Drawings.pdf

PDF 1 MB Posted

Attached to
Dept of Military, Replace Boilers-Mitchell CSMS #1
Solicitation number
25IFB13620
Issued by
Day County, South Dakota

About this file

This is a set of architectural, mechanical and electrical drawings from TSP, Inc. for a boiler replacement project at the South Dakota Army National Guard (SDARNG) Mitchell Combined Support Maintenance Shop (CSMS) #1 facility, under CFMO project #467096. The drawings detail the replacement of existing boilers and associated equipment in the facility's penthouse mechanical room, including installation of two new Lochinvar FCB6000 firetube condensing boilers rated at 6,000 MBH input each, four new Bell & Gossett circulating pumps with variable frequency drives (VFDs), new expansion tanks, and an air separator. The project includes modifications to heating water piping systems, controls, electrical power and emergency shutoff systems to serve the new equipment.

The drawings specify detailed technical requirements including 30% propylene glycol heating water solution, AL29-4C stainless steel venting systems, and compliance with the federal Build America Buy America Act requirements. Electrical modifications include new VFDs, disconnects, and emergency shutoff controls for the boilers and pumps. The drawings are dated February 12, 2025 and are signed/sealed by Professional Engineers Roger C. Nikolas (mechanical) and Jake R. Buckmiller (electrical) of TSP, Inc. No specific pricing information or contract terms are included in these construction documents.

View the file

Other files

File Type Posted
467096 TL Invitation to Builders Exchanges.pdf PDF
Project Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROGER C.

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE: 02/12/2025

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

2/1 2/2

5 8

:17 :41

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_M

_d eta ch ed

.rv t

COVER SHEET

G-001

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE BOILERS

CFMO #467096

SDARNG MITCHELL

CSMS #1

JRH02/12/2025

RCN04232099

SDARNG MITCHELL CSMS #1

REPLACE BOILERS CFMO #467096

CONSTRUCTION DOCUMENTS

02/12/2025

MITCHELL, SD

GENERAL SHEET INDEX

SHEET # SHEET NAME

G-001 COVER SHEET

DRAWING INDEX

ELECTRICAL SHEET INDEX

SHEET # SHEET NAME

E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

EP101 POWER PLAN - AREA 1

EP401 ENLARGED ELECTRICAL PLANS - PENTHOUSE MECHANICAL 2002

E-601 PARTIAL ELECTRICAL RISER DIAGRAM AND SCHEDULES

MECHANICAL SHEET INDEX

SHEET # SHEET NAME

M-001 MECHANICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

M-401 MECHANICAL HVAC PLANS - PENTHOUSE

M-402 MECHANICAL PIPING PLANS - PENTHOUSE

ME601 MECHANICAL SCHEDULES AND DETAILS

TITLE/DISCIPLINE NAME/CONTACT COMPANY PHONE

PROJECT MANAGER ROGER NIKOLAS TSP, Inc. 605.336.1160

MECHANICAL ENGINEER ROGER NIKOLAS TSP, Inc. 605.336.1160

ELECTRICAL ENGINEER JAKE BUCKMILLER TSP, Inc. 605.336.1160

DESIGN TEAM

NikolasRC@teamtsp.com

E-MAIL

NikolasRC@teamtsp.com

BuckmillerJR@teamtsp.com

INDUSTRIAL ROAD

N

OH

LM

AN

S T

NATIONAL GUARD ROAD

ISSUE DATE DESCRIPTION

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

& AND

Ø ROUND

A AIR

AC AIR CONDITIONING

ACOUS ACOUSTICAL

AD AREA DRAIN

ADD ADDENDUM

ADDL ADDITIONAL

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AG ABOVE GROUND

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AV ACID RESISTANT VENT

AW ACID RESISTANT WASTE

AUTO AUTOMATIC

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BLW BELOW

BM BEAM

BO BY OTHER

BOT BOTTOM

BSMT BASEMENT

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

BTWN BETWEEN

CAP CAPACITY

CB CATCH BASIN

CCW COUNTER CLOCKWISE

CFCV CONSTANT FLOW CONTROL VALVE

CFM CUBIC FEET PER MINUTE

CHW CIRCULATING HOT WATER

CI CAST IRON

CLG CEILING

CLG COOLING

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

COND CONDENSATE

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE/CONTINUATION

CONTR CONTRACT/CONTRACTOR

COORD COORDINATE

CTR CENTER

CUFT CUBIC FEET

CV CHECK VALVE

CW COLD WATER

CW CLOCKWISE

D DEGREE

DB DRY BULB

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DIV DIVISION

DI DEIONIZED WATER

DMPR DAMPER

DN DOWN

DWG DRAWING

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

EL ELBOW

ELEC ELECTRICAL

ELEV ELEVATION

EP EXPLOSION PROOF

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EAH EXHAUST HOOD

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FHC FIRE HOSE CABINET

FL FLOOR

FLEX FLEXIBLE

FLG FLANGE

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED PIPE

FS FULL SIZE

FS FLOOR SINK

FT FOOT/FEET

FTG FOOTING

FTR FIN TUBE RADIATION

GA GAGE/GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR/GENERAL

GPM GALLONS PER MINUTE

GR GRADE

GW GREASE WASTE

HB HOSE BIBB

HORZ HORIZONTAL

HP HORSE POWER

HP HIGH PRESSURE

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INL INLET

INSUL INSULATION

INT INTERIOR

INV INVERT

INWG INCHES WATER GAUGE

JT JOINT

LAB LABORATORY

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LF LINEAR FOOT

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LR LIQUID REFRIGERANT

LS LAWN SPRINKLER

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAN MANUAL

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBD MOTORIZED BYPASS DAMPER

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MCW MAKE-UP COLD WATER

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

N NECK / NORTH

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER / NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

OC ON CENTER

OF OVERFLOW

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PR PAIR

PRESS PRESSURE

PRIM PRIMARY

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PW POTABLE WATER

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

REFR REFRIGERATION

RH RELATIVE HUMIDITY

REQD REQUIRED

REV REVERSE

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SCHED SCHEDULE

SECT SECTION

SD SMOKE DAMPER

SHT SHEET

SIM SIMILAR

SLV SLEEVE

SM SURFACE MOUNT

SP STANDPIPE / STATIC PRESSURE

SPEC SPECIFICATION

SPS STATIC PRESSURE STATION

SQ SQUARE

SR SUCTION REFRIGERANT

SSD SOIL SUBDRAIN

SS STAINLESS STEEL

STD STANDARD

STM STEAM

STRUCT STRUCTURAL

SUCT SUCTION

SUSP SUSPENDED

T THERMOSTAT

TCP TEMPERATURE CONTROL PANEL

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UFD UNDER FLOOR DUCT

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VENT VENTILATION

VERT VERTICAL

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AFMS AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CF CABINET FAN

CF CHEMICAL FEEDER

CFP CHEMICAL FEEDER PUMP

CH CHILLER

CRU CONDENSATE RETURN UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

H HUMIDIFIER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

ILC INLINE CENTRIFUGAL

PF PROPELLER FAN

PRV POWER ROOF VENTILATOR

PWF POWER WALL FAN

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SA SHOCK ABSORBER

SAT SOUND ATTENUATOR

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

US UTILITY SET

UV UNIT VENTILATOR

WFMS WATER FLOW MEASURING STATION

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

* NOTE *

ALL OF THE GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER

DRAWINGS IN THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET

MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.

PLUMBING AND PIPING SYMBOLSGENERAL MECHANICAL SYMBOLS

HVAC SYMBOLS

LAB AND MEDICAL SYMBOLS

FIRE PROTECTION SYMBOLS

SA

RA

ELBOW WITH TURNING VANES

LAB AIRLA

CONDENSATE DRAINCD

DUAL TEMP WATER RETURNDTWR

DOMESTIC HOT WATER - RECIRCULATINGRHW

DOMESTIC HOT WATERHW

DOMESTIC COLD WATERCW

LAB DEIONIZED WATERLDE

LAB DISTILLED WATERLDI

LAB GASLG

LAB VACUUMLV

MEDICAL AIRMA

MEDICAL CO2CO2

MEDICAL GASMGAS

MEDICAL HYDROGENH

MEDICAL NITROGENNI

DOMESTIC COLD WATER - SOFTSCW

SANITARY VENTV

SANITARY WASTE - BELOW GROUNDWB

SANITARY WASTEW

MEDICAL NITROUS OXIDENO

MEDICAL OXYGENO

MEDICAL VACUUMMV

NATURAL GASG

NATURAL GAS - 2LBG-2LB

PROCESSPRO

STORM DRAINAGERD

STORM DRAINAGE - BELOW GRADERDB

STORM DRAINAGE OVERFLOWORD

STORM DRAINAGE OVERFLOW BELOW GRADEORDB

FIRE PROTECTION OTHERFP-O

DRY FIRE SPRINKLERDF

GLYCOL HOT WATER RETURNGHR

GLYCOL HOT WATER SUPPLYGHS

HEATING WATER RETURNHWR

HEATING WATER SUPPLYHWS

OIL WASTEOW

CHILLED WATER RETURNCWR

CHILLED WATER SUPPLYCWS

CONDENSER WATER RETURNCR

CONDENSER WATER SUPPLYCS

OIL VENTOV

REFRIGERANTREF

REFRIGERANT HOT GASRHG

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

ACID WASTE ABOVE GRADEAW

ACID VENT PIPINGAV

ACID WASTE BELOW GRADEAWB

COUPLING

SOUND ATTENUATOR

M

F B

S C

MOTORIZED SMOKE

COMBINATION

SMOKE & FIRE

VOLUME

DAMPER

FIRE BACKDRAFT

TYPE

CFM

S-1 (3X)

16"x16"

R-1

VOLUME DAMPER

TOTAL

(IF EXCEEDS 1)

RETURN

DIFFUSER

VAV BOX

POWER ROOF VENTILATOR

UNIT HEATER

RADIANT

PANEL

GEOTHERMAL SUPPLYGTS

GEOTHERMAL RETURNGTR

LPS

STEAM - LP CONDENSATELPR

STEAM - LP

MPS

STEAM - MP CONDENSATEMPR

STEAM - MP

HPS

STEAM - HP CONDENSATEHPR

STEAM - HP

CONDENSATE RETURNCDR

COMBINATION WASTE AND VENTCWV

COMPRESSED AIRA

PUMP DISCHARGEPD

MITIGATION VENTMIT

GREASE VENTGV

GREASE WASTEGW

DEIONIZED WATERDI

REVERSE OSMOSIS WATERRO

DUAL TEMP WATER SUPPLYDTWS

PIPE BEING DEMOLISHED

EXISTING PIPE TAG

x x-xxx

Room

POINT WHERE NEW CONNECTS TO EXISTING

NUMBER OF DETAIL ON SHEET

NUMBER OF SHEET WHERE DETAIL APPEARS

KEYNOTE

CONTINUATION SYMBOL

ROOM NAME AND NUMBER

DOMESTIC COLD WATER - HARDHCW

DOMESTIC HOT WATER - 140 DEGRESSHW 140

RECTANGULAR DUCT SIZE TAG (WIDTH X HEIGHT)16"x8"

16"/8"

16"Ø

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

ROUND DUCT SIZE TAG (DIAMETER)

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISEDROP

ROUND SUPPLY/OUTSIDE AIR DUCT RISEDROP

RECTANGULAR RETURN/TRANSFER AIR DUCT RISEDROP

ROUND RETURN/TRANSFER AIR DUCT RISEDROP

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISEDROP

ROUND EXHAUST/RELIEF AIR DUCT RISEDROP

SA

RA

EA

EA

FLEX DUCT

x-xxx EQUIPMENT TAG

LINEAR DIFFUSER

CO2 TH

CO TS

NO2 T

HS SVV

H S

TEMPERATURE & HUMIDITY SENSORCARBON DIOXIDE SENSOR

TEMPERATURE SENSORCARBON MONOXIDE SENSOR

THERMOSTATNITROGEN DIOXIDE SENSOR

MANUAL SWITCHHUMIDITY SENSOR

SENSORHUMIDISTAT

PLUG

REDUCING 45 DEGREE TEE

45 DEGREE TEE

2"4"

4"

ROOF DRAIN FIXTURE

4" RD-1

4" ORD-1

DRAIN SIZE

DRAIN TAG

TYPE (SEE SCHEDULE)

FCO WCO W

WH-1

PLUMBING FIXTURE

PLUMBING FIXTURE TAG

TYPE (SEE SCHEDULE)

DOWNSPOUT NOZZLE

FLOOR

CLEAN

OUT

WALL

CLEAN

OUT

FLOOR

DRAIN

DOMESTIC

WATER METER GAS METER END CAP PIPE BREAK

DOMESTIC HOT WATER - RECIRCULATING 140 DEGREESRHW 140

DOMESTIC COLD WATER - FILTEREDF-CW

(E)

FIRE PROTECTION PRE-ACTIONFP-PA

FIRE PROTECTION WETFP

COMBINATION FIRE & DOMESTICFP-DOM-W

UPRIGHT SPRINKLER HEAD

PENDANT SPRINKER HEAD

RECESSED SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

'D' REPRESENTS DRY SPRINKLER

HEADD

SIDEWALL SPRINKLER

HEAD

EXTENDED COVERAGE

SIDEWALL SPRINKLER HEAD

OBSTRUCTION FROM

DUCTWORK 48" AND

GREATER

48"x18" S/A

1/8" / 12" SLOPE

2"

PIPE SLOPE TAG

PIPE SIZE TAG (DIAMETER)

EXISTING DUCT TAG(E)

21. PUMP

22. FLOW SWITCH

23. PRESSURE TEMPERATURE TAP

24. MEDICAL GAS OUTLET

25. HOSE BIBB

26. WALL HYDRANT

27. FLOW METER

28. BACKFLOW PREVENTER

29. AQUASTAT

30. 3-WAY VALVE

1. SIDE CONNECTION

2. ELBOW DOWN

3. ELBOW UP

4. SHUT OFF VALVE

5. BALANCING VALVE

6. CONTROL VALVE

7. PRESSURE REDUCING VALVE

8. PRESSURE RELIEF VALVE

9. CHECK VALVE

10. AIR VENT

11. PRESSURE GAUGE

12. THERMOMETER

13. PIPE ANCHOR

14. PIPE GUIDE

15. REDUCER

16. STRAINER

17. UNION

18. DIRECTION OF FLOW

19. PITCH PIPE

20. 3-WAY CONTROL VALVE

FM AFS

2 3 4 5 6 7 8 9 10 11 12 13 14 15

302928272624232221201918 2516 17

02/12/2025

HVAC GENERAL NOTES

* NEW 1 SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.

* NEW 2 CONTRACTOR SHALL LOCATE THERMOSTATS, CO2 SENSORS, AND TEMPERATURE SENSORS AT

4'-0" AFF, A MINIMUM OF 8" FROM LIGHT SWITCH.

* NEW 3 REFER TO PIPING DRAWINGS FOR THERMOSTAT, CO2 SENSOR, AND TEMPERATURE SENSOR

LOCATIONS.

* NEW 4 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR SHALL

ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE, AND LOCAL

CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER.

* NEW 5 PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT. COORDINATE

SIZES WITH MECHANICAL EQUIPMENT SELECTED.

* NEW 6 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMENT AFTER ALL

DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.

PROJECT GENERAL NOTES

* DEMO 1 WHERE EQUIPMENT AND/OR FIXTURES ARE INDICATED TO BE REMOVED, THE EXISTING

SERVICES SHALL BE CAPPED AND CONCEALED BEHIND FINISHED SURFACES. ABANDONED

BRANCH SERVICES SHALL BE REMOVED BACK TO THE MAINS AND CAPPED, UNLESS OTHERWISE

INDICATED.

* DEMO 2 CAP ANY ABANDONED OR UNUSED PIPE AND/OR DUCT OPENINGS.

* DEMO 3 THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING TO MATCH EXISTING

WALLS, FLOORS, AND CEILINGS.

* DEMO 4 HYDRONIC AND DOMESTIC PIPING SHALL BE THOROUGHLY CLEANED BEFORE PUTTING INTO

PERMANENT SERVICE.

* DEMO 5 WHERE MATERIAL IS INDICATED TO BE REMOVED, IT SHALL REMAIN THE PROPERTY OF THE

OWNER. THIS CONTRACTOR SHALL DISPOSE OF MATERIAL AS DIRECTED BY THE OWNER.

* EXST 1 REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.

* EXST 2 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING, PRIOR TO FINAL

BID, ALL EXISTING CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS.

* EXST 3 WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT

CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO

START OF WORK.

* NEW 1 COORDINATE AND COOPERATE WITH THE OTHER TRADES ON THE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY, STRUCTURE, AND EQUIPMENT TO PREVENT

CONFLICTS.

* NEW 2 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH EXISTING AND THOSE

ILLUSTRATED BY THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE REASONABLY

ANTICIPATED INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS INVOLVED ON THIS PROJECT.

* NEW 3 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT

LIMITED TO THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE.

* NEW 4 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.

* NEW 5 ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0" FROM EDGE OF ROOF.

* NEW 6 LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT AWAY FROM THE SPACE ABOVE

ELECTRICAL PANELS, TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.

* NEW 7 ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO MECHANICAL EQUIPMENT.

* NEW 8 REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C. CONDENSATE DRAIN PIPING.

* NEW 9 PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL ANOTHER SIZE IS

SHOWN.

* NEW 10 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.

* NEW 11 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN

INSTALLATION INSTRUCTIONS.

* NEW 12 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE DRAWING, ARE

APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL BE

COORDINATED WITH ALL OTHER TRADES TO AVOID INTERFERENCE IN THE FIELD.

* NEW 13 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT

CEILINGS.

* NEW 14 MATERIALS AND EQUIPMENT SHOWN ON PLANS SHALL BE NEW AND FURNISHED BY THIS

CONTRACTOR UNLESS OTHERWISE INDICATED.

* NEW 15 THIS CONTRACTOR IS RESPONSIBLE FOR ALL SLEEVES AND/OR OPENINGS WHERE REQUIRED TO

RUN PIPES AND DUCTS THROUGH FOUNDATIONS, FLOOR SLABS, WALLS, BRIDGING AND BEAMS

EXCEPT WHERE OTHERWISE INDICATED.

* NEW 16 CEILING ACCESS IS REQUIRED AT ALL REHEAT COILS, VALVES, FIRE DAMPERS, MANUAL

DAMPERS AND MOTORIZED DAMPERS LOCATED ABOVE CEILING. CEILING ACCESS PANELS WILL

BE PROVIDED UNDER THE GENERAL SECTION OF CONSTRUCTION AND SHALL BE MINIMUM OF 24"

X 24" UNLESS OTHERWISE INDICATED. COORDINATE WITH GENERAL CONTRACTOR.

* NEW 17 THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS AND

DIMENSIONS. NOTIFY THE A/E IMMEDIATELY OF ANY DISCREPANCIES.

* NEW 18 WHERE NEW SERVICES ARE SHOWN CONNECTING TO EXISTING, VERIFY EXACT LOCATION AND

SIZE OF EXISTING.

* NEW 19 EXISTING SERVICES SHALL BE MAINTAINED UNLESS OTHERWISE INDICATED.

* NEW 20 ALL DUCTS, PIPING, FIXTURES, ETC., WHICH ARE DASHED AND/OR INDICATED BY NOTE ON

DEMOLITION PLANS SHALL BE REMOVED.

* NEW 21 ALL PLUMBING SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH NATIONAL, STATE, AND LOCAL CODES.

* NEW 22 SEAL ALL SHEET METAL DUCTWORK JOINTS.

* NEW 23 BALANCING OF AIR AND HYDRONIC SYSTEMS SHALL BE PERFORMED BY AN NEBB OR AABC

CERTIFIED TEST AND BALANCE AGENCY.

* NEW 24 PIPE PENETRATIONS OF RATED WALLS AND FLOORS SHALL BE SLEEVED AND PROPERLY FIRE

SEALED.

* NEW 25 ALL PIPE AND DUCT PENETRATIONS OF SMOKE PARTITION WALLS SHALL BE PROPERLY SEALED

TO RESIST THE PASSAGE OF SMOKE AS REQUIRED BY THE LOCAL AUTHORITY.

* NEW 26 INSTALL FLUSH VALVE OPERATORS ON WIDE SIDE OF ACCESSIBLE STALLS.

* NEW 27 THE HEATING AND/OR COOLING HYDRONIC SYSTEM SHALL BE PROVIDED AND FILLED WITH AN

ANTIFREEZE GLYCOL SOLUTION (AS INDICATED ON THE EQUIPMENT SCHEDULES) BY THE PIPING

CONTRACTOR WHO SHALL BE RESPONSIBLE FOR DETERMINING THE AMOUNT OF GLYCOL

REQUIRED.

* NEW 28 GREASE DUCTS: PROVIDE 2-INCH THICK U.L. 2-HOUR FIRE RATED DUCT WRAP ON GREASE

DUCTS BETWEEN CEILING AND ROOF PENETRATION.

SHEET INDEX - MECHANICAL

SHEET # SHEET NAME

M-001 MECHANICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

M-401 MECHANICAL HVAC PLANS - PENTHOUSE

M-402 MECHANICAL PIPING PLANS - PENTHOUSE

ME601 MECHANICAL SCHEDULES AND DETAILS

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

2/1 2/2

5 8

:17 :45

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_M

_d eta ch ed

.rv t

MECHANICAL SYMBOLS,

ABBREVIATIONS, AND

GENERAL NOTES

M-001

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE BOILERS

CFMO #467096

SDARNG MITCHELL

CSMS #1

JRH02/12/2025

RCN04232099

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

J

K K.1

PENTHOUSE

MECHANICAL

B-2B-1

3 3

4 4

Finished Floor Elevation = 100'-0"

Finished Floor Elevation = 113'-4"

J

K K.1

PENTHOUSE

MECHANICAL

Finished Floor Elevation = 100'-0"

Finished Floor Elevation = 113'-4"

02/12/2025

KEYNOTES

1 REMOVE COMBUSTION AIR FAN, MOTORIZED DAMPER, ALL DUCTWORK AND CONTROLS. CAP LOUVER

WITH 3" RIGID INSULATION AND 16 GA PANEL.

2 REMOVE BOILER STACKS THRU ROOF.

3 14" AL29-4C BOILER VENT UP THRU ROOF THRU EXISTING ROOF OPENING. INSTALL AND TERMINATE

PER MFG'S LITERATURE. PROVIDE EXIT CONE AT DISCHARGE.

4 14" PVC BOILER INTAKE UP THRU ROOF. INSTALL AND TERMINATE PER MFG'S LITERATURE. INSULATE

WITH 2" FIBERGLASS BLANKET. ALL ROOFING WORK SHALL BE PERFORMED BY GUARANTEED

ROOFING SIOUX FALLS, SD IN ORDER TO MAINTAIN ROOF WARRANTY. CONTACT: WILL TEDMON

605-331-5121.

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

KEY PLAN

AREA 1

AREA 2

AREA 3

AREA

AREA 5

2/1 2/2

5 8

:17 :52

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_M

_d eta ch ed

.rv t

MECHANICAL HVAC

PLANS - PENTHOUSE

M-401

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE BOILERS

CFMO #467096

SDARNG MITCHELL

CSMS #1

JRH02/12/2025

RCN04232099

SCALE: 1/4" = 1'-0"A1 ENLARGED MECHANICAL HVAC PLAN - PENTHOUSE PLAN NORTH

SCALE: 1/4" = 1'-0"C1 ENLARGED HVAC DEMOLITION PLAN - PENTHOUSE PLAN NORTH

NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL BUILD AMERICA BUY AMERICA

ACT REQUIREMENTS.

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

J

K K.1

PENTHOUSE

MECHANICAL

B-1 B-2

CP-3 CP-4 CP-2 CP-1

3" 3"

14 14

(TYP.)

18 18

6 6" HWR

6"

6"

4" G-2LB

(E) 4"

2PSI G

1" G-2LB

6"

6"6"

(E) 3" G-2LB

HWS

3" G-2LB

(E) 4" HWS

(E) 4" HWR

HWR

VFD-CP4

VFD-CP3

VFD-CP1VFD-CP2

ET-1

ET-2 1"

FM

Finished Floor Elevation = 100'-0"

Finished Floor Elevation = 113'-4"

AS-1

J

K K.1

PENTHOUSE

MECHANICAL

(E) 3" G-2LB

6"

6" 6"

34 5

6"

678 9

10 3" G

4" G

4" G-2LB

Finished Floor Elevation = 100'-0"

Finished Floor Elevation = 113'-4"

02/12/2025

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

KEY PLAN

AREA 1

AREA 2

AREA 3

AREA

AREA 5

2/1 2/2

5 8

:18 :01

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_M

_d eta ch ed

.rv t

MECHANICAL PIPING

PLANS - PENTHOUSE

M-402

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE BOILERS

CFMO #467096

SDARNG MITCHELL

CSMS #1

JRH / ADK02/12/2025

RCN04232099

PLAN NORTH

PLAN NORTH

KEYNOTES

1 REMOVE HOT WATER BOILERS, ALL PIPING, VALVES, AND CONTROLS.

2 REMOVE BUILDING LOOP HEATING WATER PUMPS AND PIPING SHOWN. REMOVE VFD'S. INERTIA

PADS TO REMAIN.

3 REMOVE BOILER PRIMARY PUMPS AND PIPING SHOWN.

4 REMOVE AIR SEPARATOR.

5 REMOVE 3-WAY MIXING VALVE.

6 6" HWS/R MAINS DOWN TO REMAIN.

7 REMOVE EXPANSION TANK.

8 GLYCOL MAKEUP PUMP TO REMAIN.

9 4" - 2 PSI GAS DOWN TO REMAIN.

10 REMOVE GAS PRESSURE REGULATOR. REMOVE LOW PRESSURE GAS PIPING TO BOILERS.

11 AIR HANDLING UNIT TO REMAIN.

12 MAKE-UP AIR UNIT TO REMAIN.

13 GAS UNIT HEATER TO REMAIN.

14 INSTALL NEW BOILERS ON EXISTING CONCRETE EQUIPMENT PADS. EXTEND PADS IF REQUIRED FOR

NEW BOILERS.

15 ONICON F-1200 SERIES INSERTION FLOW METER.

16 RECONNECT GLYCOL MAKE-UP PIPING INTO NEW PIPING SYSTEM SIMILAR TO EXISTING. FIELD

VERIFY PIPE SIZE AND CONNECTION LOCATION.

17 INSTALL NEW PUMPS ON EXISTING INERTIA BASES.

18 NEW GAS PRESSURE REGULATOR. 2 PSI TO 14" W.C. VENT TO OUTDOORS.

19 VFDS SERVING AHU AND MAU TO REMAIN.

20 SALVAGE CHEMICAL FEED TANK. RECONNECT TO NEW PIPING SYSTEM SIMILAR TO EXISTING.

21 PROVIDE NEW ALARM POINT AT BMS. SYSTEM SHALL ALARM WHENEVER GLYCOL PUMP IS

ENERGIZED.

22 INSTALL NEW EXPANSION TANK ON EXISTING CONCRETE PAD. CONNECT TO EXISTING PIPING.

SCALE: 1/4" = 1'-0"A1 MECHANICAL PIPING PLAN - PENTHOUSE

SCALE: 1/4" = 1'-0"C1 MECHANICAL PIPING DEMOLITION PLAN - PENTHOUSE

NOTES:

- PROVIDE 2" DEFLECTION SPRING HANGERS ON ALL NEW HWS & HWR PIPING.

- REFILL SYSTEM WITH DI WATER AND 30% DOWFROST INHIBITED PROPYLENE GLYCOL

NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL BUILD AMERICA BUY AMERICA

ACT REQUIREMENTS.

NIKOLAS

RE

GIS

TE

REDPROFESSIONALENGINE ER

REG. NO.

SOUTH DAKOTA

DATE:

2" DEFLECTION

VIBRATION ISOLATOR

GAUGE ISOLATION

VALVE (TYP)

SUCTION LINE

SHUTOFF VALVE

PRESSURE

GAUGE

SUCTION DIFFUSER WITH

INTEGRAL STRAINER

VIBRO-ACOUSTICS

SIPS INLINE PUMP

STAND (TYP.)

DRAIN VALVE

COUPLING GUARD

FLOOR

LONG RADIOUS

ELBOW REDUCING

WHERE REQUIRED

VERTICLE IN-LINE

PUMP

TRIPLE DUTY VALVE WITH

5 DIAMETERS OF

STRAIGHT PIPE

UPSTREAM

DISCHARGE LINE

1. ALL SPECIALTIES SHALL BE LINE SIZE. REDUCE AT PUMP

SUCTION OR DISCHARGE ONLY.

CONCRETE

EQUIP. PAD

EXISTING CONCRETE

INERTIA BASE WITH

SPRING ISOLATORS

1/4" COPPER TUBING

2" x 12" NIPPLE

L.K. VENT, IN

ACCESSIBLE

LOCATION

FULL SIZE TEE

SUPPLY OR

RETURN LINE

120.0°

120.0°

PIPE

INSULATION

22 GAUGE SADDLE

WOODEN PLUG OR

SECTION OF RIGID

INSULATION AS

SPECIFIED

INSULATION

PIPE

22 GAUGE SHEET

METAL SADDLE

PIPE STRAP

TRAPEZE

HANGER

THIS HANGER

FOR ALL PIPES

THIS HANGER FOR COLD

SERVICES AS SPECIFIED

WOODEN PLUGS INSULATION

AT SADDLE CONTACT POINTS

OR SECTION RIGID

INSULATION AS SPECIFIED

HIGH CAPACITY

AUTOMATIC AIR

VENT

CENTRIFUGAL AIR SEPARATOR

UNION (TYP.)

SHUTOFF VALVES (TYP.)

FROM SYSTEM

INTERNAL STRAINER

INSTALL UNIT LEAVING ADEQUAT

DISTANCE TO REMOVE STRAINER

ON UNITS WITH A STRAINER

BLOWDOWN AND DRAIN

VALVE WITH HOSE

CONNECTION

SYSTEM CONNECTION -

(CONNECT TO SIDE OF MAIN

HEADER)

UNDERSLUNG CONNECTION CREATES

THERMAN TRAP (12" MINIMUM DROP)

DRAIN VALVE WITH

HOSE CONNECTION

T&P RELIEF VALVE - (WHEN NOT

PROVIDED ON HEAT TRANSFER

DEVICE) PIPED TO FLOOR DRAIN

TO PUMP SUCTION

PRESSURE GAUGE WITH

NEEDLE VALVE, TYP.

AIR CHARGING VALVE (PRESSURIZE DRY

TANK EQUAL TO FILL VALVE PRESSURE)

TYP.

EXPANSION TANK TYP.

LOW CAPACITY AIR VENT

FROM GLYCOL MAKE-UP PUMP

NOTES:

1. ALL SPECIALTIES SHALL BE LINE SIZE. REDUCE AT PUMP SUCTION OR DISCHARGE ONLY.

FLEXIBLE COUPLING WITH GUARD

HOUSEKEEPING PAD

EXISTING CONRETE INERTIA

BASE W/SPRING ISOLATORS

PUMP DISCHARGE HEADER

CHECK VALVE

INSTALL CHECK VALVE MINIMUM

OF FIVE PIPE DIAMETERS FROM

PUMP DISCHARGE

SPILL TO FLOOR DRAIN

DRAIN VALVES MATCH

CONNECTION SIZE (TYPICAL)

ISOLATION VALVE (TYPICAL)

REDUCER / INCREASER AS

REQUIRED (TYPICAL)

SUCTION DIFFUSER

WITH STRAINER

PUMP SUCTION HEADER

PRESSURE GAUGE W/

COCK (TYPICAL)

FLEXIBLE PIPING

CONNECTORS (TYPICAL)

"D"

BALANCING VALVE

GROUT BASE BEFORE

CONNECTING PIPING

TO SYSTEM

CIRCULATOR

HWS TO

SYSTEM

AIR SEPARATOR

BOILER CIRCULATOR BY

BOILER MANUFACTURER

SEE PIPING DETAIL (TYP)

FLOW SWITCH (TYP)

THERMOMETER (TYP)

PRESSURE RELIEF VALVE,

PIPE TO FLOOR DRAIN (TYP)

TEMPERATURE / PRESSURE GAUGE (TYP)

UNION (TYP)

DRAIN VALVE, PIPE TO

FLOOR DRAIN (TYP)

1" BOILER CONDENSATE

PROVIDE CONDENSATE NEUTRALIZATION KIT (TYP)

INSTALL PER MFGS REQUIREMENTS

TERMINATE ABOVE FLOOR DRAIN.

THERMOMETER (TYP.)

HWR FROM SYSTEM

NOT TO EXCEED 4 PIPE

DIAMETERS APART

BOILER

PRESSURE GAUGE (TYP)

N.G.

6" DIRT LEG

UNION

COMBUSTION

AIR INLET PVC (TYP)

EXHAUST FLUE POSITIVE

PRESSURE AL29-4C

STAINLESS STEEL

CONDENSATE

DRIP AT ELBOW

PER MFG.(TYP)

BOILER

N.G.

6" DIRT LEG

UNION

SEE PLANS FOR PIPE SIZES

CONDENSATE DRIP AT ELBOW

PROVIDE CONDENSATE TRAP

PER MFG.

02/12/2025

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

2/1 2/2

5 8

:18 :05

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_M

_d eta ch ed

.rv t

MECHANICAL

SCHEDULES AND

DETAILS

ME601

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE BOILERS

CFMO #467096

SDARNG MITCHELL

CSMS #1

JRH02/12/2025

RCN04232099

GAS FIRED BOILER SCHEDULE

EQUIPMENT REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT

NO.

LOCATION

MANUFACTURER

MODEL

NO. TYPE

MBH

INPUT

MBH OUTPUT

@ 140F EWT

TURNDOWN

RATIO

PRESSURE

RATING FUEL

GAS PRESSURE

IN WG

WATER

AIR

INLET VENT

OPERATING

WEIGHT EQUIPMENT NOTES VOLT/PH

MIN CKT

AMP MOCP WIRE SIZE / CONDUIT

CONTROLLER

CONTROL

BY

DISCONNECT

ELECTRICAL

NOTESROOM NUMBER

DESIGN

FLOW MIN. FLOW VOLUME PD @ 385 GPM GLYCOL TYPE GLYCOL (%) TYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

B-1 PENTHOUSE MECHANICAL 2002 Lochinvar FCB6000 FIRETUBE CONDENSING 6000 5280 20 TO 1 160 psig NATURAL GAS 10 385 GPM 60 GPM 304 gal 13.0 Feet PROPYLENE 30 14" 14" 6755 lb ALL 480 V / 3 8.75 A EXISTING (10 A) SEE CIRCUIT SCHEDULE - - INTEGRAL - - DIV. 22/23 DIV. 22/23 E1 DIV. 26 - B-2 PENTHOUSE MECHANICAL 2002 Lochinvar FCB6000 FIRETUBE CONDENSING 6000 5280 20 TO 1 160 psig NATURAL GAS 10 385 GPM 60 GPM 304 gal 13.0 Feet PROPYLENE 30 14" 14" 6755 lb ALL 480 V / 3 8.75 A EXISTING (10 A) SEE CIRCUIT SCHEDULE - - INTEGRAL - - DIV. 22/23 DIV. 22/23 E1 DIV. 26 -

CIRCULATING PUMP SCHEDULE

EQUIPMENT REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT

NO.

LOCATION

SERVES MANUFACTURER MODEL NO. TYPE FLOW HEAD FLUID

BRAKE

POWER MOTOR POWER

MOTOR

RPM

IMPELLER

DIAMETER

EFF. @ DUTY

POINT SUCTION DISCHARGE VFD

EQUIPMENT

NOTES VOLT/PH

MIN CKT

AMP MOCP WIRE SIZE / CONDUIT

CONTROLLER CONTROL

BY

DISCONNECT ELECTRICAL

NOTESROOM NUMBER TYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

CP-1 PENTHOUSE MECHANICAL 2002 BOILER B-2 PRIMARY Bell & Gossett e-80 5x5x7 VIL 385.0 GPM 20.0 ftH2O 30% PG 3.1 hp 5 hp 1800 5.6 66% 5" 5" VFD-CP1 ALL 480 V / 3 9.4 A EXISTING (10 A) SEE CIRCUIT SCHEDULE VFD - PENTHOUSE MECHANICAL 2002 - - DIV. 22/23 DIV. 22/23 E1 DIV. 26 - CP-2 PENTHOUSE MECHANICAL 2002 BOILER B-1 PRIMARY Bell & Gossett e-80 5x5x7 VIL 385.0 GPM 20.0 ftH2O 30% PG 3.1 hp 5 hp 1800 5.6 66% 5" 5" VFD-CP2 ALL 480 V / 3 9.4 A EXISTING (10 A) SEE CIRCUIT SCHEDULE VFD - PENTHOUSE MECHANICAL 2002 - - DIV. 22/23 DIV. 22/23 E1 DIV. 26 - CP-3 PENTHOUSE MECHANICAL 2002 BUILDING HEATING LOOP Bell & Gossett 1510-4GC END SUCTION 565.0 GPM 115.0 ftH2O 30% PG 21.9 hp 30 hp 1800 11.1 77% 5" 4" VFD-CP3 1-2 480 V / 3 50 A EXISTING (70 A) SEE CIRCUIT SCHEDULE VFD - PENTHOUSE MECHANICAL 2002 - - DIV. 22/23 DIV. 22/23 E2 DIV. 26 - CP-4 PENTHOUSE MECHANICAL 2002 BUILDING HEATING LOOP Bell & Gossett 1510-4GC END SUCTION 565.0 GPM 115.0 ftH2O 30% PG 21.9 hp 30 hp 1800 11.1 77% 5" 4" VFD-CP4 1-2 480 V / 3 50 A EXISTING (70 A) SEE CIRCUIT SCHEDULE VFD - PENTHOUSE MECHANICAL 2002 - - DIV. 22/23 DIV. 22/23 E2 DIV. 26 -

ELEC NOTES:

E1. PROVIDE A 30A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH IN A NEMA 1 ENCLOSURE.

ELEC NOTES:

E1. PROVIDE A 30A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH IN A NEMA 1 ENCLOSURE.

E2. PROVIDE A 100A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH IN A NEMA 1 ENCLOSURE.

REMARKS:

1. PROVIDE WITH O2 TRIM.

2. FACTORY CONTROLS WITH BACNET INTERFACE TO BMS.

3. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT.

4. 5-YEAR BURNER WARRANTY.

5. AL29-4C STAINLESS STEEL VENTING.

REMARKS:

1. NEMA PREMIIUM EFFICIENCY MOTOR WITH SHAFT GROUNDING RINGS.

2. PROVIDE WITH SUCTION DIFFUSER AND TRIPLE DUTY VALVE.

3. PROVIDE VIL PUMP WITH VIBRO-ACOUSTICS SIPS INLINE PUMP STANDS WITH NEO VIBRATION ISOLATION PADS

SCALE: NOT TO SCALEA5 VERTICAL IN-LINE PUMP

SCALE: NOT TO SCALEB5 HIGH POINT AIR VENT

SCALE: NOT TO SCALEA4 HANGERS AND INSULATED SADDLES

SCALE: NOT TO SCALEA2 AIR SEPARATOR AND EXPANSION TANK PIPING

SCALE: NOT TO SCALEB3 BASE MOUNT END SUCTION PUMP

SCALE: NOT TO SCALEB2 CONDENSING BOILER PIPING DIAGRAM

H-206

EXPANSION TANK SCHEDULE

UNIT NO. MANUFACTURER MODEL NO. SYSTEM TANK VOLUME

ACCEPTANCE

VOLUME

DIMENSIONS UNIT DRY

WEIGHT EQUIPMENT NOTESDIAMETER HEIGHT

ET-1 WESSELS NLA-600 HEATING WATER 158.0 gal 158.0 gal 30" 65" 360 lb ASME TANK WITH REMOVABLE BLADDER, PROVIDE WITH

"WESSVIEW" TANK PRESSURE MONITORING GAUGES

ET-2 WESSELS NLA-600 HEATING WATER 158.0 gal 158.0 gal 30" 65" 360 lb ASME TANK WITH REMOVABLE BLADDER, PROVIDE WITH

"WESSVIEW" TANK PRESSURE MONITORING GAUGES

NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL BUILD AMERICA BUY AMERICA

ACT REQUIREMENTS.

AIR SEPARATOR SCHEDULE

UNIT NO. MANUFACTURER MODEL NO. SYSTEM FLOW WPD

CONNECTION

DIAMETER EQUIPMENT NOTES

AS-1 B&G CRS-6F-MAG HEATING 565.0 GPM 2.3 ftH2O 6" ALL

REMARKS:

1. ASME RATED COALESCING MEDIUM AIR AND SEDIMENTS SEPARATOR WITH REMOVABLE HEAD AND NEODYMIUM 45H MAGNETIC INSERT.

2. STAINLESS STEEL COALESCING MEDIUM.

3. FLOODED WEIGHT = 499 LBS.

14596

JAKE R.

BUCKMILLER

RE

GIS

TE

REDPROFESSIONALENGINE ER

REG. NO.

SOUTH DAKOTA

DATE:

E - 5 0 1

A N N NA

SHEET SEQUENCE

NUMBER 01-99

SHEET TYPE

DESIGNATOR

DISCIPLINE

CHARACTER

MODIFIER

CHARACTER

SHEET TYPE DESIGNATORS

0 GENERAL (SYMBOLS LEGEND)

1 PLANS (HORIZONTAL VIEWS)

2 ELEVATIONS (VERTICAL VIEWS)

3 SECTIONS (SECTIONAL VIEWS)

4 LARGE SCALE VIEWS

5 DETAILS

6 SCHEDULES AND DIAGRAMS

7 USER DEFINED

8 USER DEFINED

9 3D REPRESENTATIONS

1 2 3 4 5 6

E2 E3 E4

C5

A4A1 A

B

C

D

E

TSP

A

B

C

D

E

1 2 3 4 5 6

MODIFIER CHARACTERS

S SITE

D DEMOLITION

L LIGHTING

P POWER

T TECHNOLOGY

SHEET IDENTIFICATIONELECTRICAL ABBREVIATIONS LIST

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC AIR CONDITIONER

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AIC AVAILABLE INTERRUPTING FAULT

CURRENT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CB-XX RECESSED CEILING BOX (SEE SCHEDULE)

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CM CORNER MOUNT

CMPR COMPRESSOR

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR

CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER

CIRCULATING PUMP

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DT DOUBLE THROW

DTS DUAL TECHNOLOGY SENSOR

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FB-XX FLOOR BOX (SEE SCHEDULE)

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FVNR FULL VOLTAGE NON-REVERSING

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI/GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

HB HIGH BAY

HOA HANDS-OFF-AUTOMATIC

SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSB MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

OS OCCUPANCY SENSOR

PA PUBLIC ADDRESS

PB PULL BOX

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

(CONDUIT)

PWR POWER

QUAN QUANTITY

REC RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VS VACANCY SENSOR

W WATT

W/ WITH

WB-XX RECESSED WALL BOX (SEE SCHEDULE)

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

Y WYE-CONNECTED

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

SPACE TAG

REVISION TAG

KEYNOTE TAG

SECTION TAG

DETAIL TAG

ELEVATION TAG

EXISTING WORK

NEW WORK

EXISTING ITEMS TO BE REMOVED

NAME

A1 A-301

A1 A-501

A-201A1

NORTH ARROW

SHEET XXXXX

SHEET XXXXX

A1 PLAN OR DETAIL

SCALE: 1'-0" = 1'-0"

GRID COLUMN/FND GRID INDICATOR

MATCH LINE INDICATOR

DETAIL/SECTION/PLAN

INDICATOR

CONVENTIONS LEGEND

PLAN NORTH

A2

E c

1,3,5

SF-1

2,4,6

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER.

THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.

THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE 1: LIGHTING FIXTURE TYPE "A2" IS CONNECTED TO CIRCUIT 12 AND

CONTROLLED BY SWITCH "b".

EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE CIRCUIT DESIGNATION IS

INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E" WITH

SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 14.

DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH

DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX

RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH "c".

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".

SPECIAL /RECEPT CONNECTIONS. THE CIRCUIT DESIGNATION IS INDICATED BY A

NUMBER(S) ADJACENT TO THE SYMBOL. SEE KEYNOTE FOR CONFIGURATION.

EXAMPLE: 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5.

MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR

CHARACTERS ADJACENT TO THE MOTOR SYMBOL. THE CIRCUIT DESIGNATION IS

INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: MOTOR SF-1; 3

PHASE CONNECTION TO CIRCUITS 2, 4, 6.

TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER "T". SEE THE SINGLE LINE DIAGRAM OR

RISER FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS.

EXAMPLE: TRANSFORMER TYPE "T1".

PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE

OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

CONDUIT RUN CONCEALED IN CEILING OR WALL CONSTRUCTION.

HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS

SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT

DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES

(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE

CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN

TO PANELBOARD LN12; CIRCUITS 1, 3, 5.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT

TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

LN12

1,3,5

T1 d b

LIGHT FIXTURE ON EM / LIFE SAFETY BRANCH

LIGHT FIXTURE ON CRITICAL BRANCH

SYMBOL

LV

UE

EX

UHVE

OHE

OHT

c. DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT

72"

AS NOTED

CIRCUIT BREAKER PANEL

2 POLE SINGLE THROW SWITCH

SINGLE POLE SWITCH

LIGHT ON CORD REEL (TYPE DENOTED)

DIMMER SWITCH

MOMENTARY CONTACT SWITCH

OCCUPANCY SENSOR SWITCH

PUSH BUTTON

SINGLE RECEPT (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

FAN SPEED CONTROL

TIME DELAY SWITCH

DUPLEX SPLIT RECEPT

FOURPLEX RECEPT. (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

DUPLEX RECEPT (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

DUPLEX RECEPT ON EMERGENCY CIRCUIT

DUPLEX ISOLATED GROUND RECEPT

EQUIPMENT CONNECTION

RECEPT ON DROP CORD (DUPLEX SHOWN)

RECEPT ON CORD REEL (DUPLEX SHOWN)

FLOOR RECEPT. (DUPLEX SHOWN)

ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED.

AS NOTED

a. DISTANCE ABOVE TOP OF DOOR FRAME

TIMER SWITCH

AS NOTED

46" 46"

KEYED SWITCH

PILOT SWITCH

3-WAY SWITCH

4-WAY SWITCH

b. DISTANCE TO TOP OF EQUIPMENT OR DEVICE

HAND OR HAIR DRYER (SEE ARCH SPEC)

SOLENOID VALVE

AS NOTED46"

AS NOTED

AS NOTED

72" 72"

72" 72" 72"

72" 72"

72"

72"

SF-1

BUS DUCT WITH PLUG-IN DISCONNECT

(FUSED)

THERMOSTAT

PHOTOCELL/PHOTOSENSOR

ENCLOSED CIRCUIT BREAKER

RELAY

84"

COMB. MOTOR STARTER (NON-FUSED)

MAG. MOTOR STARTER

SAFETY DISC. SW. (FUSED)

SAFETY DISC. SW. (NON-FUSED)

COMB. MOTOR STARTER (FUSED)

POWER OR DISTRIBUTION PANEL

MOTOR

TRANSFORMER (TYPE DENOTED)

MOTOR HORSEPOWER RATED SWITCH

SPECIAL CABINET (TYPE DENOTED)

46"

18"

46"

18"

DESCRIPTION

FLOODLIGHT (TYPE DENOTED)

SURFACE MOUNTED LIGHT (TYPE DENOTED)

POLE MOUNTED LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

EXIT SIGN (TYPE DENOTED)

PENDANT OR HUNG LIGHT (TYPE DENOTED)

TRACK LIGHT/FLOOD LIGHT (TYPES DENOTED)

SURFACE LIGHT (TYPE DENOTED)

STRIP LIGHT (TYPE DENOTED)

EMERGENCY BATTERY LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

PER SCHED

AS NOTED

12" 96"

P2P1

E

A1 L1

A1

AA

D1

AS NOTED

HT AFF SYMBOL

S1 S1

18"

HT AFF

AS NOTED

SYMBOL

JUNCTION BOX (WALL/FLOOR/CEILING)

PULL BOX

POWER POLE (OPEN OFFICE STYLE)

MULTIOUTLET ASSEMBLY

DESCRIPTION HT AFF

12"

d. DISTANCE BELOW CEILING

ANTENNA

CCTV CAMERA

NURSE CALL MASTER STATION

NURSE CALL DOME LIGHT

NURSE CALL EQUIPMENT CABINET

AS NOTED

EQUIPOTENTIAL GROUND OUTLET

SPEAKER

HORN TYPE SPEAKER

VOLUME CONTROL

BELL / CHIME / BUZZER

CABLE TRAY (TYPE DENOTED)

COMBINATION VOICE / DATA OUTLET,

(SLASH INDICATES MOUNTING 8" ABOVE

FINISHED COUNTER)

WALL TELEPHONE OUTLET

INTERCOM OUTLET LOCATION

TELEPHONE OUTLET (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

TELEVISION OUTLET

DOOR CONTACTS / DOOR SWITCH

CARD READER

ELECTRIC STRIKE

MOTION DETECTOR

NURSE CALL DUTY STATION

NURSE CALL STAFF STATION

NURSE CALL CODE BLUE STATION

NURSE CALL SINGLE PATIENT STATION

NURSE CALL DUAL PATIENT STATION

F.A. PULLSTATION

F.A. DOOR HOLDER

FIRE ALARM SHUT DOWN RELAY

SPRINKLER VALVE TAMPER SWITCH

SPRINKLER FLOW SWITCH

HEAT DETECTOR

HT AFF

CONDUIT TRANSITION DOWN

CONDUIT TRANSITION UP

BRANCH CIRCUIT HOME RUN

UNDERGROUND HIGH VOLTAGE ELECTRICAL

UNDERGROUND ELECTRICAL

LOW VOLTAGE POWER WIRING

EXISTING CONDUIT

OVERHEAD TELEPHONE

OVERHEAD ELECTRIC

CONDUIT EXPOSED

CONDUIT STUBBED OUT

CONDUIT CONCEALED BELOW FLOOR

CONDUIT CONCEALED IN WALL OR

OVERHEAD

DESCRIPTION

FIRE ALARM CHIME

SMOKE DETECTOR

FIRE ALARM STROBE

FIRE ALARM SPEAKER / STROBE

DUCT SMOKE DETECTOR

REMOTE TEST/STATUS STATION

FIRE ALARM CHIME / STROBE

DESCRIPTION

FIRE ALARM HORN

FIRE ALARM HORN / STROBE

SYMBOL

GENERATOR (KVA DENOTED)25 KVA

UNDERGROUND TELEPHONEUT

UCOM UNDERGROUND COMMUNICATIONS

UTV UNDERGROUND CABLE (CATV OR CCTV)

UFIBR UNDERGROUND FIBER OPTIC

ELECTRICAL SYMBOL LEGEND

AS NOTED

46" 46" 46" 46" 46"

46"

46" 46" 46" 46" 46"

46"18"

18"

18" 18" 18"

18"

FOURPLEX RECEPT ON EMERGENCY CIRCUIT18"

VARIABLE FREQUENCY DRIVE

OCCUPANCY SENSOR

18"

18"

84" 84"

OUTLET IN FLOOR (MICROPHONE SHOWN)

MULTI-SERVICE OUTLET

46"

46" 46"

46" 46"

46"

46"

46"

AS NOTED

8"

90"

90"

90"

90"

90"

90"

90"

FIRE ALARM REMOTE ANNUNCIATOR

MAGNETIC LOCK

REQUEST TO EXIT

46"

CONDUIT SLEEVE (SIZE DENOTED)

C C

F F

F S

S F

FIRE ALARM SPEAKER

DATA OUTLET, (SLASH INDICATES MOUNTING

8" ABOVE FINISHED COUNTER)18"

AS NOTED AP WIRELESS ACCESS POINT

C84" SINGLE FACE CLOCK WALL MOUNTED

84" DOUBLE FACE CLOCK WALL MOUNTED

C

F

S

F

FIRE ALARM CONTROL PANEL

72" LIFE SAFETY CIRCUIT BREAKER PANEL

72" CRITICAL CIRCUIT BREAKER PANEL

72" EQUIPMENT CIRCUIT BREAKER PANEL

GFI DUPLEX RECEPT. (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)18"

GFI FOURPLEX RECEPT. (SLASH INDICATES 8"

MOUNTING ABOVE FINISHED COUNTER)

18" a a b b b b b b b b b b b b b c b b b b b b b d c c c c c c

DATA OUTLET, FLOOR

AUDIO VISUAL OUTLET18"

DH

F

T1

EM

E

E

P

J J

PB

T1

R

P

C PC

W

TV

M

S S

S

FA ANNUN

D

ES

ML

RE

DC

CR

B

D

S

P

P 2

D D

NCM

NCC

L

J

T

V

K

P D

OS

MC

T

TD

F M

VFD

OS

H

IC

AV

G S

FACP

FR

FS

TS

MD

AV

D1

72" b CONTACTOR

46"

DEAD FRONT GFI (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

D D18"

KEYPAD46"c K

LOW-VOLTAGE SWITCH46" L

LOW-VOLTAGE DIMMING SWITCH46"

LV

D

MANUAL MTR. STR. (W/OVERLOADS)46"

MM

S

J

AS NOTED SPECIAL RECEPTACLE

USB RECEPTACLEUS

B

3-WAY DIMMER SWITCH46" 3D

SWITCHBOARD

46" POWER-OPERATED DOOR ACTUATOR

46" EMERGENCY POWER OFF PUSH BUTTONEP

O

TELECOM. EQUIPMENT RACK

GROUNDING BUS BAR

C

S

MD

C D

Z12"a Z NURSE CALL ZONE LIGHT 18"

AS NOTED PROJECTOR

NURSE CALL WORKFLOW STATION46" W

NURSE CALL BATH CALL CORD STATION46" C

NURSE CALL COMBINATION STAFF/

CODE BLUE STATION46" SB

NURSE CALL 37-PIN PATIENT BED JACK18" J

ADDITIONAL NURSE CALL PATIENT STATION SYMBOL SUPERSCRIPTS

S = PATIENT STATION WITH PILLOW SPEAKER

C = PATIENT STATION WITH CALL CORD

2S = DUAL PATIENT STATION WITH PILLOW SPEAKERS

2C = DUAL PATIENT STATION WITH CALL CORD

VS VACANCY SENSOR

VACANCY SENSOR SWITCH46" VS

02/12/2025

SHEET INDEX - ELECTRICAL

SHEET # SHEET NAME

E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

EP101 POWER PLAN - AREA 1

EP401 ENLARGED ELECTRICAL PLANS - PENTHOUSE MECHANICAL 2002

E-601 PARTIAL ELECTRICAL RISER DIAGRAM AND SCHEDULES

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

2/1 2/2

5 8

:16 :49

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_E

_d eta ch ed

.rv t

ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND

GENERAL NOTES

E-001

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE EXHAUST

FANS

REPLACE BOILERS

CFMO #467096 AND

#467097

SDARNG MITCHELL

CSMS #1

KAK02/12/2025

JRB04232099

ALL PRODUCTS AND MATERIALS PROVIDED AS PART OF

THIS PROJECT SHALL COMPLY WITH FEDERAL BUILD

AMERICA, BUY AMERICA ACT (BABAA) REQUIREMENTS.

EPO

JAKE R.

BUCKMILLER

RE

GIS

TE

REDPROFESSIONALENGINE ER

REG. NO.

SOUTH DAKOTA

DATE:

6 7 9 10 11

1.7

A.5

B

G

H

J

K.1

L

2 4 5

8 9

1.7

A.5

B

C

D

E

F

G

H

J

K

K.1

L

COLD

STORAGE

112B

ELECTRICAL

ROOM

CUSTODIAL

CORRIDOR

LUMBER

STORAGE

FITNESS

111G

WOMEN'SMLATRINE

111C

MEN'S LOCKER

111A

MEN'S LATRINE

MECHANICAL

ROOM

112A

TELECOM.

ROOM 111B

STORAGE

111F

WOMEN'S

LOCKER

CORRIDOR

CUSTODIAL

CSMS POL

STORAGE

CSMS

BATTERY

CSMS

HAZARDOUS

CUSTODIAL

CORRIDOR

CSMS TOOL &

SUPPLY

PRODUCTION

CONTROL

LIBRARY

VESTIBULE

INSPECTION

SUPERVISOR

GENERAL

SUPERVISOR

CLERK TYPIST

LOBBY 109

VESTIBULE

CSMS BREAK

ROOM

OMS BREAK

ROOM

CORRIDOR

127F

WOMEN'S

LOCKER

COMM SEC

REPAIR

127G

WOMEN'S

LATRINE

127C

MEN'S LOCKER

RADIATION

CALIBRATION

127B

STORAGE

127A

MEN'S LATRINE

RADIATION

STORAGE

128A

ELECTRICAL

ROOM128

TELECOMUNICATIONS

COLD

STORAGE

132B

MECH.

CUSTODIAL

CORRIDOR

OMS

HAZARDOUS

WASTE

OMS BATTERY

OMS POL

STORAGE

CUSTODIAL

OMS SUPER.

VESTIBULE

COLD

STORAGE

OMS

FLAMMABLE

STORAGE

CSMS

FLAMMABLE

OMS TOOL &

SUPPLY

CSMS

SUPERVISOR

VESTIBULE

TS-1

MS-1

TVSS

MSB-1HP-1

HP-1A

TLP-2

LP-2

LP-2A

LP-2B

RC-1

LP-4A LP-4 TLP-3 LP-3B LP-3A LP-3 TLP-4

HP-2

HP-2A

MCC-2

RC-2

CORRIDOR

FACP

LP-1A

LP-1

02/12/2025

KEYNOTES

1 CP-1 AND CP-2 (CURRENTLY P-1 AND P-2) WILL NOW HAVE VFDS TO SERVE AS STARTERS. MODIFY

THE WIRING IN MCC-2 TO BYPASS THE CONTACTORS AND OVERLOADS FOR EACH PUMP. FEED THE

NEW VFDS FROM OVERCURRENT DEVICES IN THE MCC BUCKETS. PROVIDE LABEL ON EACH MCC

BUCKET FOR PUMPS THAT STARTER IS BYPASSED AND PUMP IS NOW CONTROLLED BY ASSOCIATED

VFD IN PENTHOUSE.

2 RELABEL BUCKETS SERVING P-1, P-2, P-3, AND P-4 TO CP-1, CP-2, CP-3, AND CP-4.

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

KEY PLAN

AREA 1

AREA 2

AREA 3

AREA

AREA 5

2/1 2/2

5 8

:16 :55

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_E

_d eta ch ed

.rv t

POWER PLAN - AREA 1

EP101

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE EXHAUST

FANS

REPLACE BOILERS

CFMO #467096 AND

#467097

SDARNG MITCHELL

CSMS #1

KAK02/12/2025

JRB04232099

SCALE: 1/8" = 1'-0"A1 POWER PLAN - AREA 1

PLAN NORTH

ALL PRODUCTS AND MATERIALS PROVIDED AS PART OF

THIS PROJECT SHALL COMPLY WITH FEDERAL BUILD

E E

EP

O

EPO

E E

VFD CP-3VFD CP-4 VFD CP-1VFD CP-2

EP

O

EPO

14596

JAKE R.

BUCKMILLER

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

J

K

K.1

PENTHOUSE

MECHANICAL

P-3 P-4

P-3P-4

P-2P-1

1 1 2 2

3 3

B-1 B-2

J

K

K.1

CP-3 CP-4

B-1 B-2

PENTHOUSE

MECHANICAL

CP-2 CP-1

16 5

8 8 9 9

11 13

02/12/2025

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

KEY PLAN

AREA 1

AREA 2

AREA 3

AREA

AREA 5

2/1 2/2

5 8

:16 :58

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_E

_d eta ch ed

.rv t

ENLARGED ELECTRICAL

PLANS - PENTHOUSE

MECHANICAL 2002

EP401

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

MITCHELL, SD

REPLACE EXHAUST

FANS

REPLACE BOILERS

CFMO #467096 AND

#467097

SDARNG MITCHELL

CSMS #1

KAK02/12/2025

JRB04232099

SCALE: 1/4" = 1'-0"C1

ENLARGED ELECTRICAL DEMOLITION PLAN - PENTHOUSE

MECHANICAL 2002

SCALE: 1/4" = 1'-0"A1 ENLARGED ELECTRICAL PLAN - PENTHOUSE MECHANICAL 2002

PLAN NORTH

PLAN NORTH

KEYNOTES

1 DISCONNECT EXISTING 480V POWER CONNECTION TO PUMP AND ASSOCIATED VFD. PUMP AND VFD

TO BE REMOVED AND REPLACED BY DIV. 23. MAINTAIN EXISTING RACEWAY AND WIRING AND EXTEND

CIRCUIT AS NEEDED FOR NEW PUMP, DISCONNECT, AND VFD.

2 DISCONNECT EXISTING 480V POWER CONNECTION FROM PUMP. PUMP TO BE REMOVED AND

REPLACED BY DIV. 23. MAINTAIN EXISTING RACEWAY AND WIRING AND EXTEND CIRCUIT AS NEEDED

FOR NEW PUMP, DISCONNECT, AND VFD.

3 DISCONNECT EXISTING 480V POWER CONNECTION TO BOILER. BOILER TO BE REMOVED AND

REPLACED BY DIV. 23. MAINTAIN EXISTING RACEWAYS AND WIRING AND EXTEND AS REQUIRED TO

SERVE NEW BOILER AND DISCONNECT SWITCH.

4 EXTEND EXISTING CIRCUITS PREVIOUSLY SERVING P-1 AND P-2 (NOW CP-1 AND CP-2 RESPECTIVELY)

TO CP-1 AND CP-2 THROUGH ASSOCIATED VFDS.

5 EXTEND EXISTING 480V, 3-PH CIRCUIT PREVIOUSLY SERVING BOILER TO SERVE NEW BOILER. ROUTE CIRCUIT THROUGH DISCONNECT AND CONTACTOR (SEE KEYNOTE 16) ASSOCIATED WITH BOILER.

6 PROVIDE A 30A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH IN A NEMA 1 ENCLOSURE.

7 EXTEND EXISTING 480V, 3-PH CIRCUIT PREVIOUSLY SERVING PUMP TO SERVE NEW PUMP. ROUTE

CIRCUIT THROUGH DISCONNECT (SEE KEYNOTE 6) ASSOCIATED WITH PUMP.

8 EXTEND EXISTING 480V, 3-PH CIRCUIT PREVIOUSLY SERVING PUMP TO SERVE NEW PUMP. ROUTE

CIRCUIT THROUGH DISCONNECT (SEE KEYNOTE 9) ASSOCIATED WITH PUMP.

9 PROVIDE A 100A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH IN A NEMA 1 ENCLOSURE. PROVIDE

UNISTRUT SUPPORT FOR DISCONNECT.

10 DISCONNECT AND REMOVE EXISTING BOILER EMERGENCY STOP PUSH BUTTON. NEW EMERGENCY

STOP PUSH BUTTON TO BE PROVIDED AT THIS LOCATION. SEE KEYNOTE 11 ON THIS SHEET FOR

MORE INFORMATION.

11 PROVIDE MUSHROOM HEAD STYLE PUSH BUTTON WITH PROTECTIVE FLIP COVER FOR EMERGENCY

BOILER SHUT DOWN. INTERLOCK PUSH BUTTON WITH CONTACTOR OF KEYNOTE 16 TO OPEN

CIRCUITS SERVING BOILERS. EMERGENCY STOP PUSH BUTTON BASIS OF DESIGN: PILLA BSD120 EMERGENCY BOILER SHUT DOWN WITH PILCLHCOV1 CLEAR HINGED FLIP COVER. EXTEND NEAREST 120V CIRCUIT TO SERVE AS CONTROL SIGNAL FOR PUSH BUTTON AND CONTACTORS OF KEYNOTE 16

TO CONTROL CONTACTOR COIL.

12 DISCONNECT 480V POWER CONNECTION TO COMBUSTION EXHAUST FAN AND DEMO CIRCUIT BACK

TO SOURCE. FAN TO BE REMOVED BY MECHANICAL CONTRACTOR.

13 REUSE EXISTING CIRCUITS PREVIOUSLY SERVING P-3 AND P4 (NOW CP-3 AND CP-4 RESPECTIVELY)

TO SERVE NEW CP-3 AND CP-4 AND ASSOCIATED VFDS.

14 SURFACE MOUNT NEW EMERGENCY STOP TO EXISTING CMU WALL. PATCH CMU WALL PENETRATION

FOR INSTALLATION OF CONDUIT SERVING EMERGENCY STOP.

15 INSTALL NEW PUSH BUTTON 60" AFF.

16 PROVIDE A 30A, HEAVY DUTY, NON-FUSED DISCONNECT SWITCH AND FOUR POLE CONTACTOR WITH

120V CONTROL COIL. CONTACTOR SHALL BE RATED AT A MINIMUM FOR THE BOILER ELECTRICAL

LOAD. PROVIDE NEMA 1 ENCLOSURE(S) FOR DISCONNECT AND CONTACTOR. WIRE 120V SIGNAL

FROM EMERGENCY STOPS OF KEYNOTE 11 ON THIS SHEET TO CONTROL COIL OF CONTACTOR TO

OPEN CONTACTOR UPON PRESSING EMERGENCY STOP PUSH BUTTON AND TO CLOSE CONTACTOR

WHEN PUSH BUTTON IS RESET. PROVIDE ALL COMPONENTS AND WIRING AS NEEDED FOR COMPLETE AND WORKING SYSTEM. PROVIDE LABEL ON CONTACTOR INDICATING CIRCUIT NUMBER AND PANEL

NAME FOR CIRCUIT CONTROLLING CONTACTOR.

ELECTRICAL DEMO GENERAL NOTES

A ALL EQUIPMENT SHOWN BOLD AND DASHED ON THE PLANS SHALL BE REMOVED UNDER THIS

CONTRACT UNLESS OTHERWISE NOTED. REMOVE ALL ABANDONED HANGERS AND ACCESSIBLE

CONDUITS. EXISTING ITEMS SHOWN SOLID SHALL BE MAINTAINED.

B WHERE EQUIPMENT IS INDICATED TO BE REMOVED, THE BRANCH CIRCUIT SHALL BE REMOVED BACK TO NEXT JUNCTION POINT. ALL ABANDONED BRANCH CIRCUITS WHICH SERVE EQUIPMENT SHALL BE

REMOVED BACK TO SOURCE.

ALL PRODUCTS AND MATERIALS PROVIDED AS PART OF

THIS PROJECT SHALL COMPLY WITH FEDERAL BUILD

JAKE R.

BUCKMILLER

RE

G IS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

N E

L

M

FIRST LEVEL

PENTHOUSE

J J

VFD CP-1 VFD CP-2 VFD CP-3 VFD CP-4

CP-1 CP-2 CP-3 CP-4

10 10

10 10

10 10

UTILITY

TRANSFORMER

TRANSITION

CABINET

GENERATOR

DOCKING

STATION

MAIN

SWITCH

TS-1

MSB-1 MCC-2

02/12/2025

© TSP, Inc. 2025

ISSUES

SHEET NUMBER

SHEET TITLE

C

A

B

2 3

D

E

1 2 3

4 5 6

4 5 6

A

B

C

D

E

TSP, Inc.

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LIS

TE

D

DR

AW

IN

GS

S

CA

LE

(S ) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L 3 x 4

FO

RM

AT

Architecture Engineering

Planning

2/1 2/2

5 8

:17 :01

A M

_S D

De pt of Mi lita ry

Mi tch ell _B oil er

_E

_d…

This is the start of the file's text. The full file is on GovTribe.