Drawings.pdf
PDF 8 MB Posted
- Solicitation number
- Y24-733
- Issued by
- Orange County, Orlando City, Florida
About this file
The document is a comprehensive set of mechanical, electrical, and architectural drawings for the Orange County Convention Center South Concourse Command Center Upgrades project in Florida. The drawings, prepared by ADC Architectural Design Collaborative, detail the proposed renovations for upgrading the command center, including mechanical, electrical, and power system modifications. The project involves relocating existing equipment, installing new conduits and wiring, updating lighting and control systems, and implementing new IDF (Intermediate Distribution Frame) cabinets. The project is estimated to cost $214,406.00, with electronic bid submissions due by 4:00 pm EST on Thursday, January 18, 2024, through the ProcureNow OpenGov e-Procurement Platform.
The drawings provide extensive technical specifications for the renovation, including detailed plans for mechanical symbol specifications, demolition plans, proposed floor plans, lighting and power layouts, and electrical details. The scope includes specific requirements for ductwork, electrical systems, fire alarm devices, and cable installations. The project appears to be focused on modernizing and improving the technological infrastructure of the command center, with particular attention to precise equipment placement, wiring configurations, and compliance with building and electrical codes. The documents indicate a comprehensive approach to upgrading the facility's technological capabilities while maintaining existing system functionalities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RETURN GRILLE
LEAVING DRY BULB
KILOWATT
INSIDE DIAMETER
HERTZ (CYCLES PER SECOND)
MAXIMUM
MANUAL DAMPER
NUMBER, NORMALLY OPEN
NOT APPLICABLE
NOT TO SCALE
LOR LIMIT OF REMOVAL
OUTSIDE DIAMETER
OPPOSED BLADE DAMPER
OUTSIDE AIR
OPERATING
REGISTER
RETURN FAN
RETURN AIR
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH
MASTER BUILDING CONTROLLER
THOUSAND BTU PER HOUR
LEAVING WET BULB
SUPPLY AIR
REHEAT COIL
SMOKE/FIRE DAMPER
TEMPERATURE
THERMOSTAT
SUPPLY FAN
VERTICAL
VOLUME DAMPER
WET BULB
VENT, VOLT
THREE WAY BLOW
TWO WAY BLOW
ONE WAY BLOW
WATER PRESSURE DROP
TERMINAL EQUIPMENT CONTROLLER
RELATIVE HUMIDITY
HEATING HOT WATER SUPPLY&RETURN
HOURHR
AND AIR CONDITIONING
HEATING VENTILATINGHVAC
GALLONS PER MINUTE
HORSEPOWER, HEAT PUMP
HAND-OFF-AUTOMATIC
FIRE/SMOKE DAMPER
FEET PER SECOND
GALLONS PER HOUR
FIRE DAMPER, FLOOR DRAIN
ENTERING WET BULB
FEET PER MINUTE
FAHRENHEIT
FEETFT
HHWS&R
HOA
HP
GPH
GPM
FPM
FPS
F/SD
EWB
F
FD
3WB
2WB
1WB
WPD
WB
VERT
V
VD
CHILLED WATER SUPPLY & RETURN
ENERGY MANAGEMENT SYSTEM
EXISTING RETURN GRILLE
DOMESTIC HOT WATER
DISCONNECT
DELIVERY
ENTERING AIR TEMPERATURE
ENTERING
EXHAUST FAN
ELEVATION
EFFICIENCY
ENTERING DRY BULB
EXHAUST AIR, EACH
EAT
ELEV
ERG
ENT
EMS
EDB
EFF
EF
DN
EA
DISC
DHW
DELIV
DOWN
CLEAN OUT
DRY BULB, DOWN BLOW
DOMESTIC COLD WATER
CONDENSATE
BRITISH THERMAL UNIT
BACKFLOW PREVENTER
CUBIC FEET PER MINUTE
CELSIUS, DEGREE CELSIUS
CENTRIFUGAL
CEILINGCLG
DEG
DCW
DB
COND
CO
DEGREE
CHWS&R
CFM
CENT
BTU
BFP
C
SF
TEC
TS
TEMP
S/FD
T
TEMPERATURE SENSOR
RM
SA
RHC
RG
RH
ROOM
REG
RF
RA
PSIG
PSI
NO OR #
OA
OBD
OPER
OD
NTS
MECHANICAL ABBREVIATIONS
AUTOMATIC TEMPERATURE CONTROL
AAV AUTOMATIC AIR VENT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
ACCESS DOOR, AIR DRYER
AIR CONDITIONING UNIT
BACK DRAFT DAMPER
AIR VENT
ACCESS PANEL
AIR PRESSURE DROP
AIR HANDLING UNIT
ALUMINUM
AIR CONDITIONING
ALUM
AV
BOT
BDD
ATC
APD
AP
BOTTOM
AFF
AHU
AFG
ACU
AC
AD
A AIR
MAX
NA
N
MIN
MBH
MBC
MD
NORTH
MINIMUM
LDB
LWB
ID
KW
IN INCH
HZ
EMS ENERGY MANAGEMENT SYSTEM
FLEXIBLE ROUND DUCT
CO CARBON DIOXIDE SENSOR
A-350
FIRE DAMPER AND ACCESS DOOR.
DAMPER, WITH ACCESS DOOR.
COMBINATION FIRE AND SMOKE
ROUND DUCT, DIAMETER SHOWN
F
SD SD
H
T THERMOSTAT OR TEMPERATURE SENSOR
FIRE STAT
SMOKE DETECTOR
HUMIDITY SENSOR
VOLUME DAMPER
SPIN-IN COLLAR WITH
M
BD
FSD
24X12
FD
BACKDRAFT DAMPER
MOTORIZED DAMPER
FIGURE IS SIDE SHOWN
RECTANGULAR DUCT, FIRST
AIR DISTRIBUTION DESIGNATION
EXHAUST AIR REGISTER/GRILLE
RETURN AIR REGISTER/GRILLE
SQUARE SUPPLY AIR DIFFUSER
SIDEWALL REGISTER OR GRILLE
AIR QUANTITY
TYPE
DUCT CONNECTION
FLEXIBLE CONNECTION
CEILING DIFFUSER - SIDE
4-WAY DISCHARGE
SUPPLY AIR DUCT - SECTION
UP
DN
ELBOW TURNED DOWN
CEILING DIFFUSER -
STANDARD BRANCH TAKEOFF
BOTTOM DUCT CONNECTION
FLOOR/CEILING ASSEMBLY
FLOOR/CEILING ASSEMBLY
EXHAUST AIR DUCT - SECTION
SUPPLY DUCT UP THRU ROOF OR
RETURN DUCT UP THRU ROOF OR
RETURN AIR DUCT - SECTION
OFFSET IN DUCTWORK - UP
OFFSET IN DUCTWORK - DOWN
TEE WITH DOUBLE THICKNESS
MANUAL DAMPER
RADIUS ELBOW
MITERED ELBOW - WHERE USED PROVIDE TURNING VANES
ELBOW TURNED UP
DUCTWORK
MECHANICAL SYMBOLS LEGEND
NEW WORK
MECHANICAL LEGEND
-CHILLED WATER SUPPLYCHWS
-CHILLED WATER RETURNCHWR
-CONDENSATE DRAINCD
-REFRIGERANT LIQUIDRL
-REFRIGERANT SUCTIONRS
-GATE VALVE
-BALL VALVE
-CALIBRATE BALANCING VALVE
-BUTTERFLY VALVE
-GAS COOK
-UNION
-STRAINER
-PSI REG.
-CHECK VALVE
-CONNECTION, BOTTOM
-CONNECTION, TOP
-ELBOW, TURNED UP
-ELBOW,TURNED DOWN
-REDUCER, CONCENTRIC
-REDUCER, ECCENTRIC STRAIGHT CROWN
-CAP
SECTION TAG
EXISTING PIPING
NEW PIPING
HWS
HWR
-HOT WATER SUPPLY
-HOT WATER RETURN
HATCH INDICATES DEMO ITEM
EXISTING DUCTWORK AND/OR PIPING
BALL VALVEBV
TYP TYPICAL
DPS DIFFERENTIAL PRESSURE SWITCH
PRESSURE GAUGEPG
WIRE MESH SCREENWMS
SMOKE DAMPER
FIRE/SMOKE DAMPER
FIRE DAMPER
STR MOTOR STARTER
VFD VARIABLE FREQUENCY DRIVE
ENLARGED PLAN TAG, FLOOR PLAN REFERENCE
ENLARGED PLAN REFERENCE
FLOOR PLAN:
ENLARGED PLAN:
SP STATIC PRESSURE SENSOR
M200
M400
M400 A
MECHANICAL SCOPE OF WORK:
1. BALANCE EXISTING TO REMAIN SUPPLY DIFFUSERS AND BALANCE CFM VALUE INDICATED
2. RELOCATION OF EXISTING THERMOSTAT
3. RELOCATION OF EXISTING CONTROL PANEL
4. EXISTING RETURNS AND DIFFUSERS CURRENT LOCATION TO REMAIN FOR RE-USE
MECHANICAL GENERAL NOTES
1. THE CONTRACTOR SHALL DEMONSTRATE EACH HVAC SYSTEMS PERFORMANCE IN THE PRESENCE OF THE ARCHITECT AND THE OWNER'S PROJECT
MANAGER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF ANY ADDITIONAL SYSTEM TEST REQUIRED IF IN THE OPINION OF THE ARCHITECT AND THE OWNERS PROJECT MANAGER THE SYSTEMS DO NOT PERFORM AS SPECIFIED.
2. IF, THE INTENT OF ARCHITECT/ ENGINEER WITH REGARD TO ANY DETAIL IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS WILL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND THE ARCHITECT/ ENGINEER SHALL MAKE CORRECTION OR EXPLANATION IN WRITING. OTHERWISE, NO EXTRA CHARGE WILL BE ALLOWED FOR THE WORK OR MATERIAL WHICH THE ARCHITECT/ENGINEER WILL REQUIRE, PROVIDED THAT IT COMES WITHIN A REASONABLE INTERPRETATION OF THE DRAWINGS AND
SPECIFICATIONS.
3. THE PLANS AND SPECIFICATIONS ARE INTENDED AS A GENERAL DESCRIPTION OF THE WORK TO BE PERFORMED. ALL ITEMS NOT SPECIFICALLY MENTIONED OR SHOWN, BUT NECESSARY FOR THE COMPLETION OF THE INSTALLATION, SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR.
THIS CONTRACTOR SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE MECHANICAL, ARCHITECTURAL AND ELECTRICAL PLANS BEFORE SUBMITTING HIS FINAL BID. NO ADDITIONAL COMPENSATION WILL BE ALLOWED DUE TO THE CONTRACTOR'S FAILURE TO FAMILIARIZE HIMSELF WITH THE PLANS.
4. UNFORESEEN CONDITIONS MAY EXIST AND WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAYBE NECESSARY. IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. SUCH DEVIATIONS MAY NOT BE CONSIDERED AS PART OF THIS CONTRACT WHEN PROPERLY DOCUMENTED IN WRITING. THE PLANS ARE NOT COMPLETELY TO SCALE. CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES ETC PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
5. ALL PIPING AND DUCT IS TO BE CONCEALED ABOVE CEILING OR IN NEW WALLS UNLESS SPECIFICALLY NOTED AS EXPOSED OR SURFACE MOUNTED.
CONTRACTOR TO COORDINATE WITH THE GENERAL CONTRACTOR TO PAINT ALL EXPOSED PIPING TO MATCH CORRESPONDING EXPOSED AREAS.
6. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE AND ALL LOCAL CODES.
7. THE SIZE AND LOCATION OF EQUIPMENT INSTALLED UNDER DIVISION 23 MECHANICAL SHALL BE COORDINATED WITH OTHER TRADES. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED
FOR EQUIPMENT FURNISHED.
8. PROVIDE A VOLUME DAMPER AT EVERY BRANCH DUCT AND AS SHOWN ON THE DOCUMENTS FOR ALL DUCTWORK SYSTEMS. ALL DAMPERS MAY NOT BE
SHOWN ON THE DOCUMENTS FOR CLARITY.
9. VERIFY EXISTING CONDITIONS IN FIELD AND COORDINATE WITH ALL TRADES INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL, LIGHTING, POWER, SYSTEMS, PLUMBING, FIRE PROTECTION AND OTHER EXISTING AND NEW WORK.
10. INTERRUPTION OF EXISTING SERVICES SHALL BE MINIMAL AND SHALL BE FULLY COORDINATED WITH THE OWNER AND ALL TRADES IN ADVANCE TO
SCHEDULE ALL INTERRUPTIONS DURING NON-CRITICAL TIMES.
11. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION. SUPPORT ALL OBJECTS FROM STRUCTURE WITHOUT PENETRATING THE CEILING.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH NFPA 90A AND 90B.
14. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSIONS.
15. BEFORE FABRICATION, VERIFY AND COORDINATE ALL DIMENSIONS IN FIELD. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL
SUIT EQUIPMENT FURNISHED.
16. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDING DUCTS) AND TRANSITIONS
AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.
17. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES UPSTREAM OF SPLIT.
18. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING AND MAINTENANCE OF ALL
MECHANICAL EQUIPMENT.
19. ALL DUCT BENDS FROM VERTICAL TO THE HORIZONTAL AND ANGLED TURNS OF DUCTWORK SHALL HAVE LONG RADIUS ELBOWS INSTALLED.
20. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS
TO ALLOW FOR INSPECTIONS OF RATED WALLS.
21. DIFFUSER NECKS SHALL MATCH SIZES OF FLEX DUCTS TO BE CONNECTED.
22. FLEXIBLE DUCTWORK SHALL BE FULLY EXTENDED NOT TO EXCEED 8'-0" IN LENGTH.
23. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.
24. COORDINATE WITH ARCHITECT BEFORE PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION DEVICES TO VERIFY
FINISH.
25. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT BLACK.
26. ALL SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED GALVANIZED STEEL. DUCTWORK SHALL BE SUPPORTED WITH MINIMUM 1" SHEET METAL
STRAPS AT 5'-0" ON CENTERS.
27. PROVIDE FIRE DAMPERS AT EACH FIRE RATED WALL PENETRATION OF ALL AIR SUPPLY, RETURN, EXHAUST AND VENTILATION DUCTS. IF NOT SHOWN ON THE DOCUMENTS THIS MUST BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BID.
28. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING MATERIALS, EQUIPMENT, APPLIANCES AND DEVICES THAT ARE TO BE REUSED SHALL BE RECONDITIONED, TESTED AND PLACED IN GOOD AND PROPER WORKING CONDITION AND APPROVED. ANY DISCREPANCIES MUST BE BROUGHT TO THE
ATTENTION OF THE ENGINEER PRIOR TO BID.
29. ALL EQUIPMENT SHALL BE FREE OF ANY DAMAGE AT THE TIME OF ACCEPTANCE. ALL DENTS, SCRATCHES, AND ANY OTHER DAMAGE MUST BE REPAIRED
PRIOR TO THE INSTALLATION OF THE EQUIPMENT.
30. ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH EXTERNALLY WRAPPED INSULATION AND INSTALLED PER SMACNA GUIDELINES.
DUCTS/MATERIALS SHALL BE PROPERLY STORED, PROTECTED FROM MOISTURE, DUST AND DEBRIS, AND INTERIORS CLEANED PRIOR TO INSTALLATION.
31. ALL SUPPLY, RETURN, EXHAUST, AND OUTSIDE AIR BRANCH OR RUN-OUT DUCTS SHALL BE PROVIDED WITH MANUAL DAMPERS FOR AIR VOLUME
CONTROL AND ADJUSTMENT.
32. AIR HANDLING AND DUCTWORK SYSTEMS SHALL BE PROTECTED FROM CONSTRUCTION DUST AND WEATHER DURING THE CONSTRUCTION PERIOD.
AFTER CONSTRUCTION, SYSTEMS SHALL BE OBSERVED BY THE ENGINEER AND CLEANED BY CONTRACTOR IF NECESSARY.
33. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR COORDINATING HIS/HER WORK WITH THE TEST AND BALANCE FIRM. PRIOR TO TEST AND BALANCE, THE CONTRACTOR SHALL START-UP, PRE-BALANCE, AND REPLACE ALL AIR FILTERS FOR EVERY AHU BEING TESTED. ALL DISCREPANCIES, DRIVE CHANGES, ETC. REPORTED BY ENGINEER OR TEST AND BALANCE FIRM SHALL BE CORRECTED BY CONTRACTOR WITHIN FIVE CALENDAR DAYS AT NO ADDITIONAL COST. TEST AND BALANCE SHALL BE COMPLETED PRIOR TO SUBSTANTIAL COMPLETION. THE TEST AND BALANCE SHALL BE INCLUDED IN CONTRACTOR'S
SCOPE OF WORK.
34. OPERATION AND MAINTENANCE MANUALS SHALL INCLUDE AS A SEPARATE SUBMITTAL ITEM A LIST OF ALL EQUIPMENT INSTALLED, AND PREVENTATIVE MAINTENANCE REQUIREMENTS ALONG WITH TIME SCHEDULE(S) FOR EACH ITEM. THE SEQUENCE OF OPERATION SHALL ALSO INCLUDE A DEFINITIVE SEQUENCE OF OPERATION OF THE MECHANICAL SYSTEM AND COMPONENTS AS THEY FUNCTION INTEGRALLY AND INDEPENDENTLY WITH THE SYSTEM.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING TRANSFERRING CONTROL OF THE SYSTEM TO THE OWNER ENERGY CONTROL DEPARTMENT PRIOR TO FINAL CLOSEOUT OF THE PROJECT. THIS IS REQUIRED PRIOR TO ISSUANCE OF ANY FORM OF OCCUPANCY CERTIFICATE
35. THE HVAC SYSTEMS SHOULD BE TESTED AND BALANCED UNDER THE DIRECTION OF A PROFESSIONAL ENGINEER OR BY AN AABC OR NEBB CERTIFIED TEST AND BALANCE CONTRACTOR EMPLOYED BY THE CONSTRUCTION MANAGER. TEST AND BALANCE SHALL BE COMPLETED PRIOR TO SUBSTANTIAL COMPLETION. THE TEST AND BALANCE SHALL BE INCLUDED IN CONTRACTOR'S SCOPE OF WORK.
36. THE OWNER RESERVES THE RIGHT TO PROVIDE VERIFICATION OF THE TEST AND BALANCE REPORTS AND SUCH VERIFICATION SHALL BE BY A SECOND INDEPENDENT BALANCER. REPORTS FOUND TO BE INACCURATE WILL BE DISALLOWED AND THE BALANCER WILL BE REQUIRED TO REPEAT OPERATIONS UNDER THE SUPERVISION OF THE SECOND INDEPENDENT BALANCER UNTIL ACCURATE REPORTS ARE COMPLETED AND AGREED UPON. THE COST OF INITIAL CHECKING WILL BE BY THE CONTRACTOR, UNLESS THE INITIAL REPORT IS FOUND TO BE INACCURATE AND/OR INCOMPLETE. IN SUCH CASE, THE COSTS OF THE VERIFICATION TEST AND BALANCE AND ALL SUBSEQUENT COSTS OF SUPERVISION IN ORDER TO SECURE ACCEPTABLE REPORTS WILL BE
BY THE BALANCER.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:3 8''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
MECHANICAL SYMBOL SPECIFICATIONS
M001
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text 2022-538
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text OCCC S CONCOURSE COMMAND CENTRAL ALTERATION 9800 INTERNATIONAL DRIVE ORLANDO, FL 32819
166 CFM
(TYP.3)
METASYS
CONTROL
PANEL
T VA
V-
B x8
10x6 x8 x8
1 T
VAV-C
14x6 x6
8Ø
20x10
1. RELOCATE EXITING THERMOSTATS AS REQUIRED. SEE RENOVATION PLANS
FOR NEW LOCATIONS.
2. REMAIN EXISTING DIFFUSERS AS REQUIRED
3. RELOCATE EXISTING CONTROL PANEL AS REQUIRED. CONTRACTOR TO FIELD
VERIFY NEW LOCATION AND COORDINATE WITH WITH EXISTING FURNITURE
AND EQUIPMENT.
PLAN KEY NOTES:#
GENERAL NOTES:
A. REFER TO SHEETS M001 AND M002 FOR MECHANICAL GENERAL NOTES AND
SYMBOLS LEGEND.
B. COORDINATE WORK SCHEDULE WITH PROJECT MANAGER. DISRUPTION OF
COOLING TO THE ADJACENT SPACES OR CAMPUS IS NOT ALLOWED.
C. DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL LAYOUT OF
MECHANICAL COMPONENTS, FOR EXACT BUILDING DIMENSIONS SEE
ARCHITECTURAL AND STRUCTURAL DRAWINGS.
D. COORDINATE DUCTWORK ROUTING WITH ALL TRADES.
E. LOCATE EQUIPMENT SO THAT MANUFACTURERS SERVICE CLEARANCES ARE
MAINTAINED.
F. COORDINATE WITH ELECTRICAL CONTRACTOR LOCATION OF DISCONNECTS. DO
NOT BLOCK SERVICE CLEARANCE TO EQUIPMENT.
G. DUCTWORK SHALL REMAIN SEALED DURING CONSTRUCTION. .IF DUCTWORK IS
LEFT UNCOVERED DURING CONSTRUCTION, CONTRACTOR WILL BE REQUIRED
TO CLEAN ALL DUCTWORK PRIOR TO UNIT START-UP.
H. EXISTING DUCTWORK IS SHOWN AS REFERENCE ONLY, AND FOR TEST AND
BALANCE PURPOSE.
I. CONTRACTOR SHALL SEAL ALL WALL PENETRATIONS.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:3 8''
File Name
Drawn By:
Checked By
AR
CH
IT
EC
TU
RE
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023
Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
MECHANICAL DEMO FLOOR PLAN
MD201
N
00 8' 16'4'SCALE: 3/8"=1'-0"
MECHANICAL DEMO FLOOR PLAN
AutoCAD SHX Text
CONSOLE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.7
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.5
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text 2022-538
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
174 CFM
240 CFM
(TPY.3)
VA
V-
B
VAV-C
x8
10x6
14x6 x6
8Ø x8 x8
20x10
METASYS
CONTROL
PANEL
T
T
(E)
6"Ø
6"Ø
GENERAL NOTES:
PLAN KEY NOTES:
A. REFER TO SHEETS M001 AND M002 FOR MECHANICAL GENERAL NOTES AND
SYMBOLS LEGEND.
B. COORDINATE WORK SCHEDULE WITH PROJECT MANAGER. DISRUPTION OF
COOLING TO THE ADJACENT SPACES OR CAMPUS IS NOT ALLOWED.
C. DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL LAYOUT OF
MECHANICAL COMPONENTS, FOR EXACT BUILDING DIMENSIONS SEE
ARCHITECTURAL AND STRUCTURAL DRAWINGS.
D. COORDINATE DUCTWORK ROUTING WITH ALL TRADES.
E. LOCATE EQUIPMENT SO THAT MANUFACTURERS SERVICE CLEARANCES ARE
MAINTAINED.
F. COORDINATE WITH ELECTRICAL CONTRACTOR LOCATION OF DISCONNECTS. DO
NOT BLOCK SERVICE CLEARANCE TO EQUIPMENT.
G. DUCTWORK SHALL REMAIN SEALED DURING CONSTRUCTION. .IF DUCTWORK IS
LEFT UNCOVERED DURING CONSTRUCTION, CONTRACTOR WILL BE REQUIRED
TO CLEAN ALL DUCTWORK PRIOR TO UNIT START-UP.
H. EXISTING DUCTWORK IS SHOWN AS REFERENCE ONLY, AND FOR TEST AND
BALANCE PURPOSE.
I. CONTRACTOR SHALL SEAL ALL WALL PENETRATIONS.
1. REMAIN EXISTING SUPPLY DIFFUSERS AND BALANCE TO CFM VALUE INDICATED.
2. RELOCATED EXISTING THERMOSTAT AS REQUIRED.
3. RELOCATE EXISTING CONTROL PANEL. PROPOSED LOCATION IS APPROXIMATE.
CONTRACTOR TO FIELD VERIFY NEW LOCATION AND COORDINATE WITH EXISTING
FURNITURE AND EQUIPMENT.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:3 8''
File Name
Drawn By:
Checked By
AR
CH
IT
EC
TU
RE
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023
Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
MECHANICAL FLOOR PLAN PROPOSED
M201
N
00 8' 16'4'SCALE: 3/8"=1'-0"
MECHANICAL FLOOR PLAN PROPOSED
AutoCAD SHX Text
CONSOLE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.7
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.5
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text 2022-538
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:3 8''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
MECHANICAL DETAILS
M801
DUCT TO SUPPLY DIFFUSER CONN. DETAIL
CEILING
SUPPLY AIR DUCT
SECURE FLEX DUCT TO
DIFFUSER NECK USING
STAINLESS STEEL CLAMP OR
PANDUIT STRAP
UL 181, CLASS 1 FLEX DUCT
MAXIMUM LENGTH 7 FEET
2" WIDE GALVANIZED STEEL
FLEX DUCT SUPPORT STRAP
SPIN IN FITTING W/MANUAL
VOLUME DAMPER
SEAL FLEX TO DUCT USING
TIMA APPROVED DUCT TAPE
OR GLASS FABRIC & MASTIC
STAINLESS STEEL BAND
OR PANDUIT STRAP
2" BATT INSULATION WITH FOIL
VAPOR BARRIER ON OUTSIDE
SEAL INSULATION TO FLEX DUCT AND
DIFFUSER USING TIMA APPROVED DUCT
TAPE TO MAINTAIN VAPOR BARRIER
NOT TO SCALE
DIFFUSER- SEE PLAN AND
SCHEDULE FOR TYPE
SUPPLY DUCT
SPIN-IN FITTING
WITH DAMPER INSULATED ROUND FLEXIBLE
DUCT (MAX. 6'-0" LONG) SIZE
TO MATCH DIFFUSER NECK.
INSULATION
CEILING DIFFUSERCEILING
ROUND METAL DUCT
(EXTERNAL INSULATION)
CEILING DIFFUSER RUNOUT DETAIL
NOT TO SCALE
M8.01
60" MAX
HANGER STRAPS DUCT
HANGER STRAPS
DUCT HANGING DETAIL
NOT TO SCALE
SUPPORT BY EXISTING
STRUCTURE
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text 2022-538
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
TV
TV
LIGHTING FIXTURES
POWER DEVICES
SINGLE RECEPTACLE
JUNCTION BOX
DUPLEX RECEPTACLE
DISCONNECT SWITCH
DOOR BELL PUSH BUTTON
EQUIPMENT CONNECTION
SPECIAL PURPOSE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE
PHOTOCELL
DOOR BELL
TIMECLOCK
TRANSFORMER
DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
DUPLEX RECEPTACLE, GROUND FAULT
SINGLE 250V NON-LOCKING TYPE RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, HALF SWITCHED
MOTOR
120/208V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, SURFACE MOUNT
POWER/DATA POLE
PULL BOX
CEILING MOUNTED RECEPTACLE
RECESSED FLOOR RECEPTACLE
FLOOR MOUNTED JUNCTION BOX
120/208V PANELBOARD, RECESSED
277/480V PANELBOARD, RECESSED
FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
STARTER/DISCONNECT SWITCH
GENERATOR
CLOCK
LOCKBOX
DUPLEX RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP) WEATHERPROOF
"IN USE" COVER. TAYMAC MX3200 OR EQUAL
DUPLEX RECEPTACLE, GROUND FAULT
LOCATE WITHIN ELECTRIC WATER COOLER PER
MANUFACTURER'S INSTRUCTIONS
DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION
DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF. LOCATE IN
COMMON BOX WITH CCTV
DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF UNLESS
NOTED OTHERWISE.
AIR TERMINAL (ALUMINUM CLASS 1 MIN).
ROOFTOP MAIN CONDUCTOR, RUN EXPOSED ACROSS
ROOF.
DOWN CONDUCTOR, RUN CONCEALED IN STRUCTURE -
COPPER CLASS 1
COPPER-CLAD DRIVEN GROUND ROD AND TEST WELL.
SEE SPECIFICATIONS.
BOLTED 3-WAY SPLICE
BOLTED 4-WAY SPLICE
GROUND BUS BAR
GROUND ROD WITH TEST INSPECTION WELL. SEE
SPECIFICATIONS.
PIR-WALL SWITCH DECORATOR MOTION SENSOR, 120/277 VAC,
800/1200W. WATTSTOPPER PW-100 OR EQUAL.
DUAL ULTRASONIC/PIR-WALL SWITCH DECORATOR MOTION SENSOR,
120/277VAC, 800/1200W. WATTSTOPPER DW-100 OR EQUAL.
*DUAL ULTRASONIC/PIR-CEILING MOUNT SENSOR, 24 VDC/VAC,
35mA. WATTSTOPPER DT-305 OR EQUAL.
*DUAL ULTRASONIC/PIR-WALL MOUNT SENSOR, 24 VAC/VDC, 35mA.
WATTSTOPPER DT-205 OR EQUAL.
POWER PACK 120/277 VAC; 20 AMPS, 225mA SECONDARY.
WATTSTOPPER BZ-250 OR EQUAL.
*PIR-WALL MOUNT SENSOR, LOW TEMP, 24 VDC/AC, 20mA.
WATTSTOPPER CB-100 OR EQUAL.
*PIR-CEILING MOUNT SENSOR 24 VDC/VAC, 11mA, WATTSTOPPER
CI-205 OR EQUAL.
QUAD RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP) WEATHERPROOF "IN USE"
COVER. TAYMAC MX 6200 OR EQUAL.
TRACK FIXTURE
CEILING MOUNTED RECESSED, DOWN LIGHT
EMERGENCY LIGHT FIXTURE
2'x4' FIXTURE
1'x4' FIXTURE
2'x2' FIXTURE
SURFACE MOUNTED LIGHTING FIXTURE
2'x4' FIXTURE, BATTERY/EMERGENCY
2'x2' FIXTURE, BATTERY/EMERGENCY
1'x4' FIXTURE, BATTERY/EMERGENCY
FLOOD LIGHT FIXTURE
BOLLARD OR PENDANT LIGHT FIXTURE
POWER DISTRIBUTION
LIGHTING CONTROL DEVICES
LIGHTNING PROTECTION
MISCELLANEOUS SYMBOL LEGEND
ABBREVIATIONS
AMPERES
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW FINISHED GRADE
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ELECTRICAL METALLIC TUBING
BELOW FINISHED CEILING
EWH
FLUOR
FA
EXIST
EXH
EQUIP
EWC
EUH
EMT
EF
FLUORESCENT
FIRE ALARM
EXHAUST
EXISTING
EXHAUST FAN
EQUIPMENT
CLG
DISC
DWG
EA
CU
CL
CAB
CKT
BFG
CEILING
CENTERLINE
DISCONNECT(ING)
DRAWING(S)
EACH
COPPER
CABINET
CIRCUIT
CONDUIT
AFG
BFC
A
AFF
NATIONAL ELECTRICAL CODE
POLYVINYL CHLORIDE
UNLESS OTHERWISE NOTED
XFMR
V
WP
VA
TEL
UON
TRANSFORMER
TELEPHONE
VOLT-AMPERES
WEATHER PROOF
VOLTS
PVC
PNL
REC
NEC
MTR
MTG
MTD
MISC
MIN
RECEPTACLE
PANEL
MINIMUM
MISCELLANEOUS
MOUNTED
MOUNTING
MOTOR
HEATING/VENTILATING/
KILO-VOLTS-AMPERES
KILO-WATT-HOURS
MOTOR CONTROL CENTERMCC
MH
MFR
MAX
LTG
kVA kWH kW kV
JB
METAL HALIDE
LIGHTING
MANUFACTURER
MAXIMUM
JUNCTION BOX
KILO-VOLTS
KILO-WATTS
HVAC
HV
INC
HP HORSEPOWER
HIGH VOLTAGE
INCANDESCENT
FLA FULL LOAD AMPERES
ABOVE FINISHED CEILINGAFC
W WATTS
TYP TYPICAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CURRENT TRANSFORMERSCT's
KILO-VOLTS-AMPERES REACTIVEkVAR
RGS RIGID GALVANIZED STEEL
C m METER mm MILLIMETER
AIC AMPERES INTERUPTING
CAPACITY
MCB MAIN CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
AIR CONDITIONING
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
HIGH PRESSURE SODIUM
HID
HOA
HPS
GND
HGT
GROUND
HEIGHT
GFP GROUND FAULT PROTECTION
VFD VARIABLE FREQUENCY DRIVE
AMERICAN WIRE GAUGEAWG
PULL STATION INSIDEPSI
EXP EXPLOSION PROOFAUDIO ENHANCEMENTAE
1R1-1,3,5
1M1-1:3:5
1R1-1
1M1-1:3
1R1-1,3
4' WALL MOUNT FIXTURE
4' WALL MOUNT FIXTURE, EMERGENCY
CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT
BOLLARD OR PENDANT LUMINAIRE, EMERGENCY
WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY
POLE MOUNTED LUMINAIRE
SINGLE POLE MOUNT LUMINAIRE-RECTANGLES INDICATE
NUMBER OF FIXTURES
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT, SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE CIRCUIT:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE
SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
E200
TITLE
SCALE: DETAIL TITLE REFERENCE
DETAIL NUMBER
SHEET NUMBER WHERE DETAIL IS REFERENCED
ADDITIONAL SHEET REFERENCES
E200
DETAIL NUMBER
SHEET NUMBER TO WHERE DETAIL IS REFERENCED
XX.XX
XX
WP
WP
EWC
CEILING MOUNTED RECESSED, WALL WASHER (ARROW
INDICATES DIRECTION OF WASH)
SINGLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
DOUBLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
POLE MOUNTED SITE LIGHTING FIXTURE RECTANGLES INDICATE
NUMBER OF FIXTURES
PC
TC
C
QUAD RECEPTACLE, GROUND FAULT
C
POWER POLE
J
J
PB
C
ST
DB
G
ALUMINUMAL
P
PD
PP
T
DN
SPD SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.
SPD SURGE PROTECTION DEVICE
ECB
MMS
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH
LT
R9
PP
W
CI
DT
S
D1
C
NOTIFICATION APPLIANCE CIRCUIT
*ULTRASONIC-CEILING CORRIDOR MOTION SENSOR, 24 VDC/VAC,
40mA. WATTSTOPPER WT-2250 OR EQUAL.
NAC
SWITCH, 1 POLE, LETTER INDICATES SWITCHLEG CONTROLLED.
SWITCH, KEYSWITCH
S3 4S
S
PS
2S
SWITCH
a
SWITCH, 2 POLE
S
SWITCH, 3-WAY
SWITCH, 4-WAY
KS
SWITCH - PILOT LIGHT
MS
S
MOTOR RATED SWITCH
S
SWITCH, 3-WAY, LETTER INDICATES SWITCHLEG CONTROLLED
SWITCH, KEYSWITCH, 3-WAY
NIGHT LIGHT, UNSWITCHEDNL
*FOR LOW VOLTAGE OCCUPANCY SENSORS, PROVIDE POWER
PACK(S) 120/277 VAC; 20 AMPS, 225mA SECONDARY AS NEEDED FOR
ZONE/AREA CONTROL. WATTSTOPPER BZ-250 OR EQUAL.
SWITCHES
SWITCH - LINE VOLTAGE TIMER, 120/277 VAC. WATTSTOPPER
TS-400 OR EQUAL.
DUAL ULTRASONIC/PIR-DUAL RELAY WALL SWITCH DECORATOR
MOTION SENSOR, 120/277VAC, 800/1200W. WATTSTOPPER DW-200 OR
EQUAL.
D2
S SWITCH, EXPLOSION PROOF
QUAD RECEPTACLE FOR COMPUTER WORKSTATION
C
4' STRIP FIXTURE
4' STRIP FIXTURE, BATTERY/EMERGENCY
4' STRIP FIXTURE, WALL MOUNTED
4' STRIP FIXTURE, WALL MOUNTED,
BATTERY/EMERGENCY
3a
3K
EXP
LB
VARIABLE FREQUENCY DRIVEVFD
UL 924 LISTED FAILSAFE EMERGENCY SWITCHING RELAY, LVS EPC-A
OR EQUAL. LOWER CASE LETTER NEXT TO DEVICE INDICATES
SWITCHLEG CONTROLLED.
LVS
S SWITCH, LOW VOLTAGE MOMENTARYL
TS
SWP
SWITCH, WEATHERPROOF
LIGHTING CONTACTORLC
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
ELECTRICAL SYMBOL SPECIFICATIONS
E001
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
WAP
EXEX
EX
EX
EX
EX
EX
EX
1 1 1
1 1
1 1
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ITEMS SCREENED ARE EXISTING TO REMAIN. ITEMS IN FULL PEN
WEIGHT SHALL BE DEMOLISHED
PLAN KEY NOTES:
1. CONTRACTOR TO REMOVE ALL DEVICES, WIRING, AND CONDUIT
BACK TO THE SOURCE.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
LIGHTING DEMO PLAN
ED201
N
00 8' 16'4'SCALE: 3/8"=1'-0"
LIGHTING DEMO PLAN
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
EX EX
EX
EX
EX
EX
EXEXEX
EX
EX
J
1AELC-13,15
1AELC-11
1AELC-17
1AELC-25
1AELC-19
1AELC-21
1AELC-23
F
F
F S
F
2 2
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ITEMS SCREENED ARE EXISTING TO REMAIN. ITEMS IN FULL PEN
WEIGHT SHALL BE DEMOLISHED
PLAN KEY NOTES:
1. CONTRACTOR TO REMOVE EXISTING FIRE ALARM DEVICES
CONTRACTOR TO PROTECT EXISTING FIRE ALARM CIRCUIT TO BE
REUSED.
2. CONTRACTOR TO REMOVE ALL DEVICES, WIRING, AND CONDUIT
BACK TO THE SOURCE.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
POWER DEMO PLAN
ED301
N
00 8' 16'4'SCALE: 3/8"=1'-0"
POWER DEMO PLAN
AutoCAD SHX Text
CONSOLE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.7
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.5
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
MATCH
LINE
MATCH
LINE
1APC
1AEHC
1AEPC
1AELC
ELECTRICAL ROOM
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
EXHIBIT LEVEL 1
E101
N
00 8' 16'4'SCALE: 3/8"=1'-0"
EXHIBIT LEVEL 1
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
WAP
EXEX
EX
EX
EX
EX
EX
EX
S
3S
A
AA
A
A
A
A
1 1
A
A
A
A
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
f. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
g. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
h. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
i. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
j. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
PLAN KEY NOTES:
1. CONTRACTOR TO REUSE EXISTING LIGHTING CIRCUIT. EXTEND
EXISTING CIRCUIT (CONDUIT AND WIRING AS NEEDED). CONTRACTOR
TO REPROGRAM EXISTING LIGHTING SYSTEM COMBINING THE TWO
ROOMS. ALL FIXTURES SHALL BE CAPABLE OF DIMMING
CONTRACTOR TO PROGRAM DIMMING.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
LIGHTING PLAN RCP
E201
N
00 8' 16'4'SCALE: 3/8"=1'-0"
LIGHTING PLAN RCP
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
1AELC-13
1AELC-17
1AELC-25
1AELC-19
1AELC-21
1AELC-23
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
1AELC-15
75CD S
J4
+68"
+68"
+68"
+68"
+58"
+58"
S4
1AELC-34
NEW IDF
CABINET
1AELC-36:38
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
f. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
g. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
h. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
i. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
j. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW CONDUIT AND WIRING
FOR POWER AND DATA FOR MONITORS. CONTRACTOR REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT LOCATION AND HEIGHTS OF
MONITORS.
2. CONTRACTOR TO PROVIDE AND INSTALL NEW CONDUIT AND WIRING
FOR POWER AND DATA AT NEW CONTROL CONSOLE. ALL CONDUIT
TO BE INSTALLED ON EXISTING COLUMN UNTIL NEW CONSOLE
CABINET. CONTRACTOR TO INSTALL CONDUIT AND WIRING IN
CONSOLE SO THAT IT IS CONCEALED FROM VIEW.
3. CONTRACTOR TO CONNECT NEW FIRE ALARM DEVICES INTO
EXISTING CIRCUIT. CONTRACTOR TO PROVIDE ALL CONDUIT,WIRING,
AND FIRE ALARM DEVICES AS NEEDED.
4. CONTRACTOR TO INSTALL CONDUIT AND WIRING ON THE COLUMN
FOR THE POWER AND DATA TO THE CONSOLE.
5. PROVIDE AND INSTALL NEW IDF CABINET. CONTRACTOR TO INSTALL
FIBER TO NEAREST IDF CABINET.
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
POWER PROPOSED PLAN
E301
N
00 8' 16'4'SCALE: 3/8"=1'-0"
POWER PROPOSED PLAN
AutoCAD SHX Text
CONSOLE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.7
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 6-113.5
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
PANEL SCHEDULES
E701
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
* NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2002
EDITION OF THE UL FIRE RESISTANCE DIRECTORY
1. Wall Assembly - The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 in. deep channels spaced max 24 in. OC.
B. Gypsum Board* - Nom 5/8 in. thick, 4 ft. wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual Wall and Partition Design. Diam of circular through opening cut through gypsum wallboard on each side of wall assembly to be min 0 in. (point contact) to max 1 in. larger than outside diam of flexible metal conduit (Item 2) installed in through opening. Side edge of circular opening to be min 3 in.
from nearest stud in wall cavity.
C. Fasteners - When wood stud framing is employed, gypsum wallboard attached to studs with cement coated nails as specified in the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self-drilling, self-tapping bugle-head steel screws as specified in the individual Wall or Partition Design.
2. Through Penetrating Product* - Flexible Metal Conduit - Nom 4 in. diam (or smaller) aluminum or steel Flexible Metal Conduit+. Max one flexible metal conduit to be installed near center of circular opening in gypsum wallboard. Flexible metal conduit to be rigidly supported on both sides of wall assembly.
AFC CABLE SYSTEMS INC
3. Fill,Void or Cavity Material* - Caulk - Caulk fill material forced into annular space around entire circumference of through penetrating product to completely fill opening in gypsum wallboard layers on each side of the wall assembly. A min 5/8 in.
thickness of caulk is required for the 1 hr F Rating. A min 1-1/4 in. thickness of caulk is required for the 2 hr F Rating.
MINNESOTA MINING & MFG CO - CP 25WB+
*Bearing the UL Classification Marking
F RATINGS-- 1 AND 2 HR (SEE ITEM 3)
T RATING-- 0 HR
L RATING AT AMBIENT--LESS THAN 1 CFM/sq ft L RATING AT 400° F--LESS THAN 1 CFM/sq ft
SYSTEM NO. W-L-1017
A
A
1C
1B
1A
SECTION A-A
SECTION A-A
1 44
A
A
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening ) is 27-1/4 in. (692 mm).
See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers.
1A. Steel Sleeve — (Optional, Not Shown) - Nom 28 in. (711 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. As an alternate, nom 28 in. (711 mm) diam (or smaller) sleeve fabricated from nom 0.028 in. (0.71 mm) thick galv steel cast or grouted into floor or wall assembly flush with floor or wall surfaces.
2. Through-Penetrant — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (point contact) to max 3-1/4 in. (83 mm) is required within the firestop system . When optional steel sleeve is used, min annular space shall be 1/2 in. (13 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe — Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).
B. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or nom 6 in. (152 mm) diam (or smaller) steel conduit.
C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, tubing diam shall not exceed nom 4 in.
(102 mm).
D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 4 in. (102 mm).
E. Iron Pipe — Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).
3. Packing Material — Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material.
3A. Forming Material* — As an alternate to the packing material in Item 3, nom 4 in. (102 mm) wide strips of min 1/2 in (13 mm) thick compressible mat to be stacked to a thickness greater than the width of the annular space and compression-fitted, edge-first, to fill the annular space to a min 4 in. (102 mm) depth. Top of forming material to be recessed from top surface of floor or steel sleeve or from both surfaces of wall or steel sleeve in wall as necessary to accommodate the required thickness of caulk fill material.
3M COMPANY 3M FIRE PROTECTION PRODUCTS — Fire Barrier Packing Material
4. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within annulus, flush with top surface of floor or both surfaces of wall assembly. At the point contact location between pipe and concrete, a min 1/2 in. (13 mm) diam bead of sealant shall be applied at the concrete/pipe interface on the top surface of floor and on both surfaces of wall assembly.
3M COMPANY 3M FIRE PROTECTION PRODUCTS — Types FB-2000, FB-2000+, FB-1000 NS, FB-1003 SL or
FB-3000 WT.
(Note - W Rating applies only when FB-1000 NS, FB-1003 SL or FB-3000 WT Sealant is used.)
*Bearing the UL Classification Mark
System No. C-AJ-1058 May 09, 2013
ANSI/UL1479 (ASTM E814)
F Rating — 3 Hr T Rating — 0 Hr
L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT
L RATING AT 400 F — LESS THAN 1 CFM/SQ FT
W RATING — CLASS 1 (SEE ITEM 4)
System No. C-AJ-1058 May 09, 2013
CAN/ULC S115
F Rating — 3 Hr
FT Rating — 0 Hr FH Rating — 3 Hr
FTH Rating — 0 Hr
L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT L
RATING AT 400 F — LESS THAN 1 CFM/SQ FT
BUNDLED VOICE/DATA PDS CABLING, RUN
FROM CABLE TRAY, THROUGH
PENETRATION
FIRE-RATED
PARTITION
4" EMT SLEEVE
CABLE TIE
SECTION THOUGH RATED WALL
UL LISTED FIRE-WALL PENETRATION ASSEMBLY, WIREMOLD
"FLAMESTOPPER FS-4" SERIES, STI "EZ PATH SYSTEM" OR
APPROVED SUBSTITUTE
ADJUSTING
SCREWS (2)
INTEGRAL INTUMESCENT
FIRESTOPPING MATERIAL
FRONT VIEW ISOMETRIC VIEW
4" EMT SLEEVE
Consultant ● Seal/Signature
Sheet Title:
Project Number:
2022-538
Scale:38''
File Name
Drawn By:
Checked By
AR
CH
ITE
CT
UR
E
PL
AN
NI
NG
IN
TE
RI
OR
D
ES
IG
N
SP
AC
E
PL
AN
NI
NG
Issue Date:09/18/2023 Project Status:
100% CONSTRUCTION DOCUMENTS
PR
IN
TE
D
ON
Client Information
ADCARCHITECTURAL DESIGN COLLABORATIVE
Architect ● Seal/Signature
Issue
Project Documents for:
Date Issue Description
Project:
Check By
945 N. PENNSYLVANIA AVENUE
WINTER PARK, FLORIDA 32789
OFFICE: (407) 629-1188
FAX: (407) 388-1220
WWW. ADCINTERNATIONAL.NET
2022-538
ELECTRICAL DETAILS
E801
AutoCAD SHX Text
MC CABLE THRU GYP BOARD PENETRATION DETAIL
AutoCAD SHX Text No Scale
AutoCAD SHX Text
AutoCAD SHX Text
EMT THRU CONCRETE PENETRATION DETAIL
AutoCAD SHX Text No Scale
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DETAIL - UL LISTED FIRE WALL PENETRATION ASSEMBLY FOR VOICE/DATA PDS CABLE
AutoCAD SHX Text No Scale
AutoCAD SHX Text
PENETRATIONS THROUGH RATED WALLS
AutoCAD SHX Text ALBERT JOSEPH COOPER III AR-0010460 STATE OF FLORIDA REGISTRATION NUMBER AA-C001315
AutoCAD SHX Text
AutoCAD SHX Text 09/18/2023
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
| M001 MECHANICAL SYMBOL SPECIFICATIONS |
| MD201 MECHANICAL DEMO FLOOR PLAN |
| M201 MECHANICAL FLOOR PLAN PROPOSED |
| M801 MECHANICAL DETAILS |
| E001 ELECTRICAL SYMBOL SPECIFICATIONS |
| ED201 LIGHTING DEMO PLAN |
| ED301 POWER DEMO PLAN |
| E101 EXHIBIT LEVEL 1 |
| E201 LIGHTING PLAN RCP |
| E301 POWER PROPOSED PLAN |
| E701 PANEL SCHEDULES |
| E801 ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .