DWGs 2017 CMCF East FS.pdf

PDF 8 MB Posted

Attached to
472/25362. CTS; Central MI CF - Various HVAC Imprvmnt
Solicitation number
RFP-171-250000002855-2
Issued by
Gogebic County, Michigan

About this file

These architectural and engineering documents detail the Cooler & Freezer Replacement and HVAC System Renovation project for the East Food Service Building at the Central Michigan Correctional Facility, located at 320 N. Hubbard in St. Louis, Michigan. The project, numbered 2016094.2 and dated August 2019, involves comprehensive mechanical, electrical, and architectural renovations for the facility's food service area. The design documents, prepared by WTA Architects and MacLean Associates, Inc., provide detailed floor plans, demolition plans, electrical and HVAC revisions, and mechanical specifications for replacing refrigeration equipment, updating electrical systems, and renovating the existing food service infrastructure.

The project scope includes replacing rooftop units (RTUs), installing new ductwork, updating electrical systems, and implementing mechanical revisions across the facility's food service building. The documents specify technical details such as equipment specifications for Trane Precedent rooftop units with varying cooling and heating capacities, new gas piping, ventilation systems, and electrical circuit modifications. The renovation aims to improve the facility's infrastructure with modern, efficient systems, including energy-efficient equipment, updated electrical circuits, and improved mechanical ventilation. The project documents indicate careful consideration of existing conditions, requiring contractors to verify site measurements, coordinate with other trades, and ensure a fully operational mechanical and electrical system upon completion.

View the file

Other files

File Type Posted
DWG CMCF overall.pdf PDF
RFP Billable Rate 25362 (1).pdf PDF
LEIN Request 25362.pdf PDF
Addendum 1 - 25362.pdf PDF
SAMPLE Billable Rate Contract (Rev 04-25).pdf PDF
DWGs 1989 St Louis Temp.pdf PDF
DWGs 2017 CMCF West Admin.pdf PDF
Proj State 25362.pdf PDF
DWGs 1999 St Louis LVL1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NUMBERPROJECT NUMBER

PROJECT DATE

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

RAM

FLOOR PLAN

HVAC DEMOLITION

M1.01

FLOOR PLAN - HVAC DEMOLITION

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

RAM

M1.02

FLOOR PLAN

HVAC REVISIONS

FLOOR PLAN - HVAC REVISIONS

COOLER

STORAGE STORAGE

WASH AREA

DINING

OFFICE

DRY

STORAGE

OFFICE

PREPERATION

TOILET

TOILET

LAUNDRY

MECHANICAL

OFFICE

DINING

COOLER

FREEZER

153 S.F.

138 S.F.

KEYED NOTES

ALL NEW DUCTWORK SHALL BE MOUNTED TIGHT TO

UNDERSIDE OF EXISTING CEILING.

FIELD VERIFY EXACT LOCATION OF ALL NEW

THERMOSTATS. PROVIDE AND INSTALL VANDAL

RESISTANT LOCKABLE COVERS.

INSTALL NEW MAKE-UP AIR DUCTWORK ABOVE FREEZER

AND BELOW EXISTING CEILING, CONNECT

NEW 36” X 14” DUCT TO (6) 24” X 12” HOOD SUPPLY AIR

DUCT COLLARS.

SHUT-OFF VALVE WITH DIRT LEG. (TYP)

EXPOSED DUCTWORK (TYP)

FLEX CONNECTION (TYP)

DUCTWORK TO BE INSTALLED IN ATTIC SPACE WITH

EXTERNAL INSULATION.

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

RAM

MECHANICAL

DETAILS AND

SCCHEDULES

M1.03

INLINE EXHAUST FAN DETAIL

BRANCH DUCT CONNECTION TO DIFFUSER OR GRILLE DETAIL

RECTANGULAR TO ROUND DUCT SUPPLY, RETURN OR EXHAUST DUCT

SUPPLY DUCT RETURN OR EXHAUST DUCT

RECTANGULAR DUCT BRANCH TAKE-OFF DETAILS

DUCTWORK RADIUS ELBOW

DUCTWORK SQUARE VANE MITERED ELBOWS

FIRE DAMPER DETAIL

KITCHEN HOOD EXHAUST FAN DETAIL (PITCHED ROOF)

DUCT SECTION

ROOF TOP UNIT DETAIL (ON GRADE)

ROOF TOP AIR HANDLING UNIT ON GRADE

CONTROL AND COMPRESSOR ACCESS PANEL

EVAPORATOR SECTION ACCESS PANEL

ECONOMIZER HOOD

GAS SHUT OFF VALVE

BAROMETRIC OR POWER RELIEF (SEE SCHEDULE OR

SPECIFICATIONS FOR OPTIONS)

TRAPPED CONDENSATE DRAIN-DRIP TO ROOF

6"REINFORCED CONCRETE PAD

12" ROOF CURB ON PAD

GAS PIPE CONNECTION

6" LONG DIRT LEG WITH CAP (LOCATE AT ELEVATION

CHANGES)

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

RAM

MECHANICAL

SPECIFICATIONS

M1.04

CODES, PERMITS & INSPECTIONS

CONTRACTOR SHALL SECURE PERMITS, INSPECTIONS AND TESTS, PAY ALL FEES,

DEPOSITS, AND COSTS FOR ALL MECHANICAL UTILITIES AND SERVICES INVOLVED

AND PRESENT THE OWNER A CERTIFICATE OF INSPECTION AND APPROVAL FROM THE

DEPARTMENT HAVING JURISDICTION OVER HIS WORK. SHOULD ANY CHANGE IN THE

DRAWINGS AND SPECIFICATIONS BE REQUIRED TO COMPLY WITH ALL APPLICABLE

CODES, RULES, REGULATIONS, ETC., CONTRACTOR SHALL NOTIFY THE ENGINEER

BEFORE SUBMITTING BID. AFTER ENTERING INTO CONTRACT, ALL WORK NECESSARY

TO MEET THE REQUIREMENTS SHALL BE COMPLETED WITHOUT ADDITION TO THE

CONTRACT AMOUNT. WHERE WORK INDICATED IS MORE THAN REQUIRED BY CODES,

ETC., SUCH WORK SHALL BE AS INDICATED.

JOB OBSERVATION

NOTWITHSTANDING ANY REFERENCE TO ANY CODE, RULE OR REGULATION,

ENGINEER SHALL HAVE NO RESPONSIBILITY FOR SAFETY ON THE JOB SITE, SHALL

HAVE NO RIGHT TO CHANGE OR STOP THE WORK, SHALL NOT CONTROL THE MEANS

OF THE WORK, AND SHALL NOT HAVE ANY DUTY TO PROVIDE SUPERVISION OF

MEANS, METHODS, PROCESSES OR PROCEDURES OF CONSTRUCTION.

FIRST-CLASS WORKABLE SYSTEMS

FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN

THE OPINION OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS

ARE REQUIRED TO PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR

SHALL REQUEST AN INTERPRETATION FROM THE ENGINEER BEFORE PROCEEDING

WITH THE WORK. IF THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, NO EXCUSE

WILL THEREAFTER BE ENTERTAINED FOR FAILURE TO PROVIDE FIRST-CLASS

WORKABLE SYSTEMS.

DRAWINGS

DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN, AND

EXTENT OF THE WORK AND ARE DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE

SCALED FOR ROUGH-IN MEASUREMENTS NOR TO SERVE AS SHOP DRAWINGS. THE

ENGINEERS AND OWNER RESERVE THE RIGHT TO MAKE MINOR CHANGES IN THE

LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. AT THE TIME OF ROUGH-IN

WITHOUT ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL FIELD VERIFY ALL

DIMENSIONS, LOCATIONS, ETC. FOR ACCURACY AND POSSIBILITY OF INTERFERENCES

DUE TO FIELD CONDITIONS AND ACTUAL BUILDING STRUCTURE. FAILURE TO CHECK

WILL BE NO REASON FOR ADDITIONAL COMPENSATION.

SHOP DRAWINGS

SUBMIT ELECTRONIC SET OF COMPLETE SHOP DRAWINGS FOR ALL MECHANICAL

EQUIPMENT AND MATERIALS TO THE ENGINEER FOR REVIEW BEFORE FABRICATION

OF WORK OR ORDERING OF EQUIPMENT. DRAWINGS MUST BE REVIEWED BY THE

ENGINEER BEFORE ORDERING EQUIPMENT. ALL SHOP DRAWINGS REJECTED SHALL

BE CORRECTED AND RESUBMITTED TO THE ENGINEER BEFORE ORDERING.

GUARANTEE

CONTRACTOR SHALL GUARANTEE EQUIPMENT, MATERIALS AND WORKMANSHIP IN HIS

CONTRACT AND SHALL MAKE GOOD AT HIS OWN EXPENSE ANY DEFECTS WHICH MAY

DEVELOP WITHIN ONE YEAR AFTER START-UP OF EACH PIECE OF EQUIPMENT,

OCCUPANCY BY OWNER, OR FINAL ACCEPTANCE OF THE JOB, WHICHEVER OCCURS

FIRST.

CONTRACTORS RECORD/AS-BUILT DRAWINGS

CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET

OF “RECORD” DRAWINGS REFLECTING "AS-BUILT" CONDITIONS OF THEIR

WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND ELEVATIONS FOR

ALL UNDERGROUND WORK. UPON COMPLETION OF THIS PROJECT, THE

CONTRACTOR SHALL DELIVER TO THE ENGINEER THE “RECORD” DRAWINGS.

LOCAL CONDITIONS

BEFORE SUBMITTING BIDS AND/OR PROCEEDING WITH THE PROJECT, THE

CONTRACTOR SHALL EXAMINE ALL DRAWINGS, SPECIFICATIONS AND ADDENDA

ISSUED FOR THE PROJECT AND SHALL EXAMINE THE PROJECT SITE. THE

CONTRACTOR SHALL THOROUGHLY INVESTIGATE THE PROJECT SITE AND BECOME

FULLY INFORMED AS TO THE EXTENT OF HIS WORK AND COORDINATION OF THIS

WORK WITH ALL OTHER TRADES AND INCLUDE ALL COST TO PERFORM AND

COMPLETE WORK FOR THIS PROJECT PER DRAWINGS AND SPECIFICATION AND ALL

CODES.

OPERATION AND MAINTENANCE MANUALS

CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER TWO (2) COPIES OF AN

APPROVED BOUND (3-RING BINDER) BOOK WITH TABS FOR SECTIONS COVERING

EACH ITEM OF EQUIPMENT. THESE NOTEBOOKS SHALL INCLUDE SHOP DRAWINGS,

MAINTENANCE MANUALS, OPERATING MANUALS AND PARTS LIST AS NECESSARY TO

INSTRUCT THE OWNER ON PROPER OPERATION AND USE AS WELL AS MAINTENANCE

FOR EACH PIECE OF EQUIPMENT FOR THIS PROJECT. THESE BOOKS SHALL ALSO

INCLUDE CONTRACTOR'S, SUBCONTRACTOR'S AND MANUFACTURER'S NAMES,

TELEPHONE NUMBERS AND ADDRESSES. MANUALS SHALL ALSO INCLUDE SEQUENCE

OF OPERATION, CONTROL EQUIPMENT LITERATURE, WIRING AND CONTROL

DIAGRAMS, CERTIFICATES OF GUARANTEES, CERTIFICATES OF INSPECTION,

MECHANICAL SYSTEM TEST AND BALANCING REPORTS. THE CONTRACTOR SHALL

ACCUMULATE AND SUMMARIZE THE CONTROL AND MAINTENANCE SEQUENCE IN

TYPEWRITTEN SHEET TO BE INCLUDED IN THE REPORT. THESE MANUALS SHOULD BE

HARD BOUND IN BEST QUALITY BINDERS AND TURNED OVER TO THE

ARCHITECT/ENGINEER FOR APPROVAL AT COMPLETION OF PROJECT.

START-UP SERVICE

CONTRACTOR SHALL ARRANGE WITH EQUIPMENT MANUFACTURERS FOR PROVIDING

COMPLETE START-UP SERVICE FOR ALL EQUIPMENT ON THIS PROJECT. ALL

START-UP SERVICES SHALL BE PERFORMED IN THE PRESENCE OF THE OWNER

AND/OR ENGINEER. A WRITTEN REPORT SHALL BE SUBMITTED TO THE ENGINEER

STATING DATE OF START-UP, MANUFACTURER APPROVAL OF SYSTEM OPERATION

AND INSTALLATION.

CUTTING AND PATCHING

CUTTING AND PATCHING SHALL BE BY TRADES REGULARLY ENGAGED IN THIS TYPE

OF WORK, EXCEPT DRILLING OF HOLES SHALL BE DONE BY THE TRADES REQUIRING

SAME. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED.

SALVAGEABLE MATERIAL

SALVAGEABLE MATERIAL SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL

BE STORED AT LOCATIONS AS DIRECTED BY THE OWNER, EXCEPT THE OWNER

RESERVES THE RIGHT TO DESIGNATE CERTAIN ITEMS OF SALVAGEABLE MATERIAL TO

BE REMOVED FROM THE PROJECT SITE.

RIGGING AND HOISTING

PERFORM ALL REQUIRED RIGGING, HOISTING, TRANSPORTATION, MOVING, ETC. OF

ALL EQUIPMENT, MATERIALS, ETC. TO BE FURNISHED AND/OR INSTALLED AS SHOWN

ON DRAWINGS, WHETHER FURNISHED BY THIS CONTRACTOR OR BY THE OWNER OR

OTHER TRADES.

STORAGE FACILITY

FURNISH AND MAINTAIN A WEATHERPROOF STORAGE FACILITY ON THE SITE OF

ADEQUATE SIZE TO STORE MISCELLANEOUS EQUIPMENT AND/OR MATERIALS TO

PREVENT EXPOSURE TO THE WEATHER. LOCATION OF SHED SHALL BE DETERMINED

BY THE OWNER AND ARCHITECT/ENGINEER. THE OWNER RESERVES THE RIGHT TO

DENY STORAGE OF MATERIALS OR EQUIPMENT IN ANY EXISTING OR NEW BUILDINGS.

PROTECTION FROM DAMAGE

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIALS, EQUIPMENT, ETC.

AND ALL WORK INSTALLED BY HIMSELF AND SHALL PROTECT IT FROM DAMAGE UNTIL

FINAL ACCEPTANCE OF THIS PROJECT BY THE OWNER.

FURNISH ALL COVERINGS AND PROTECTION FROM DIRT, DUST, RAIN, STORM, HEAT,

TRAFFIC, WEAR, ETC. AND ALL POSSIBLE INJURY INCLUDING THAT BY OTHER

WORKMEN. ANY EQUIPMENT, WORKMANSHIP, MATERIALS, ETC. DAMAGED PRIOR TO

FINAL ACCEPTANCE BY THE OWNER OF THIS PROJECT SHALL BE PROPERLY

REPAIRED AT NO EXPENSE TO THE OWNER.

PROTECT ALL EQUIPMENT FROM DAMAGE BY COVERING OR COATING. ANY DENTED,

SCRATCHED, RUSTED OR MARRED SURFACE FINISHES WILL NOT BE ACCEPTED.

PROTECT ALL EQUIPMENT, MATERIALS, ETC. FROM FREEZING.

NATURAL GAS PIPING, ABOVE GRADE INSIDE BUILDING

NATURAL GAS PIPING 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK CARBON STEEL

ASTM A53, SEAMLESS WITH BLACK MALLEABLE IRON FITTINGS, 150 PSIG SCREWED

ASME B16.3.

NATURAL GAS PIPING 2 1/2" AND LARGER SHALL BE SCHEDULE 40 BLACK CARBON

STEEL ASTM A53 SEAMLESS WITH WELDED FITTINGS ASTM A234.

PIPING FOR 1 PSIG OR HIGHER GAS PRESSURE SHALL BE IN ACCORDANCE WITH

CODE FOR PRESSURE PIPING ANSI B31.1.

FURNISH LUBRICATED PLUG SHUT-OFF VALVES ON MAIN BRANCHES AND AT

DOMESTIC PRESSURE REGULATORS. LOCATE WRENCH NEAR METER. STOP VALVES

AT EQUIPMENT AND OUTLETS SHALL BE BALL VALVES WHERE 2" AND SMALLER. GAS

PIPING SHALL HAVE DRIPS AT BOTTOM OF RISERS WITH BRANCHES TAKEN FROM TOP

OR SIDE OF HORIZONTAL PIPE. CAP ALL GAS PIPE OUTLETS UNTIL CONNECTED TO

GAS EQUIPMENT. ALL GAS PIPING SHALL BE RUN IN SPACES WHICH ARE ACCESSIBLE

FOR INSPECTION AND SERVICE.

VALVES

GATE VALVES:

UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TRIM, SCREWED BONNET,

RISING STEM, HANDWHEEL, INSIDE SCREW WITH BACKSEATING STEM, SOLID WEDGE

DISC, ALLOY SEAT RINGS, SOLDER OR THREADED ENDS.

BALL VALVES:

UP TO AND INCLUDING 2 INCHES: BRONZE ONE PIECE BODY, STAINLESS STEEL BALL,

TEFLON SEATS AND STUFFING BOX RING, LEVER HANDLE WITH BALANCING STOPS,

SOLDER OR THREADED ENDS.

OVER 2 INCHES: CAST STEEL BODY, CHROME PLATED STEEL BALL, TEFLON SEAT AND

STUFFING BOX SEALS, LEVER HANDLE, OR GEAR DRIVE HANDWHEEL FOR SIZES 10

INCHES AND OVER, FLANGED. DUCTILE IRON BODY, CHROME PLATED CARBON STEEL

BALL AND STEM, TFE SEATS, LEVER HANDLE OR GEAR OPERATOR, GROOVED ENDS.

VICTAULIC SERIES 726.

PLUG VALVES:

UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TAPERED PLUG, FULL PORT

OPENING, NON-LUBRICATED, TEFLON PACKING, THREADED ENDS. OPERATOR: ONE

PLUG VALVE WRENCH FOR EVERY TEN PLUG VALVES MINIMUM OF ONE.

OVER 3 INCHES: CAST IRON BODY AND PLUG, FULL PORT OPENING, PRESSURE

LUBRICATED, TEFLON PACKING, FLANGED ENDS OR GROOVED ENDS IF VICTAULIC

GROOVED END FITTINGS ARE USED. DUCTILE IRON BODY AND PLUG, STANDARD

PORT OPENING, NON-LUBRICATED ECCENTRIC-TYPE, WELDED-IN NICKEL SEAT,

GROOVED ENDS. VICTAULIC SERIES 377. OPERATOR: EACH PLUG VALVE SHALL HAVE

A WRENCH HANDLE WITH SET SCREW.

UNIONS

UNIONS OR FLANGES SHALL BE USED AT EQUIPMENT CONNECTIONS. DIELECTRIC

CONNECTIONS BETWEEN COPPER AND IRON OR STEEL PIPE SHALL BE MADE WITH

DIELECTRIC NIPPLES SIMILAR TO VICTAULIC STYLE 47. A BRASS ADAPTER

DIELECTRIC UNION IS NOT ACCEPTABLE.

PLATES AND SLEEVES

PROVIDE AND INSTALL PIPE SLEEVES FOR ALL PIPING AND DUCTS PASSING THROUGH

WALLS, FLOORS AND CEILINGS. SLEEVES THROUGH WALLS AND CEILINGS MAY BE 20

GAUGE GALVANIZED SHEET METAL. WHERE PIPES ARE INSULATED, SLEEVES SHALL

BE LARGE ENOUGH TO PASS THE INSULATION. ALL PENETRATION VOIDS SHALL BE

SEALED SMOKE TIGHT WITH NON-COMBUSTIBLE MATERIALS SIMILAR TO 3M OR HILTI

FIRESTOP SYSTEMS TO MAINTAIN THE INTEGRITY OF THE FIRE RATED STRUCTURE. IN

A NON-FIRE RATED ASSEMBLY, SEAL ALL VOIDS WITH NON-HARDENING SEALANT.

HANGERS AND SADDLES

SHALL BE MODERN PIPE SUPPORTS CORP., GRINNELL/ANVIL, AUTO GRIP OR M-CO.

FOR COPPER PIPE WITH STEEL HANGERS, CLEAN AND WRAP PIPE WITH TWO LAYERS

OF PLASTIC INSULATING TAPE AT POINTS OF CONTACT. HANGERS FOR PIPING WITH

VAPOR BARRIER SEALED INSULATION SHALL BE MULTIPURPOSE PIPE SADDLES

FITTING OVER THE INSULATION. WIRE OR PERFORATED STRAP IRON WILL NOT BE

PERMITTED FOR PIPE SUPPORTS. HANGERS SHALL BE CLEVIS OR SPLIT RING TYPE

WITH VERTICAL ADJUSTMENT AND BEAM CLAMP SIMILAR TO GRINNELL/ANVIL FIG. 260,

WITH MAXIMUM SPACING PER ASHRAE STANDARDS:

PIPE SIZE STEEL PIPE COPPER PIPE PVC PIPE ROD SIZE

1/2 TO 3/4 INCH 6 FEET 5 FEET 4 FEET 3/8”

1 INCH 7 FEET 5 FEET 4 FEET 3/8”

1 1/4 INCH 7 FEET 7 FEET 4 FEET 3/8”

1 1/2 INCH 7 FEET 7 FEET 4 FEET 1/2”

2 INCH 10 FEET 8 FEET 4 FEET 1/2"

2 1/2 INCH 11 FEET 9 FEET 4 FEET 5/8”

3 INCH 11 FEET 9 FEET 4 FEET 5/8”

3 1/2 INCH 13 FEET 11 FEET 4 FEET 5/8”

4 INCH 14 FEET 12 FEET 4 FEET 5/8”

PIPE IDENTIFICATION

ALL PIPING SHALL BE IDENTIFIED PER ANSI/OSHA OR OWNER'S STANDARDS WITH

COLOR PIPE BANDS, IDENTIFICATION LABELS AND FLOW ARROWS. PIPES SHALL BE

BANDED AND LABELED ON 10'-0" CENTERS ON CONTINUOUS LINES, AT EQUIPMENT

CONNECTIONS, AT BOTH SIDES OF A WALL THROUGH WHICH PIPE PASSES AT EVERY

BRANCH CONNECTION, ON PIPING WITHIN SIGHT OF AN ACCESS DOOR OR PANEL.

SHOW SLOPE DIRECTIONAL ARROWS AT EACH IDENTIFICATION POINT. LABELS, FLOW

ARROWS AND STENCIL AND PAINT SHALL BE 1" HIGH ON PIPING UP TO 2 1/2" AND

SHALL BE 2" HIGH ON PIPE SIZES OF 3" AND LARGER. BANDS SHALL BE 1 1/2" WIDE.

LABELS SHALL BE AS MANUFACTURED BY SETON OR W.H. BRADY COMPANY OR

EQUAL. VERIFY TYPE, SIZE AND COLORS OF PIPE IDENTIFICATION WITH OWNER.

DUCTWORK

DUCTS, CASINGS, HOUSINGS, ETC. SHALL BE FABRICATED FROM, PRIME QUALITY,

HOT DIP GALVANIZED STEEL SHEET AS RECOMMENDED IN THE LATEST ISSUES OF

ASHRAE GUIDE AND SMACNA DUCT MANUALS IN VARIABLE AIR VOLUME SYSTEMS,

WHEN USED. SUPPLY AIR DUCTS LOCATED BETWEEN AIR HANDLING SYSTEM AND

VAV BOXES; DUCT CONSTRUCTION AND INSTALLATION SHALL MEET SMACNA

STANDARDS FOR 6" W.C. FOR ALL OTHER SUPPLY AIR DUCTWORK AND EXHAUST AIR,

RETURN AIR, OUTSIDE AIR INTAKE AND RELIEF AIR DUCTS, DUCT CONSTRUCTION AND

INSTALLATION SHALL MEET SMACNA STANDARDS FOR 2" W.C.

RECTANGULAR DUCTS SHALL HAVE TEES, ELBOWS AND BENDS WITH A MINIMUM

THROAT RADIUS OF 1 TIMES THE DUCT WIDTH AND BE OF THE SAME GAUGE AND

MATERIAL AS THE STRAIGHT DUCT. INCREASE DUCT SIZES GRADUALLY, NOT

EXCEEDING 15 DEGREES DIVERGENCE IF POSSIBLE; MAXIMUM 30 DEGREES

DIVERGENCE UPSTREAM OF EQUIPMENT AND 45 DEGREES CONVERGENCE

DOWNSTREAM. WHERE VOLUME BOXES ARE CONNECTED TO DUCT MAIN OR WHERE

DIFFUSERS ARE CONNECTED TO DUCT BRANCHES BY ROUND FLEX DUCT, INSTALL

DUCT SPIN-IN FITTINGS SUCH AS FLEXMASTER USA, INC. MODEL #FLD WITH DAMPER

AND POSITIVE LOCKING WING NUT. SEAL ALL EDGES WITH FIRE RETARDANT DUCT

SEALER. FLEXIBLE INSULATED DUCTS (CONNECTIONS FROM MAIN DUCT TO VOLUME

BOX AND/OR FROM DUCT BRANCH TO DIFFUSERS) SHALL BE FLEXMASTER USA, INC.

TYPE #3. USE MAXIMUM LENGTH OF 5'-0" TO EACH CONNECTION. INSTALL FLEXIBLE

DUCT WITH MINIMUM OF BENDS USING LONG RADIUS BENDS ONLY.

DUCT SEALANT

ALL DUCTWORK INCLUDING SUPPLY AIR, OUTSIDE AIR, RETURN AIR, EXHAUST AIR

AND RELIEF AIR DUCT SYSTEMS SHALL HAVE ALL JOINTS SEALED. DUCTWORK

DESIGNED AT SMACNA 6” PRESSURE SHALL MEET SMACNA CLASS “A” SEAL

REQUIREMENTS. DUCTWORK DESIGNED AT SMACNA 2” PRESSURE SHALL MEET

SMACNA CLASS “C” SEAL REQUIREMENTS.

DUCT HANGERS

HORIZONTAL STEEL DUCTWORK SHALL BE SUPPORTED BY MEANS OF TRAPEZE BARS

AND ROUND STEEL ROD OF SIZES LISTED BELOW. ROUND STEEL RODS SHALL BE

ELECTRO-GALVANIZED ALL-THREAD ROD. HANGERS SHALL BE PROVIDED AT BOTH

SIDES OF FLAT SIDED DUCTWORK FOR THE FULL HEIGHT OF DUCT. ROUND

DUCTWORK SHALL BE PROVIDED WITH A BAND OF THE SAME SIZE AS THE HANGER TO

COMPLETELY ENCIRCLE THE DUCT. BAND SHALL BE SECURED TO THE HANGER BY

MEANS OF A MINIMUM 3/16" BOLT. MINIMUM DUCT HANGER SIZES SHALL BE AS LISTED

BELOW

MIN. UPPER MINIMUM

DUCT ATTACHMENT STEEL MAXIMUM NO. OF TRAPEZE

SIZE RATING ROD SPACING HANGERS SHELF ANGLE

UP TO 16" 750 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"

19" TO 36" 1000 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"

37" TO 120" 3000 LBS. 3/8" 8' 2 2" X 2" X 1/4"

DUCT INSULATION

DUCTWORK LOCATED IN CONCEALED AREAS (CONCEALED AREAS SHALL INCLUDE

DUCT SHAFTS, SPACES ABOVE DROPPED CEILINGS, SPACES BETWEEN WALLS, ETC.)

SHALL BE WRAPPED EXTERNALLY WITH OWENS-CORNING, KNAUF, MANSVILLE, OR

EQUAL, FIBERGLAS ALL-SERVICE DUCT WRAP, LIGHT DENSITY GLASS FIBER

INSULATION FACED WITH A REINFORCED FOIL/KRAFT LAMINATE MEETING THE

REQUIREMENTS OF ASTM C553, 1.0 LBS. PER CUBIC FOOT DENSITY, 1 1/2" THICK.

WHERE DUCTS ARE 24" IN WIDTH OR GREATER, MECHANICAL FASTENERS SPACED AT

18" (APPROX.) CENTERS ARE REQUIRED ON THE BOTTOM OF THE DUCT TO PREVENT

THE INSULATION FROM SAGGING. ALL SEAMS, TEARS, PUNCTURES, AND OTHER

PENETRATIONS SHALL BE CLOSED WITH 3" PRESSURE SENSITIVE, VAPOR BARRIER

MASTIC REINFORCED GLASS SCRIM TAPE.

KITCHEN HOOD EXHAUST DUCT WRAP SHALL BE “FIRE MASTER” AS MANUFACTURED

BY 3M FIRE BARRIER PRODUCTS, INSTALLED AS RECOMMENDED BY MANUFACTURER

IN TWO LAYERS WITH STAINLESS STEEL BANDING TO GIVE DUCT A 2 HOUR UL RATED

ENCLOSURE. DUCT WRAP SHALL BE A 1 1/2” THICK REFRACTORY CERAMIC FIBER

BLANKET ENCAPSULATED WITH ALUMINUM FOIL SCRIM. DUCT WRAP SHALL BE

CLASSIFIED BY U.L. AS A GREASE DUCT APPROVED ENCLOSURE AND TESTED TO

ASTM E84/UL 723 WITH A FLAME SPREAD AND SMOKE DEVELOPED RATING OF 5. DUCT

WRAP SHALL HAVE A MINIMUM THERMAL RESISTANCE “R” VALUE OF 4.15 PER INCH

AT 70 DEGREES F. TWO LAYERS OF DUCT WRAP SHALL BE INSTALLED, APPLIED

DIRECTLY TO THE DUCT. A 3” PERIMETER AND LONGITUDINAL OVERLAP SHALL BE

EMPLOYED ON BOTH LAYERS. FILAMENT TAPE SHALL BE USED AS A TEMPORARY

HOLD UNTIL STAINLESS STEEL BANDING IS IN PLACE. FOR DUCT SPANS OF 24” OR

GREATER, INSULATION PINS SHALL BE UTILIZED ON THE BOTTOM OF HORIZONTAL

AND ON VERTICAL DUCT RUNS TO PREVENT SAGGING. SEE “3M INSTALLATION

GUIDE” FOR INSTALLATION DETAILS. INSTALLATION SHALL HAVE THE APPROVAL OF

OWNER'S INSURANCE UNDERWRITER AND THE FIRE MARSHAL HAVING JURISDICTION.

INTERNAL ACOUSTIC DUCT LINER

WHERE CALLED FOR, LINE DUCT WITH 1” THICK FIBERGLASS AEROFLEX ACOUSTICAL

INTERNAL DUCT LINER, IN LIEU OF EXTERNAL DUCT INSULATION. INSULATION SHALL

BE 1.5 LB. DENSITY, WITH A FIRE RESISTANT COATING TO BOND FIBERS OF THE AIR

STREAM SIDE SURFACE, INSTALLED AS RECOMMENDED BY MANUFACTURER.

DUCTWORK LOCATED OUTDOORS

ALL DUCTWORK (SUPPLY, RETURN, EXHAUST, OUTSIDE AIR, RELIEF AIR) LOCATED

OUTDOORS SHALL BE COVERED EXTERNALLY WITH EITHER 2” OF FLEXIBLE

ELASTOMERIC CLOSED-CELL INSULATION, OR 2” OF FOAMGLAS® CLOSED CELL

INSULATION. INSTALLATION SHALL MEET MANUFACTURER'S

RECOMMENDATIONS, WITH ALL JOINTS FIRMLY BUTTED AND SECURED WITH

ADHESIVES OR FASTENERS. ALL DUCTWORK INSULATION SHALL BE JACKETED WITH

A MULTI-PLY, FABRIC REINFORCED, SELF ADHESIVE INSULATION CLADDING MATERIAL

WITH A VAPOR BARRIER AND A THICKNESS OF 0.015”. JACKETING SYSTEM SHALL BE

VENTURE CLAD PLUS #1579CW-E, OR EQUAL. INSTALL ALL INSULATION AND

JACKETING IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL JACKETING SEAMS MUST BE TAPED WITH MANUFACTURER'S RECOMMENDED

JOINT/SEAMING TAPE.

RECTANGULAR DUCTWORK SHALL BE INSTALLED WITH A CROWN OR SLOPE ON TOP

TO PREVENT WATER FROM PONDING. INSULATION AND JACKETING SHALL BE

INSTALLED ON TOP OF DUCT AND CROWN OR SLOPE SHIM. JACKETING SHALL BE

INSTALLED TO EACH OF THE SIDES SEPARATELY, STARTING WITH BOTTOM, THEN

SIDES AND FINALLY THE TOP. EACH SIDE SHALL OVERLAP THE OTHER BY 3”. THE

SIDES SHALL OVERLAP THE BOTTOM AND THE TOP SHALL OVERLAP THE SIDES.

TESTING, ADJUSTING AND BALANCING

TESTING, ADJUSTING AND BALANCING SHALL BE PERFORMED BY AN INDEPENDENT

CERTIFIED AGENCY IN ACCORDANCE WITH AABC, ADC, ASHRAE III, NEBB AND SMACNA

STANDARDS. FURNISH 5 SETS OF REPORTS OF AIR AND WATER SYSTEMS BALANCE

REPORTS TO THE ENGINEER INDICATING DESIGN AND ACTUAL QUANTITIES,

NAMEPLATE DATA, ETC.

ACCEPTABLE TEST AND BALANCE CONTRACTORS:

1. HITECH TEST AND BALANCE (FREELAND, MI)

2. ABSOLUTE BALANCE COMPANY (SOUTH LYON, MI)

3. ENVIRO-AIRE/TOTAL BALANCE COMPANY (ST. CLAIR SHORES, MI)

4. ENER-TECH TESTING (HOLLY, MI)

5. INTERNATIONAL TEST AND BALANCE (SOUTHFIELD, MI)

AIR SYSTEMS ADJUST AIR HANDLING, DISTRIBUTION SYSTEMS, AIR INLETS AND

OUTLETS, ETC. TO PROVIDE SUPPLY, RETURN, EXHAUST, OUTSIDE AIR AND RELIEF

AIR QUANTITIES TO WITHIN 10% OF REQUIRED OR DESIGNED AIR QUANTITIES. VERIFY

THAT SYSTEMS ARE COMPLETE AND OPERABLE BEFORE COMMENCING WORK.

VERIFY SYSTEMS ARE STARTED AND OPERATING AT A SAFE AND NORMAL

OPERATION, TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND

OPERABLE, PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL

EQUIPMENT, FINAL FILTERS ARE CLEAN AND IN PLACE, DUCT SYSTEMS ARE CLEAN OF

DEBRIS, FANS ARE ROTATING CORRECTLY, FIRE AND VOLUME DAMPERS ARE IN

PLACE AND IN OPEN POSITIONS, AIR COIL FINS ARE CLEANED AND COMBED, ACCESS

DOORS ARE CLOSED AND DUCT END CAPS ARE IN PLACE, AIR OUTLETS ARE

INSTALLED AND CONNECTED, DUCT SYSTEM LEAKAGE IS MINIMIZED, ETC. MEASURE

AND RECORD ALL AIR MOVING EQUIPMENT, AIR INLETS AND OUTLETS STATIC

PRESSURES, RPM'S, ETC.

WATER SYSTEMS VERIFY THAT SYSTEMS ARE COMPLETE AND OPERABLE BEFORE

COMMENCING WORK. VERIFY SYSTEMS ARE STARTED AT A SAFE AND NORMAL

OPERATION, TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND

OPERABLE, PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL

EQUIPMENT, HYDRONIC SYSTEMS ARE FLUSHED, FILLED AND VENTED, PUMPS ARE

ROTATING CORRECTLY, PROPER STRAINER BASKETS ARE CLEAN AND IN PLACE,

SERVICE AND BALANCE VALVES ARE OPEN, ETC. ADJUST WATER SYSTEMS TO

PROVIDE REQUIRED OR DESIGN QUANTITY AND TO PROVIDE SPECIFIED OR

SCHEDULES PRESSURE DROPS AND FLOWS THROUGH EQUIPMENT, COILS, ETC.

ADJUST FLOWS BY MEANS OF BALANCING COCKS, VALVES AND FITTINGS.

DIFFUSER AND GRILLE SCHEDULE

TYPE A: HEAVY DUTY SUPPLY AIR REGISTER: PRICE #152L DOUBLE DEFLECTION AIR FOIL BLADE

SUPPLY AIR REGISTER, ALL EXTRUDED ALUMINUM CONSTRUCTION, INDIVIDUALLY

ADJUSTABLE BLADES, FRONT BLADE, TO BE PARALLEL TO THE REGISTER LONG DIMENSION,

BAKED-ON WHITE ENAMEL FINISH. FURNISH FRAME AND MOUNTING HARDWARE ARE AS

NECESSARY FOR CEILING TYPE OR DIRECT DUCT MOUNT. SEE DRAWINGS FOR SIZES.

TYPE B: HEAVY DUTY WALL RETURN OR EXHAUST AIR GRILLE: PRICE 91DL(91DS) (96DL OR DS FOR

CONCEALED SCREWS) OR EQUAL CARNES OR T&B WALL RETURN OR EXHAUST GRILLE, ALL

STEEL CONSTRUCTION, BAKED-ON ENAMEL FINISH WITH COLOR BY ARCHITECT. ONE SET OF

HORIZONTAL BLADES SET AT 35 DEGREES. FURNISH OPPOSED BLADE DAMPER WITH BLACK

FINISH. IF GRILLE SIZE REQUIRES 2 OR MORE SECTIONS, DECREASE WIDTH OF TRIM AT JOINT

AS MUCH AS POSSIBLE. [48” MAXIMUM DIMENSION FOR SINGLE SECTION]

ROOFTOP UNIT SCHEDULE

RTU-1,2,

4 & 5: TRANE PRECEDENT #TYSC092 GAS/ELECTRIC 7.58 TON HORIZONTAL ROOFTOP UNIT. 3000 CFM

AT .50” EXTERNAL STATIC PRESSURE, 3 H.P., 460V-3PH, 21 MCA, 25 AMP MAXIMUM CIRCUIT

BREAKER.

COOLING PERFORMANCE: 94,800 BTUH GROSS COOLING CAPACITY, 90,000 BTUH ARI NET

COOLING CAPACITY. 80/67F EDB/EWB,F LWB, 2 SCROLL COMPRESSORS. R-410A REFRIGERANT

11.2 EER.

HEATING PERFORMANCE: 200,000 BTUH NATURAL GAS INPUT, 140,000 BTUH OUTPUT.

RTU-3: TRANE PRECEDENT #TYSC060 GAS/ELECTRIC 5 TON HORIZONTAL ROOFTOP UNIT. 1950 CFM

AT .50” EXTERNAL STATIC PRESSURE, 1.5 H.P., 460V-3PH,14 MCA, 20 AMP MAXIMUM CIRCUIT

BREAKER.

COOLING PERFORMANCE: 60,000 BTUH GROSS COOLING CAPACITY, 58,500 BTUH ARI NET

COOLING CAPACITY. 80/67F EDB/EWB, 1 SCROLL COMPRESSOR. R-410A REFRIGERANT.

HEATING PERFORMANCE: 150,000 BTUH NATURAL GAS INPUT, 105,000 BTUH OUTPUT.

RTU NOTES:

1. THE MECHANICAL TRADE SHALL VERIFY UNIT CONFIGURATION (HORIZONTAL OR DOWNFLOW)

WITH SCHEDULE LISTED ABOVE AND PROJECT DESIGN DRAWINGS.

2. UNITS SHALL HAVE REFERENCE ENTHALPY BASED ECONOMIZERS WITH POWER RELIEF EXHAUST

FAN AND LOW AMBIENT CONTROL FOR OPERATION IN 0 DEGREES F AMBIENT CONDITION.

3. FURNISH PREFABRICATED ROOF CURB FOR EACH UNIT, WITH HEIGHT OF CURB TO GIVE

MINIMUM 12” CLEAR FROM FINISHED CONCRETE SLAB. THE MECHANICAL TRADE SHALL FURNISH

AND SET IN PLACE/LEVEL THE CURB.

4. ALL UNITS SHALL HAVE 4” THICK HIGH EFFICIENCY THROW AWAY FILTERS.

5. OUTSIDE AIR INTAKE DAMPERS SHALL BE ULTRA LOW-LEAK TYPE WITH BLADE AND JAMB SEALS.

6. MOTORS SHALL BE PREMIUM EFFICIENCY TYPE.

7. EACH RTU TO HAVE:

A. SERVICE VALVES ON LIQUID, SUCTION AND DISCHARGE LINES.

B. THRU-THE-BASE ELECTRICAL PROVISION.

C. NON-FUSED DISCONNECT SWITCH WITH EXTERNAL HANDLE.

D. TRANE COMMUNICATION INTERFACE WITH SUPPLY AIR SENSING AND CLOGGED FILTER SWITCH.

E. VENTILATION OVERRIDE.

F. HINGED SERVICE ACCESS.

G. CONDENSER COIL GUARDS.

H. SLOPED STAINLESS STEEL DRAIN PANS.

8. ALL UNITS SHALL HAVE DRY CONTACTS FOR DUCT SMOKE DETECTOR CIRCUIT FACTORY WIRED

TO STOP UNIT UPON DETECTION OF SMOKE. TWO DUCT SMOKE DETECTORS FOR EACH RTU AND

REMOTE WIRING FURNISHED BY ELECTRICAL TRADES. SENSING TUBES FOR DUCT SMOKE

DETECTORS SHALL BE INSTALLED BY MECHANICAL TRADES. THE DUCT SMOKE DETECTORS

SHALL BE POWERED FROM AN INDEPENDENT CIRCUIT AND NOT THROUGH THE RTU POWER

CIRCUIT.

(WITH NO FIRE ALARM) ALL UNITS SHALL HAVE DRY CONTACTS FOR DUCT SMOKE DETECTOR

CIRCUIT FACTORY WIRED TO STOP UNIT UPON DETECTION OF SMOKE. TWO DUCT SMOKE

DETECTORS FOR EACH RTU AND REMOTE WIRING FURNISHED BY MECHANICAL TRADES.

MECHANICAL TRADES SHALL BE RESPONSIBLE FOR POWER AND CONTROL WIRING TO DUCT

SMOKE DETECTORS AND SHALL POWER THE DUCT SMOKE DETECTORS THROUGH AN

INDEPENDENT CIRCUIT AND NOT THROUGH THE RTU POWER CIRCUIT. SENSING TUBES FOR DUCT

SMOKE DETECTORS SHALL BE INSTALLED BY MECHANICAL TRADES.

9. THE MECHANICAL TRADES SHALL BE RESPONSIBLE FOR COMPLETING ALL LOW-VOLTAGE WIRING, CONDUIT, AND ASSOCIATED POWER SUPPLY NECESSARY FOR A COMPLETE AND OPERATIONAL

TEMPERATURE CONTROL SYSTEM. REFER TO THE ELECTRICAL DRAWINGS FOR AVAILABLE 120

VOLT POWER LOCATIONS. THE ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR PROVIDING THE

MAIN POWER FEED FOR ALL MECHANICAL EQUIPMENT. REFER TO THE ELECTRICAL DRAWINGS

FOR CLARIFICATION OF ELECTRICAL TRADES FURNISHED POWER.

10. FURNISH 5 YEAR COMPRESSOR WARRANTY FOR ROOFTOP UNITS.

11. FURNISH ONE YEAR OF COMPLETE SERVICE AND MAINTENANCE OF ROOFTOP UNITS. INCLUDE

CHECK TEST AND START-UP OF ROOFTOP UNITS AND CONTROL SYSTEM. PROVIDE FACTORY AND

FIELD WIRING DIAGRAMS, AND PROVIDE TECHNICAL ASSISTANCE AS REQUIRED TO ASSURE FIRST

CLASS OPERATING SYSTEMS.

12. FURNISH TRANE COMMUNICATION INTERFACE SYSTEM (FOR EACH UNIT).

GENERAL MECHANICAL NOTES

1. THE MECHANICAL TRADES SHALL FAMILIARIZE THEMSELVES WITH ALL EXISTING AND NEW

CONDITIONS, THESE DRAWINGS, ADDENDA & RELATED SPECIFICATIONS. THEY SHALL

COMPLETELY SATISFY THEMSELVES AS TO THE CONDITIONS TO WHICH THE WORK IS TO BE

PERFORMED BEFORE SUBMITTING THEIR BID. NO ALLOWANCES OR CONSIDERATIONS WILL BE

GIVEN AT A LATER DATE FOR ALLEGED MISUNDERSTANDINGS AS TO THE REQUIREMENTS OF THE

WORK, MATERIALS TO BE FURNISHED, OR CONDITIONS REQUIRED BY THE NATURE OF THIS

PROJECT SITE DUE TO NEGLECT ON THE BIDDERS PART TO MAKE SUCH AN EXAMINATION AND

COORDINATION.

2. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW APPROXIMATE LOCATION AND

GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. DRAWINGS SHALL NOT BE SCALED FOR

LOCATION OF SYSTEMS, EQUIPMENT, ETC. ALL LOCATIONS OF SYSTEMS AND EQUIPMENT SHALL

BE VERIFIED IN FIELD AND COORDINATED WITH ALL OTHER TRADES AND EXISTING FIELD

CONDITIONS. SOME SYSTEMS (PIPING, DUCTWORK, ETC.) AND EQUIPMENT LOCATIONS MAY

REQUIRE CHANGES IN LOCATION DUE TO FIELD CONDITIONS AND COORDINATION WITH OTHER

TRADES. THESE CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER. FAILURE

TO VERIFY AND COORDINATE WILL BE NO REASON FOR ADDITIONAL COMPENSATION.

3. THE INSTALLATION OF ALL SYSTEMS, EQUIPMENT, ETC., IS SUBJECT TO CLARIFICATION WITH

SUBMITTED SHOP DRAWINGS AND FIELD COORDINATION REQUIREMENTS. EQUIPMENT OUTLINES

SHOWN ON DRAWINGS OR DIMENSIONED ON DRAWINGS ARE LIMITING DIMENSIONS. ANY

EQUIPMENT THAT REDUCES THE INDICATED CLEARANCES OR EXCEEDS SPECIFIED OR

SCHEDULED EQUIPMENT DIMENSIONS SHALL NOT BE USED.

4. THE MECHANICAL CONTRACTOR SHALL COORDINATE FINAL LOCATION OF ALL EQUIPMENT WITH

PIPING, DUCTWORK, ETC., AT THE TIME OF ROUGH-IN. ALL EQUIPMENT TO BE SERVICEABLE.

5. THESE DRAWINGS AND THE ASSOCIATED SPECIFICATIONS ARE INTENDED TO PROVIDE

COMPLETELY FURNISHED, INSTALLED AND OPERATIONAL MECHANICAL SYSTEM (HEATING,

VENTILATING, AIR CONDITIONING, AND PIPING, ETC.). IF THESE DRAWINGS AND ASSOCIATED

SPECIFICATIONS HAVE INFORMATION OMITTED THAT WOULD NOT ALLOW A COMPLETELY

OPERATIONAL SYSTEM AS IS THE INTENT OF THE ENGINEER, THE BIDDER SHALL NOTIFY THE

ENGINEER A MINIMUM ONE WEEK PRIOR TO THE BID DATE TO ALLOW FOR ADDENDA. ONCE BIDS

HAVE BEEN RECEIVED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIAL, LABOR,

ETC., TO FURNISH AND INSTALL A COMPLETELY OPERATIONAL MECHANICAL SYSTEM AS IS THE

INTENT OF THESE DRAWINGS AND ASSOCIATED SPECIFICATION. ALL EQUIPMENT SHALL BE

INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IF ANY DISCREPANCIES ARE ON DRAWINGS,

AS COMPARED TO MANUFACTURER'S INSTALLATION INSTRUCTIONS, THE CONTRACTOR SHALL

NOTIFY THE ENGINEER AND INSTALL EQUIPMENT AS REQUIRED AT NO ADDITIONAL COST TO THE

PROJECT.

6. THE MECHANICAL TRADES SHALL TAKE OUT ALL PERMITS AND ARRANGE FOR NECESSARY

INSPECTIONS AND SHALL PAY ALL FEES AND COSTS.

7. THE MECHANICAL TRADES SHALL VERIFY AMOUNT OF EXISTING PIPING, VALVES, DUCTWORK, ETC.

TO BE REMOVED OR RELOCATED TO ALLOW FOR INSTALLATION OF NEW PIPING, DUCTWORK,

VALVES, EQUIPMENT, WALLS, ETC.

8. THE MECHANICAL TRADES SHALL COORDINATE ALL WORK WITH OTHER TRADES AND SHALL

COORDINATE ANY SYSTEMS SHUT-DOWN WITH THE ARCHITECT/ENGINEER AND OWNER.

9. ALL EXISTING EQUIPMENT, PIPING, DUCTWORK, ETC. THAT IS TO BE REMOVED SHALL REMAIN THE

PROPERTY OF THE OWNER. THE CONTRACTOR SHALL REMOVE AND LOCATE THIS MATERIAL THAT

REMAINS THE PROPERTY OF THE OWNER TO A LOCATION DETERMINED BY THE OWNER

SOMEWHERE ON SITE. IF THE OWNER DOES NOT WANT TO MAINTAIN POSSESSION OF THE

REMOVED MATERIAL, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING MATERIAL

FROM THE SITE AND DISPOSING OF THIS MATERIAL AS NECESSARY TO MEET ALL CODES AND

REQUIREMENTS AND SHALL PAY ALL COSTS AS REQUIRED FOR ANY DISPOSAL FEES,

INSPECTIONS, PERMITS, ETC.

10. ATTACHMENTS OF MECHANICAL OR ELECTRICAL EQUIPMENT TO STRUCTURAL MEMBERS ARE

THE RESPONSIBILITY OF THE INSTALLING TRADE. STRUCTURAL MEMBERS SHALL NOT BE FIELD

CUT, WELDED OR OTHERWISE MODIFIED WITHOUT APPROVAL OF THE ARCHITECT/ENGINEER.

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

EAB

E1.01

FLOOR PLAN

ELECTRICAL DEMOLITION

FLOOR PLAN - ELECTRICAL DEMOLITION

NORTH

JB

8 T

CHECKED BY

SHEET TITLE

PROJECT TITLE

COPYRIGHT 2019

C

Saginaw, Michigan 48607

989 752 8107

100 S Jefferson Ave, Suite 601

WTAARCH.COM

ARCHITE SCT

61220

INDEX NO.

472/16319.JAG

FILE NO.

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

EAST FOOD SERVICE BUILDING FOR:

CENTRAL MICHIGAN

CORRECTIONAL FACILITY

ST. LOUIS, MICHIGAN

2016094.2

AUGUST, 2019

RENOVATIONS TO

DATENO. REVISION

EAB

E1.02

FLOOR PLAN

ELECTRICAL REVISIONS

FLOOR PLAN - ELECTRICAL REVISIONS

NORTH

2 2

T

JB

JB

AD.01-2016094.2 _RD
A2.01-2016094.2_RD
A2.02-2016094.2 _RD
2019.11.14 Visitor Center Renovations Central Michigan MDOC Facility Bulletin No.3
2016-1558-M-M1.01-FSB-DEMO
2016-1558-M-M1.01-FSB-DEMO-Model
LIMITS
2016-1558-M-M1.02-FSB-HVAC
2016-1558-M-M1.02-FSB-HVAC-Model
LIMITS
2016-1558-M-M1.03-FSB-DET
2016-1558-M-M1.03-FSB-DET-Model
LIMITS
2016-1558-M-M1.04-FSB-SPECS
2016-1558-M-M1.04-FSB-SPECS-Model
LIMITS
2016-1558-E1.01-ELEC-MECH RM
2016-1558-E-E1.01-FSB-DEMO BULL 3
2016-1558-E-E1.01-FSB-DEMO BULL 3-Model
LIMITS
2016-1558-E-E1.02-FSB-ELEC REVISIONS BULL 3
2016-1558-E-E1.02-FSB-ELEC REVISIONS BULL 3-Model
LIMITS
Food Service
BL3.3 dwg
2016-1558-M-M1.02-FSB-HVAC-Model
LIMITS
M102
2016-1558-M-M1.02-FSB-HVAC-Model
LIMITS

File details come from the government source that posted it. Updated .