Electrical Drawings - Stilley Station

This is an electrical design drawing document prepared for Stilley Station, a waste management facility located in Beaufort County, North Carolina. The project involves the installation of a comprehensive electrical system including site lighting, multiple electrical panels (Panels A, B, and C), grounding systems, and distribution infrastructure to support various operational equipment including compactors, a multi-material processor, and facility buildings. The electrical system is designed for 120/208V three-phase service with a 600-amp main service panel rated at 92 amps continuous load. The drawings specify LED lighting fixtures from Lithonia, including roadway-type fixtures and exterior canopy lights mounted on 40-foot wood poles, with approximately 26 total pole-mounted fixtures distributed across the site. The design accommodates multiple 15HP and 30HP compactor motors, HVAC systems, receptacles, and emergency lighting throughout the facility.

The electrical installation must comply with the 2020 National Electrical Code (NEC) and includes detailed specifications for conduit sizing (ranging from 1/2-inch to 3-inch PVC and rigid steel), wire gauges (#12 through #500 AWG copper conductors), grounding electrodes consisting of three 3/4-inch by 10-foot ground rods, and comprehensive bonding requirements. The contractor is responsible for all labor, materials, coordination with other trades, utility location, and compliance with manufacturer specifications. Panel schedules indicate load calculations totaling 144.6 kVA demand, with dedicated circuits for specific equipment loads. The design includes provisions for future expansion with spare circuits and conduit runs, along with photocell-controlled lighting and multiple GFI-protected receptacles in wet locations. Documentation requirements include shop drawing submittals, panel schedules with load descriptions, operating and maintenance manuals, one-year warranty on all materials and installation, and coordination with the utility company for service connection and any owner-furnished equipment.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E2

E2

YARD WASTE

PAD

CUSTOMER

UNLOADING

AREA

3/31/26

SCALE: N1 ELECTRICAL SITE LIGHTING PLAN

1" = 75'-0"

LIGHTING NOTES:

LIGHT FIXTURE SCHEDULE

INSTALLATION KEYED NOTES " # ":

E1

EL

EC

TR

IC

AL

S

IT

E

PL

AN

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text A-6,8

AutoCAD SHX Text B

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text A-10,12

AutoCAD SHX Text

#6AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#6AWG

AutoCAD SHX Text

#10AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text B

AutoCAD SHX Text A-6,8

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

#10AWG

AutoCAD SHX Text

#10AWG

AutoCAD SHX Text

PANEL "C"

AutoCAD SHX Text

AutoCAD SHX Text

#10AWG

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text A-2,4

AutoCAD SHX Text

#8AWG

AutoCAD SHX Text

PANEL "A"

AutoCAD SHX Text

REV.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

CLIENT DWG. NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

PROJECT/LOCATION

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

APPROVED BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

PROJECT MGR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

(919) 778-9064

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

P.O. BOX 11527

AutoCAD SHX Text

BY

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

GOLDSBORO, NC 27532

AutoCAD SHX Text

TEL:

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

BEAUFORT COUNTY

AutoCAD SHX Text

PROJNO

AutoCAD SHX Text

JDH

AutoCAD SHX Text

STILLEY STATION

AutoCAD SHX Text

NC LIC #: C-1132

AutoCAD SHX Text N/A

AutoCAD SHX Text

BLT

AutoCAD SHX Text

JDH

AutoCAD SHX Text

JDH

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text M

AutoCAD SHX Text

SEAL

AutoCAD SHX Text A

AutoCAD SHX Text 31466

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text J

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text

1. ELECTRICAL CONTRACTOR SHALL CIRCUIT ALL EXTERIOR POLES TO PANEL "A". RACEWAY SHALL BE 1" MINIMUM. ELECTRICAL CONTRACTOR SHALL CIRCUIT ALL EXTERIOR POLES TO PANEL "A". RACEWAY SHALL BE 1" MINIMUM. CONTRACTOR SHALL PROVIDE ALL SITE LIGHTING. 2. INSTALLATION OF POLES AND LIGHTING FIXTURES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. INSTALLATION OF POLES AND LIGHTING FIXTURES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. 3. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL UTILITIES PRIOR TO THE BEGINNING OF WORK AND AVOIDING THEM CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL UTILITIES PRIOR TO THE BEGINNING OF WORK AND AVOIDING THEM DURING INSTALLATION OPERATIONS. 4. MOUNTING HEIGHTS MEASURED FROM PARKING SURFACE OR GRADE AT BASE OF POLE. HEIGHTS SHOWN ARE FIXTURE MOUNTING HEIGHTS MEASURED FROM PARKING SURFACE OR GRADE AT BASE OF POLE. HEIGHTS SHOWN ARE FIXTURE HEIGHTS. 5. POLE LOCATED ADJACENT TO ROAD OR PARKING EDGES SHALL BE SET BACK 36" FROM EDGE OF PAVEMENT/GRAVEL.POLE LOCATED ADJACENT TO ROAD OR PARKING EDGES SHALL BE SET BACK 36" FROM EDGE OF PAVEMENT/GRAVEL.

AutoCAD SHX Text

REF MANF

AutoCAD SHX Text

MARK

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

QUALITY AND APPEARANCE

AutoCAD SHX Text

INPUT WATTS

AutoCAD SHX Text

FIXTURE

AutoCAD SHX Text

VOLTS

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

MULTI-VOLT INPUT

AutoCAD SHX Text

BATTERY BACK-UP - 1400 LUMENS

AutoCAD SHX Text

STANDARD COLOR SELECTED BY ARCH.

AutoCAD SHX Text

CUSTOM COLOR SELECTED BY ARCH.

AutoCAD SHX Text

LED

AutoCAD SHX Text

SOURCE

AutoCAD SHX Text

LUMENS

AutoCAD SHX Text

CRI

AutoCAD SHX Text

COLOR

AutoCAD SHX Text

TEMP

AutoCAD SHX Text

BATTERY BACK-UP

AutoCAD SHX Text

MODEL NUMBER FOR FIXTURE REFERENCE

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

LED

AutoCAD SHX Text 25,070

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AEL

AutoCAD SHX Text

ROADWAY TYPE 5

AutoCAD SHX Text

LED

AutoCAD SHX Text 36,305

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AEL

AutoCAD SHX Text D

AutoCAD SHX Text

ATB0 P454 MVOLT R5 MP

AutoCAD SHX Text

ATB2 P604 MVOLT R4 MP

AutoCAD SHX Text

EXTERIOR CANOPY LIGHT

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

PCNY LED ALO2 SWW2 FPCL MVOLT DWHXD M3

AutoCAD SHX Text

LED

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROADWAY TYPE 4

AutoCAD SHX Text 13,000

AutoCAD SHX Text

AutoCAD SHX Text

ARM

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

AMACE T20 US2 DDBXD

AutoCAD SHX Text

2' ELLIPTICAL TUBE ARM

AutoCAD SHX Text

PROVIDE WITH 3 PIN NEMA PHOTOCELL

AutoCAD SHX Text

COLOR

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

QTY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PROVIDE WITH 3 PIN NEMA PHOTOCELL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

POLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

40' WOOD POLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. PRODUCTS LISTED ARE DESIGN BASIS. EQUAL SUBSTITUTION SUBMITTALS WILL BE EVALUATED. PRODUCTS LISTED ARE DESIGN BASIS. EQUAL SUBSTITUTION SUBMITTALS WILL BE EVALUATED. 2. CONTRACTOR SHALL SUBMIT LIGHTING PLAN SHEET WITH SCHEDULE TO SUPPLIER FOR FIXTURE SELECTION. CONTRACTOR SHALL SUBMIT LIGHTING PLAN SHEET WITH SCHEDULE TO SUPPLIER FOR FIXTURE SELECTION. 3. SUPPLIER SHALL PROVIDE LIGHTING CALCULATIONS EQUAL OR BETTER THAN SPECIFIED FIXTURES. SUPPLIER SHALL PROVIDE LIGHTING CALCULATIONS EQUAL OR BETTER THAN SPECIFIED FIXTURES. CALCULATIONS SHALL BE PROVIDED FOR BOTH SPECIFIED AND SUBSTITUTED FIXTURES FOR COMPARISON.

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8,000

AutoCAD SHX Text 1,500

AutoCAD SHX Text

LED

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

LED

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

EXTERIOR CANOPY LIGHT

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

PCNY LED ALO2 SWW2 FPCL MVOLT DWHXD M3

AutoCAD SHX Text

EXTERIOR WALL PACK

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

ARC1 LED P1 40K MVOLT PE

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

PROVIDE WITH PHOTOCELL

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text 7,600

AutoCAD SHX Text

LED

AutoCAD SHX Text 40K

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DK BRONZE

AutoCAD SHX Text

EXTERIOR STRIP LIGHT

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

CLX L48 7000LM SEF RDL 40K 80CRI THCLX

AutoCAD SHX Text

AutoCAD SHX Text

1. COORDINATE LOCATION OF PANEL WITH UTILITY POLES. COORDINATE LOCATION OF PANEL WITH UTILITY POLES. COORDINATE LOCATION OF SIGN WITH OWNER.

3/31/26

SCALE: N1 ELECTRICAL SITE LIGHTING PLAN

1" = 20'-0"

INSTALLATION KEYED NOTES " # ":

SCALE: N2 ELECTRICAL - EQUIPMENT SHED PLAN

1/8" = 1'-0"

E2

EL

EC

TR

IC

AL

S

IT

E

PL

AN

PANEL "A"

AutoCAD SHX Text A-18

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-16

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-16

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-18

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-30

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-30

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text S

AutoCAD SHX Text

WR

AutoCAD SHX Text A-31,33,35

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text A-1,3,5

AutoCAD SHX Text F

AutoCAD SHX Text A-7,9,11

AutoCAD SHX Text A-13,15,17

AutoCAD SHX Text A-19,21,23

AutoCAD SHX Text A-25,27,29

AutoCAD SHX Text A-30

AutoCAD SHX Text

VIA PHOTOCELL

AutoCAD SHX Text A-34

AutoCAD SHX Text

VIA PHOTOCELL

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text S

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

WR

AutoCAD SHX Text A-32

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-32

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-32

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-32

AutoCAD SHX Text

WR

AutoCAD SHX Text

GFI

AutoCAD SHX Text A-32

AutoCAD SHX Text A-32

AutoCAD SHX Text

VIA PHOTOCELL

AutoCAD SHX Text G

AutoCAD SHX Text

REV.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

CLIENT DWG. NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

PROJECT/LOCATION

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

APPROVED BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

PROJECT MGR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

(919) 778-9064

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

P.O. BOX 11527

AutoCAD SHX Text

BY

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

GOLDSBORO, NC 27532

AutoCAD SHX Text

TEL:

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

BEAUFORT COUNTY

AutoCAD SHX Text

PROJNO

AutoCAD SHX Text

JDH

AutoCAD SHX Text

STILLEY STATION

AutoCAD SHX Text

NC LIC #: C-1132

AutoCAD SHX Text N/A

AutoCAD SHX Text

BLT

AutoCAD SHX Text

JDH

AutoCAD SHX Text

JDH

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text M

AutoCAD SHX Text

SEAL

AutoCAD SHX Text A

AutoCAD SHX Text 31466

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text J

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text

1. INSTALL PHOTOCELL ON TOP CORNER OF CANOPY FACING NORTH. INSTALL PHOTOCELL ON TOP CORNER OF CANOPY FACING NORTH. 2. PROVIDE (4) RECEPTACLES IN WORK SHED. COORDINATED LOCATIONS WITH PROVIDE (4) RECEPTACLES IN WORK SHED. COORDINATED LOCATIONS WITH OWNER. 3. PROVIDE POLE LIGHTS ALONG DUMPSTER WALL AS AN ALTERNATE PRICE IF PROVIDE POLE LIGHTS ALONG DUMPSTER WALL AS AN ALTERNATE PRICE IF CANOPY IS NOT A CHOSEN. PROVIDE WITH A 30' SQUARE ALUMINUM POLE (DARK BRONZE). UTILIZE CIRCUIT "A-34". 4. PANEL "B" IS LOCATED IN THE OFFICE. PANEL FURNISHED BY OTHERS, E.C. PANEL "B" IS LOCATED IN THE OFFICE. PANEL FURNISHED BY OTHERS, E.C. SHALL PROVIDE FEEDER AND CONNECT WIRING TO PANEL.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:5 DIRECT BURIED CONDUITS

N.T.S.

SCALE:7 TYPICAL BONDING & GROUNDING DIAGRAM

N.T.S.

SCALE:4 TYPICAL MADE GROUNDING ELECTRODE

N.T.S.

SCALE:1 SERVICE EQUIPMENT GROUNDING DIAGRAM

N.T.S.

SCALE:2 DEDICATED WORKING SPACE REQUIREMENTS

N.T.S.

SCALE:6 POLE INSTALLATION

N.T.S.

SCALE:3 ELECTRICAL DETAIL (MAIN ENTRANCE)

N.T.S.

E3

EL

EC

TR

IC

AL

D

ET

AI

LS

REV.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

CLIENT DWG. NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

PROJECT/LOCATION

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

APPROVED BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

PROJECT MGR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

(919) 778-9064

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

P.O. BOX 11527

AutoCAD SHX Text

BY

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

GOLDSBORO, NC 27532

AutoCAD SHX Text

TEL:

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

BEAUFORT COUNTY

AutoCAD SHX Text

PROJNO

AutoCAD SHX Text

JDH

AutoCAD SHX Text

STILLEY STATION

AutoCAD SHX Text

NC LIC #: C-1132

AutoCAD SHX Text N/A

AutoCAD SHX Text

BLT

AutoCAD SHX Text

JDH

AutoCAD SHX Text

JDH

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text M

AutoCAD SHX Text

SEAL

AutoCAD SHX Text A

AutoCAD SHX Text 31466

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text J

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text

SPACERS

AutoCAD SHX Text

4" DATA CONDUITS SCH 40 PVC

AutoCAD SHX Text

MARKER TAPE AND TRACER WIRE 12" ABOVE CONDUITS

AutoCAD SHX Text

24" MIN

AutoCAD SHX Text

CLEAN NATIVE SOIL OR SAND BACK FILL

AutoCAD SHX Text

EARTH FILL

AutoCAD SHX Text NOTES: 1. DIRECT BURIED CONDUITS APPLY TO BRANCH CIRCUITS FROM DIRECT BURIED CONDUITS APPLY TO BRANCH CIRCUITS FROM PANELBOARDS, DATA, AND SECURITY RACEWAYS. 2. UNDERGROUND WARNING TAPE: PROVIDE WATERPROOF MARKING CORD UNDERGROUND WARNING TAPE: PROVIDE WATERPROOF MARKING CORD (130-POUND TENSILE TEST MARKED AT LEAST EVERY FOOT EQUIVALENT TO GREENLEE NO. 435) IN ALL DUCTS, INCLUDING SPARES, ONCE CLEAN AND FREE OF OBSTRUCTIONS. INSTALL WARNING TAPE 24" ABOVE RACEWAY, OR 12" BELOW GRADE IF CONDUIT IS BURIED 24" BELOW GRADE. 3. PROVIDE GRC CONDUIT ELBOWS AT TURN UP TO EQUIPMENT AND AT PROVIDE GRC CONDUIT ELBOWS AT TURN UP TO EQUIPMENT AND AT BUILDING ENTRANCES THROUGH FLOOR. 4. THIS DETAIL IS TYPICAL FOR ALL CONDUITS REGARDLESS OF QUANTITY. THIS DETAIL IS TYPICAL FOR ALL CONDUITS REGARDLESS OF QUANTITY. SEE PLANS FOR EXACT SIZES AND QUANTITY.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. GROUNDING ELECTRODE CONDUCTOR SHALL BE RUN CONTINUOUSLY (UNBROKEN) GROUNDING ELECTRODE CONDUCTOR SHALL BE RUN CONTINUOUSLY (UNBROKEN) FROM COLD WATER LINE AND/OR BUILDING STEEL AND GROUND ROD TO GROUND BAR BEFORE BONDING TO ANY CONDUIT BUSHING. 2. ALL THE FOLLOWING GROUNDING ELECTRODES THAT ARE AVAILABLE SHALL BE ALL THE FOLLOWING GROUNDING ELECTRODES THAT ARE AVAILABLE SHALL BE BONDED TOGETHER TO FORM THE GROUNDING ELECTRODE SYSTEM PER NEC 250.52: 2.1. METAL UNDERGROUND WATER PIPE IN DIRECT CONTACT WITH EARTH FOR 10 FT METAL UNDERGROUND WATER PIPE IN DIRECT CONTACT WITH EARTH FOR 10 FT OR MORE 2.2. METAL FRAME OF THE BUILDING, METAL FRAME OF THE BUILDING, 2.3. ANY ELECTRODE ENCASED BY AT LEAST 2 IN. OF CONCRETE, CONSISTING OF ANY ELECTRODE ENCASED BY AT LEAST 2 IN. OF CONCRETE, CONSISTING OF 20 FT OR MORE BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS NOT LESS THAN 1/2" IN DIAMETER. 2.4. GROUND RING ENCIRCLING THE BUILDING GROUND RING ENCIRCLING THE BUILDING 2.5. ROD AND PIPE ELECTRODES NOT LESS THAN 8 FT. ROD AND PIPE ELECTRODES NOT LESS THAN 8 FT. 2.6. PLATE ELECTRODESPLATE ELECTRODES

AutoCAD SHX Text MAIN BONDING JUMPER - PROVIDE AT FACTORY OR SIZED PER NEC TABLE 250-102(C)(1)250-102(C)(1)

AutoCAD SHX Text

INCOMING NEUTRAL/GROUND CONDUCTOR

AutoCAD SHX Text

LIGHTING OR POWER PANELBOARD CABINET (208 VOLT)

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text

BUSHING

AutoCAD SHX Text

LOCKNUT

AutoCAD SHX Text

LOCKNUT

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

PANEL CAN OR ENCLOSURE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

NEUTRAL BAR (NOT GROUNDED HERE)

AutoCAD SHX Text

NEUTRAL BAR

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

PLASTIC BUSHING

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

CONNECTION (TYPICAL)

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text

MAIN (208 VOLT) PANELBOARD OR SWITCHBOARD CABINET

AutoCAD SHX Text

BONDING BUSHING

AutoCAD SHX Text

SERVICE ENTRANCE CONDUIT

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

PLASTIC BUSHING

AutoCAD SHX Text

EQUIVALENT CONNECTION (TYPICAL)

AutoCAD SHX Text

10' MIN.

AutoCAD SHX Text

(TYPICAL)

AutoCAD SHX Text

10' X 3/4" (THREE REQUIRED)

AutoCAD SHX Text

COPPERCLAD OR COPPERWELD STEEL ROD,

AutoCAD SHX Text

TO SERVICE EQUIPMENT

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text

AS SHOWN ON POWER

AutoCAD SHX Text

RISER DIAGRAM & GROUNDING SCHEMATIC

AutoCAD SHX Text

CADWELD, THERMOWELD OR

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

MIN. #3/0 BARE STRANDED COPPER, UNO. BURY 30" BELOW GRADE.

AutoCAD SHX Text

SERVICE EQUIPMENT NEUTRAL BAR

AutoCAD SHX Text

JUMPER

AutoCAD SHX Text

WATER VALVE

AutoCAD SHX Text

BUILDING STRUCTURE

AutoCAD SHX Text

GROUND CLAMP

AutoCAD SHX Text

EXOTHERMIC WELD

AutoCAD SHX Text

GROUND CONDUCTOR

AutoCAD SHX Text

TO FOOTING REINFORCING STEEL IF ACCESSIBLE

AutoCAD SHX Text

(MAX REQUIRED SIZE #4 AWG)

AutoCAD SHX Text

JUMPER SIZED PER NEC TABLE 250-66 OR 250-28D

AutoCAD SHX Text

BUS-BAR OR CONDUCTOR

AutoCAD SHX Text

GROUND BUSHING ON METALLIC CONDUITS

AutoCAD SHX Text

SUPPLY SIDE

AutoCAD SHX Text

(3) 3/4" x 10' GROUND RODS

AutoCAD SHX Text

TABLE 250.122

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

#6 BARE COPPER

AutoCAD SHX Text

GROUNDING CONDUCTOR SIZE = #1/0 AWG

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXOTHERMIC WELD

AutoCAD SHX Text 4"x24"x1/4" THICK COPPER GROUND BAR UL LISTED AND FACTORY DRILLED

AutoCAD SHX Text NOTES: 1. ALL UNDERGROUND CONNECTIONS SHALL BE EXOTHERMIC WELDS OR IRREVERSIBLE ALL UNDERGROUND CONNECTIONS SHALL BE EXOTHERMIC WELDS OR IRREVERSIBLE COMPRESSION CONNECTIONS, EXCEPT MECHANICAL CONNECTIONS IN TEST WELLS. 2. LABEL RACEWAYS OR CONDUCTORS AT GROUND BUS WITH PHENOLIC TAGS TO IDENTIFY LABEL RACEWAYS OR CONDUCTORS AT GROUND BUS WITH PHENOLIC TAGS TO IDENTIFY CONNECTION LOCATION SUCH AS: "GAS PIPING", "GROUND RODS" OR "BUILDING STEEL".

AutoCAD SHX Text %%uALL ELECTRIC EQUIPMENT

AutoCAD SHX Text 1 2 3

AutoCAD SHX Text

VOLTAGE TO GROUND

AutoCAD SHX Text

WORKING CLEARANCES

AutoCAD SHX Text

(NOMINAL)

AutoCAD SHX Text 151-600

AutoCAD SHX Text 0-150

AutoCAD SHX Text

(MINIMUM CLEAR DISTANCE)

AutoCAD SHX Text

TABLE "A"

AutoCAD SHX Text 3'

AutoCAD SHX Text 3'

AutoCAD SHX Text

CONDITION:

AutoCAD SHX Text 3'

AutoCAD SHX Text 3 1/2'

AutoCAD SHX Text 25'-0"

AutoCAD SHX Text

SEE TABLE "A"

AutoCAD SHX Text

THIS DISTANCE

AutoCAD SHX Text

LIGHT FIXTURE

AutoCAD SHX Text

WALL

AutoCAD SHX Text %%uPANELBOARDS

AutoCAD SHX Text

LIGHT FIXTURE

AutoCAD SHX Text

PANELBOARD

AutoCAD SHX Text

WALL

AutoCAD SHX Text 4'

AutoCAD SHX Text 3'

AutoCAD SHX Text WHERE THE "CONDITIONS" ARE AS FOLLOWS: 1. EXPOSED LIVE PARTS ON ONE SIDE AND NO LIVE OR GROUNDED PARTS ON THE EXPOSED LIVE PARTS ON ONE SIDE AND NO LIVE OR GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING SPACE, OR EXPOSED LIVE PARTS ON BOTH SIDES EFFECTIVELY GUARDED BY SUITABLE WOOD OR OTHER INSULATING MATERIALS. INSULATED WIRE OR INSULATED BUSBARS OPERATING AT NOT OVER 300 VOLTS SHALL NOT BE CONSIDERED LIVE PARTS. 2. EXPOSED LIVE PARTS ON ONE SIDE AND GROUNDED PARTS ON THE OTHER SIDE. EXPOSED LIVE PARTS ON ONE SIDE AND GROUNDED PARTS ON THE OTHER SIDE. 3. EXPOSED LIFE PARTS ON BOTH SIDES OF THE WORK SPACE (NOT GUARDED AS EXPOSED LIFE PARTS ON BOTH SIDES OF THE WORK SPACE (NOT GUARDED AS PROVIDED IN CONDITION 1) WITH THE OPERATOR BETWEEN.

AutoCAD SHX Text DEDICATED SPACE CONTINUES THROUGH SUSPENDED CEILING TO 6' ABOVE ELECTRICAL EQUIPMENT OR STRUCTURAL CEILING, WHICHEVER IS LOWER.

AutoCAD SHX Text

STRUCTURAL CEILING

AutoCAD SHX Text

SUSPENDED CEILING

AutoCAD SHX Text

EXCLUSIVELY DEDICATED SPACE

AutoCAD SHX Text

EXCLUSIVELY DEDICATED SPACE

AutoCAD SHX Text

STRUCTURAL CEILING

AutoCAD SHX Text

SUSPENDED CEILING

AutoCAD SHX Text

EXCLUSIVELY DEDICATED SPACE

AutoCAD SHX Text

ELECTRIC EQUIPMENT

AutoCAD SHX Text

PLANE OF FRONT EDGE OF ELECTRIC EQUIPMENT

AutoCAD SHX Text

6 1/2' MINIMUM OR HEIGHT OF EQUIPMENT

AutoCAD SHX Text 30" OR WIDTH OF EQUIPMENT IF EQUIPMENT IS WIDER THAN 30" DOES NOT HAVE TO BE CENTERED ON THE EQUIPMENT BUT AT LEAST EVEN WITH ONE EDGE. EQUIPMENT DOOR SHALL BE ABLE TO OPEN AT LEAST 90°.

AutoCAD SHX Text NOTES: 1. THIS FIGURE ILLUSTRATES THE ADDITIONAL EXCLUSIVELY THIS FIGURE ILLUSTRATES THE ADDITIONAL EXCLUSIVELY DEDICATED SPACE REQUIRED OVER AND UNDER PANELBOARDS FOR CABLES, RACEWAYS, ETC. TO AND FROM PANELBOARDS REQUIRED BY NEC SECTION 110-26. 2. NO PIPING DUCTWORK OR EQUIPMENT FOREIGN TO THE NO PIPING DUCTWORK OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THROUGH THE DEDICATED SPACES SHOWN. FOR EXCEPTIONS SEE NEC SECTION 110-26f.

AutoCAD SHX Text NOTES: 1. THIS FIGURE ILLUSTRATES THE WORKING SPACE IN THIS FIGURE ILLUSTRATES THE WORKING SPACE IN FRONT OF ELECTRICAL EQUIPMENT REQUIRED BY NEC SECTION 110-26. 2. THIS INCLUDES BUT IS NOT LIMITED TO PANELBOARDS, THIS INCLUDES BUT IS NOT LIMITED TO PANELBOARDS, SAFETY SWITCHES, MOTOR STARTERS, JUNCTION BOXES AND OTHER ELECTRICAL EQUIPMENT.

AutoCAD SHX Text 34'

AutoCAD SHX Text

NEMA 3R JUNCTION

AutoCAD SHX Text

BOX (TYP.)

AutoCAD SHX Text

#8 IN 1" PVC

AutoCAD SHX Text

(2) #12, (1) #12 IN 1/2" PVC

AutoCAD SHX Text

PROVIDE 40' CLASS 5 TREATED WOOD POLES

AutoCAD SHX Text

PROVIDE FIXTURE, BRACKETS & HARDWARE

AutoCAD SHX Text

GRADE

AutoCAD SHX Text 6'

AutoCAD SHX Text

1" PVC TO ALL POLES.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. SETTING POLES ON SLOPING GROUND, MEASURE THE DEPTH OF THE HOLE FROM SETTING POLES ON SLOPING GROUND, MEASURE THE DEPTH OF THE HOLE FROM THE LOW SIDE OF THE HOLE. 2. TAMP POLE BACKFILL FOR THE FULL DEPTH OF THE HOLE AND MOUND THE TAMP POLE BACKFILL FOR THE FULL DEPTH OF THE HOLE AND MOUND THE EXCESS FILL AROUND THE POLE. 3. WOOD POLES SHALL BE INSPECTED AND COMPLY WITH ANSI O5.1 AND RUS BULL WOOD POLES SHALL BE INSPECTED AND COMPLY WITH ANSI O5.1 AND RUS BULL 1728F-700. GAIN, BORE, AND ROOF POLES BEFORE TREATMENT. TREAT FULL LENGTH WITH CCA OR ACA ACCORDING TO AWPA T1 AND AWPA U1. PROVIDE POLES BRANDED BY MANUFACTURER WITH MANUFACTURER'S MARK AND DATE OF TREATMENT, HEIGHT AND CLASS OF POLE, WOOD SPECIES, PRESERVATION CODE, AND RETENTION.

AutoCAD SHX Text

6" X 6" PRESSURE TREATED TIMBER OR PRESSURE TREATED POLE

AutoCAD SHX Text

WEATHERHEAD

AutoCAD SHX Text

ATTACHMENT POINT

AutoCAD SHX Text

DUKE ENERGY SERVICE CABLE

AutoCAD SHX Text

POINT OF DELIVERY

AutoCAD SHX Text

RISER

AutoCAD SHX Text

METER ENCLOSURE

AutoCAD SHX Text

PANELBOARD

AutoCAD SHX Text

GROUND WIRE

AutoCAD SHX Text

FINAL GRADE

AutoCAD SHX Text

4' TO 5'-6"

AutoCAD SHX Text

14' MIN.

AutoCAD SHX Text

20'-0" CLASS 10

AutoCAD SHX Text

5'-0" POLE DEPTH

AutoCAD SHX Text

* TYPICAL GROUNDING ELECTRODE PER N.E.C. (SEE FIG. 14A)

AutoCAD SHX Text

* UPPER END OF GROUND ROD SHALL BE FLUSH WITH OR BELOW FINAL GRADE UNLESS THE ROD END AND GROUND CONDUCTOR ATTACHMENT ARE PROTECTED AGAINST PHYSICAL DAMAGE.

AutoCAD SHX Text NOTES: : 1. UTILITY COMPANY FURNISHES AND INSTALLS SERVICE UTILITY COMPANY FURNISHES AND INSTALLS SERVICE CABLE AND APPROPRIATE METER. 2. CONTRACTOR FURNISHES AND INSTALLS PROPERLY CONTRACTOR FURNISHES AND INSTALLS PROPERLY SIZED TIMBER/POLE, RISER, WEATHERHEAD, ATTACHMENT POINT, METER ENCLOSURE, GROUNDING AND ALL OTHER ITEMS BEYOND POINT OF DELIVERY.

PANELBOARD SCHEDULESERVICE LOAD SUMMARY (PANELBOARD "A")

SCALE:1 ELECTRICAL RISER

N.T.S.

INSTALLATION KEYED NOTES " # ":

SCALE:2 ELECTRICAL RISER (MAIN ENTRANCE)

N.T.S.

PANELBOARD SCHEDULE

SCALE:3 SERVICE EQUIPMENT SUPPORT DETAIL

N.T.S. E4

EL

EC

TR

IC

AL

R

IS

ER

S

SC

H

ED

U

LE

S

AutoCAD SHX Text

REV.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

CLIENT DWG. NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

PROJECT/LOCATION

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

APPROVED BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

PROJECT MGR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

(919) 778-9064

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

P.O. BOX 11527

AutoCAD SHX Text

BY

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

GOLDSBORO, NC 27532

AutoCAD SHX Text

TEL:

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

BEAUFORT COUNTY

AutoCAD SHX Text

PROJNO

AutoCAD SHX Text

JDH

AutoCAD SHX Text

STILLEY STATION

AutoCAD SHX Text

NC LIC #: C-1132

AutoCAD SHX Text N/A

AutoCAD SHX Text

BLT

AutoCAD SHX Text

JDH

AutoCAD SHX Text

JDH

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text M

AutoCAD SHX Text

SEAL

AutoCAD SHX Text A

AutoCAD SHX Text 31466

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text J

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text

LOAD SERVED

AutoCAD SHX Text

WIRE SIZE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WIRE SIZE

AutoCAD SHX Text

LOAD (AMPS)

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

NO.

AutoCAD SHX Text

CKT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

22K AIC

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

CKT

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

LOAD SERVED

AutoCAD SHX Text

LOAD (AMPS)

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text 3R

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

NEMA

AutoCAD SHX Text

MOUNTED

AutoCAD SHX Text

COPPER BUS

AutoCAD SHX Text

FEED

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

BOTTOM

AutoCAD SHX Text

VOLT

AutoCAD SHX Text

AMP (FEEDER SIZE)

AutoCAD SHX Text 120/208

AutoCAD SHX Text

AutoCAD SHX Text

3%%C, 4 WIRE

AutoCAD SHX Text

BOLT ON BREAKER

AutoCAD SHX Text

AMP (BUS RATING)

AutoCAD SHX Text

AutoCAD SHX Text

SERVICE ENTRANCE RATED

AutoCAD SHX Text

COMPACTOR #6

AutoCAD SHX Text 3#2 & 1#6G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SHED LTS & RECP.

AutoCAD SHX Text

MULTI-MAT. LIGHTING

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

SPARE

AutoCAD SHX Text 2#4 & 1#4G

AutoCAD SHX Text 2#10 & 1#10G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2#4 & 1#4G

AutoCAD SHX Text 2#8 & 1#8G

AutoCAD SHX Text

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

DROP-OFF LTG

AutoCAD SHX Text 2#8 & 1#8G

AutoCAD SHX Text 1"

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

PANEL B

AutoCAD SHX Text 3#3 & 1#8G.

AutoCAD SHX Text 2"

AutoCAD SHX Text COORDINATE BREAKERS AND WIRE SIZES FOR OWNER FURNISHED EQUIPMENT WITH SUBMITTALS PROVIDE SEPARATE NEUTRALS FOR ALL CIRCUITS.

AutoCAD SHX Text

1 HORSEPOWER UNKNOWN. CONTRACTOR TO VERIFY WIRE AND BREAKER SIZES.

AutoCAD SHX Text 2 PROVIDE JUNCTION BOX AT DEVICE TO ALLOW SPLICE IN WIRING DOWN TO MATCH DEVICE RATINGS.

AutoCAD SHX Text

3 WIRE LIGHTS THROUGH PHOTOCELL.

AutoCAD SHX Text

AutoCAD SHX Text

COMPACTOR #1

AutoCAD SHX Text 3#2 & 1#6G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

COMPACTOR #2

AutoCAD SHX Text 3#6 & 1#8G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

COMPACTOR #3

AutoCAD SHX Text 3#4 & 1#6G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

COMPACTOR #4

AutoCAD SHX Text 3#4 & 1#6G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

COMPACTOR #5

AutoCAD SHX Text 3#6 & 1#8G

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

SITE LIGHTING

AutoCAD SHX Text 2#6 & 1#6G

AutoCAD SHX Text 1"

AutoCAD SHX Text

SITE LIGHITING

AutoCAD SHX Text 2#8 & 1#8G

AutoCAD SHX Text 1"

AutoCAD SHX Text

SITE LIGHTING

AutoCAD SHX Text 2#6 & 1#6G

AutoCAD SHX Text 1"

AutoCAD SHX Text

(MULTI-MATERIAL)

AutoCAD SHX Text

(PRECRUSHER)

AutoCAD SHX Text

(PRECRUSHER)

AutoCAD SHX Text

30HP

AutoCAD SHX Text

30HP

AutoCAD SHX Text

15HP

AutoCAD SHX Text

15HP

AutoCAD SHX Text

15HP

AutoCAD SHX Text

15HP

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text 0.208

AutoCAD SHX Text

KVA

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

0.208 x

AutoCAD SHX Text

KVA (TRANSFORMER)

AutoCAD SHX Text 3 x %%%Z

AutoCAD SHX Text

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

FAULT CURRENT @ TRANSFORMER SECONDARY TERMINALS

AutoCAD SHX Text

SERVICE LOAD

AutoCAD SHX Text 1.5

AutoCAD SHX Text 27,800

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OCCUPANCY TYPE - SITE LIGHTINGSITE LIGHTING

AutoCAD SHX Text

BUILDING AREA - XX SQUARE FEETXX SQUARE FEET

AutoCAD SHX Text

CONTINUOUS LOAD DESCRIPTION

AutoCAD SHX Text

LOAD (KVA)

AutoCAD SHX Text

NEC REFERENCE

AutoCAD SHX Text

DEMAND FACTOR

AutoCAD SHX Text

NEC REFERENCE

AutoCAD SHX Text

LOAD (KVA)

AutoCAD SHX Text

INDOOR LIGHTING

AutoCAD SHX Text 1.0

AutoCAD SHX Text

TABLE 220.12

AutoCAD SHX Text 100%

AutoCAD SHX Text

TABLE 220.42

AutoCAD SHX Text 1.0

AutoCAD SHX Text

OUTDOOR LIGHTING

AutoCAD SHX Text 7.5

AutoCAD SHX Text

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text 7.5

AutoCAD SHX Text

SIGN LIGHTING

AutoCAD SHX Text 1.2

AutoCAD SHX Text

220.14 F

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text 1.2

AutoCAD SHX Text

LARGEST COMPACTOR MOTOR (30HP)

AutoCAD SHX Text 33.0

AutoCAD SHX Text

ARTICLE 430

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text 33.0

AutoCAD SHX Text

PACKAGED HVAC UNITS

AutoCAD SHX Text 3.5

AutoCAD SHX Text

ARTICLE 440

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text 3.5

AutoCAD SHX Text

AIR HANDLER FANS (SPLIT SYSTEMS)

AutoCAD SHX Text

ARTICLE 440

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AIR HANDLER ELECTRIC HEAT

AutoCAD SHX Text 422.12

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE BUILDING

AutoCAD SHX Text 12.0

AutoCAD SHX Text

AutoCAD SHX Text 100%

AutoCAD SHX Text

AutoCAD SHX Text 12.0

AutoCAD SHX Text

SUBTOTAL CONTINUOUS LOADS

AutoCAD SHX Text 58.2

AutoCAD SHX Text

230.42 A 1

AutoCAD SHX Text x 125%

AutoCAD SHX Text

CONT. LOAD TOTAL

AutoCAD SHX Text 72.8

AutoCAD SHX Text

NON CONTINUOUS LOAD DESCRIPTION

AutoCAD SHX Text

RECEPTACLES UP TO 10 KVA

AutoCAD SHX Text 1.6

AutoCAD SHX Text

220.14 1

AutoCAD SHX Text 100% OF 1st 10 KVA

AutoCAD SHX Text 1.6

AutoCAD SHX Text

RECEPTACLES OVER 10 KVA

AutoCAD SHX Text 0.0

AutoCAD SHX Text

220.14 1

AutoCAD SHX Text

50% ABOVE 10 KVA

AutoCAD SHX Text 0.0

AutoCAD SHX Text

COMPACTOR MOTORS (1-30HP & 3-15HP)

AutoCAD SHX Text 84.0

AutoCAD SHX Text

AutoCAD SHX Text DIVERSITY x 80%

AutoCAD SHX Text 67.2

AutoCAD SHX Text

FUTURE COMPACTOR MOTOR (1)

AutoCAD SHX Text 15.0

AutoCAD SHX Text

AutoCAD SHX Text DIVERSITY x 20%

AutoCAD SHX Text 3.0

AutoCAD SHX Text

MISC. LOADS

AutoCAD SHX Text 0.0

AutoCAD SHX Text

AutoCAD SHX Text NONCONTINUOUS LOAD x 100%

AutoCAD SHX Text 0.0

AutoCAD SHX Text

SUBTOTAL NON-CONTINUOUS LOADS

AutoCAD SHX Text 71.8

AutoCAD SHX Text

TOTAL CONTINUOUS AND NON CONTINUOUS LOADS

AutoCAD SHX Text 144.6

AutoCAD SHX Text 120/208V 3%%C

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

NEW UTILITY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CP-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CP-2

AutoCAD SHX Text 3R

AutoCAD SHX Text

400 AMP

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

4 WIRE

AutoCAD SHX Text 120/208V

AutoCAD SHX Text 3%%C

AutoCAD SHX Text #1/0G

AutoCAD SHX Text

PANEL A

AutoCAD SHX Text M

AutoCAD SHX Text

CT CABINET

AutoCAD SHX Text

4#500 IN 3"C.

AutoCAD SHX Text

1. COORDINATE WITH UTILITY FOR UNDERGROUND CONDUIT COORDINATE WITH UTILITY FOR UNDERGROUND CONDUIT REQUIREMENTS.

AutoCAD SHX Text

NEW

AutoCAD SHX Text

PANEL BY OTHERS

AutoCAD SHX Text

GROUND RODS

AutoCAD SHX Text 3R

AutoCAD SHX Text

CP-3

AutoCAD SHX Text 3R

AutoCAD SHX Text

CP-4

AutoCAD SHX Text 3R

AutoCAD SHX Text

CP-5

AutoCAD SHX Text 3R

AutoCAD SHX Text

CP-6

AutoCAD SHX Text 3R

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

100 AMP

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

4 WIRE

AutoCAD SHX Text 120/208V

AutoCAD SHX Text 3%%C

AutoCAD SHX Text

PANEL B

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text 2(3)"C.

AutoCAD SHX Text

WIRING BY UTILITY CO.

AutoCAD SHX Text

3#3 & 1#8G. IN 2"C.

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

UTILITY

AutoCAD SHX Text

NEW

AutoCAD SHX Text 240V 1%%C

AutoCAD SHX Text M

AutoCAD SHX Text

WIRING BY UTILITY CO.

AutoCAD SHX Text

4#3 IN 2"C.

AutoCAD SHX Text

NEW

AutoCAD SHX Text

METER

AutoCAD SHX Text

LOAD SERVED

AutoCAD SHX Text

WIRE SIZE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WIRE SIZE

AutoCAD SHX Text

LOAD (AMPS)

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

NO.

AutoCAD SHX Text

CKT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

10K AIC

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

CKT

AutoCAD SHX Text

AutoCAD SHX Text

LOAD SERVED

AutoCAD SHX Text

LOAD (AMPS)

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text 3R

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

NEMA

AutoCAD SHX Text

MOUNTED

AutoCAD SHX Text

COPPER BUS

AutoCAD SHX Text

FEED

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

TOP

AutoCAD SHX Text

VOLT

AutoCAD SHX Text

AMP (FEEDER SIZE)

AutoCAD SHX Text 120/240

AutoCAD SHX Text

AutoCAD SHX Text

1%%C, 3 WIRE

AutoCAD SHX Text

BOLT ON BREAKER

AutoCAD SHX Text

AMP (BUS RATING)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GATE MOTOR

AutoCAD SHX Text 2#12 & 1#12G

AutoCAD SHX Text 1"

AutoCAD SHX Text

SITE SIGN

AutoCAD SHX Text 2#12 & 1#12G

AutoCAD SHX Text 1"

AutoCAD SHX Text COORDINATE BREAKERS AND WIRE SIZES FOR OWNER FURNISHED EQUIPMENT WITH SUBMITTALS PROVIDE SEPARATE NEUTRALS FOR ALL CIRCUITS.

AutoCAD SHX Text

1 HORSEPOWER UNKNOWN. CONTRACTOR TO VERIFY WIRE AND BREAKER SIZES.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text #4G

AutoCAD SHX Text

(3) NEW

AutoCAD SHX Text

GROUND RODS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 12" x30" DEEPCONCRETE CAISSON

AutoCAD SHX Text

POST CAP

AutoCAD SHX Text

2" GALVANIZED POST

AutoCAD SHX Text

1 5/8" MIN, 12 GA. HOT DIP SUPPORT CHANNEL

AutoCAD SHX Text

TO UTILITY POLE

AutoCAD SHX Text

PANELBOARD "A"

AutoCAD SHX Text

METER

AutoCAD SHX Text CT CABINET 30"x30" PROVIDE 3/4" PLYWOOD BACKER

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LOAD (KVA)

AutoCAD SHX Text

OUTDOOR LIGHTING

AutoCAD SHX Text

AutoCAD SHX Text

GROSS PHASE TOTALS (AMPS) A = 12 B = 12

AutoCAD SHX Text

CONNECTED

AutoCAD SHX Text

LOAD (KVA)

AutoCAD SHX Text

DEMAND

AutoCAD SHX Text

TOTALS:

AutoCAD SHX Text

= 2.9 KVA

AutoCAD SHX Text

DEMAND

AutoCAD SHX Text

FACTOR

AutoCAD SHX Text

MINIMUM PANEL SIZE: 3 KVA X 125%%% = 4 KVA (15 AMPS)

AutoCAD SHX Text = 1.4

AutoCAD SHX Text

DEDICATED RECP/EQUIP

AutoCAD SHX Text

INDOOR LIGHTING

AutoCAD SHX Text

AutoCAD SHX Text 100%

AutoCAD SHX Text 100%

AutoCAD SHX Text 100%%%

AutoCAD SHX Text

SIGN

AutoCAD SHX Text = 1.4

AutoCAD SHX Text 100%

AutoCAD SHX Text

= 2.9 KVA

AutoCAD SHX Text = 1.4

AutoCAD SHX Text = 1.4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

100 AMP

AutoCAD SHX Text

NEMA 3R

AutoCAD SHX Text

MAIN BKR

AutoCAD SHX Text

3 WIRE

AutoCAD SHX Text 120/240V

AutoCAD SHX Text 1%%C

AutoCAD SHX Text

PANEL C

AutoCAD SHX Text

NEW

ELECTRICAL NOTESELECTRICAL LEGEND

SCALE:1 POLE BASE DETAIL (ALT @ DUMPTERS)

N.T.S. E5

EL

EC

TR

IC

AL

N

O

TE

S

AutoCAD SHX Text

REV.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

CLIENT DWG. NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

PROJECT/LOCATION

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

APPROVED BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

PROJECT MGR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

(919) 778-9064

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

P.O. BOX 11527

AutoCAD SHX Text

BY

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

GOLDSBORO, NC 27532

AutoCAD SHX Text

TEL:

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

BEAUFORT COUNTY

AutoCAD SHX Text

PROJNO

AutoCAD SHX Text

JDH

AutoCAD SHX Text

STILLEY STATION

AutoCAD SHX Text

NC LIC #: C-1132

AutoCAD SHX Text N/A

AutoCAD SHX Text

BLT

AutoCAD SHX Text

JDH

AutoCAD SHX Text

JDH

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text 03/31/2026

AutoCAD SHX Text M

AutoCAD SHX Text

SEAL

AutoCAD SHX Text A

AutoCAD SHX Text 31466

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text J

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text : GENERAL 1. ELECTRICAL PLANS ARE INTENDED TO PROVIDE INFORMATION FOR INSTALLATION OF A ELECTRICAL PLANS ARE INTENDED TO PROVIDE INFORMATION FOR INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM. PROVIDE ALL ESSENTIAL LABOR, MATERIALS & DEVICES REQUIRED TO PRODUCE A QUALITY END PRODUCT. THIS INCLUDES ALL REQUIRED CONTROL WIRING OR WIRING CALLED FOR BY THE MANUFACTURER AND OTHER MISCELLANEOUS ITEMS REQUIRED FOR THE OPERATION OF THE SYSTEM, WHETHER SPECIFICALLY CALLED OUT OR NOT. INSTALLATION SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS. 2. CONTRACTOR SHALL REVIEW & BECOME FAMILIAR WITH THE WORK OF ALL TRADES CONTRACTOR SHALL REVIEW & BECOME FAMILIAR WITH THE WORK OF ALL TRADES FOR PURPOSES OF COORDINATION AND ROUTING. CONTRACTOR SHALL PROVIDE REQUIRED PLANNING, COORDINATION AND SEQUENCING OF ELECTRICAL INSTALLATION WITH BUILDING COMPONENTS AND OTHER TRADES. 3. ALL WORK SHALL COMPLY WITH THE 2020 VERSION OF THE NATIONAL ELECTRICAL ALL WORK SHALL COMPLY WITH THE 2020 VERSION OF THE NATIONAL ELECTRICAL CODE (NEC). WORKMANSHIP SHALL MEET OR EXCEED INDUSTRY STANDARDS. 4. BEFORE SUBMITTING SHOP DRAWINGS TO ENGINEER FOR REVIEW, ELECTRICAL BEFORE SUBMITTING SHOP DRAWINGS TO ENGINEER FOR REVIEW, ELECTRICAL CONTRACTOR SHALL REVIEW, STAMP, AND COORDINATE SUBMITTALS (SHOP DRAWINGS) WITH OTHER SUBMITTALS AND WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. BY APPROVAL AND SUBMITTAL OF SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND SIMILAR SUBMITTALS TO THE ENGINEER, THE CONTRACTOR REPRESENTS THAT IT HAS DETERMINED AND VERIFIED AND CHECKED THE INFORMATION WITHIN THE SUBMITTAL WITH THE REQUIREMENTS OF THE WORK AND THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR AND SHALL DETERMINE AND VERIFY ALL FIELD MEASUREMENTS, QUANTITIES, DIMENSIONS, AND INSTALLATION REQUIREMENTS. PROVIDE WRITTEN NOTICE ON SUBMITTAL OF ANY DEVIATIONS. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR DEVIATIONS FROM CONTRACT DOCUMENTS REQUIREMENTS BY THE ARCHITECT'S APPROVAL OF SHOP DRAWINGS OR OTHER SUBMITTALS UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE ENGINEER IN WRITING OF SUCH DEVIATION AT THE TIME OF THE SUBMITTAL AND SUCH DEVIATION HAS BEEN APPROVED IN WRITING. ALL OPTIONS AND ACCESSORIES SHALL BE CLEARLY MARKED ON THE CUTSHEETS. 5. THE CITED EXAMPLES OF PRODUCTS ARE USED ONLY TO DENOTE THE QUALITY THE CITED EXAMPLES OF PRODUCTS ARE USED ONLY TO DENOTE THE QUALITY STANDARD OF PRODUCT DESIRED AND THEY DO NOT RESTRICT BIDDERS TO A SPECIFIC BRAND, MAKE, MANUFACTURER OR SPECIFIC NAME; THAT THEY ARE USED ONLY TO SET FORTH AND CONVEY TO BIDDERS THE GENERAL STYLE, TYPE, CHARACTER AND QUALITY OF PRODUCT DESIRED; AND THAT EQUIVALENT PRODUCTS WILL BE ACCEPTABLE. 6. PROTECT ALL NEW MATERIALS FROM THE WEATHER IN STORAGE TRAILERS OR PROVIDE PROTECT ALL NEW MATERIALS FROM THE WEATHER IN STORAGE TRAILERS OR PROVIDE SUITABLE COVERING. 7. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL DISCONNECTS, STARTERS, DEVICES AND ELECTRICAL CONTRACTOR SHALL PROVIDE ALL DISCONNECTS, STARTERS, DEVICES AND ELECTRICAL COMPONENTS UNLESS SPECIFICALLY NOTED AS PROVIDED BY OTHERS. COORDINATE LOCATION AND WIRING OF DEVICES WITH OTHER TRADES OR SUPPLIERS OF EQUIPMENT SUCH AS: ELEVATOR, FIRE PUMP AND FIRE PROTECTION PLANS, KITCHEN HOOD, KITCHEN COOLER, ETC. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL FIELD WIRING OF SPECIALTY ITEMS UNLESS NOTED OTHERWISE. 8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LINE AND LOAD SIDE WIRING INCLUDING ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LINE AND LOAD SIDE WIRING INCLUDING ALL TERMINATIONS TO EQUIPMENT PROVIDED UNDER OTHER TRADES. POWER WIRING TO CONTROL DEVICES SHALL BE PROVIDED BY E.C.. INTERLOCK WIRING SHALL BE PROVIDED BY THE CONTRACTOR INSTALLING THE CONTROL DEVICE. 9. ALL WIRING, PANELBOARDS, DEVICES AND OTHER LIKE MATERIALS SHALL BE UL LISTED ALL WIRING, PANELBOARDS, DEVICES AND OTHER LIKE MATERIALS SHALL BE UL LISTED & LABELED. ALL MATERIALS SHALL MEET THE NEC FOR THE INTENDED USE AND INSTALLED IN ACCORDANCE WITH THE NEC. LOW VOLTAGE CONDUCTORS (600V OR LESS) 10. PROVIDE THHN/THWN COPPER WIRE (UL 83 LISTED). PROVIDE A MINIMUM WIRE SIZE PROVIDE THHN/THWN COPPER WIRE (UL 83 LISTED). PROVIDE A MINIMUM WIRE SIZE OF #12. ALL WIRE #8 AWG AND LARGER SHALL BE STRANDED, #10 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS AND CONDUIT ON PLANS AND SCHEDULES REFLECT AMPACITIES PER NEC TABLE 310.16 75C RATING. CONTRACTOR SHALL VERIFY ALL TERMINATIONS, LUGS, ETC. ARE RATED FOR USE PER NEC 110.14(C). OTHERWISE PROVIDE CONDUCTOR AND CONDUIT SIZED PER LOWEST TEMPERATURE RATING OF ANY TERMINATION WITHIN A CIRCUIT. A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE PROVIDED FOR ALL CIRCUITS. ALL EQUIPMENT FEEDERS SHALL BE RUN CONTINUOUS FROM THE BREAKER TO THE DISCONNECT SWITCH; SPLICES ARE NOT ALLOWED. WHERE MORE THAN THREE CURRENT-CARRYING CONDUCTORS ARE INSTALLED IN THE SAME RACEWAY, DERATE PER NEC TABLE 310.15(C)(1). #10 AWG #10 AWG SHALL BE USED FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A TOTAL INSTALLED LENGTH GREATER THAN 100 FEET. WHERE THE CONDUCTOR LENGTH FROM THE PANEL TO THE FIRST OUTLET ON A 120 VOLT CIRCUIT EXCEEDS 100 FEET, THE CONDUCTOR TO THE FIRST OUTLET SHALL NOT BE SMALLER THAN #10 AWG. WHERE WHERE WHERE THE CONDUCTOR LENGTH IS GREATER THAN 150 FEET, THEN USE #8 AWG, AND IF GREATER THAN 250 FEET, USE #6 AWG. 11. COLOR CODING OF WIRE SHALL BE AS FOLLOWS: COLOR CODING OF WIRE SHALL BE AS FOLLOWS: 208/120V PHASE A BLACK PHASE A BLACK BLACK PHASE B RED RED PHASE C BLUE BLUE NEUTRAL WHITE WHITE EQ. GROUND GREEN GREEN 12. PROVIDE LABELS ON ALL RECEPTACLES IDENTIFYING PANEL AND CIRCUIT NUMBER. PROVIDE LABELS ON ALL RECEPTACLES IDENTIFYING PANEL AND CIRCUIT NUMBER. LABELS SHALL BE BRADY CLEAR POLYESTER 1"W X 0.375"H OR PANDUIT EQUAL, WITH BLACK LETTERING. MARK ALL JUNCTION BOXES ABOVE CEILING INDICATING PANEL AND CIRCUIT NUMBER USING PERMANENT MARKER. PROVIDE PHENOLIC LABEL ON EXTERIOR BOXES WITH EQUIPMENT DESCRIPTION, AND PANEL AND CIRCUIT NUMBER. BOXES SHALL NOT BE INSTALLED IN AN INACCESSIBLE LOCATION. RACEWAYS AND BOXES 13. PROVIDE MINIMUM 3/4" CONDUIT FOR ALL WIRING. ALL RACEWAYS SHALL BE PROVIDE MINIMUM 3/4" CONDUIT FOR ALL WIRING. ALL RACEWAYS SHALL BE INSTALLED WITHIN WALLS, INCLUDING BLOCK, UNLESS NOTED OTHERWISE. EMT OR RIGID SHALL BE USED WHERE EXPOSED TO PHYSICAL DAMAGE. CONDUIT ABOVE GRADE SHALL BE STEEL. EMT SHALL NOT BE USED IN DIRECT CONTACT WITH THE EARTH, EXTERIOR LOCATIONS, OR WHERE EXPOSED TO SEVERE PHYSICAL DAMAGE. FITTINGS ON EMT CONDUIT SHALL BE COMPRESSION TYPE. FITTINGS ON IMC OR RGS SHALL BE THREADED. MOTOR CONNECTIONS SHALL BE MADE WITH FMC, MIN. 18" LONG AND MAX 36". USE PVC JACKETED FLEXIBLE LIQUID TIGHT CONDUIT TYPE UA FOR CONNECTIONS IN WET LOCATIONS. LOCATE JUNCTION AND PULL BOXES SUCH THAT THEY REMAIN ACCESSIBLE AFTER ALL CONSTRUCTION WORK IS COMPLETE. 14. ALL EMPTY RACEWAYS SHALL BE PROVIDED WITH PULL STRING. INSTALL NO MORE ALL EMPTY RACEWAYS SHALL BE PROVIDED WITH PULL STRING. INSTALL NO MORE INSTALL NO MORE THAN EQUIVALENT OF THREE 90-DEGREE BENDS IN CONDUIT RUN. SUPPORT WITHIN 12 INCH OF CHANGES IN DIRECTION. MAKE BENDS IN RACEWAY USING LARGE-RADIUS PREFORMED ELLS EXCEPT FOR PARALLEL BENDS. FIELD BENDING MUST BE IN ACCORDANCE WITH NFPA 70 MINIMUM RADII REQUIREMENTS. PROVIDE ONLY EQUIPMENT SPECIFICALLY DESIGNED FOR MATERIAL AND SIZE INVOLVED. SUPPORT CONDUIT WITHIN 12 INCH OF ENCLOSURES TO WHICH ATTACHED. SEAL SERVICE RACEWAYS ENTERING A . SEAL SERVICE RACEWAYS ENTERING A BUILDING FROM AN UNDERGROUND SYSTEM PER NEC 230.8 AND 300.5(G). WHERE CONCENTRIC, ECCENTRIC OR OVER-SIZED KNOCKOUTS ARE ENCOUNTERED, A GROUNDING-TYPE INSULATED BUSHING SHALL BE PROVIDED FOR CIRCUITS OVER 250V PER NEC 250.97. 15. PROVIDE ONE-INCH CONDUITS EXTENDING TO CABLE TRAY (WHERE PROVIDED) OR PROVIDE ONE-INCH CONDUITS EXTENDING TO CABLE TRAY (WHERE PROVIDED) OR ABOVE CORRIDOR CEILING FOR ALL TELEPHONE AND DATA OUTLETS SHOWN ON PLANS. PROVIDE PROTECTIVE BUSHINGS ON ENDS OF CONDUIT. SEE PLAN DETAILS FOR CABLE REQUIREMENTS AT EACH LOCATION. PROVIDE 12 INCH SERVICE LOOP ABOVE EACH OUTLET. 16. PROVIDE 3/4-INCH EMPTY CONDUITS TERMINATING ABOVE THE CEILING FOR ALL HVAC PROVIDE 3/4-INCH EMPTY CONDUITS TERMINATING ABOVE THE CEILING FOR ALL HVAC THERMOSTATS. JUNCTION BOXES SHALL MATCH ORIENTATION OF THERMOSTATS PROVIDED BY M.C.. MOUNT JUNCTION BOXES 48-INCHES A.F.F. UNLESS NOTED OTHERWISE. PROVIDE PROTECTIVE BUSHINGS ON ENDS OF CONDUIT. PANELBOARDS 17. PANELBOARDS FOR SERVICE ENTRANCE SHALL BE SERVICE ENTRANCE RATED. PROVIDE PANELBOARDS FOR SERVICE ENTRANCE SHALL BE SERVICE ENTRANCE RATED. PROVIDE NEMA 3R PANELBOARDS WHERE LOCATED OUTSIDE. PROVIDE COPPER NEUTRAL AND GROUNDING BARS IN ALL PANELBOARDS UNLESS NOTED OTHERWISE (ALUMINUM IS NOT ALLOWED). GROUND ALL SERVICE ENTRANCE PANELS AND RACEWAYS (BONDING BUSHINGS) IN ACCORDANCE WITH THE NEC. PROVIDE BOLT-IN BREAKERS UNLESS NOTED OTHERWISE. PROVIDE A MINIMUM OF THREE SPARE 3/4" CONDUITS TO ABOVE CEILING FOR ALL FLUSH MOUNTED PANELBOARDS. PANELS SHALL BE FULLY RATED FOR SHORT CIRCUIT CURRENT, SERIES RATINGS ARE NOT ALLOWED.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .