This file contains standard detail sheets and technical drawings for a Kentucky County count station maintenance project, providing specifications for electrical infrastructure, conduit installation, utility placement, and equipment mounting. The drawings establish installation requirements for underground utility conduits, electrical service poles with meter bases and service disconnects, pad-mounted and pole-mounted enclosures, junction boxes, inductive loop detectors, and piezoelectric sensors for traffic monitoring systems. Key specifications include rigid steel conduit installation with minimum 24-inch depth under pavement, conduit sizing requirements ranging from 2 inches to 1.5 inches depending on application, proper grounding conductor installation with ground rods, and specific dimensional requirements for various equipment types. The technical details cover conduit trench construction with class A concrete backfill, warning tape placement, equipment mounting hardware specifications including wood screws and lag bolts, and grounding bushing installations for electrical safety.
The drawings provide three distinct junction box types with specified dimensions—Type A measuring 23 by 14 by 18 inches, Type B measuring 18 by 11 by 12 inches, and Type C measuring 36 by 2 by 30 inches—along with installation guidance for in-pavement sensor loops configured as 6-foot by 6-foot squares with four turns of 14 AWG wire. Grounding requirements mandate 5/8-inch by 8-foot copperweld ground rods installed minimum 6 inches below grade with solid copper ground wire connections. All specifications comply with National Electrical Code requirements, and the drawings explicitly address traffic safety considerations including minimum clearance distances from guardrails (50 inches for cabinet assemblies and 60 inches for junction box assemblies) and breakaway support stub height restrictions to prevent vehicle hazards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB 26.627 Bid Sheet.xlsx | XLSX spreadsheet | |
| District Map.pdf | ||
| Final_RFB_605_2600000627_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
l :.·
STANDARD DETAIL SHEETS
24" M ·S _B- AS
24" MIN. 2' RIGID STEEL CONDUIT IMIN. I OR AS SPECIFIED. UNLESS
'OPEN CUT ROADWAY' IS INCLUDED AS A BID ITEM, CONDUIT
SHALL BE INSTALLED WITHOUT DISTURBING PAVEMENT.
CONDUIT SHALL EXTEND A MINIMUM OF 24" PAST THE
SUB-BASE UNLESS OTHERWISE DIRECTED BY THE ENGINEER.
J 24'MIN.
CONDUIT UNDER PAVEMENT
TOTAL TRENCH WIDTH SHALL BE 3" INOM. I WIDER THAN
THE SUM OF THE OUTSIDE DIAMETERISI OF THE CONDUITISI
INSTALLED. CONDUITISI SHALL BE CENTERED IN TRENCH.
CONTRACTOR SHALL PLACE BACKFILL IN LIFTS 19" MAX. I
COMPACT BACKFILL, AND RESTORE DISTURBED AREA TO THE
SATISFACTION OF THE ENGINEER
CONTRACTOR SHALL INSTALL UNDERGROUND UTILITY
WARNING TAPE ABOVE CONDUIT AS SHOWN.
FINISHED GRADE
"4 BARS© 8' O.C.-
EACH WAY
7"3f-f- .•.• 9" .. • :. ,: ... :-•• • • G
;------- ;f- I
18"
24" MIN.
/ 0
-WARNING TAPE
BACKFILL
24"
:: • .- •• ·.: _....,.....---- CLASS A CONCRETE
RIGID STEEL CONDUIT
/ -CONDUIT
- DUCTED CABLE
CONDUIT TRENCH OPEN CUT PAVEMENT DETAIL
CONDUIT INSTALLATION
NOT TO SCALE
SERVICE POLE WITH WEATHERHEAD
AND ELECTRICAL SERVICE DROP
DRIP LOOP
11/4' CONDUIT FROM
WEATHERHEAD
TO METER BASE
CONDUIT STRAP ITYP.1 WITH
2/2" WOOD SCREWS 130" 0. C. I
METER
CONDUIT
-WEATHERPROOF HUB
LOCKNUT ITYP. I
!BOTH S!OESI
TER BASE HOUSING
BUSHING
ROUNDING BUSHING
CK NUT ITYP. I
TH SIDES!
METER BASE HOUSING
SECURE METER BASE AND SERVICE
DISCONNECT ENCLOSURES TO POLE
WITH FOUR 141 21/2°' WOOD SCREWS
AND WASHERS. INST ALL THROUGH
BACK OF ENCLOSUREISI IF NECESSARY
BASE
SERVICE
DISCONNECT
CONDUIT
-WEATHERPROOF HUB
LOCKNUT ITYP I
!BOTH S!DESI
SCONNECT HOUSING
14• CONDUIT ANO LB CONOULETS
FOR POLE MOUNT ENCLOSURE
IIF REOU!REOI
14" CONDUI
!FOR GROUNDIN
CONDUCTO
3/, CONDUIT FOR PAD MOUNT
ENCLOSURE IIF REOUIREOI
NDING BUSHING
CKNUT ITYP.I
0TH SIDES!
DISCONNECT HOUSING
- CONDUIT
�2 4' --------- , LIMIT OF CONDUIT INCIDENTAL TO
ELECTRICAL SERVICE IS 24" FROM
THE FACE OF THE POLE.
INSTALL GROUNDING CONDUCTOR
FROM METER BASE, THROUGH
DISCONNECT, TO GROUND ROD.
ROUND ROD
ELECTRICAL SERVICE
20"x20"x8" CABINET�
LOCKNUT ITYP. I
!BOTH SIDES!
BOX HOUSING
�" x �" x 96" WOOD
◄--POST ITYP.I
METAL FRAMING CHANNEL
WITH 21// LAG BOLTS
38" -PIPE CLAMP FITTING
◄ RIGID STEEL CONDUIT
WASHER R
T
3/8" IMIN. I BOL
DRILL HOLE THROU
TO ACCOMMODA
18" MIN.
35"
CLASS A CONCRETE
CABINET/POST ASSEMBLY LOCATED
BEHIND GUARDRAIL SHALL BE A
MINIMUM OF 50" FROM THE FACE
OF THE GUARDRAIL
FRONT VIEW t 50" !MIN. I
METAL FRAMING
CHANNEL AND PIPE
CLAMP FITTING
1%" � A
�21// LAG BOLT
� A AND WASHER ITYP. I
FRONT A-A
METAL FRAMING CHANNEL
GALVANIZED STEEL CABINET
DOUBLE POST ASSEMBLY
RIGHT VIEW
l f
JUNCTION BOX/POST ASSEMBLY LOCATED BEHIND
GUARDRAIL SHALL BE A MINIMUM OF 60" FROM
THE FACE OF THE GUARDRAIL
60' !MIN. I /
INSTALL BOX AWAY
FROM TRAFFIC FLOW
LOCKNUT ITYPI
!BOTH SIDES!
BOX HOUSING
SECURE BOX TO POST
WITH FOUR 141 21/2" WOOD
SCREWS AND WASHERS
�·x48
I WOOD. POST
18" i l
CONDUIT STRAP WITH
21/z' WOOD SCREWS
!SEE LAYOUT SHEET FOR SIZEI
18' MIN.
JUNCTION BOX IO"xB"xLJ"
AND POST ASSEMBLY
D
• MINIMUM C STACKABLE BOXES ARE PERMITTED
J
GROUNDING
CONDUCTOR
CONDUIT WITH
GROUNDING -
BUSHING ITYP. I
INSTALL BOX FLUSH
1TH FINISHED GRADE
8"
WHERE REQUIRED, JUNCTION BOX
SHALL BE ORIENTED SUCH THAT
THE DIMENSIONS COMPLY WITH
THE NATIONAL ELECTRICAL CODE.
2"
GR ADA TJON SIZE
NO. 57 AGGREGATE
ELEVATION
/GROUNDING CONDUCTOR
r
GROUNDING BUSHING ITYP I
uX
GROUNDING DETAIL
◄-- RIGID STEEL CONDUIT ITYP. I
JUNCTION BOX - TYPE A, TYPE B, TYPE C
JUNCTION BOX DIMENSIONS INOMINALI
A B C D• E F
TYPE A 23" 14" 18" 2" 25" 16"
TYPE B 18" II" 12" (74" 20" 13"
TYPE C 36" 2�" 30" 3" 38" 26"
y
EXTEND CUT BEYOND CORNER
LL DEPTH
LL I 1// HOLE AND/OR
RNER TO SLOT DEPTH
A TE SHARP EDGES
3/s" SAW SLOT
----t- 2"
FINISHED SURF ACE
NON-SHRINK GROUT
I/z' BACKER ROD
LOOP WIRES ENCAPSULATED
IN LOOP SEALANT
I : :
SECTION A-A (CONCRETE)
�-- FINISHED SURFACE
SAW CUT PLAN T UNLESS SPECIFIED OTHERWISE, ALL LOOPS
SHALL BE 6' x 6' SQUARE, CENTERED IN EACH LANE, WITH FOUR TURNS OF 14 AWG LOOP WIRE.
ADJACENT SAW SLOTS SHALL BE A MINIMUM OF
12" APART.
---NON-SHRINK GROUT
--- 1// BACKER ROD
'/s"
SECTION A-A (ASPHALT)
LOOP WIRES ENCAPSULATED
IN LOOP SEALANT
WIRING PLAN
EDGE OF PAVED
SURFACE OR
FACE OF CURB
9"-12"
IRES IN SAW SLOT
OM
LDER
IT.
TO JUNCTION BOX
OR CABINET
18' MIN. DEPTH
SAW SLOT EDGE OF PAVEMENT TRANSITION
INDUCTIVE LOOP DETECTOR
J
7f\''
-----'3>- A SERVICE POLE
METER BASE AND
SERVICE DISCONNECT
GROUNDING CONDUCTOR
ANO GROUND ROD
LIMIT OF CONDUIT INCIDENT AL
24" TO ELECTRICAL SERVICE IS 24'
BEYOND THE FACE OF THE POLE.
ENCLOSURE BASE --
ANCHOR BOLT ITYP.1--
CONCRETE PAD-
14" RIGID STEEL CONDUIT
LIMIT OF CONDUITS INCIDENTAL
24"
I rn INSTALL PAD MOUNT ENCLOSURE
FOR ELECTRICAL SERVICE: 24" JS 24" BEYOND THE EDGE OF THE
14" RIGID STEEL CONDUIT ,I I CONCRETE BASE.
FOR GROUNDING CONDUCTORIS�
36"
10.5"
II II
u u n
GRON N II
CONDU TO @
- DOOR ITYP. I
---+- 2" RIGID STEEL CONDUITS TO
IN-PAVEMENT SENSORS AS TIMIT OF CONDUITS INCIDENTAL
-----'3>- A 26. 5" SPECIFIED ON THE LAYOUT
SHEET. INSTALL 1-2' SPARE
RIGID STEEL CONDUIT,
THREADED AND CAPPED
ON BOTH ENOS.
f
TO INSTALL PAD MOUNT ENCLOSURE
" JS 24' BEYOND THE EDGE OF THE
CONCRETE BASE.
ORIENT ENCLOSURE TO ROADWAY WITH HINGES
AWAY FROM TRAFFIC.
FURNISH AND INSTALL A GROUNDING BUSHING
ON EACH CONDUIT IN THE ENCLOSURE BASE.
BOND EACH CONDUIT BUSHING WITH GROUNDING
CONDUCTOR AND CONNECT TO GROUND ROD.
PLAN
PAO MOUNT ENCLOSURE (I OF 3)
SERVICE POLE
WEATHERHEAD AND
ELECTRICAL SERVICE DROP
-00'
CHOR BOLT
FOR ELECTRICAL SERVICE:
FOR GROUNDING CONDUCTOR
ANCHOR BOLT ITYP. I
I" CHAMFER -
GROUND IN
CONDUCT
NUT
WASHER
NCLOSURE
NCHOR BOLT
CRETE BASE
FINISH GRADE TO DRAIN
AWAY FROM ENCLOSU
78"
GROUND ROD
2" RIGID STEEL CONDUITS FROM
IN-PAVEMENT SENSORS !QUANTITY
AS SPECIFIED ON THE LAYOUT SHEET!.
INSTALL 1-2" SPARE RIGID STEEL
CONDUIT, THREADED AND CAPPED
AT EACH END.
ELEVATION WITH DOORS OPEN
PAD MOUNT ENCLOSURE (2 OF 3)
SERVICE POLE WITH METER BASE
AND SERVICE DISCONNECT ISEE
ELECTRICAL SERVICE DETAIL!
I
CONDUIT STRAP ITYP. I WITH
21f2'' WOOD SCREWS 130" 0. C I ijj
14" CONDUIT
ANCHOR BOLT ITYP I -
I' CHAMFER -
FINISH GRADE TO DRAIN
AWAY FROM ENCLOSURE
24" MIN. 36"
GROU
FOR SERVICE
LIMIT OF CONDUIT INCIDENTAL
TO ELECTRICAL SERVICE AND
TELEPHONE SERVICE IS 24" BEYOND
THE FACE OF THE POLE
' RIGID STEEL CONDUIT
FOR ELECTRICAL SERVICE:
74 RIGID STEEL CONDUIT -
FOR GROUNDING CONDUCTORISI
FOR ENCLOSURE
SECTION A-A
2 RIGID STEEL CONDUITS FROM
IN-PAVEMENT SENSORS AS
SPECIFIED ON THE LAYOUT SHEET.
INSTALL 1-2" SPARE RIGID STEEL
CONDUIT, THREADED AND CAPPED
AT EACH END.
LIMIT OF CONDUITS INCIDENTAL
TO INSTALL PAD MOUNT ENCLOSURE
IS 24" BEYOND THE EDGE OF THE
CONCRETE BASE.
PAD MOUNT ENCLOSURE (3 OF 3)
I
EXTEND SAW SLOT A
MINIMUM OF 2" BEYOND
THE END OF THE SENSOR.
PIEZO
(SENSOR
PIEZO SENSOR SLOT
SUPPORT
BRACKET
IQ 5" ITYP.I
HOME
RUN
SLOT
PJEZO
SENSOR
I'
PLAN
- BRACKET
IQ 5' ITYP. I
ROADWAY
r SURFACE
PASSIVE CABLE
15°
BACKER ROD
SURFACE
------r- , DEPTH OF TOP OF BACKER ROD
SHALL BE A MINIMUM OF 2' IN
ASPHALT OR CONCRETE.
- GROUT
SURF ACE
PASSIVE CABLE
ENCAPSULATED
IN SEALANT
SENSOR
BRACKET
- BACKER ROD
J-
PASSIVE CABLE
ENCAPSULATED
IN SEALANT
SECTION A-A
GROUT
SECTION B-B
EDGE OF PAVED
SURFACE OR
FACE OF CURB IRES IN SAW SLOT
OM
LDER
IT.
TO JUNCTION BOX
18' MIN. DEPTH
SAW SLOT EDGE OF PAVEMENT TRANSITION
PIEZOELECTRIC SENSOR INSTALLATION
CONDUIT STRAP
ITYP. I �8" 0. C.
GROUNDING BUSHING
IBOTH SIDES)
CABINET HOUSING
CONDUIT ;,o/
ELECTRIC_:1/
CONDUIT TO TELEPHONE
NETWORK INTERFACE
LB CONDULET
CONDUIT WITH
f 18" I
DEVICE IIF REOU!REDI SERVICE POLE WITH METER BASE
AND SERVICE DISCONNECT ISEE
ELECTRICAL SERVICE DET AILI
�- CONDUIT STRAP
ITYP. I �8' 0. C.
MOUNTING BRACKET ITYP. I
MOUNTING STRAP ITYP. I �
3/4' RIGID STEEL CONDUIT
FOR TELEPHONE SERVICE:
14" RIGID STEEL CONDUIT
° FOR ELECTRICAL SERVICE:
� -", ���� 14" RIGID STEEL CONDUIT
GROUND RO
FOR POL 14"
:D. ��H:�� FOR GROUNDING CONDUCTOR
LOCKNUT ITYPI CONDUIT AND c' _,_j 11 J-S)-------'coNDUIT FOR SIGNAL
GROUND ROD
GRO FOR SERVICE
FOR CABINET
!BOTH S f'--l1 WIRES AND CABLE
!NUMBER AND SIZE
AS SPECIFIED OR
REQUIRED BY NECI
36"
POLE .I
FOR SERVIC
LEFT VIE
STEEL POLE MOUNT ENCLOSURE
UNO ROD
POLE
CONDUIT STRAP ITYP.1 WITH
21// WOOD SCREWS 130 0. C. I
GROUNDING BUSHING
!BOTH SIDES!
CABINET HOUSING
CONDUIT ANDV
CONDULETS TO
ELECTRICAL
3/ 4" CONDUIT
WITH GROUNDING
LB CONDULET
CONDUIT AND CONDULETS TO TELEPHONE
NETWORK INTERFACE DEVICE INIDI
21/z" WOOD SCREWS
MOUNTING BRACKET ITYP.1
SERVICE POLE WITH METER BASE
AND SERVICE DISCONNECT !SEE
ELECTRICAL SERVICE DET AILI
r::===::J
MOUNTING STRAP ITYP. I
UNO ROD
14" CONDUIT AND
LB CONDULETS
3/4" CONDUIT WITH
GROUNDING CONDUCTOR
LB CONDULET ITYP.
CONDUIT !NUMBER AND
SIZE AS SPECIFIED OR
REQUIRED BY NECI
35"
21/2" WOOD SCREWS
18" !MIN. I
MOUNTING BRACKET (TYPICAL)
SIZE AND NUMBER/POSITIONS
OF OPENINGS MAY DIFFER
FOR SERV!C
NDUIT INCIDENTAL TO
OUNT ENCLOSURE IS 24"
FROM THE FACE OF THE POLE.
ROUND ROD
V
LEFT VIEW
WOOD POLE MOUNT ENCLOSURE NOT TO SCALE
i
COUNTY OF
ITEM NO. SHEET NO.
GROUND LINE f4"SCHEDULE 80 PVC CONDUIT
IWJTH BUSHING>FOR GROUND
WIRE <EACH BASE>AND SHALL BE
A MIN OF 24"FROM THE EDGE OF
THE POLE BASE.
'i GROUND LINE t z
C) w
0w: i"i'
0:
THE ANCHOR BOLTS AND CONDUITS SHALL NOT BE
PROJECTED MORE 4 INCHES ABOVE A GROUND LINE
BETWEEN THE STRADDLING WHEELS OF A VEHICLE.
BREAKAWAY SUPPORT STUB HEIGHT MEASUREMENT
DUCTED CABLE INSTALLED THROUGH 3"
CONDUIT CROSSINGS TO LUMINAIRE POLE BASE:
INSTALL DUCTED CABLE INTO THE POLE BASE. THE DUCT SHOULD BE EXTENDED
-24•1
•4 A.W.G. SOLID
COPPER GROUND
WIRE
6" MIN.
BRONZE GROUND CLAMP
%" X 8' COPPERWELD
GROUND ROD AND SHALL
BE A MINIMUM OF 48" FROM
THE EDGE OF POLE BASE.
IF DUCTED CABLE INSTALLED BETWEEN POLE
BASES:
INSTALL RIGID STEEL/DUCTED CABLE
9 COUPLING. USE BONDUIT CONDUIT ADHESIVE
z OR APPROVED EQUAL TO CONNECT THE RIGID 0g STEEL TO DUCTED CABLE. RACEWAYS SHALL
I"
ABOVE THE CONDUIT. THE CONDUIT SWEEP
SHOULD BE INSTALL ACCORDING TO THE
MANUFACTURER OF THE DUCTED CABLE TO
PREVENT THE DUCTED CABLE FROM CRIMPING.
FROM GROUND LUG< IN TRANSFORMER
BUSHINGS
■ 4 SOLID BARETCOOPGPREORUNDWILRUEG
> IN TRANSFORMER BASE OR POLE
GROUNDING DETAIL
BE THE SAME SIZE AS THE DUCTED CABLE
C) WHICH ATTACHS TO THE RIGID STEEL � CONDUIT. ALTERNATELY IF DUCTED CABLE
BSHAASFETOR POLE SHAFT
f4"SCHEDULE 80 PVC CONDUIT <WITH BUSHING>FOR GROUND rl2"MIN.J
�"' IRSIGIUDSEDST,EETHLECOCNODNUTIRTACTTOWRO
CTAIMNESINSTTHAELLSIZE WIRE <EACH BASE> CONNECTING BOLT
OF THE DUCT AND RUN THE DUCT INSIDE
THIS CONDUIT. THE SWEEP FOR THE
8w CTOHNEDUBIETNDISNHGALLRADBIEUSINCRREECAOSMEMDENDTEOD ADBHYERTEHETO "
V
TO GROUND ROD
l!lf SPACER PLATES SHALL BE USED TO
--,.-------- PREVENT OPENINGS ON TOP OF BASE.
THEFT DETTERENT DOOR OPENING <LOCATE
z MANUFACTURER OF THE DUCT.
u:
I" CHAMFER
-2•MJN.-
TYPICAL GROUNDING DETAIL
GROUNDING REQUIREMENTS:
CONTRACTOR SHALL PROVIDE A MINIMUM OF 6
17" MIN.
DOOR ON SIDE AWAY FROM ON-COMING
TRAFFIC>
GROUNDING NUT OR LUG
ON BASE FLANGE PLATE
� RACEWAY 11/4"
5fil CONDUIT MIN.
A f ·::�=:::::�·:\.
18" MIN. •• •··':
6' MIN. BELOW !
LOWEST GRADE
4" BELOW GROUND
CHl
INCHES OF GROUND WIRE FOR TESTING PRIOR
TO CONNECTING THE WIRE TO TRANSFORMER
BASE.
POLE/TRANSFORMER BASE GROUND - GROUND
WIRE SHALL COME FROM THE GROUND ROD
THROUGH THE PVC CONDUIT, CONNECTING TO
THE TRANSFORMER BASE/POLE AND THEN TO
L
L,s·MJN._J
STEEL PLATES !4l
MINIMUM OF TWO
a' REQUIRED. IF ONE
� IS A SPARE CONDUIT, V
i3 AN ARROW SHALL
BE ETCHED ON THE TOP
OF THE BASE TO SHOW
THE LOCATION/DIRECTION
OF THE SPARE CONDUIT.
CLASS "A"
CONCRETE-
6-NO. 5 BARS
2" RIGID STEELCONDUIT FOR SERVICE
<WHERE REQUIRED>
EACH RIGID STEEL GROUNDING BUSHING.
NOTES:
ALL CONDUITS USED FOR THE GROUNDING,
SPARES AND CONDUCTORS THAT ARE
INSTALLED IN THE POLE BASE ARE
CONCRETE BASES SHALL BE POURED LEVEL.
NO MORE THAN A "¾• GAP SHALL EXIST BETWEEN
CONCRETE BASE AND TRANSFORMER BASE WHEN THE
POLE IS PLUMBED.
TYPICAL
4-ANCHOR BOLTS
NO. 3 BARS
ALL POLE BASES SHALL HAVE A MINIMUM
OF TWO CONDUITS <NOT INCLUDING
f4"SCHEDULE 80 PVC CONDUIT
TH BUSHING>FOR GROUND
IRE <EACH BASE> AND SHALL BE
A MINIMUM OF 24" FROM POLE BASE.
6-NO. 5 BARS
INCIDENTAL TO BID ITEM '4740". THIS
INCLUDES PROVIDING A MINIMUM OF 24
INCHES OF CONDUIT PAST THE EDGE OF THE
POLE BASE.
CAST ALUMINUM TRANSFORMER BASE
NOT�
THE TRANSFORMER BASE DOOR SHALL HAVE
A 4"BY 6"ARC FLASH WARNING STICKER
INSTALL 3"FROM THE TOP OF THE DOOR.
SPECIAi. IIOTE FOR TRAIISfORUER BASES.
Fi,!NJSH Alt ARC FLASH AICI 5HOCll HAZARD IARIIJIIG S TJCUR OIi TRAIISfORUER BASE 11TH TH[ FOI.LOIIIIG JIIFORMATJOlls VOi.TAG[ 1410 VOi.Tl
CONDUIT>. THE SPARE CONDUIT SHALL BE
180 DEGREE FROM THE CONDUIT FOR THE
CONDUCTORS.
FOUNDATION DETAIL
NOTE: PRECAST CONCRETE
BASES ARE NOT
ACCEPTABLE
THE STICKER SHALL BE METALCRAFT
PLY695 PREM STYLEMARK LABEL WITH
.007 THICKNESS, WITH UV WHITE
POLYCARBINATE MATERIAL, AND WITH
MC53FL PRESSURE SENSTIVE ADHESIVE
OR APPROVAL EQUAL. THIS SHALL BE
INCIDENTAL TO PROJECT.
Ci.OVE CLASS 101
LIUJ TED APPROACH IIOIH)AIIY 141 1111
RESTRICTED APPROACH IIOIH)ARY 111 JIii UlldlUI CLOTH.II«. ARC RATING ICAT 11
SEE IIFPA TOE FOR ADDJTJOIIAI. PP[ REOUJRED
2/18/2025 TRANSFORMER BASE_DETAIL
| Maintenance Contract RFP 5-4-26 (1).pdf |
| STANDARD DETAIL SHEETS |
| GALVANIZED STEEL CABINET DOUBLE POST ASSEMBLY |
| l |
| AND POST ASSEMBLY |
| I: : |
| INDUCTIVE LOOP DETECTOR |
| I:: |
| PIEZOELECTRIC SENSOR INSTALLATION |
| STEEL POLE MOUNT ENCLOSURE |
| 0 |
| BREAKAWAY SUPPORT STUB HEIGHT MEASUREMENT |
| TYPICAL GROUNDING DETAIL |
| TYPICAL |
| CAST ALUMINUM TRANSFORMER BASE |
| FOUNDATION DETAIL |