DWGs 2017 CMCF East FS.pdf
PDF 8 MB Posted
- Solicitation number
- RFP-171-250000002855-2
- Issued by
- Gogebic County, Michigan
About this file
These architectural and engineering documents detail the Cooler & Freezer Replacement and HVAC System Renovation project for the East Food Service Building at the Central Michigan Correctional Facility, located at 320 N. Hubbard in St. Louis, Michigan. The project, numbered 2016094.2 and dated August 2019, involves comprehensive mechanical, electrical, and architectural renovations for the facility's food service area. The design documents, prepared by WTA Architects and MacLean Associates, Inc., provide detailed floor plans, demolition plans, electrical and HVAC revisions, and mechanical specifications for replacing refrigeration equipment, updating electrical systems, and renovating the existing food service infrastructure.
The project scope includes replacing rooftop units (RTUs), installing new ductwork, updating electrical systems, and implementing mechanical revisions across the facility's food service building. The documents specify technical details such as equipment specifications for Trane Precedent rooftop units with varying cooling and heating capacities, new gas piping, ventilation systems, and electrical circuit modifications. The renovation aims to improve the facility's infrastructure with modern, efficient systems, including energy-efficient equipment, updated electrical circuits, and improved mechanical ventilation. The project documents indicate careful consideration of existing conditions, requiring contractors to verify site measurements, coordinate with other trades, and ensure a fully operational mechanical and electrical system upon completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DWG CMCF overall.pdf | ||
| RFP Billable Rate 25362 (1).pdf | ||
| LEIN Request 25362.pdf | ||
| Addendum 1 - 25362.pdf | ||
| SAMPLE Billable Rate Contract (Rev 04-25).pdf | ||
| DWGs 1989 St Louis Temp.pdf | ||
| DWGs 2017 CMCF West Admin.pdf | ||
| Proj State 25362.pdf | ||
| DWGs 1999 St Louis LVL1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBERPROJECT NUMBER
PROJECT DATE
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
RAM
FLOOR PLAN
HVAC DEMOLITION
M1.01
FLOOR PLAN - HVAC DEMOLITION
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
RAM
M1.02
FLOOR PLAN
HVAC REVISIONS
FLOOR PLAN - HVAC REVISIONS
COOLER
STORAGE STORAGE
WASH AREA
DINING
OFFICE
DRY
STORAGE
OFFICE
PREPERATION
TOILET
TOILET
LAUNDRY
MECHANICAL
OFFICE
DINING
COOLER
FREEZER
153 S.F.
138 S.F.
KEYED NOTES
ALL NEW DUCTWORK SHALL BE MOUNTED TIGHT TO
UNDERSIDE OF EXISTING CEILING.
FIELD VERIFY EXACT LOCATION OF ALL NEW
THERMOSTATS. PROVIDE AND INSTALL VANDAL
RESISTANT LOCKABLE COVERS.
INSTALL NEW MAKE-UP AIR DUCTWORK ABOVE FREEZER
AND BELOW EXISTING CEILING, CONNECT
NEW 36” X 14” DUCT TO (6) 24” X 12” HOOD SUPPLY AIR
DUCT COLLARS.
SHUT-OFF VALVE WITH DIRT LEG. (TYP)
EXPOSED DUCTWORK (TYP)
FLEX CONNECTION (TYP)
DUCTWORK TO BE INSTALLED IN ATTIC SPACE WITH
EXTERNAL INSULATION.
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
RAM
MECHANICAL
DETAILS AND
SCCHEDULES
M1.03
INLINE EXHAUST FAN DETAIL
BRANCH DUCT CONNECTION TO DIFFUSER OR GRILLE DETAIL
RECTANGULAR TO ROUND DUCT SUPPLY, RETURN OR EXHAUST DUCT
SUPPLY DUCT RETURN OR EXHAUST DUCT
RECTANGULAR DUCT BRANCH TAKE-OFF DETAILS
DUCTWORK RADIUS ELBOW
DUCTWORK SQUARE VANE MITERED ELBOWS
FIRE DAMPER DETAIL
KITCHEN HOOD EXHAUST FAN DETAIL (PITCHED ROOF)
DUCT SECTION
ROOF TOP UNIT DETAIL (ON GRADE)
ROOF TOP AIR HANDLING UNIT ON GRADE
CONTROL AND COMPRESSOR ACCESS PANEL
EVAPORATOR SECTION ACCESS PANEL
ECONOMIZER HOOD
GAS SHUT OFF VALVE
BAROMETRIC OR POWER RELIEF (SEE SCHEDULE OR
SPECIFICATIONS FOR OPTIONS)
TRAPPED CONDENSATE DRAIN-DRIP TO ROOF
6"REINFORCED CONCRETE PAD
12" ROOF CURB ON PAD
GAS PIPE CONNECTION
6" LONG DIRT LEG WITH CAP (LOCATE AT ELEVATION
CHANGES)
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
RAM
MECHANICAL
SPECIFICATIONS
M1.04
CODES, PERMITS & INSPECTIONS
CONTRACTOR SHALL SECURE PERMITS, INSPECTIONS AND TESTS, PAY ALL FEES,
DEPOSITS, AND COSTS FOR ALL MECHANICAL UTILITIES AND SERVICES INVOLVED
AND PRESENT THE OWNER A CERTIFICATE OF INSPECTION AND APPROVAL FROM THE
DEPARTMENT HAVING JURISDICTION OVER HIS WORK. SHOULD ANY CHANGE IN THE
DRAWINGS AND SPECIFICATIONS BE REQUIRED TO COMPLY WITH ALL APPLICABLE
CODES, RULES, REGULATIONS, ETC., CONTRACTOR SHALL NOTIFY THE ENGINEER
BEFORE SUBMITTING BID. AFTER ENTERING INTO CONTRACT, ALL WORK NECESSARY
TO MEET THE REQUIREMENTS SHALL BE COMPLETED WITHOUT ADDITION TO THE
CONTRACT AMOUNT. WHERE WORK INDICATED IS MORE THAN REQUIRED BY CODES,
ETC., SUCH WORK SHALL BE AS INDICATED.
JOB OBSERVATION
NOTWITHSTANDING ANY REFERENCE TO ANY CODE, RULE OR REGULATION,
ENGINEER SHALL HAVE NO RESPONSIBILITY FOR SAFETY ON THE JOB SITE, SHALL
HAVE NO RIGHT TO CHANGE OR STOP THE WORK, SHALL NOT CONTROL THE MEANS
OF THE WORK, AND SHALL NOT HAVE ANY DUTY TO PROVIDE SUPERVISION OF
MEANS, METHODS, PROCESSES OR PROCEDURES OF CONSTRUCTION.
FIRST-CLASS WORKABLE SYSTEMS
FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN
THE OPINION OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS
ARE REQUIRED TO PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR
SHALL REQUEST AN INTERPRETATION FROM THE ENGINEER BEFORE PROCEEDING
WITH THE WORK. IF THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, NO EXCUSE
WILL THEREAFTER BE ENTERTAINED FOR FAILURE TO PROVIDE FIRST-CLASS
WORKABLE SYSTEMS.
DRAWINGS
DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN, AND
EXTENT OF THE WORK AND ARE DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE
SCALED FOR ROUGH-IN MEASUREMENTS NOR TO SERVE AS SHOP DRAWINGS. THE
ENGINEERS AND OWNER RESERVE THE RIGHT TO MAKE MINOR CHANGES IN THE
LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. AT THE TIME OF ROUGH-IN
WITHOUT ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, LOCATIONS, ETC. FOR ACCURACY AND POSSIBILITY OF INTERFERENCES
DUE TO FIELD CONDITIONS AND ACTUAL BUILDING STRUCTURE. FAILURE TO CHECK
WILL BE NO REASON FOR ADDITIONAL COMPENSATION.
SHOP DRAWINGS
SUBMIT ELECTRONIC SET OF COMPLETE SHOP DRAWINGS FOR ALL MECHANICAL
EQUIPMENT AND MATERIALS TO THE ENGINEER FOR REVIEW BEFORE FABRICATION
OF WORK OR ORDERING OF EQUIPMENT. DRAWINGS MUST BE REVIEWED BY THE
ENGINEER BEFORE ORDERING EQUIPMENT. ALL SHOP DRAWINGS REJECTED SHALL
BE CORRECTED AND RESUBMITTED TO THE ENGINEER BEFORE ORDERING.
GUARANTEE
CONTRACTOR SHALL GUARANTEE EQUIPMENT, MATERIALS AND WORKMANSHIP IN HIS
CONTRACT AND SHALL MAKE GOOD AT HIS OWN EXPENSE ANY DEFECTS WHICH MAY
DEVELOP WITHIN ONE YEAR AFTER START-UP OF EACH PIECE OF EQUIPMENT,
OCCUPANCY BY OWNER, OR FINAL ACCEPTANCE OF THE JOB, WHICHEVER OCCURS
FIRST.
CONTRACTORS RECORD/AS-BUILT DRAWINGS
CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET
OF “RECORD” DRAWINGS REFLECTING "AS-BUILT" CONDITIONS OF THEIR
WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND ELEVATIONS FOR
ALL UNDERGROUND WORK. UPON COMPLETION OF THIS PROJECT, THE
CONTRACTOR SHALL DELIVER TO THE ENGINEER THE “RECORD” DRAWINGS.
LOCAL CONDITIONS
BEFORE SUBMITTING BIDS AND/OR PROCEEDING WITH THE PROJECT, THE
CONTRACTOR SHALL EXAMINE ALL DRAWINGS, SPECIFICATIONS AND ADDENDA
ISSUED FOR THE PROJECT AND SHALL EXAMINE THE PROJECT SITE. THE
CONTRACTOR SHALL THOROUGHLY INVESTIGATE THE PROJECT SITE AND BECOME
FULLY INFORMED AS TO THE EXTENT OF HIS WORK AND COORDINATION OF THIS
WORK WITH ALL OTHER TRADES AND INCLUDE ALL COST TO PERFORM AND
COMPLETE WORK FOR THIS PROJECT PER DRAWINGS AND SPECIFICATION AND ALL
CODES.
OPERATION AND MAINTENANCE MANUALS
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER TWO (2) COPIES OF AN
APPROVED BOUND (3-RING BINDER) BOOK WITH TABS FOR SECTIONS COVERING
EACH ITEM OF EQUIPMENT. THESE NOTEBOOKS SHALL INCLUDE SHOP DRAWINGS,
MAINTENANCE MANUALS, OPERATING MANUALS AND PARTS LIST AS NECESSARY TO
INSTRUCT THE OWNER ON PROPER OPERATION AND USE AS WELL AS MAINTENANCE
FOR EACH PIECE OF EQUIPMENT FOR THIS PROJECT. THESE BOOKS SHALL ALSO
INCLUDE CONTRACTOR'S, SUBCONTRACTOR'S AND MANUFACTURER'S NAMES,
TELEPHONE NUMBERS AND ADDRESSES. MANUALS SHALL ALSO INCLUDE SEQUENCE
OF OPERATION, CONTROL EQUIPMENT LITERATURE, WIRING AND CONTROL
DIAGRAMS, CERTIFICATES OF GUARANTEES, CERTIFICATES OF INSPECTION,
MECHANICAL SYSTEM TEST AND BALANCING REPORTS. THE CONTRACTOR SHALL
ACCUMULATE AND SUMMARIZE THE CONTROL AND MAINTENANCE SEQUENCE IN
TYPEWRITTEN SHEET TO BE INCLUDED IN THE REPORT. THESE MANUALS SHOULD BE
HARD BOUND IN BEST QUALITY BINDERS AND TURNED OVER TO THE
ARCHITECT/ENGINEER FOR APPROVAL AT COMPLETION OF PROJECT.
START-UP SERVICE
CONTRACTOR SHALL ARRANGE WITH EQUIPMENT MANUFACTURERS FOR PROVIDING
COMPLETE START-UP SERVICE FOR ALL EQUIPMENT ON THIS PROJECT. ALL
START-UP SERVICES SHALL BE PERFORMED IN THE PRESENCE OF THE OWNER
AND/OR ENGINEER. A WRITTEN REPORT SHALL BE SUBMITTED TO THE ENGINEER
STATING DATE OF START-UP, MANUFACTURER APPROVAL OF SYSTEM OPERATION
AND INSTALLATION.
CUTTING AND PATCHING
CUTTING AND PATCHING SHALL BE BY TRADES REGULARLY ENGAGED IN THIS TYPE
OF WORK, EXCEPT DRILLING OF HOLES SHALL BE DONE BY THE TRADES REQUIRING
SAME. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED.
SALVAGEABLE MATERIAL
SALVAGEABLE MATERIAL SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL
BE STORED AT LOCATIONS AS DIRECTED BY THE OWNER, EXCEPT THE OWNER
RESERVES THE RIGHT TO DESIGNATE CERTAIN ITEMS OF SALVAGEABLE MATERIAL TO
BE REMOVED FROM THE PROJECT SITE.
RIGGING AND HOISTING
PERFORM ALL REQUIRED RIGGING, HOISTING, TRANSPORTATION, MOVING, ETC. OF
ALL EQUIPMENT, MATERIALS, ETC. TO BE FURNISHED AND/OR INSTALLED AS SHOWN
ON DRAWINGS, WHETHER FURNISHED BY THIS CONTRACTOR OR BY THE OWNER OR
OTHER TRADES.
STORAGE FACILITY
FURNISH AND MAINTAIN A WEATHERPROOF STORAGE FACILITY ON THE SITE OF
ADEQUATE SIZE TO STORE MISCELLANEOUS EQUIPMENT AND/OR MATERIALS TO
PREVENT EXPOSURE TO THE WEATHER. LOCATION OF SHED SHALL BE DETERMINED
BY THE OWNER AND ARCHITECT/ENGINEER. THE OWNER RESERVES THE RIGHT TO
DENY STORAGE OF MATERIALS OR EQUIPMENT IN ANY EXISTING OR NEW BUILDINGS.
PROTECTION FROM DAMAGE
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIALS, EQUIPMENT, ETC.
AND ALL WORK INSTALLED BY HIMSELF AND SHALL PROTECT IT FROM DAMAGE UNTIL
FINAL ACCEPTANCE OF THIS PROJECT BY THE OWNER.
FURNISH ALL COVERINGS AND PROTECTION FROM DIRT, DUST, RAIN, STORM, HEAT,
TRAFFIC, WEAR, ETC. AND ALL POSSIBLE INJURY INCLUDING THAT BY OTHER
WORKMEN. ANY EQUIPMENT, WORKMANSHIP, MATERIALS, ETC. DAMAGED PRIOR TO
FINAL ACCEPTANCE BY THE OWNER OF THIS PROJECT SHALL BE PROPERLY
REPAIRED AT NO EXPENSE TO THE OWNER.
PROTECT ALL EQUIPMENT FROM DAMAGE BY COVERING OR COATING. ANY DENTED,
SCRATCHED, RUSTED OR MARRED SURFACE FINISHES WILL NOT BE ACCEPTED.
PROTECT ALL EQUIPMENT, MATERIALS, ETC. FROM FREEZING.
NATURAL GAS PIPING, ABOVE GRADE INSIDE BUILDING
NATURAL GAS PIPING 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK CARBON STEEL
ASTM A53, SEAMLESS WITH BLACK MALLEABLE IRON FITTINGS, 150 PSIG SCREWED
ASME B16.3.
NATURAL GAS PIPING 2 1/2" AND LARGER SHALL BE SCHEDULE 40 BLACK CARBON
STEEL ASTM A53 SEAMLESS WITH WELDED FITTINGS ASTM A234.
PIPING FOR 1 PSIG OR HIGHER GAS PRESSURE SHALL BE IN ACCORDANCE WITH
CODE FOR PRESSURE PIPING ANSI B31.1.
FURNISH LUBRICATED PLUG SHUT-OFF VALVES ON MAIN BRANCHES AND AT
DOMESTIC PRESSURE REGULATORS. LOCATE WRENCH NEAR METER. STOP VALVES
AT EQUIPMENT AND OUTLETS SHALL BE BALL VALVES WHERE 2" AND SMALLER. GAS
PIPING SHALL HAVE DRIPS AT BOTTOM OF RISERS WITH BRANCHES TAKEN FROM TOP
OR SIDE OF HORIZONTAL PIPE. CAP ALL GAS PIPE OUTLETS UNTIL CONNECTED TO
GAS EQUIPMENT. ALL GAS PIPING SHALL BE RUN IN SPACES WHICH ARE ACCESSIBLE
FOR INSPECTION AND SERVICE.
VALVES
GATE VALVES:
UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TRIM, SCREWED BONNET,
RISING STEM, HANDWHEEL, INSIDE SCREW WITH BACKSEATING STEM, SOLID WEDGE
DISC, ALLOY SEAT RINGS, SOLDER OR THREADED ENDS.
BALL VALVES:
UP TO AND INCLUDING 2 INCHES: BRONZE ONE PIECE BODY, STAINLESS STEEL BALL,
TEFLON SEATS AND STUFFING BOX RING, LEVER HANDLE WITH BALANCING STOPS,
SOLDER OR THREADED ENDS.
OVER 2 INCHES: CAST STEEL BODY, CHROME PLATED STEEL BALL, TEFLON SEAT AND
STUFFING BOX SEALS, LEVER HANDLE, OR GEAR DRIVE HANDWHEEL FOR SIZES 10
INCHES AND OVER, FLANGED. DUCTILE IRON BODY, CHROME PLATED CARBON STEEL
BALL AND STEM, TFE SEATS, LEVER HANDLE OR GEAR OPERATOR, GROOVED ENDS.
VICTAULIC SERIES 726.
PLUG VALVES:
UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TAPERED PLUG, FULL PORT
OPENING, NON-LUBRICATED, TEFLON PACKING, THREADED ENDS. OPERATOR: ONE
PLUG VALVE WRENCH FOR EVERY TEN PLUG VALVES MINIMUM OF ONE.
OVER 3 INCHES: CAST IRON BODY AND PLUG, FULL PORT OPENING, PRESSURE
LUBRICATED, TEFLON PACKING, FLANGED ENDS OR GROOVED ENDS IF VICTAULIC
GROOVED END FITTINGS ARE USED. DUCTILE IRON BODY AND PLUG, STANDARD
PORT OPENING, NON-LUBRICATED ECCENTRIC-TYPE, WELDED-IN NICKEL SEAT,
GROOVED ENDS. VICTAULIC SERIES 377. OPERATOR: EACH PLUG VALVE SHALL HAVE
A WRENCH HANDLE WITH SET SCREW.
UNIONS
UNIONS OR FLANGES SHALL BE USED AT EQUIPMENT CONNECTIONS. DIELECTRIC
CONNECTIONS BETWEEN COPPER AND IRON OR STEEL PIPE SHALL BE MADE WITH
DIELECTRIC NIPPLES SIMILAR TO VICTAULIC STYLE 47. A BRASS ADAPTER
DIELECTRIC UNION IS NOT ACCEPTABLE.
PLATES AND SLEEVES
PROVIDE AND INSTALL PIPE SLEEVES FOR ALL PIPING AND DUCTS PASSING THROUGH
WALLS, FLOORS AND CEILINGS. SLEEVES THROUGH WALLS AND CEILINGS MAY BE 20
GAUGE GALVANIZED SHEET METAL. WHERE PIPES ARE INSULATED, SLEEVES SHALL
BE LARGE ENOUGH TO PASS THE INSULATION. ALL PENETRATION VOIDS SHALL BE
SEALED SMOKE TIGHT WITH NON-COMBUSTIBLE MATERIALS SIMILAR TO 3M OR HILTI
FIRESTOP SYSTEMS TO MAINTAIN THE INTEGRITY OF THE FIRE RATED STRUCTURE. IN
A NON-FIRE RATED ASSEMBLY, SEAL ALL VOIDS WITH NON-HARDENING SEALANT.
HANGERS AND SADDLES
SHALL BE MODERN PIPE SUPPORTS CORP., GRINNELL/ANVIL, AUTO GRIP OR M-CO.
FOR COPPER PIPE WITH STEEL HANGERS, CLEAN AND WRAP PIPE WITH TWO LAYERS
OF PLASTIC INSULATING TAPE AT POINTS OF CONTACT. HANGERS FOR PIPING WITH
VAPOR BARRIER SEALED INSULATION SHALL BE MULTIPURPOSE PIPE SADDLES
FITTING OVER THE INSULATION. WIRE OR PERFORATED STRAP IRON WILL NOT BE
PERMITTED FOR PIPE SUPPORTS. HANGERS SHALL BE CLEVIS OR SPLIT RING TYPE
WITH VERTICAL ADJUSTMENT AND BEAM CLAMP SIMILAR TO GRINNELL/ANVIL FIG. 260,
WITH MAXIMUM SPACING PER ASHRAE STANDARDS:
PIPE SIZE STEEL PIPE COPPER PIPE PVC PIPE ROD SIZE
1/2 TO 3/4 INCH 6 FEET 5 FEET 4 FEET 3/8”
1 INCH 7 FEET 5 FEET 4 FEET 3/8”
1 1/4 INCH 7 FEET 7 FEET 4 FEET 3/8”
1 1/2 INCH 7 FEET 7 FEET 4 FEET 1/2”
2 INCH 10 FEET 8 FEET 4 FEET 1/2"
2 1/2 INCH 11 FEET 9 FEET 4 FEET 5/8”
3 INCH 11 FEET 9 FEET 4 FEET 5/8”
3 1/2 INCH 13 FEET 11 FEET 4 FEET 5/8”
4 INCH 14 FEET 12 FEET 4 FEET 5/8”
PIPE IDENTIFICATION
ALL PIPING SHALL BE IDENTIFIED PER ANSI/OSHA OR OWNER'S STANDARDS WITH
COLOR PIPE BANDS, IDENTIFICATION LABELS AND FLOW ARROWS. PIPES SHALL BE
BANDED AND LABELED ON 10'-0" CENTERS ON CONTINUOUS LINES, AT EQUIPMENT
CONNECTIONS, AT BOTH SIDES OF A WALL THROUGH WHICH PIPE PASSES AT EVERY
BRANCH CONNECTION, ON PIPING WITHIN SIGHT OF AN ACCESS DOOR OR PANEL.
SHOW SLOPE DIRECTIONAL ARROWS AT EACH IDENTIFICATION POINT. LABELS, FLOW
ARROWS AND STENCIL AND PAINT SHALL BE 1" HIGH ON PIPING UP TO 2 1/2" AND
SHALL BE 2" HIGH ON PIPE SIZES OF 3" AND LARGER. BANDS SHALL BE 1 1/2" WIDE.
LABELS SHALL BE AS MANUFACTURED BY SETON OR W.H. BRADY COMPANY OR
EQUAL. VERIFY TYPE, SIZE AND COLORS OF PIPE IDENTIFICATION WITH OWNER.
DUCTWORK
DUCTS, CASINGS, HOUSINGS, ETC. SHALL BE FABRICATED FROM, PRIME QUALITY,
HOT DIP GALVANIZED STEEL SHEET AS RECOMMENDED IN THE LATEST ISSUES OF
ASHRAE GUIDE AND SMACNA DUCT MANUALS IN VARIABLE AIR VOLUME SYSTEMS,
WHEN USED. SUPPLY AIR DUCTS LOCATED BETWEEN AIR HANDLING SYSTEM AND
VAV BOXES; DUCT CONSTRUCTION AND INSTALLATION SHALL MEET SMACNA
STANDARDS FOR 6" W.C. FOR ALL OTHER SUPPLY AIR DUCTWORK AND EXHAUST AIR,
RETURN AIR, OUTSIDE AIR INTAKE AND RELIEF AIR DUCTS, DUCT CONSTRUCTION AND
INSTALLATION SHALL MEET SMACNA STANDARDS FOR 2" W.C.
RECTANGULAR DUCTS SHALL HAVE TEES, ELBOWS AND BENDS WITH A MINIMUM
THROAT RADIUS OF 1 TIMES THE DUCT WIDTH AND BE OF THE SAME GAUGE AND
MATERIAL AS THE STRAIGHT DUCT. INCREASE DUCT SIZES GRADUALLY, NOT
EXCEEDING 15 DEGREES DIVERGENCE IF POSSIBLE; MAXIMUM 30 DEGREES
DIVERGENCE UPSTREAM OF EQUIPMENT AND 45 DEGREES CONVERGENCE
DOWNSTREAM. WHERE VOLUME BOXES ARE CONNECTED TO DUCT MAIN OR WHERE
DIFFUSERS ARE CONNECTED TO DUCT BRANCHES BY ROUND FLEX DUCT, INSTALL
DUCT SPIN-IN FITTINGS SUCH AS FLEXMASTER USA, INC. MODEL #FLD WITH DAMPER
AND POSITIVE LOCKING WING NUT. SEAL ALL EDGES WITH FIRE RETARDANT DUCT
SEALER. FLEXIBLE INSULATED DUCTS (CONNECTIONS FROM MAIN DUCT TO VOLUME
BOX AND/OR FROM DUCT BRANCH TO DIFFUSERS) SHALL BE FLEXMASTER USA, INC.
TYPE #3. USE MAXIMUM LENGTH OF 5'-0" TO EACH CONNECTION. INSTALL FLEXIBLE
DUCT WITH MINIMUM OF BENDS USING LONG RADIUS BENDS ONLY.
DUCT SEALANT
ALL DUCTWORK INCLUDING SUPPLY AIR, OUTSIDE AIR, RETURN AIR, EXHAUST AIR
AND RELIEF AIR DUCT SYSTEMS SHALL HAVE ALL JOINTS SEALED. DUCTWORK
DESIGNED AT SMACNA 6” PRESSURE SHALL MEET SMACNA CLASS “A” SEAL
REQUIREMENTS. DUCTWORK DESIGNED AT SMACNA 2” PRESSURE SHALL MEET
SMACNA CLASS “C” SEAL REQUIREMENTS.
DUCT HANGERS
HORIZONTAL STEEL DUCTWORK SHALL BE SUPPORTED BY MEANS OF TRAPEZE BARS
AND ROUND STEEL ROD OF SIZES LISTED BELOW. ROUND STEEL RODS SHALL BE
ELECTRO-GALVANIZED ALL-THREAD ROD. HANGERS SHALL BE PROVIDED AT BOTH
SIDES OF FLAT SIDED DUCTWORK FOR THE FULL HEIGHT OF DUCT. ROUND
DUCTWORK SHALL BE PROVIDED WITH A BAND OF THE SAME SIZE AS THE HANGER TO
COMPLETELY ENCIRCLE THE DUCT. BAND SHALL BE SECURED TO THE HANGER BY
MEANS OF A MINIMUM 3/16" BOLT. MINIMUM DUCT HANGER SIZES SHALL BE AS LISTED
BELOW
MIN. UPPER MINIMUM
DUCT ATTACHMENT STEEL MAXIMUM NO. OF TRAPEZE
SIZE RATING ROD SPACING HANGERS SHELF ANGLE
UP TO 16" 750 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"
19" TO 36" 1000 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"
37" TO 120" 3000 LBS. 3/8" 8' 2 2" X 2" X 1/4"
DUCT INSULATION
DUCTWORK LOCATED IN CONCEALED AREAS (CONCEALED AREAS SHALL INCLUDE
DUCT SHAFTS, SPACES ABOVE DROPPED CEILINGS, SPACES BETWEEN WALLS, ETC.)
SHALL BE WRAPPED EXTERNALLY WITH OWENS-CORNING, KNAUF, MANSVILLE, OR
EQUAL, FIBERGLAS ALL-SERVICE DUCT WRAP, LIGHT DENSITY GLASS FIBER
INSULATION FACED WITH A REINFORCED FOIL/KRAFT LAMINATE MEETING THE
REQUIREMENTS OF ASTM C553, 1.0 LBS. PER CUBIC FOOT DENSITY, 1 1/2" THICK.
WHERE DUCTS ARE 24" IN WIDTH OR GREATER, MECHANICAL FASTENERS SPACED AT
18" (APPROX.) CENTERS ARE REQUIRED ON THE BOTTOM OF THE DUCT TO PREVENT
THE INSULATION FROM SAGGING. ALL SEAMS, TEARS, PUNCTURES, AND OTHER
PENETRATIONS SHALL BE CLOSED WITH 3" PRESSURE SENSITIVE, VAPOR BARRIER
MASTIC REINFORCED GLASS SCRIM TAPE.
KITCHEN HOOD EXHAUST DUCT WRAP SHALL BE “FIRE MASTER” AS MANUFACTURED
BY 3M FIRE BARRIER PRODUCTS, INSTALLED AS RECOMMENDED BY MANUFACTURER
IN TWO LAYERS WITH STAINLESS STEEL BANDING TO GIVE DUCT A 2 HOUR UL RATED
ENCLOSURE. DUCT WRAP SHALL BE A 1 1/2” THICK REFRACTORY CERAMIC FIBER
BLANKET ENCAPSULATED WITH ALUMINUM FOIL SCRIM. DUCT WRAP SHALL BE
CLASSIFIED BY U.L. AS A GREASE DUCT APPROVED ENCLOSURE AND TESTED TO
ASTM E84/UL 723 WITH A FLAME SPREAD AND SMOKE DEVELOPED RATING OF 5. DUCT
WRAP SHALL HAVE A MINIMUM THERMAL RESISTANCE “R” VALUE OF 4.15 PER INCH
AT 70 DEGREES F. TWO LAYERS OF DUCT WRAP SHALL BE INSTALLED, APPLIED
DIRECTLY TO THE DUCT. A 3” PERIMETER AND LONGITUDINAL OVERLAP SHALL BE
EMPLOYED ON BOTH LAYERS. FILAMENT TAPE SHALL BE USED AS A TEMPORARY
HOLD UNTIL STAINLESS STEEL BANDING IS IN PLACE. FOR DUCT SPANS OF 24” OR
GREATER, INSULATION PINS SHALL BE UTILIZED ON THE BOTTOM OF HORIZONTAL
AND ON VERTICAL DUCT RUNS TO PREVENT SAGGING. SEE “3M INSTALLATION
GUIDE” FOR INSTALLATION DETAILS. INSTALLATION SHALL HAVE THE APPROVAL OF
OWNER'S INSURANCE UNDERWRITER AND THE FIRE MARSHAL HAVING JURISDICTION.
INTERNAL ACOUSTIC DUCT LINER
WHERE CALLED FOR, LINE DUCT WITH 1” THICK FIBERGLASS AEROFLEX ACOUSTICAL
INTERNAL DUCT LINER, IN LIEU OF EXTERNAL DUCT INSULATION. INSULATION SHALL
BE 1.5 LB. DENSITY, WITH A FIRE RESISTANT COATING TO BOND FIBERS OF THE AIR
STREAM SIDE SURFACE, INSTALLED AS RECOMMENDED BY MANUFACTURER.
DUCTWORK LOCATED OUTDOORS
ALL DUCTWORK (SUPPLY, RETURN, EXHAUST, OUTSIDE AIR, RELIEF AIR) LOCATED
OUTDOORS SHALL BE COVERED EXTERNALLY WITH EITHER 2” OF FLEXIBLE
ELASTOMERIC CLOSED-CELL INSULATION, OR 2” OF FOAMGLAS® CLOSED CELL
INSULATION. INSTALLATION SHALL MEET MANUFACTURER'S
RECOMMENDATIONS, WITH ALL JOINTS FIRMLY BUTTED AND SECURED WITH
ADHESIVES OR FASTENERS. ALL DUCTWORK INSULATION SHALL BE JACKETED WITH
A MULTI-PLY, FABRIC REINFORCED, SELF ADHESIVE INSULATION CLADDING MATERIAL
WITH A VAPOR BARRIER AND A THICKNESS OF 0.015”. JACKETING SYSTEM SHALL BE
VENTURE CLAD PLUS #1579CW-E, OR EQUAL. INSTALL ALL INSULATION AND
JACKETING IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
ALL JACKETING SEAMS MUST BE TAPED WITH MANUFACTURER'S RECOMMENDED
JOINT/SEAMING TAPE.
RECTANGULAR DUCTWORK SHALL BE INSTALLED WITH A CROWN OR SLOPE ON TOP
TO PREVENT WATER FROM PONDING. INSULATION AND JACKETING SHALL BE
INSTALLED ON TOP OF DUCT AND CROWN OR SLOPE SHIM. JACKETING SHALL BE
INSTALLED TO EACH OF THE SIDES SEPARATELY, STARTING WITH BOTTOM, THEN
SIDES AND FINALLY THE TOP. EACH SIDE SHALL OVERLAP THE OTHER BY 3”. THE
SIDES SHALL OVERLAP THE BOTTOM AND THE TOP SHALL OVERLAP THE SIDES.
TESTING, ADJUSTING AND BALANCING
TESTING, ADJUSTING AND BALANCING SHALL BE PERFORMED BY AN INDEPENDENT
CERTIFIED AGENCY IN ACCORDANCE WITH AABC, ADC, ASHRAE III, NEBB AND SMACNA
STANDARDS. FURNISH 5 SETS OF REPORTS OF AIR AND WATER SYSTEMS BALANCE
REPORTS TO THE ENGINEER INDICATING DESIGN AND ACTUAL QUANTITIES,
NAMEPLATE DATA, ETC.
ACCEPTABLE TEST AND BALANCE CONTRACTORS:
1. HITECH TEST AND BALANCE (FREELAND, MI)
2. ABSOLUTE BALANCE COMPANY (SOUTH LYON, MI)
3. ENVIRO-AIRE/TOTAL BALANCE COMPANY (ST. CLAIR SHORES, MI)
4. ENER-TECH TESTING (HOLLY, MI)
5. INTERNATIONAL TEST AND BALANCE (SOUTHFIELD, MI)
AIR SYSTEMS ADJUST AIR HANDLING, DISTRIBUTION SYSTEMS, AIR INLETS AND
OUTLETS, ETC. TO PROVIDE SUPPLY, RETURN, EXHAUST, OUTSIDE AIR AND RELIEF
AIR QUANTITIES TO WITHIN 10% OF REQUIRED OR DESIGNED AIR QUANTITIES. VERIFY
THAT SYSTEMS ARE COMPLETE AND OPERABLE BEFORE COMMENCING WORK.
VERIFY SYSTEMS ARE STARTED AND OPERATING AT A SAFE AND NORMAL
OPERATION, TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND
OPERABLE, PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL
EQUIPMENT, FINAL FILTERS ARE CLEAN AND IN PLACE, DUCT SYSTEMS ARE CLEAN OF
DEBRIS, FANS ARE ROTATING CORRECTLY, FIRE AND VOLUME DAMPERS ARE IN
PLACE AND IN OPEN POSITIONS, AIR COIL FINS ARE CLEANED AND COMBED, ACCESS
DOORS ARE CLOSED AND DUCT END CAPS ARE IN PLACE, AIR OUTLETS ARE
INSTALLED AND CONNECTED, DUCT SYSTEM LEAKAGE IS MINIMIZED, ETC. MEASURE
AND RECORD ALL AIR MOVING EQUIPMENT, AIR INLETS AND OUTLETS STATIC
PRESSURES, RPM'S, ETC.
WATER SYSTEMS VERIFY THAT SYSTEMS ARE COMPLETE AND OPERABLE BEFORE
COMMENCING WORK. VERIFY SYSTEMS ARE STARTED AT A SAFE AND NORMAL
OPERATION, TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND
OPERABLE, PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL
EQUIPMENT, HYDRONIC SYSTEMS ARE FLUSHED, FILLED AND VENTED, PUMPS ARE
ROTATING CORRECTLY, PROPER STRAINER BASKETS ARE CLEAN AND IN PLACE,
SERVICE AND BALANCE VALVES ARE OPEN, ETC. ADJUST WATER SYSTEMS TO
PROVIDE REQUIRED OR DESIGN QUANTITY AND TO PROVIDE SPECIFIED OR
SCHEDULES PRESSURE DROPS AND FLOWS THROUGH EQUIPMENT, COILS, ETC.
ADJUST FLOWS BY MEANS OF BALANCING COCKS, VALVES AND FITTINGS.
DIFFUSER AND GRILLE SCHEDULE
TYPE A: HEAVY DUTY SUPPLY AIR REGISTER: PRICE #152L DOUBLE DEFLECTION AIR FOIL BLADE
SUPPLY AIR REGISTER, ALL EXTRUDED ALUMINUM CONSTRUCTION, INDIVIDUALLY
ADJUSTABLE BLADES, FRONT BLADE, TO BE PARALLEL TO THE REGISTER LONG DIMENSION,
BAKED-ON WHITE ENAMEL FINISH. FURNISH FRAME AND MOUNTING HARDWARE ARE AS
NECESSARY FOR CEILING TYPE OR DIRECT DUCT MOUNT. SEE DRAWINGS FOR SIZES.
TYPE B: HEAVY DUTY WALL RETURN OR EXHAUST AIR GRILLE: PRICE 91DL(91DS) (96DL OR DS FOR
CONCEALED SCREWS) OR EQUAL CARNES OR T&B WALL RETURN OR EXHAUST GRILLE, ALL
STEEL CONSTRUCTION, BAKED-ON ENAMEL FINISH WITH COLOR BY ARCHITECT. ONE SET OF
HORIZONTAL BLADES SET AT 35 DEGREES. FURNISH OPPOSED BLADE DAMPER WITH BLACK
FINISH. IF GRILLE SIZE REQUIRES 2 OR MORE SECTIONS, DECREASE WIDTH OF TRIM AT JOINT
AS MUCH AS POSSIBLE. [48” MAXIMUM DIMENSION FOR SINGLE SECTION]
ROOFTOP UNIT SCHEDULE
RTU-1,2,
4 & 5: TRANE PRECEDENT #TYSC092 GAS/ELECTRIC 7.58 TON HORIZONTAL ROOFTOP UNIT. 3000 CFM
AT .50” EXTERNAL STATIC PRESSURE, 3 H.P., 460V-3PH, 21 MCA, 25 AMP MAXIMUM CIRCUIT
BREAKER.
COOLING PERFORMANCE: 94,800 BTUH GROSS COOLING CAPACITY, 90,000 BTUH ARI NET
COOLING CAPACITY. 80/67F EDB/EWB,F LWB, 2 SCROLL COMPRESSORS. R-410A REFRIGERANT
11.2 EER.
HEATING PERFORMANCE: 200,000 BTUH NATURAL GAS INPUT, 140,000 BTUH OUTPUT.
RTU-3: TRANE PRECEDENT #TYSC060 GAS/ELECTRIC 5 TON HORIZONTAL ROOFTOP UNIT. 1950 CFM
AT .50” EXTERNAL STATIC PRESSURE, 1.5 H.P., 460V-3PH,14 MCA, 20 AMP MAXIMUM CIRCUIT
BREAKER.
COOLING PERFORMANCE: 60,000 BTUH GROSS COOLING CAPACITY, 58,500 BTUH ARI NET
COOLING CAPACITY. 80/67F EDB/EWB, 1 SCROLL COMPRESSOR. R-410A REFRIGERANT.
HEATING PERFORMANCE: 150,000 BTUH NATURAL GAS INPUT, 105,000 BTUH OUTPUT.
RTU NOTES:
1. THE MECHANICAL TRADE SHALL VERIFY UNIT CONFIGURATION (HORIZONTAL OR DOWNFLOW)
WITH SCHEDULE LISTED ABOVE AND PROJECT DESIGN DRAWINGS.
2. UNITS SHALL HAVE REFERENCE ENTHALPY BASED ECONOMIZERS WITH POWER RELIEF EXHAUST
FAN AND LOW AMBIENT CONTROL FOR OPERATION IN 0 DEGREES F AMBIENT CONDITION.
3. FURNISH PREFABRICATED ROOF CURB FOR EACH UNIT, WITH HEIGHT OF CURB TO GIVE
MINIMUM 12” CLEAR FROM FINISHED CONCRETE SLAB. THE MECHANICAL TRADE SHALL FURNISH
AND SET IN PLACE/LEVEL THE CURB.
4. ALL UNITS SHALL HAVE 4” THICK HIGH EFFICIENCY THROW AWAY FILTERS.
5. OUTSIDE AIR INTAKE DAMPERS SHALL BE ULTRA LOW-LEAK TYPE WITH BLADE AND JAMB SEALS.
6. MOTORS SHALL BE PREMIUM EFFICIENCY TYPE.
7. EACH RTU TO HAVE:
A. SERVICE VALVES ON LIQUID, SUCTION AND DISCHARGE LINES.
B. THRU-THE-BASE ELECTRICAL PROVISION.
C. NON-FUSED DISCONNECT SWITCH WITH EXTERNAL HANDLE.
D. TRANE COMMUNICATION INTERFACE WITH SUPPLY AIR SENSING AND CLOGGED FILTER SWITCH.
E. VENTILATION OVERRIDE.
F. HINGED SERVICE ACCESS.
G. CONDENSER COIL GUARDS.
H. SLOPED STAINLESS STEEL DRAIN PANS.
8. ALL UNITS SHALL HAVE DRY CONTACTS FOR DUCT SMOKE DETECTOR CIRCUIT FACTORY WIRED
TO STOP UNIT UPON DETECTION OF SMOKE. TWO DUCT SMOKE DETECTORS FOR EACH RTU AND
REMOTE WIRING FURNISHED BY ELECTRICAL TRADES. SENSING TUBES FOR DUCT SMOKE
DETECTORS SHALL BE INSTALLED BY MECHANICAL TRADES. THE DUCT SMOKE DETECTORS
SHALL BE POWERED FROM AN INDEPENDENT CIRCUIT AND NOT THROUGH THE RTU POWER
CIRCUIT.
(WITH NO FIRE ALARM) ALL UNITS SHALL HAVE DRY CONTACTS FOR DUCT SMOKE DETECTOR
CIRCUIT FACTORY WIRED TO STOP UNIT UPON DETECTION OF SMOKE. TWO DUCT SMOKE
DETECTORS FOR EACH RTU AND REMOTE WIRING FURNISHED BY MECHANICAL TRADES.
MECHANICAL TRADES SHALL BE RESPONSIBLE FOR POWER AND CONTROL WIRING TO DUCT
SMOKE DETECTORS AND SHALL POWER THE DUCT SMOKE DETECTORS THROUGH AN
INDEPENDENT CIRCUIT AND NOT THROUGH THE RTU POWER CIRCUIT. SENSING TUBES FOR DUCT
SMOKE DETECTORS SHALL BE INSTALLED BY MECHANICAL TRADES.
9. THE MECHANICAL TRADES SHALL BE RESPONSIBLE FOR COMPLETING ALL LOW-VOLTAGE WIRING, CONDUIT, AND ASSOCIATED POWER SUPPLY NECESSARY FOR A COMPLETE AND OPERATIONAL
TEMPERATURE CONTROL SYSTEM. REFER TO THE ELECTRICAL DRAWINGS FOR AVAILABLE 120
VOLT POWER LOCATIONS. THE ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR PROVIDING THE
MAIN POWER FEED FOR ALL MECHANICAL EQUIPMENT. REFER TO THE ELECTRICAL DRAWINGS
FOR CLARIFICATION OF ELECTRICAL TRADES FURNISHED POWER.
10. FURNISH 5 YEAR COMPRESSOR WARRANTY FOR ROOFTOP UNITS.
11. FURNISH ONE YEAR OF COMPLETE SERVICE AND MAINTENANCE OF ROOFTOP UNITS. INCLUDE
CHECK TEST AND START-UP OF ROOFTOP UNITS AND CONTROL SYSTEM. PROVIDE FACTORY AND
FIELD WIRING DIAGRAMS, AND PROVIDE TECHNICAL ASSISTANCE AS REQUIRED TO ASSURE FIRST
CLASS OPERATING SYSTEMS.
12. FURNISH TRANE COMMUNICATION INTERFACE SYSTEM (FOR EACH UNIT).
GENERAL MECHANICAL NOTES
1. THE MECHANICAL TRADES SHALL FAMILIARIZE THEMSELVES WITH ALL EXISTING AND NEW
CONDITIONS, THESE DRAWINGS, ADDENDA & RELATED SPECIFICATIONS. THEY SHALL
COMPLETELY SATISFY THEMSELVES AS TO THE CONDITIONS TO WHICH THE WORK IS TO BE
PERFORMED BEFORE SUBMITTING THEIR BID. NO ALLOWANCES OR CONSIDERATIONS WILL BE
GIVEN AT A LATER DATE FOR ALLEGED MISUNDERSTANDINGS AS TO THE REQUIREMENTS OF THE
WORK, MATERIALS TO BE FURNISHED, OR CONDITIONS REQUIRED BY THE NATURE OF THIS
PROJECT SITE DUE TO NEGLECT ON THE BIDDERS PART TO MAKE SUCH AN EXAMINATION AND
COORDINATION.
2. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW APPROXIMATE LOCATION AND
GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. DRAWINGS SHALL NOT BE SCALED FOR
LOCATION OF SYSTEMS, EQUIPMENT, ETC. ALL LOCATIONS OF SYSTEMS AND EQUIPMENT SHALL
BE VERIFIED IN FIELD AND COORDINATED WITH ALL OTHER TRADES AND EXISTING FIELD
CONDITIONS. SOME SYSTEMS (PIPING, DUCTWORK, ETC.) AND EQUIPMENT LOCATIONS MAY
REQUIRE CHANGES IN LOCATION DUE TO FIELD CONDITIONS AND COORDINATION WITH OTHER
TRADES. THESE CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER. FAILURE
TO VERIFY AND COORDINATE WILL BE NO REASON FOR ADDITIONAL COMPENSATION.
3. THE INSTALLATION OF ALL SYSTEMS, EQUIPMENT, ETC., IS SUBJECT TO CLARIFICATION WITH
SUBMITTED SHOP DRAWINGS AND FIELD COORDINATION REQUIREMENTS. EQUIPMENT OUTLINES
SHOWN ON DRAWINGS OR DIMENSIONED ON DRAWINGS ARE LIMITING DIMENSIONS. ANY
EQUIPMENT THAT REDUCES THE INDICATED CLEARANCES OR EXCEEDS SPECIFIED OR
SCHEDULED EQUIPMENT DIMENSIONS SHALL NOT BE USED.
4. THE MECHANICAL CONTRACTOR SHALL COORDINATE FINAL LOCATION OF ALL EQUIPMENT WITH
PIPING, DUCTWORK, ETC., AT THE TIME OF ROUGH-IN. ALL EQUIPMENT TO BE SERVICEABLE.
5. THESE DRAWINGS AND THE ASSOCIATED SPECIFICATIONS ARE INTENDED TO PROVIDE
COMPLETELY FURNISHED, INSTALLED AND OPERATIONAL MECHANICAL SYSTEM (HEATING,
VENTILATING, AIR CONDITIONING, AND PIPING, ETC.). IF THESE DRAWINGS AND ASSOCIATED
SPECIFICATIONS HAVE INFORMATION OMITTED THAT WOULD NOT ALLOW A COMPLETELY
OPERATIONAL SYSTEM AS IS THE INTENT OF THE ENGINEER, THE BIDDER SHALL NOTIFY THE
ENGINEER A MINIMUM ONE WEEK PRIOR TO THE BID DATE TO ALLOW FOR ADDENDA. ONCE BIDS
HAVE BEEN RECEIVED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIAL, LABOR,
ETC., TO FURNISH AND INSTALL A COMPLETELY OPERATIONAL MECHANICAL SYSTEM AS IS THE
INTENT OF THESE DRAWINGS AND ASSOCIATED SPECIFICATION. ALL EQUIPMENT SHALL BE
INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IF ANY DISCREPANCIES ARE ON DRAWINGS,
AS COMPARED TO MANUFACTURER'S INSTALLATION INSTRUCTIONS, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER AND INSTALL EQUIPMENT AS REQUIRED AT NO ADDITIONAL COST TO THE
PROJECT.
6. THE MECHANICAL TRADES SHALL TAKE OUT ALL PERMITS AND ARRANGE FOR NECESSARY
INSPECTIONS AND SHALL PAY ALL FEES AND COSTS.
7. THE MECHANICAL TRADES SHALL VERIFY AMOUNT OF EXISTING PIPING, VALVES, DUCTWORK, ETC.
TO BE REMOVED OR RELOCATED TO ALLOW FOR INSTALLATION OF NEW PIPING, DUCTWORK,
VALVES, EQUIPMENT, WALLS, ETC.
8. THE MECHANICAL TRADES SHALL COORDINATE ALL WORK WITH OTHER TRADES AND SHALL
COORDINATE ANY SYSTEMS SHUT-DOWN WITH THE ARCHITECT/ENGINEER AND OWNER.
9. ALL EXISTING EQUIPMENT, PIPING, DUCTWORK, ETC. THAT IS TO BE REMOVED SHALL REMAIN THE
PROPERTY OF THE OWNER. THE CONTRACTOR SHALL REMOVE AND LOCATE THIS MATERIAL THAT
REMAINS THE PROPERTY OF THE OWNER TO A LOCATION DETERMINED BY THE OWNER
SOMEWHERE ON SITE. IF THE OWNER DOES NOT WANT TO MAINTAIN POSSESSION OF THE
REMOVED MATERIAL, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING MATERIAL
FROM THE SITE AND DISPOSING OF THIS MATERIAL AS NECESSARY TO MEET ALL CODES AND
REQUIREMENTS AND SHALL PAY ALL COSTS AS REQUIRED FOR ANY DISPOSAL FEES,
INSPECTIONS, PERMITS, ETC.
10. ATTACHMENTS OF MECHANICAL OR ELECTRICAL EQUIPMENT TO STRUCTURAL MEMBERS ARE
THE RESPONSIBILITY OF THE INSTALLING TRADE. STRUCTURAL MEMBERS SHALL NOT BE FIELD
CUT, WELDED OR OTHERWISE MODIFIED WITHOUT APPROVAL OF THE ARCHITECT/ENGINEER.
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
EAB
E1.01
FLOOR PLAN
ELECTRICAL DEMOLITION
FLOOR PLAN - ELECTRICAL DEMOLITION
NORTH
JB
8 T
CHECKED BY
SHEET TITLE
PROJECT TITLE
COPYRIGHT 2019
C
Saginaw, Michigan 48607
989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
ARCHITE SCT
61220
INDEX NO.
472/16319.JAG
FILE NO.
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ROBERT C. HALL, RA, NCARB, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
EAST FOOD SERVICE BUILDING FOR:
CENTRAL MICHIGAN
CORRECTIONAL FACILITY
ST. LOUIS, MICHIGAN
2016094.2
AUGUST, 2019
RENOVATIONS TO
DATENO. REVISION
EAB
E1.02
FLOOR PLAN
ELECTRICAL REVISIONS
FLOOR PLAN - ELECTRICAL REVISIONS
NORTH
2 2
T
JB
JB
| AD.01-2016094.2 _RD |
| A2.01-2016094.2_RD |
| A2.02-2016094.2 _RD |
| 2019.11.14 Visitor Center Renovations Central Michigan MDOC Facility Bulletin No.3 |
| 2016-1558-M-M1.01-FSB-DEMO |
| 2016-1558-M-M1.01-FSB-DEMO-Model |
| LIMITS |
| 2016-1558-M-M1.02-FSB-HVAC |
| 2016-1558-M-M1.02-FSB-HVAC-Model |
| LIMITS |
| 2016-1558-M-M1.03-FSB-DET |
| 2016-1558-M-M1.03-FSB-DET-Model |
| LIMITS |
| 2016-1558-M-M1.04-FSB-SPECS |
| 2016-1558-M-M1.04-FSB-SPECS-Model |
| LIMITS |
| 2016-1558-E1.01-ELEC-MECH RM |
| 2016-1558-E-E1.01-FSB-DEMO BULL 3 |
| 2016-1558-E-E1.01-FSB-DEMO BULL 3-Model |
| LIMITS |
| 2016-1558-E-E1.02-FSB-ELEC REVISIONS BULL 3 |
| 2016-1558-E-E1.02-FSB-ELEC REVISIONS BULL 3-Model |
| LIMITS |
| Food Service |
| BL3.3 dwg |
| 2016-1558-M-M1.02-FSB-HVAC-Model |
| LIMITS |
| M102 |
| 2016-1558-M-M1.02-FSB-HVAC-Model |
| LIMITS |
File details come from the government source that posted it. Updated .