E_-_Revision_1_Electrical_Drawings.pdf

PDF 3 MB Posted

Attached to
Anacostia II WWPS PLC Upgrades project
Solicitation number
98587
Issued by
Prince George's County, Maryland

About this file

This document is a set of electrical drawings (Revision 1) for the Anacostia II Wastewater Pump Station (WWPS) PLC Upgrades project, prepared by the Washington Suburban Sanitary Commission (WSSC) and designed by a licensed professional engineer in Maryland. The drawings provide detailed electrical specifications and site plans for the replacement, modification, and upgrade of the Distributed Process Control System (DPCS) at the Anacostia #2 Wastewater Pump Station located in Capitol Heights, Maryland. The scope of work includes installation of a new WSSC-furnished Pumping System PLC panel, demolition and upgrade of UPS and power panels, replacement of instrumentation including level meters, switches, transmitters, and pressure gauges, modification of Remote Terminal Units (RTU) and Remote Input/Output (RIO) units, relocation of pump motor starters, and installation of new DPCS network cabling and fiber-optic communications infrastructure. The drawings include site plans showing the electrical substation, screen room, chemical feed facility, pump station building, overall pump room layouts, conduit and wire schedules, and standard electrical details for conduit mounting, equipment enclosure installation, above-grade conduit penetrations, watertight conduit penetrations, and underground duct bank specifications. Sealed bid responses are due by 2:00 p.m. on March 26, 2026 (with an alternate deadline of April 9, 2026), with a mandatory site visit scheduled for March 11, 2026, at 10:00 a.m., and questions due by March 12, 2026, at 2:00 p.m.

Bidders must be Maryland-licensed General Contractors with a minimum of six years of experience in wastewater treatment or pumping station construction, including at least two completed projects valued at $500,000 or greater within the past five years. Key personnel, including a Project Manager and Foreman/Field Supervisor, must each have a minimum of five years of relevant experience. The contractor must employ a Control Systems Integrator subcontractor with minimum seven years' experience in municipal wastewater control systems and UL 508/508A fabrication capabilities. The project requires strict maintenance of plant operations (MOPO) procedures throughout construction due to the facility's continuous 24/7 operations, with constraints including maximum two simultaneous pump shutdowns, 21-day advance notice requirements, and minimum one business day between shutdowns. The total contract value is $2,500,000.00 for the complete construction services with a three-year base term and no renewal options. Pricing is structured as a fixed lump-sum base bid with contingent unit-price items available as directed during construction. Maryland Prevailing Wage requirements apply, with mandatory hourly wage rates ranging from $20.00 to $57.16 depending on classification, fringe benefits, and mandatory electronic payroll submission within 14 calendar days of each payroll period; contractors face liquidated damages of $10.00 per calendar day for delinquent payroll submissions. The solicitation includes a 15 percent Minority-Owned Business Enterprise (MBE) and Small Local Business Enterprise (SLBE) subcontracting goal. A 5 percent bid guarantee is required, along with 100 percent performance, payment, and maintenance bonds. All pricing must remain firm during the base term, with final payment due within 30 days of acceptance and a 20-day final acceptance test period demonstrating continuous system operation.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONTRACT: CP7725A24

DATE REVISIONS

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

DRAWN:

CHECKED:

DESIGN:

NO

OF 60

ANACOSTIA II WWPS

PLC UPGRADES

THESE DOCUMENTS CONTAIN

PRIVILEGED AND CONFIDENTIAL

INFORMATION WHICH SHALL NOT BE

REDISTRIBUTED WITHOUT PRIOR WSSC

APPROVAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 33083

EXPIRATION DATE: 12/18/2026

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

PA

TH

TE

M

PL

AT

E

LA

YO

U T

C U

R R

EN

T as o f:

/1 4/

10306 Eaton Place, Suite 220 Fairfax, VA 22030 Tel: (703) 691-6500

3/20/2026 - PLOT DATE

09/08/2025

09/08/2025

09/08/2025

SITE

PLAN

EX. WEST

METERING

VAULT

EX. EAST

METERING

VAULT

GENERAL NOTES:

KEYED NOTES:

REFER TO G-4 FOR PUMP ROOM BUILDING AREA

CLASSIFICATION PLANS.

METERING VAULTS ARE CLASS I, DIVISION 2 PER NFPA 820

TABLE 4.2.2 ROW 34 a. CLASSIFIED AREA COVERS ENTIRE

VAULT AND EXTENDS 3-FT IN ALL DIRECTIONS AROUND

OPENINGS AND VENTS.

NO WORK IS PERFORMED IN THIS AREA.

1. AREA CLASSIFICATION PLANS ON THIS SHEET WERE

PROVIDED BY WSSC WATER FROM ' ANACOSTIA NO.2

WWPS BAR SCREEN & NFPA 820 UPGRADES' CONFIRMED

DRAWINGS DATED AUGUST 2022.

2. NO MODIFICATIONS WILL BE MADE TO THE

CLASSIFICATION OF ANY AREAS AS A RESULT OF THIS

PROJECT.

3. PROVIDE ALL NECESSARY SEAL OFFS AS ANY CONDUIT

ENTERS OR EXITS CLASSIFIED AREAS IN ACCORDANCE

WITH NEC REQUIREMENT AND AS DEFINED IN THESE

CONTRACT DOCUMENTS.

G-3OVERALL AREA

CLASSIFICATION SITE PLAN

ELECTRICAL

SUBSTATION

SCREEN ROOM

CHEMICAL

FEED FACILITY

PUMP STATION

BUILDING

N

LEGEND

CLASS I, DIVISION 2 AREA.

CM

TM

RMM

REVISION 103/25/2026

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

DRAWN:

CHECKED:

DESIGN:

NO

OF 60

ANACOSTIA II WWPS

PLC UPGRADES

THESE DOCUMENTS CONTAIN

PRIVILEGED AND CONFIDENTIAL

INFORMATION WHICH SHALL NOT BE

REDISTRIBUTED WITHOUT PRIOR WSSC

APPROVAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 33083

EXPIRATION DATE: 12/18/2026

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

PA

TH

TE

M

PL

AT

E

LA

YO

U T

C U

R R

EN

T as o f:

/1 4/

10306 Eaton Place, Suite 220 Fairfax, VA 22030 Tel: (703) 691-6500

3/20/2026 - PLOT DATE

09/08/2025

09/08/2025

09/08/2025

PLAN

GENERAL NOTES:

KEYED NOTES:

EXISTING DEVICES TO REMAIN. DISCONNECT AND

REMOVE CONTROL AND SIGNAL WIRES TO SOURCE.

CLEAN EXISTING CONDUIT AND VERIFY CONDUIT IS

SUITABLE FOR RE-USE. PULL NEW WIRE FROM DEVICE TO

NEW PUMP SYSTEM PLC AS SHOWN ON RISER DIAGRAMS.

IF EXISTING UNDERGROUND CONDUIT IS DAMAGED,

PROVIDE NEW UNDERGROUND CONDUIT FOR CONTROL

AND SIGNAL WIRES AS SHOWN ON RISER DIAGRAM.

REFER TO SHEETS E-11 AND E-12 FOR THE RISER

DIAGRAM.

REFER TO SHEETS E-7 AND E-8 FOR ELECTRICAL ROOM

ENLARGED PLANS.

REFER TO SHEETS E-9 AND E-10 FOR PUMPING AREA

ENLARGED PLANS.

BOND TO THE EXISTING GROUNDING SYSTEM.

SAWCUT ROADWAY FOR INSTALLATION OF DUCTBANK.

AFTER INSTALLATION OF THE DUCTBANK, FILL & PATCH

THE SURFACE TO MATCH ADJACENT SURFACE FINISH

MATERIALS & FINISHES.

DASHED LINE TO DISTINGUISH BETWEEN

POWER/CONTROL CONDUITS AND SIGNAL CONDUITS.

CONDUITS SHALL BE SPECIFIED IN SPECIFICATION

SECTION 16050.

1. EXISTING CONDITIONS ARE SHOWN BASED ON WSSC

PROVIDED DOCUMENTATION AND SITE INSPECTION

DURING DESIGN. FIELD VERIFY EXISTING CONDITIONS

PRIOR TO PERFORMING ANY DEMOLITION WORK.

2. REFER TO PROCESS AND INSTRUMENTATION DRAWINGS

AND ELECTRICAL RISER DIAGRAM.

3. REFER TO DRAWING E-3 FOR GENERAL DEMOLITION

NOTES.

4. REFER TO SHEET G3 & G4 FOR AREA CLASSIFICATION

PLANS.

5. DUCTBANK ROUTING SHOWN FOR REFERENCE IF THE

EXISTING UNDERGROUND CONDUITS ARE NOT

RE-USABLE. ROUTE DUCTBANK TO AVOID EQUIPMENT

SHOWN FOR DEMOLITION AS A PART OF THE SURGE

TANKS REMOVAL PROJECT (CONTRACT 23303290A).

6. DIMENSIONS SHOWN ARE APPROXIMATE. REFER TO

DETAILS FOR ADDITIONAL DUCT BANK SECTION

DIMENSIONS.

E-4ELECTRICAL

SITE PLAN

ELECTRICAL

SUBSTATION

N

SCALE: 1" = 15'-0"

SCREEN ROOM

SITE

PUMP STATION

BUILDING

CHEMICAL FEED

FACILITY

CPC

TM

RMM

REVISION 103/25/2026

D E-26

- SECTION 1 SECTION 3

SECTION 2 SECTION 4

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

DRAWN:

CHECKED:

DESIGN:

NO

OF 60

ANACOSTIA II WWPS

PLC UPGRADES

THESE DOCUMENTS CONTAIN

PRIVILEGED AND CONFIDENTIAL

INFORMATION WHICH SHALL NOT BE

REDISTRIBUTED WITHOUT PRIOR WSSC

APPROVAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 33083

EXPIRATION DATE: 12/18/2026

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

PA

TH

TE

M

PL

AT

E

LA

YO

U T

C U

R R

EN

T as o f:

/1 4/

10306 Eaton Place, Suite 220 Fairfax, VA 22030 Tel: (703) 691-6500

3/20/2026 - PLOT DATE

09/08/2025

09/08/2025

09/08/2025

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 64859

EXPIRATION DATE: 05/06/2027

E-10

ELECTRICAL

OVERALL PUMP ROOM

NEW WORK PLAN

GENERAL NOTES:

1. REFER TO PROCESS AND INSTRUMENTATION DRAWINGS

AND ELECTRICAL RISER DIAGRAM.

2. REFER TO SHEET G-3 AND G-4 FOR HAZARDOUS AREA

CLASSIFICATION. PROVIDE ALL NECESSARY SEAL OFFS

AS ANY CONDUIT ENTERS OR EXITS CLASSIFIED AREAS IN

ACCORDANCE WITH NEC REQUIREMENTS AND AS

DEFINED HERE IN THESE CONTRACT DOCUMENTS.

3. EXISTING CONDITIONS ARE SHOWN BASED ON WSSC

PROVIDED RECORD DRAWINGS.

OVERALL PUMPING SYSTEM NEW WORK

LOWER LEVEL

PLAN

GRAPHIC SCALE

4 2 0 8

1/8" = 1'-0"

EAST

PUMP

ROOM

WEST

PUMP

ROOM

PUMP

NO.1

PUMP

NO.12

PUMP

NO.3

PUMP

NO.2

PUMP

NO.4

PUMP

NO.5

PUMP

NO.11

PUMP

NO.10

PUMP

NO.9

PUMP

NO.8

WEST

SCREENS

EFFLUENT

CHANNEL

EAST

SCREENS

EFFLUENT

CHANNEL

SOUTHEAST

WETWELL

SOUTHWEST

WETWELL

NORTHWEST

WETWELL

NORTHEAST

WETWELL

KEYED NOTES:

EXISTING DEVICES TO REMAIN. PROVIDE NEW CONDUIT

AND WIRE AS SHOWN ON RISER DIAGRAM AND CONDUIT

AND WIRE SCHEDULE.

SCREEN

CHANNEL NO. 1

(BYPASS

CHANNEL)

SCREEN

NO.2

SCREEN

NO.3

SCREEN

NO.4

SCREEN

NO.5

SCREEN

NO.6

SCREENS

INFLUENT

CHANNEL

P-370 P-360 P-390 P-350 P-340

P-300 P-310 P-380 P-320 P-330

N

CPC

TM

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

DRAWN:

CHECKED:

DESIGN:

NO

OF 60

ANACOSTIA II WWPS

PLC UPGRADES

THESE DOCUMENTS CONTAIN

PRIVILEGED AND CONFIDENTIAL

INFORMATION WHICH SHALL NOT BE

REDISTRIBUTED WITHOUT PRIOR WSSC

APPROVAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 33083

EXPIRATION DATE: 12/18/2026

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

PA

TH

TE

M

PL

AT

E

LA

YO

U T

C U

R R

EN

T as o f:

/1 4/

10306 Eaton Place, Suite 220 Fairfax, VA 22030 Tel: (703) 691-6500

3/20/2026 - PLOT DATE

09/08/2025

09/08/2025

09/08/2025

17ELECTRICAL

CONDUIT AND WIRE SCHEDULE E-13

CONDUIT AND WIRE

SCHEDULE

CPC

TM

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

DRAWN:

CHECKED:

DESIGN:

NO

OF 60

ANACOSTIA II WWPS

PLC UPGRADES

THESE DOCUMENTS CONTAIN

PRIVILEGED AND CONFIDENTIAL

INFORMATION WHICH SHALL NOT BE

REDISTRIBUTED WITHOUT PRIOR WSSC

APPROVAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I

AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 33083

EXPIRATION DATE: 12/18/2026

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

PA

TH

TE

M

PL

AT

E

LA

YO

U T

C U

R R

EN

T as o f:

/1 4/

10306 Eaton Place, Suite 220 Fairfax, VA 22030 Tel: (703) 691-6500

3/20/2026 - PLOT DATE

09/08/2025

09/08/2025

09/08/2025

30ELECTRICAL

STANDARD DETAIL I E-26

DETAIL A - CONDUIT MOUNTING

SCALE: NTS

DETAIL B - EQUIPMENT ENCLOSURE MOUNTED ON BRICK OR MASONRY WALL

SCALE: NTS

DETAIL C - EQUIPMENT MOUNTING RACK

DETAIL D - ABOVE GRADE CONDUIT PENETRATIONS THROUGH EXISTING BUILDING OR STRUCTURES

SCALE: NTS

DETAIL E - WATERTIGHT CONDUIT PENETRATION THROUGH EXISTING CONCRETE WALL

SCALE: NTS

DETAIL F - CONDUIT PENETRATION EXISTING WALL

SCALE: NTS

DETAIL G - CONDUIT PENETRATION

SCALE: NTS

CPC

TM

RMM

DETAIL N - UNDERGROUND DUCT BANK

DETAIL O - STRUCTURE PENETRATION

File details come from the government source that posted it. Updated .