Drawings - Final.pdf
PDF 2 MB Posted
- Attached to
- Expand Parking Lighting and Rewiring Federal contract opportunity
- Solicitation number
- 36C24622R0011
About this file
This document package includes construction drawings and specifications for a parking lighting and rewiring project at a Department of Veterans Affairs medical center. The project scope involves upgrading and expanding parking lot lighting and wiring across the campus, including installing new light poles, concrete bases, LED streetlights, security cameras, and rewiring all streetlights. Bidders are required to provide all material, labor, utility locating, erosion control, and surface repairs to complete the work shown in the contract documents. The project will be conducted in phases to control interruptions to buildings and parking lots. Work is expected to occur outside normal business hours, with a completion time of 180 calendar days.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Map of Panel Locations.pdf | ||
| Questions and Responses - Parking Lighting Amendment 0002.pdf | ||
| Site Map - Utilities.pdf | ||
| 36C24622R0011 - Parking Lighting Amendment 0002 1.26.2022.pdf | ||
| NC Wage Determination 1.07.2022.pdf | ||
| Site Visit Sign-in Sheet pg 1.jpg | JPG image | |
| Site Visit Sign-in Sheet pg 2.jpg | JPG image | |
| 36C24622R0011 0001 - Parking Lighting 1.21.2022.pdf | ||
| Spec - Final 12.21.2021.pdf | ||
| 36C24622R0011_2.pdf | ||
| Map of Hospital - Path to B15 .jpg | JPG image | |
| Cost Estimate Worksheet Blank.xlsx | XLSX spreadsheet | |
| 36C24622R0011 RFP - Parking Lighting and Rewiring.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R i c e v i l l e o a d
T u n n e l
R o a d
H
W
Y
A
R
E
A
W
A
Y
C
A
N
O
P
Y
C
O
N
C
E
T
A
L
L
C
A
N
O
P
Y
686.2614
NORTH
3A
4A
E
L
E
C
T
R
I
S
I T
G
E
A
R
PATIENT PARKING LOTS
BUILDINGS
BELL TOWER
WALKING TRAIL
WALKING TRAIL
WALKING
HELICOPTER
TANKSO2
TRAIL
SOUTH
TOWER
WEST
TOWER
EAST
TOWER
AC
A
72T
POWER PLANT
EMPLOYEE PARKING LOTS
BOILER PLANT
3B
4B
5B
5C
WATER TANK
LEGEND
SMOKING
SHELTER
SMOKING
SHELTER
73T
R1
R2
R3
R4
1A
R5
R6
R7
R8
LANDING
AREA
5A
70T
Am bulatory C are Addition
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
CONSTRUCTION
BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
637-20-104
N/A
06/18/2021Revisions: Date:
www.atriaxgroup.com
Atriax PLLC
102 3rd Avenue, NE
Hickory, NC 28601
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204 704.348.3097
6/18/2021
S E A L
024911
H
A
R
O
L
D
J .
M
A
R
V
I
N
P
R
O
F
E
SS
IO
N
A
L
E
N
G
I N
E
E
R
N
O
R
T
A R
O
L
I
N
A
G001
HJMHJM
COVER SHEET
CHARLES GEORGE
VETERANS AFFAIRS
MEDICAL CENTER
ASHEVILLE
NORTH CAROLINA
SITE
RICEVILLE RD.
U
T
L
E
N
N
R
D
R
D
M
T
N
A
L
B
K
C
L B
E
U
D
R
I
E
G
Y
K
P
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Approved:
Date:
Approved:
Date:
Approved: Date: Approved: Date:
Requesting ServiceChief, FMS
Infection ControlMedical Center Director
M & O SupervisorAssociate Director
Safety ManagerChief of Staff
AFGEAssociate Director for Patient Care Services
HOURS OF
OPERATION
"CONFIDENTIAL"
ASHEVILLE
MEDICAL CENTER
DEPARTMENT of VETERANS AFFAIRS
NORTH CAROLINA
EXPAND PARKING LIGHTING AND REWIRING
PROJECT NO. 637-20-104
CONSTRUCTION BID DOCUMENTS
INDEX OF DRAWINGS
64 FIRE PUMP ROOM
63 STORAGE
47 MAIN HOSPITAL
24 CREDIT UNION
15 ADMINISTRATION/HUMAN RESOURCES
14 ADMINISTRATION / FMS SHOPS
12 GROUNDS - MAINTENANCE
11 LINEN
9 MENTAL HEALTH
2 & 3 QUARTERS
BUILDING FUNCTION
62 COMMUNITY LIVING CENTER
65 BLDG.15 GROUND SOURCE HEAT PUMP
70T MENTAL HEALTH
4,5,6,7
72T SWING SPACE
MENTAL HEALTH
73T MENTAL HEALTH
STATEMENT OF BID ITEM(S)
N0 BID DEDUCTS
AutoCAD SHX Text T
AutoCAD SHX Text
CONC. WALL
AutoCAD SHX Text C & G
AutoCAD SHX Text
RAMP
AutoCAD SHX Text
ASPHALT DRIVE
AutoCAD SHX Text C & G
AutoCAD SHX Text
BLOCK WALL
AutoCAD SHX Text
BLOWER PAD
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NORMAL BUSINESS HOURS 8:00AM - 4:30PM. CONTRACT WORK HOURS - EVENINGS AFTER 4PM AND WEEKENDS UNLESS APPROVED BY THE C.O.R. NO WORK ON GOVERNMENT HOLIDAYS
AutoCAD SHX Text THESE DRAWINGS MUST BE RETURNED TO MUST BE RETURNED TO BE RETURNED TO FACILITIES MANAGEMENT SERVICE, PROJECT SECTION, UPON COMPLETION, OR FINAL USE BY THE CONTRACTOR FOR BIDDING PURPOSES.
AutoCAD SHX Text G001 1 COVER SHEET 1 COVER SHEET COVER SHEET E000 2 ELECTRICAL SYMBOLS AND ABBREVIATIONS 2 ELECTRICAL SYMBOLS AND ABBREVIATIONS ELECTRICAL SYMBOLS AND ABBREVIATIONS E100 3 SITE PLAN - ELECTRICAL 3 SITE PLAN - ELECTRICAL SITE PLAN - ELECTRICAL E200 4 ELECTRICAL SCHEDULES & DETAILS 4 ELECTRICAL SCHEDULES & DETAILS ELECTRICAL SCHEDULES & DETAILS E201 5 SECURITY DETAILS 5 SECURITY DETAILS SECURITY DETAILS
AutoCAD SHX Text
DWG.#
AutoCAD SHX Text
SHEET #
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text BID ITEM I (BASE BID): ALL WORK SHOWN OR SPECIFIED WITHIN THE DRAWINGS AND SPECIFICATIONS. THE PROJECT WILL UPGRADE AND EXPAND THE PARKING LOT LIGHTING AND WIRING AT THE CHARLES GEORGE VA MEDICAL CENTER. CONTRACTOR TO PROVIDE ALL MATERIAL AND LABOR NECESSARY TO CONSTRUCT WORK SHOWN ON CONTRACT DRAWINGS INCLUDING LOCATING AND MARKING OF ALL UNDERGROUND UTILITIES, PROTECTING UTILITIES DURING CONSTRUCTION, DEMO, INSTALLATION OF NEW POLES, NEW CONCRETE BASES, LED STREETLIGHTS, SECURITY CAMERAS, REWIRING OF ALL STREETLIGHTS ON CAMPUS PER CONTRACT DRAWINGS, PROVIDING ANY EROSION AND SEDIMENT CONTROL NEEDED DURING INSTALLATION AND REPAIRING ANY SURFACES OR UTILITIES TO THAT ARE DAMAGED DURING CONSTRUCTION BACK TO EXISTING CONDITIONS OR BETTER. PHASING IS PRESCRIPTIVE TO CONTROL BUILDING AND PARKING LOT INTERRUPTIONS AND DOWN TIMES. WORK IS EXPECTED TO BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS. CONTRACT COMPLETION TIME: 180 CALENDAR DAYS AFTER CONSTRUCTION NOTICE TO PROCEED. BID ITEM II (DEDUCT ALTERNATE 1): ALL WORK AS SPECIFIED FOR BID ITEM I (BASE BID) MINUS THE FOLLOWING: ALL WORK ASSOCIATED WITH LIGHTING UPGRADES AND REWIRING WEST OF RICEVILLE ROAD. CONTRACT COMPLETION TIME: 180 CALENDAR DAYS AFTER CONSTRUCTION NOTICE TO PROCEED. NOTICE: 1. THE BASE BID CONTAINS ALL THE PROJECT WORK. EACH BID DEDUCT DELETES A PORTION OF THE WORK. THE BASE BID CONTAINS ALL THE PROJECT WORK. EACH BID DEDUCT DELETES A PORTION OF THE WORK. 2. IT IS ANTICIPATED THAT AWARD WILL BE MADE ON BID ITEM 1 (BASE BID). HOWEVER, IF THE BIDS EXCEED THE IT IS ANTICIPATED THAT AWARD WILL BE MADE ON BID ITEM 1 (BASE BID). HOWEVER, IF THE BIDS EXCEED THE FUNDS AVAILABLE, AWARD WILL BE MADE ON BID ITEM II (DEDUCT ALTERNATE 1). 3. THE BID ITEMS ARE LISTED IN DESCENDING ORDER. THE BID ITEMS ARE LISTED IN DESCENDING ORDER. 4. BIDDERS SHALL AFFIX A PRICE TO EACH BID ITEM. FAILURE TO DO SO MAY RENDER THE BID AS NON-RESPONSIVE.BIDDERS SHALL AFFIX A PRICE TO EACH BID ITEM. FAILURE TO DO SO MAY RENDER THE BID AS NON-RESPONSIVE.
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
102 3rd Avenue, NE
Hickory, NC 28601
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Revisions: Date: Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
06/18/2021 20363
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g /2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/3
/2
:5 :3
A
M
E000
ELECTRICAL SYMBOLS AND
ABBREVIATIONSSpecialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
06/18/2021 SBH CJF
ELECTRICAL MISC SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
CABLE TRAY PROVIDE CABLE TRAY AT LOCATIONS INDICATED ON PLANS. REFER TO FLOOR PLANS FOR TYPE DESIGNATION.
COORDINATE MOUNTING WITH OTHER TRADES AND REQUIREMENTS IN SPECIFICATION.
TYPE 'WIDTH x DEPTH", WIRE BASKET CABLE TRAY:
PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.
TYPE 'WIDTH LADDER', LADDER CABLE TRAY:
PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.
LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
AREA POLE LIGHT
BOLLARD
EMERGENCY HATCH
SHEET INDEX - ELECTRICAL - FOR COVER...
Sheet Number Sheet Name
E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E100 SITE PLAN - ELECTRICAL
E200 ELECTRICAL SCHEDULES & DETAILS
E201 SECURITY DETAILS
Grand total: 4
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD/SWITCHGEAR
TRANSFORMER
UPS PANEL
UTILITY METER
VENT
PIPE
BOX
VENT
VENT
BOX
VENT
BOX
BOTTLES
GAS
G A S
FUEL FILL
CAPS
FUEL
TANKS
(2)VENTS
PROPANE
TANK
G G
G
G
G
(3 )S
TEA
M
STEAM MH
RIM=2207.82
STEAM VAULT
RIM=2213.29
RIM=2192.92
STEAM MH
RIM=2186.37
STEAM MH
STEAM MH
RIM=2173.23
STEAM MH
RIM=2172.87
STEAM MH
RIM=2189.06
GV
F.F.E. 2224.77
7.0
0 (
FIR
ST
F.F
.E.)
1.0
0 (
GRO
UND
F.
F.E
CA
NO
PY
ARE
AW
AY
AREAW
AY
NEW
CH
ILLE
R
NEW
CO
OLI
NG
TOW
ERS
TOW
ERSCO
OLI
NGFUT
URE
A
B
C
D
E
F
G
H
M
J I
L
K
P
O
CO
CO
CO
CO
S
T
V
U
M
M
M
M
M
M
M
M
M
M
M
U
(100' PUBLIC R/W)
R/W
MH
RIM=2190.56
JB
U
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
U
D
D D
D
SS
SS
SS
SS
SS
CO
CO
CO
4"
6"
8" 8"
8"
SS
8"
SS
8"
MH3
SS
MH1
SS
SS
S S
S S
SS
SS
SS
SS
S S
SS
SS
SS
S S
S S
SS
SS
S S
S S
S S
S S
S S
S S
A B A N D O N E D
SS
SS
SS
SS
S
S
S
S
S
S
S
S
S
GV
G
GVGV
GV
x x x x x x x x x x x x x x x x xx x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
WV
W
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOTNEWSPOT
NEWSPOT
NEWSPOT
NEWSPOTNEWSPOT
NEWSPOT
NEWSPOT
NEWSPOTNEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOTNEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
NEWSPOT
80338032
80298028
80258024
80068005
2200.60
2212.35
.50
.45
.00
2212.00
2219.50
.50
2221.00
2224.69
2224.69
.45
2210.95
2206.252211.85
2212.40
.90
2209.202213.10
.90
2217.50
2209.402214.50
.50
2220.10
.50
2219.90
2222.50
.25
2218.85
2221.20
2221.50
2223.80
2223.80
2224.50
2221.50
2220.50
2210.25
2211.00
2211.75
2208.50 2208.90
2209.80
2205.75
2206.80
2205.10
2205.10BELL TOWER
WALKING TRAIL
WALKING TRAIL
WALKING
TRAIL
WATER TANK
686.2614
T
Spaces
Spaces
Spaces
Spaces
Spaces
Spaces
Spaces
Spaces
Spaces
Spaces
(164 Total Spaces)
Spaces
Spaces
J
J
J
J
J
J
J
C
C
C
C
C
C
C
C A. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS
INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK
(R-RELOCATION).
B. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS
RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW
CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND
CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE
OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING
THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION
ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE
CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND IS
ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
C. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES
SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
D. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE
REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH
WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED
CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE
AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED,
REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE.
WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS
SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE
AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED
MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE
BOXES ARE NOT REUSED. REMOVE CONCRETE EQUIPMENT PADS THAT REMAIN, TO BE FLUSH WITH
FLOOR/GRADE.
E. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT
AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO
ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO
REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
F. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF
SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT
DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE
RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE
PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES.
APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF
ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS
REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT BECOME INACCESSIBLE DUE TO NEW
WORK.
G. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
H. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE
COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL
CAPACITY, QUALITY, AND FUNCTIONALITY.
I. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED
ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND
FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
J. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS.
SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE
MAINTAINED AT ALL TIMES.
K. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO
MATCH ADJACENT SURFACE.
L. ALL UNLABELED ELECTRICAL DEVICES [WITH CIRCUITRY OR DEVICES MODIFIED DURING
CONSTRUCTION] [THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE] SHALL BE
CIRCUIT TRACED AS NEEDED WITH A LABEL PROVIDED.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING
CONTROLLED. WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S)
LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER
IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH
MATCHING SUBSCRIPT SHALL CONTROL CORRESPONDING LIGHT FIXTURES.
B. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR
PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS
WITH ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT
INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT
SPECIFICATIONS.
C. FIXTURES DESIGNATED 'LS' AND EXIT LIGHTS SHALL BE SERVED FROM A COMMON 20A 277V LIFE SAFETY BRANCH CIRCUIT EXIT LIGHTS SHALL BE ILLUMINATED AT NIGHT AND DURING HOURS OF
DARKNESS.
D. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.
(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)
LIGHTING GENERAL NOTES:
14 6
S1
S2
6 7
E
6 6
S1
S2
S3
S3
S2
S3
6 14
6 14
15 15
6 6
EP-17
EP-17
EP-17
EP-17
EP-17
EP-17
EP-17
EP-17
EP-17
EP-17
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-19
EP-17
PB
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
BEG-10,12
BNG-1,3
BNG-1,3
BEG-10,12
BNG-1,3
BEG-10,12
BEG-10,12
BEG-10,12
BEG-10,12
BEG-10,12
BEG-10,12
BEG-10,12
BNG-1,3
BEG-10,12
BNG-1,3
BEG-10,12
BNG-1,3
BNG-1,3
BNG-1,3
BNG-1,3
BEG-10,12
BEG-10,12
BNG-1,3
BUILDING
47SOUTH
TOWER
EAST
TOWER
WEST
TOWER
BUILDING
BUILDING
ACH
BUILDING
BUILDING
BUILDING
BUILDING
BUILDING
BEG-10,12
BNG-1,3
BNG-1,3
BNG-1,3
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
E
E
E
E
E
E
E
E
E
EHP-5,7
EHP-5,7
EHP-5,7
EHP-5,7
EHP-5,7
EHP-5,7
EHP-5,7
23 23
24 24
73T
24 24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA
1CHA-18,20,22,24
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
102 3rd Avenue, NE
Hickory, NC 28601
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Revisions: Date: Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
06/18/2021 20363
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/2
/2
:4
:2
P
M
E100
SITE PLAN - ELECTRICAL
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
06/18/2021 SBH CJF
SHEET NOTES:
1. EXISTING POST LUMINAIRE TO BE REPLACED WITH NEW POLE MOUNTED SINGLE HEAD LUMINAIRE TO
MATCH EXISTING PHILLIPS LEDGINE LUMINAIRE WITH GARDCO ECOFORM, SMALL, 48 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. REUSE EXISTING CIRCUIT FROM BUILDING 15 BUT PROVIDE NEW CONDUIT AND WIRE TO
REPLACE DIRECT BURIED CABLE. IT IS ACCPETABLE TO USE HDPE FOR CABLE RACEWAY.
2. PROVIDE NEW SINGLE HEAD LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, SMALL, 48 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. EXTEND EXISTING BUILDING 15 SITE LIGHTING CIRCUITING TO THIS LOCATION. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. PROVIDE NEW CONDUIT AND WIRE. IT IS ACCPETABLE TO USE HDPE
FOR CABLE RACEWAY.
3. EXISTING PHOTOCELL TO REMAIN.
4. REMOVE EXISTING BUILDING MOUNTED FLOOD LIGHT TO REDUCE LIGHT POLLUTION AND LIGHT DARK
AREAS TO PARKING WITH NEW POLE MOUNTED LUMINAIRE.
5. EXISTING POST LUMINAIRE TO REMAIN.
6. EXISTING AREA LUMINAIRE TO REMAIN. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE.
PROVIDE NEW EMERGENCY POWER CIRCUIT FROM BUILDING 47 BUT PROVIDE NEW CONDUIT AND
WIRE TO REPLACE DIRECT BURIED CABLE. IT IS ACCPETABLE TO USE HDPE FOR CABLE RACEWAY.
7. PROVIDE NEW DUAL HEAD POLE MOUNTED LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, LARGE, 80 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL.
PROVIDE NEW EMERGENCY POWER CIRCUIT FROM BUILDING 47 BUT PROVIDE NEW CONDUIT AND
WIRE TO REPLACE DIRECT BURIED CABLE. IT IS ACCPETABLE TO USE HDPE FOR CABLE RACEWAY.
8. EXISTING POST LUMINAIRE TO BE REPLACED WITH NEW POLE MOUNTED DOUBLE HEAD LUMINAIRE TO MATCH EXISTING PHILLIPS LEDGINE LUMINAIRE WITH GARDCO ECOFORM, SMALL, 48 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. REUSE EXISTING CIRCUIT FROM BUILDING 47 BUT PROVIDE NEW CONDUIT AND WIRE TO
REPLACE DIRECT BURIED CABLE. IT IS ACCPETABLE TO USE HDPE FOR CABLE RACEWAY.
9. PROVIDE NEW SINGLE HEAD LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, SMALL, 48 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. . PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. PROVIDE NEW CONDUIT AND WIRE. IT IS ACCEPTABLE
TO USE HDPE FOR CABLE RACEWAY.
10. PROVIDE NEW SINGLE HEAD LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, SMALL, 48 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. EXTEND EXISTING BUILDING 14 SITE LIGHTING CIRCUITING TO THIS LOCATION. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. PROVIDE NEW CONDUIT AND WIRE. IT IS ACCEPTABLE TO USE HDPE
FOR CABLE RACEWAY.
11. PROVIDE NEW DUAL HEAD POLE MOUNTED LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, LARGE, 80 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL.
PROVIDE NEW EMERGENCY POWER CIRCUIT. PROVIDE NEW CONDUIT AND WIRE TO REPLACE DIRECT
BURIED CABLE. IT IS ACCEPTABLE TO USE HDPE FOR CABLE RACEWAY.
12. PROVIDE NEW SINGLE HEAD POLE MOUNTED LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO ECOFORM, LARGE, 80 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL.
PROVIDE NEW EMERGENCY POWER CIRCUIT FROM BUILDING 47 BUT PROVIDE NEW CONDUIT AND
WIRE TO REPLACE DIRECT BURIED CABLE. IT IS ACCEPTABLE TO USE HDPE FOR CABLE RACEWAY.
13. PROVIDE NEW SINGLE HEAD POLE MOUNTED LUMINAIRE TO REPLACE EXISTING POST LUMINAIRE, LARGE, 80 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. PROVIDE NEW
EMERGENCY POWER CIRCUIT FROM BUILDING 47 BUT PROVIDE NEW CONDUIT AND WIRE TO REPLACE
DIRECT BURIED CABLE. IT IS ACCEPTABLE TO USE HDPE FOR CABLE RACEWAY.
14. PROVIDE NEW FIVE FOOT DEEP CONCRETE BASE TO PROTECT AGAINST CAR DAMAGE.
15. EXISTING AREA LUMINAIRE TO REMAIN. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE.
PROVIDE NEW EMERGENCY POWER CIRCUIT FROM BUILDING ACA BUT PROVIDE NEW CONDUIT AND WIRE TO REPLACE DIRECT BURIED CABLE. IT IS ACCEPTABLE TO USE HDPE FOR CABLE RACEWAY.
16. PROVIDE NEW SINGLE HEAD LUMINAIRE TO MATCH EXISTING PHILLIPS LUMINAIRE WITH GARDCO
ECOFORM, LAGE, 80 LED POLE MOUNTED LIGHT, PROVIDE NEW LUMINAIRE AND POLL. EXTEND
EXISTING BUILDING 15 SITE LIGHTING CIRCUITING TO THIS LOCATION. PROVIDE NEW FUSED DISCONNECT AT BASE OF POLE. PROVIDE NEW CONDUIT AND WIRE. IT IS ACCEPTABLE TO USE HDPE
FOR CABLE RACEWAY.
17. EXISTING POST LIGHT TO REMAIN
18. PROVIDE NEW POST LIGHT TO MATCH EXISTING, CIRCUIT BACK TO BUILDING 47.
19. PROVIDE NEW GARDCO DB30 BOLLARD FOR PATHWAY LIGHTING.
20. EXISTING PULL BOX.
21. PROVIDE JUNCTION BOX MOUNTED ON POLE FOR SECURITY CAMERA.
22. ADD DUAL HEAD LUMINAIRE.
23. MOVE LIGHT POLE TO CURB.
24. REMOVE EXPOSED CONDUIT.
25. 360 CAMERA.
26. PROVIDE LIGHT GUARDS ON LUMINAIRE TO NOT ALL LIGHT TRESPASS BEYOND PROPERTY LINE.
27. PROVIDE GROUND MOUNTED FLOOD LIGHT, INSIGHT 5SP-15-40K-15°-TR-UNV-NO-**-DV
1/64" = 1'-0"
SITE PLAN - ELECTRICAL
REMARKS: (LIGHTING FIXTURE SCHEDULE)
1. EXIT SIGNS - REFER TO ELECTRICAL PLANS FOR DIRECTION INDICATORS AND MOUNTING TYPE.
2. WALL MOUNTING - COORDINATE EXACT LOCATION WITH ARCHITECT AND ARCHITECTURAL DETAILS. COORDINATE FRAMING
AND BOX SUPPORTS PRIOR TO ROUGH-IN FOR EXACT PLACEMENT OF BOX TO ACHIEVE CENTERING AND ALIGNMENT WITH
FINAL ARCHITECTURAL FINISHES.
3. COVE - COORDINATE EXACT QUANTITIES WITH ARCHITECTURAL DETAILS TO PROVIDE CONTINUOUS ILLUMINATION FOR ENTIRE
LENGTH OF COVE.
4. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED
PENDANT/SUSPENSION LENGTH WITH ARCHITECT AND ARCHITECTURAL DETAILS.
5. [HEIGHT] POLE MOUNT - PROVIDE [HEIGHT], [STEEL][ALUMINUM], [STRAIGHT][TAPERED], [ROUND][SQUARE WITH VIBRATION DAMPER] POLE WITH PAINT OVER [PRIMER][GALVINIZED] FINISH TO MATCH FIXTURE. PROVIDE [HEIGHT] POLE BASE PER DETAIL
[###] ON SHEET [###].
6. GYP CEILING MOUNTING - PROVIDE WITH MANUFACTURER'S FLANGE MOUNTING KIT/ACCESSORY(S) TO ALLOW FOR
RECESSED MOUNTING OF LUMINAIRE WITHIN GYP CEILING.
GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)
A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS
AND CATALOG NUMBER PRIOR TO ORDERING.
B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH
'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.
WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND
CHARACTERISTICS AS THAT SCHEDULED:
1. ACUITY BRANDS
2. EATON/COOPER BRANDS
3. HUBBELL
4. WILLIAMS
5. PHILLIPS/SIGNIFY BRANDS
C. DOWNLIGHT - PROVIDE DOWNLIGHT REFLECTOR FINISH/COLOR AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE.
SELECT CEILING TRIM FINISH/COLOR TO COORDINATE WITH CEILING TYPE. "WHITE" TRIM FOR DOWNLIGHTS MOUNTED IN WHITE ACOUSTICAL TILE CEILINGS. "CLEAR" (TO MATCH REFLECTOR FINISH/COLOR) FOR DOWNLIGHTS MOUNTED
IN PAINTED GYPSUM BOARD CEILINGS.
D. COVE – DRAWINGS PROVIDE GENERAL ILLUSTRATION OF COVE LAYOUT. COORDINATE EXACT UNIT LENGTHS AND QUANTITIES WITH ARCHITECTURAL DETAILS TO PROVIDE CONTINUOUS ILLUMINATION FOR ENTIRE LENGTH OF COVE.
LED COVE LIGHTING FIXTURES SHALL BE INSTALLED END-TO-END (NO GAP BETWEEN FIXTURES) WITH A MAXIMUM 6” GAP AT COVE ENDS AND CORNERS. SELECT UNIT LENGTHS AND QUANTITIES TO ACHIEVE THE ABOVE REQUIRED
PERFORMANCE (SHORTER UNIT LENGTHS IN GREATER QUANTITIES MAY BE REQUIRED).
E. TRACK – PROVIDE SINGLE-CIRCUIT TRACK SYSTEM WITH ALL NECESSARY COMPONENTS FOR A COMPLETE INSTALLATION, INCLUDING, BUT NOT LIMITED TO: POWER FEEDS, STAND OFFS, CONNECTORS, END CAPS, AND TRANSFORMERS. TRACK AND ACCESSORY FINISH SHALL MATCH FINISH OF SPECIFIED TRACK HEAD. PROVIDE TRACK LENGTHS AND TRACK HEAD QUANTITIES PER PLANS. COORDINATE TRACK TYPE FOR COMPATIBILITY WITH SPECIFIED TRACK HEAD FIXTURE. PROVIDE REMOTE TRANSFORMER QUANTITIES AND SIZES TO ACCOMMODATE LOAD OF TRACK HEADS INDICATED. PROVIDE POWER FEEDS AND TRACK CONNECTORS AS NEEDED TO PROVIDE TRACK LENGTH INDICATED. MOUNT REMOTE TRANSFORMER ABOVE NEAREST ACCESSIBLE CEILING. COORDINATE LENGTH OF
STANDOFFS AND POWER FEEDS AND EXACT SHAPE OF CURVED TRACKS WITH ARCHITECT.
F. UNDERCABINET- PROVIDE ALL NECESSARY MANUFACTURER'S INSTALLATION ACCESSORIES TO ACCOMMODATE INSTALLATION, INCLUDING, BUT NOT LIMITED TO: SPLICE BOXES, END CONNECTORS, AND JUMPER/DAISY CHAIN
CONNECTORS.
G. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.
H. WALL-TO-WALL MOUNTING - PROVIDE FIXTURE WITH CONTINUOUS ILLUMINATION FROM WALL TO WALL. COORDINATE EXACT WALL DIMENSIONS WITH GENERAL CONTRACTOR AND ARCHITECTURAL DETAILS. PROVIDE MANUFACTURER'S
WALL-TO-WALL MOUNTING ACCESSORY(S) AS REQUIRED FOR A COMPLETE INSTALLATION.
GENERAL NOTES: (LIGHTING CONTROL SCHEDULE)
A. SUBMIT MANUFACTURER INTERCONNECTION DIAGRAMS INDICATING DEVICE QUANTITIES, LOCATIONS, AND ASSOCIATED CONTROLS CABLING FOR APPROVAL.
B. REFER TO LIGHTING PLAN FOR WALL DEVICE TYPES, QUANTITIES, AND LOCATIONS. REFER TO SYMBOL LEGEND FOR LIGHTING PUSH BUTTON TYPE DESCRIPTIONS.
C. DEVICE QUANTITIES NOT INDICATED. PROVIDE TYPE AND QUANTITY OF DEVICES AS REQUIRED TO PROVIDE COMPLETE COVERAGE OF SPACE AND INTENDED SYSTEM
OPERATION.
D. WHERE BI-LEVEL SWITCHING AND AUTO ON TO 50% ARE USED IN THE SAME SPACE, THE ZONE THAT IS AUTOMATICALLY TURNED ON SHALL BE CONTROLLED BY THE BOTTOM
BUTTON OF WALL DEVICES.
E. WHERE PHOTOCELLS ARE BEING UTILIZED FOR DAYLIGHT HARVESTING, PROVIDE ADDITIONAL COMPONENTS AS NEEDED TO CONTROL LIGHTING WITHIN DAYLIGHT ZONES
INDEPENDENT OF GENERAL AREA LIGHTING WITHIN SPACE. PROVIDE MINIMUM OF (1) PHOTOCELL DEVICE PER DAYLIGHT ZONE.
F. UNLESS NOTED OTHERWISE, LIGHTING SHALL UTILIZE CONTINUOUS DIMMING AND EXTERIOR LIGHTING SHALL UTILIZE MULTI-LEVEL STEP DIMMING.
G. UNDERCABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM MAIN ROOM LIGHTING. UNDERCABINET LIGHTING SHALL BE CONTROLLED BY THE AUTO OFF FUNCTION OF
OCCUPANCY SENSORS.
H. WHERE PHOTOCELLS ARE UTILIZED FOR DAYLIGHT HARVESTING, TARGET ILLUMINANCE LEVELS SHALL BE MEASURED AT WORK PLANE OF PRIMARY TASK IN SPACE.
I. COORDINATE PROGRAMMING OF BUSINESS HOURS WITH OWNER PRIOR TO OCCUPANCY.
J. "DEVICES":
• "OCC" - OCCUPANCY SENSOR. PROVIDE TYPE INDICATED BELOW. CEILING MOUNT UNLESS NOTED OTHERWISE.
• "IR" = PASSIVE INFRARED
• "US" = ULTRASONIC/MICROPHONIC
• "DT" = DUAL TECHNOLOGY
• "N" = NO OCCUPANCY SENSOR
• "DAYLIGHT" - DAYLIGHT CONTROLS. CEILING MOUNT UNLESS NOTED OTHERWISE.
• "Y" = PROVIDE DAYLIGHT PHOTOCELL. PHOTOCELLS MAY NOT BE COMBINED WITH OCCUPANCY SENSORS UNLESS NOTED OTHERWISE.
• "N" = NO DAYLIGHT PHOTOCELL.
• "AUX" - AUXILIARY CONTACT.
• "Y" = PROVIDE AUXILIARY CONTACT/RELAY TO INDICATE OCCUPANCY FOR USE BY OTHER SYSTEMS. AUXILIARY CONTACT/RELAY MAY BE INTEGRATED WITH OCCUPANCY
SENSOR. AUXILIARY CONTACTS MAY BE OMITTED IF SYSTEM IS FULLY NETWORKED AND ROOM STATUS IS COMMUNICATED TO OTHER SYSTEMS THROUGH SOFTWARE INTEGRATION. COORDINATE WITH OTHER SYSTEMS AND CONFIRM THIS DESIGN IS ACCEPTABLE WITH OWNER AND ENGINEER PRIOR TO ORDERING PARTS.
• "N" = NO AUXILIARY CONTACT.
• "NETWK" - NETWORKED LIGHTING CONTROL COMMUNICATIONS.
• "Y" = NETWORK ROOM DEVICES TO BUILDING-WIDE LIGHTING CONTROLS NETWORK COMMUNICATIONS.
• "N" = BUILDING-WIDE LIGHTING CONTROLS NETWORK COMMUNICATIONS NOT REQUIRED TO THIS ROOM.
• "REC" - CONTROLLED RECEPTACLES
• "Y" = PROVIDE AUTOMATIC CONTROL OF SELECTED RECEPTACLES WITHIN SPACE. REFER TO POWER PLAN FOR RECEPTACLES TO BE CONTROLLED.
• "N" = NO CONTROLLED RECEPTACLES.
PROVIDE ONE (1) SPARE 1" CONDUIT PER POLE BASE,
STUBBED TO APPROXIMATELY 3' FROM CENTER OF POLE
BASE. CAP BOTH ENDS OF CONDUIT AND PROVIDE WITH
A PULL STRING. LABEL CONDUIT AS SPARE WITHIN POLE
BASE COVER. MARK BURIED END OF CONDUIT WITH
STEEL STAKE, MINIMUM 3' LONG, DRIVEN VERTICALLY AT
END OF CONDUIT TO A DEPTH OF 6" BELOW GRADE TO
TOP OF STAKE.
24"
B
4"
HANDHOLE
BASE COVER TO MATCH POLE
3/4" CHAMFER
ANCHOR BOLTS
FURNISHED WITH POLE
ACTIVE CONDUIT
ROUND POURED
CONCRETE BASE
#12 (MIN.) TO FIXTURE HEADS
IN-LINE FUSE - EACH PHASE
SPLICE
PHASE CONDUCTORS PER PLAN
GROUT BETWEEN POLE BASE PLATE
AND CONCRETE BASE
TOOL FINISH AT EDGE OF BASE PLATE
8'-15'
16'-29'
30'-40'
60"
72"
POLE
HEIGHT
B
48"
FINISHED SURFACE
SITE LIGHT POLE
(REFER TO LIGHTING
FIXTURE SCHEDULE)
#6 BARE BONDED TO REBAR AND POLE
A
SIX (6) #6 VERTICAL REBARS
AND #4 HORIZONTAL
REBARS 12" ON CENTER
16"8'-15'
16'-29'
30'-40'
20"
24"
A (MINIMUM
CONCRETE BASE
DIAMETER OR 2"
LARGER THAN FINAL
SELECTED POLE)
POLE
HEIGHT
GENERAL NOTE:
1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.
BOND TO EQUIPMENT GROUNDING
CONDUCTOR SIZED PER DRAWINGS.
A
B
24"
30"
HANDHOLE
BASE COVER TO MATCH POLE
3/4" CHAMFER
ANCHOR BOLTS
FURNISHED WITH POLE
ACTIVE CONDUIT
ROUND POURED
CONCRETE BASE
SIX (6) #6 VERTICAL REBARS
AND #4 HORIZONTAL
REBARS 12" ON CENTER
16"8'-15'
16'-29'
30'-40'
20"
24"
A (MINIMUM
CONCRETE BASE
DIAMETER OR 2"
LARGER THAN FINAL
SELECTED POLE)
GROUT BETWEEN POLE BASE PLATE
AND CONCRETE BASE
TOOL FINISH AT EDGE OF BASE PLATE
8'-15'
16'-29'
30'-40'
60"
72"
B
48"
#12 (MIN.) TO FIXTURE HEADS
IN-LINE FUSE - EACH PHASE
SPLICE
PHASE CONDUCTORS PER PLAN
PROVIDE ONE (1) SPARE 1" CONDUIT PER POLE BASE,
STUBBED TO APPROXIMATELY 3' FROM CENTER OF POLE
BASE. CAP BOTH ENDS OF CONDUIT AND PROVIDE WITH
A PULL STRING. LABEL CONDUIT AS SPARE WITHIN POLE
BASE COVER. MARK BURIED END OF CONDUIT WITH
STEEL STAKE, MINIMUM 3' LONG, DRIVEN VERTICALLY AT
END OF CONDUIT TO A DEPTH OF 6" BELOW GRADE TO
TOP OF STAKE.
POLE
HEIGHT
POLE
HEIGHT
FINISHED SURFACE
SITE LIGHT POLE
(REFER TO LIGHTING
FIXTURE SCHEDULE)
#6 BARE BONDED TO REBAR AND POLE
GENERAL NOTE:
1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.
BOND TO EQUIPMENT GROUNDING
CONDUCTOR SIZED PER DRAWINGS.
SPOT LIGHT OR FLOOD LIGHT
(REFER TO LIGHTING
FIXTURE SCHEDULE)
PROVIDE MANUFACTURER'S
FLOOD LIGHT BASE ENCLOSURE
FOR WIRING TERMINATION,
INSTALL PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS
3/4" CHAMFER
FINISHED SURFACE
ACTIVE CONDUIT
ROUND POURED
CONCRETE BASE
AIM PER PLAN
42"
24"
4"
12" MINIMUM
DIAMETER OR 2"
LARGER THAN
FINAL SELECTED
POLE
24"
42"
12" MINIMUM
DIAMETER OR 2"
LARGER THAN
FINAL SELECTED
POLE
BOLLARD (REFER TO LIGHTING
FIXTURE SCHEDULE)
3/4" CHAMFER, EXCEPT
WHEN INSTALLED WITHIN
CONCRETE AREA
FINISHED SURFACE
ANCHOR BOLTS
FURNISHED WITH
BOLLARD
ACTIVE CONDUIT
ROUND POURED
CONCRETE BASE
FOUR (4) #4 VERTICAL
REBARS AND #4
HORIZONTAL REBARS
12" ON CENTER
4" ABOVE FINISHED SURFACE,
EXCEPT WHEN INSTALLED WITHIN
CONCRETE AREA
INSTALL FLUSH WITH CONCRETE
AREA
6" BARE BONDED TO REBAR AND POLE
GENERAL NOTE:
1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.
BOND TO EQUIPMENT
GROUNDING CONDUCTOR
SIZED PER DRAWINGS.
NOTES:
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE
INSTALLATION.
2. PROGRAM REQUIREMENTS:
NORMAL NIGHTTIME HOURS - LIGHT FIXTURES "ON"
NORMAL DAYTIME HOURS - LIGHT FIXTURES "OFF"
3. COORDINATE PROGRAMMING WITH OWNER.
LIGHTING
CONTROL
PANEL
(PER PLANS)
UNSWITCHED
BRANCH CIRCUIT
POWER PHOTO CELL FROM
BRANCH CIRCUIT HOUSE1-78
PHOTOELECTRIC CONTROL AIMED NORTH.
MOUNT ON 24" RIGID STEM ON ROOF,
LOCATION PER SHEET ES101
LOW VOLTAGE WIRING
PER MANUFACTURER'S
RECOMMENDATIONS
INDIVIDUAL LOW
VOLTAGE INPUT
INDIVIDUAL LIGHTING RELAY
EXTERIOR BUILDING
MOUNTED FIXTURE(S)
EXTERIOR POLE
MOUNTED FIXTURE(S)
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
102 3rd Avenue, NE
Hickory, NC 28601
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Revisions: Date: Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
06/18/2021 20363
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g /2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/3
/2
:5 :4
A
M
E200
ELECTRICAL SCHEDULES &
DETAILSSpecialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
06/18/2021 SBH CJF
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION SUBS MANUFACTURER CATALOG # (NOTE A)
LAMP /
NOMINAL
LUMENS CCT
MINIMUM
CRI VOLTAGE
HIDE
SES_Watts
Per Foot
HIDE
SES_Load VA
INPUT
WATTS MOUNTING REMARKS
P1 - - 480 V 0 W 0 VA 0
S1 - - 480 V 0 W 0 VA 0
S2 - - 480 V 0 W 0 VA 0
S3 - - 0 VA 0
U1 - - 480 V 0 W 0 VA 0
LIGHTING CONTROL SCHEDULE add remarks
TAG ROOM TYPE
DEVICES
SEQUENCE OF OPERATIONOCC DAY LT AUX NETWK REC
NO SCALEE200
SITE LIGHT POLE BASE - 4" HEIGHT4
NO SCALEE200
SITE LIGHT POLE BASE - 30" HEIGHT5
NO SCALEE200
FLOOD LIGHT BASE1
NO SCALEE200
BOLLARD BASE2
NO SCALEE200
EXTERIOR LIGHTING (RELAY PANEL)3
3/4" CONDUIT TO
ACCESSIBLE SPACE
CAT 6 CABLE TO
NEAREST TR BY SCC
22"
ACCESS
CONTROL
PANEL
COLLECTION
BOX
PATCH
PANEL
120/240
VAC
ACCESS
POWER
SUPPLY
NETWORK
SWITCH
22"
(POE)
F/O PATCH
PANEL
MEDIA
CNVTR
MEDIA
CNVTR
POE
INJCTR
INTRUSION
DETECTION
PANEL
TYPICAL MOTION SENSOR
TYPICAL EXTERIOR POLE IP
CAMERA
TYPICAL DURESS BUTTON
TYPICAL EXTERIOR IP CAMERA
CAT-6
UPS
CAT-6
MINIDOME IP CAMERA
COMPUTER WORKSTATION
TYPICAL ACCESS DOOR
TYPICAL MONITORED DOOR
HEAD END
WALL-MOUNT
120 VAC
NVR
120 VAC
120 VAC
EQUIP
RACK
SRVR
POE SWITCH
NVR
NVR
F/O PATCH
RACK UPS
EQUIP
RACK
POE SWITCH
PATCH
F/O PATCH
RACK UPS
PATCH
PATCH
PATCH
NVR
EQUIP
RACK
POE SWITCH
PATCH
F/O PATCH
RACK UPS
PATCH
PATCH
PATCH
EQUIP
RACK
POE SWITCH
PATCH
F/O PATCH
RACK UPS
PATCH
PATCH
PATCH
EQUIP
RACK
POE SWITCH
PATCH
F/O PATCH
RACK UPS
PATCH
PATCH
PATCH
EQUIP
RACK
SRVR
POE SWITCH
F/O PATCH
RACK UPS
EQUIP
RACK
POE SWITCH
PATCH
F/O PATCH
RACK UPS
PATCH
PATCH
PATCH
WRK STATN
PATCH
ROOF
SPECIAL SYSTEMS
OPERATIONS ROOM
ALL RACKS
TYP.
ALL RACKS
TYP.
SEE VA IT/IS RACK LAYOUT FOR DETAILS
SERVICE ENTRANCE FIBER OPTIC CABLES
12 STRAND / 6 PAIR MULTIMODE
12 STRAND / 6 PAIR MULTIMODE
4 STRAND / 2 PAIR MULTIMODE
12 STRAND / 6 PAIR MULTIMODE
CAT 6E (TYP.)
CAT 6E (TYP.)
CAT 6E (TYP.)
4 STRAND / 2 PAIR MULTIMODE
ACCESS CONTROL
PANELS
SSTV
CAMERA
SSTV
CAMERA
SSTV
CAMERA
SSTV
CAMERA
MOTION
SECURITY
MONITORING
SSTV
CAMERA
(EXT. POLE)
MEDIA
CNVRTR
120V
120V
120V/208V120V/208V 120V
GENERAL NOTES: (SECURITY CAMERA SCHEDULE)
A. GENERAL (S2):
PROVIDE [POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED] POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE NOTES FOR EACH CAMERA AT LOCATIONS INDICATED. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE
(1) CATEGORY [5E] [6] [6A] NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK ABOVE CEILING AT LOCATION INDICATED. PROVIDE 4" SQUARE BACK BOX, MOUNTED AT 84” AFF WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS.
PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. [PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.] COORDINATE EXACT MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.
B. GENERAL (S4):
PROVIDE [POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED] POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE NOTES FOR EACH CAMERA AT LOCATIONS INDICATED. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE
(1) CATEGORY [5E] [6] [6A] NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK ABOVE CEILING AT LOCATION INDICATED. PROVIDE 4" SQUARE BACK BOX, MOUNTED AT 84” AFF WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS.
PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. [PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.] COORDINATE EXACT MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.
C. GENERAL (S5):
PROVIDE [POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED] POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE NOTES FOR EACH CAMERA AT LOCATIONS INDICATED. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE
(1) CATEGORY [5E] [6] [6A] NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK ABOVE CEILING AT LOCATION INDICATED. PROVIDE 4" SQUARE BACK BOX, MOUNTED AT 84” AFF WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS.
PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. [PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.] COORDINATE EXACT MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.
D. GENERAL (S7):
PROVIDE [POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED] POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CAMERA TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR CAMERA DESIGNATION. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE (1) CATEGORY [5E] [6] [6A] NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK AT LOCATION INDICATED. INSTALL CAMERA CENTERED IN CEILING TILE. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR HEATED ENCLOSURES, PAN-TILT-ZOOM FUNCTIONS, AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION 271200. [PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 282300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.] COORDINATE EXACT MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
102 3rd Avenue, NE
Hickory, NC 28601
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Revisions: Date: Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
06/18/2021 20363
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g /2
V
A A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/3
/2
:5 :4
A
M
E201
SECURITY DETAILS
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
06/18/2021
NO SCALEE201
TYPICAL PENDANT MOUNTED CAMERA4
NO SCALEE201
BASIC IP BASED SECURITY SYSTEM ONELINE5
NO SCALEE201
SECURITY SYSTEM RISER DIAGRAM6
| Sheets and Views |
| GI001 |
| 3-E100 Site Plan-Electrical.pdf |
| Sheets |
| E100 - SITE PLAN - ELECTRICAL |
File details come from the government source that posted it. Updated .