EXISTING SINGLE-POLE, SINGLE-THROW SWITCH TO BE DEMOLISHED.S
EXISTING NON-FUSED DISCONNECT TO BE DEMOLISHED.
EXISTING PANELBOARD TO BE DEMOLISHED.
EXISTING WALL MOUNTED FIXTURE TO BE DEMOLISHED.
EXISTING SURFACE MOUNTED FIXTURE TO BE DEMOLISHED.
EXISTING CEILING MOUNTED RECEPTACLE TO REMAIN.
EXISTING PANELBOARD TO REMAIN.
EXISTING CEILING MOUNTED RECEPTACLE TO BE DEMOLISHED.
EXISTING EXIT SIGN WITH EMERGENCY FIXTURES TO BE
DEMOLISHED.
EXISTING SURFACE MOUNTED LINEAR FIXTURE TO BE DEMOLISHED.
EXISTING 2X4 RECESSED FIXTURE TO BE DEMOLISHED.
EXISTING CAN LIGHT TO BE DEMOLISHED.
EMERGENCY BUG LIGHT TO BE DEMOLISHED.
EXISTING PANELBOARD TO BE DEMOLISHED.
EXISTING WALL MOUNTED FIXTURE TO BE DEMOLISHED.
EXISTING METER TO REMAIN.
ETR
EXISTING EXIT SIGN TO BE DEMOLISHED.
ETR
SMK
SMK
ETR EXISTING LED HIGH BAY FIXTURES TO REMAIN.
EXISTING LED HIGH BAY FIXTURES TO BE DEMOLISHED.
EXISTING 2X4 FIXTURE WITH SURFACE MOUNT KIT TO BE
DEMOLISHED.
EXISTING 2X2 FIXTURE WITH SURFACE MOUNT KIT TO BE
DEMOLISHED.
EXISTING VANITY FIXTURE TO BE DEMOLISHED.
A. PRIOR TO BEGINNING WORK, SURVEY EXISTING ELECTRICAL SYSTEMS.
DOCUMENT, IN WRITING, SIGNED BY THE CONTRACTING OFFICER, ANY
PORTIONS OF THE EXISTING SYSTEMS THAT ARE NOT OPERATING PROPERLY
BEFORE CONSTRUCTION BEGINS. ANY ELECTRICAL SYSTEMS FOUND
INOPERABLE AT THE END OF THE CONSTRUCTION PROCESS THAT HAVE NOT
BEEN SO DOCUMENTED SHALL BE REPAIRED BY THE CONTRACTOR AT HIS
OWN EXPENSE.
B. PRIOR TO BEGINNING THE DEMOLITION PROCESS, CONDUCT A
COMPREHENSIVE SITE SURVEY WITH THE ASSISTANCE OF THE CONTRACTING
OFFICER. IDENTIFY AND MARK ALL EXISTING EQUIPMENT TO REMAIN AND ALL
EXISTING RACEWAYS AND CIRCUITRY THAT ARE PRESENTLY PASSING
THROUGH THE CONSTRUCTION AREA THAT ARE FEEDING EXISTING
EQUIPMENT TO REMAIN.
C. REMOVE ELECTRICAL EQUIPMENT FEEDING OTHER EQUIPMENT BEING
DEMOLISHED. REMOVE RACEWAYS AND CIRCUITRY BACK TO THE PANEL OF
ORIGINATION. WHERE CIRCUITS ARE NOT BEING COMPLETELY DEMOLISHED,
REMOVE RACEWAYS AND CIRCUITRY BACK TO A JUNCTION BOX OR OTHER
COMMON CONNECTION POINT AND RECIRCUIT EXISTING ELECTRICAL
EQUIPMENT TO REMAIN AS REQUIRED. WHERE NECESSARY, COMPLETELY
REFEED EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IF REQUIRED.
IT IS THE INTENT OF THESE DOCUMENTS THAT ALL EXISTING EQUIPMENT TO
REMAIN BE KEPT COMPLETELY OPERABLE DURING CONSTRUCTION AND LEFT
COMPLETELY OPERABLE AT THE END OF THE CONSTRUCTION PROCESS.
D. THE ELECTRICAL EQUIPMENT SHOWN IS PROVIDED TO CONVEY THE
APPROXIMATE SCOPE OF THE WORK.
E. PROVIDE BLANK OUTLET COVERS FOR ALL EXISTING OUTLET BOXES AS
REQUIRED.
F. PERFORM DEMOLITION WORK AS FOLLOWS:
1. DEMOLISH DEVICE OR END OF LINE EQUIPMENT.
2. DEMOLISH RACEWAYS BACK TO A JUNCTION BOX OR OTHER COMMON
CONNECTION POINT AND CIRCUITRY FEEDING END OF LINE EQUIPMENT
(INCLUDING ALL RACEWAYS AND CIRCUITRY ASSOCIATED WITH
CONTROLS).
3. LEAVE ALL RACEWAYS AND CIRCUITRY THAT COMPLETELY
PASS-THROUGH THE SPACE COMPLETELY OPERABLE BY REROUTING
THE CIRCUITS AS REQUIRED.
EXISTING STROBE TO REMAIN.
EXISTING HORN/STROBE TO REMAIN.
EXISTING MANUAL PULL STATION TO BE RELOCATED TO 45" A.F.F.
EXISTING SMOKE DETECTOR TO REMAIN.
EXISTING SMOKE DETECTOR TO BE RELOCATED.
EXISTING CEILING MOUNTED STROBE TO REMAIN.
F
RL
RL
S
ETR
F
F
F
ETR
ETR
ETR
EXISTING HORN TO BE DEMOLISHED.
EXISTING CIRCUITRY AND RACEWAYS TO BE DEMOLISHED.
BASE BID:
1. BUILDING 17 (MAIN LAB)
ADDITIVE ALTERNATE #1:
1. ALL GREEN HOUSE WORK.
ADDITIVE ALTERNATE #2:
1. BUILDING 18 (HEADHOUSE)
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D0
.dw g Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED000
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL DEMOLITION
LEGEND AND NOTES
2B
2C
2A
6 8 10
1A
1B
9 11
12 14 16
11-C
MEN
WOMEN
18 20 22
17 23
TELECOM
SOIL ROOM
MEN
WOMEN
OFFICEOFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE OFFICE
OFFICE
LABLAB
LAB LAB
LAB LAB
LABLAB
STORAGESTORAGE
BREAK ROOM
MECH. ROOM
INCUBATION/
STORAGE
LIBRARY/CONFERENCE
STORAGE
JANITOR
F
S
S
S
S
S
S
S
S
S
S S
S
S S S
S S S S S S
S
S S S S S
MDP
LO-3
LO-1
LO-2
MCC
S S SS
RL
F F F
F S
F
RLF
RL RL RL RL
RL
F
RL
DATA
RACK
ETR
S S
S S S SSSSEF
ETR
DP-2
UTILITY
TRANSFORMER
RLRL SRL SRLRL SSRL ETR ETR ETR ETR
S
ETR
S
S
ETR
ETR
ETR
ETR
ETR
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
SMK
ETR
ETR
ETR
ATS2
ETRATS1
ETR
L4
TDBB
F
RL
FRL
ETR
ETR
ETR
ETR
ETR
S S S S S S S S SS
S S
S S
SS
SSSSSSSS
S
S S
S SS
S S
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D1
.dw g Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED101
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
BASED BID WORK.
B. ALL LIGHTING CIRCUITRY IS EXISTING TO
REMAIN. ALL FIXTURES ON THIS SHEET SHALL BE
DEMOLISHED. SEE SHEET EL100 FOR NEW
LIGHTING PLAN.
C. ALL EXTERIOR FIXTURES MEAN OF CONTROL
SHALL REMAIN.
GENERAL NOTE
SCALE:
ELECTRICAL
1/8" = 1'-0"
PLAN
NORTH
ED101
ELECTRICAL DEMOLITION PLAN -
BUILDING 17
SCALE:
ELECTRICAL
1/8" = 1'-0"
PLAN
NORTH
ED101
2A
6 8 10
1A
1B
9 11
12 14 16
11-C
MEN
WOMEN
18 20 22
17 23
TELECOM
SOIL ROOM
MEN
WOMEN
OFFICEOFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE OFFICE
OFFICE
LABLAB
LAB LAB
LAB LAB
LABLAB
STORAGESTORAGE
BREAK ROOM
MECH. ROOM
INCUBATION/
STORAGE
LIBRARY/CONFERENCE
STORAGE
JANITOR
LO-1
LO-2
1 & 2
ED300
HYDRONIC
WATER HEATER
HYDRONIC
WATER HEATER
SF (ROOF)
EF (ROOF)
EF (ROOF)
HYDRONIC
WATER HEATER
HYDRONIC
WATER HEATER
HYDRONIC
WATER HEATER
EF (ROOF)
EF (ROOF)
FUME HOOD
DP-2
UTILITY
TRANSFORMER
ETR
ETR ETR
ETRHYDRONIC
WATER HEATER MDP
LO-3
MCC
ETR
EF (ROOF)
ETR
ETR
HYDRONIC
WATER HEATER HEATING COIL
HEATING COIL
HEATING COIL
8 HYDRONIC
WATER HEATER
FUME HOOD
HYDRONIC
WATER HEATER
ATS2
ETRATS1
ETR
EF (ROOF)
2 6
FUME HOOD
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D1
A.d wg Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED101A
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
1 DEMOLISH EXISTING HYDRONIC WATER UNIT
HEATER. RETAIN DISCONNECT, CIRCUITRY,
RACEWAYS, AND BREAKER. SEE SHEET EP101
FOR NEW WORK.
2 DEMOLISH EXISTING ROOF- MOUNTED EXHAUST
FAN. SEE SHEET EP104 FOR DEMOLITION WORK.
SEE SHEET EP104 FOR NEW WORK.
3 DEMOLISH EXISTING ROOF-MOUNTED SUPPLY
FAN. SEE SHEET EP104 FOR DEMOLITION WORK.
SEE SHEET EP104 FOR NEW WORK.
4 DEMOLISH FUME HOOD EXHAUST FAN. RETAIN
CIRCUITRY, RACEWAYS, AND BREAKER. SEE
SHEET EP101 FOR NEW WORK.
5 DEMOLISH EXISTING HYDRONIC HOT WATER
RADIANT HEATER, DISCONNECT, CIRCUITRY,
RACEWAYS, AND BREAKER. SEE SHEET EP101
FOR NEW WORK.
6 DEMOLISH EXISTING HEATING COIL,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER. SEE SHEET EP101 FOR NEW WORK.
KEYED NOTES
SCALE:
ELECTRICAL POWER
1/8" = 1'-0"
PLAN
NORTH
ED101A
ELECTRICAL DEMOLITION PLAN -
BUILDING 17
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
BASED BID WORK.
GENERAL NOTE
UP
DN
S S
S S
S
S
S
RL
F
S S
SMK SMK
SMKSMK
SMK
SMK
SMK
SMK
SMK SMK SMK
SMKSMKSMK
SMKSMKSMK
SMK
RL
F
RL
F
LH1
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
S
LH2
FACP FAC
ETRETR
ETRETR
F
F ETR
F ETR
F
ETR
F
ETR
F
F
ETR
ETR
ETR
RL
F
F
ETR
OPEN TO WORK AREA BELOW
OPEN TO WORK AREA BELOW
EF-2
EF-3
EF-2
EF-3
(208V, 3Ø, 3HP)(208V, 3Ø, 3HP)
(208V, 3Ø, 5HP)
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D1
.dw g Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED102
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
1 DEMOLISH EXISTING WALL-MOUNTED EXHAUST,
DISCONNECT, AND 30/3 BREAKER IN PANEL LH-1
SPACE 26. RETAIN EXISTING CIRCUITRY AND
RACEWAYS. SEE SHEET EP101 FOR NEW WORK.
2 DEMOLISH EXISTING WALL-MOUNTED SUPPLY,
DISCONNECT, AND 15/3 BREAKER IN PANEL LH-1
IN SPACE 27. RETAIN EXISTING CIRCUITRY AND
RACEWAYS. SEE SHEET EP101 FOR NEW WORK.
3 DEMOLISH EXISTING ROOF-MOUNTED EXHAUST
FAN AND BREAKER. RETAIN EXISTING
DISCONNECT, CIRCUITRY, AND RACEWAYS. SEE
SHEET EP101 FOR NEW WORK.
4 DEMOLISH EXISTING WALL-MOUNTED EXHAUST,
SUPPLY FAN CONTROLLER, DISCONNECT,
CIRCUITRY, RACEWAYS, AND BREAKER.
5 EXISTING FIRE ALARM CONTROL PANEL SHALL
REMAIN. FIRELITE MS-5UD FALCO ALARM
COMPANY (405)-743-4201.
6 EXISTING REMAIN FIRE ALARM COMMUNICATOR
SHALL REMAIN. HONEYWELL HWF2V-COM.
7 DEMOLISH EXISTING WALL-MOUNTED SUPPLY,
DISCONNECT, AND 15/3 BREAKER IN PANEL LH-2
IN SPACE 11. RETAIN EXISTING CIRCUITRY AND
RACEWAYS. SEE SHEET EP101 FOR NEW WORK.
KEYED NOTES
SCALE:
ELECTRICAL FIRST FLOOR
1/8" = 1'-0"
PLAN
NORTH
ED102
ELECTRICAL DEMOLITION PLAN -
BUILDING 18
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
ADDITIVE ALTERNATE #2 WORK.
B. ALL EXTERIOR FIXTURES MEAN OF CONTROL
SHALL REMAIN.
GENERAL NOTE
SCALE:
ELECTRICAL MEZZANINE
1/8" = 1'-0"
PLAN
NORTH
ED102 SCALE:
ELECTRICAL ROOF
1/8" = 1'-0"
PLAN
NORTH
ED102
18 E 18 F
17 J17 H17 G17 F
17 A 17 B 17 C 17 D 17 E
27 24
L-G14 L-G15
L-G8 L-G9
GREEN HOUSE
17 H
GREEN HOUSE
17 J GREEN HOUSE
18 E
GREEN HOUSE
18 F
L-G15-GL
ETR
ETR ETR ETR
ETR
S
S
S
S
S
S
S
S
L-G6
L-G7
GREEN HOUSE
17 F
GREEN HOUSE
17 G
L-G6B
ETR
ETR
ETRS
S
S
S
L-G1 L-G2 L-G3 L-G4 L-G5
ETR
ETR
GREEN HOUSE
17 A GREEN HOUSE
17 B
GREEN HOUSE
17 C
GREEN HOUSE
17 D
GREEN HOUSE
17 E
L-G1B ETR ETR ETR ETR
S
S3
S
S
S
S
S3 S3 S3 S3
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D1
.dw g Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED103
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
KEY PLAN
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
BUILDINGS 17 A-E DEMOLITION PLANS (GREENHOUSES)1
BUILDINGS 17 F-G DEMOLITION PLANS (GREENHOUSES)
SCALE: 1/16"=1'-0"
2 BUILDINGS 17 H-J DEMOLITION PLANS (GREENHOUSES)3 BUILDINGS 18 E-F DEMOLITION PLANS (GREENHOUSES)4
SCALE: 1/16"=1'-0"
SCALE: 1/16"=1'-0"SCALE: 1/16"=1'-0"
ED103
ED103 ED103 ED103
GENERAL NOTES
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
ADDITIVE ALTERNATE #1 WORK.
B. SEE SHEET EP103 AND EL103 FOR ALL NEW
WORK.
C. THE LOCATION AND NUMBER OF ELECTRICAL
DEVICES ON THIS SHEET IS BASED ON
DRAWINGS PROVIDED TO US BY THE
GOVERNMENT FROM 1980 AND A SITE
SURVEY CONDUCTED BY OUR TEAM.
DEMOLITION SHALL INCLUDE ALL
RECEPTACLES BELOW 24". PERFORM
DEMOLITION WORK AS FOLLOWS:
C.1. DEMOLISH DEVICE OR END OF LINE
EQUIPMENT.
C.2. DEMOLISH CIRCUITRY BACK TO
BREAKER.
C.3. DEMOLISH RACEWAYS ABOVE THE SLAB.
CAP AND ABANDON ALL RACEWAYS
ROUTED UNDER THE SLAB.
D. FLUORESCENT FIXTURES TO BE DEMOLISHED
ARE ALL HOUSE LIGHTING FIXTURES. DO NOT
DEMOLISH ANY GROW LIGHTS-EVEN IF THEY
ARE FLUORESCENT FIXTURES.
ELECTRICAL DEMOLITION PLAN -
GREENHOUSES
SF (ROOF)
EF (ROOF)
EF (ROOF)
EF (ROOF)
EF (ROOF)
EF (ROOF)EF (ROOF)
EF (ROOF)
SF (ROOF)
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D1
.dw g Ju n 1 3,
- 1 1:5
8a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED104
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
1 DEMOLISH EXISTING ROOF-MOUNTED EXHAUST
FAN, DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER. SEE SHEET EP104 FOR NEW WORK.
2 DEMOLISH EXISTING ROOF-MOUNTED SUPPLY
FAN, DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER. SEE SHEET EP104 FOR NEW WORK.
KEYED NOTES
SCALE:
ELECTRICAL ROOF
1/8" = 1'-0"
PLAN
NORTH
ED104
ELECTRICAL POWER PLAN -
BUILDING 17
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
BASE BID WORK.
MECH. ROOM
1 1 1 1
ETR
ETRMDP
LO-3
MCC
ETR
ATS1
ETR1213
7 7
6 6
10 11
MECH. ROOM
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D3
.dw g Ju n 1 3,
- 1 1:5
9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED300
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
SCALE:
BUILDING 17 MECHANICAL ROOM
1/4" = 1'-0"
PLAN
NORTH
KEYED NOTES
1. DEMOLISH EXISTING AIR HANDLING UNIT,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER. NOT TO BE REPLACED.
2. DEMOLISH EXISTING CHILLER, DISCONNECT,
CIRCUITRY, RACEWAYS, AND BREAKER. SEE
SHEET EP300 FOR NEW WORK.
3. DEMOLISH EXISTING BOILER, DISCONNECT,
CIRCUITRY, RACEWAYS, AND BREAKER. SEE
SHEET EP300 FOR NEW WORK
4. DEMOLISH EXISTING CHILLED WATER PUMP,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER. SEE SHEET EP300 FOR NEW WORK.
5. DEMOLISH EXISTING HEATING HOT WATER PUMP
AND DISCONNECT. RETAIN CIRCUITRY,
RACEWAYS, AND BREAKER. SEE SHEET EP300
FOR NEW WORK.
6. DEMOLISH EXISTING RETURN AIR FAN,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
7. DEMOLISH EXISTING EXPANSION TANK,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
8. DEMOLISH EXISTING UNIT HEATER,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
9. DEMOLISH EXISTING HOOD SUPPLY FAN,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
10. DEMOISH EXISTING ROOF-MOUNTED
MECHANICAL ROOM VENTILATION FAN,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
11. DEMOLISH EXISTING ROOF-MOUNTED
MECHANICAL ROOM EXHAUST FAN,
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
12. DEMOLISH EXISTING AIR COMPRESSOR
DISCONNECT, CIRCUITRY, RACEWAYS, AND
BREAKER.
13. DEMOLISH EXISTING AIR DRYER, DISCONNECT,
CIRCUITRY, RACEWAYS, AND BREAKER.
KEYED NOTES
SCALE:
BUILDING 17 MECHANICAL ROOM
1/4" = 1'-0"
PLAN
NORTH
ED300 ED300
EXIST. DOMESTIC
WATER HEATING
EQUIPMENT TO REMAIN
ELECTRICAL DEMOLITION PLAN -
MECHANICAL ROOM BUILDING 17
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
BASED BID WORK.
MDP
GRADE
EXTERIOR OF THE
BUILDING.
MAIN LABORATORY
BUILDING 17
MCC
EXISTING DIP
POLE TO REMAIN
Scale: NONE
ED600
ELECTRICAL - EXISTNG SINGLE LINE (BASE BID)
LO-3
(SECTION 1)
ETR ETR
EXISTING
500KVA,
120/208V, 3Ø
TRANSFORMER
TO REMAIN.
ETR
LO-1
ETR
LO-2
ETR
HEAD HOUSE
BUILDING 18.
LH-1
ETR
CORRIDOR
DP-2
ETR
ANNEX
L4
ETR
PANEL L-22
ETR
LH-2
ETR
ATS2: 800A
208Y/120V
SERVICE
ENTRANCE
RATED,
3-POLE
ETR
ATS1: 1200A
208Y/120V
SERVICE
ENTRANCE
RATED,
3-POLE
ETR
ETR
GENERATOR
250KW, .8PF,
208Y/120V, 3Ø, 4W
ETR ETR
ETR
ETR
ETR ETR
ETR
ETR
ETR
ETR
ETR
ETR
TO PULL BOX (SEE
DETAIL 2 ON THIS SHEET)
Scale: NONE
ED600
ELECTRICAL - EXISTNG PULLBOX SINGLE LINE (ADDITIVE ALTERNATE #2)
RM 7
L-22
ETR
PULL BOX (FIELD
VERIFY LOCATION
PRIOR TO BEGINNING
WORK)
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
TO MDP IN BUILDING 17 (RM 18)
TO MDP IN BUILDING 17 (RM 18)
TO MDP IN BUILDING 17 (RM 18)
TO MDP IN BUILDING 17 (RM 18)
TO GREENHOUSES 18A, 18B, & 18C
TO GREENHOUSES 18D, 18E, & 18F
TO GREENHOUSES 17F & 17G
TO GREENHOUSES 17H & 17J
GRADE
LO-3
(SECTION 2)
ETR
3 3
ETR ETR
ETR
TO MDP IN BUILDING 17 (RM 18)
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D6
.dw g Ju n 1 3,
- 1 1:5
9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED600
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL DEMOLITION
EXISTING SINGLE LINE
1 EXISTING CIRCUITRY AND RACEWAYS TO
GREENHOUSES 17A, 17B, AND 17C SHALL
REMAIN.
2 EXISTING CIRCUITRY AND RACEWAYS TO
GREENHOUSES 17D & 17E. SHALL REMAIN.
3 THIS EQUIPMENT WAS NOT INSTALLED DURING
OUR SITE SURVEY VISIT. SEE GENERAL NOTE
A ON THIS SHEET.
KEYED NOTES
GENERAL NOTES
A. OUR SITE SURVEY OF THE EXISTING CONDITIONS
WAS CONDUCTED PRIOR TO INSTALLATION OF
THE EMERGENCY GENERATOR PROJECT NO:
P09651.0100. THE SINGLE LINE SHOWN IS BASED
ON THE EXISTING CONDITIONS DURING THE SITE
SURVEY AND PROJECT: P9651.0100.
B. DP-2 PANEL SCHEDULE IS NOT SHOWN AS WE ARE
NOT MODIFYING THE PANEL. IT HAS AN 800/3 MAIN,
225/3 FEEDING 225A PANEL IN ANNEX, A 100/3
FEEDING PANEL L-22 IN ROOM 7, A 225/3 SPARE,
AND A 100/3 SPARE.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D7
.dw g Ju n 1 3,
- 1 1:5
9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED700
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL DEMOLITION PANEL
SCHEDULES
A. ALL PANEL SCHEDULES SHOWN ON THIS SHEET
ARE FOR REFERENCE ONLY.
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D7
.dw g Ju n 1 3,
- 1 1:5
9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED701
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL DEMOLITION PANEL
SCHEDULES
GENERAL NOTE
A. ALL WORK INVOLVING GREENHOUSES IS
ALTERNATE #1 WORK.
B. ALL PANEL SCHEDULES ON THIS SHEET IS FOR
REFERENCE ONLY.
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E D7
.dw g Ju n 1 3,
- 1 1:5
9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
ED702
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL DEMOLITION PANEL
SCHEDULES
A. ALL WORK INVOLVING GREENHOUSES IS
ALTERNATE #1 WORK.
B. ALL PANEL SCHEDULES ON THIS SHEET IS FOR
REFERENCE ONLY.
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT CIRCUIT INTERRUPTING
DEVICES.
3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF WHILE-IN-USE.
4. DEVICES NOTED AS "ETR" SHALL BE EXISTING TO REMAIN.
5. DEVICES NOTED AS "RL" SHALL BE RELOCATED.
6. FIXTURES NOTED AS "SMK" SHALL HAVE A SURFACE MOUNT KIT.
7. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY PACKS. LED DIMMER MOUNT CENTERLINE OF BOX AT 45"A.F.F. UNLESS NOTED
OTHERWISE.
SINGLE-POLE, SINGLE-THROW SWITCH. MOUNT CENTERLINE OF BOX AT
45"A.F.F. UNLESS NOTED OTHERWISE.
POWER PACK.PP
S
D
S M
HORSEPOWER RATED SWITCH WITH THERMAL OVERLOADS (MANUAL
MOTOR STARTER).
ST
PASSIVE INFRARED AND ULTRASONIC DUAL TECHNOLOGY OCCUPANCY
SENSOR WITH A 12' RADIAL COVERAGE. CEILING MOUNTED.MD1
F-?
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO BOTTOM OF
BOX UNLESS NOTED OTHERWISE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE COVER PLATE,
MOUNTED 18" A.F.F. TO BOTTOM OF BOX UNLESS NOTED OTHERWISE.
FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER OF
POLES/ENCLOSURE TYPE; F-(RATING OF FUSES).
NON-FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER
OF POLES/ENCLOSURE TYPE.
PANELBOARD.
SURFACE MOUNTED OR SUSPENDED FIXTURE.
SURFACE MOUNTED OR SUSPENDED EMERGENCY FIXTURE.
RECESSED CEILING FIXTURE.
CEILING MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS INDICATED
BY ARROWS.
WALL MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS INDICATED BY
ARROWS.
WALL MOUNTED FIXTURE.
WALL MOUNTED LINEAR FIXTURE.
SURFACE MOUNT FIXTURE.
NOTE: THE NUMBER INSIDE THE CIRCLE IS THE CIRCUIT NUMBER. THE LETTER BESIDE THE SYMBOL
IS THE FIXTURE TYPE DESCRIBED IN THE LIGHT FIXTURE SCHEDULE.
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE,
THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS
PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR FLOOR.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS
TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED
SURFACE-MOUNTED RACEWAY (SEE SPECIFICATIONS).
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT
NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE
THEM MAY NOT SHOW THE CIRCUIT NUMBERS AT THE HOMERUN
ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL PARTIAL
HOMERUNS THAT ARE ON THE SAME CIRCUIT IN A JUNCTION BOX
PRIOR TO ENTERING THE PANELBOARD.
LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR
CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS FOR
CONDUCTOR REQUIREMENTS.
EMERGENCY FIXTURE.
AUTOMATIC WALL SWITCH. MOUNT CENTERLINE OF BOX AT 45" A.F.F.
UNLESS NOTED OTHERWISE.
2'X2' RECESSED FIXTURE.
TELECOMMUNICATIONS & DATA BACKBOARD
2'X4' RECESSED FIXTURE.
S M2
DUAL TECHNOLOGY, DUAL RELAY WALL SWITCH. MOUNT CENTERLINE
OF BOX AT 45" A.F.F. UNLESS NOTED OTHERWISE. WITH TWO
CIRCUITS-ONE FOR LIGHTS AND THE OTHER FOR THE EXHAUST FAN
SHOWN ON EP101.
F
S D
D R
F
F
FAC
FACP
MANUAL PULL STATION MOUNTED 45"A.F.F. TO CENTERLINE OF
BOX.
STROBE MOUNTED 80"A.F.F. TO BOTTOM OF BOX.
COMBINATION HORN AND STROBE. MOUNTED 80"A.F.F. TO BOTTOM
OF BOX.
SMOKE DETECTOR.
DUCT SMOKE DETECTOR IN RETURN DUCT.
DUCT SMOKE DETECTOR IN SUPPLY DUCT.
FIRE ALARM CONTROL PANEL.
FIRE ALARM COMMUNICATION.
FIRE ALARM STROBE MOUNTED ON THE CEILING TO A FLUSH
MOUNTED BOX.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 42"A.F.F. TO CENTERLINE
OF BOX UNLESS NOTED OTHERWISE. RECEPTACLE SHALL BE G.F.I TYPE
AND UTILIZE CAST METAL BOXES WITH GASKETED METALLIC
WEATHERPROOF-WHILE-IN-USE COVER.
TWO-POLE, 30A SWITCH MOUNTED IN CAST METAL BOX ADJACENT
WATER HEATER FOR USE AS A DISCONNECT.
S 2P
COMBINATION TELEPHONE/DATA OUTLET MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
FIRE ALARM HORN AND STROBE MOUNTED ON THE CEILING TO A
FLUSH MOUNTED BOX.FAHS
S
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 42"A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE. RECEPTACLE SHALL
BE G.F.I TYPE AND UTILIZE CAST METAL BOXES WITH GASKETED
METALLIC WEATHERPROOF-WHILE-IN-USE COVER.
MAGNETIC MOTOR STARTER.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E -00
0.d wg
Ju n 1
3,
- 1
1:5 9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
E-000 06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL NEW WORK
LEGEND
REQUIREDBREAKER
AMPACITY
CIRCUITRY SIZING TABLE
CIRCUITRY
2 #12, #12(G), 3/4" C.15
POLES
2 #12, #12(G), 3/4" C.20 1 2 #10, #10(G), 3/4" C.30 1 2 #8, #10(G), 3/4" C.40 1 2 #6, #10(G), 1" C.50 1 2 #4, #8(G), 1 1/4" C.60 1 2 #12, #12(G), 3/4" C.15 2 2 #12, #12(G), 3/4" C.20 2 2 #10, #10(G), 3/4" C.30 2 2 #8, #10(G), 3/4" C.40 2 2 #6, #10(G), 1" C.50 2 2 #4, #8(G), 1 1/4" C.60 2 3 #12, #12(G), 3/4" C.15 3 3 #12, #12(G), 3/4" C.20 3 3 #10, #10(G), 3/4" C.30 3 3 #8, #10(G), 3/4" C.40 3 3 #6, #10(G), 1" C.50 3 3 #4, #8(G), 1 1/4" C.60 3 4 #4, #8(G), 1 1/4" C.70 3 4 #3, #8(G), 1 1/4" C.80 3 4 #2, #8(G), 1 1/4" C.90 3 4 #1, #8(G), 1 1/2" C.100 3 4 #1/0, #6(G), 1 1/2" C.125 3
150 3 4 #2/0, #6(G), 2" C.175 3
200 3
4 #1/0, #6(G), 1 1/2" C.
4 #3/0, #6(G), 2" C.
4 #4/0, #4(G), 2 1/2" C.225 3
250 3 4 #250, #4(G), 3" C.
4 #350KCM, #4(G), 3" C.300 3
350 3 4 #500KCM, #3(G), 3 1/2" C.
4 #500KCM, #3(G), 3 1/2" C.400 3
500 3 TWO RUNS 3" C., EACH WITH 4 #250KCM, #2(G)
600 3 700 3 800 3
TWO RUNS 3 1/2" C., EACH WITH 4 #500KCM, #1/0(G)
TWO RUNS 3 1/2" C., EACH WITH 4 #350KCM, #1(G)
TWO RUNS 3 1/2" C., EACH WITH 4 #500KCM, #1/0(G)
A. REPLACE EXISTING MAIN SWITCHBOARD SHOWN ON THE DEMOLITION DRAWINGS
WITH A NEW SWITCHBOARD SHOWN ON THE NEW WORK DRAWINGS. USE EXISTING
CIRCUITRY TO THE EXTENT PRACTICAL. WHERE NECESSARY TO REACH NEW
BREAKERS, SPLICE CONDUCTORS USING COMPRESSION CONNECTORS INSIDE NEW
PANELS AND EXTEND THE CIRCUITRY USING THE TABLE BELOW.
B. ALL CIRCUIT BREAKERS SHOWN IN THE TABLE MAY NOT BE USED IN THIS PROJECT.
C. FOR CIRCUIT BREAKERS IN BETWEEN THE SIZES SHOWN, USE CIRCUITRY FOR THE
NEXT LARGER CIRCUIT BREAKER.
D. COORDINATE THE REQUIREMENTS FOR NEUTRALS FOR 2-POLE AND 3-POLE
BREAKERS WITH EXISTING EQUIPMENT LOADS. PROVIDE NEUTRALS WHERE
REQUIRED BY EQUIPMENT. DO NOT PROVIDE NEUTRALS WHERE NOT REQUIRED BY
EQUIPMENT. THE TABLE ASSUMES THAT NEUTRALS ARE NEEDED FOR 3-POLE 70
CIRCUITS AND LARGER, BUT NOT NEEDED FOR SMALLER 3-POLE CIRCUITS.
CIRCUITRY SIZING TABLE NOTES:
MSA
GRADE
EXTERIOR OF THE
BUILDING.
MAIN LABORATORY
BUILDING 17
EXISTING DIP
POLE TO REMAIN
Scale: NONE
E-600
ELECTRICAL - EXISTNG SINGLE LINE (BASE BID)
LO-3
(SECTION 1)
ETR
EXISTING
500KVA,
120/208V, 3Ø
TRANSFORMER
TO REMAIN.
ETR
LO-1
ETR
LO-2
ETR
HEAD HOUSE
BUILDING 18.
LH-1
ETR
CORRIDOR
DP-2
ETR
ANNEX
L4
ETR
PANEL L-22
ETR
LH-2
ETR
ATS2: 800A
208Y/120V
SERVICE
ENTRANCE
RATED,
3-POLE
ETR
ATS1: 1200A
208Y/120V
SERVICE
ENTRANCE
RATED,
3-POLE
ETR
ETR
GENERATOR
250KW, .8PF,
208Y/120V, 3Ø, 4W
ETR ETR
ETR
ETR
ETR ETR
ETR
ETR
ETR
ETR
ETR
ETR
TO PULL BOX (SEE
DETAIL 2 ON THIS SHEET)
Scale: NONE
E-600
ELECTRICAL - EXISTNG PULLBOX SINGLE LINE (ADDITIVE ALTERNATE #2)
RM 7
L-22
ETR
PULL BOX
(FIELD VERIFY
LOCATION
PRIOR TO
BEGINNING
WORK)
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
TO MSA IN BUILDING 17 (RM 18)
TO MSA IN BUILDING 17 (RM 18)
TO MSA IN BUILDING 17 (RM 18)
TO MSA IN BUILDING 17 (RM 18)
TO GREENHOUSES 18A, 18B, & 18C
TO GREENHOUSES 18D, 18E, & 18F
TO GREENHOUSES 17F & 17G
TO GREENHOUSES 17H & 17J
GRADE
LO-3
(SECTION 2)
ETR
3 3
EXTERIOR OF THE
BUILDING.
NLO-5 NLO-6
ETR
4 #4/0, #4(G), 2-1/2"C.
ETRETR
TO MSA IN BUILDING 17 (RM 18)
ETR
3-1/2"C. EACH CONTAINING
4 RUNS OF 4#350KCM, #3/0(G)
4 #1, #6(G), 1-1/2"C.
(5.5% IMPEDANCE)
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E -60
0.d wg
Ju n 1
3,
- 1
1:5 9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
E-600 06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL NEW WORK SINGLE
LINE DIAGRAM
1 EXISTING CIRCUITRY AND RACEWAYS TO
GREENHOUSES 17A, 17B, AND 17C SHALL
REMAIN.
2 EXISTING CIRCUITRY AND RACEWAYS TO
GREENHOUSES 17D & 17E. SHALL REMAIN.
3 THIS EQUIPMENT WAS NOT INSTALLED DURING
OUR SITE SURVEY VISIT. SEE GENERAL NOTE
A ON THIS SHEET.
4 ROUTE 2#14, #14(G), 3/4"C. TO ENERGY
MANAGEMENT SYSTEM TO PROVIDE A SIGNAL
THAT EACH ATS IS OPERATING IN GENERATOR
POSITION. THE CONTROL SYSTEM
CONTRACTOR SHALL PROGRAM THE SYSTEM
TO SHUT OFF THE CHILLER WHEN RUNNING
ON THE GENERATION.
KEYED NOTES
GENERAL NOTES
A. OUR SITE SURVEY OF THE EXISTING CONDITIONS
WAS CONDUCTED PRIOR TO INSTALLATION OF
THE EMERGENCY GENERATOR PROJECT NO:
P09651.0100. THE SINGLE LINE SHOWN IS BASED
ON THE EXISTING CONDITIONS DURING THE SITE
SURVEY AND PROJECT: P9651.0100. FIELD VERIFY
EXISTING CONDITIONS PRIOR TO SUBMITTING
ELECTRICAL BROCHURES FOR REVIEW. NOTIFY
CONTRACTING OFFICER OF AN DISCREPANCIES
B. DP-2 PANEL SCHEDULE IS NOT SHOWN AS WE ARE
NOT MODIFYING THE PANEL. IT HAS AN 800/3 MAIN,
225/3 FEEDING 225A PANEL IN ANNEX, A 100/3
FEEDING PANEL L-22 IN ROOM 7, A 225/3 SPARE,
AND A 100/3 SPARE.
C. COMPLY COMPLETELY WITH ALL UTILITY
COMPANY REQUIREMENTS EVEN IF DIFFERENT
FROM THE INFORMATION SHOWN. NOTIFY THE
ENGINEER AT LEAST TEN DAYS PRIOR TO BID OF
ANY DISCREPANCIES BETWEEN THE UTILITY
COMPANY REQUIREMENTS AND THE INFORMATION
SHOWN. PAY ALL UTILITY COMPANY CHARGES.
CONTACT STILLWATER ELECTRIC UTILITY TANYA
BACON (TANYA.BACON@STILLWATER.ORG).
D. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND
EQUIPMENT, DARKER COLORS DENOTE NEW
CIRCUITRY AND EQUIPMENT.
FOR REFERENCE ONLY
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E -70
0.d wg
Ju n 1
3,
- 1
1:5 9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
E-700 06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL NEW WORK PANEL
SCHEDULES
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E -70
1.d wg
Ju n 1
3,
- 1
1:5 9a m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
E-701 06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL NEW WORK PANEL
SCHEDULE
GENERAL NOTES
A. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND
EQUIPMENT, DARKER COLORS DENOTE NEW
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E -70
2.d wg
Ju n 1
3,
- 1
2:0 0p m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
E-702 06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL NEW WORK PANEL
SCHEDULE
GENERAL NOTES
A. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND
EQUIPMENT, DARKER COLORS DENOTE NEW
2A
6 8 10
1A
1B
9 11
12 14 16
11-C
MEN
WOMEN
18 20 22
17 23
TELECOM
SOIL ROOM
MEN
WOMEN
OFFICEOFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE OFFICE
OFFICE
LABLAB
LAB LAB
LAB LAB
LABLAB
STORAGESTORAGE
BREAK ROOM
MECH. ROOM
INCUBATION/
STORAGE
LIBRARY/CONFERENCE
STORAGE
JANITOR
A2
A2
A2
A2
A2
A2 A3
A3
A3
A2E
A2
A2EA2 A2 A2E A2 A2E A2 A2E A2 A2E A2 A2E A2 A2E A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A1 A1
A1 A1
A1 A1
A1
A1
A1 A2 A2
A2 A2
A2 A2
A2 A2
A2
A2
A2 A2
A2 A2
A2
A2E
A2E
A2E
A2
A2
A2
A2
A2
A2 A2
A2E
A1
A1
A1
A1
A1
A1
A2
A2
A2
A2
A2
A2
X
D
X
X
D
D
WE W
D
D
D
S M
S M
S M
D D
D D D D
X
A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK
S S D D D
LO-1
LO-2
W WE
FE
X X X
WE WEWE WE
X
A2 A2 A2 A2
A2 A2 A2 A2
A2 A2
A2
A2
FDATA
RACKD1
D1
D1
D1
D1
ETR
A2
A2
A2
A2
A2
A2
B1 B1 B1
B1E
B1EB1
B1B1B1E
B1
V
V
V1
V1
D D D DS
M
D1
A2E
A2
A2
A2
A2
A2
A2
A2
A1
A1
A1
A2
A2
A2
A2
A2
A2
MSA
LO-3
ETR
DP-2
UTILITY
TRANSFORMER
ETR
ETR
ETR
PPMD1
PPMD1
PP
MD1
PP
MD2
PP
MD1
PP
MD1
PP
MD2
PP
MD1
PP
MD1
PP
MD1MD1MD1MD1
MD1
MD1
PP
MD1
PP
MD1
PP
MD1
PP
MD1
PP
MD1
PP
MD1
PP
MD1MD1
MD2
PPMD1
PPMD1
MD2 MD2 MD2 MD2 MD2 MD1
PP
PPETR
ETR
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK
A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK
ETR
ATS1
ETR
ATS2
ETR
L-22
ETR
PP
PP
PP
PP
MD1
PP
MD1
S M
PP
1 PP
1 1 1 1 1 1
1 1
PP
MD1 1
PP
MD2
D
NLO-5
NLO-6
1 1 1
A2
A2
A2
A2
A2E
A2
A2
A2
A2
A2
A2
A2
A1
A1
A1
A1
A1
A1
A2A2
A2A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A1
A1
A1
A1
A1
A1
A2A2A2
A2 A2E A2
A2 A2E A2
F
FE
FE
F
D1
D1 FE
F
F
L4 A1
A1E
TDBB
V
VE
V
VE
B1E
A1E
W
W
W
W
X
X
PP
MD1
PP
MD1
PP
MD1
PP
MD1
PP
MD1
PP MD11
PP
MD1
PP
MD2
PP
MD2
MD1 MD1MD1
PP1
PP
MD1
PP
MD1
PP
MD1
PP
MD1
1D D D D
S
M
S
M
S
MD1
PP
D
D
PP
MD1
PP MD11
S
D
DDDDD
S T
SWITCH FOR
EXTERIOR
LIGHTS
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E L1
.dw g Ju n 1 3,
- 1 2:0
0p m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
EL101
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
SCALE:
ELECTRICAL
1/8" = 1'-0"
PLAN
NORTH
EL101
ELECTRICAL LIGHTING PLAN -
BUILDING 17
SCALE:
ELECTRICAL
1/8" = 1'-0"
PLAN
NORTH
EL101
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
BASE BID WORK.
B. ALL LIGHTING CIRCUITRY IS EXISTING TO
REMAIN. UNLESS OTHERWISE SHOWN.
C. PROVIDE UNSWITCHED POWER TO ALL
EMERGENCY BATTERY PACKS.
D. PROVIDE BLANK COVERS FOR ALL UNUSED
SWITCH OUTLETS.
E. ALL EXTERIOR FIXTURES SHALL BE CONNECTED
TO THEIR EXISTING MEANS OF CONTROL.
GENERAL NOTE
1 PROVIDE UNSWITCHED POWER FROM THE
EXISTING CIRCUIT FEEDING THE EXISTING
LIGHTS TO POWER PACK AND TO ALL
FIXTURES WITH BATTERY PACKS. FIXTURES
WITH BATTERY PACKS SHALL BE SWITCHED
WITH OCCUPANCY SENSOR AND CONTROLLED
BY WALL SWITCH IN ALL ROOMS. FIXTURES
WITH BATTERY PACKS IN CORRIDORS SHALL
BE UNSWITCHED NIGHT LIGHTS.
KEYED NOTES
C3 C3 C2 C2
C2E
C2E
C2E
C2EV1
V1
D
M S
M
S
M
S
M
D
S
C4
X
X1 X1
X1
WE
W
WE
W
WE
W
B2
SMK SMK
SMKSMK
SMK
SMK
SMK
SMK
SMK SMK SMK
SMKSMKSMK
SMKSMKSMK
SMK
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
C1E
C1
C1
C1
C1
C1
B2
B2E
B2
B2E
B2
S
LH1LH2
FACP FAC
ETRETR
ETRETR
D
PPMD2
NO
ROOF
WORK
C1
C1
C1
C1
C1
C1E
C1
C1
C1
C1
C1E
C1
C1
C1
C1
B2E
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E L1
.dw g Ju n 1 3,
- 1 2:0
0p m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
EL102
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
SCALE:
ELECTRICAL FIRST FLOOR
1/8" = 1'-0"
PLAN
NORTH
SCALE:
ELECTRICAL MEZZANINE
1/8" = 1'-0"
PLAN
NORTH
EL102 EL102
ELECTRICAL LIGHTING PLAN -
BUILDING 18
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
ADDITIVE ALTERNATE #2 WORK.
B. ALL LIGHTING CIRCUITRY IS EXISTING TO
REMAIN. UNLESS OTHERWISE SHOWN.
C. PROVIDE UNSWITCHED POWER TO ALL
EMERGENCY BATTERY PACKS.
D. PROVIDE BLANK COVERS FOR ALL UNUSED
SWITCH OUTLETS.
E. ALL EXTERIOR FIXTURES SHALL BE CONNECTED
TO THEIR EXISTING MEANS OF CONTROL.
GENERAL NOTE
KEYED NOTES
1 PROVIDE UNSWITCHED POWER FROM THE
EXISTING CIRCUIT FEEDING THE EXISTING
LIGHTS TO POWER PACK AND TO ALL
FIXTURES WITH BATTERY PACKS. FIXTURES
WITH BATTERY PACKS SHALL BE SWITCHED
WITH OCCUPANCY SENSOR AND CONTROLLED
BY WALL SWITCH IN ALL ROOMS. FIXTURES
WITH BATTERY PACKS IN CORRIDORS SHALL
BE UNSWITCHED NIGHT LIGHTS.
17 A 17 B 17 C 17 D 17 E
27 24
G
G
G
G
G
G G
G
G
G
G
G
G
G
G
G
G G
G
G
G
G
GREEN HOUSE
17 H
GREEN HOUSE
17 J GREEN HOUSE
18 E
GREEN HOUSE
18 F
S
S
S
S
S
S
S
S
WP WP WP WP
WP WP WP WP
S
3 WP S
3 WP
S
3 WP
S
3 WP
G
G
G
G
G
G
G
G
G
G
G
G
G
GREEN HOUSE
17 F
GREEN HOUSE
17 G
S
S
S
S
3 WP WP
WP
WP
S
3 WP
S
3 WP
S
3 WP S
3 WP
G
G
G
G
G
G
G
G
G
G
G
G
G
G
NO
LIGHTING
WORK
G
G
G
G
G
G
G
G
G
G
GREEN HOUSE
17 A GREEN HOUSE
17 B
GREEN HOUSE
17 C
GREEN HOUSE
17 D
GREEN HOUSE
17 E
S
S
S
S
S
S
S
S
S
S
WP WP WP WP WP
WPWPWPWPWP
S
3 WP
S
3 WP
S
3 WP
S
3 WP
S
3 WP
S
3 WP S
3 WP
S
3 WP S
3 WP
S
3 WP
S
3 WP
S
3 WP
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E L1
.dw g Ju n 1 3,
- 1 2:0
0p m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
EL103
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
KEY PLAN
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
BUILDINGS 17 A-E LIGHTING PLANS (GREENHOUSES)1
BUILDINGS 17 F-G LIGHING PLANS (GREENHOUSES)
SCALE: 1/16"=1'-0"
2 BUILDINGS 17 H-J LIGHTING PLANS (GREENHOUSES)3 BUILDINGS 18 E-F LIGHTING PLANS (GREENHOUSES)4
SCALE: 1/16"=1'-0"
SCALE: 1/16"=1'-0"SCALE: 1/16"=1'-0"
EL103
EL103 EL103 EL103
ELECTRICAL LIGHTING PLAN -
GREENHOUSES
A. ALL WORK SHOWN ON THIS SHEET SHALL BE
ADDITIVE ALTERNATE #1 WORK.
LUMINAIRE REQUIREMENTS:
FIXTURE TYPE: B1, B1E, B2, B2E
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.
6.
7.
8.
HOUSING - CHANNEL AND COVER ARE FORMED FROM
CODE-GAUGE COLD- ROLLED STEEL. HOUSING AND LENS
END CAPS ARE INJECTION MOLDED PLASTIC WITH 7/8" KNOCK
OUT.
LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM
EFFICACY OF 140LUMENS/WATT, WITH A MINIMUM CRI OF 80.
· LUMENS = 4,000 LM FOR FIXTURE "B1" AND "B1E".
· LUMENS = 5,000LM FOR FIXTURE "B2" AND "B2E".
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - CSA CERTIFIED TO US. FOR USE IN DAMP
LOCATIONS BETWEEN -20C AND 40C.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=48" X W=3.5" X D=3.75")
4' LED LINEAR STRIP FIXTURE
10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC
TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE
"B1E AND B2E".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - RECESSED MOUNTING.
6.
7.
8.
FIXTURE TYPE: A1, A2, A2E, A3
HOUSING - CONSTRUCTED OF A METAL HOUSING WITH
DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE
DIFFUSER FOR EVEN ILLUMINATION.
LIGHT SOURCE - 4000K COLOR TEMPERATURE ,
MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A
MINIMUM CRI OF 80.
· LUMENS = 3,000 LM FOR FIXTURE "A1" .
· LUMENS = 4,000LM FOR FIXTURE "A2" AND "A2E".
· LUMENS = 4,800LM FOR FIXTURE "A3".
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")
2X4 RECESSED LED
10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC
TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE
"A2E".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - WALL MOUNT ABOVE MIRROR.
6.
7.
HOUSING - IS CONSTRUCTED OF AN ACRYLIC DIFFUSER.
LIGHT SOURCE - 4000K COLOR TEMPERATURE,
MINIMUM EFFICACY OF 100 LUMENS/WATT, WITH A
MINIMUM CRI OF 80, LUMENS = 1,889LM FOR
FIXTURE "V1".
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL LISTED TO US SAFETY STANDARDS.
LISTED FOR DAMP LOCATIONS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: FIXTURE "V1" (L=24" X W=4.4"
X D=2")
2' LED SQUARE VANITY FIXTURE
FIXTURE TYPE: V1
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.
6.
7.
8.
FIXTURE TYPE: A1SMK, A1ESMK
HOUSING - CONSTRUCTED OF A METAL HOUSING WITH
DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE
DIFFUSER FOR EVEN ILLUMINATION.
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")
2X4 SURFACE MOUNTED LED
10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC
TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE
"A1ESMK".
LIGHT SOURCE - 4000K COLOR TEMPERATURE,
MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A
MINIMUM CRI OF 80.
· LUMENS = 3,000LM FOR FIXTURE "A1SMK"
· LUMENS = 3,00LM FOR FIXTURE "A1ESMK".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.
6.
7.
8.
FIXTURE TYPE: C1SMK, C1ESMK, C2SMK, C2ESMK, C3SMK
HOUSING - CONSTRUCTED OF A METAL HOUSING WITH
DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE
DIFFUSER FOR EVEN ILLUMINATION.
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")
2X4 SURFACE MOUNTED LED
10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC
TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE
TYPE "C1ESMK" AND "C2ESMK".
LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM
EFFICACY OF 128-132.6 LUMENS/WATT, WITH A MINIMUM CRI
OF 80.
· LUMENS = 3,000LM FOR FIXTURE "C1SMK".
· LUMENS = 4,000LM FOR FIXTURE "C2SMK" AND "C2ESMK".
· LUMENS = 4,800LM FOR FIXTURE "C3SMK".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO METAL TRUSSES.
6.
7.
HOUSING - ONE-PIECE 5VA FIBERGLASS HOUSING WITH
INTERGRAL PERIMETER CHANNEL UTILIZING CONTINUOUS
POURED-IN-PLACE NEMA 4X GASKET. APPROVED FOR
THROUGH WIRING. CAPTIVE POLYMERIC LATCHES. FROSTED
,LOW PROFILE, POLYCARBONATE LENSE.
LIGHT SOURCE - 4000K COLOR TEMPERATURE,
MINIMUM EFFICACY OF 100 LUMENS/WATT, WITH A
MINIMUM CRI OF 80, LUMENS = 8,000 LM FOR
FIXTURE "G".
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - CSA CERTIFIED TO UL STANDARDS.
SUITABLE FOR WET LOCATION. IP65, IP66, IP67 RATED. NSF
SPLASH ZONE 2 AND NON-FOOD RATED. NEMA 4X RATED.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: FIXTURE "G" (L=51.75" X
W=6.8" X D=4.2")
4' LED STRIP FIXTURE
FIXTURE TYPE: G
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.
6.
7.
HOUSING - CONSTRUCTED OF A METAL HOUSING WITH
DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE
DIFFUSER FOR EVEN ILLUMINATION.
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=23.7" X W=23.7" X D=2.38")
2X2 SURFACE MOUNTED LED
LIGHT SOURCE - 4000K COLOR TEMPERATURE,
MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A
MINIMUM CRI OF 80.
· LUMENS = 4,000LM FOR FIXTURE "C4SMK"
FIXTURE TYPE: C4SMK
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
Z:\
3_
Pro jec ts\
2 -
US
DA
St illw ate r O
K P lan t S cie nc es
La b R en ov ati on s\D
RA
WI
NG
S\E L5
.dw g Ju n 1 3,
- 1 2:0
0p m
USDA AGRICULTURAL RESEARCH SERVICE
WPOFCRU MAIN LABORATORY
WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS
STILLWATER, OK
EL500
06/12/24
S.M.E.
B.C.W
G.A.C
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
3623-E
XXX
XXX
XXX
XXX 78
ELECTRICAL LIGHTING
SCHEDULE
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5.
6.
7.
FIXTURE TYPE: X
LED EXIT SIGN
HOUSING - DIE-CAST ALUMINUM CONSTRUCTION - COMPACT
HOUSING. FULLY OVERLAPPING LIGHT SEAL TO PREVENT
LIGHT LEAKS. UNIVERSAL DIRECTIONAL CHEVRON
KNOCKOUTS.
· X - DOUBLE SIDED CHEVRON SIGN.
LIGHT SOURCE - LED'S MOUNTED ON PRINTED CIRCUIT
BOARD. 10 YEARS WARRANTY.
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE.
GREEN LETTERS AS INDICATED. PROVIDE CHEVRONS AS
INDICATED EITHER LEFT, RIGHT OR BOTH DIRECTIONS AS
INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING
AS REQUIRED.
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT
TYPE BATTERY CHARGER WITH MAINTENANCE-FREE,
NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
TEST SWITCH.
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING,
WALL OR END-OF-FIXTURE MOUNTING.
ILLUMINATION - PROVIDED BY RED HIGH-OUTPUT LEDS
INSIDE OF FIXTURE HOUSING. PROVIDE POLYSTYRENE
DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR
MAXIMUM LED LIGHT OUTPUT.
VOLTAGE - OPERATING VOLTAGE OF 120-277V.
8. NOM. DIMENSIONS: (L=11.75" X W=8.25" X D=2").
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - RECESSED MOUNTING.
6.
7.
8.
FIXTURE TYPE: C1, C1E
HOUSING - CONSTRUCTED OF A METAL HOUSING WITH
DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE
DIFFUSER FOR EVEN ILLUMINATION.
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")
2X4 RECESSED LED
10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC
TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE
TYPE "C1E".
LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM
EFFICACY OF 128-132.6 LUMENS/WATT, WITH A MINIMUM CRI
OF 80.
· LUMENS = 3,000LM FOR FIXTURE "C1" AND "C1E".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - RECESS MOUNT TO GYP BOARD CEILING.
6.
7.
8.
FIXTURE TYPE: D1
HOUSING - GALVANIZED STEEL MOUNTING PLASTER FRAME,
GALVANIZED STEEL JUNCTION BOX WITH BOTTOM-HINGED
ACCESS COVERS AND SPRING LATCHES. TWO COMBINATION
1/2"-3/4" AND 4 1/2" KNOCKOUTS FOR STRAIGHT-THROUGH
CONDUIT RUNS.
LIGHT SOURCE - 4000K COLOR TEMPERATURE,
MINIMUM EFFICACY OF 80 LUMENS/WATT, WITH A
MINIMUM CRI OF 80, LUMENS = 750LM.
DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO
10%. (0-10 VOLT DIMMING)
CERTIFICATION - CERTIFIED TO US SAFETY STANDARDS. WET
LOCATION STANDARD (COVERED CEILING). IP55 RATED.
THIS SKETCH IS A NON-PROPRIETARY GRAPHIC
REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
NOM. DIMENSIONS: (L=9.5" X W=11.25" X D=4")
LED CAN FIXTURE
10W, BATTERY PACK WITH SELF-DIAGNOSTIC TESTING
FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE "GE".
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5.
6.
7.
FIXTURE TYPE: X1
LED EXIT SIGN
HOUSING ENGINEERING GRADE THERMOPLASTIC HOUSING
IS IMPACT-RESISTANT AND CORROSION PROOF.
· X1 - SINGLE SIDED CHEVRON SIGN WITH.
LIGHT SOURCE - LED'S MOUNTED ON PRINTED CIRCUIT
BOARD. 10 YEARS WARRANTY.
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE.
GREEN LETTERS AS INDICATED. PROVIDE CHEVRONS AS
INDICATED EITHER LEFT, RIGHT OR BOTH DIRECTIONS AS
INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING
AS REQUIRED.
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT
TYPE BATTERY CHARGER WITH MAINTENANCE-FREE,
NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
TEST SWITCH.
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING,
WALL OR END-OF-FIXTURE MOUNTING.
ILLUMINATION - PROVIDED BY RED HIGH-OUTPUT LEDS
INSIDE OF FIXTURE HOUSING. PROVIDE POLYSTYRENE
DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR
MAXIMUM LED LIGHT OUTPUT.
VOLTAGE - OPERATING VOLTAGE OF 120-277V.
8. NOM. DIMENSIONS: (L=19.25" X W=4.75" X D=8").
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5. MOUNTING - SURFACE MOUNT TO CANOPY.
6.
8.
HOUSING - CAST-ALUMINUM HOUSING WITH POWDER COAT
FINISH SEALED…