Drawings_I_85 _ SR 74 Water Main Relocation.pdf
PDF 776 KB Posted
- Solicitation number
- PE-66073-NONST-2026-000000025
- Issued by
- Fulton County, Georgia
About this file
The documents are Utility Relocation Plans for the I-85 @ SR 7/Senoia Road Interchange Improvements project, prepared by the Georgia Department of Transportation (GDOT). The project involves comprehensive water main and utility infrastructure modifications across multiple parcels along SR 74, including relocating existing water lines, fire hydrants, water meters, and adjusting utility infrastructure to accommodate new storm drainage systems. The plans detail specific utility relocations and modifications at stations ranging from 109+00 to 137+00, with key work including installing new fire hydrants, cutting and capping existing water lines, and vertically realigning water mains to avoid conflicts with proposed storm drainage pipes.
The utility relocation plans demonstrate careful engineering to minimize service disruption, with detailed elevation data showing precise vertical and horizontal positioning of existing and proposed water mains, storm drainage pipes, and associated infrastructure. The documents include specific notes about mechanical joint restraints, concrete collar requirements, and coordination protocols with the water system for service disconnections. The project appears to be part of a larger interchange improvement initiative, with multiple commercial properties and businesses (including Chick-fil-A, McDonald's, Starbucks, and Tractor Supply) impacted by the infrastructure modifications. The plans are dated with a revision on 5/21/2024 and include comprehensive technical details to guide construction and utility relocation efforts.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Cost Sheet_I_85 _ SR 74 Water Main Relocation.xlsx | XLSX spreadsheet | |
| ITB 25_016 Fairburn Water Main Relocation Pro.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
44-0014
16" WATER MAIN THROUGHOUT CONSTRUCTION
CONTRACTOR TO MAINTAIN SERVICE IN
UTILITY RELOCATION PLANS
44-0014
I-85 @ SR 7/SENOIA ROAD
INTERCHANGE IMPROVEMENTS
M A T C
H L I
N E
S T
A
S E
D W
G
M A T
C H L I
N E
S T
A
S
G
O A
K L E
Y
I
N
B L
V D
O A
K L E
Y
I
V D
CONST CL SR 74
REVISION DATES
5/21/2024 ggsmith
GPLOT-V8
gplotborder-V8i-PO-color_0007841.tbl
0007841_44-0014.dgn
6:45:54 PM
GPLN10/23/2015
CHECKED:
BACKCHECKED:
CORRECTED:
VERIFIED:
DATE:
DATE:
DATE:
DRAWING No.
Project No.
0007841
EASEMENT FOR CONSTR
EASEMENT FOR CONSTR OF SLOPES
EASEMENT FOR CONSTR OF DRIVES
CONSTRUCTION LIMITS
& MAINTENANCE OF SLOPES
C F
REQUIRED R/W LINE
PROPERTY AND EXISTING R/W LINE PL
ORANGE BARRIER FENCE
LIMIT OF ACCESS
BEGIN LIMIT OF ACCESS............BLA
END LIMIT OF ACCESS..............ELA
REQ'D R/W & LIMIT OF ACCESS
(SEE ERIT TABLE)
ESA - ENV. SENSITIVE AREA
50 100 200
SCALE IN FEET
JB
CONCRETE
C O
N C
R E
T E
JB
JB
JB
INV OUT(E 24"RCP)=980.30
INV IN(W 24"RCP)=980.46
TOP=986.43
DOUBLE CATCH BASIN
JB
INV OUT(E 18"RCP)=981.87
TOP=987.04
DOUBLE CATCH BASIN
JB
JB
INV OUT(S-30"RCP)=984.03
INV IN(NW-30"RCP)=984.08
TOP=988.98
DOUBLE CATCH BASIN
JB
JB
C O
N C
R E
T E
LP
LP LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
A29
A30
A32
A31
A33
A34
A35
A36
A37
A38
A39
A40
A41
A42
A43
A44
A45 A46 A47
A48
A49
A50
B1
B2 B3
B4
B5 B6
B7 B8
B9
4# EVRUC
CONST CL SR 74
6+00
13+00
ON PARCEL 12
AND LIGHT POLE
COMMERCIAL SIGN
DO NOT DISTURB
ON PARCEL 22
HYDRANT, AND SIGNS
DO NOT DISTURB LIGHTS,
STORAGE TANKS ON PARCEL 23
VENT STACKS, & UNDERGROUND
DO NOT DISTURB PRICE SIGN,
PARCEL 24
AISLE AROUND THE CARWASH ON
CONCRETE, CURBING, AND DRIVE
CONTRACTOR SHALL NOT DISTURB
SIGNS (2) ON PARCEL 27
BUILDING AND COMMERCIAL
DO NOT DISTURB
ON PARCEL 9B
LIGHT POLE
COMMERCIAL
DO NOT DISTURB
ON PARCEL 20
METER & MONUMENT SIGN
DO NOT DISTURB WATER
9B
24 26
88' RT
STA.109+00.00(SR 74);
END L/A 9A
18" PIPE
PLUG EXIST
TO REMAIN
EXISTING 30" RCP
AT BOTH ENDS - GA STD 9031U
INSTALL CONCRETE COLLARS
TO REMAIN
EXISTING 24" RCP
TO REMAIN
EXISTING 15" PVC
TO REMAIN
EXISTING 24" RCP
PB
PB
PB
PB
PB
PB
PB
P B
P B
P B
P B
P B
P B
PB
PB
P B
PB
PB
PBPBPB
PB
O A
K L E
Y
I
V D
O A
K L E
Y
I
V D
SR 74
SR 74
S V C
U G
T
R
M
S V
C 16" DIP (COA)16" DIP (COA)
16" DIP (COA)
D
IP
IN
C A S
IN
G
UNK SIZE/TYPE
D
IP
12" DIP
S V
C
UNK SIZE/TYPE
S V
C(4) WATER VALVES
S V C
S V C
(1) 12" DIP UW
(1) 6" DIP UW
UNK SIZE/TYPE
HYDRANT
6" DIP TO
HYDRANT
6" DIP TO
HYDRANT
6" DIP TO
(2) SVC
HYDRANT
6" DIP TO
(2) UW SVC METERS
(4) UW SVC METERS
(1) UNK SIZE/TYPE UW
HYDRANT
6" DIP TO
W A T E R
S E R V I C E
L I N E
C U T
A N D
C A P
E X I S T I N G
R E L O C A T E
E X I S T I
G
A T
R
M
T E R
S T A
R T
WATER SERVICE LINE
CUT AND CAP EXISTING
RELOCATE EXISTING WATER METER
STA 10+98, 63' LT
WATER SERVICE LINE
42 LF OF 1"
RELOCATED WATER METER
PROPOSED LOCATION FOR
STA 114+87, 96' RT
6" WATER LINE
CUT AND CAP EXISTING
RETURN TO COA DWM
EXISTING FIRE HYDRANT
REMOVE AND SALVAGE
STA 121+68, 89' RT
VALVE ASSEMBLY
USING 16"x6" TAPPING SLEEVE AND
CONNECT TO EXISTING 16" DIP WM
37 LF OF 6" WATER LINE
WITH THRUST BLOCK
INSTALL FIRE HYDRANT
STA 121+94, 88' RT
47 LF OF 1" WATER SERVICE LINE
RELOCATED WATER METER
PROPOSED LOCATION FOR
STA 109+52, 86' RT
RETURN TO COA DWM
EXISTING FIRE HYDRANT
REMOVE AND EXTEND
STA 10+95, 51' LT
77 LF OF 6" WATER LINE
WITH THRUST BLOCK
INSTALL FIRE HYDRANT
STA 114+43, 132' RT
TO FINISHED GRADE
ADJUST EXISTING WATER VALVE BOX
STA 121+36, 95' LT
ADJUST WATER VALVE BOXES (2) TO FINISHED GRADE
ADJUST WATER MANHOLE TO FINISHED GRADE
STA 121+35, 56' RT
STA 121+30, 56' RT
STA 121+25, 56' RT
TO FINISHED GRADE
ADJUST EXISTING WATER VALVE BOXES (2)
STA 113+42, 115' LT
WATER SERVICE LINE)
(CONTRACTOR TO CONFIRM SIZE AND TYPE OF EXISTING
EXTEND EXISTING WATER SERVICE LINE
RELOCATE EXISTING WATER METER
STA 109+57, 47' RT
Proposed Storm
Proposed Storm
P ro po se d S to rm
Z ax by s
BP Gas Station
Wingate by Wyndham
BojanglesM cD on al d' s
C hi ck -f il- A
W en dy 's
12" Existing DIP Water Ground elev: 988.72 Top pipe elev: 985.93 Btm pipe elev: 984.93
18" Proposed Storm Top pipe elev: 986.05 Btm pipe elev: 984.55
Water line to be relocated vertically (See detail on page 3)
100 ft
12" Existing DIP Water Ground elev: 986.00 Top pipe elev: 981.50 Btm pipe elev: 980.50
30" Proposed Storm Top pipe elev: 982.50 Btm pipe elev: 979.90
Water line to be relocated vertically (See detail on page 3)
12" Existing DIP Water Ground elev: 989.90 Top pipe elev: 980.90 Btm pipe elev: 979.90
30" Proposed Storm Top pipe elev: 986.80 Btm pipe elev: 984.30
No conflict at this location
12" Existing DIP Water Ground elev: 990.20 Top pipe elev: 979.20 Btm pipe elev: 978.20
18" Proposed Storm Top pipe elev: 986.80 Btm pipe elev: 984.80
No conflict at this location
44-0015
16" WATER MAIN THROUGHOUT CONSTRUCTION
CONTRACTOR TO MAINTAIN SERVICE IN
UTILITY RELOCATION PLANS
I-85 @ SR 7/SENOIA ROAD
INTERCHANGE IMPROVEMENTS
M A T
C H L I
N E
S T
A
S
G
M A T C
H L I
N E
S T
A
S
G
H A R R I S
R
D
REVISION DATES
5/21/2024 ggsmith
GPLOT-V8
gplotborder-V8i-PO-color_0007841.tbl
0007841_44-0015.dgn
6:46:05 PM
GPLN10/23/2015
CHECKED:
BACKCHECKED:
CORRECTED:
VERIFIED:
DATE:
DATE:
DRAWING No.
Project No.
0007841
EASEMENT FOR CONSTR
EASEMENT FOR CONSTR OF SLOPES
EASEMENT FOR CONSTR OF DRIVES
CONSTRUCTION LIMITS
& MAINTENANCE OF SLOPES
C F
REQUIRED R/W LINE
PROPERTY AND EXISTING R/W LINE PL
ORANGE BARRIER FENCE
LIMIT OF ACCESS
BEGIN LIMIT OF ACCESS............BLA
END LIMIT OF ACCESS..............ELA
REQ'D R/W & LIMIT OF ACCESS
(SEE ERIT TABLE)
ESA - ENV. SENSITIVE AREA
50 100 200
SCALE IN FEET
P V
C
P
V C
P V
C
P V
C 1 P
V C
P V
C
P V
C
D I
P
P V
C
H D
P E
P V
C
H D P E
18"PVC
P V
C
H D
P E
P V C
H D
P E
P V
C
P V
C
P V
C
JB
INV OUT(N 18"RCP)=972.39
INV IN(S 18"RCP)=972.51
TOP=976.67
CATCH BASIN
INV OUT(E 24"RCP)=972.16
INV IN(S 18"RCP)=972.22
INV IN(W 18"RCP)=972.28
INV IN(N 18"RCP)=972.50
TOP=976.78
CATCH BASIN
JB
M I L E
INV=983.25
12"cpp
JB
JB
INV OUT(S 18"RCP)=984.23
INV IN(N 18"RCP)=984.25
TOP=988.13
STORM MANHOLE
LP
LP LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
LP
A51
A52
A53
A54
A55
A56
A57
A58
A59
A60
A61
A62
A63
A64 A65
A66
A67
A68 A69
A70
A71
END TAPER
16.00' RT
STA 133+59
C1
C2 C3
C4
C5 C6
BEGIN TAPER
28.00' RT
STA 128+19
47 RS LC TSNOC
ON PARCEL 35
PARKING LOT
SE CORNER OF
AIR STATION AT
DO NOT DISTURB
SIGNS ON PARCEL 36
DO NOT DISTURB3
PARCEL 30
TACO BELL SIGN ON
DO NOT DISTURB
RELOCATED SIGN
DO NOT DISTURB
ON PARCEL 38B & 38C
DO NOT DISTURB SIGNS
VAULT
WATER UTILITY
& FIRE LINE
EXISTING SIGN
DO NOT DISTURB
ON PARCEL 27
EXISTING SIGN
DO NOT DISTURB
34 38C 38D 38E
38B 38A
39A
TO REMAIN
EXISTING 18" PVC
TO REMAIN
EXISTING 18" RCP
TO REMAIN
EXISTING 24" CMP
GA STD 9031U
INSTALL CONCRETE COLLAR
EXISTING 18" RCP TO REMAIN
PB
PB
PB
PB
PB
PB
P B
P B
P B
P B
P B
PB PB PB
PB
P B
P B
P B P
B
P B
H A
R R I S
H A
R R I S
U N
K
S
IZ
E /T
Y P E
16" DIP (COA)
16" DIP (COA)
16" DIP (COA)
S V C
12" DIP
12" DIP
D
IP
12" DIP
UNK SIZE/TYPE
UNK SIZE/TYPE
HYDRANT
6" DIP TO
HYDRANT
6" DIP TO
HYDRANT
6" DIP TO
(4) METERS
VAULT &
9'x6' UW
(1) UNK SIZE/TYPE UW
HYDRANT
6" DIP TO
6" WATER LINE
CUT AND CAP EXISTING
RETURN TO COA DWM
EXISTING FIRE HYDRANT
REMOVE AND SALVAGE
STA 127+47, 75' RT
20 LF OF 6" WATER LINE
WITH THRUST BLOCK
INSTALL FIRE HYDRANT
STA 127+75, 75' RT
VALVE ASSEMBLY
USING 16"x6" TAPPING SLEEVE AND
CONNECT TO EXISTING 16" DIP WM
W
STANDARD DETAIL
REALIGNED PER COA
DIP WATER MAIN TO BE
EXISTING 16"
STA 124+76, 56' RT
W
STANDARD DETAIL
REALIGNED PER COA
DIP WATER MAIN TO BE
EXISTING 16"
STA 124+76, 56' RT
P ro po se d S to rm
Proposed Storm
Proposed Storm
P ro po se d S to rm
Taco Bell Starbucks
Tim Hortons
Krystal
S he rw in
-W ill ia m s
Cracker Barrel
Tractor Supply
Quick Trip Gas Station
12" Existing DIP Water Ground elev: 983.36 Top pipe elev: 978.92 Btm pipe elev: 977.92
18" Proposed Storm Top pipe elev: 982.93 Btm pipe elev: 981.43
No conflict at this location
12" Existing DIP Ground elev: 975.97 Top pipe elev: 972.57 Btm pipe elev: 971.57
18" Proposed Storm Top pipe elev:974.07 Btm pipe elev: 972.57
Water line to be relocated vertically (see detail on page 3)
100 ft
WATER LINE CONFLICT
CXXX
XX
SCALE: N.T.S.
SAN SEWER
18" MIN FOR
6' MIN OR MAINTAIN
12" MIN
DIP OF SIMILAR DIAMETER
TO EXISTING WATER MAIN
NEW OR EX.
WATER MAIN
SIZE VARIES
CONC. COLLAR
W/ MEGALUG
RESTRAINT (TYP)
MAXIMUM 45° DIP
BENDS (TYP)
NEW OR EX.
DRAINAGE PIPE
SEE PLANS
NOTES:
1. PROVIDE MECHANICAL RESTRAINED JOINTS
FOR ALL FITTINGS.
2. USE MIN 3,000 PSI CONC. FOR CONC. COLLARS.
3. COORDINATE W/ WATER SYSTEM FOR
DISCONNECTION OF WATER SERVICE.