This document is an electrical bid document for a first-level electrical project at 2852 South 11th Street in Springfield, Illinois, prepared by Fuhrmann Engineering (WRH Engineers, LLC). The bid documents, dated 04-09-2025 and expiring 11-30-2025, detail a comprehensive electrical system upgrade that includes the installation of a 300 kW natural gas-fired emergency generator. The project specifications require installing the generator on an 8-inch thick concrete pad, routing a 4-inch gas line both buried 30 inches below grade and exposed on the building, and connecting to the existing gas meter. Additional electrical work includes routing conduits for battery chargers and block heaters.
The project documents specify strict adherence to the 2020 National Electric Code, with requirements for a typed circuit directory for all panelboards. The electrical plan covers the entire first level of the facility, detailing room assignments and electrical infrastructure across various departments including Human Resources, Print Departments, EARS Offices, and various administrative spaces. The bid documents provide precise installation instructions, including surface restoration requirements, gas line routing specifications, and electrical conduit guidelines. The project appears to be for the Illinois Office of the Comptroller, with the electrical upgrade aimed at improving emergency power infrastructure and electrical system reliability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Invitation-for-bid-offer-to-the-state-of-illinois-v-25-3 - 7-14-25.pdf | ||
| Contract Template for IFB for IOC - 8-8-25.docx | DOCX document | |
| IOC_Plan_Set_Issued_08-08-25.pdf | ||
| Ipg-active-registered-vendor-disclosure-formerly-forms-b-v.23.1 - 7-14-25.docx | DOCX document | |
| E-1.pdf | ||
| Addendum No1-00-91-13 - 9-4-25.pdf | ||
| Invitation-for-bid-vendor-instructions-and-requirements - 8-13-25.docx | DOCX document | |
| IOC Project Manual.pdf | ||
| E-4.pdf | ||
| Vendor-Disclosure-Formerly-Forms-A - 7-14-25.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
P
RAMP UP
UP
DN
DN
DN
DN UP
DN
DN
FE
FE
FE
KB
ALARM
ANNUNCIATOR
PANEL
FE
FE
P
Men -- Women
Print Dept
Print Dept
Print Dept
Print Dept
Print Dept
Elevators
Print Shop Supplies
Room
EARS Office
EARS Office
EARS Office
EARS Office
Copier
Room
Office
Office
Office
Office
Room
Office 128 Conference Room
Office
Human Resources
Office
Office
Office
Kitchen
Vault
Security Desk
Entry
HR Server
Office
Alarms
Office
Office
Vestibule
Conference Room
Union Office 110A
Room
Mechanical Room
Records Center
Office
Vault
Office
Office
Office
Break Room
Office
Office
Internal Audit
Office
Records Center
Supplies Procurement
Supplies Procurement
Computer Lab
Room 118A
Break Rm 109A
Room 109B
JC
2852 SOUTH 11TH STREET
SPRINGFIELD. ILLINOIS 62703
P: 217.529.5577
WWW.FUHRMANN-ENG.COM
BID DOCUMENTS
R24-111
DATE: 04-09-2025
EXPIRES: 11-30-2025
1/8" = 1'-0"
FIRST LEVEL - ELECTRICAL
NORTH
E-2
1. PERFORM ALL WORK IN STRICT ACCORDANCE WITH THE 2020 EDITION OF
THE NATIONAL ELECTRIC CODE.
2. PROVIDE A TYPED CIRCUIT DIRECTORY FOR ALL PANELBOARDS.
X
1. INSTALL 300 KW, NATURAL GAS FIRED EMERGENCY GENERATOR IN THIS
LOCATION. INSTALL GENERATOR ON A 8" THICK CONCRETE PAD. PAD
SHALL EXTEND 6" PAST GENERATOR FOOTPRINT ON ALL SIDES.
2. ROUTE A 4" GAS LINE BURIED 30" BELOW GRADE. REMOVE SECTION OF
ASHPALT AS REQUIRED. RESTORE SURFACES TO ORIGINAL CONDITIONS.
3. ROUTE A 4" GAS LINE EXPOSED ON THE BUILDING. MOUNT GAS LINE TO
BUILDING. GAS LINE ELEVATION SHALL BE ABOVE THE ENTRY CANOPY
INTO THE BUILDING.
4. CONNECT NEW GAS LINE AT EXISTING GAS METER. COORDINATE WITH
GAS UTILITY.
5. ROUTE
BURIED 30" BELOW GRADE. ROUTE 4-#10 AWG & #10 AWG GND IN A 1"
CONDUIT FOR BATTERY CHARGER AND BLOCK HEATER. REMOVE
SECTION OF ASHPALT AS REQUIRED. RESTORE SURFACES TO ORIGINAL
CONDITIONS.
6. ROUTE
EXPOSED DOWN COLUMN. ROUTE 4-#10 AWG & #10 AWG GND IN A 1"
CONDUIT FOR BATTERY CHARGER AND BLOCK HEATER.