CASE NUMBER
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
N/A
EXCELLENT
GOOD
FAIR
POOR
MISSING
OVERALL TREADS STRINGERS RAILS STRUCTURAL CEMENT GRATING LADDER CANTILEVERPAINT CATWALK
INSPECTION RESULTS Certifiable Emergency Repairs Required Repairs Required Replace
The Fire Escape System has FAILED the Fire Escape Confidence Test (Visual Opinion Examination) and cannot be CERTIFIED AND OR LOAD TESTED at this time. OVERALL: The Fire Escape System was found in POOR condition due to lack of required routine maintenance (structural) and deterioration (paint). This fire escape system has multiple connection failures due to internal rust growth (corrosion) in connections and original hardware fasteners that are suspect due to their age (50-75 yrs). The support connections to the building wall - cement or thru-bolt are unverified and require internal and/or external verification or duplication.
Here are some violation issues we found on your system they are as follows:
1 Treads not fully Welded 2. Welded Connections 3. Original Hardware 4. Rusted angles 5. Cantilever needs balance and arm. 6 New suppports needs bolting due to welds.
Other Issues to be discussed during review.
FIRE ESCAPE REPAIR PROCEDURES & SPECIFICATIONS
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
FIRE ESCAPES: (1) MUST BE KEPT PAINTED (2) MUST BE STRUCTURLY SOUND
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
C11 CANTILEVER FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS
C12 CANTILEVER FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED
BY CODE TO PASS
C13 CANTILEVER FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
C14 CANTILEVER FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
C15 CANTILEVER FAILED
REPACK CEMENT AS REQUIRED BY CODE
C16 CANTILEVER FAILED
CANTILEVER STAIRS OUT OF BALANCE - DOES NOT DROP
PROPERLY REPAIR RELEASE ARM
C17 CANTILEVER FAILED
CANTILEVER STAIRS OUT OF BALANCE - DOES NOT DROP
PROPERLY REPLACE RELEASE ARM
E11 EGRESS FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS AT TOP OR BOTTOM STRINGER CLIP
E12 EGRESS FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED BY
CODE TO PASS
E13 EGRESS FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
E14 EGRESS FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
E15 EGRESS FAILED
LOOSE CEMENT AT FOOTING, REMOVE AND REPACK AS
REQUIRED BY CODE
E16 EGRESS FAILED
EXCESSIVE RUST AND OR MISSING METAL ON RAIL REINFORCE
AS REQUIRED BY CODE
E17 EGRESS FAILED
EXCESSIVE RUST AND OR MISSING METAL ON RAIL REPLACE
AS REQUIRED BY CODE
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
G11 GRATING FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE ANY
RUSTED THRU RODS
G12 GRATING FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED BY CODE
TO PASS
G13 GRATING FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
G14 GRATING FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS REQUIRED
BY CODE
G15 GRATING FAILED
LOOSE CEMENT, REMOVE AND REPACK AS REQUIRED BY CODE
L11 LADDER FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS
L12 LADDER FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED
BY CODE TO PASS
L13 LADDER FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
L14 LADDER FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
L15 LADDER FAILED
LOOSE CEMENT AT FOOTING, REMOVE AND REPACK AS
REQUIRED BY CODE
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
S11 SUPPORT FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR
REINFORCE ANY RUSTED BOLTS
S12 SUPPORT FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS
REQUIRED BY CODE TO PASS
S13 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE
AS REQUIRED BY CODE
S14 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
S15 SUPPORT FAILED
REPACK CEMENT AS REQUIRED BY CODE
R11 RAIL FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS AT TOP OR BOTTOM STRINGER CLIP
R12 RAIL FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED BY
CODE TO PASS
R13 RAIL FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
R14 RAIL FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
R15 RAIL FAILED
LOOSE CEMENT AT FOOTING, REMOVE AND REPACK AS
REQUIRED BY CODE
R16 RAIL FAILED
EXCESSIVE RUST AND OR MISSING METAL ON RAIL REINFORCE
AS REQUIRED BY CODE
R17 RAIL FAILED
EXCESSIVE RUST AND OR MISSING METAL ON RAIL REPLACE
AS REQUIRED BY CODE
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
S21 SUPPORT FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS
S22 SUPPORT FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED
BY CODE TO PASS
S23 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
S24 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
S25 SUPPORT FAILED
REPACK CEMENT AS REQUIRED BY CODE
S31 SUPPORT FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR
REINFORCE ANY RUSTED BOLTS
S32 SUPPORT FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS
REQUIRED BY CODE TO PASS
S33 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
S34 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
S35 SUPPORT FAILED
REPACK CEMENT AS REQUIRED BY CODE
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
S41 SUPPORT FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS
S42 SUPPORT FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED
BY CODE TO PASS
S43 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
S44 SUPPORT FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
S45 SUPPORT FAILED
REPACK CEMENT AS REQUIRED BY CODE
T11 TREAD FAILED
EXCESSIVE RUST: REMOVE RUST, REPLACE OR REINFORCE
ANY RUSTED BOLTS
T12 TREAD FAILED
EXCESSIVE RUST: SCRAPE, PRIME & PAINT AS REQUIRED
BY CODE TO PASS
T13 TREAD FAILED
EXCESSIVE RUST AND OR MISSING METAL REINFORCE AS
REQUIRED BY CODE
T14 TREAD FAILED
EXCESSIVE RUST AND OR MISSING METAL REPLACE AS
REQUIRED BY CODE
T15 TREAD FAILED
LOOSE CEMENT AT FOOTING, REMOVE AND REPACK AS
REQUIRED BY CODE
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
TREADS : ALL CLIP ANGLE CONNECTIONS OF EACH TREAD MUST BE 100%
FREE OF RUST BEFORE RE-BOLTING. ALL TOP BOLTS MUST BE 100% FREE
OF RUST. RE-BOLT, REINFORCE OR REPLACE ENTIRE TREAD IF REQUIRED.
(REPAIR BY WELDING OPTIONAL, BUT MUST HAVE FIRE DETAIL PERMIT ON
SITE.) TREAD CLIP AND STRINGER SURFACES MUST BE FREE OF RUST AND
WIRE BRUSHED. ALL CONNECTIONS MUST BE SILICON SEALED (50 YEAR
SILICONE) AFTER REPAIR. ALL FIRE ESCAPE SURFACES MUST BE PAINTED
WITH PRIMER THEN PAINTED.
SUPPORTS : ALL CONNECTIONS TO SUPPORTS MUST BE 100% RUST FREE
BEFORE RE-BOLTING. ALL GUSSET BOLTS MUST BE A MINIMUM OF 1/2" (4
PER GUSSET) OR 5/8" (SINGLE BOLT CONNECTION). ALL STRUCTURAL STEEL
COMPONENTS MUST BE A MINIMUM 2" X 2" X 1/4" ANGLE. ALL THRU BOLTS
MUST BE A MINIMUM OF 5/8" ROUND STEEL WITH 1/2" BACKING PLATE
EMBEDDED INSIDE WALL AND ANCHORED TO AT LEAST ONE WALL STUD. FIRE
ESCAPES MUST MEET THE MINIMUM LOAD CAPACITY OF 100 POUNDS PER
SQUARE FOOT. TO MEET THIS REQUIRED LOAD CAPACITY SUPPORTS MUST BE
NO GREATER THAN 54" APART. ALL STEEL COMPONENTS MUST BE
REINFORCED OR REPLACED IF RUSTED OR LESS THAN MINIMUM SIZE. (REPAIR
BY WELDING IS OPTIONAL BUT THERE MUST BE A FIRE DETAIL PERMIT ON
SITE.) ALL CONNECTIONS MUST BE SILICON SEALED (50 YEAR SILICONE)
AFTER REPAIR. ALL FIRE ESCAPE SURFACES MUST BE PAINTED WITH PRIMER
THEN PAINTED.
RAILS : ALL CONNECTIONS TO RAILINGS ON PLATFORMS AND STAIRS MUST
BE 100% RUST FREE BEFORE RE-BOLTING. ALL TOP AND BOTTOM RAILS AS
WELL AS THE BARS MUST BE 100% RUST FREE. ANY STEEL COMPONENT OF
LESS THAN MINIMUM THICKNESS MUST BE REINFORCED OR REPLACED.
(REPAIR BY WELDING IS OPTIONAL BUT THERE MUST BE A FIRE DETAIL
PERMIT ON SITE.) ALL CONNECTIONS MUST BE SILICON SEALED (50 YEAR
SILICONE) AFTER REPAIR. ALL FIRE ESCAPE SURFACES MUST BE PAINTED
WITH PRIMER THEN PAINTED.
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
GRATING : REPLACEMENT OF GRATING WITH NEW GALVANIZED STEEL
GRATING IS RECOMMENDED. ALL GRATING MUST BE 100% RUST FREE. ALL
1" SEPARATORS MUST BE REINFORCED AS REQUIRED. GRATING MUST BE J-
BOLTED TO SECURE PROPERLY. (REPAIR BY WELDING IS OPTIONAL BUT
THERE MUST BE A FIRE DETAIL PERMIT ON SITE.) ALL CONNECTIONS MUST
BE SILICON SEALED (50 YEAR SILICONE) AFTER REPAIR. ALL FIRE ESCAPE
SURFACES MUST BE PAINTED WITH PRIMER THEN PAINTED.
CEMENT : ALL LOOSE CEMENT NEEDS TO BE REMOVED. HAMMER DRILL
WITH A 3/8 MASONRY BIT INTO CONNECTION TO REMOVE BROKEN CEMENT.
REPACK WITH FAST DRYING ANCHORING CEMENT. CLEAN AREA OF EXCESS
AND SEAL IF POSSIBLE.
PAINT : ENTIRE SURFACE AREA SHOULD BE CLEANED OF LOOSE RUST AND
DIRT (POWER WASH IF NEEDED). ALL LOOSE RUST MUST BE HAND SCRAPED
OR POWER BRUSHED OFF. ALL REPAIR AREAS MUST BE RUST FREE AND
PRIMED. ALL MAJOR AND IN SOME CASES MINOR CONNECTIONS SHOULD BE
SEALED WITH 50 YEAR SILICONE. ONE TOP COAT OF PAINT MUST BE APPLIED
BY HAND ROLLER (1’ SAUSAGE ROLLER).
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.
Cisco Meneses
INSPECTOR
Bob
(617) 494-3029
INSPECTION DATE
FIRST NAME
PHONE
robert.hallet@dot.govHallett
LAST NAMETM
©2012
Oakdale
CITY
Sgt Messerschmidt Rd
SITE ADDRESS
PA 15071
SUITE/APT STATE ZIP CODE
FULL STAIRS WITH PLATFORMS :
THE FIRE ESCAPE MUST BE MADE OF NON - COMBUSTIBLE MATERIALS AS REQUIRED
BY LAW AND MUST EGRESS TO GROUND USING STAIRS AND PLATFORMS WITHOUT
CROSSING TO NEIGHBOR'S PROPERTY AT ANY POINT. THERE MUST BE NO
OBSTRUCTION TO OR ON THE FIRE ESCAPE SUCH AS AIR CONDITIONERS, PLANTS OR
WINDOW GRATES (UNLESS WITH AN EMERGENCY RELEASE MECHANISM INSTALLED).
FULL STAIRS WITH CANTILEVER :
THE FIRE ESCAPE MUST BE MADE OF NON - COMBUSTIBLE MATERIALS AS REQUIRED
BY LAW AND MUST EGRESS TO GROUND USING STAIRS, PLATFORMS AND CANTILEVER
WITHOUT CROSSING TO NEIGHBOR'S PROPERTY AT ANY POINT. CANTILEVER MUST
HAVE RELEASE ARM AND BE BALANCED TO DROP DOWN WITH
NO ASSISTANCE. THERE MUST BE NO OBSTRUCTION TO OR ON THE FIRE ESCAPE
SUCH AS AIR CONDITIONERS, PLANTS OR WINDOW GRATES (UNLESS WITH AN
EMERGENCY RELEASE MECHANISM INSTALLED).
BALCONIES WITH LADDERS :
THE FIRE ESCAPE MUST BE MADE OF NON - COMBUSTIBLE MATERIALS AS REQUIRED
BY LAW AND MUST EGRESS TO GROUND USING BALCONIES AND LADDERS WITHOUT
CROSSING TO NEIGHBOR'S PROPERTY AT ANY POINT. THERE MUST BE NO
OBSTRUCTION TO OR ON THE FIRE ESCAPE SUCH AS AIR CONDITIONERS, PLANTS OR
WINDOW GRATES (UNLESS WITH AN EMERGENCY RELEASE MECHANISM INSTALLED).
CROSSOVER :
THE FIRE ESCAPE MUST BE MADE OF NON - COMBUSTIBLE MATERIALS AS REQUIRED
BY LAW AND MUST EGRESS TO GROUND USING CROSSOVERS TO CROSS OVER THE
FIRE WALL OF THE NEIGHBOR'S PROPERTY TO EVACUATE. THERE MUST BE NO
OBSTRUCTION TO OR ON THE FIRE ESCAPE SUCH AS AIR CONDITIONERS, PLANTS OR
WINDOW GRATES (UNLESS WITH AN EMERGENCY RELEASE MECHANISM INSTALLED).
CATWALK :
THE FIRE ESCAPE MUST BE MADE OF NON - COMBUSTIBLE MATERIALS AS REQUIRED
BY LAW AND THE CATWALK MUST BE PART OF A CONTINUOUS FIRE EGRESS SYSTEM
OVER THE ROOF AREA AND WITH FULL CONTROL OF PATH TO GROUND. AT NO TIME
CAN ANYONE TOUCH THE ROOF IN AN EMERGENCY EGRESS. THERE MUST BE NO
OBSTRUCTION TO OR ON THE FIRE ESCAPE SUCH AS AIR CONDITIONERS, PLANTS OR
WINDOW GRATES (UNLESS WITH AN EMERGENCY RELEASE MECHANISM INSTALLED).
TM
©2012
COPYRIGHT 2012 THIS REPORT AND ATTACHED DOCUMENTS ARE FOR THE EXPRESS PURPOSE OF SUMMARY NOTIFICATION TO APPROPRIATE FIRE DEPARTMENT, HOUSING OR CODE ENFORCEMENT OFFICIALS AND CANNOT BE USED BY OR FOR PRIVATE OR COMMERCIAL PURPOSES UNLESS PERMISSION IS GIVEN IN WRITING BY FIRE ESCAPE INSPECTIONAL SERVICES INC. FULL REPORTS MUST BE SUBMITTED ATTACHED TO THIS REPORT AND ON TESTING AGENCY'S LETTERHEAD.