NFEA.org
RESPONSIBLE PARTY
US Department Of Transportation
NAME TITLE COMPANY OR DBA
MAILING ADDRESS
TESTING SITE ADDRESS
(617) 494-3029
PHONE
SITE PHONE OR FAX
OCCUPANCY TYPE NUMBER OF STORIES YEAR BUILT CONSTRUCTION TYPE SQUARE FOOTAGE
INSPECTION DETAILS
DATE
Fire Escape Engineers
INSPECTION COMPANY PHONE
19 Wesley Park Somerville MA 02143
INSPECTION COMPANY ADDRESS
I HEREBY CERTIFY THAT TO THE BEST OF MY KNOWLEDGE, INFORMATION AND BELIEF THE FIRE PROTECTION EQUIPMENT IS OR WAS 1) FABRICATED AS PER BUILDING CODE (PAST OR PRESENT) 2) PROFESSIONALLY INSTALLED AS PER CODE (PAST OR PRESENT) 3) HAS BEEN MAINTAINED AS PER CODE (PAST OR PRESENT) AND HAS BEEN FULLY TESTED IN ACCORDANCE WITH STATE AND FEDERAL FIRE/BUILDING CODES AND THAT THE RESULTS ARE ACCURATELY LISTED
ABOVE AND THAT THE EQUIPMENT IS FULLY OPERABLE EXCEPT AS NOTED.
Cisco Meneses INSPECTOR'S NAME & CERTIFICATE NUMBER INSPECTOR'S SIGNATURE FIRE DEPARTMENT WITNESS (SIGNATURE & ASSIGNMENT)
REPAIR AND RETEST: IF DEFECTS ARE FOUND IN THE FIRE ESCAPE SYSTEM TESTED, CORRECTION ON SUCH DEFECTS SHALL COMMENCE FORTHWITH WITH REQUIRED ENGINEER OVERSIGHT AND PERMITS (IF NEEDED) AND SHALL BE COMPLETED AS SOON AS POSSIBLE, BUT IN EVERY CASE WITHIN 30 DAYS OF INITIAL CONFIDENCE TEST. AT THE COMPLETION OF REPAIR, THE FIRE ESCAPE SYSTEM SHALL BE LOAD TESTED OR CERTIFIED REFURBISHED IN LIEU OF LOAD TEST BY ENGINEER.
ENGINEER'S NAME & CERTIFICATE NUMBER ENGINEER'S SIGNATURE BUILDING DEPARTMENT WITNESS (SIGNATURE & ASSIGNMENT)
RETURN WITHIN 7 TO 10 DAYS TO:
INSPECTOR PERMIT NUMBER PHONE INSPECTOR ASSIGNMENT DATE
INTERNATIONAL FIRE CODE: TESTING AND CERTIFICATION: ANY FIRE ESCAPE SYSTEM FOUND IN A STATE OF DETERIORATION OR UNSAFE SHALL BE REPAIRED IMMEDIATELY. DEPENDING UPON STRUCTURAL CONDITION, A LOAD TEST SHALL BE CONDUCTED.
NFPA LIFE SAFETY CODE 101 7.2.8.6.2 : THE AUTHORITY HAVING JURISDICTION SHALL BE PERMITTED TO APPROVE ANY EXISTING FIRE ESCAPE STAIR THAT HAS BEEN SHOWN BY LOAD TEST OR OTHER SATISFACTORY EVIDENCE TO HAVE ADEQUATE STRENGTH.
INTERNATIONAL BUILDING CODE: TESTING & CERTIFICATION: ALL EXTERIOR FIRE ESCAPE SYSTEMS SHALL BE EXAMINED & OR TESTED (SPOT REPAIRED THEN LOAD TESTED) AND/OR CERTIFIED FOR STRUCTURAL ADEQUACY AND SAFETY (FULLY REFURBISHED IN LIEU OF LOAD TEST) .
FIRE DEPARTMENT NOTIFICATION (2 FULL WORKING DAYS PRIOR TO TESTING.)
EQUIPMENT INSPECTED
NOTIFICATION DATE
800-649-3333 info@fireescapeengineers.com info@fireescapeengineers.com
INSPECTION RESULTS Certifiable Emergency Repairs Required Repairs Required Replace
Cisco Meneses
INSPECTOR'S NAME & CERTIFICATE NUMBER
DATE ENGINEER COMPANY PHONE
ENGINEER COMPANY ADDRESS EMAIL
Sgt Messerschmidt Rd Oakdale PA 15071
N/A
GOOD
FAIR
POOR
MISSING
OVERALL TREADS STRINGERS RAILS STRUCTURAL CEMENT GRATING LADDER CANTILEVERPAINT CATWALK
EXCELLENT
FIRE ESCAPE SYSTEM HAS FAILED THE INITIAL CONFIDENCE TEST AND CANNOT BE LOAD TESTED UNTIL SPOT REPAIRS ARE MADE. A FULL REFURBISHMENT IN LIEU OF LOAD TEST IS ACCEPTED BY THE
FIRE/CODE OFFICIAL.
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
THE FIRE ESCAPE IS OR HAS BEEN MAINTAINED AND PAINTED SINCE INSTALLATION. (MINOR SURFACE RUST OF NOT MORE THAN 25% ON NON CRITICAL AREAS ALLOWED)
THERE ARE NO OBSTRUCTIONS LEADING TO, ON OR FROM THE FIRE ESCAPE (AC UNITS, WINDOW GUARDS, PLANTS, SATELLITE DISHES, ETC.)
ALL ACCESS DOORS AND/OR WINDOWS ARE OPENABLE FROM THE INSIDE. MUST BE SINGLE ACTION, WITHOUT THE USE OF A KEY OR
SPECIAL KNOWLEDGE.
ALL WINDOWS HAVE MINIMUM OPENING OF 29" HEIGHT AND 29" WIDTH WITH SILLS NO MORE THAN 30" FROM FLOOR OR HAS INSIDE STEPS.
THERE ARE NO ELECTRICAL LINES OR OTHER HAZARDS ON OR WITHIN 10 FEET OF THE FIRE ESCAPE UNLESS PROTECTED AND APPROVED BY
APPROPRIATE OFFICIAL. (AC UNITS, ELECTRICAL MOTORS, FLAG POLES, GAS LINES, ETC.)
EXIT SIGNS AND LIGHTING TO AND ON THE FIRE ESCAPE ARE FUNCTIONING AS REQUIRED BY CODE AS PER DATE OF INSTALLATION.
ALL EGRESS WINDOWS ARE IDENTIFIED WITH STICKERS NO SMALLER THAN 3"X3" STATING IT IS AN EGRESS WINDOW, NOT TO BE BLOCKED BY
WINDOW GUARDS, AC UNITS OR PLANTS.
A SIGN IS PERMANENTLY POSTED ON OR NEAR THE FIRE ESCAPE AT GRADE AND IS EASILY READ BY ANYONE WHO MAY USE THE FIRE ESCAPE FOR MAINTENANCE AND/OR EMERGENCY EVACUATION (7 FOOT MAXIMUM HEIGHT FROM GRADE). THE SIGN IS MADE OF PLASTIC 8.5"X11"AND RED IN COLOR WITH "DO NOT REMOVE" THEN DATE OF LAST TEST, INSPECTOR'S NAME, LICENSE NUMBER, COMPANY AND CONTACT INFORMATION.
WHERE APPLICABLE THE FOLLOWING COMPONENTS (ORIGINAL, REFURBISHED, MODIFIED AND/OR REPLACED) ARE INTACT, FREE OF ALL INTERNAL RUST/ROT AND MEET OR EXCEED LOAD REQUIREMENTS AS PER CODE ON DAY OF INSTALLATION. ALL MATERIALS ARE NON - COMBUSTIBLE AND/OR MATCH BUILDING TYPE (WOOD 2 INCH MINIMUM).
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
ALL ANCHORING DEVICES TO BUILDING AND/OR MASONRY CONNECTIONS AT THE FIRE ESCAPE BASE ARE INTACT AND FREE OF ALL INTERNAL RUST/ROT:
1) THRU BOLTED WITH THREADED ROD AND BACKING PLATE INSIDE INTERIOR WALL ON ALL WOODEN STRUCTURES
2) CEMENTED INTO STRUCTURAL MASONRY WALL 8 TO 12 INCHES
3) SUPPORT LEGS TO GRADE ON CEMENT PIERS OR EQUIVALENT FOOTINGS
YES NO N/A
YES NO N/A
YES NO N/A
NAILS/SCREWS (WOOD)
MATERIALS (WOOD OR STEEL)
STAIRCASES
TREADS
RAILING
YES NO N/A GRATING/FLATS
LADDERS/CANTILEVERS
SUPPORTS
PLATFORMS
STANDPIPE CONNECTIONS
EQUIPMENT INSPECTED
SITE ADDRESSDATE
Cisco Meneses
INSPECTOR
CANTILEVERS AND LADDERS ARE BALANCED AND OPERATIONAL; DROPPED AND STAYED DOWN AT GRADE WHEN ACTIVATED AND/OR RELEASED REQUIRING NO SPECIAL KNOWLEDGE AND ALLOWS FOR UNRESTRICTED ACCESS TO A PUBLIC WAY. RELEASE WAS ATTEMPTED TWICE.
(NO ENCLOSED COURTYARDS OR LOCKED FENCING ETC.)
ALL CATWALKS AND WALKWAYS ARE CONTINUOUS OVER ROOFS FROM FIRE ESCAPE TO PUBLIC WAY OR CROSSES FIRE WALL TO SEPARATE BUILDING
OR AREA OF REFUGE. (MUST BE NON - COMBUSTIBLE AND/OR MATCH BUILDING TYPE)
ANY AND ALL WORK PERFORMED WAS OR WILL BE DONE UNDER PERMIT BY LICENSED VENDORS AND ALL LIFE SAFETY ISSUES WERE OR WILL BE REPORTED TO APPROPRIATE OFFICIALS.
BOLTS/RIVETS
WELDS
CONNECTIONS
CONNECTORS
JOINTS/PLATES
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A
YES NO N/A YES NO N/A YES NO N/A
OVERALL: THE FIRE ESCAPE SYSTEM WAS FOUND IN POOR CONDITION DUE TO LACK OF REQUIRED MAINTENANCE (STRUCTURAL) AND DETERIORATION (PAINT). THIS FIRE ESCAPE SYSTEM HAS MULTIPLE CONNECTION FAILURES DUE TO INTERNAL RUST GROWTH. THE SUPPORT CONNECTIONS TO THE BUILDING WALL - CEMENT OR THRU-BOLT ARE UNVERIFIED AND REQUIRE INTERNAL AND/OR EXTERNAL VERIFICATION OR DUPLICATION. THE FIRE OR CODE OFFICIAL REQUIRES THAT THIS SYSTEM BE SPOT REPAIRED AND THEN LIVE LOAD TESTED OR REFURBISHED WITH PERMIT (IF NEEDED) BUT UNDER ENGINEER OVERSIGHT TO
AVOID HAVING TO BE LIVE LOAD TESTED.
NFPA LIFE SAFETY CODE 101 7.2.8.6.2: THE AUTHORITY HAVING JURISDICTION SHALL BE PERMITTED TO APPROVE ANY EXISTING FIRE ESCAPE SYSTEM THAT HAS BEEN SHOWN BY LOAD TEST OR OTHER SATISFACTORY EVIDENCE TO HAVE ADEQUATE STRENGTH
EPA PAINT GUIDELINES APPLY TO ALL FIRE ESCAPE SYSTEMS OLDER THAN 1978, PRESUMED TO HAVE LEAD PAINT. EPA RENOVATORS LICENSE IS REQUIRED BY ALL VENDORS. ALL REPAIRS MUST BE SPOT PRIMED AND SEALED WITH SILICONE.
APPROVAL OR VERIFICATION OF REPAIRS BY OFFICIAL OR ENGINEER MAY BE REQUIRED PRIOR TO FINAL PAINT AND SUBSEQUENT LIVE LOAD TEST OR CERTIFIED REFURBISHMENT IN LIEU OF LIVE LOAD TEST. ALL VENDORS BIDDING THIS PROJECT MUST HAVE LICENSES, WORKMAN'S COMPENSATION & LIABILITY INSURANCE, AS WELL AS FIRE ESCAPE REFERENCES.
DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :
DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :GENERAL NOTES
STRUCTURAL NOTES
STRUCTURAL REVIEW ALL DEFECTS/VIOLATIONS MUST BE IDENTIFIED ON THE FIRE ESCAPE WITH SPRAY PAINT OR IN A DETAILED DRAWING OF THE FIRE ESCAPE.
Fire Escape Engineers
INSPECTION COMPANY
YES NO N/A
GENERAL REVIEW
Sgt Messerschmidt Rd Oakdale PA 15071
IF THE INTERNAL CONNECTION OR BACKING PLATE CANNOT BE VISUALLY VERIFIED TO BE STRUCTURALLY SAFE THEN A NEW CONNECTION MUST BE INSTALLED OF EQUAL OR GREATER STRENGTH AT EACH AND EVERY UNVERIFIABLE CONNECTION.
SUPPORTS ARE NEVER LAG BOLTED INTO WOOD OR SLEEVE ANCHORED INTO MASONRY UNLESS SUPPORT LEGS TO GRADE AND ON CEMENT PIERS.
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
SITE ADDRESSDATE
EQUIPMENT INSPECTED
Cisco Meneses
INSPECTOR
IN LAYMAN’S TERMS, THE CITY OFFICIAL IS LOOKING FOR A QUALIFIED LICENSED REPAIR VENDOR TO DO ALL WORK UNDER REPAIR PERMIT (IF REQUIRED) WITH ENGINEER OVERSIGHT OF REPAIR CRITERIA SUBMITTED FOR APPROVAL TO THE OFFICIAL IN LIEU OF LIVE LOAD TEST. ALL CONNECTIONS MUST BE FREE OF INTERNAL RUST OR ROT, SPOT PRIMED AND SEALED. ALL WORN MATERIAL REPAIRED AND OR REPLACED. ALL SUPPORTS INTO WALL REINFORCED, REPAIRED AND CERTIFIED IN A FIRE ESCAPE CONFIDENCE TEST. IN LIEU OF LIVE LOAD TEST, ALL SQUARE HEAD BOLTS, RIVETS AND OR WELDED CONNECTIONS MUST BE CERTIFIED, REINFORCED AND OR REPLACED BASED ON AGE OR CONDITION. ALL LADDERS AND CANTILEVERS MUST BE BALANCED AND DROP 2-3 FT PER SECOND, HIT THE GROUND AND STAY DOWN AND MUST LEAD TO A PUBLIC WAY. ALL ROOF LADDERS MUST BE SECURE. NO FULL PAINTING OF ANY FIRE ESCAPE UNTIL ALL SPOT PAINTED REPAIRS ARE INSPECTED AND CERTIFIED UNDER ENGINEER OVERSIGHT AND OR CITY OFFICIAL PERMIT SIGN-OFF. FULL REPLACEMENT IS SUBJECT TO PERMITS AND OR POSSIBLE
CODE UPGRADE REQUIREMENTS.
NFPA LIFE SAFETY CODE 101 7.2.8.6.2: THE AUTHORITY HAVING JURISDICTION SHALL BE PERMITTED TO APPROVE ANY EXISTING FIRE ESCAPE SYSTEM THAT HAS
BEEN SHOWN BY LOAD TEST OR OTHER SATISFACTORY EVIDENCE TO HAVE ADEQUATE STRENGTH
DISCLAIMER: THIS IS A CRITICAL BUT LIMITED CURSORY VISUAL OBSERVATIONS OF VISIBLE AND OR IDENTIFIABLE SIGNS OF RUST, ROT, DETERIORATION OF MATERIALS (STEEL AND OR WOOD), RIVETS, BOLTS, SCREWS, WELDS, CONNECTORS, THRU-BOLT/CEMENT CONNECTION, FOOTINGS, BALANCED CANTILEVER OR LADDERS AND CATWALKS OVER ROOFS. THERE IS NO CLAIM, EITHER STATED OR IMPLIED THAT ALL CONDITIONS WERE OBSERVED, ACCESSIBLE OR ANALYTICALLY EVALUATED (CALCULATED OR LIVE LOAD TESTED). THIS VISUAL CONFIDENCE TEST ONLY CONFIRMS THAT TO THE BEST INFORMATION KNOWLEDGE, BELIEF AND
IN LAYMAN'S TERMS, THE CITY OFFICIAL IS LOOKING FOR A PAINT VENDOR (EPA CERTIFIED RENOVATOR IF REQUIRED) TO DO ALL WORK AS PER EPA GUIDELINES DUE TO THE FACT THAT ALL FIRE ESCAPES OLDER THAN 1978 ARE PRESUMED TO HAVE LEAD (EPA) UNLESS IDENTIFIED AS NO LEAD OR LOW LEAD BY A LICENSED LEAD INSPECTOR. ENTIRE BUILDING WILL BE NOTIFIED WITH SIGNAGE AND ALL PRECAUTIONS SHALL BE TAKEN TO COLLECT PAINT CHIPS AT GRADE. NO SANDBLASTING OR POWER ASSISTED SCRAPING WITHOUT FULL FIRE ESCAPE ENCAPSULATION UNDER EPA GUIDELINES. ALL MAJOR CONNECTION SHALL BE SEALED FROM WATER INTRUSION BEFORE DURING OR AFTER PAINTING. ALL ESCAPES SHOULD BE SPOT PAINTED EVERY 3-5 YRS AND FULLY PAINTED EVERY 5-10 YRS OR AS NEEDED OR ORDERED BY FIRE/CODE
OFFICIAL.
STEPS TO PASS FIRE ESCAPE AS PER CONVERSATIONS AND REVIEW WITH THE FIRE/CODE OFFICIAL.
1. ENGINEER OVERSIGHT FOR LOAD TEST OR CERTIFIED REFURBISHMENT
2. ALL VENDORS MUST BE APPROVED BY OFFICIAL OR PULL PERMITS IF NEEDED.
3. REPAIR CRITERIA OR LOAD TEST CRITERIA MUST BE APPROVED BY OFFICIAL.
PLEASE REVIEW ALL INFORMATION AND CALL FIRE ESCAPE ENGINEERS AS WELL AS YOUR LOCAL OFFICIAL
GENERAL NOTES
STRUCTURAL NOTES DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :
DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :
Fire Escape Engineers
INSPECTION COMPANY
Sgt Messerschmidt Rd Oakdale PA 15071
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
SITE ADDRESSDATE
EQUIPMENT INSPECTED
Cisco Meneses
INSPECTOR
LISTED BELOW ARE FIRE ESCAPE SYSTEM (FES) REPAIRS AND PAINTING STANDARDS FOR ALL FES REPAIR VENDORS.
1_LADDER TO ROOF: ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (TOP, BOTTOM) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50YR SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. LADDER CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD TEST IF
REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
2_PLATFORM RAIL(S): ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (POSTS, TIE BACKS) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50 SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. RAIL CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD
TEST IF REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
3_PLATFORM SUPPORTS: ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR EXTERNAL CRITICAL CONNECTIONS (GUSSETS, CONNECTIONS) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50YR SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. ALL INTERNAL MASONRY CONNECTIONS AND OR THRU-BOLTS W/PLATES WILL BE VERIFIED/DOCUMENTED (PHOTO) AND OR DUPLICATED WITH A NEW 3/4" EPOXY BOLT (8-12") AT EACH AND EVERY SUPPORT CONNECTION AND OR SUPPORTING BRACKET SYSTEMS. (LADDERS ASSEMBLIES, ETC.) SUPPORT CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD TEST IF REQUIRED BY THE FIRE
DEPT. AND OR CODE OFFICIAL.
4_STAIRCASE(S): ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (TOP HANGER, LOWER SHOE,RAILS) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50YR SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. STRINGER AND RAIL CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3
LIVE LOAD TEST IF REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
5_TREADS: ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (NOSING, ANGLE CLIPS ETC.) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50 SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. TREAD CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD
TEST IF REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
6_FIXED LADDERS: ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (RUNGS, WALL BRACKETS, ETC) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50YR SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. TREAD CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD
TEST IF REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
7_WEIGHT BALANCED CANTILEVER(S) AND OR LADDER(S): ALL ORIGINAL HARDWARE (BOLTS/RIVETS/WELDS), IDENTIFIED OR NOT ON ANY REPORT, AT MAJOR CRITICAL CONNECTIONS (PULLEYS,RUNGS, WALL BRACKETS, ETC) WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED W/50YR SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. 4 NEW LADDER SYSTEMS WITH WEIGHTS AND LOCK SYSTEM WILL BE DESIGNED AND ENGINEERED FOR SUBMITTAL TO CODE OFFICIAL DURING PERMIT REVIEW PROCESS FOR PLAN REVIEW WITH A FINAL APPROVED DRAWING TO FIRE ESCAPE ENGINEERS FOR OUR RECORDS. 2 ORIGINAL WEIGHTED LADDERS WILL BE RE-CABLED, NEW LOCK SYSTEM, NEW PIN WHEEL ASSEMBLIES (PULLEYS), SEALED WEIGHT BOXES AND STABILIZERS AT GRADE FOR LADDERS. CANTILEVER/LADDER CONSTRUCTION, STRENGTH AND MATERIALS WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD TEST IF
REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
8_MORTAR CONNECTIONS AND FOOTINGS: ALL STEEL IMPLEMENTS (MAJOR CRITICAL CONNECTIONS) INTO MASONRY BUILDINGS, IDENTIFIED OR NOT IN ANY REPORT, WILL BE VERIFIED AND PHOTO DOCUMENTED OR DUPLICATED WHICH EVER IS LESS EXPENSIVE TO THE CLIENT AS EXPLAINED IN SECTION 3. ALL RAILING TIE BACKS WILL BE REPAIRED, REINFORCED AND OR REPLACED, SCRAPED/WIRE BRUSHED, SPOT PRIMED AND SEALED MASONRY SILICONE AS PER CONTRACT AND OR INDUSTRY STANDARD. ALL FOOTINGS WILL BE FIELD VERIFIED AND OR MODIFIED TO MEET CODE. (48" BELOW GRADE) ALL FOOTING CONNECTIONS OF STEEL TO CONCRETE WILL BE WITH ANGLE CLIP AND SLEEVE ANCHOR. ALL IMBEDDED STEEL WILL BE MODIFIED WITH NEW ANCHOR CLIP. REMOVAL OF STEEL IN CONCRETE NOT REQUIRED BUT MUST BE SEALED WITH TAR TO AVOID FUTURE SPLITTING/SPAULING OF FOOTINGS. MORTAR CONNECTIONS AND FOOTINGS CONSTRUCTION, CEMENT STRENGTH AND SURROUNDING MATERIALS (BRICK, DIRT, ETC.) WILL BE REPAIRED, REINFORCED, REPLACED AND OR VERIFIED/DOCUMENTED BY VENDOR AS CERTIFIABLE TO ACCEPT A LEVEL 3 LIVE LOAD TEST IF REQUIRED BY THE FIRE DEPT. AND OR CODE OFFICIAL.
9._EPA PAINT GUIDELINES APPLY TO ALL FIRE ESCAPE SYSTEMS OLDER THAN 1978, PRESUMED TO HAVE LEAD PAINT. EPA RENOVATORS LICENSE IS REQUIRED BY ALL VENDORS.
ALL REPAIRS MUST BE SPOT PRIMED AND SEALED WITH SILICONE. APPROVAL OR VERIFICATION OF REPAIRS BY OFFICIAL OR ENGINEER MAY BE REQUIRED PRIOR TO FINAL PAINT AND SUBSEQUENT LIVE LOAD TEST OR CERTIFIED REFURBISHMENT IN LIEU OF LIVE LOAD TEST. ALL VENDORS BIDDING THIS PROJECT MUST HAVE LICENSES, WORKMAN'S COMPENSATION &
LIABILITY INSURANCE, AS WELL AS FIRE ESCAPE REFERENCES.
LETTERS&/ORATTACHMENTS DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :
Fire Escape Engineers
INSPECTION COMPANY
Sgt Messerschmidt Rd Oakdale PA 15071
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
SITE ADDRESSDATE
EQUIPMENT INSPECTED
Cisco Meneses
INSPECTOR
LETTERS&/ORATTACHMENTS DEFECTS, VIOLATIONS, RECOMMENDATIONS AND COMMENTS IN EQUIPMENT TESTED IN ADDITION TO OR NOT COVERED IN DETAILS ABOVE. PLEASE SUMMARIZE ATTACHED FULL REPORT IN THIS AREA :
Fire Escape Engineers
INSPECTION COMPANY
Sgt Messerschmidt Rd Oakdale PA 15071
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.