INCLUDE THE TURF GRASS PERMANENT SEEDING MIXTURE. 3. PRIOR TO PLACING FILL AROUND EXISTING TREES, INSTALL SOXX FILLED WITH MEDIA AND SEEDING OFFSET A MINIMUM OF 12" FROM THE TREE TRUNK.
AutoCAD SHX Text
18" WEIGHTED, SEEDED
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text 2"x2" WOODEN STAKE
AutoCAD SHX Text
PLACED 10' O.C.
AutoCAD SHX Text
FILTREXX GROSOXX
AutoCAD SHX Text
18" FILTREXX GROSOXX TREE WELL PROTECTION BERM
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text NOTES: 1.) Post size depends on fence height, weight and wind loads. See IMPASSE post sizing chart. post sizing chart. 2.) See Ameristar gate table for standard out to outs. Custom gate openings available for special out to out/leaf widths. 3.) Additional styles of gate hardware are available on request. This could change the Latch & Hinge Clearance. 4.) Third rail optional. (Some heights noted require the third rail.)
AutoCAD SHX Text
NOT TO SCALE
IMPASSE II STRONGHOLD GATE DETAIL
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
N/A
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
ABBREVIATIONS & NOTES
S-001
DSER
EXISTING SWITCHGEAR BUILDING #11
EXISTING UNDERGROUND FUEL TANK
BUILDING #12
MECHANICAL YARD
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
SITE
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
KEYPLAN
AREA OF
WORK
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
DEMOLITION SITE PLAN
12-SD101
RPER
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
BUILDING #12 DEMOLITION
SECTIONS & ELEVATIONS
12-SD201
W
W
W PUMP HOUSE
EXISTING
SWITCHGEAR BUILDING #11
ROOF
EXISTING
WATER TANK
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
SITE
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
KEYPLAN
AREA OF
WORK
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
SITE PLAN
SS101
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
SITE
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
KEYPLAN
AREA OF
WORK
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
ENLARGED PARTIAL SITE PLAN
SS401
MEDICAL
GAS
STOR
2D50B
OXYGEN
STOR
2D50C
GAS STORAGE
2D38 (2E336)
LOADING DOCK
2D50
ELECTRICAL
EE200
OFFICE SUPPLY STORAGE
2D33
HOUSEKEEPING/E.M.S.
STORAGE 2D39
WAREHOUSE
2D28 (2E300)
SURGICAL STORAGE
2D34
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
KEYPLAN
AREA OF
WORK
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
PARTIAL FRAMING PLAN
BUILDING #01 - 2ND FLOOR
01-SF121
BC06-1
BC0
B C -1
BC07A-1
BC10A-1
ELECTRIC
BC11 (NB-59A)
FEC
PHONE
BC
J J
BC06-1
BC0
B C -1
BC07A-1
ELECTRIC
BC11 (NB-59A)
PHONE
BC1
2N214-1
2N216-1
2N215-1 OF
CORRIDOR
2C4 (2N210)
OF
ELEC
2C16
ELEC
2C14
R
2N214-1
2N216-1
2N215-1 OF
CORRIDOR
2C4 (2N210)
OF
ELEC
2C16
ELEC
2C14
J
J
SP1W465-1
ROOM
1W458)
(1W235)
ELECTRICAL
1B17
TOILET 1B15A
(1W458A)
SP1W465-1
M ROOM
(1W458)
(1W235)
ELECTRICAL
1B17
TOILET 1B15A
(1W458A)
R
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
KEYPLAN
AREA OF
WORK
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
ENLARGED PLANS
BLDG #01 - BASEMENT, 1ST & 2ND FLR
S-401
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
N/A
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
SECTIONS & DETAILS
S-501
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
N/A
Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
STRUCTURAL
SECTIONS & DETAILS
S-502 on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
N/A Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
ELECTRICAL
LEGENDS, NOTES, &
ABBREVIATIONS
E-001
DRRLIB
AutoCAD SHX Text
FUSE WITH RATING
AutoCAD SHX Text
MOLDED CASE CIRCUIT BREAKER
AutoCAD SHX Text
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
AutoCAD SHX Text
TRANSFORMER, DELTA CONNECTION
AutoCAD SHX Text
TRANSFORMER, SINGLE LINE
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
PULL BOX
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
GENERATOR, POWER
AutoCAD SHX Text
DISCONNECT SWITCH, FUSED
AutoCAD SHX Text
DISCONNECT SWITCH, UNFUSED
AutoCAD SHX Text
STARTER, COMBINATION WITH DISCONNECT SWITCH
AutoCAD SHX Text
STARTER OR MOTOR CONTROLLER
AutoCAD SHX Text
METER
AutoCAD SHX Text
WATT-HOUR METER
AutoCAD SHX Text
TRANSFORMER, PLAN
AutoCAD SHX Text
MOTOR
AutoCAD SHX Text
TRANSFORMER, WYE CONNECTION
AutoCAD SHX Text
PUSH BUTTON
AutoCAD SHX Text
RECEPTACLE, DUPLEX
AutoCAD SHX Text
RECEPTACLE, DUPLEX ISOLATED GROUND
AutoCAD SHX Text
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
AutoCAD SHX Text
RECEPTACLE, QUADRAPLEX
AutoCAD SHX Text
RECEPTACLE, DUPLEX W/ GROUND FAULT CIRCUIT INTERRUPTER & ISOLATED GROUND
AutoCAD SHX Text
RECEPTACLE, QUADRAPLEX ISOLATED GROUND
AutoCAD SHX Text RECEPTACLE, SPECIAL PURPOSE A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R. B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R. C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R. D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R. E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R. F = 208V, 30A, 3 PHASE, 3-POLE, 4W, NEMA 15-30R. G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R. H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
AutoCAD SHX Text ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.
AutoCAD SHX Text
ELECTRICAL SYMBOLS
AutoCAD SHX Text
RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
AutoCAD SHX Text
DP#__
AutoCAD SHX Text
DISTRIBUTION PANEL
AutoCAD SHX Text
LP#__/PP#__
AutoCAD SHX Text
LIGHTING OR POWER PANEL
AutoCAD SHX Text
PANELBOARD CABINET, FLUSH MOUNTED
AutoCAD SHX Text
PANELBOARD CABINET, SURFACE MOUNTED
AutoCAD SHX Text RECEPTACLE, DUPLEX (DASHED LINE INDICATES FLOOR MOUNTED, TYPICAL ALL TYPES OF RECEPTACLES)
AutoCAD SHX Text
MULTIPLE KEY NOTES APPLYING TO THE SAME ITEM
AutoCAD SHX Text
CR
AutoCAD SHX Text
ST
AutoCAD SHX Text
CONTROL RELAY; COIL RELAY
AutoCAD SHX Text
SHUNT-TRIP COIL
AutoCAD SHX Text
TRANSFORMER, SINGLE LINE
AutoCAD SHX Text
PRIMARY
AutoCAD SHX Text
SECONDARY
AutoCAD SHX Text
TRANSFORMER SIZE
AutoCAD SHX Text
INDICATES EQUIPMENT TO BE DEMOLISHED
AutoCAD SHX Text
DWM
AutoCAD SHX Text
DIGITAL POWER METER
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
POTENTIAL TRANSFORMER
AutoCAD SHX Text BRANCH CIRCUIT HOMERUN. HALF-ARROWS INDICATE NUMBER OF CIRCUITS. ONE SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN; NOT SHOWN
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text J
AutoCAD SHX Text G
AutoCAD SHX Text
HP
AutoCAD SHX Text
CIRCUIT #
AutoCAD SHX Text
RECEPTACLE, DUPLEX - EMERGENCY
AutoCAD SHX Text
RECEPTACLE, QUADRAPLEX - EMERGENCY
AutoCAD SHX Text
RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER & ISOLATED GROUND
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
WH
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EMERGENCY POWER OFF
AutoCAD SHX Text
LIGHTING OR POWER PANEL, SINGLE LINE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 112.5
AutoCAD SHX Text
ENCLOSED CIRCUIT BREAKER
AutoCAD SHX Text ???A/3P
AutoCAD SHX Text
ENCLOSED CIRCUIT BREAKER, SINGLE LINE
AutoCAD SHX Text
ENCLOSED CIRCUIT BREAKER
AutoCAD SHX Text
RECEPTACLE, DUPLEX - CEILING
AutoCAD SHX Text
RECEPTACLE, SIMPLEX - EMERGENCY
AutoCAD SHX Text
RECEPTACLE, SIMPLEX
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EP101
AutoCAD SHX Text
KEY NOTE SYMBOL
AutoCAD SHX Text
DETAIL IDENTIFIER DETAIL # DRAWING # (WHERE DETAIL IS FOUND)
AutoCAD SHX Text
CEILING MOUNTED, SINGLE CONVENIENCE OUTLET
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
OR
AutoCAD SHX Text
ELECTRICAL ABBREVIATIONS
AutoCAD SHX Text
TELE/DATA OUTLET
AutoCAD SHX Text
TELEPHONE OUTLET
AutoCAD SHX Text
DATA OUTLET
AutoCAD SHX Text
AUX/DATA/COMMUNICATION SYMBOLS
AutoCAD SHX Text
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
AutoCAD SHX Text SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND. MTD. 7'-6" AFF UNLESS MTD. 7'-6" AFF UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
TV
AutoCAD SHX Text
TELEVISION OUTLET
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text
SWITCH BLANK = SINGLE POLE M = MOTOR RATED
AutoCAD SHX Text
AutoCAD SHX Text
FIRE ALARM SYMBOLS
AutoCAD SHX Text
LIGHTING SYMBOLS
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text
FACP
AutoCAD SHX Text
CM
AutoCAD SHX Text
FS
AutoCAD SHX Text
RA
AutoCAD SHX Text
NAC
AutoCAD SHX Text H
AutoCAD SHX Text
SD
AutoCAD SHX Text
TS
AutoCAD SHX Text
PS
AutoCAD SHX Text C
AutoCAD SHX Text
CD
AutoCAD SHX Text
SS
AutoCAD SHX Text C
AutoCAD SHX Text
CD
AutoCAD SHX Text
MM
AutoCAD SHX Text R
AutoCAD SHX Text
DH
AutoCAD SHX Text
DR
AutoCAD SHX Text
RTS
AutoCAD SHX Text
FATC
AutoCAD SHX Text FIRE ALARM CONTROL PANEL (MOUNT 6'-0" ABOVE FINISHED FLOOR TO TOP) PROVIDED WITH BACK-UP BATTERIES RATED FOR 24 HOUR MIN. SERVICE / 5 MINUTES IN ALARM MODE
AutoCAD SHX Text
FIRE ALARM TERMINAL CABINET (MOUNT 5'-0" ABOVE FINISHED FLOOR TO TOP)
AutoCAD SHX Text
FIRE ALARM REMOTE ANNUNIATOR (MOUNT 5'-0" ABOVE FINISHED FLOOR TO TOP)
AutoCAD SHX Text NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL (MOUNT 6'-0" ABOVE FINISHED FLOOR TO TOP) PROVIDED WITH BACK-UP BATTERIES RATED FOR 24 HOUR MIN. SERVICE / 5 MINUTES IN ALARM MODE
AutoCAD SHX Text
MANUAL PULLSTATION (MOUNT 48" ABOVE FINISHED FLOOR TO TOP OF DEVICE)
AutoCAD SHX Text DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS: R/T = COMBINATION F = FIXED TEMP. RISE (135°) F = FIXED TEMP. RISE (135°) R/C = RATE COMPENSATION R = RATE OFR = RATE OF
AutoCAD SHX Text DETECTOR; LETTER INDICATES AS FOLLOWS: BLANK = PHOTOELECTRIC SMOKE DETECTOR H = HEAT I = IONIZATION IH = IONIZATION AND HEAT IP = IONIZATION AND PHOTOELECTRIC PH = PHOTOELECTRIC AND HEAT IPH = IONIZATION, PHOTOELECTRIC, AND HEAT
AutoCAD SHX Text DETECTOR, SMOKE, FOR DUCT (FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR; WIRED BY THE ELECTRICAL CONTRACTOR)
AutoCAD SHX Text SPRINKLER ALARM VALVE TAMPER SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)
AutoCAD SHX Text SPRINKLER ALARM VALVE WATER FLOW SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)
AutoCAD SHX Text SPRINKLER ALARM PRESSURE SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)
AutoCAD SHX Text AUTO SYNC STROBE UNIT WITH SELECTABLE CANDELA ADA COMPLIANT (MOUNT 80" ABOVE FINISHED FLOOR OR 6" BELOW FINISHED CEILING TO TOP OF DEVICE) BLANK = WALL MOUNTED C = CEILING P = PENDANT C = CEILING P = PENDANT P = PENDANT CD = CANDELA LEVEL
AutoCAD SHX Text FIRE SPEAKER UNIT BLANK = WALL MOUNTED C = CEILING P = PENDANTC = CEILING P = PENDANTP = PENDANT
AutoCAD SHX Text FIRE SPEAKER STROBE (AUTO SYNC) UNIT WITH SELECTABLE CANDELA; ADA COMPLIANT (MOUNT 80" ABOVE FINISHED FLOOR OR 6" BELOW FINISHED CEILING TO TOP OF DEVICE) BLANK = WALL MOUNTED C = CEILING P = PENDANT C = CEILING P = PENDANT P = PENDANT CD = CANDELA LEVEL
AutoCAD SHX Text
CONTROL MODULE
AutoCAD SHX Text
MONITORING MODULE
AutoCAD SHX Text
120VAC, 20A RELAY IN NEMA 1 ENLCOSURE
AutoCAD SHX Text
MAGNETIC DOOR HOLDER
AutoCAD SHX Text
ELECTROMAGNETIC DOOR RELEASE OR DOOR RELEASE RELAY
AutoCAD SHX Text
DUCT SMOKE DETECTOR REMOTE TEST/TEST SWITCH
AutoCAD SHX Text
END OF LINE RESISTOR
AutoCAD SHX Text CARD ACCESS READER; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL H-ELEVATOR HALL CALL M-MAG STRIP P-PROXIMITY S-SMART CARD P-PROXIMITY S-SMART CARD S-SMART CARD T-TOKEN
AutoCAD SHX Text ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKEH-HYBRID L-LATCH SET M-MAGNETIC S-STRIKEL-LATCH SET M-MAGNETIC S-STRIKEM-MAGNETIC S-STRIKES-STRIKE
AutoCAD SHX Text MOTION DETECTOR; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC IR-INFRARED M-MICROWAVE U-ULTRASONIC M-MICROWAVE U-ULTRASONIC U-ULTRASONIC X-REQUEST-FOR-EXIT
AutoCAD SHX Text SECURITY ACCESS, VIDEO CAMERA WITH LENS M = MOTION DETECTOR PZ = MOTION DETECTOR WITH PAN AND ZOOM PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM
AutoCAD SHX Text
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
AutoCAD SHX Text PUSH BUTTON; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE D-DURESS P-PANIC R-DOOR RELEASE P-PANIC R-DOOR RELEASE R-DOOR RELEASE X-REQUEST-FOR-EXIT
AutoCAD SHX Text
SECURITY SYMBOLS
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text 40%%d
AutoCAD SHX Text M
AutoCAD SHX Text
PTZ
AutoCAD SHX Text
AIR TERMINAL
AutoCAD SHX Text
WIRELESS ACCESS POINT
AutoCAD SHX Text
DENOTES MOUNTING HEIGHT OF +60" A.F.F. TYPICAL ALL TYPES OF OUTLETS
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL SYMBOLS
AutoCAD SHX Text FLOORBOX. FB1 = 2 COMPARTMENT FLOOR BOX WITH (1) QUAD RECEPTACLE AND (1) QUAD DATA FB2 = 3 COMPARTMENT FLOOR BOX WITH (1) QUAD RECEPTACLE, (1) QUAD DATA AND A 2-1/2" CONDUIT FOR RGB AV
AutoCAD SHX Text
FB1
AutoCAD SHX Text
DOWN CONDUCTOR AT AIR TERMINAL
AutoCAD SHX Text
CONDUCTOR DROP FROM HIGHER ROOF TO LOWER ROOF
AutoCAD SHX Text SWITCH a = (LOWER CASE) LIGHT CONTROLLED BY TAGGED SWITCH = (LOWER CASE) LIGHT CONTROLLED BY TAGGED SWITCH 2 = 2 POLE = 2 POLE 3 = 3 WAY = 3 WAY 4 = 4 WAY = 4 WAY D = DIMMER = DIMMER F = FUSED SWITCH = FUSED SWITCH IL = ILLUMINATED TOGGLE = ILLUMINATED TOGGLE ILLUMINATED TOGGLE K = KEY OPERATED = KEY OPERATED L = LOCK = LOCK LM = LOW VOLTAGE MASTER = LOW VOLTAGE MASTER LV = LOW VOLTAGE = LOW VOLTAGE M = MANUAL MOTOR STARTING = MANUAL MOTOR STARTING MC = MOMENTARY CONTACT = MOMENTARY CONTACT MP = MOTOR SNAP W/PILOT LIGHT (THERMAL TYPE) = MOTOR SNAP W/PILOT LIGHT (THERMAL TYPE) OS = OCCUPANCY SENSOR (W/ MANUAL OVERRIDE) = OCCUPANCY SENSOR (W/ MANUAL OVERRIDE) P = WITH PILOT LIGHT = WITH PILOT LIGHT PB = PUSH BUTTON STATION = PUSH BUTTON STATION RC = REMOTE CONTROL = REMOTE CONTROL WP = WEATHER PROOF = WEATHER PROOF X = EXPLOSION PROOF= EXPLOSION PROOF
AutoCAD SHX Text
OCCUPANCY SENSOR - WALL MOUNTED
AutoCAD SHX Text
OCCUPANCY SENSOR - CEILING MOUNTED
AutoCAD SHX Text
EMERGENCY LIGHT WITH 2 HEADS (90 MINUTE BATTERY)
AutoCAD SHX Text A
AutoCAD SHX Text EXIT SIGN: ARROW DIRECTION INDICATED ON PLANS. SINGLE SHADING INDICATES SINGLE FACE OR 2 SHADED AREAS INDICATES DOUBLE FACED UNIT.
AutoCAD SHX Text
PX-##
AutoCAD SHX Text LIGHTING FIXTURE: UPPER CASE LETTER ABOVE FIXTURE DENOTES FIXTURE TYPE IN LIGHTING FIXTURE SCHEDULE. UPPER CASE LETTERS BELOW INDICATES PANEL AND/OR CIRCUIT POWERING FIXTURE. LOWER CASE LETTERS INDICATE SWITCH LEG.
AutoCAD SHX Text HALF SHADED FIXTURE INDICATES FIXTURE IS ON EMERGENCY CIRCUIT OR NIGHT LIGHT (SEE FIXTURE SCHEDULE)
AutoCAD SHX Text
EMERGENCY COMBO LIGHT/SIGN WITH 2 HEADS (90 MINUTE BATTERY)
AutoCAD SHX Text
EMERGENCY LIGHT REMOTE DUAL HEAD
AutoCAD SHX Text
EMERGENCY LIGHT REMOTE SINGLE HEAD
AutoCAD SHX Text
PC
AutoCAD SHX Text
PHOTOCELL
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
WAP
AutoCAD SHX Text
INDICATES POINT OF DISCONNECT
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
CEILING - HEIGHT VARIES
AutoCAD SHX Text
ALIGN WHEN MOUNTED ON SAME WALL
AutoCAD SHX Text
LIGHT SWITCH OR DIMMER
AutoCAD SHX Text
FIRE ALARM PULL STATION
AutoCAD SHX Text
TELEPHONE OR DATA JACK
AutoCAD SHX Text MOUNT STROBE, SPEAKER/STOBE OR HORN/STROBE DEVICE 80" (MIN), 96" (MAX.) AFF TO STROBE LENS.
AutoCAD SHX Text
WALL MOUNTED TELEPHONE
AutoCAD SHX Text RECEPTACLE: ABOVE COUNTER REFER TO ARCH DWGS FOR HEIGHT. (GFCI TYPE IF WITHIN 6' OF WATER SOURCE)
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL DEVICE MOUNTING HEIGHTS
AutoCAD SHX Text
ALL DIMENSIONS SHOWN ARE TYPICAL UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
NTS
AutoCAD SHX Text
WALL MOUNTED TV/MONITOR. REFER TO ARCH DWGS FOR HEIGHT.
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
COUNTERTOP
+ DEVICE MOUNTED ABOVE STD DEVICE MOUNTED ABOVE STD HEIGHT. REFER TO ARCH. PLANS FOR ELEVATION 1PH SINGLE-PHASE SINGLE-PHASE 1P SINGLE POLE SINGLE POLE 2/C TWO-CONDUCTOR TWO-CONDUCTOR 3/C THREE-CONDUCTOR THREE-CONDUCTOR 3PH THREE-PHASE THREE-PHASE 4/C FOUR-CONDUCTOR FOUR-CONDUCTOR 4W FOUR-WIRE FOUR-WIRE A/C AIR CONDITIONING UNIT AIR CONDITIONING UNIT A/E ARCHITECT/ENGINEER ARCHITECT/ENGINEER AC ALTERNATING CURRENT ALTERNATING CURRENT AF AMPERE FRAME OR AMP FUSE AMPERE FRAME OR AMP FUSE AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE AH AMPERE HOUR AMPERE HOUR AHJ AUTHORITY HAVING JURISDICTION AUTHORITY HAVING JURISDICTION AIC AMPERE INTERRUPTING CAPACITY AMPERE INTERRUPTING CAPACITY ALT ALTERNATE ALTERNATE AMB AMBIENT AMBIENT AMP AMPERE AMPERE ASC AMPS SHORT CIRCUIT AMPS SHORT CIRCUIT AT AMPERE TRIP AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH BAT BATTERY BATTERY BIL BASIC INSULATION LEVEL BASIC INSULATION LEVEL BLDG BUILDING BUILDING BRKR BREAKER BREAKER BYP BY PASS BY PASS C CONDUIT CONDUIT CAB CABINET CABINET CALC CALCULATE CALCULATE CAP CAPACITY CAPACITY CAT CATALOG CATALOG CATV COMMUNITY ANTENNA TELEVISION COMMUNITY ANTENNA TELEVISION CCTV CLOSED CIRCUIT TELEVISION CLOSED CIRCUIT TELEVISION cd CANDELA CANDELA CD CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS CF CONTRACTOR FURNISHED CONTRACTOR FURNISHED CKT CIRCUIT CIRCUIT CLF CURRENT LIMITING FUSE CURRENT LIMITING FUSE CLG CEILING CEILING CMU CONCRETE MASONRY UNIT CONCRETE MASONRY UNIT COMM COMMUNICATION COMMUNICATION COMPT COMPARTMENT COMPARTMENT CONC CONCRETE CONCRETE CONT CONTINUE CONTINUE CONTR CONTRACTOR CONTRACTOR CRI COLOR RENDERING INDEX COLOR RENDERING INDEX CT CURRENT TRANSFORMER CURRENT TRANSFORMER CTV CABLE TELEVISION CABLE TELEVISION CU COPPER COPPER CU FT CUBIC FEET CUBIC FEET (D) DEMOLISH DEMOLISH DB DECIBEL OR DIRECT BURIAL DECIBEL OR DIRECT BURIAL DC DIRECT CURRENT DIRECT CURRENT DEMO DEMOLITION DEMOLITION DIAG DIAGRAM DIAGRAM DISC DISCONNECT DISCONNECT DN DOWN DOWN DPDT DOUBLE POLE, DOUBLE THROW DOUBLE POLE, DOUBLE THROW DPST DOUBLE POLE, SINGLE THROW DOUBLE POLE, SINGLE THROW DS DISCONNECT SWITCH DISCONNECT SWITCH DWG DRAWING DRAWING (E) EXISTING EXISTING (ER) EXISTING TO BE RELOCATED EXISTING TO BE RELOCATED EC EMPTY CONDUIT EMPTY CONDUIT EG EQUIPMENT GROUND EQUIPMENT GROUND EL ELEVATION ELEVATION ELEC ELECTRIC OR ELECTRICAL ELECTRIC OR ELECTRICAL ELEV ELEVATOR ELEVATOR EMER EMERGENCY EMERGENCY EMI ELECTROMAGNETIC INTERFERENCE ELECTROMAGNETIC INTERFERENCE EMT ELECTRICAL METALLIC TUBING ELECTRICAL METALLIC TUBING ENCL ENCLOSURE ENCLOSURE EPO EMERGENCY POWER OFF EMERGENCY POWER OFF EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER EXIST EXISTING EXISTING FA FIRE ALARM FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FC FOOTCANDLE FOOTCANDLE FIXT FIXTURE FIXTURE FLA FULL LOAD AMPS FULL LOAD AMPS FLEX FLEXIBLE METALLIC CONDUIT FLEXIBLE METALLIC CONDUIT FLUOR FLUORESCENT FLUORESCENT FP FIRE PROTECTION FIRE PROTECTION FT FEET OR FOOT FEET OR FOOT FU SW FUSED SWITCH FUSED SWITCH FVNR FULL VOLTAGE NON-REVERSING FULL VOLTAGE NON-REVERSING FVR FULL VOLTAGE REVERSING FULL VOLTAGE REVERSING G OR GND GROUND OR GENERATOR GROUND OR GENERATOR GEN GENERATOR GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER HID HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE HOA HAND-OFF-AUTOMATIC HAND-OFF-AUTOMATIC HP HORSEPOWER HORSEPOWER HT HEIGHT HEIGHT HZ HERTZ HERTZ IMC INTERMEDIATE METAL CONDUIT INTERMEDIATE METAL CONDUIT IR INFRARED INFRARED J-BOX JUNCTION BOX JUNCTION BOX kV KILOVOLT KILOVOLT kVA KILOVOLT AMPERE KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE KILOVOLT AMPERE REACTIVE kW KILOWATT KILOWATT kWH KILOWATT HOUR KILOWATT HOUR kWHM KILOWATT HOUR METER KILOWATT HOUR METER LED LIGHT EMITTING DIODE LIGHT EMITTING DIODE LF LINEAR FEET (FOOT) LINEAR FEET (FOOT) LP LIGHT POLE LIGHT POLE LRA LOCKED ROTOR AMPS LOCKED ROTOR AMPS LT LIGHT LIGHT LTG LIGHTING LIGHTING LTG PNL LIGHTING PANEL LIGHTING PANEL LV LOW VOLTAGE LOW VOLTAGE MAX MAXIMUM MAXIMUM MC METAL-CLAD METAL-CLAD MCA MINIMUM CIRCUIT AMPS MINIMUM CIRCUIT AMPS MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MECH MECHANICAL MECHANICAL MH MANHOLE MANHOLE MIN MINIMUM MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MAXIMUM OVERCURRENT PROTECTION MLO MAIN LUGS ONLY MAIN LUGS ONLY MT MOUNT MOUNT MTD MOUNTED MOUNTED MTG MOUNTING MOUNTING MTS MANUAL TRANSFER SWITCH MANUAL TRANSFER SWITCH MV MEDIUM VOLTAGE MEDIUM VOLTAGE MVA MEGAVOLT-AMPERE MEGAVOLT-AMPERE MW MEGAWATT MEGAWATT NA NOT APPLICABLE NOT APPLICABLE NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEUT OR N NEUTRAL NEUTRAL NFPA NATIONAL FIRE PROTECTION NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NOT IN CONTRACT NO NORMALLY OPEN NORMALLY OPEN NTS NOT TO SCALE NOT TO SCALE OC ON CENTER ON CENTER OD OUTSIDE DIAMETER OUTSIDE DIAMETER P POLE POLE PA PUBLIC ADDRESS PUBLIC ADDRESS PB PUSHBUTTON PUSHBUTTON PC PHOTOELECTRIC CELL PHOTOELECTRIC CELL PED PEDESTAL PEDESTAL PEND PENDANT PENDANT PF POWER FACTOR POWER FACTOR PH PHASE PHASE PNL PANEL PANEL PT POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE (PLASTIC) POLYVINYL CHLORIDE (PLASTIC) PWR POWER POWER (R) REMOVE (DEMOLISH) REMOVE (DEMOLISH) (RE) RELOCATED EXISTING RELOCATED EXISTING RCP REFLECTED CEILING PLAN REFLECTED CEILING PLAN REC RECESSED RECESSED RECPT RECEPTACLE RECEPTACLE RGS RIGID GALVANIZED STEEL RIGID GALVANIZED STEEL RM ROOM ROOM RMS ROOT MEAN SQUARE ROOT MEAN SQUARE REQD REQUIRED REQUIRED SCC SHORT CIRCUIT CAPACITY SHORT CIRCUIT CAPACITY SCHED SCHEDULE SCHEDULE SD SMOKE DETECTOR SMOKE DETECTOR SF SQUARE FOOT (FEET) SQUARE FOOT (FEET) SHT SHEET SHEET SI INTERNATIONAL SYSTEM OF UNITS INTERNATIONAL SYSTEM OF UNITS SPEC SPECIFICATION SPECIFICATION SPST SINGLE POLE, SINGLE THROW SINGLE POLE, SINGLE THROW SURF SURFACE SURFACE SW SWITCH SWITCH SWBD SWITCHBOARD SWITCHBOARD SWGR SWITCHGEAR SWITCHGEAR TC TIME CLOCK TIME CLOCK TEL TELEPHONE TELEPHONE TP TWISTED PAIR TWISTED PAIR TPS TWISTED PAIR SHIELDED TWISTED PAIR SHIELDED TTB TELEPHONE TERMINAL BOARD TELEPHONE TERMINAL BOARD TV TELEVISION TELEVISION TYP TYPICAL TYPICAL UL UNDERWRITERS LABORATORY UNDERWRITERS LABORATORY UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UNINTERRUPTIBLE POWER SUPPLY UTIL UTILITY UTILITY V VOLT VOLT VA VOLT AMPERE VOLT AMPERE VAR VOLT AMPERE REACTIVE VOLT AMPERE REACTIVE VFD VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE VOLT VOLTAGE VOLTAGE W WATT WATT WH WATER HEATER WATER HEATER WP WEATHERPROOF WEATHERPROOF XFER TRANSFER TRANSFER XFMR TRANSFORMER TRANSFORMER on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER
PHASE 3
ERIE VA MEDICAL CENTER, PA
562-21-708
Project Director
2023-07-12
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
N/A Civil Engineering:
PENNTERRA ENGINEERING, INC.
M-R PROJECT NO: 0517-0002
ELECTRICAL
NOTES
E-002
DRRLIB
AutoCAD SHX Text
1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED BY THE OWNER AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN TEAM FOR THE PURPOSE OF ENGINEERING DESIGN. EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO BEGINNING INSTALLATION OR FABRICATION WORK. 1.1. DRAWINGS ARE DIAGRAMMATIC. DRAWINGS ARE DIAGRAMMATIC. 1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE DRAWINGS, OR IN THE SPECIFICATIONS, CONSULT THE ENGINEER FOR NECESSARY CLARIFICATIONS, AND CONFORM TO THOSE CLARIFICATIONS INSOFAR AS THEY ARE CONSISTENT WITH THE ORIGINAL DRAWINGS AND SPECIFICATIONS. IN NO CASE SHALL WORK PROCEED IN UNCERTAINTY. 1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE INTENT OF THE ORIGINAL DESIGN. 1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT SITE PRIOR TO STARTING WORK. 2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE EMPLOYED DIRECTLY AND INDIRECTLY BY HIM ON THE PREMISES, AND THE OWNER'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED. 2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES, APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH GIVE PROPER AND UNDERSTANDABLE WARNING TO PERSONS WITH REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION WITH THE WORK. 3. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION INCLUDING, BUT NOT LIMITED TO THE FOLLOWING: ELECTRICAL: NATIONAL ELECTRIC CODE: NFPA 70 - CURRENT VERSION NATIONAL ELECTRIC CODE: NFPA 70 - CURRENT VERSION 4. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE), INDUSTRY STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. 5. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUIVALENT. SUBSTITUTED EQUIPMENT OR MATERIALS SHALL NOT BE INSTALLED UNTIL GIVEN WRITTEN APPROVAL BY THE OWNER. 6. EACH TRADE CONTRACTOR SHALL BE WHOLLY RESPONSIBLE FOR PROVIDING, EACH TRADE CONTRACTOR SHALL BE WHOLLY RESPONSIBLE FOR PROVIDING, INSTALLING, AND MAINTAINING ALL TEMPORARY POWER SOURCES AND ANY REQUIRED UTILITIES FOR ANY TEMPORARY MECHANICAL, PLUMBING, AND/OR ELECTRICAL EQUIPMENT OR SYSTEMS (REQUIRED BY THEIR INDIVIDUAL TRADES SCOPE OF WORK) DURING THE COURSE OF CONSTRUCTION AND PHASING/SEQUENCING OF WORK. THIS SHALL INCLUDE BUT NOT BE LIMITED TO THE INSTALLATION AND ROUTING OF: TEMPORARY FEEDERS, CONDUIT, TRANSFORMERS, ON-SITE GENERATOR PACKAGES, OVERCURRENT PROTECTION DEVICES, DISCONNECTS, CONNECTIONS AND DISCONNECTION OF EQUIPMENT, ETC. ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF PROVISIONS INCLUDED IN THESE CONDITIONS. 8. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH, SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD STRUCTURES, AND OTHER MATERIALS OR EQUIPMENT THAT WAS REQUIRED IN CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF. 9.
This is the start of the file's text. The full file is on GovTribe.