Equipment List.pdf
PDF 3 MB Posted
- Solicitation number
- 36C25726Q0643
About this file
This is a Medical Gas Annual Inspection Report for El Paso VAMC dated January 6, 2026, prepared by Medical Gas Installers (MGI) technician Brayden Seger. The inspection evaluated compliance with NFPA 99 2018 Code requirements across all medical gas and vacuum systems serving the facility.
The inspection covered nine major components: source equipment (oxygen, medical air, vacuum, nitrous oxide, nitrogen, dental air, and dental vacuum systems), master alarm panels, zone valve boxes, area alarm panels, and patient outlet terminals. Overall results show 9 of 9 source equipment systems passed inspection, with 39 of 46 master alarm signals passing and 291 of 292 patient outlets passing (99.7% success rate). Three zone valve box locations failed inspection due to incorrect gauge ranges, and five area alarm panels all passed. Seven corrective actions were identified addressing gauge specifications, pressure switch wiring, and demand check fittings on pressure devices, all related to NFPA 99 2018 Code Section 5.1.8 requirements. The dental air system's dew point exceeded acceptable limits (53°F and 50°F versus 35°F maximum), though facility management confirmed ordering of replacement dryer equipment. One nitrous oxide outlet in OR-6 exhibited leakage without adapter insertion. No future corrections were identified as other non-compliant items are permitted to remain until area renovations occur without affecting patient care.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| EPVA Medical Center_As-Built_Plumbing Sheets.pdf | ||
| S02 36C25726Q0643.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
System Manufacturer Model # Serial # Location / Room Details
Medical Air Powerex MPD10084P5 (H)2/26/2019-000001539-425 1st Floor Mech. Room C106 duplex, medical reciprocating piston compressors (oil-less), desiccant dyer
Medical Vacuum Dekker VMX0203KA3-40-ES I19576 1st Floor Mech. Room C106 triplex, oil-sealed liquid ring, separator reservoir, receiver tank
Dental Air Powerex TDR80GVLHPR50 (H)2/19/2019-000001539-395 4th Floor Mech. Room A421 quadplex, scroll compressors (oil-less), refrigerated dryer
Dental Vacuum Tech West Inc. VPD30D5 VPD30-5038 3rd Floor Mech. Room A327 duplex, dry rotary vane vacuum system, separator tank, amalgam separators
Liquid Oxygen Bulk
(with Reserve Cylinder Bank) AirGas Exterior Oxygen Storage Yard 18 reserve cylinder bank
Nitrous Oxide Cylinder Bank Allied Healthcare
Products Chemetron 4000 Series 20111206003 Mech. Yard Storage Room F103
Auto Switchover Manifold, 6 in-use & 6 reserve cylinder configuration
Nitrogen Cylinder Bank Allied Healthcare
Products Chemetron 4000 Series 20111209001 Mech. Yard Storage Room F102
Auto Switchover Manifold, 6 in-use & 6 reserve cylinder configuration
Medical Gas & Vacuum System Equipment List
**As of April 2026, could be subject to change by time of contract award**
Medical Air
Medical Vacuum
Dental Air
Dental Vacuum
Liquid Oxygen Bulk PRV
STATION
Nitrous Oxide Cylinder Bank
Nitrogen Cylinder Bank
PREPARED BY: BRAYDEN SEGER
SERVICE DATE: JANUARY 6TH, 2026
EL PASO VAMC
MEDICAL GAS
ANNUAL
INSPECTION
5001 N PIEDRAS ST
EL PASO, TX 79930
ITEMS TESTED/INSPECTED
OXYGEN MEDICAL AIR
MEDICAL
VACUUM
NITROUS
OXIDE
NITROGEN
CARBON
DIOXIDE
INST. AIR WAGD
SOURCE EQUIPMENT P P P P P
MASTER ALARMS P P P P P
ZONE VALVES P P P P P P
ZONE VERIFICATION P P P P P P
CROSS CONNECTION P P P P P P
AREA ALARMS P P P P P
PATIENT OUTLETS P P P P P P
PARTICLE ANALYSIS P P P P
PURITY ANALYSIS P P P P
MGI MEDICAL GAS VERIFIER: BRAYDEN SEGER
SIGNATURE:
DATE: 1/6/2026
MEDICAL GAS ANNUAL TESTING ANALYSIS
MEDICAL GAS TYPE
SCOPE OF
TESTING/VERIFICATION
NFPA 99 2018 Compliant Medical Gas Annual Inspection for a Category 1 Medical Facility. Includes testing of all medical gas source equipment, medical gas zone valves, medical gas master alarm panels, medical gas area alarm panels, medical gas control panels, medical gas flexible terminals and medical gas terminals and medical gas labeling.
ADDITIONAL COMMENTS
https://qrplanet.com/8lq61w
EXECUTIVE SUMMARY
SIGNALS
PASSED
SIGNALS
FAILED
TOTALS 2 46 39 7
MASTER ALARM PANEL OHIO HEALTHCAIR 1 23 20 3
MASTER ALARM PANEL OHIO HEALTHCAIR 1 23 19
2 2 0
SOURCE EQUIPMENT MASTER ALARMS
EQUIPMENT
EQUIPMENT MAKE &
MODEL
ALARM PANEL
COUNT
ALARM SIGNAL
COUNT
TOTAL 9 9 0
MASTER ALARM PANEL ALARMS
DENTAL AIR SCROLL 1 1 0
DENTAL VACUUM TURBINE 1 1 0
NITROGEN GAS X GAS MANIFOLD 1 1 0
OXYGEN BULK OXYGEN 1 1 0
MEDICAL AIR RECIPROCATING 1 1 0
EXECUTIVE OVERALL SUMMARY-SOURCE
SOURCE EQUIPMENT
GAS TYPE SOURCE TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED
VACUUM LIQUID RING 1 1 0
NITROUS OXIDE GAS X GAS MANIFOLD 1 1 0
FAILED REPAIRED FAILED REPAIRED
TOTAL PERCENTAGE OF
OUTLETS TESTED
100.0%
TOTAL OUTLET
FAILURES
TOTAL OUTLETS
REPAIRED
1 0
TOTAL 292 291 1 0
PERCENTAGE 99.7% 0.3% 0.0%
WAGD 16 16 0 0
NITROUS OXIDE 16 15 1 0
NITROGEN 25 25 0 0
VACUUM 104 104 0
03 0
PATIENT OUTLET TERMINALS
MEDICAL AIR 53 53 0 0
0 0
EXECUTIVE OVERALL SUMMARY-PIPELINE
ZONE VALVE BOXES AREA ALARM PANELS
TOTAL ZVB LOCATIONS TOTAL AREA ALARM PANELSTOTAL PASSED TOTAL PASSED
513 510
MISSING VALVES MISSING ALARMS
OXYGEN 78 78 0 0
GAS TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED TOTAL UNAVAILABLE
MGI TECHNICIAN: BRAYDEN SEGER
1 SPECIFIC OUTLET REPAIRED BY REPAIR DATE
NITROUS OXIDEOR-6 LEFT COLUMN ALLIED - CNT2 - CH LEAKS W/OUT ADAPTER INSERTED
END OF OUTLET ISSUES
OUTLET ISSUES EL PASO VAMC
ROOM OUTLET SPECS ISSUE
EL PASO VAMC
CORRECTED
CORRECTED
CORRECTED
CORRECTED
NFPA 99 2018 CODE 5.1.8.1.3*
The scale range of positive pressure analog indicators shall be such that the normal operating pressure is within the middle third of the total range [e.g., an indicator of 0 to 2070 kPa (0 to 300 psi) would have a lower third of 0 to 690 kPa (0 to 100 psig), a middle third of 690 kPa to 1380 kPa (100 psig to 200 psig), and a top third of 1380 kPa to 2070 kPa (200 psig to 300 psig)].
CORRECTIVE ACTIONS
AREA ISSUE NFPA 99 2018 CODE
ZONE VALVE FOR MEDICAL AIR SERVING
BIOMED
NORMAL OPERATING PRESSURE DOES NOT FALL IN
THE MIDDLE THIRD OF THE ZONE VALVE GAUGE.
NFPA 99 2018 CODE 5.1.8.1.3*
The scale range of positive pressure analog indicators shall be such that the normal operating pressure is within the middle third of the total range [e.g., an indicator of 0 to 2070 kPa (0 to 300 psi) would have a lower third of 0 to 690 kPa (0 to 100 psig), a middle third of 690 kPa to 1380 kPa (100 psig to 200 psig), and a top third of 1380 kPa to 2070 kPa (200 psig to 300 psig)].
CORRECTIVE
ACTION
INTALL A 0-100 PSI GAUGE ON THE MEDICAL AIR ZONE VALVE
AREA ISSUE NFPA 99 2018 CODE
CORRECTIVE
ACTION
AREA ISSUE NFPA 99 2018 CODE
NFPA 99 2018 CODE
PRESSURE SWITCH/GAUGES FOR OXYGEN,
VACUUM, NITROGEN, AND NITROUS OXIDE
PRESSURE SWITCHES/GAUGES ARE NOT ON GAS
SPECIFIC DISS DEMAND CHECKS.
NFPA 99 2018 CODE 5.1.8.2.3
All pressure-sensing devices and main line pressure gauges downstream of the source valves shall be provided with a gas-specific demand check fitting to facilitate service testing or replacement.
ISSUE
INSTALL GAS SPECIFIC DISS DEMAND CHECKS ON THE PRESSURE SWITCH/GAUGE.
ZONE VALVE FOR NITROUS OXIDE SERVING
OR-4
NORMAL OPERATING PRESSURE DOES NOT FALL IN
THE MIDDLE THIRD OF THE ZONE VALVE GAUGE.
NFPA 99 2018 CODE 5.1.8.1.3*
The scale range of positive pressure analog indicators shall be such that the normal operating pressure is within the middle third of the total range [e.g., an indicator of 0 to 2070 kPa (0 to 300 psi) would have a lower third of 0 to 690 kPa (0 to 100 psig), a middle third of 690 kPa to 1380 kPa (100 psig to 200 psig), and a top third of 1380 kPa to 2070 kPa (200 psig to 300 psig)].
CORRECTIVE
ACTION
INSTALL 0-100 PSI GAUGE ON THE NITROUS OXIDE ZONE VALVE
CORRECTIVE
ACTION
INTALL A 0-100 PSI GAUGE ON THE MEDICAL AIR ZONE VALVE
AREA
ZONE VALVE FOR MEDICAL AIR SERVING
DENTAL CLINIC
NORMAL OPERATING PRESSURE DOES NOT FALL IN
THE MIDDLE THIRD OF THE ZONE VALVE GAUGE.
CORRECTIVE ACTIONS
CORRECTED
CORRECTED
CORRECTED
CORRECTIVE
ACTION
CHECK WIRING AT THE MASTER ALARM PANEL AND THE PRESSURE SWITCH.
AREA ISSUE NFPA 99 2018 CODE
MASTER ALARMS
THE MEDICAL AIR HIGH DEWPOINT DID NOT ALARM
AT THE ENGINEERING BUILDING MASTER ALARM
Master alarm panels for medical gas and vacuum systems shall each include the following signals: (NFPA
99 2018 5.1.9.2.4)
(10) Medical air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than +2°C (+35°F)
MASTER ALARMS
THE DENTAL AIR HIGH LINE PRESSURE ALARMED AS
LOW LINE PRESSURE AND THE LOW LINE PRESSURE
ALARMED AS HIGH LINE PRESSURE
Master alarm panels for medical gas and vacuum systems shall each include the following signals: (NFPA
99 2018 5.1.9.2.4)
(7) Alarm indication when the pressure in the main line of each separate medical gas system increases 20 percent or decreases 20 percent from the normal operating pressure.
CORRECTIVE
ACTION
REWIRE THE PRESSURE SWITCH TO FIX THE MISMATCHED ALARMS.
CORRECTIVE
ACTION
WIRE IN THE OXYGEN LINE PRESSURE HIGH TO BOTH MASTER ALARM PANELS.
AREA ISSUE NFPA 99 2018 CODE
AREA ISSUE NFPA 99 2018 CODE
MASTER ALARMS
OXYGEN LINE PRESSURE HIGH DOES NOT HAVE A
SIGNAL RAN TO THE MASTER ALARM PANELS
Master alarm panels for medical gas and vacuum systems shall each include the following signals: (NFPA
99 2018 5.1.9.2.4)
(7) Alarm indication when the pressure in the main line of each separate medical gas system increases 20 percent or decreases 20 percent from the normal operating pressure.
END OF CORRECTIVE ACTIONS
NOTE: CORRECTIVE ACTIONS ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE NFPA 99 2018 CODE AND SHOULD BE UPGRADED OR REPAIRED TO MEET THE
NFPA 99 2018 CODE.
NOTE: THESE ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE 2018 NFPA 99 CODE, HOWEVER THEY ARE PERMITTED TO
REMAIN IN USE UNTIL THE AREA(S) ARE UPGRADED OR RENOVATED DUE TO THE ABOVE NOT AFFECTING PATIENT CARE.
END OF FUTURE CORRECTIONS
FUTURE CORRECTIONS
AREA ISSUE NFPA 99 2018 CODE
NONE
FUTURE
CORRECTION
MEDICAL GAS MASTER
ALARM ANALYSIS
MASTER ALARM CODE REQUIREMENTS
Master alarm panels for medical gas and vacuum systems shall each include the following signals: (NFPA
99 2018 5.1.9.2.4)
(1) Alarm indication when, or just before, changeover occurs in a medical gas system that is supplied by a manifold or other alternating-type bulk system that has as a part of its normal operation a changeover from one portion of the operating supply to another.
(2) Alarm indication for a bulk cryogenic liquid system when the main supply reaches an average day’s supply, indicating low contents.
(3) Alarm indication when, or just before, the changeover to the reserve supply occurs in a medical gas system that consists of one or more units that continuously supply the piping system while another unit remains as the reserve supply and operates only in the case of an emergency.
(4) Alarm indication for cylinder reserve pressure low when the content of a cylinder reserve header is reduced below one average day’s supply.
(5) For bulk cryogenic liquid systems, an alarm when or at a predetermined set point before the reserve supply contents fall to one day’s average supply, indicating reserve low.
(6) Where a cryogenic liquid storage unit is used as a reserve for a bulk supply system, an alarm indication when the gas pressure available in the reserve unit is below that required for the medical gas system to function.
(7) Alarm indication when the pressure in the main line of each separate medical gas system increases 20 percent or decreases 20 percent from the normal operating pressure.
(8) Alarm indication when the medical–surgical vacuum pressure in the main line of each vacuum system drops.
(9) Alarm indication(s) from the local alarm panel(s) as described in 5.1.9.5.2 to indicate when one or more of the conditions being monitored at a site is in alarm.
(10) Medical air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than +2°C (+35°F)
(11) WAGD low alarm when the WAGD vacuum level or flow is below effective operating limits.
(12) An instrument air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than −30°C (−22°F).
(13) Alarm indication if the primary or reserve production stops on a proportioning system.
EL PASO VAMC MGI TECHNICIAN: BRAYDEN SEGER
EL PASO, TX 79930 TESTING DATE: 1/6/2026
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P P P
P P P
P P P
NO SIGNAL RAN FOR HIGH
P P P
P P P
P DID NOT ALARM AT PANEL
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P ALARMED AS HIGH LINE PRESSURE
P P ALARMED AS LOW LINE PRESSURE
ALARM MAKE AND MODEL: ENGINEERING BUILDING
COMMENTS
PASS/FAIL
FAIL
PER NFPA 99 2018 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
DENTAL AIR HIGH LINE PRESSURE FAIL
OHIO HEALTHCAIR LOCATION:
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
DENTAL AIR LOW LINE PRESSURE FAIL
NITROGEN LINE PRESSURE HIGH PASS
NITROGEN LINE PRESSURE LOW PASS
NITROUS OXIDE RESERVE IN USE PASS
DENTAL AIR SYSTEM GENERAL ALARM PASS
NITROUS OXIDE LINE PRESSURE HIGH PASS
NITROUS OXIDE LINE PRESSURE LOW PASS
DENTAL AIR HIGH DEW POINT PASS
NITROGEN RESERVE IN USE PASS
MEDICAL VACUUM LAG IN USE PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN PASS
MEDICAL AIR GENERAL ALARM PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MEDICAL AIR LINE PRESSURE LOW PASS
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW PASS
OXYGEN RESERVE IN USE PASS
OXYGEN RESERVE LOW PASS
OXYGEN LINE PRESSURE HIGH FAIL
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR RESERVE COMP IN USE PASS
MEDICAL AIR HIGH DEW POINT FAIL
EL PASO VAMC MGI TECHNICIAN: BRAYDEN SEGER
EL PASO, TX 79930 TESTING DATE: 1/6/2026
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P P P
P P P
P P P
NO SIGNAL RAN FOR HIGH
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P ALARMED AS HIGH LINE PRESSURE
P P ALARMED AS LOW LINE PRESSURE
ALARM MAKE AND MODEL: BIOMED
COMMENTS
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW PASS
OXYGEN RESERVE LOW PASS
OXYGEN LINE PRESSURE HIGH FAIL
OXYGEN RESERVE IN USE PASS
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR RESERVE COMP IN USE PASS
MEDICAL AIR HIGH DEW POINT PASS
MEDICAL AIR GENERAL ALARM PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MEDICAL AIR LINE PRESSURE LOW PASS
MEDICAL VACUUM LAG IN USE PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN PASS
OHIO HEALTHCAIR LOCATION:
NITROUS OXIDE LINE PRESSURE HIGH PASS
NITROUS OXIDE LINE PRESSURE LOW PASS
DENTAL AIR HIGH LINE PRESSURE FAIL
DENTAL AIR SYSTEM GENERAL ALARM PASS
DENTAL AIR HIGH DEW POINT PASS
DENTAL AIR LOW LINE PRESSURE FAIL
PER NFPA 99 2018 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
PASS/FAIL
FAIL
NITROUS OXIDE RESERVE IN USE PASS
NITROGEN RESERVE IN USE PASS
NITROGEN LINE PRESSURE HIGH PASS
NITROGEN LINE PRESSURE LOW PASS
MEDICAL GAS AREA
ALARM ANALYSIS
(2) *Critical Care Areas
(4) Means to visually indicate a lamp or LED failure
AREA ALARM CODE REQUIREMENTS
Area alarm systems used for medical gas and vacuum systems shall include the following:
(NFPA 99 2018 5.1.9.1)
(1) Separate visual indicators for each condition monitored, except as permitted in 5.1.9.5.2 for local alarms that are displayed on master alarm panels.
(2) Visual indicators that remain in alarm until the situation that has caused the alarm is resolved.
(3) Cancelable audible indication of each alarm condition that produces a sound with a minimum level of
80 dBA at 0.92m (3 ft)
(2)*Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered shall have the sensors installed either on the source side of any of the individual room zone valve box assemblies or on the patient or use side of each of the individual zone valve box assemblies.
(5) Visual and audible indication that the communication with an alarm-initiating devices is disconnected.
(6) Labeling of each indicator, indication the condition monitored.
(7) Labeling of each alarm panel for its area of surveillance.
(8) Reinitiating of the audible signal if another alarm condition occurs while the audible alarm is silenced.
(9) Power for master, area alarms, sensors, and switches from the life safety branch of the emergency electrical system as described in Chapter 6.
Area Alarms. Area alarm panels shall be provided to monitor all medical gas, medical–surgical vacuum, and piped WAGD systems supplying the following: (NFPA 99 2018 5.1.9.4)
(1) Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered.
Area alarm panels for medical gas systems shall indicate if the pressure in the lines in the area being monitored increases or decreases by 20 percent from the normal line pressure. (NFPA 99 2018 5.1.9.4.2)
Area alarm panels for medical–surgical vacuum systems shall indicate if the vacuum in the area drops to or below 300 mm (12 in.) gauge HgV. (NFPA 99 2018 5.1.9.4.3)
Alarm sensors for area alarms shall be located as follows: (NFPA 99 2018 5.1.9.4.4)
(1)*Critical care areas shall have the alarm sensors installed on the patient or use side of each individual zone valve box assemblies.
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 46 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
END OF 3RD FLOOR AREA ALARM ANALYSIS
AREA ALARM ANALYSIS
3RD FLOOR
AREA MONITORED: COMMENTS
RADIOLOGY ROOMS B309,
B312, B315, B317
RADIOLOGY CHECK IN ALARM MAKE AND MODEL: CHEMETRON IMPACT
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 56 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 47 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 48 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 55 PSI PASS 60 PSI 40 PSI PASS PASS MAINLINE P
MED AIR 46 PSI PASS 60 PSI 40 PSI PASS PASS MAINLINE P
VACUUM 20" HG PASS N/A 12" HG PASS PASS MAINLINE P
N2O 52 PSI PASS 60 PSI 40 PSI PASS PASS MAINLINE P
NITROGEN 160 PSI PASS 195 PSI 155 PSI PASS PASS MAINLINE P
FLOOR: 4TH ALARM LOCATION:
AREA ALARM ANALYSIS
4TH FLOOR
AREA MONITORED: COMMENTS
ASU RECOVERY BAYS 1-16
CHEMETRON IMPACT
NURSES STATION ALARM MAKE AND MODEL: CHEMETRON IMPACT
END OF 4TH FLOOR AREA ALARM ANALYSIS
AREA MONITORED: COMMENTS
PROCEDURE ROOMS B459 AND
B457
ACROSS CHECK IN DESK ALARM MAKE AND MODEL:
AREA MONITORED: COMMENTS
OR'S 1-8
CLEAN CORE ALARM MAKE AND MODEL: CHEMETRON IMPACT
AREA MONITORED: COMMENTS
DENTAL CLINIC
OUTSIDE B421 ALARM MAKE AND MODEL: CHEMETRON IMPACT
MEDICAL GAS
ZONE VALVE ANALYSIS
Zone valves shall be readily operable from a standing position in the corridor on the same floor they serve. (NFPA 99 2018 5.1.4.6.2)
ZONE VALVE CODE REQUIREMENTS
Zone Valves. All station outlets/inlets shall be supplied through a zone valve as follows:
(NFPA 99 2018 5.1.4.6.1)
(1) The zone valve shall be placed such that a wall intervenes between the valve and outlets/inlets that it controls.
(2) The zone valves shall serve only outlets/inlets located on that same story.
(3) The zone valve shall not be located in a room with station outlets/inlets that it controls.
Zone valves shall be labeled in accordance with 5.1.11.2.7
Zone valves shall be so arranged that shutting off the supply of medical gas or vacuum to one zone will not affect the supply of medical gas or vacuum to another zone or the rest of the system.
(NFPA 99 2018 5.1.4.6.3)
A pressure/vacuum indicator shall be provided on the station outlet/inlet side of each zone valve.
(NFPA 99 2018 5.1.4.6.4)
Zone valve boxes shall be installed where they are visible and accessible at all times.
(NFPA 99 2018 5.1.4.6.1)
Zone valve boxes shall not be installed behind normally open or normally closed doors or otherwise hidden from plain view. (NFPA 99 2018 5.1.4.6.1)
Zone valve boxes shall not be located in closed or locked rooms, areas, or closets.
(NFPA 99 2018 5.1.4.6.1)
Zone valves shall be so arranged that shutting off the supply of gas to any one operating room or anesthetizing location will not affect the others. (NFPA 99 2018 5.1.4.6.3)
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 1/2" BALL PASS PASS
VACUUM 22" HG PASS PASS 1" BALL PASS PASS P
N2 160 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION: OUTSIDE BIOMED VALVE MANUFACTURER: CHEMETRON
END OF 1ST FLOOR ZONE VALVE ANALYSIS
ZONE VALVE ANALYSIS
1ST FLOOR
AREA SERVED: COMMENTS
BIOMED
MED AIR GAUGE NEEDS
TO BE O-100 PSI
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 56 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 22" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
END OF 3RD FLOOR ZONE VALVE ANALYSIS
ACROSS B317 VALVE MANUFACTURER: CHEMETRON
ZONE VALVE ANALYSIS
3RD FLOOR
AREA SERVED: COMMENTS
RADIOLOGY ROOMS B309, B312, B315,
B317
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 59 PSI PASS PASS 1" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 1" BALL PASS PASS P
VACUUM 25" HG PASS PASS 1-1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 25" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 53 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 3/4" BALL PASS PASS
VACUUM 24" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM
WAGD
24" HG PASS PASS 3/4" BALL PASS PASS P
N2O 51 PSI PASS PASS 1/2" BALL PASS PASS P
N2 170 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 58 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM
WAGD
21" HG PASS PASS 3/4" BALL PASS PASS P
N2O 50 PSI PASS PASS 1/2" BALL PASS PASS P
N2 165 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
PROCEDURE ROOMS B459 AND B457
ZONE VALVE ANALYSIS
4TH FLOOR
AREA SERVED: COMMENTS
ASU RECOVERY BAYS 1-16
OUTSIDE RECOVERY VALVE MANUFACTURER: CHEMETRON
AREA SERVED: COMMENTS
AREA SERVED: COMMENTS
DENTAL CLINIC
MEDICAL AIR NEEDS A 0-
100 PSI GAUGE
ACROSS B414 VALVE MANUFACTURER:
OUTSIDE OR-1 VALVE MANUFACTURER: CHEMETRON
OR-1 (A-405)
AREA SERVED: COMMENTS
OUTSIDE OR-2 VALVE MANUFACTURER:
OUTSIDE PROCEDURE ROOMS VALVE MANUFACTURER: CHEMETRON
CHEMETRON
AREA SERVED: COMMENTS
CHEMETRON
OR-2 (A-406)
ZONE VALVE ANALYSIS
4TH FLOOR
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM
WAGD
22" HG PASS PASS 3/4" BALL PASS PASS P
N2O 55 PSI PASS PASS 1/2" BALL PASS PASS P
N2 170 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 55 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 48 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 24" HG PASS PASS 3/4" BALL PASS PASS P
N2O 55 PSI PASS PASS 1/2" BALL PASS PASS
N2 160 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 59 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 48 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 22" HG PASS PASS 3/4" BALL PASS PASS P
N2O 50 PSI PASS PASS 1/2" BALL PASS PASS P
N2 175 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 58 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 26" HG PASS PASS 3/4" BALL PASS PASS P
N2O 53 PSI PASS PASS 1/2" BALL PASS PASS P
N2 175 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
AREA SERVED: COMMENTS
OR-3 (B-473)
OUTSIDE OR-3 VALVE MANUFACTURER: CHEMETRON
AREA SERVED: COMMENTS
OR-4 (B-474)
N2O NEEDS A 0-100 PSI
GAUGE
OUTSIDE OR-4 VALVE MANUFACTURER: CHEMETRON
AREA SERVED: COMMENTS
OR-5 (B-475)
ACROSS OR-5 VALVE MANUFACTURER: CHEMETRON
AREA SERVED: COMMENTS
OR-6 (D-403)
OUTSIDE OR-6 VALVE MANUFACTURER: CHEMETRON
ZONE VALVE ANALYSIS
4TH FLOOR
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 56 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 48 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 23" HG PASS PASS 3/4" BALL PASS PASS P
N2O 54 PSI PASS PASS 1/2" BALL PASS PASS P
N2 165 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 59 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 26" HG PASS PASS 3/4" BALL PASS PASS P
N2O 52 PSI PASS PASS 1/2" BALL PASS PASS P
N2 170 PSI PASS PASS 1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
END OF 4TH FLOOR ZONE VALVE ANALYSIS
AREA SERVED: COMMENTS
OR-7 (C-409)
OUTSIDE OR-7 VALVE MANUFACTURER: CHEMETRON
AREA SERVED: COMMENTS
OR-8 (C-408)
OUTSIDE OR-8 VALVE MANUFACTURER: CHEMETRON
MEDICAL GAS
OUTLET ANALYSIS
Support gas outlets shall deliver 140 SLPM (5.0 SCFM) with a pressure drop of not more than 35 kPa (5 psi) gauge and static pressure of 1100 kPa to 1275 kPa (160 psi to 185 psi) gauge.
(NFPA 99 2018 5.1.12.4.10.3)
OUTLET CODE REQUIREMENTS
Each station outlet/inlet for medical gases or vacuums shall be gas-specific, whether the outlet/inlet is threaded or is a noninterchangeable quick coupler. (NFPA 99 2018 5.1.5.1)
Each outlet/inlet shall be legibly identified in accordance with 5.1.11.3. (NFPA 99 2018 5.1.5.5)
Each station outlet/inlet, including those mounted in columns, hose reels, ceiling tracks, or other special installations, shall be designed so that parts or components that are required to be gas specific for compliance with 5.1.5.1 and 5.1.5.9 cannot be interchanged between the station outlet/inlet for different gases. (NFPA 99 2018 5.1.5.7)
All gas outlets with a gauge pressure of 345 kPa (50 psi), including, but not limited to, oxygen, nitrous oxide, medical air, and carbon dioxide, shall deliver 100 SLPM (3.5 SCFM) with a pressure drop of not more than 35 kPa (5 psi) and static pressure of 345 kPa to 380 kPa (50 psi to 55 psi).
(NFPA 99 2018 5.1.12.4.10.2)
Medical–surgical vacuum inlets shall draw 85 Nl/min (3 SCFM) without reducing the vacuum pressure below 300 mm (12 in.) gauge HgV at any adjacent station inlet. (NFPA 99 2018 5.1.12.4.10.4)
Oxygen and medical air outlets serving critical care areas shall allow a transient flow rate of 170 SLPM
(6 SCFM) for 3 seconds. (NFPA 99 2018 5.1.12.4.10.5)
Medical gas concentration & flow rate requirements. (NFPA 99 2018 Table 5.1.12.4.11)
GAS FLOW RATE CONCENTRATION
OXYGEN Non-critical 3.5 SCFM Critical 6.0 SCFM ≥99% oxygen
MEDICAL AIR Non-critical 3.5 SCFM Critical 6.0 SCFM 19.5%–23.5% oxygen
NITROUS OXIDE 3.5 SCFM ≥99% nitrous oxide
NITROGEN 5.0 SCFM ≤1% O2 or ≥99% N2
OTHER GASES 3.5 SCFM
As specified by ±1%, unless otherwise specified
VACUUM 3.0 SCFM N/A
WAGD 3.0 SCFM N/A
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e w
/o
A d ap te r O p er a ti o n al
Fl o w
St at ic P re ss u re
C o n ce n tr a ti o n
C o n d it io
La b el in g
PASS FAIL
PARTICULATE
CONTAMINATION
REPAIRED BY
1ST FLOOR OXYGEN MEDICAL AIR VACUUM N2
BIOMED 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
3RD FLOOR
B309 1 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
B312 1 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
B315 1 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
B317 1 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
TOTAL COUNT: 5 5 5 1
OUTLET ANALYSIS
OUTLET SPECS COMMENTS
N2 IS ALLIED - 500 - DISS
GAS TYPE & OUTLET QUANTITY
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p e ra ti o w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io e lin g
PASS FAIL
PARTICULATE
CONTAMINATION
REPAIRED BY
4TH FLOOR OXYGEN MEDICAL AIR VACUUM
ASU BAY 1 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 2 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 3 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 4 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 5 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 6 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 7 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 8 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 9 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 10 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 11 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 12 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 13 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 14 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 15 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
ASU BAY 16 2 2 3 ALLIED 400 CH P P P P P P P <1MG ALL OUTLETS
B457 1 2 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
B459 1 2 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B403 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B409 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B412 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B413 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B414 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B415 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
DENTAL ROOM B416 1 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
TOTAL COUNT: 41 32 59
OUTLET ANALYSIS
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
BACK WALL VAC IS
ALLIED - CNT2 - CH
BACK WALL VAC IS
ALLIED - CNT2 - CH
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p e ra ti o w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io e li n g
PASS FAIL
PARTICULATE
CONTAMINATION
REPAIRED
OR'S OXY MED AIR
MED
VAC
N2O N2 WAGD
OR-1 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-1 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-1 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-2 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-2 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-2 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-3 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-3 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-3 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-4 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-4 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-4 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-5 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-5 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-5 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-6 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-6 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P <1MG ALL OUTLETS
OR-6 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-7 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-7 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-7 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
OR-8 RIGHT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-8 LEFT COLUMN 2 1 1 1 1 1 ALLIED CNT2 CH P P P P P P P <1MG ALL OUTLETS
OR-8 WALL 3 1 ALLIED 500 CH P P P P P P P <1MG ALL OUTLETS
TOTAL COUNT: 32 16 40 16 24 16
OUTLET ANALYSIS
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
N2O LEAKS W/O ADAPTER
INSERTED
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
N2 IS CHEMETRON - CP - DISS
MEDICAL GAS SOURCE
EQUIPMENT ANALYSIS
LOCATION BULK PAD
AREA(S) OF FACILITY SERVED ENTIRE FACILITY
BULK SUPPLIER AIRGAS
SYSTEM TYPE LIQ X 18 HP RESERVE
PRIMARY LIQUID LEVEL 53"
PRIMARY PRESSURE 155 PSI
RESERVE LIQUID LEVEL N/A
RESERVE PRESSURE 2200 PSI
PRIMARY FINAL LINE PRESSURE 55 PSI
RESERVE FINAL LINE PRESSURE 55 PSI
SOURCE VALVE PRESSURE 53 PSI
MAIN VALVE PRESSURE 54 PSI
SOURCE VALVE TYPE BALL
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION C100 MECHANICAL ROOM
EOSC VALVE SIZE 1" BALL
EOSC LOCATION(S) OUTSIDE DOCK
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Proper fill circuit (inlet, strainer, check valve, purge valve, supports)
BULK OXYGEN
SOURCE EVALUATION DATA
NFPA 99 2018 SCHEMATIC
NFPA 99 2018 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Enclosure (min 6' height) non-combustible, proper ventilation & 2 lockable entries/exits
Containers permanently anchored & cylinders adequately secured
Noncombustible pad w/3' maintenance clearance, accessible for delivery & pad adequately sized for vehicles
Top & bottom fill, hose purge, & vent valves present
Piped w/brazed copper, brass, or stainless & no flex connects/fittings wear & leaks
Reserve and primary check valves in place for reserve to feed automatically
Reserve economizer in place to feed upstream final regulators
Drainage prevented towards (buildings, drains, etc.) & from hazards
Labeling: pipeline, source/main valves & "Oxygen-No Smoking, No Open Flames"
Vaporizer appears adequately sized & isolation valves arranged for service w/o supply interruption
Emergency Supply (3' clearance) or (IBER) w/2 checks, secured, & labeled
Distance from the following: 1' - all structures (Type I & II), * 50' - wood framed Type III, IV, or V building types, * 50' - Public assembly or nearest non- ambulatory patient, * 5' -
Property lines & overhead electrical wiring, 10' building openings, * 10' - public sidewalks & parked vehicles, * 15' - Hazardous piping materials & below ground flammable liquid tanks, * 25' - 0-1000 gal flammable liquids/liquefied gas, below ground flammable liquid fill or vent, 0-25,000 scf flammable gases, or slow burning solids, * 50' - >1000 gal flammable liquids/liquefied gas, >25,000 scf flammable gases, or rapidly burning solids, 3' - combustible surfaces (asphalt & expansion joint filler) where liquid oxygen may fall, 8' - Sewer or drain openings to delivery connects, reliefs, mobile supply equipment, & liquid withdrawal connects, Walls may not form a 3-4 sided court.
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
LOCATION C106 MECHANICAL ROOM LINE PRESSURE
AREA(S) OF FACILITY SERVED ENTIRE FACILITY DRYER TYPE
MANUFACTURER POWEREX DRYER INFO
MODEL NUMBER MPD10084P5 DEW POINT MONITOR INFO
SERIAL NUMBER (H)2/26/2019-000001539-425 CO MONITOR INFO
SYSTEM TYPE RECIPROCATING SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL N/A PUMP 1 HOURS
HORSEPOWER 10 H.P. PUMP 2 HOURS
LEAD ON/OFF 95 PSI / 115 PSI PUMP 3 HOURS
LAG ON/OFF 65 PSI / 85 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) 35 DEG F -75 DEG F PASS
DEW POINT (CS MONITOR) 35 DEG F -55 DEG F PASS
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
CARBON DIOXIDE 500 PPM 97 PPM PASS
METHANE 25 PPM 1 PPM PASS
CHLOROFORM 2 PPM 0 PPM PASS
OXYGEN 19.5%-23.5% 21.3% PASS
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PIntake turned down and screened
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
Intake above roof level, >20' above ground, 10 ft from doors, windows, other openings, and 25' from exhausts
System is equipped with manual disconnects
System is equipped with a local lag, dew point and CO alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
System power supplied from emergency power
N/A
MEDICAL AIR COMP MAINTENANCE REQUIRED
NFPA 99 2018 SCHEMATIC MEDICAL AIR PURITY ANALYSIS
COMMENTS
NFPA 99 2018 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical air compressors
System is supplied with flexible connectors on inlet and outlet sides of the compressors
N/A
MEDICAL AIR SYSTEM
SOURCE EVALUATION DATA
50 PSI
DESICCANT
PMD35000AJ
POWEREX BUILT IN
ENMET CO GUARD
AT SOURCE
AT SOURCE
LOCATION C106 MECHANICAL ROOM
AREA(S) OF FACILITY SERVED ENTIRE FACILITY
MANUFACTURER DEKKER
MODEL NUMBER VMX0203KA3-40-ES
SERIAL NUMBER 119576
SYSTEM TYPE LIQUID RING
CONFIGURATION TRIPLEX
PUMP MAKE AND MODEL DEKKER DV0200B-KA3
HORSEPOWER 15 H.P.
LEAD ON/OFF 19" HG / 24" HG
LAG ON/OFF 14" HG / 19" HG
LINE PRESSURE 24" HG
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION AT SOURCE
PUMP 1 HOURS 37630
PUMP 2 HOURS 41941
PUMP 3 HOURS 31451
PUMP 4 HOURS N/A
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PASS
ADDITIONAL COMMENTS
System automatically alternates the pumps evenly
Source valve in proper location and labeled
Mainline and exhaust piping properly labeled
Exhaust is turned down and screened
Exhaust ≥25' from doors, windows, intakes, building openings & public assembly & copper or stainless, no dips, drip legs installed, & sufficient diameter
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System visibly complies with above schematic per NFPA 99.
Located in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical vacuum pumps
System has flexible connectors
System has antivibration mountings
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
NFPA 99 2018 CHECKLIST
MEDICAL VACUUM SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2018 SCHEMATIC
LOCATION NITROUS OXIDE MANIFOLD ROOM
AREA(S) OF FACILITY SERVED OR'S
MANUFACTURER CHEMETRON
MODEL NUMBER 4000
SERIAL NUMBER 20111206003
SYSTEM TYPE HP X HP
CYLINDERS ON RIGHT BANK 6
CYLINDERS ON LEFT BANK 6
RIGHT BANK PRESSURE 600 PSI
LEFT BANK PRESSURE 600 PSI
CHANGE OVER PRESSURE 150 PSI
LINE PRESSURE 55 PSI
SOURCE VALVE TYPE BALL
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION C100 MECHANICAL ROOM
PASS FAIL N/A
P
P
P
P
P
N/A
P
P
P
P
P
P
P
P
P
P
ADDITIONAL COMMENTS
Cylinders secured with racks or chains
Headers have header valve and check valves
Cylinders prevented from reaching temperatures in excess 130°F. and lower than 20°F.
Door Labeling: CAUTION, Medical Gases, No Smoking or Open Flame, Room May Have Insufficient Oxygen Open Door & Allow Room to Ventilate before
Entering
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS PASS
Electrical devices protected in room
System visibly complies with above schematic per NFPA 99.
Secured with lockable doors or gates or otherwise secured.
1 hour fire rated door and walls.
Source valve labeled per NFPA 99.
Proper natural ventilation
Proper mechanical ventilation
Manifold power supplied from emergency power
Automatic bank alternation
Warning lights when banks alternate
Relief Valves vented outside, pipe size, turned down, & screened
No flammable materials, cylinders containing flammable gases, or containers containing flammable liquids
NFPA 99 2018 CHECKLIST
NITROUS OXIDE MANIFOLD SYSTEM
LOCATION NITROGEN MANIFOLD ROOM
AREA(S) OF FACILITY SERVED BIOMED AND OR'S
MANUFACTURER CHEMETRON
MODEL NUMBER 4000
SERIAL NUMBER 20111209001
SYSTEM TYPE HP X HP
CYLINDERS ON RIGHT BANK 6
CYLINDERS ON LEFT BANK 6
RIGHT BANK PRESSURE 2000 PSI
LEFT BANK PRESSURE 1400 PSI
CHANGE OVER PRESSURE 250 PSI
LINE PRESSURE 165 PSI
SOURCE VALVE TYPE BALL
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION C100 MECHANICAL ROOM
PASS FAIL N/A
P
P
P
P
P
N/A
P
P
P
P
P
P
P
P
P
P
ADDITIONAL COMMENTS
Cylinders secured with racks or chains
Headers have header valve and check valves
Cylinders prevented from reaching temperatures in excess 130°F. and lower than 20°F.
Door Labeling: CAUTION, Medical Gases, No Smoking or Open Flame, Room May Have Insufficient Oxygen Open Door & Allow Room to Ventilate before
Entering
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS PASS
Electrical devices protected in room
System visibly complies with above schematic per NFPA 99.
Secured with lockable doors or gates or otherwise secured.
1 hour fire rated door and walls.
Source valve labeled per NFPA 99.
Proper natural ventilation
Proper mechanical ventilation
Manifold power supplied from emergency power
Automatic bank alternation
Warning lights when banks alternate
Relief Valves vented outside, pipe size, turned down, & screened
No flammable materials, cylinders containing flammable gases, or containers containing flammable liquids
NFPA 99 2018 CHECKLIST
NITROGEN MANIFOLD SYSTEM
LOCATION A421 MECHANICAL ROOM LINE PRESSURE
AREA(S) OF FACILITY SERVED DENTAL CLINIC DRYER TYPE
MANUFACTURER POWEREX DRYER INFO
MODEL NUMBER SEQ200740AJ DEW POINT MONITOR INFO
SERIAL NUMBER (M)3/18/2019-S1539-905 CO MONITOR INFO
SYSTEM TYPE ENCLOSED SCROLL SOURCE VALVE LOCATION
CONFIGURATION QUADPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL POWEREX PUMP 1 HOURS
HORSEPOWER 20 H.P. PUMP 2 HOURS
LEAD ON/OFF 95 PSI / 115 PSI PUMP 3 HOURS
LAG ON/OFF 65 PSI / 85 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) 35 DEG F 53 DEG F FAIL
DEW POINT (CS MONITOR) 35 DEG F 50 DEG F FAIL
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
DENTAL AIR SYSTEM
SOURCE EVALUATION DATA
50 PSI
REFRIGERANT
HANKISON HPR50
NEWPORT SCIENTIFICS 1092E
DYNAMATION ABL-4021
AT SOURCE
AT SOURCE
NFPA 99 SCHEMATIC DENTAL AIR PURITY ANALYSIS
COMMENTS
Each pump has an isolation valve so a pump can be serviced without interruption of the system
NFPA 99 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more instrument air compressors or a standby header
System is supplied with flexible connectors on inlet and outlet sides of the compressors
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag and dew point alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
PASS
ADDITIONAL COMMENTS
FACILITY IS AWARE OF THE HIGH DEWPOINT. THEY HAVE ORDERED A NEW DRYER TO FIX THIS ISSUE.
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
MEETS ALL NFPA 99 CODE REQUIREMENTS
LOCATION A421 MECHANICAL ROOM
AREA(S) OF FACILITY SERVED DENTAL CLINIC
MANUFACTURER TECH WEST
MODEL NUMBER VPD30D5
SERIAL NUMBER VPD30-5038
SYSTEM TYPE TURBINE
CONFIGURATION DUPLEX
PUMP MAKE AND MODEL N/A
HORSEPOWER 7.5 H.P.
LEAD ON/OFF 7" HG / 10" HG
LAG ON/OFF 5" HG / 7" HG
LINE PRESSURE 10" HG
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION N/A
PUMP 1 HOURS 10366
PUMP 2 HOURS 10193
PUMP 3 HOURS N/A
PUMP 4 HOURS N/A
PASS FAIL N/A
P
P
P
P
P
P
P
N/A
N/A
P
P
P
P
P
P
N/A
N/A
NFPA 99 2018 CHECKLIST
MEDICAL VACUUM SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2018 SCHEMATIC
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System visibly complies with above schematic per NFPA 99.
Located in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical vacuum pumps
System has flexible connectors
System has antivibration mountings
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
PASS
ADDITIONAL COMMENTS
System automatically alternates the pumps evenly
Source valve in proper location and labeled
Mainline and exhaust piping properly labeled
Exhaust is turned down and screened
Exhaust ≥25' from doors, windows, intakes, building openings & public assembly & copper or stainless, no dips, drip legs installed, & sufficient diameter
MEETS ALL NFPA 99 2018 CODE REQUIREMENTS
END OF REPORT
5001 N PIEDRAS ST
EL PASO, TX 79930