This document appears to be a set of drawings related to the installation of a fire suppression system. The drawings provide detailed information about the layout and components of the planned fire suppression system, including the locations of piping, sprinklers, and other equipment. A related federal contract opportunity has been issued by the Department of the Air Force Materiel Command Test Center for the installation of this fire suppression system. The solicitation number is FA282324QA042, and the project is titled "Fire Suppression System Install". The contract opportunity is in the pre-solicitation phase, and interested contractors are encouraged to review the attached drawings and technical requirements to determine their capability to provide the required services. No other details, such as response dates, pricing terms, or set asides, are provided in the information given.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| TRD_Redacted.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEYPLAN - WEST
S-101/S-103/S-105
S-102/S-104/S-106
A
B GFEC.2 D.4
C D
2.7
S-201 1
S-202
S-202
M A
T C
H
LI
N E
3.7
6.5
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X7X5/16
HSS7X
7X
5/
HSS7X
7X
5/
HSS7X
7X
5/
HSS7X
7X
5/
HSS7X
7X
5/
HSS6X
6X
1/
HSS6X
6X
1/
HSS6X
6X
1/
HSS7X
7X
5/
HSS7X
7X
5/
HSS6X
6X
1/
HSS6X
6X
5/
HSS6X
6X
5/
HSS6X
6X
1/
HSS6X
6X
1/
HSS6X
6X
1/
HSS6X
6X
1/
HSS6X
6X
5/
HSS6X
6X
3/
HSS6X
6X
1/
2 HSS6X
6X 1/
HSS8X
6X
5/
F6.0
F9.0 F9.0 F9.0 F9.0
F9.0
F9.0
F9.0
F7.0
F7.0
F9.0
F8.0
F9.0 F9.0
F9.0 F9.0
F9.0
F9.0
F9.0
F9.0
F10.0
F9.0
F9.0
F10.0
S-402
S-501
14" DEEP x 18" WIDE
TROUGH W/ CHECKER
PLATED TOP
'-4
'-8
'-5
1' -3
/4
1'
-0
'-7
4'
-7
/4
3' -0
/2
2'
-1 1"
'-5
F38.0x12.0
F38.0x12.0
26'-5" 24'-9"
1'-4"
24'-8" 12'-8" 13'-4" 26'-0" 26'-0"
WF6.0
W F
6.
F38.5x14.0
-1'-2"-1'-2"
-1'-2"
WF2.5 WF2.5
W F
2.
W F
2.
W F
2.
W F
2.
WF2.5
WF2.0
WF2.0
WF2.0
WF2.0
W F
2.
W F
2.
W F
2.
W F
2.
S-203 1 S-2032
S-401
S-401
S-401
Sim
S-402
S-401
6" SLAB
4" SLAB
4" SLAB
4" SLAB
4" SLAB
4" SLAB
6" SLAB
4" SLAB
4" SLAB
WF2.5 WF2.5
8" 8"
S-402
TYP. @ INT. COLUMNS
WITH ACCESS FLOOR
1/2" BACKER ROD AND
CAULKED EXPANSION JOINT;
TYP. @ SIM. LOCATIONS
1' -1
1"
12" SCREENWALL TYPE A
S C
R E
E N
W A
LL
T
Y P
E A
S-401
Sim
S-301
Sim
S-401
S-301
Sim
S-301
Sim
S-301
Sim
F.O.S.S.
1 3/8"
F .O
.S
5' -7
/8
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S.C.J.
S .C
.J
S.C.J.
S.C.J.
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S .C
.J . S
.C .J.
S.C.J.
S.C.J.
S.C.J.
S.C.J.
S .C
.J
S .C
.J
S .C
.J
S.C.J.
S.C.J. S.C.J.
S .C
.J
S .C
.J
S .C
.J
S .C
.J
S.C.J.
S.C.J.
S .C
.J
S .C
.J
S .C
.J
S.C.J.
S.C.J.
S .C
.J . S .C
.J
S .C
.J
T S
2.
S.C.J.
MECH. SLAB
REFER TO S-503
MECH. SLAB
REFER TO S-503
MECH. SLAB
REFER TO S-503
S-301
Sim
S-301
Sim
S-301
Sim
S .C
.J
S .C
.J
6" SLAB
S-307
S-403
T D x2
TD24x24
TD24x24
T D x2
3' -4
2'
-7
A.C.C.
TYP. U.N.O.
9'-8"
S-404
F.O.S.S.
4'-11 5/8"
F.O.S.S.
6'-10 5/8"
F.O.S.S.
3'-1 1/16"
F.O.S.S.
9/16"
F .O
.S .S
3"
F .O
.S .S
3"
F .O
.S .S
'-2
/8
F .O
.S .S
3"
F.O.S.S.
4'-3 5/8"
20'-8 23/64"
-1'-2"
-0'-3/4"-0'-3/4"
4" SLAB
-0'-3/4"
CURB
3 5/8"
CURB
3 5/8"
C U
R B
6"
CURB
6"
C U
R B
6"
C U
R B
5/
8"
CURB
3 5/8"
C U
R B
6"
C U
R B
5/
8"
S-404
C U
R B
6"
'-8
/2
39'-3 5/8"
S-404
R.C.P.20x14
R.C.P.20x14
R.C.P.20x14
R.C.P.36x14 R.C .P
.2 0x1
R.C .P
.2 0x1
R.C .P
.2 0x1
R.C .P
.2 0x1
R.C .P
.5 4x1
R.C .P
.2 0x1
TYP. @ PERIMETER
WALL COLUMNS W/OUT ACCESS FLR.
TYPICAL CMU WALL
STEP AT COLUMN, U.N.O.
R.C.P.36x14
WF2.5
WF2.5
WF2.5
S
-2 '-0
-3 '-4
S
-2 '-0
-3 '-4
FOUNDATION AND SLAB-ON-GRADE NOTES & LEGEND
ADDITIONAL GROUT FILLED AND REINFORCED
CELL IN ADDITION TO TYPICAL REINFORCING.
PROVIDE BAR SIZE TO MATCH WALL REINF.
12" NOMINAL CMU WALL. UNLESS NOTED
OTHERWISE (U.N.O.), WALL SHALL BE
REINFORCED WITH #6 VERTICAL REINFORCING
AT 2'-0" ON CENTER IN CENTER OF GROUT
FILLED CELLS. PROVIDE HORIZONTAL JOINT
REINFORCING AND ADDITIONAL VERTICAL
REINFORCING AS OUTLINED IN THE GENERAL
NOTES, TYPICAL DETAILS AND SECTIONS IN
THESE DRAWINGS. ALL EXTERIOR CMU WALLS
SHALL BE FULLY GROUT FILLED.
SAWN CONTRACTION JOINT OR CONSTRUCTION
JOINT; CONTRACTOR'S OPTION U.N.O. REFER
TO S-503 FOR TYPICAL DETAILS
S.C.J.
SLAB DEPRESSION; SEE PLAN FOR
DEPRESSION EXTENTS AND DEPRESSION
DEPTH BELOW REF. EL: 0'-0"
-X'-X"
4" MINIMUM THICKNESS SLAB-ON-GRADE
REINFORCED WITH WWF 6x6 W2.0xW2.0 WITH
2" CLR. POSITIVE SUPPORT FROM BOTTOM OF
SLAB. SLAB SHALL BE PLACED OVER A
VAPOR BARRIER AND CAPILLARY BREAK AS
INDICATED IN THE GENERAL NOTES SECTION
2.08 ON SHEET S-001.
4" SLAB =
(2) #4x4'-0" RE-ENTRANT CRACK CONTROL
REINF. W/ 1" CLR TO TOP OF SLAB
S
= FOOTING STEP, SEE DET. 2/S-503
= REINFORCED CONCRETE PIER 1'-6"X1'-6",
SEE DET. 2/S-402. (8) #6 VERT.
RCP18
6" MINIMUM THICKNESS SLAB-ON-GRADE
REINFORCED WITH WWF 6x6 W2.9xW2.9 WITH
3" CLR. POSITIVE SUPPORT FROM BOTTOM OF
SLAB. SLAB SHALL BE PLACED OVER A
VAPOR BARRIER AND CAPILLARY BREAK AS
INDICATED IN THE GENERAL NOTES SECTION
2.08 ON SHEET S-001.
6" SLAB =
VERTICAL MASONRY CONTROL JOINT
LOCATION; REFER TO S-501
12" SCREENWALL
TYPE A
12" NOMINAL CMU WALL. UNLESS NOTED
OTHERWISE (U.N.O.), WALL SHALL BE
REINFORCED WITH #7 VERTICAL REINFORCING
AT 1'-4" ON CENTER IN CENTER OF GROUT
FILLED CELLS. PROVIDE HORIZONTAL JOINT
REINFORCING AND ADDITIONAL VERTICAL
REINFORCING AS OUTLINED IN THE GENERAL
NOTES, TYPICAL DETAILS AND SECTIONS IN
THESE DRAWINGS. ALL EXTERIOR CMU WALLS
SHALL BE FULLY GROUT FILLED.
12" SCREENWALL
TYPE B
= HSS 4x4x1/4" ELEVATOR RAIL SUPPORT
COLUMN AND HOIST BEAM SUPPORT. G.C.
FIELD LOCATE BASED ON FINAL RAIL
SUPPORT LOCATIONS.
HSS4-R.S.
= ALUMINUM CANOPY COLUMN BY
DELEGATED DESIGN ENGINEER.
A.C.C.
= FACE OF SLAB STEP, REFER TO DETAILSF.O.S.S.
EXISTING CONDUITS BELOW GRADE,
CONTRACTOR SHALL LOCATE AND PROTECT
DURING CONSTRUCTION. REFER TO 5/S-404
FOR DETAILS WHERE CONDUIT CONFLICTS
WITH STRUCTURAL FOUNDATIONS AND
STEMWALLS
SIMILAR TO TYPE B, EXCEPT BASE OF WALL
IS REQUIRED TO BE CAST-IN-PLACE
CONCRETE; SEE 4/S-503 FOR DETAILS
12" SCREENWALL
TYPE C
=REFER TO DETAIL 5/S-502 FOR LOOSE LAID HOT-DIP
GALVANIZED CMU VENEER LINTELS, REFER TO SPECIFIC
DETAILS IN THIS SET FOR OPENINGS > 6'-4" IN WIDTH
FOUNDATION SCHEDULE
FOOTING MARK LENGTH WIDTH THICKNESS TOP REINFORCING BOTTOM REINFORCING
F7.0 1'-2" (7) #5 E.W.(7) #5 E.W.
SEE PLAN 2'-0" 1'-0" N/A (3) #5 L.W. & #5 @ 24" O.C. S.W.
WF6.0
WF8.0
SEE PLAN 6'-0" 1'-6" (5) #5 L.W. & #5 @ 12" O.C. S.W.
F8.0 8'-0" 8'-0" 1'-4" (9) #5 E.W. (9) #5 E.W.
7'-0" 7'-0"
F5.0 1'-0" (7) #4 E.W.N/A5'-0" 5'-0"
WF2.0
SEE PLAN 1'-6"8'-0" (8) #5 L.W. & #5 @ 8" O.C. S.W.
F6.0 1'-0" (8) #4 E.W.N/A6'-0" 6'-0"
F9.0 9'-0" 9'-0" 1'-6" (8) #6 E.W. (8) #6 E.W.
F11.0 11'-0" 11'-0" 1'-10" (9) #7 E.W. (9) #7 E.W.
F38.0x12.0
F38.5x14.0
38'-0" 12'-0" 3'-6" #7 @ 8" O.C. E.W.
38'-6" 14'-0" 3'-6" #7 @ 8" O.C. E.W.
#7 @ 8" O.C. E.W.
#7 @ 8" O.C. E.W.
(3) #4 L.W. & #4 @ 24" O.C. S.W.
(6) #4 L.W. & #4 @ 18" O.C. S.W.
SEE PLAN 2'-6" 1'-0" N/A (3) #5 L.W. & #5 @ 24" O.C. S.W.WF2.5
F10x12 10'-0" 12'-0" 1'-6" #6 @ 12" O.C. E.W. #6 @ 12" O.C. E.W. W/STD. 90 DEG. HKS
F12x14 12'-0" 14'-0" 1'-6" #6 @ 12" O.C. E.W. #6 @ 12" O.C. E.W. W/STD. 90 DEG. HKS
F10.0 10'-0" 10'-0" 1'-8" (10) #6 E.W. (10) #6 E.W.
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
S-101FTFA 16-3007
F O
U N
D A
T
IO
N A
N D
S L
A B
-O N
-G R
A D
E P
L A
N
W E
S T
IC
M
IC
M
B J
B
L J
D
M
A Y
M E
F
S
T.O.SLAB REF. ELEV: 0'-0" U.N.O.; REF. EL: 0'-0" = ELEV: 57.50'
NORTH
0 4' 8' 16'
SCALE 1/8":1'-0"
2' 1/8" = 1'-0"S-101
1 FOUNDATION AND SLAB-ON-GRADE PLAN-WEST
1 1
A
M E
N D
J U
L Y
AMENDMENT 0002
L O
C U
S S
D U
S S
D
USSD
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
MECHANICAL YARD
ACR GSSO
128 ACR STORAGE
ACR ISSO
130B
ACR ISSM
ACR SYSADM
ACR CONF. RM
CORRIDOR
AVIONICS TEST
LAB
COMM RM
CYBER/EW LAB
STAIR 1
FIRE PUMP
THREAT
DEVELOPMENT
LAB
144C
REPORT WRITING
REPORT WRITING
THREAT
RESEARCH ROOM
ACR SERVER
C/EW ANALYSIS
ATL STORAGE
CORR.
A B C.2C D D.4 E F G
2.8
1.6
R
CRAC UNIT
SHUT DOWN RELAYS
R
R
CRAC UNIT
SHUT DOWN RELAYS
R
P
P
P
P
MM
MM
MM
MONITOR ANECHOIC CHAMBER
CLEAN AGENT FIRE
SUPPRESSION SYSTEM FOR
ALARM, SUPERVISORY,
AND TROUBLE CONDITIONS.
CLEAN AGENT SYSTEM IS BUILT-
IN/PROVIDED BY THE ANECHOIC
CHAMBER MANUFACTURER.
EXACT LOCATION OF MONITOR
MODULES IS TO BE
DETERMINED IN THE FIELD
MM MM
MM MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MM
MM
MM
MM
MM
MM
MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MONITOR SPRINKLER
WATERFLOW SWITCH
AND TAMPER SWITCH
75 75
15 15
30 30
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MM
FIRE PUMP RUNNING,
LOSS OF POWER,
AND PHASE REVERSAL
WP
WP
ATL ANALYSIS
DEV & RE LAB
144B
MM
MM
MM
MM
MM
MM
FIRE PROTECTION CONTROL
VALVES. SEE SHEET FX401
FOR VALVE LOCATIONS
TEXT
T E
X T
T E
X T
R R
R
SURFACE MOUNTED
M A
T C
H
LI
N E
1/ F
A
1/ F
A
M A
T C
H
LI
N E
1/ F
A
1/ F
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA102
P A
R T
IA
L
F
IR
S T
F L
O O
R F
IR
E
A L
A R
M P
L A
N
W E
S T
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0"FA102
1 PARTIAL FIRST FLOOR FIRE ALARM PLAN - WEST
FIRE ALARM SYSTEM SEQUENCE OF OPERATION MATRIX
MANUAL PULL STATION
ALARM AT
FACU & FSA
SUPERVISORY
AT FACU &
FSA
TROUBLE AT
FACU & FSA
ALARM AT
RECEIVING
STATION
TROUBLE
AT
RECEIVING
STATION
SUPERVISORY
AT RECEIVING
STATION
ACTIVATE
SPEAKERS,
STROBES
& FIRE
ALARM
MESSAGE
SILENCE
SPEAKERS
& STROBES
SHUTDOWN
AHU / ERV
SMOKE DETECTOR
WATERFLOW SWITCH
INPUT RECEIVED FROM
MASS NOTIFICATION
SYSTEM (MNS)
TAMPER SWITCH
FIRE ALARM TROUBLE
CONDITION (OPENS,
SHORTS OR GROUNDS)
ALARM SILENCE AT
FACU OR FSA
DUCT SMOKE DETECTOR
MNS PANEL TROUBLE
OVERRIDE FA
MESSAGE
OVERRIDE PA
SYSTEM
MNS SYSTEM
TROUBLE AT
RECEIVING
STATION
*SEE SPECIFICATION SECTION 28 31 76, PARAGRAPH 2.20.2 FOR SPECIFIC SIGNALS REQUIRED TO BE TRANSMITTED TO THE RECEIVING STATION
ULTRA-SENSITIVE SMOKE
DETECTOR MOST
SENSITIVE ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR SECOND
LEVEL ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR LEAST
SENSITIVE ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR SUPERVISORY
CONDITION
ULTRA-SENSITIVE SMOKE
DETECTOR TROUBLE
CONDITION
NOTE
ALARM LEVEL 1 DEFAULT
SETTING SHALL BE 0.025%
OBSCURATION PER FOOT
ALARM LEVEL 2 DEFAULT
SETTING SHALL BE 0.044%
OBSCURATION PER FOOT
ALARM LEVEL 3 DEFAULT
SETTING SHALL BE 0.062%
OBSCURATION PER FOOT
FIRE PUMP RUNNING
FIRE PUMP LOSS OF
POWER
FIRE PUMP PHASE
REVERSAL
ANECHOIC CHAMBER
CLEAN AGENT ALARM
ANECHOIC CHAMBER
CLEAN AGENT
SUPERVISORY
ANECHOIC CHAMBER
CLEAN AGENT TROUBLE
INITIATE
ELEVATOR
PRIMARY
RECALL
INITIATE
ELEVATOR
SECONDARY
RECALL
INITIATE
ELEVATOR
SHUNT TRIP
ACTIVATE
SPEAKERS,
STROBES
& MNS
MESSAGE
ELEVATOR MACHINE ROOM
WATERFLOW SWITCH
ACTIVATE
FLASHING
FIRE
FIGHTER'S
HAT
ELEVATOR MACHINE
ROOM SMOKE DETECTOR
ELEVATOR 1ST FLOOR
LOBBY SMOKE DETECTOR
ELEVATOR 2ND FLOOR
LOBBY SMOKE DETECTOR
SHUTDOWN
CRAC
UNITS
ACTIVATE
STEADY
FIRE
FIGHTER'S
HAT
CLEAN AGENT
DISCHARGE
ALARM AT
RECEIVING
STATION
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA502
F
IR
E A
L A
R M
S E
Q U
E N
C E
O F
O P
E R
A T
IO
N
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: NONEFA502
1 SEQUENCE OF OPERATION MATRIX
INDICATES AIR FLOW
INDICATES DUCT INLET SIZE
INDICATES TYPE
INDICATES QTY
THERMIDISTAT
HEX SHEET NOTE
HUMIDISTAT
CARBON DIOXIDE SENSOR
SQUARE SHEET NOTE
TRIANGLE SHEET NOTE
ROUND SHEET NOTE
CONNECT TO EXISTING
DOOR UNDER CUT3/4"
SENSOR
FLOW SENSOR
AD
AD
RELATIVE HUMIDITY
TEMPERATURE SENSOR
SMOKE DETECTOR
FLOW MEASURING STATION
DAMPER ACTUATOR
STATIC PRESSURE TRENDS
ROOM TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
ANALOGUE IN
ANALOGUE OUT
DIGITAL IN
DIGITAL OUT
DEMO TO THIS POINT
INDICATES SECTION
SHEET WHERE SECTION
IS REFERENCED
SHEET WHERE SECTION
IS DRAWN
INDICATES SECTION
SHEET WHERE SECTION
IS DRAWN
SECTION TAG
CALLOUT TAG
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
EXHAUST AIR DUCT UP
EXHAUST AIR DUCT DOWN
WxH
RECTANGULAR DUCTWORK, SIZES SHOWN ARE
INTERNAL CLEAR DIMENSIONS. FIRST FIGURE IS SIDE
SHOWN.
W/H
OVAL DUCTWORK, SIZES SHOWN ARE INTERNAL CLEAR
DIMENSIONS. FIRST FIGURE IS SIDE SHOWN.
ø ø ø ROUND SPIRAL SEAM GALVANIZED STEEL DUCTWORK.
SIZE SHOWN IS SHEET METAL DIAMETER.
W xH ø
ROUND BRANCH DUCT TAKEOFF FROM ROUND DUCT
MAIN. BRANCH DUCT SHALL BE ROUND SNAPLOCK
GALVANIZED STEEL DUCTWORK OR FLEXIBLE ROUND
DUCT. ROUND DUCT TAP IN SHALL BE MADE WITH SPIN-
IN COLLAR WITH MANUAL VOLUME DAMPER.
ROUND BRANCH DUCT TAKEOFF FROM RECTANGULAR
DUCT MAIN. BRANCH DUCT SHALL BE ROUND SNAPLOCK
GALVANIZED STEEL DUCTWORK OR FLEXIBLE ROUND
DUCT. ROUND DUCT TAP IN SHALL BE MADE WITH SPIN-
IN COLLAR WITH MANUAL VOLUME DAMPER.
W xH
WxH RECTANGULAR BRANCH DUCT TAKE OFF FROM
RECTANGULAR DUCT MAIN WITH 45° COLLAR AND
MANUAL VOLUME DAMPER.
WxH DOUBLE WALL DUCTWORK
SQUARE THROAT ELBOW IN RECTANGULAR DUCT
WITH DOUBLE WALL TURNING VANES.
LONG RADIUS ELBOW IN RECTANGULAR DUCT.
RECTANGULAR TO ROUND DUCT TRANSITION.
RECTANGULAR TO RECTANGULAR DUCT TRANSITION.
AUTOMATIC OPPOSED BLADE DAMPER
AUTOMATIC PARALLEL BLADE DAMPER
ROUND MANUAL VOLUME DAMPER
RECTANGULAR MANUAL VOLUME DAMPER
M
M
24"x24" FACE CEILING DIFFUSER EQUAL TO "TITUS TMSA-
AA". PROVIDE SURFACE MOUNT STYLE WITH TRIM RING
FOR GYPSUM BOARD CEILING AND LAY-IN TYPE AT T-BAR
CEILING GRID. ROUND NECK SIZE AND AIRFLOW AS
INDICATED. 4-WAY DIRECTION OF THROW, UNLESS
OTHERWISE INDICATED WITH ARROW. PROVIDE WITH
OPPOSED BLADE VOLUME CONTROL DAMPER AT
BRANCH TAKEOFF.BACK FACE OF DIFFUSER SHALL
HAVE INSULATION BLANKET.
SIDE WALL MOUNTED SUPPLY REGISTER, EQUAL TO
"TITUS 272FL".
SIDE WALL MOUNTED RETURN REGISTER, EQUAL TO
"TITUS 350FL".
CD 8"ø
200 CFM
TYP. OF 2
DIFFUSER / GRILLE TAG
SYMBOLS
T
CO2
H
S
CEILING DIFFUSER EQUAL TO "TITUS 250-AA". PROVIDE
SURFACE MOUNT STYLE WITH TRIM RING FOR GYPSUM
BOARD CEILING AND LAY-IN TYPE AT T-BAR CEILING
GRID. ROUND NECK SIZE AND AIRFLOW AS INDICATED.
4-WAY DIRECTION OF THROW, UNLESS OTHERWISE
INDICATED WITH ARROW. PROVIDE WITH OPPOSED
BLADE VOLUME CONTROL DAMPER AT BRANCH
TAKEOFF.BACK FACE OF DIFFUSER SHALL HAVE
INSULATION BLANKET.
FS
12"x12" FACE CEILING DIFFUSER EQUAL TO "TITUS TMSA-
AA". PROVIDE SURFACE MOUNT STYLE WITH TRIM RING
FOR GYPSUM BOARD CEILING AND LAY-IN TYPE AT T-BAR
CEILING GRID. ROUND NECK SIZE AND AIRFLOW AS
INDICATED. 4-WAY DIRECTION OF THROW, UNLESS
OTHERWISE INDICATED WITH ARROW. PROVIDE WITH
OPPOSED BLADE VOLUME CONTROL DAMPER AT
BRANCH TAKEOFF.BACK FACE OF DIFFUSER SHALL
HAVE INSULATION BLANKET.
RETURN AIR CEILING GRILLE EQUAL TO "TITUS 350FL".
PROVIDE SURFACE MOUNT STYLE WITH TRIM RING FOR
GYPSUM BOARD CEILING AND LAY-IN TYPE AT T-BAR
CEILING GRID.
EXHAUST AIR GRILLE EQUAL TO "TITUS 350FL".
PROVIDE SURFACE MOUNT STYLE WITH TRIM RING
FOR GYPSUM BOARD CEILING AND LAY-IN TYPE AT T-
BAR CEILING GRID.
SIDE WALL MOUNTED EXHAUST REGISTER, EQUAL TO
"TITUS 350FL".
RH
TS
SD
FMS
DA
SPT
RTS
DPS
AI
AO
DI
DO
M-401
M-101 M-101
HVAC LEGEND
TYPICAL SECURE AREA CONSTRUCTION NOTES
HVAC GENERAL NOTES
1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR HVAC WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
4. THE APPROXIMATE LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN WHERE APPLICABLE. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES AND PROTECT BEFORE COMMENCING WORK.
5. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION.
6. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT, VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.
7. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 IN. PAD SHALL
EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 IN. ON ALL SIDES.
8. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO SERVICE DAMPERS, VALVES, SMOKE
DETECTORS, AND OTHER CONCEALED MECHANICAL EQUIPMENT.
9. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DECTECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS, AND OTHER ITEMS LOCATED IN THE DUCTWORK THAT REQUIRE SERVICE AND/OR INSPECTION.
10. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION-FREE
INSTALLATION.
11. LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED.
12. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH LISTED FIRESTOP SYSTEM.
13. ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, TRAPPED PER MANUFACTURERS DETAILS FOR ACTUAL EQUIPMENT AND STATIC PRESSURE. CONDENSATE SHALL BE PIPED TO THE NEAREST MECHANICAL
ROOM FLOOR DRAIN OR JANITOR'S CLOSET SINK. PROVIDE CONDENSATE PUMPS AS REQUIRED.
14. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
15. THERMOSTATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18” OF JAMB AT LOCATIONS WITH LIGHT SWITCHES, LOCATE THERMOSTAT SUCH THAT LIGHT SWITCH IS BETWEEN THERMOSTAT AND JAMB. VERIFY THERMOSTAT LOCATION WITH SYSTEM
FURNITURE LAYOUT PRIOR TO INSTALLING THERMOSTATS.
16. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS.
17. PROVIDE ALL 90-DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS
WITH TURNING VANES.
18. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND OTHER
CEILING MOUNTED EQUIPMENT AND MAKE MINOR DUCT MODIFICATIONS TO SUIT.
19. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY. LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE FRAME OR FLANGES.
APPROXIMATE ROUGH OPENING IN WALL ASSEMBLY IS INDICATED ON ARCHITECTURAL.
20. AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 6” CLEARANCE BETWEEN MECHANICAL EQUIPMENT AND DUCT INSULATION TO TOP OF LIGHTS. PROVIDE CLEARANCE AND ACCESS ALL AROUND AND
BELOW MECHANICAL EQUIPMENT AS REQUIRED FOR ROUTINE MAINTENANCE.
21. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT.
22. ALL AIR INTAKES OPENING TO EXTERIOR SHALL HAVE A MIN 10'-0” CLEARANCE FROM ANY EXHAUST OPENING TO PREVENT RECIRCULATION.
23. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHERWISE NOTED.
24. EXPOSED DUCTWORK SHALL BE DOUBLE-WALL INSULATED WITH A SOLID LINER. PROVIDE GALVANIZED FINISH SUITABLE FOR PAINTING.
PRIME AND PAINT TO COLOR SELECTED BY GOVERNEMNT.
25. ALL ROUND FLEXIBLE DUCT SHALL BE FACTORY PREINSULATED THERMOFLEX OR EQUAL. MAXIMUM LENGTH OF ANY FLEXIBLE DUCT RUNOUT SHALL BE 5'-0". WHERE LENGTH REQUIRED EXCEEDS 5'-0", INSTALL EXTERNALLY INSULATED ROUND SNAPLOCK DUCT FOR
BALANCE OF DISTANCE TO SPIN-IN TAP AT MAIN DUCT TRUNK.
26. ALL SUPPLY AIR DUCTWORK UPSTREAM OF TERMINAL UNITS SHALL BE MEDIUM PRESSURE RECTANGULAR, ROUND, OR FLAT OVAL SPIRAL SEAM AS INDICATED. SMACNA STATIC PRESSURE CLASS 4" W.G., SEAL CLASS A, EXTERNALLY INSULATED.
27. ALL SUPPLY AIR DUCTWORK DOWNSTREAM OF AIR TERMINAL UNITS (EXCEPT TAKEOFFS TO SUPPLY AIR DIFFUSERS) SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 2" W.G., SEAL CLASS A, EXTERNALLY INSULATED.
28. ALL RETURN AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 1” W.G., SEAL CLASS A.
29. RETURN AIR DUCTWORK SHALL NOT BE INSULATED.
30. ALL OUTSIDE AIR INTAKE DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 1” W.G., SEAL CLASS A, EXTERNALLY INSULATED.
31. EXHAUST AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 1/2" W.G., SEAL CLASS A, EXTERNALLY INSULATED.
32. EMERGENCY AIR DISTRIBUTION SHUTDOWN SWITCHES SHALL BE EASILY ACCESSIBLE BY BUILDING OCCUPANTS AND LOCATED ADJACENT TO OR IN BUILDING MASS NOTIFICATION SYSTEM (MNS) LOCAL OPERATING CONSOLES (LOC.) SHUTOFF SWITCHES SHALL BE WELL
LABELED, AND OF A DIFFERENT COLOR THAN FIRE ALARM PULL STATIONS.
1. REFER TO DRAWINGS G-107 THRU G-110 FOR SECURE AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA CONSTRUCTION NOTES.
2. ALL PENETRATIONS THROUGH SECURITY WALLS SHALL BE SEALED TO MAINTAIN STC RATING AND FIRE RATING AS
APPLICABLE.
3. METALLIC NON-PRESSURE PIPING AND CONDUITS PENETRATING SECURITY WALLS, FLOORS AND CEILINGS SHALL
HAVE NON-METALLIC SEPARATIONS.
4. PRESSURE PIPING SHALL BE GROUNDED TO THE BUILDING STRUCTURE. SEE DETAIL ON SHEET M-504.
5. DUCTWORK PENETRATING SECURITY PERIMETER SHALL HAVE NON-METALLIC SEPARATIONS, AND SOUND MASKING
WHITE NOISE. SECURITY MAN BARS WITH INSPECTION PORTS ARE REQUIRED IN DUCTS LARGER THAN 96 SQUARE INCHES THAT PENETRATE WALLS DESIGNED TO ICD/ICS 705 STANDARDS. REFER TO DETAILS ON SHEET M-504.
6. SECURITY MAN BAR INSPECTION PORTS SHALL BE INSTALLED IN A LOCATION TO PROVIDE SUFFICENT CLEARANCE FOR SECURITY PERSONNEL ACCESS ON LADDERS TO ACCESS INSPECTION PORT, SO ADJACENT BUILDING SYSTEMS (DUCTWORK, CABLE TRAY, PIPPING, CONDUITS, ETC.) SHALL BE INSTALLED TO PROVIDE SUFFICIENT CLEARANCE TO
THE INSPECTION PORT.
7. ALL BUILDING SYSTEMS, EQUIPMENT, UTILITIES, DUCTWORK, PIPING, CONDUITS AND PATHWAYS, CABLING AND DEVICES SHALL NOT BE INSTALLED WITHIN DESIGNATED SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED BELOW THE SECURITY STC CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES. UTILITIES INTENDED TO BE INSTALLED CONCEALED (NOT EXPOSED) TO BE INSTALLED IN THE DESIGNATED “FRANGIBLE” PORTION OF THE WALL ASSEMBLY.
8. LIGHT GAGE STEEL FRAMING OF THE SECURITY STC CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES SHALL NOT BE UTILIZED TO SUPPORT UTILITIES AND UTILITY SUPPORT ASSEMBLIES. ALL UTILITY AND SUPPORTS SHALL BE HUNG
FROM THE BUILDING STRUCTURE.
FLD - 24"x24" FLOOR DIFFUSER 3, EQUAL TO
"TATE DIRECTPERF 32%". PROVIDE WITH
MULTI-ZONE OPPOSED BLADE DAMPER.
EMERGENCY AIR DISTRIBUTION SHUTDOWN SWITCHSS
SECURITY MAN BARS IN DUCTSB
A
SHEET
IDENTIFICATION
US Army Corps of Engineers ® Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T M
O B
IL
E
A
L A
B A
M A
M E
F
M A
Y
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2019009
PETERSON ENGINEERING INC.PETERSON ENGINEERING INC.PETERSON ENGINEERING INC.PETERSON ENGINEERING INC.
FTFA 16-3007
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y E
G L
IN
A
F B
F
L O
R
ID
A
M-001
H V
A C
L E
G E
N D
S
N O
T E
S
A B
B R
E V
IA
T
IO
N
E K
B E
J E
K
G D
P
M A
Y
M E
F
M
A
M E
N D
R E
V
IS
E D
H V
A C
G E
N E
R A
L N
O T
E J U
L Y
AMENDMENT 0001
145 146
130B
144C
MA
TC
HL
IN
E- A
MA
TC
HL
IN
E- A
MA
TC
HL
IN
E- A
MA
TC
HL
IN
E- A
144A
144B
ACC
MSAHU
1-2
MSAHU
1-1
MSCU
1-2MSCU
1-1
MSCU
2-2MSCU
2-1
BT
VAV
1-10
VAV
1-11VAV
1-25 VAV
1-18
VAV
1-27
VAV
1-12
VA
V
1-
VA
V
1-
VAV
1-17
VAV
1-19
VAV
1-20
AHU
44"/24"
VAV
1-30
"/2
4"
SA
0A
FCU
VAV
1-26
VAV
1-24
VAV
1-23
VAV
1-22
VAV
1-21
"x1
0"
14"x14" 16"x16"
12"x 10"
450 CFM
SWS
TYP. OF 4
"ø
14"x14"
10"x 10"
305 CFM
SWS
TYP. OF 6
"x1
4"
CD 12"ø
455 CFM
TYP. OF 3
40"/24"
"ø
CD 8"ø
175 CFM
"x1
6"
CD 6"ø
100 CFM
CD 10"ø
365 CFM
TYP. OF 2
CD 6"ø
100 CFM
"x1
4"
"x1
2"
CD 10"ø
225 CFM
TYP. OF 3
8" x1
6"
CD 12"ø
415 CFM
24"x22" 18"x18"
"x1
8"
24"x24"
"x1
0"
CD 8"ø
140 CFM
"x2
4"
"x2
4"
"x1
2"
60"x22"
8" x8
8"x8"
"x1
0"
CRAC
1-6
CRAC
1-7
CRAC
1-8
CRAC
1-10
CRAC
1-9
M-401
ANECHOIC CHAMBER AIR SUPPLY 325 CFM
EACH DAMPERED OUTLET. RETURN AIR
OUTLETS ON TOP OF ANECHOIC CHAMBER
SHALL BE OPEN TO ROOM 139. CONTRACTOR
SHALL COORDINATE FINAL DUCT CONNCTION
WITH ANECHOIC CHAMBER MANUFACTURER.
ANECHOIC CHAMBER IS GOVERNMENT
FURNISHED GOVERNMENT INSTALLED.
MOUNT THERMOSTAT IN ANECHOIC CHAMBER
COORDINATE EXACT LOCATION WITH THE
GOVERNMENT.
CRAC
1-4
CRAC
1-5
CD 8"ø 180 CFM CD 8"ø
210 CFM
12"x12"
"x1
4"
52"x24"
RAG 6"x 6"
100 CFM
RAG 8"x 8"
180 CFM
RAG 8"x 8"
210 CFM
8" ø
8" ø
"ø
CD 10"ø
250 CFM
RAG12"x 12"
415 CFM
RAG12"x 12"
500 CFM
VAV
1-14
14"x14"
12"x14" 8"x10"
6" ø
CD 6"ø
35 CFM
CD 8"ø
160 CFM
TYP OF 5
CD 8"ø
210 CFM
40"x24"
32"x24"18"x20"
"x1
2"
RAG 6"x 6"
140 CFM
18"x 18"
1100 CFM
SWR
TYP OF 2
14"x14"
18"x18"12"x14"
18"x 18"
1100 CFM
SWR
TYP OF 2 RAG22"x 22"
1365 CFM
RAG10"x 10"
310 CFM
RAG10"x 10"
400 CFM
TYP OF 2
10"ø
"ø
16"ø
"ø
RAG 8"x 8"
175 CFM
RAG 8"x 8"
210 CFM
RAG10"x 10"
400 CFM
TYP. OF 2
12"x12"
"x1
2"
12" øCD 8"ø
155 CFM
CD 8"ø
155 CFM
16"x 16"
830 CFM
SWR
TYP OF 4
CD 8"ø
200 CFM
TYP OF 4
CD 8"ø
145 CFM
8"x10"
12"ø
8" ø
8"ø
8" ø
8" ø8" ø
RAG 8"x 8"
150 CFM
RAG16"x 16"
675 CFM
10"ø
10"ø
10"ø
12"x12"
10"x 8"
300 CFM
SWS
TYP. OF 2
14"x 14"
600 CFM
SWR
VAV
1-16
10"x 8"
285 CFM
SWS
"x1
0"
RAG 6"x 6"
130 CFM
8"x 6"
130 CFM
SWS
"ø
"ø12"ø
"ø
"ø
"ø
12"x 12"
500 CFM
SWS
TYP. OF 5
20"x 20"
1250 CFM
SWS
TYP. OF 2
16"x16"
16"x16"
12"x 10"
450 CFM
SWS
TYP. OF 4
20"x 20"
1250 CFM
SWS
TYP. OF 2
20"x 20"
1250 CFM
SWS
TYP. OF 2
16"x22"
16"x22"
16"x22"
18"x18"
20"x 20"
1250 CFM
SWS
TYP. OF 2
T VAV 1-19
T CRAC 1-19T
VA
V
1-
T
VAV 1-23
T
T
T
VA
V
1-
T
T
T VAV 1-27
T
VAV 1-26
VAV 1-25 T
T
T
T
T
T
T
MSCU
1-3
MSAHU
1-3
ACC
CHWP
CHWP
CHWP
CHWP
10"x 10"
330 CFM
SWS
TYP. OF 6
A B CC.2 D D.4 E F G
2.2 2.7
3.3 3.7 3.8 3.9
4.1 4.4
5.3
6.5
7.4
AD
850 CFM
FLD
TYP. OF 7
24"x 24"
T
CR
AC
1-
CRAC 1-7
VAV 1-9
VAV 1-18
VAV 1-15
VA
V
1-
T
CRAC 1-10
"x1
2"
18"x18"
8" ø
40"x24"
"x2
4"
14"ø
14"ø
8" x8
RAG22"x 22"
1340 CFM
RAG16"x 16"
730 CFM
CD 14"ø
670 CFM
TYP. OF 2
8" ø
8"ø
6"ø
10"ø 10"ø
24"x24"
10"ø
10"ø
8"ø
48"/24" 54"/24"
60" x22
44"x24"
44"x24"26"x26"
32"/24"
10"ø
10"ø
10"ø
"ø
8"ø
8"x8"
10"ø
10"ø
VAV 1-22
T VAV 1-25
T VA
V
1-
20 TVAV 1-16
TCRAC 1-5
TCRAC 1-4
TVAV 1-30
12"x8"
T
T
VA
V
1-
VA
V
1-
T
VA
V
1-
T
VAV 1-17
SS
EMERGENCY AIR
DISTRIBUTION
SHUTOFF SWITCH
10"x 8"
270 CFM
SWS
"ø
16"ø
16"ø
SB
SB SB
SB
SB
SB
SB
SB
SB SB SB
SB
SB
SB
SB
SB
SBSBSB
SB
SB
SB SB
SB SB
SB SB
SB
SB SB
SB SB
SB
"x2
4"
"/2
4"
TWO SUPPLY DUCTS AND TWO RETURN AIR
DUCT OPENINGS IN THE ANECHOIC CHAMBER
SHALL BE PROVIDED WITH AUTOMATIC FIRE
DAMPERS. FIRE DAMPERS SHALL BE
CONNECTED TO AND CONTROLLED BY THE
ANECHOIC CHAMBER CLEAN AGENT SYSTEM.
COORDINATE WITH GOVERNMENT
FURNISHED GOVERNMENT INSTALLED
ANECHOIC CHAMBER .
6"x 6"
50 CFM
SWS
SCALE: 1/8"=1'-0"
8' 8' 16'0'
KEY PLAN WEST
A
SHEET
IDENTIFICATION
US Army Corps of Engineers ® Mobile District
U .S
. A
RM
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
DE
SI
G
NE
D
BY
BU
LL
O
CK
T
IC
E
AS
SO
CI
AT
ES
E.
C
ER
VA
NT
ES
S
TR
EE
T
PE
NS
AC
O
LA
, F
LO
RI
DA
2 3 4 5
B
C
D
D
RA
W N
B Y:
SB
M
T B
Y:
PL
O
T
SC
AL
E:
SI
ZE
CK
D
B Y:
PL
O
T
DA
TE
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
CO
N
TR
A
CT
N
O
PR
O
JE
C
T
NU
M
BE
R:
FI
LE
N
AM
E:
M
AR
K
DE
SC
R
IP
TI
O
N D
AT
E
A
PP
R
1:
x
M O
B
IL
E D
IS
TR
IC
T
M O
B
IL
E, A
LA
B
AM
A
M
EF
M
AY
, 2
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
(PROF. ENG. #: 3600)
PEI JOB #2019009
PETERSON ENGINEERING INC.
FTFA 16-3007
C
YB
ER
SP
AC
E
TE
ST
G R
O U
P
FA
CI
LI
TY
EG
LI
N
A
FB
, F
LO
RI
D
A
M-102
PA
RT
IA
L
FI
R
ST
F
LO
O
R P
LA
N
-H
VA
C W
ES
T
EK BE
J
EK
G
DP
M
AY
, 2
M
EF
7M
1/8" = 1'-0"M-102
PARTIAL FIRST FLOOR PLAN - HVAC WEST1
N
A B C
C.2
D
D.4
E F
G
2.7
2.2
3.3
3.7
3.8
4.1
4.4
6.5
7.4
ACR GSSO
ACR STORAGE
ACR ISSO
130B
ACR ISSM
ACR SYSADM
ACR CONF. RM
CORRIDOR
AVIONICS TEST
LAB
COMM RM
CYBER/EW LAB
STAIR 1
FIRE PUMP
THREAT
DEVELOPMENT
LAB
144C
REPORT WRITING
REPORT WRITING
ACR SERVER
ATL STORAGE
CORR.
POWER
VESTIBULE
MANTRAP
144A
DEV & RE LAB
144B
ATL ANALYSIS
C/EW ANALYSIS
BUS DUCT 1'x1'x14'
KEYNOTES:
1. CONTINUOUS SOLID GROUND BUSBAR(NO PREDRILLED HOLES); INSTALL GROUND
BUSBAR 40" A.F.F. BUSBAR SHALL BE 1/4" THICK BY 4" HIGH. BUSBAR SHALL BE
CONTINUOUS AROUND LAB. WHERE BUSBAR IS BROKEN DUE TO DOORS OR
EQUIPMENT, INSTALL A BONDING CONDUCTOR BETWEEN BUSBARS. BONDING
CONDUCTOR SHALL BE #3/0.
2. GROUND BUSBAR BELOW RAISED FLOOR. SEE RAISED FLOOR GROUNDING DETAIL,
SHEET E008.
3. SEE TELECOMMUNICATIONS SHEETS FOR GROUNDING BUS BAR LOCATIONS AND
REQUIREMENTS FOR THIS ROOM.
2 2
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
FTFA 16-3007
W
R
M A
Y
M A
Y
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
E-113
F
IR
S T
F L
O O
R G
R O
U N
D
IN
G P
L A
N
W E
S T
D C
O L
E M
A N
M N
O E
L L
D B
A G
W E
L L
B E
I
N
1/8" = 1'-0"E-113
FIRST FLOOR GROUNDING PLAN - WEST1
0'8' 8' 16
SCALE: 1/8"=1'-0"
KEY PLAN
SEE FIRST FLOOR SECURITY PLAN SHEET G107 FOR SECURE AREA BOUNDARY LOCATIONS.
SEE SHEET E009 FOR SECURE BOUNDARY PENETRATION DETAILS. SEE ARCHITECTURAL
DRAWINGS FOR FRANGIBLE WALL LOCATIONS.
SECURE AREA NOTE:
M E
F
E
A
M E
N D
M E
N T
/2
/2
AMENDMENT 0002
R G
U
RGU RGU RGU
RGU RGU RGU
ACACAC
R G
A
RGA RGA
RGA RGA
R G
A
R G
A
J
J
J J
J
J
COMM RM
C/EW ANALYSIS
CYBER/EW LAB
'CLD'
'CW1'
'CLN1''CLN2'
'CLN3'
'CLN4'
'CLN5'
'C4H1'
'C4H2'
'CDC1'
'CDC2'
'C270DC'
CLN1 -4
CLN1 -19
CLN1 -20CLN1 -5
CLN1 -21CLN1 -22
CLN1 -18
CLN1 -17
CLN1 -16
CLN1 -15
CLN1 -14
CLN1 -13
CLN2 -9
CLN2 -8
CLN1 -12
CLN1 -3
CLN1 -11
CLN1 -2
CLN1 -10
CLN2 -10,12 CLN2 -11,13 CLN2 -14,16
CLN2 -1CLN2 -2CLN2 -3CLN2 -4CLN2 -5
CLN2 -7CLN2 -6
CLN1 -30 CLN1 -29 CLN1 -28 CLN1 -27
CLN1 -26
CLN1 -25
CLN1 -24
CLN1 -23
CLN1 -8
CLN1 -1
CLN1 -9
CLN5 -4,6
CLN5 -2
CLN5 -1 CLN5 -11
CLN5 -9
CLN5 -13,15
CLN5 -18
CLN5 -20
CLN5 -22,24
CLN5 -21,23,25
CLN4 -12,14,16
CLN4 -13,15
CLN4 -9
CLN4 -3,5,7
CLN4 -4,6
CLN4 -2
CLN4 -1
CLN3 -22,24,26
CLN3 -23,25
CLN3 -21
CLN3 -20
CLN4 -20
CLN4 -18
CLN4 -22,24
CLN4 -21,23,25
KEYNOTES:
1. 2#10, 1#10 GND IN 1/2" C.
2. 4#10, 1#10 GND IN 1" C.
3. 3#10, 1#10 GND IN 3/4" C.
4. 4#10, 1#10 GND IN 1" ALUMINUM CONDUIT.
5. 3#4, 1#10 GND IN 1-1/4" C.
6. 2#1/0, 1#6 GND IN 1-1/2" C.
7. 3#8, 1#10 GND IN 3/4"C
8. CONNECT 3#8, 1#10 GND IN 3/4"C TO CRANE
9. ANECHOIC CHAMBER BY GOVERNMENT. COORDINATE POWER
REQUIREMENTS WITH EQUIPMENT FURNISHED. CONTRACTOR SHALL CONNECT
ANECHOIC CHAMBER TO BUILDING POWER SUPPLY.
10. JUNCTION BOX ABOVE CEILING FOR DOOR HARDWARE POWER.
11. JUNCTION BOX IN WALL TO SUPPLY POWER FOR INTRUSION DETECTION SYSTEM.
COORDINATE LOCATION WITH SECURITY DRAWINGS.
CLN2 -17,19,21
CLN2 -22,24
CLN2 -23
CLN2 -18,20
CLN2 -15
CLN3 -1
CLN3 -3,5
CLN3 -8
CLN3 -2,4,6
CLN3 -7,9
CLN3 -10
CLN3 -12,14
CLN3 -17 CLN3 -11,13,15
CLN3 -16,18
CLN7 -1
CLN7 -2,4
CLN7 -9
CLN7 -6,8
CLN7 -3,5,7
CLN6 -25,27
CLN6 -20,22,24
CLN6 -26
CLN6 -21,23
CLN6 -19
CLN6 -3,5
CLN6 -7,9
CLN6 -8
CLN6 -2,4,6 CLN6 -10
CLN6 -12,14
CLN6 -16,18
CLN6 -17
CLN6 -11,13,15
'CLN6'
2 1
1 3
270VDC RECTIFIER
5 5
CLN3 -19
1 2
CLN3 -27,29
CLN4 -8,10
CLN4 -11
CLN4 -17,19 3
CLN4 -26,283
CLN5 -3,5,7
CLN5 -8,10
3 1
CLN5 -12,14,16
CLN5 -17,19
3CLN5 -26,28
CLN6 -1
'CLN7'
'CDC3'
'28VDC
RECTIFIER'
CLN1 -6
CLN7 -10
CLN7 -11,13,15
CLN1 -7
CLN3 -28
CLN7 -12
60/3/1
CW1 -4
CW1 -2
CW1 -1
CW1 -3
CW1 -9,11
CW1 -10,12
CW1 -7
CW1 -8
CW1 -6
CW1 -5
UPS
+72"
CLN7 -16
+36" +36"
CLN7 -14
CLN7 -17
A
SHEET
IDENTIFICATION
US Army Corps of Engineers ® Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T M
O B
IL
E
A
L A
B A
M A
M E
F
FTFA 16-3007
W
R
M A
Y
M A
Y
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y E
G L
IN
A
F B
F
L O
R
ID
A
E-501
C Y
B E
R /E
W L
A B
E N
L A
R G
E D
R O
O M
P L
A N
H z
D C
O L
E M
A N
M N
O E
L L
D B
A G
W E
L L
B E
I
N
1/4" = 1'-0"E-501
CYBER/EW LAB 60Hz ENLARGED ROOM PLAN1
0'4' 4' 8'
SCALE: 1/4"=1'-0"
M E
F
E
ALL CONDUITS INSTALLED BELOW THE RAISED FLOOR SHALL BE INSTALLED TIGHT TO SLAB TO
ALLOW FOR INSTALLATION OF COMMUNICATIONS TRAY AND CABLING. REFER TO
TELECOMMUNICATIONS DRAWINGS FOR COMMUNICATIONS TRAY ROUTING.
RAISED FLOOR CONDUIT INSTALLATION NOTE: