EXISTING SINGLE-POLE, SINGLE-THROW SWITCH TO BE DEMOLISHED.S

EXISTING NON-FUSED DISCONNECT TO BE DEMOLISHED.

EXISTING PANELBOARD TO BE DEMOLISHED.

EXISTING WALL MOUNTED FIXTURE TO BE DEMOLISHED.

EXISTING SURFACE MOUNTED FIXTURE TO BE DEMOLISHED.

EXISTING CEILING MOUNTED RECEPTACLE TO REMAIN.

EXISTING PANELBOARD TO REMAIN.

EXISTING CEILING MOUNTED RECEPTACLE TO BE DEMOLISHED.

EXISTING EXIT SIGN WITH EMERGENCY FIXTURES TO BE

DEMOLISHED.

EXISTING SURFACE MOUNTED LINEAR FIXTURE TO BE DEMOLISHED.

EXISTING 2X4 RECESSED FIXTURE TO BE DEMOLISHED.

EXISTING CAN LIGHT TO BE DEMOLISHED.

EMERGENCY BUG LIGHT TO BE DEMOLISHED.

EXISTING PANELBOARD TO BE DEMOLISHED.

EXISTING WALL MOUNTED FIXTURE TO BE DEMOLISHED.

EXISTING METER TO REMAIN.

ETR

EXISTING EXIT SIGN TO BE DEMOLISHED.

ETR

SMK

SMK

ETR EXISTING LED HIGH BAY FIXTURES TO REMAIN.

EXISTING LED HIGH BAY FIXTURES TO BE DEMOLISHED.

EXISTING 2X4 FIXTURE WITH SURFACE MOUNT KIT TO BE

DEMOLISHED.

EXISTING 2X2 FIXTURE WITH SURFACE MOUNT KIT TO BE

DEMOLISHED.

EXISTING VANITY FIXTURE TO BE DEMOLISHED.

A. PRIOR TO BEGINNING WORK, SURVEY EXISTING ELECTRICAL SYSTEMS.

DOCUMENT, IN WRITING, SIGNED BY THE CONTRACTING OFFICER, ANY

PORTIONS OF THE EXISTING SYSTEMS THAT ARE NOT OPERATING PROPERLY

BEFORE CONSTRUCTION BEGINS. ANY ELECTRICAL SYSTEMS FOUND

INOPERABLE AT THE END OF THE CONSTRUCTION PROCESS THAT HAVE NOT

BEEN SO DOCUMENTED SHALL BE REPAIRED BY THE CONTRACTOR AT HIS

OWN EXPENSE.

B. PRIOR TO BEGINNING THE DEMOLITION PROCESS, CONDUCT A

COMPREHENSIVE SITE SURVEY WITH THE ASSISTANCE OF THE CONTRACTING

OFFICER. IDENTIFY AND MARK ALL EXISTING EQUIPMENT TO REMAIN AND ALL

EXISTING RACEWAYS AND CIRCUITRY THAT ARE PRESENTLY PASSING

THROUGH THE CONSTRUCTION AREA THAT ARE FEEDING EXISTING

EQUIPMENT TO REMAIN.

C. REMOVE ELECTRICAL EQUIPMENT FEEDING OTHER EQUIPMENT BEING

DEMOLISHED. REMOVE RACEWAYS AND CIRCUITRY BACK TO THE PANEL OF

ORIGINATION. WHERE CIRCUITS ARE NOT BEING COMPLETELY DEMOLISHED,

REMOVE RACEWAYS AND CIRCUITRY BACK TO A JUNCTION BOX OR OTHER

COMMON CONNECTION POINT AND RECIRCUIT EXISTING ELECTRICAL

EQUIPMENT TO REMAIN AS REQUIRED. WHERE NECESSARY, COMPLETELY

REFEED EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IF REQUIRED.

IT IS THE INTENT OF THESE DOCUMENTS THAT ALL EXISTING EQUIPMENT TO

REMAIN BE KEPT COMPLETELY OPERABLE DURING CONSTRUCTION AND LEFT

COMPLETELY OPERABLE AT THE END OF THE CONSTRUCTION PROCESS.

D. THE ELECTRICAL EQUIPMENT SHOWN IS PROVIDED TO CONVEY THE

APPROXIMATE SCOPE OF THE WORK.

E. PROVIDE BLANK OUTLET COVERS FOR ALL EXISTING OUTLET BOXES AS

REQUIRED.

F. PERFORM DEMOLITION WORK AS FOLLOWS:

1. DEMOLISH DEVICE OR END OF LINE EQUIPMENT.

2. DEMOLISH RACEWAYS BACK TO A JUNCTION BOX OR OTHER COMMON

CONNECTION POINT AND CIRCUITRY FEEDING END OF LINE EQUIPMENT

(INCLUDING ALL RACEWAYS AND CIRCUITRY ASSOCIATED WITH

CONTROLS).

3. LEAVE ALL RACEWAYS AND CIRCUITRY THAT COMPLETELY

PASS-THROUGH THE SPACE COMPLETELY OPERABLE BY REROUTING

THE CIRCUITS AS REQUIRED.

EXISTING STROBE TO REMAIN.

EXISTING HORN/STROBE TO REMAIN.

EXISTING MANUAL PULL STATION TO BE RELOCATED TO 45" A.F.F.

EXISTING SMOKE DETECTOR TO REMAIN.

EXISTING SMOKE DETECTOR TO BE RELOCATED.

EXISTING CEILING MOUNTED STROBE TO REMAIN.

F

RL

RL

S

ETR

F

F

F

ETR

ETR

ETR

EXISTING HORN TO BE DEMOLISHED.

EXISTING CIRCUITRY AND RACEWAYS TO BE DEMOLISHED.

BASE BID:

1. BUILDING 17 (MAIN LAB)

ADDITIVE ALTERNATE #1:

1. ALL GREEN HOUSE WORK.

ADDITIVE ALTERNATE #2:

1. BUILDING 18 (HEADHOUSE)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D0

.dw g Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED000

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL DEMOLITION

LEGEND AND NOTES

2B

2C

2A

6 8 10

1A

1B

9 11

12 14 16

11-C

MEN

WOMEN

18 20 22

17 23

TELECOM

SOIL ROOM

MEN

WOMEN

OFFICEOFFICEOFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE OFFICE

OFFICE

LABLAB

LAB LAB

LAB LAB

LABLAB

STORAGESTORAGE

BREAK ROOM

MECH. ROOM

INCUBATION/

STORAGE

LIBRARY/CONFERENCE

STORAGE

JANITOR

F

S

S

S

S

S

S

S

S

S

S S

S

S S S

S S S S S S

S

S S S S S

MDP

LO-3

LO-1

LO-2

MCC

S S SS

RL

F F F

F S

F

RLF

RL RL RL RL

RL

F

RL

DATA

RACK

ETR

S S

S S S SSSSEF

ETR

DP-2

UTILITY

TRANSFORMER

RLRL SRL SRLRL SSRL ETR ETR ETR ETR

S

ETR

S

S

ETR

ETR

ETR

ETR

ETR

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

SMK

ETR

ETR

ETR

ATS2

ETRATS1

ETR

L4

TDBB

F

RL

FRL

ETR

ETR

ETR

ETR

ETR

S S S S S S S S SS

S S

S S

SS

SSSSSSSS

S

S S

S SS

S S

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D1

.dw g Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED101

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

BASED BID WORK.

B. ALL LIGHTING CIRCUITRY IS EXISTING TO

REMAIN. ALL FIXTURES ON THIS SHEET SHALL BE

DEMOLISHED. SEE SHEET EL100 FOR NEW

LIGHTING PLAN.

C. ALL EXTERIOR FIXTURES MEAN OF CONTROL

SHALL REMAIN.

GENERAL NOTE

SCALE:

ELECTRICAL

1/8" = 1'-0"

PLAN

NORTH

ED101

ELECTRICAL DEMOLITION PLAN -

BUILDING 17

SCALE:

ELECTRICAL

1/8" = 1'-0"

PLAN

NORTH

ED101

2A

6 8 10

1A

1B

9 11

12 14 16

11-C

MEN

WOMEN

18 20 22

17 23

TELECOM

SOIL ROOM

MEN

WOMEN

OFFICEOFFICEOFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE OFFICE

OFFICE

LABLAB

LAB LAB

LAB LAB

LABLAB

STORAGESTORAGE

BREAK ROOM

MECH. ROOM

INCUBATION/

STORAGE

LIBRARY/CONFERENCE

STORAGE

JANITOR

LO-1

LO-2

1 & 2

ED300

HYDRONIC

WATER HEATER

HYDRONIC

WATER HEATER

SF (ROOF)

EF (ROOF)

EF (ROOF)

HYDRONIC

WATER HEATER

HYDRONIC

WATER HEATER

HYDRONIC

WATER HEATER

EF (ROOF)

EF (ROOF)

FUME HOOD

DP-2

UTILITY

TRANSFORMER

ETR

ETR ETR

ETRHYDRONIC

WATER HEATER MDP

LO-3

MCC

ETR

EF (ROOF)

ETR

ETR

HYDRONIC

WATER HEATER HEATING COIL

HEATING COIL

HEATING COIL

8 HYDRONIC

WATER HEATER

FUME HOOD

HYDRONIC

WATER HEATER

ATS2

ETRATS1

ETR

EF (ROOF)

2 6

FUME HOOD

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D1

A.d wg Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED101A

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

1 DEMOLISH EXISTING HYDRONIC WATER UNIT

HEATER. RETAIN DISCONNECT, CIRCUITRY,

RACEWAYS, AND BREAKER. SEE SHEET EP101

FOR NEW WORK.

2 DEMOLISH EXISTING ROOF- MOUNTED EXHAUST

FAN. SEE SHEET EP104 FOR DEMOLITION WORK.

SEE SHEET EP104 FOR NEW WORK.

3 DEMOLISH EXISTING ROOF-MOUNTED SUPPLY

FAN. SEE SHEET EP104 FOR DEMOLITION WORK.

SEE SHEET EP104 FOR NEW WORK.

4 DEMOLISH FUME HOOD EXHAUST FAN. RETAIN

CIRCUITRY, RACEWAYS, AND BREAKER. SEE

SHEET EP101 FOR NEW WORK.

5 DEMOLISH EXISTING HYDRONIC HOT WATER

RADIANT HEATER, DISCONNECT, CIRCUITRY,

RACEWAYS, AND BREAKER. SEE SHEET EP101

FOR NEW WORK.

6 DEMOLISH EXISTING HEATING COIL,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER. SEE SHEET EP101 FOR NEW WORK.

KEYED NOTES

SCALE:

ELECTRICAL POWER

1/8" = 1'-0"

PLAN

NORTH

ED101A

ELECTRICAL DEMOLITION PLAN -

BUILDING 17

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

BASED BID WORK.

GENERAL NOTE

UP

DN

S S

S S

S

S

S

RL

F

S S

SMK SMK

SMKSMK

SMK

SMK

SMK

SMK

SMK SMK SMK

SMKSMKSMK

SMKSMKSMK

SMK

RL

F

RL

F

LH1

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

S

LH2

FACP FAC

ETRETR

ETRETR

F

F ETR

F ETR

F

ETR

F

ETR

F

F

ETR

ETR

ETR

RL

F

F

ETR

OPEN TO WORK AREA BELOW

OPEN TO WORK AREA BELOW

EF-2

EF-3

EF-2

EF-3

(208V, 3Ø, 3HP)(208V, 3Ø, 3HP)

(208V, 3Ø, 5HP)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D1

.dw g Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED102

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

1 DEMOLISH EXISTING WALL-MOUNTED EXHAUST,

DISCONNECT, AND 30/3 BREAKER IN PANEL LH-1

SPACE 26. RETAIN EXISTING CIRCUITRY AND

RACEWAYS. SEE SHEET EP101 FOR NEW WORK.

2 DEMOLISH EXISTING WALL-MOUNTED SUPPLY,

DISCONNECT, AND 15/3 BREAKER IN PANEL LH-1

IN SPACE 27. RETAIN EXISTING CIRCUITRY AND

RACEWAYS. SEE SHEET EP101 FOR NEW WORK.

3 DEMOLISH EXISTING ROOF-MOUNTED EXHAUST

FAN AND BREAKER. RETAIN EXISTING

DISCONNECT, CIRCUITRY, AND RACEWAYS. SEE

SHEET EP101 FOR NEW WORK.

4 DEMOLISH EXISTING WALL-MOUNTED EXHAUST,

SUPPLY FAN CONTROLLER, DISCONNECT,

CIRCUITRY, RACEWAYS, AND BREAKER.

5 EXISTING FIRE ALARM CONTROL PANEL SHALL

REMAIN. FIRELITE MS-5UD FALCO ALARM

COMPANY (405)-743-4201.

6 EXISTING REMAIN FIRE ALARM COMMUNICATOR

SHALL REMAIN. HONEYWELL HWF2V-COM.

7 DEMOLISH EXISTING WALL-MOUNTED SUPPLY,

DISCONNECT, AND 15/3 BREAKER IN PANEL LH-2

IN SPACE 11. RETAIN EXISTING CIRCUITRY AND

RACEWAYS. SEE SHEET EP101 FOR NEW WORK.

KEYED NOTES

SCALE:

ELECTRICAL FIRST FLOOR

1/8" = 1'-0"

PLAN

NORTH

ED102

ELECTRICAL DEMOLITION PLAN -

BUILDING 18

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

ADDITIVE ALTERNATE #2 WORK.

B. ALL EXTERIOR FIXTURES MEAN OF CONTROL

SHALL REMAIN.

GENERAL NOTE

SCALE:

ELECTRICAL MEZZANINE

1/8" = 1'-0"

PLAN

NORTH

ED102 SCALE:

ELECTRICAL ROOF

1/8" = 1'-0"

PLAN

NORTH

ED102

18 E 18 F

17 J17 H17 G17 F

17 A 17 B 17 C 17 D 17 E

27 24

L-G14 L-G15

L-G8 L-G9

GREEN HOUSE

17 H

GREEN HOUSE

17 J GREEN HOUSE

18 E

GREEN HOUSE

18 F

L-G15-GL

ETR

ETR ETR ETR

ETR

S

S

S

S

S

S

S

S

L-G6

L-G7

GREEN HOUSE

17 F

GREEN HOUSE

17 G

L-G6B

ETR

ETR

ETRS

S

S

S

L-G1 L-G2 L-G3 L-G4 L-G5

ETR

ETR

GREEN HOUSE

17 A GREEN HOUSE

17 B

GREEN HOUSE

17 C

GREEN HOUSE

17 D

GREEN HOUSE

17 E

L-G1B ETR ETR ETR ETR

S

S3

S

S

S

S

S3 S3 S3 S3

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D1

.dw g Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED103

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

KEY PLAN

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

BUILDINGS 17 A-E DEMOLITION PLANS (GREENHOUSES)1

BUILDINGS 17 F-G DEMOLITION PLANS (GREENHOUSES)

SCALE: 1/16"=1'-0"

2 BUILDINGS 17 H-J DEMOLITION PLANS (GREENHOUSES)3 BUILDINGS 18 E-F DEMOLITION PLANS (GREENHOUSES)4

SCALE: 1/16"=1'-0"

SCALE: 1/16"=1'-0"SCALE: 1/16"=1'-0"

ED103

ED103 ED103 ED103

GENERAL NOTES

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

ADDITIVE ALTERNATE #1 WORK.

B. SEE SHEET EP103 AND EL103 FOR ALL NEW

WORK.

C. THE LOCATION AND NUMBER OF ELECTRICAL

DEVICES ON THIS SHEET IS BASED ON

DRAWINGS PROVIDED TO US BY THE

GOVERNMENT FROM 1980 AND A SITE

SURVEY CONDUCTED BY OUR TEAM.

DEMOLITION SHALL INCLUDE ALL

RECEPTACLES BELOW 24". PERFORM

DEMOLITION WORK AS FOLLOWS:

C.1. DEMOLISH DEVICE OR END OF LINE

EQUIPMENT.

C.2. DEMOLISH CIRCUITRY BACK TO

BREAKER.

C.3. DEMOLISH RACEWAYS ABOVE THE SLAB.

CAP AND ABANDON ALL RACEWAYS

ROUTED UNDER THE SLAB.

D. FLUORESCENT FIXTURES TO BE DEMOLISHED

ARE ALL HOUSE LIGHTING FIXTURES. DO NOT

DEMOLISH ANY GROW LIGHTS-EVEN IF THEY

ARE FLUORESCENT FIXTURES.

ELECTRICAL DEMOLITION PLAN -

GREENHOUSES

SF (ROOF)

EF (ROOF)

EF (ROOF)

EF (ROOF)

EF (ROOF)

EF (ROOF)EF (ROOF)

EF (ROOF)

SF (ROOF)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D1

.dw g Ju n 1 3,

- 1 1:5

8a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED104

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

1 DEMOLISH EXISTING ROOF-MOUNTED EXHAUST

FAN, DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER. SEE SHEET EP104 FOR NEW WORK.

2 DEMOLISH EXISTING ROOF-MOUNTED SUPPLY

FAN, DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER. SEE SHEET EP104 FOR NEW WORK.

KEYED NOTES

SCALE:

ELECTRICAL ROOF

1/8" = 1'-0"

PLAN

NORTH

ED104

ELECTRICAL POWER PLAN -

BUILDING 17

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

BASE BID WORK.

MECH. ROOM

1 1 1 1

ETR

ETRMDP

LO-3

MCC

ETR

ATS1

ETR1213

7 7

6 6

10 11

MECH. ROOM

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D3

.dw g Ju n 1 3,

- 1 1:5

9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED300

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

SCALE:

BUILDING 17 MECHANICAL ROOM

1/4" = 1'-0"

PLAN

NORTH

KEYED NOTES

1. DEMOLISH EXISTING AIR HANDLING UNIT,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER. NOT TO BE REPLACED.

2. DEMOLISH EXISTING CHILLER, DISCONNECT,

CIRCUITRY, RACEWAYS, AND BREAKER. SEE

SHEET EP300 FOR NEW WORK.

3. DEMOLISH EXISTING BOILER, DISCONNECT,

CIRCUITRY, RACEWAYS, AND BREAKER. SEE

SHEET EP300 FOR NEW WORK

4. DEMOLISH EXISTING CHILLED WATER PUMP,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER. SEE SHEET EP300 FOR NEW WORK.

5. DEMOLISH EXISTING HEATING HOT WATER PUMP

AND DISCONNECT. RETAIN CIRCUITRY,

RACEWAYS, AND BREAKER. SEE SHEET EP300

FOR NEW WORK.

6. DEMOLISH EXISTING RETURN AIR FAN,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

7. DEMOLISH EXISTING EXPANSION TANK,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

8. DEMOLISH EXISTING UNIT HEATER,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

9. DEMOLISH EXISTING HOOD SUPPLY FAN,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

10. DEMOISH EXISTING ROOF-MOUNTED

MECHANICAL ROOM VENTILATION FAN,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

11. DEMOLISH EXISTING ROOF-MOUNTED

MECHANICAL ROOM EXHAUST FAN,

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

12. DEMOLISH EXISTING AIR COMPRESSOR

DISCONNECT, CIRCUITRY, RACEWAYS, AND

BREAKER.

13. DEMOLISH EXISTING AIR DRYER, DISCONNECT,

CIRCUITRY, RACEWAYS, AND BREAKER.

KEYED NOTES

SCALE:

BUILDING 17 MECHANICAL ROOM

1/4" = 1'-0"

PLAN

NORTH

ED300 ED300

EXIST. DOMESTIC

WATER HEATING

EQUIPMENT TO REMAIN

ELECTRICAL DEMOLITION PLAN -

MECHANICAL ROOM BUILDING 17

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

BASED BID WORK.

MDP

GRADE

EXTERIOR OF THE

BUILDING.

MAIN LABORATORY

BUILDING 17

MCC

EXISTING DIP

POLE TO REMAIN

Scale: NONE

ED600

ELECTRICAL - EXISTNG SINGLE LINE (BASE BID)

LO-3

(SECTION 1)

ETR ETR

EXISTING

500KVA,

120/208V, 3Ø

TRANSFORMER

TO REMAIN.

ETR

LO-1

ETR

LO-2

ETR

HEAD HOUSE

BUILDING 18.

LH-1

ETR

CORRIDOR

DP-2

ETR

ANNEX

L4

ETR

PANEL L-22

ETR

LH-2

ETR

ATS2: 800A

208Y/120V

SERVICE

ENTRANCE

RATED,

3-POLE

ETR

ATS1: 1200A

208Y/120V

SERVICE

ENTRANCE

RATED,

3-POLE

ETR

ETR

GENERATOR

250KW, .8PF,

208Y/120V, 3Ø, 4W

ETR ETR

ETR

ETR

ETR ETR

ETR

ETR

ETR

ETR

ETR

ETR

TO PULL BOX (SEE

DETAIL 2 ON THIS SHEET)

Scale: NONE

ED600

ELECTRICAL - EXISTNG PULLBOX SINGLE LINE (ADDITIVE ALTERNATE #2)

RM 7

L-22

ETR

PULL BOX (FIELD

VERIFY LOCATION

PRIOR TO BEGINNING

WORK)

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

TO MDP IN BUILDING 17 (RM 18)

TO MDP IN BUILDING 17 (RM 18)

TO MDP IN BUILDING 17 (RM 18)

TO MDP IN BUILDING 17 (RM 18)

TO GREENHOUSES 18A, 18B, & 18C

TO GREENHOUSES 18D, 18E, & 18F

TO GREENHOUSES 17F & 17G

TO GREENHOUSES 17H & 17J

GRADE

LO-3

(SECTION 2)

ETR

3 3

ETR ETR

ETR

TO MDP IN BUILDING 17 (RM 18)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D6

.dw g Ju n 1 3,

- 1 1:5

9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED600

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL DEMOLITION

EXISTING SINGLE LINE

1 EXISTING CIRCUITRY AND RACEWAYS TO

GREENHOUSES 17A, 17B, AND 17C SHALL

REMAIN.

2 EXISTING CIRCUITRY AND RACEWAYS TO

GREENHOUSES 17D & 17E. SHALL REMAIN.

3 THIS EQUIPMENT WAS NOT INSTALLED DURING

OUR SITE SURVEY VISIT. SEE GENERAL NOTE

A ON THIS SHEET.

KEYED NOTES

GENERAL NOTES

A. OUR SITE SURVEY OF THE EXISTING CONDITIONS

WAS CONDUCTED PRIOR TO INSTALLATION OF

THE EMERGENCY GENERATOR PROJECT NO:

P09651.0100. THE SINGLE LINE SHOWN IS BASED

ON THE EXISTING CONDITIONS DURING THE SITE

SURVEY AND PROJECT: P9651.0100.

B. DP-2 PANEL SCHEDULE IS NOT SHOWN AS WE ARE

NOT MODIFYING THE PANEL. IT HAS AN 800/3 MAIN,

225/3 FEEDING 225A PANEL IN ANNEX, A 100/3

FEEDING PANEL L-22 IN ROOM 7, A 225/3 SPARE,

AND A 100/3 SPARE.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D7

.dw g Ju n 1 3,

- 1 1:5

9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED700

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL DEMOLITION PANEL

SCHEDULES

A. ALL PANEL SCHEDULES SHOWN ON THIS SHEET

ARE FOR REFERENCE ONLY.

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D7

.dw g Ju n 1 3,

- 1 1:5

9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED701

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL DEMOLITION PANEL

SCHEDULES

GENERAL NOTE

A. ALL WORK INVOLVING GREENHOUSES IS

ALTERNATE #1 WORK.

B. ALL PANEL SCHEDULES ON THIS SHEET IS FOR

REFERENCE ONLY.

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E D7

.dw g Ju n 1 3,

- 1 1:5

9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

ED702

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL DEMOLITION PANEL

SCHEDULES

A. ALL WORK INVOLVING GREENHOUSES IS

ALTERNATE #1 WORK.

B. ALL PANEL SCHEDULES ON THIS SHEET IS FOR

REFERENCE ONLY.

1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS

OTHERWISE NOTED.

2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT CIRCUIT INTERRUPTING

DEVICES.

3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF WHILE-IN-USE.

4. DEVICES NOTED AS "ETR" SHALL BE EXISTING TO REMAIN.

5. DEVICES NOTED AS "RL" SHALL BE RELOCATED.

6. FIXTURES NOTED AS "SMK" SHALL HAVE A SURFACE MOUNT KIT.

7. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY PACKS. LED DIMMER MOUNT CENTERLINE OF BOX AT 45"A.F.F. UNLESS NOTED

OTHERWISE.

SINGLE-POLE, SINGLE-THROW SWITCH. MOUNT CENTERLINE OF BOX AT

45"A.F.F. UNLESS NOTED OTHERWISE.

POWER PACK.PP

S

D

S M

HORSEPOWER RATED SWITCH WITH THERMAL OVERLOADS (MANUAL

MOTOR STARTER).

ST

PASSIVE INFRARED AND ULTRASONIC DUAL TECHNOLOGY OCCUPANCY

SENSOR WITH A 12' RADIAL COVERAGE. CEILING MOUNTED.MD1

F-?

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO BOTTOM OF

BOX UNLESS NOTED OTHERWISE.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE COVER PLATE,

MOUNTED 18" A.F.F. TO BOTTOM OF BOX UNLESS NOTED OTHERWISE.

FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER OF

POLES/ENCLOSURE TYPE; F-(RATING OF FUSES).

NON-FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER

OF POLES/ENCLOSURE TYPE.

PANELBOARD.

SURFACE MOUNTED OR SUSPENDED FIXTURE.

SURFACE MOUNTED OR SUSPENDED EMERGENCY FIXTURE.

RECESSED CEILING FIXTURE.

CEILING MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS INDICATED

BY ARROWS.

WALL MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS INDICATED BY

ARROWS.

WALL MOUNTED FIXTURE.

WALL MOUNTED LINEAR FIXTURE.

SURFACE MOUNT FIXTURE.

NOTE: THE NUMBER INSIDE THE CIRCLE IS THE CIRCUIT NUMBER. THE LETTER BESIDE THE SYMBOL

IS THE FIXTURE TYPE DESCRIBED IN THE LIGHT FIXTURE SCHEDULE.

CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING.

TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT

GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE

PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND

THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS

SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT

GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE,

THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS

PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE

PROVIDED.

CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR FLOOR.

TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT

GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE

PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND

THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS

SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT

GROUNDING CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS

TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN

EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.

CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED

SURFACE-MOUNTED RACEWAY (SEE SPECIFICATIONS).

HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED

CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT

NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE

THEM MAY NOT SHOW THE CIRCUIT NUMBERS AT THE HOMERUN

ARROWS.

PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL PARTIAL

HOMERUNS THAT ARE ON THE SAME CIRCUIT IN A JUNCTION BOX

PRIOR TO ENTERING THE PANELBOARD.

LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR

CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS FOR

CONDUCTOR REQUIREMENTS.

EMERGENCY FIXTURE.

AUTOMATIC WALL SWITCH. MOUNT CENTERLINE OF BOX AT 45" A.F.F.

UNLESS NOTED OTHERWISE.

2'X2' RECESSED FIXTURE.

TELECOMMUNICATIONS & DATA BACKBOARD

2'X4' RECESSED FIXTURE.

S M2

DUAL TECHNOLOGY, DUAL RELAY WALL SWITCH. MOUNT CENTERLINE

OF BOX AT 45" A.F.F. UNLESS NOTED OTHERWISE. WITH TWO

CIRCUITS-ONE FOR LIGHTS AND THE OTHER FOR THE EXHAUST FAN

SHOWN ON EP101.

F

S D

D R

F

F

FAC

FACP

MANUAL PULL STATION MOUNTED 45"A.F.F. TO CENTERLINE OF

BOX.

STROBE MOUNTED 80"A.F.F. TO BOTTOM OF BOX.

COMBINATION HORN AND STROBE. MOUNTED 80"A.F.F. TO BOTTOM

OF BOX.

SMOKE DETECTOR.

DUCT SMOKE DETECTOR IN RETURN DUCT.

DUCT SMOKE DETECTOR IN SUPPLY DUCT.

FIRE ALARM CONTROL PANEL.

FIRE ALARM COMMUNICATION.

FIRE ALARM STROBE MOUNTED ON THE CEILING TO A FLUSH

MOUNTED BOX.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 42"A.F.F. TO CENTERLINE

OF BOX UNLESS NOTED OTHERWISE. RECEPTACLE SHALL BE G.F.I TYPE

AND UTILIZE CAST METAL BOXES WITH GASKETED METALLIC

WEATHERPROOF-WHILE-IN-USE COVER.

TWO-POLE, 30A SWITCH MOUNTED IN CAST METAL BOX ADJACENT

WATER HEATER FOR USE AS A DISCONNECT.

S 2P

COMBINATION TELEPHONE/DATA OUTLET MOUNTED 18" A.F.F. TO

CENTERLINE OF BOX UNLESS NOTED OTHERWISE.

FIRE ALARM HORN AND STROBE MOUNTED ON THE CEILING TO A

FLUSH MOUNTED BOX.FAHS

S

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 42"A.F.F. TO

CENTERLINE OF BOX UNLESS NOTED OTHERWISE. RECEPTACLE SHALL

BE G.F.I TYPE AND UTILIZE CAST METAL BOXES WITH GASKETED

METALLIC WEATHERPROOF-WHILE-IN-USE COVER.

MAGNETIC MOTOR STARTER.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E -00

0.d wg

Ju n 1

3,

- 1

1:5 9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

E-000 06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL NEW WORK

LEGEND

REQUIREDBREAKER

AMPACITY

CIRCUITRY SIZING TABLE

CIRCUITRY

2 #12, #12(G), 3/4" C.15

POLES

2 #12, #12(G), 3/4" C.20 1 2 #10, #10(G), 3/4" C.30 1 2 #8, #10(G), 3/4" C.40 1 2 #6, #10(G), 1" C.50 1 2 #4, #8(G), 1 1/4" C.60 1 2 #12, #12(G), 3/4" C.15 2 2 #12, #12(G), 3/4" C.20 2 2 #10, #10(G), 3/4" C.30 2 2 #8, #10(G), 3/4" C.40 2 2 #6, #10(G), 1" C.50 2 2 #4, #8(G), 1 1/4" C.60 2 3 #12, #12(G), 3/4" C.15 3 3 #12, #12(G), 3/4" C.20 3 3 #10, #10(G), 3/4" C.30 3 3 #8, #10(G), 3/4" C.40 3 3 #6, #10(G), 1" C.50 3 3 #4, #8(G), 1 1/4" C.60 3 4 #4, #8(G), 1 1/4" C.70 3 4 #3, #8(G), 1 1/4" C.80 3 4 #2, #8(G), 1 1/4" C.90 3 4 #1, #8(G), 1 1/2" C.100 3 4 #1/0, #6(G), 1 1/2" C.125 3

150 3 4 #2/0, #6(G), 2" C.175 3

200 3

4 #1/0, #6(G), 1 1/2" C.

4 #3/0, #6(G), 2" C.

4 #4/0, #4(G), 2 1/2" C.225 3

250 3 4 #250, #4(G), 3" C.

4 #350KCM, #4(G), 3" C.300 3

350 3 4 #500KCM, #3(G), 3 1/2" C.

4 #500KCM, #3(G), 3 1/2" C.400 3

500 3 TWO RUNS 3" C., EACH WITH 4 #250KCM, #2(G)

600 3 700 3 800 3

TWO RUNS 3 1/2" C., EACH WITH 4 #500KCM, #1/0(G)

TWO RUNS 3 1/2" C., EACH WITH 4 #350KCM, #1(G)

TWO RUNS 3 1/2" C., EACH WITH 4 #500KCM, #1/0(G)

A. REPLACE EXISTING MAIN SWITCHBOARD SHOWN ON THE DEMOLITION DRAWINGS

WITH A NEW SWITCHBOARD SHOWN ON THE NEW WORK DRAWINGS. USE EXISTING

CIRCUITRY TO THE EXTENT PRACTICAL. WHERE NECESSARY TO REACH NEW

BREAKERS, SPLICE CONDUCTORS USING COMPRESSION CONNECTORS INSIDE NEW

PANELS AND EXTEND THE CIRCUITRY USING THE TABLE BELOW.

B. ALL CIRCUIT BREAKERS SHOWN IN THE TABLE MAY NOT BE USED IN THIS PROJECT.

C. FOR CIRCUIT BREAKERS IN BETWEEN THE SIZES SHOWN, USE CIRCUITRY FOR THE

NEXT LARGER CIRCUIT BREAKER.

D. COORDINATE THE REQUIREMENTS FOR NEUTRALS FOR 2-POLE AND 3-POLE

BREAKERS WITH EXISTING EQUIPMENT LOADS. PROVIDE NEUTRALS WHERE

REQUIRED BY EQUIPMENT. DO NOT PROVIDE NEUTRALS WHERE NOT REQUIRED BY

EQUIPMENT. THE TABLE ASSUMES THAT NEUTRALS ARE NEEDED FOR 3-POLE 70

CIRCUITS AND LARGER, BUT NOT NEEDED FOR SMALLER 3-POLE CIRCUITS.

CIRCUITRY SIZING TABLE NOTES:

MSA

GRADE

EXTERIOR OF THE

BUILDING.

MAIN LABORATORY

BUILDING 17

EXISTING DIP

POLE TO REMAIN

Scale: NONE

E-600

ELECTRICAL - EXISTNG SINGLE LINE (BASE BID)

LO-3

(SECTION 1)

ETR

EXISTING

500KVA,

120/208V, 3Ø

TRANSFORMER

TO REMAIN.

ETR

LO-1

ETR

LO-2

ETR

HEAD HOUSE

BUILDING 18.

LH-1

ETR

CORRIDOR

DP-2

ETR

ANNEX

L4

ETR

PANEL L-22

ETR

LH-2

ETR

ATS2: 800A

208Y/120V

SERVICE

ENTRANCE

RATED,

3-POLE

ETR

ATS1: 1200A

208Y/120V

SERVICE

ENTRANCE

RATED,

3-POLE

ETR

ETR

GENERATOR

250KW, .8PF,

208Y/120V, 3Ø, 4W

ETR ETR

ETR

ETR

ETR ETR

ETR

ETR

ETR

ETR

ETR

ETR

TO PULL BOX (SEE

DETAIL 2 ON THIS SHEET)

Scale: NONE

E-600

ELECTRICAL - EXISTNG PULLBOX SINGLE LINE (ADDITIVE ALTERNATE #2)

RM 7

L-22

ETR

PULL BOX

(FIELD VERIFY

LOCATION

PRIOR TO

BEGINNING

WORK)

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

TO MSA IN BUILDING 17 (RM 18)

TO MSA IN BUILDING 17 (RM 18)

TO MSA IN BUILDING 17 (RM 18)

TO MSA IN BUILDING 17 (RM 18)

TO GREENHOUSES 18A, 18B, & 18C

TO GREENHOUSES 18D, 18E, & 18F

TO GREENHOUSES 17F & 17G

TO GREENHOUSES 17H & 17J

GRADE

LO-3

(SECTION 2)

ETR

3 3

EXTERIOR OF THE

BUILDING.

NLO-5 NLO-6

ETR

4 #4/0, #4(G), 2-1/2"C.

ETRETR

TO MSA IN BUILDING 17 (RM 18)

ETR

3-1/2"C. EACH CONTAINING

4 RUNS OF 4#350KCM, #3/0(G)

4 #1, #6(G), 1-1/2"C.

(5.5% IMPEDANCE)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E -60

0.d wg

Ju n 1

3,

- 1

1:5 9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

E-600 06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL NEW WORK SINGLE

LINE DIAGRAM

1 EXISTING CIRCUITRY AND RACEWAYS TO

GREENHOUSES 17A, 17B, AND 17C SHALL

REMAIN.

2 EXISTING CIRCUITRY AND RACEWAYS TO

GREENHOUSES 17D & 17E. SHALL REMAIN.

3 THIS EQUIPMENT WAS NOT INSTALLED DURING

OUR SITE SURVEY VISIT. SEE GENERAL NOTE

A ON THIS SHEET.

4 ROUTE 2#14, #14(G), 3/4"C. TO ENERGY

MANAGEMENT SYSTEM TO PROVIDE A SIGNAL

THAT EACH ATS IS OPERATING IN GENERATOR

POSITION. THE CONTROL SYSTEM

CONTRACTOR SHALL PROGRAM THE SYSTEM

TO SHUT OFF THE CHILLER WHEN RUNNING

ON THE GENERATION.

KEYED NOTES

GENERAL NOTES

A. OUR SITE SURVEY OF THE EXISTING CONDITIONS

WAS CONDUCTED PRIOR TO INSTALLATION OF

THE EMERGENCY GENERATOR PROJECT NO:

P09651.0100. THE SINGLE LINE SHOWN IS BASED

ON THE EXISTING CONDITIONS DURING THE SITE

SURVEY AND PROJECT: P9651.0100. FIELD VERIFY

EXISTING CONDITIONS PRIOR TO SUBMITTING

ELECTRICAL BROCHURES FOR REVIEW. NOTIFY

CONTRACTING OFFICER OF AN DISCREPANCIES

B. DP-2 PANEL SCHEDULE IS NOT SHOWN AS WE ARE

NOT MODIFYING THE PANEL. IT HAS AN 800/3 MAIN,

225/3 FEEDING 225A PANEL IN ANNEX, A 100/3

FEEDING PANEL L-22 IN ROOM 7, A 225/3 SPARE,

AND A 100/3 SPARE.

C. COMPLY COMPLETELY WITH ALL UTILITY

COMPANY REQUIREMENTS EVEN IF DIFFERENT

FROM THE INFORMATION SHOWN. NOTIFY THE

ENGINEER AT LEAST TEN DAYS PRIOR TO BID OF

ANY DISCREPANCIES BETWEEN THE UTILITY

COMPANY REQUIREMENTS AND THE INFORMATION

SHOWN. PAY ALL UTILITY COMPANY CHARGES.

CONTACT STILLWATER ELECTRIC UTILITY TANYA

BACON (TANYA.BACON@STILLWATER.ORG).

D. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND

EQUIPMENT, DARKER COLORS DENOTE NEW

CIRCUITRY AND EQUIPMENT.

FOR REFERENCE ONLY

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E -70

0.d wg

Ju n 1

3,

- 1

1:5 9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

E-700 06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL NEW WORK PANEL

SCHEDULES

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E -70

1.d wg

Ju n 1

3,

- 1

1:5 9a m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

E-701 06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL NEW WORK PANEL

SCHEDULE

GENERAL NOTES

A. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND

EQUIPMENT, DARKER COLORS DENOTE NEW

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E -70

2.d wg

Ju n 1

3,

- 1

2:0 0p m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

E-702 06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL NEW WORK PANEL

SCHEDULE

GENERAL NOTES

A. LIGHT COLORS DENOTE EXISTING CIRCUITRY AND

EQUIPMENT, DARKER COLORS DENOTE NEW

2A

6 8 10

1A

1B

9 11

12 14 16

11-C

MEN

WOMEN

18 20 22

17 23

TELECOM

SOIL ROOM

MEN

WOMEN

OFFICEOFFICEOFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE OFFICE

OFFICE

LABLAB

LAB LAB

LAB LAB

LABLAB

STORAGESTORAGE

BREAK ROOM

MECH. ROOM

INCUBATION/

STORAGE

LIBRARY/CONFERENCE

STORAGE

JANITOR

A2

A2

A2

A2

A2

A2 A3

A3

A3

A2E

A2

A2EA2 A2 A2E A2 A2E A2 A2E A2 A2E A2 A2E A2 A2E A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A1 A1

A1 A1

A1 A1

A1

A1

A1 A2 A2

A2 A2

A2 A2

A2 A2

A2

A2

A2 A2

A2 A2

A2

A2E

A2E

A2E

A2

A2

A2

A2

A2

A2 A2

A2E

A1

A1

A1

A1

A1

A1

A2

A2

A2

A2

A2

A2

X

D

X

X

D

D

WE W

D

D

D

S M

S M

S M

D D

D D D D

X

A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK

S S D D D

LO-1

LO-2

W WE

FE

X X X

WE WEWE WE

X

A2 A2 A2 A2

A2 A2 A2 A2

A2 A2

A2

A2

FDATA

RACKD1

D1

D1

D1

D1

ETR

A2

A2

A2

A2

A2

A2

B1 B1 B1

B1E

B1EB1

B1B1B1E

B1

V

V

V1

V1

D D D DS

M

D1

A2E

A2

A2

A2

A2

A2

A2

A2

A1

A1

A1

A2

A2

A2

A2

A2

A2

MSA

LO-3

ETR

DP-2

UTILITY

TRANSFORMER

ETR

ETR

ETR

PPMD1

PPMD1

PP

MD1

PP

MD2

PP

MD1

PP

MD1

PP

MD2

PP

MD1

PP

MD1

PP

MD1MD1MD1MD1

MD1

MD1

PP

MD1

PP

MD1

PP

MD1

PP

MD1

PP

MD1

PP

MD1

PP

MD1MD1

MD2

PPMD1

PPMD1

MD2 MD2 MD2 MD2 MD2 MD1

PP

PPETR

ETR

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK

A1ESMK A1SMK A1SMK A1SMK A1ESMK A1SMK

ETR

ATS1

ETR

ATS2

ETR

L-22

ETR

PP

PP

PP

PP

MD1

PP

MD1

S M

PP

1 PP

1 1 1 1 1 1

1 1

PP

MD1 1

PP

MD2

D

NLO-5

NLO-6

1 1 1

A2

A2

A2

A2

A2E

A2

A2

A2

A2

A2

A2

A2

A1

A1

A1

A1

A1

A1

A2A2

A2A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A1

A1

A1

A1

A1

A1

A2A2A2

A2 A2E A2

A2 A2E A2

F

FE

FE

F

D1

D1 FE

F

F

L4 A1

A1E

TDBB

V

VE

V

VE

B1E

A1E

W

W

W

W

X

X

PP

MD1

PP

MD1

PP

MD1

PP

MD1

PP

MD1

PP MD11

PP

MD1

PP

MD2

PP

MD2

MD1 MD1MD1

PP1

PP

MD1

PP

MD1

PP

MD1

PP

MD1

1D D D D

S

M

S

M

S

MD1

PP

D

D

PP

MD1

PP MD11

S

D

DDDDD

S T

SWITCH FOR

EXTERIOR

LIGHTS

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E L1

.dw g Ju n 1 3,

- 1 2:0

0p m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

EL101

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

SCALE:

ELECTRICAL

1/8" = 1'-0"

PLAN

NORTH

EL101

ELECTRICAL LIGHTING PLAN -

BUILDING 17

SCALE:

ELECTRICAL

1/8" = 1'-0"

PLAN

NORTH

EL101

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

BASE BID WORK.

B. ALL LIGHTING CIRCUITRY IS EXISTING TO

REMAIN. UNLESS OTHERWISE SHOWN.

C. PROVIDE UNSWITCHED POWER TO ALL

EMERGENCY BATTERY PACKS.

D. PROVIDE BLANK COVERS FOR ALL UNUSED

SWITCH OUTLETS.

E. ALL EXTERIOR FIXTURES SHALL BE CONNECTED

TO THEIR EXISTING MEANS OF CONTROL.

GENERAL NOTE

1 PROVIDE UNSWITCHED POWER FROM THE

EXISTING CIRCUIT FEEDING THE EXISTING

LIGHTS TO POWER PACK AND TO ALL

FIXTURES WITH BATTERY PACKS. FIXTURES

WITH BATTERY PACKS SHALL BE SWITCHED

WITH OCCUPANCY SENSOR AND CONTROLLED

BY WALL SWITCH IN ALL ROOMS. FIXTURES

WITH BATTERY PACKS IN CORRIDORS SHALL

BE UNSWITCHED NIGHT LIGHTS.

KEYED NOTES

C3 C3 C2 C2

C2E

C2E

C2E

C2EV1

V1

D

M S

M

S

M

S

M

D

S

C4

X

X1 X1

X1

WE

W

WE

W

WE

W

B2

SMK SMK

SMKSMK

SMK

SMK

SMK

SMK

SMK SMK SMK

SMKSMKSMK

SMKSMKSMK

SMK

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

C1E

C1

C1

C1

C1

C1

B2

B2E

B2

B2E

B2

S

LH1LH2

FACP FAC

ETRETR

ETRETR

D

PPMD2

NO

ROOF

WORK

C1

C1

C1

C1

C1

C1E

C1

C1

C1

C1

C1E

C1

C1

C1

C1

B2E

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E L1

.dw g Ju n 1 3,

- 1 2:0

0p m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

EL102

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

SCALE:

ELECTRICAL FIRST FLOOR

1/8" = 1'-0"

PLAN

NORTH

SCALE:

ELECTRICAL MEZZANINE

1/8" = 1'-0"

PLAN

NORTH

EL102 EL102

ELECTRICAL LIGHTING PLAN -

BUILDING 18

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

ADDITIVE ALTERNATE #2 WORK.

B. ALL LIGHTING CIRCUITRY IS EXISTING TO

REMAIN. UNLESS OTHERWISE SHOWN.

C. PROVIDE UNSWITCHED POWER TO ALL

EMERGENCY BATTERY PACKS.

D. PROVIDE BLANK COVERS FOR ALL UNUSED

SWITCH OUTLETS.

E. ALL EXTERIOR FIXTURES SHALL BE CONNECTED

TO THEIR EXISTING MEANS OF CONTROL.

GENERAL NOTE

KEYED NOTES

1 PROVIDE UNSWITCHED POWER FROM THE

EXISTING CIRCUIT FEEDING THE EXISTING

LIGHTS TO POWER PACK AND TO ALL

FIXTURES WITH BATTERY PACKS. FIXTURES

WITH BATTERY PACKS SHALL BE SWITCHED

WITH OCCUPANCY SENSOR AND CONTROLLED

BY WALL SWITCH IN ALL ROOMS. FIXTURES

WITH BATTERY PACKS IN CORRIDORS SHALL

BE UNSWITCHED NIGHT LIGHTS.

17 A 17 B 17 C 17 D 17 E

27 24

G

G

G

G

G

G G

G

G

G

G

G

G

G

G

G

G G

G

G

G

G

GREEN HOUSE

17 H

GREEN HOUSE

17 J GREEN HOUSE

18 E

GREEN HOUSE

18 F

S

S

S

S

S

S

S

S

WP WP WP WP

WP WP WP WP

S

3 WP S

3 WP

S

3 WP

S

3 WP

G

G

G

G

G

G

G

G

G

G

G

G

G

GREEN HOUSE

17 F

GREEN HOUSE

17 G

S

S

S

S

3 WP WP

WP

WP

S

3 WP

S

3 WP

S

3 WP S

3 WP

G

G

G

G

G

G

G

G

G

G

G

G

G

G

NO

LIGHTING

WORK

G

G

G

G

G

G

G

G

G

G

GREEN HOUSE

17 A GREEN HOUSE

17 B

GREEN HOUSE

17 C

GREEN HOUSE

17 D

GREEN HOUSE

17 E

S

S

S

S

S

S

S

S

S

S

WP WP WP WP WP

WPWPWPWPWP

S

3 WP

S

3 WP

S

3 WP

S

3 WP

S

3 WP

S

3 WP S

3 WP

S

3 WP S

3 WP

S

3 WP

S

3 WP

S

3 WP

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E L1

.dw g Ju n 1 3,

- 1 2:0

0p m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

EL103

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

KEY PLAN

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

BUILDINGS 17 A-E LIGHTING PLANS (GREENHOUSES)1

BUILDINGS 17 F-G LIGHING PLANS (GREENHOUSES)

SCALE: 1/16"=1'-0"

2 BUILDINGS 17 H-J LIGHTING PLANS (GREENHOUSES)3 BUILDINGS 18 E-F LIGHTING PLANS (GREENHOUSES)4

SCALE: 1/16"=1'-0"

SCALE: 1/16"=1'-0"SCALE: 1/16"=1'-0"

EL103

EL103 EL103 EL103

ELECTRICAL LIGHTING PLAN -

GREENHOUSES

A. ALL WORK SHOWN ON THIS SHEET SHALL BE

ADDITIVE ALTERNATE #1 WORK.

LUMINAIRE REQUIREMENTS:

FIXTURE TYPE: B1, B1E, B2, B2E

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.

6.

7.

8.

HOUSING - CHANNEL AND COVER ARE FORMED FROM

CODE-GAUGE COLD- ROLLED STEEL. HOUSING AND LENS

END CAPS ARE INJECTION MOLDED PLASTIC WITH 7/8" KNOCK

OUT.

LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM

EFFICACY OF 140LUMENS/WATT, WITH A MINIMUM CRI OF 80.

· LUMENS = 4,000 LM FOR FIXTURE "B1" AND "B1E".

· LUMENS = 5,000LM FOR FIXTURE "B2" AND "B2E".

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - CSA CERTIFIED TO US. FOR USE IN DAMP

LOCATIONS BETWEEN -20C AND 40C.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=48" X W=3.5" X D=3.75")

4' LED LINEAR STRIP FIXTURE

10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC

TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE

"B1E AND B2E".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - RECESSED MOUNTING.

6.

7.

8.

FIXTURE TYPE: A1, A2, A2E, A3

HOUSING - CONSTRUCTED OF A METAL HOUSING WITH

DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE

DIFFUSER FOR EVEN ILLUMINATION.

LIGHT SOURCE - 4000K COLOR TEMPERATURE ,

MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A

MINIMUM CRI OF 80.

· LUMENS = 3,000 LM FOR FIXTURE "A1" .

· LUMENS = 4,000LM FOR FIXTURE "A2" AND "A2E".

· LUMENS = 4,800LM FOR FIXTURE "A3".

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")

2X4 RECESSED LED

10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC

TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE

"A2E".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - WALL MOUNT ABOVE MIRROR.

6.

7.

HOUSING - IS CONSTRUCTED OF AN ACRYLIC DIFFUSER.

LIGHT SOURCE - 4000K COLOR TEMPERATURE,

MINIMUM EFFICACY OF 100 LUMENS/WATT, WITH A

MINIMUM CRI OF 80, LUMENS = 1,889LM FOR

FIXTURE "V1".

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL LISTED TO US SAFETY STANDARDS.

LISTED FOR DAMP LOCATIONS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: FIXTURE "V1" (L=24" X W=4.4"

X D=2")

2' LED SQUARE VANITY FIXTURE

FIXTURE TYPE: V1

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.

6.

7.

8.

FIXTURE TYPE: A1SMK, A1ESMK

HOUSING - CONSTRUCTED OF A METAL HOUSING WITH

DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE

DIFFUSER FOR EVEN ILLUMINATION.

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")

2X4 SURFACE MOUNTED LED

10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC

TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE

"A1ESMK".

LIGHT SOURCE - 4000K COLOR TEMPERATURE,

MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A

MINIMUM CRI OF 80.

· LUMENS = 3,000LM FOR FIXTURE "A1SMK"

· LUMENS = 3,00LM FOR FIXTURE "A1ESMK".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.

6.

7.

8.

FIXTURE TYPE: C1SMK, C1ESMK, C2SMK, C2ESMK, C3SMK

HOUSING - CONSTRUCTED OF A METAL HOUSING WITH

DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE

DIFFUSER FOR EVEN ILLUMINATION.

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")

2X4 SURFACE MOUNTED LED

10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC

TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE

TYPE "C1ESMK" AND "C2ESMK".

LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM

EFFICACY OF 128-132.6 LUMENS/WATT, WITH A MINIMUM CRI

OF 80.

· LUMENS = 3,000LM FOR FIXTURE "C1SMK".

· LUMENS = 4,000LM FOR FIXTURE "C2SMK" AND "C2ESMK".

· LUMENS = 4,800LM FOR FIXTURE "C3SMK".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO METAL TRUSSES.

6.

7.

HOUSING - ONE-PIECE 5VA FIBERGLASS HOUSING WITH

INTERGRAL PERIMETER CHANNEL UTILIZING CONTINUOUS

POURED-IN-PLACE NEMA 4X GASKET. APPROVED FOR

THROUGH WIRING. CAPTIVE POLYMERIC LATCHES. FROSTED

,LOW PROFILE, POLYCARBONATE LENSE.

LIGHT SOURCE - 4000K COLOR TEMPERATURE,

MINIMUM EFFICACY OF 100 LUMENS/WATT, WITH A

MINIMUM CRI OF 80, LUMENS = 8,000 LM FOR

FIXTURE "G".

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - CSA CERTIFIED TO UL STANDARDS.

SUITABLE FOR WET LOCATION. IP65, IP66, IP67 RATED. NSF

SPLASH ZONE 2 AND NON-FOOD RATED. NEMA 4X RATED.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: FIXTURE "G" (L=51.75" X

W=6.8" X D=4.2")

4' LED STRIP FIXTURE

FIXTURE TYPE: G

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO EXPOSED CEILING.

6.

7.

HOUSING - CONSTRUCTED OF A METAL HOUSING WITH

DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE

DIFFUSER FOR EVEN ILLUMINATION.

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=23.7" X W=23.7" X D=2.38")

2X2 SURFACE MOUNTED LED

LIGHT SOURCE - 4000K COLOR TEMPERATURE,

MINIMUM EFFICACY OF 120 LUMENS/WATT, WITH A

MINIMUM CRI OF 80.

· LUMENS = 4,000LM FOR FIXTURE "C4SMK"

FIXTURE TYPE: C4SMK

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

Z:\

3_

Pro jec ts\

2 -

US

DA

St illw ate r O

K P lan t S cie nc es

La b R en ov ati on s\D

RA

WI

NG

S\E L5

.dw g Ju n 1 3,

- 1 2:0

0p m

USDA AGRICULTURAL RESEARCH SERVICE

WPOFCRU MAIN LABORATORY

WPOFCRU MAINTENANCE AND DEFICIENCY REPAIRS

STILLWATER, OK

EL500

06/12/24

S.M.E.

B.C.W

G.A.C

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

3623-E

XXX

XXX

XXX

XXX 78

ELECTRICAL LIGHTING

SCHEDULE

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5.

6.

7.

FIXTURE TYPE: X

LED EXIT SIGN

HOUSING - DIE-CAST ALUMINUM CONSTRUCTION - COMPACT

HOUSING. FULLY OVERLAPPING LIGHT SEAL TO PREVENT

LIGHT LEAKS. UNIVERSAL DIRECTIONAL CHEVRON

KNOCKOUTS.

· X - DOUBLE SIDED CHEVRON SIGN.

LIGHT SOURCE - LED'S MOUNTED ON PRINTED CIRCUIT

BOARD. 10 YEARS WARRANTY.

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE.

GREEN LETTERS AS INDICATED. PROVIDE CHEVRONS AS

INDICATED EITHER LEFT, RIGHT OR BOTH DIRECTIONS AS

INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING

AS REQUIRED.

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT

TYPE BATTERY CHARGER WITH MAINTENANCE-FREE,

NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND

TEST SWITCH.

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING,

WALL OR END-OF-FIXTURE MOUNTING.

ILLUMINATION - PROVIDED BY RED HIGH-OUTPUT LEDS

INSIDE OF FIXTURE HOUSING. PROVIDE POLYSTYRENE

DIFFUSER IN COLOR INDICATED WITH

FREQUENCY-MATCHED SILKSCREEN COATING FOR

MAXIMUM LED LIGHT OUTPUT.

VOLTAGE - OPERATING VOLTAGE OF 120-277V.

8. NOM. DIMENSIONS: (L=11.75" X W=8.25" X D=2").

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - RECESSED MOUNTING.

6.

7.

8.

FIXTURE TYPE: C1, C1E

HOUSING - CONSTRUCTED OF A METAL HOUSING WITH

DECORATIVE PLASTIC END CAPS. WITH POLYCARBONATE

DIFFUSER FOR EVEN ILLUMINATION.

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - UL 1598 CERTIFIED TO U.S. STANDARDS.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=47.4" X W=5.5" X D=2.6")

2X4 RECESSED LED

10W, 1,400 LUMEN BATTERY PACK WITH SELF-DIAGNOSTIC

TESTING FEATURE AND 90 BATTERY PACK FOR FIXTURE

TYPE "C1E".

LIGHT SOURCE - 4000K COLOR TEMPERATURE, MINIMUM

EFFICACY OF 128-132.6 LUMENS/WATT, WITH A MINIMUM CRI

OF 80.

· LUMENS = 3,000LM FOR FIXTURE "C1" AND "C1E".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - RECESS MOUNT TO GYP BOARD CEILING.

6.

7.

8.

FIXTURE TYPE: D1

HOUSING - GALVANIZED STEEL MOUNTING PLASTER FRAME,

GALVANIZED STEEL JUNCTION BOX WITH BOTTOM-HINGED

ACCESS COVERS AND SPRING LATCHES. TWO COMBINATION

1/2"-3/4" AND 4 1/2" KNOCKOUTS FOR STRAIGHT-THROUGH

CONDUIT RUNS.

LIGHT SOURCE - 4000K COLOR TEMPERATURE,

MINIMUM EFFICACY OF 80 LUMENS/WATT, WITH A

MINIMUM CRI OF 80, LUMENS = 750LM.

DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO

10%. (0-10 VOLT DIMMING)

CERTIFICATION - CERTIFIED TO US SAFETY STANDARDS. WET

LOCATION STANDARD (COVERED CEILING). IP55 RATED.

THIS SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

NOM. DIMENSIONS: (L=9.5" X W=11.25" X D=4")

LED CAN FIXTURE

10W, BATTERY PACK WITH SELF-DIAGNOSTIC TESTING

FEATURE AND 90 BATTERY PACK FOR FIXTURE TYPE "GE".

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5.

6.

7.

FIXTURE TYPE: X1

LED EXIT SIGN

HOUSING ENGINEERING GRADE THERMOPLASTIC HOUSING

IS IMPACT-RESISTANT AND CORROSION PROOF.

· X1 - SINGLE SIDED CHEVRON SIGN WITH.

LIGHT SOURCE - LED'S MOUNTED ON PRINTED CIRCUIT

BOARD. 10 YEARS WARRANTY.

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE.

GREEN LETTERS AS INDICATED. PROVIDE CHEVRONS AS

INDICATED EITHER LEFT, RIGHT OR BOTH DIRECTIONS AS

INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING

AS REQUIRED.

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT

TYPE BATTERY CHARGER WITH MAINTENANCE-FREE,

NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND

TEST SWITCH.

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING,

WALL OR END-OF-FIXTURE MOUNTING.

ILLUMINATION - PROVIDED BY RED HIGH-OUTPUT LEDS

INSIDE OF FIXTURE HOUSING. PROVIDE POLYSTYRENE

DIFFUSER IN COLOR INDICATED WITH

FREQUENCY-MATCHED SILKSCREEN COATING FOR

MAXIMUM LED LIGHT OUTPUT.

VOLTAGE - OPERATING VOLTAGE OF 120-277V.

8. NOM. DIMENSIONS: (L=19.25" X W=4.75" X D=8").

LUMINAIRE REQUIREMENTS:

1.

2.

3.

4.

5. MOUNTING - SURFACE MOUNT TO CANOPY.

6.

8.

HOUSING - CAST-ALUMINUM HOUSING WITH POWDER COAT

FINISH SEALED…