Drawings.pdf
PDF 2 MB Posted
- Attached to
- JAGA Intrusion & Fire Alarm System Installation Federal contract opportunity
- Solicitation number
- 140P6424B0008
About this file
This document is a solicitation notice for an Invitation for Bids (IFB) issued by the Department of the Interior National Park Service Midwest Region for an Intrusion & Fire Alarm System Installation project at the James A. Garfield National Historic Site in Mentor, Ohio. The scope of work involves the removal and replacement of a fire and intrusion alarm system in nine buildings, including the installation of over 225 new devices and associated wiring, as well as new CAT-6 and fiber-optic cable. The project is estimated to be between $250,000 and $500,000 and is set aside for Total Small Businesses under NAICS code 238210. The solicitation number is 140P6424B0008, and the bid is due by 12:00 PM ET on August 21, 2024. An organized site visit is scheduled for July 30, 2024. The successful bidder will be the responsive, responsible bidder offering the lowest aggregate price for the base bid and one additive item.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6424B0008.pdf | ||
| WD_-_Lake_County__OH.pdf | ||
| Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| Construction_Contract_Administration.pdf | ||
| Suggested_Products.pdf | ||
| Bid_Schedule.xlsx | XLSX spreadsheet | |
| Project_Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAINTENANCE
BLDG.
GRAINERY
HORSE
BARN
VISITOR
CENTER
TENANT
HOUSE
COMFORT
STATION
WINDMILL
CAMPAIGN
OFFICE
GARFIELD
HOME
MAIN
GATE
M
E
N
T
O
R
A
V
E
JAMES A. GARFIELD
STATE
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
REGION COUNTY
DEPARTMENT OF THE INTERIOR
UNITED STATES
TITLE OF DRAWING
OF
PKG.
NO.
SHEET
DRAWING NO.
487/
MIDWEST
COVER SHEET
QUALITY DESIGN CERTIFICATION
OR
OR
Development (Title I)
Prepared in Accordance with Design by Design Development (Title I)
Construction Drawing Not Preceded
Approved by Superintendent on
Variance from Design Development (Title I)
Project Manager
Drawing No.
Date
Date
SheetMark REVISION Date Initial
NA
NA
80010
KENNETH HAHN
ARCHITECTS
NO. 145-091
A/E FIRM - A/E CONTRACT NO.
PRIME/ARCHITURE:
KENNETH HAHN ARCHITECTS
OMAHA, NE
MEP:
ALVINE ENGINEERING
OMAHA, NE
MENTOR, OHIO
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
NAME OF PARK
LAKE OHIO
INDEX OF DRAWINGS
1. TS1 COVER SHEET AND SITE MAP
2. A1 VISITOR CENTER FIRST & SECOND LEVEL PLANS
3. A2 GARFIELD HOUSE BASEMENT & MAIN LEVEL PLANS
4. A3 GARFIELD HOUSE SECOND & THIRD LEVEL PLANS
5. A3 CAMPAIGN OFFICE, TENANT HOUSE, COMFORT STATION PLANS
6. A4 WINDMILL & GRANARY PLANS
7. A5 MAINTENANCE SHOP & HORSE BARN PLANS
8. E0 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND NOTES
9. ED1 SITE PLAN - ELECTRICALDEMOLITION
10. ED2 VISITOR CENTER FLOOR PLANS -ELECTRICALDEMOLITION
11. ED3 MAIN HOUSE FLOOR PLANS -ELECTRICAL DEMOLITION
12. ED4 MAIN HOUSE FLOOR PLANS -ELECTRICAL DEMOLITION
13. ED5 CAMPAIGN HQ FLOOR PLANS - ELECTRICAL DEMOLITION
14. ED6 TENANT HOUSE FLOOR PLANS -ELECTRICAL DEMOLITION
15. ED7 COMFORT STATION FLOOR PLAN - ELECTRICAL DEMOLITION
16. ED8 WINDMILL FLOOR PLANS -ELECTRICAL DEMOLITION
20. ED9 GRAINERY FLOOR PLANS - ELECTRICAL DEMOLITION
21. ED10 MAINTENANCE BLDG & HORSE BARN FLOOR PLANS -ELECTRICAL DEMOLITION
22. E1 SITE PLAN - ELECTRICAL
23. E2 VISITOR CENTER FLOOR PLANS - ELECTRICAL
24. E3 MAIN HOUSE FLOOR PLANS - ELECTRICAL
25. E4 MAIN HOUSE FLOOR PLANS - ELECTRICAL
26. E5 CAMPAIGN HQ FLOOR PLANS - ELECTRICAL
27. E6 TENANT HOUSE FLOOR PLANS - ELECTRICAL
28. E7 COMFORT STATION FLOOR PLAN - ELECTRICAL
29. E8 WINDMILL FLOOR PLANS - ELECTRICAL
30. E9 GRANERY FLOOR PLANS - ELECTRICAL
31. E10 HORSE BARN & MAINTENANCE BARN FLOOR PLANS - ELECTRICAL
32. E11 ELECTRICAL DETAILS AND SCHEDULES
33. E12 ELECTRICAL DETAILS
33 E13 FIBER OPTIC CABLE CONNECTIVITY DIAGRAM
NATIONAL
SERVICE
PARK
DESIGN DEVELOPMENT SUBMITTAL
12/1/2023 PMIS 319395
NATIONAL HISTORICAL SITE
JAMES A. GARFIELD
NATIONAL HISTORICAL SITE
NOT TO SCALE
1. THE CONTRACTOR SHALL PROTECT EXISTING BUILDING AND
SITE MATERIALS SCHEDULED TO REMAIN, AND SHALL BE
RESPONSIBLE FOR DAMAGE TO SAME RESULTING FROM WORK
UNDER THIS CONTRACT. THE CONTRACTOR SHALL RESTORE
DAMAGED EXISTING BUILDING AND SITE MATERIALS TO THEIR
ORIGINAL CONDITION.
2. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
SHALL BE RESPONSIBLE FOR THE SAME. COORDINATE ALL
WORK AND SHOP DRAWINGS WITH OTHER TRADES.
3. INFORMATION PERTAINING TO THE EXISTING BUILDING HAS
BEEN OBTAINED THROUGH THE BUILDING'S ORIGINAL
DRAWINGS, WHERE AVAILABLE. REPORT DISCREPANCIES TO
THE CONTRACTING OFFICER PRIOR TO ANY DEMOLITION.
CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO COMMENCING WORK.
4. THE CONTRACTOR SHALL COORDINATE ALL TESTING AND
INSPECTIONS AS SPECIFIED, OR AS NECESSARY TO
DEMONSTRATE A COMPLETE AND SATISFACTORY
INSTALLATION.
5. THE CONTRACTOR SHALL COORDINATE ON-SITE STORAGE OF
BUILDING MATERIALS, EQUIPMENT, AND TRASH CONTAINERS
WITH THE PARK.
6. ALL WORK SHALL COMPLY WITH LOCAL CODES AND ALL OTHER
APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
7. ALL MATERIALS AND EQUIPMENT OF THE SAME TYPE SHALL BE
SUPPLIED BY THE SAME MANUFACTURER, AND SHALL BE NEW,
OF THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS.
8. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS
EXISTING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
ALL WORK. CONTRACTOR SHALL ANTICIPATE AREAS WHERE
THE INSTALLATION OF MECHANICAL AND ELECTRICAL WORK
WILL BE RESTRICTED, CONGESTED, OR DIFFICULT TO INSTALL,
AND SHALL COORDINATE INSTALLATION BETWEEN THE
TRADES.
10. CONTRACTOR SHALL COORDINATE LOCATIONS FOR ALL
MECHANICAL AND ELECTRICAL ITEMS WITH THE EXISTING
CONDITIONS AND NEW CONSTRUCTION. CONTRACTOR SHALL
NOTIFY THE CONTRACTING OFFICER OF ANY DISCREPANCIES
PRIOR TO INSTALLATION AND/OR FABRICATION.
11. IT IS THE INTENT OF THIS CONTRACT THAT ALL AREAS
AFFECTED BY CONSTRUCTION SHALL PROVIDE A FINISHED
AND COMPLETE PROJECT, UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PATCH, REPAIR, AND ADJUST AS
REQUIRED TO ACHIEVE THIS FINISHED PROJECT.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING
ALL WORK AND PROVIDING ALL MATERIALS REQUIRED TO
ACHIEVE THE DESIGN INTENT SHOWN ON THESE DRAWINGS.
THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR ANY
ADDITIONAL EXPENSE TO THE CONTRACTOR IF THE
CONDITIONS CAUSING THOSE EXPENSES COULD HAVE BEEN
DISCOVERED IN AN ON-SITE INSPECTION PRIOR TO BID
SUBMITTAL.
13. THE BUILDING, LANDSCAPE AND SURROUNDINGS ARE ON THE
NATIONAL REGISTER OF HISTORIC PLACES. THE ENTIRE SITE IS
A HISTORIC PROPERTY AND ALL REASONABLE PRECAUTIONS
SHALL BE TAKEN TO PREVENT COLLATERAL DAMAGE TO
HISTORIC MATERIALS SURROUNDING THE WORK AREA. IF
DAMAGE OCCURS, REPAIRS SHALL BE MADE AT NO
ADDITIONAL COST TO THE GOVERNMENT TO THE
SATISFACTION OF THE CONTRACTING OFFICER. EVERY
OPPORTUNITY SHOULD BE TAKEN TO PRESERVE, REPAIR AND
CONSERVE HISTORIC MATERIALS AND DESIGNS. COORDINATE
ALL NEW PENETRATIONS AND ANY ALTERATIONS TO THE
BUILDING WHICH MIGHT AFFECT THE HISTORIC INTEGRITY OF
THE BUILDING WITH THE CONTRACTING OFFICER PRIOR TO
BEGINNING WORK.
14. "REMOVE" MEANS TO DEMOLISH AND DISPOSE OF AN ITEM OFF
OF NPS PROPERTY.
GENERAL NOTES
JAMES A. GARFIELD NATIONAL HISTORIC SITE MAPS
PROJECT
LOCATION
MENTOR, OHIO AREA MAP REGIONAL MAP
NOT TO SCALE
SITE MAP
PROJECT
LOCATION
AutoCAD SHX Text Cuyahoga Valley NRA
AutoCAD SHX Text Dayton Aviation Heritage NHP
AutoCAD SHX Text George Rogers Clark NHP
AutoCAD SHX Text Hopewell Culture NHP
AutoCAD SHX Text Indiana Dunes NL
AutoCAD SHX Text James A Garfield NHS
AutoCAD SHX Text Jefferson NEM
AutoCAD SHX Text Lincoln Boyhood NMEM
AutoCAD SHX Text Perry's Victory IPM
AutoCAD SHX Text Ulysses S Grant NHS
AutoCAD SHX Text William Howard Taft NHS
AutoCAD SHX Text
WEST VIRGINIA
AutoCAD SHX Text
PENNSYLVANIA
AutoCAD SHX Text
OHIO
AutoCAD SHX Text
INDIANA
AutoCAD SHX Text
TOLEDO
AutoCAD SHX Text
ST. LOUIS
AutoCAD SHX Text
CLEVELAND
AutoCAD SHX Text
CINCINNATI
AutoCAD SHX Text
MILWAUKEE
AutoCAD SHX Text
INDIANAPOLIS
AutoCAD SHX Text
COLUMBUS
AutoCAD SHX Text
LANSING
AutoCAD SHX Text
MADISON
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
SPRINGFIELD
AutoCAD SHX Text
DAYTON
AutoCAD SHX Text
DETROIT
AutoCAD SHX Text
AKRON
AutoCAD SHX Text
FORT WAYNE
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
PEORIA
1ST FLR XREF 45' R FOR BSMT
XXXXXXXX
STAIR
STAIR
UP
UP
RECEPTION
SALES
VESTIBULE
RR
JAN.
SPRINKLER
SERVICE
EXHIBIT
LOBBY
EXHIBIT
EXHIBIT
EXHIBIT
ELEC
101B
AUDITORIUM
EXHIBIT
GAS
COLLECT.
1ST FLR XREF 45' R FOR BSMT
XXXXXXXX
ADMIN.
OFFICE
STORAGE.
LOUNGE
STORAGE
ELEC.
CLOSET
STAIR
STAIR
HALL
201A
DN
DN
GENERAL NOTES
G1. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G2. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G3. WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
LOCATE DEVICE WITH CLEAR LINE
OF SIGHT. INSTALL WEATHERTIGHT.
SEE ELECTRICAL.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
A1
VISITOR CENTER FIRST &
SECOND LEVEL PLANS
x
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
SECOND LEVEL FLOOR PLAN
N2
D e c p m
C
T o d d A
K
H w o r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
FIRST LEVEL FLOOR PLAN
N1
2 2
BASEMENT
BOILER
PIT
HALL
CRAWL
ELEV.
EQUIP.
CELLAR
HALL
AREAWAY
PARLOR
RECEPTION
HALL
CLOSET
BEDROOM
ANTEROOM
DINING
ROOM
BEDROOM
VEST
CLO
VEST
HALL
HALL
PANTRY
EXHIBITS
12 1
LAUNDRY
PANTRY
EXHIBITS
ENTRY
HALL
LAV
114 TLT
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
LOCATE DEVICE WITH CLEAR LINE
OF SIGHT. INSTALL WEATHERTIGHT.
SEE ELECTRICAL.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
GENERAL NOTES
G1. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G2. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G3. WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
G4. BUILDING HAS WALL/ CEILING
COVERINGS (W/CC) IN SOME
ROOMS. CONTRACTOR IS TO
PROTECT W/CC AND MAKE EFFORT
TO NOT HAVE TO PATCH OR REPAIR
W/CC. CONTRACTOR IS
RESPONSIBLE TO PATCH /REPAIR
W/CC IF NEEDED BY REMOVAL/
DEMOLITION/PATCHING SCOPE OR
IF DAMAGE IS INCURRED BY THE
GC. A2.1
GARFIELD HOUSE BASEMENT
& MAIN LEVEL PLANS
x c
T o d d A
K r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
MAIN LEVEL FLOOR PLAN N
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
BASEMENT LEVEL FLOOR PLAN N
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
CRAWL 004
AutoCAD SHX Text
PIT
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
LIFT
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
DN
BEDROOM
HALL
HALL
HALL
HALL
HALL
ALCOVE
BEDROOM
BEDROOM
CLO
CLO
CLO
VAULT
LIBRARY
BEDROOM
CLO
BATH
CLO
CLO
CLO
BEDROOM
OFFICE
BEDROOM
CLO
CLO
BEDROOM
WATER
TANK
MECH
MECH
MECH
HALL
HALL
WATER
TANK
303BEDROOM
BEDROOM
CLO
ALCOVE
CLO
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
LOCATE DEVICE WITH CLEAR LINE
OF SIGHT. INSTALL WEATHERTIGHT.
SEE ELECTRICAL.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
GENERAL NOTES
G1. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G2. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G3. WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
G4. BUILDING HAS WALL/ CEILING
COVERINGS (W/CC) IN SOME
ROOMS. CONTRACTOR IS TO
PROTECT W/CC AND MAKE EFFORT
TO NOT HAVE TO PATCH OR REPAIR
W/CC. CONTRACTOR IS
RESPONSIBLE TO PATCH /REPAIR
W/CC IF NEEDED BY REMOVAL/
DEMOLITION/PATCHING SCOPE OR
IF DAMAGE IS INCURRED BY THE
GC. A2.2
GARFIELD HOUSE SECOND &
THIRD LEVEL PLANS
x
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
THIRD LEVEL FLOOR PLAN
c
T o d d A
K r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
SECOND LEVEL FLOOR PLAN
N1
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
ELEV
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
UP
OFFICE
RM.1
RM.2
RM.3
RM.4
RM.5
RM.6
STAIR
S1
RM.21
STAIR
S1
RM.22
RM.23
RR
LAUNDRY
RM.
STAIR
S0
FURNACE
RM.
CRAWL
SPACE
GENERAL NOTES
G1. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G2. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G3. WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
G4. PAINT ANY NEW CEILING/WALL
MOUNTED CONDUITS TO MATCH
ADJACENT SURFACE.
G5. CAMPAIGN HQ - PROTECT
STAINED/VARNISHED SURFACES.
MOUNT NEW DEVICES IN SAME
LOCATIONS AS EXISTING DEVICES.
LIMIT ANY NEEDED REPAIRS AND
REFINISH TO ONLY FOOTPRINT OF
EXISTING DEVICE.
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
MEN
WOMEN
A3
CAMPAIGN OFFICE & TENANT
HOUSE PLANS
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
TENANT HOUSE FLOOR PLANS
c
T o d d A
K r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
CAMPAIGN OFFICE FLOOR PLANS
N
FIRST FLOOR CRAWL SPACE
FIRST FLOOR SECOND FLOOR BASEMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
COMFORT STATION PLAN
N4
G5
LOFT
GENERAL NOTES
G1. PAINT ALL NEW CEILING/WALL
MOUNTED CONDUIT TO MATCH
ADJACENT SURFACE IF THE
MOUNTING SURFACE IS ALREADY
PAINTED.
G2. INSTALL SURFACE MOUNTED
CONDUIT IN A NEAT AND ORDERLY
MANNER. DO NOT RUN CONDUIT
DIAGONALLY. SEE ELECTRICAL
DRAWINGS AND SPECIFICATIONS.
G3. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G4. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G5 WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
PROVIDE FINISHED PLYWOOD
CABINET FOR NEW PANELS. SEE
3/A4. CABINET TO BE HEATED- SEE
ELECTRICAL.
LOCATE DEVICE WITH CLEAR LINE
OF SIGHT. INSTALL WEATHERTIGHT.
SEE ELECTRICAL.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
7'- 0"
4'-0"
A4
WINDMILL & GRANARY
PLANS
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
GRANARY FLOOR PLANS
c
T o d d A
K r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
WINDMILL FLOOR PLANS
N
FOURTH LEVEL
GROUND LEVEL SECOND LEVEL THIRD LEVEL GROUND LEVEL UPPER LEVEL
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
CABINET
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
HORSE
STALL
HORSE
STALL
TACK
ROOM
COMMON
101 HAY
LOFT
GENERAL NOTES
G1. PAINT ALL NEW CEILING/WALL
MOUNTED CONDUIT TO MATCH
ADJACENT SURFACE IF THE
MOUNTING SURFACE IS ALREADY
PAINTED.
G2. INSTALL SURFACE MOUNTED
CONDUIT IN A NEAT AND ORDERLY
MANNER. DO NOT RUN CONDUIT
DIAGONALLY. SEE ELECTRICAL
DRAWINGS AND SPECIFICATIONS.
G3. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G4. PATCH CEILING/WALL WHERE A
DEVICE/CONDUIT WAS REMOVED
AND NOT REPLACED AT THE SAME
LOCATION.
G5 WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ DEMOLITION/
PATCHING; PAINT ENTIRE CEILING/
WALL PLANE CORNER TO CORNER,
EDGE TO EDGE. PAINT COLOR AND
FINISH TO MATCH ADJACENT
CEILING/ WALL.
LOCATE EXTERIOR FIRE ALARM
NOTIFICATION DEVICE UNDER EAVE
WITH CLEAR LINE OF SIGHT. INSTALL
WEATHERTIGHT. SEE ELECTRICAL.
KEYED NOTES
REPAIR DOOR FRAME AS NEEDED
WHERE CONTACT WAS REMOVED.
FINISH TO MATCH FRAME. (TYP.)
SEE ELECTRICAL FOR NEW WORK.
NOTE- KEYED NOTES DO NOT
APPEAR ON EVERY SHEET.
MAINTENANCE
A5
MAINTENANCE SHOP &
HORSE BARN PLANS
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
HORSE BARN FLOOR PLANS
N c
T o d d A
K r k p a r k s
A l a r m s a n d
F i r e
P r o t e c t i o n J A
G A
D r a w i n g s
J A
G A
A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
DRAWN BY:
TECH. REVIEW:
DATE:
12/1/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CZ
DESIGN DEVELOPMENT
FIRST FLOOR HAY LOFT
(UPPER)
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
MAINTENANCE SHOP PLAN
N
AutoCAD SHX Text
UP
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 7p m
E0
.dw g jsa nc he z
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
XX
E0
ELECTRICAL SYMBOLS,
ABBREVIATIONS, AND NOTES
1. FIRE ALARM MANUAL PULL STATIONS, SMOKE DETECTORS, AND HEAT DETECTORS TO BE THE WIRELESS TYPE. IN THE FOLLOWING CONDITIONED BUILDINGS: VISITOR CENTER, GARFIELD HOUSE, COMFORT STATION BUILDING, TENANT HOUSE, AND HORSE BARN. IF THERE ARE SPACES IN THESE BUILDINGS THAT ARE UNCONDITIONED SUCH AS ATTIC SPACES THAN
THOSE DEVICES SHALL BE THE WIRED TYPE.
2. FIRE ALARM MANUAL PULL STATIONS AND HEAT DETECTORS TO BE THE WIRED TYPE IN THE FOLLOWING UNCONDITIONED
BUILDINGS: WINDMILL, MAINTENANCE BUILDING, CAMPAIGN HEADQUARTERS, AND GRAINERY.
3. FIRE ALARM HORN/STROBE LIGHTS AND STROBE LIGHTS TO BE WIRED.
4. FIRE ALARM DUCT DETECTORS TO BE WIRED.
5. FIRE ALARM WIRING SHALL BE IN CONDUIT.
6. MINIMUM SIZE CONDUIT SHALL BE 3/4".
7. CONDUIT SHALL BE CONCEALED FROM VIEW EXCEPT IN ATTICS, MECHANICAL ROOMS, AND CRAWL SPACES. IN BUILDINGS WITH OPEN TRUSSES, CONCEAL NEW CONDUITS FROM VIEW. COORDINATE WITH CONTRACTING OFFICER.
8. METAL CLAD COVERED FIRE ALARM WIRING SHALL BE ALLOWED WHERE FISHED ABOVE EXISTING CEILINGS OR IN EXISTING
WALLS.
9. INTRUSION DETECTION DEVICES SHALL BE WIRELESS TYPE, UNLESS OTHERWISE NOTED, IN THE FOLLOWING CONDITIONED BUILDINGS: VISITOR CENTER, GARFIELD HOUSE, COMFORT STATION BUILDING, TENANT HOUSE, AND HORSE BARN.
10. INTRUSION DETECTION DEVICES SHALL BE THE WIRED TYPE, UNLESS OTHERWISE NOTED, IN THE FOLLOWING UNCONDITIONED BUILDINGS: WINDMILL, MAINTENANCE BUILDING, CAMPAIGN HEADQUARTERS, AND GRAINERY.
11. EXACT LOCATION OF NEW DEVICES TO BE COORDINATED WITH CONTRACTING OFFICER.
12. THIS PROJECT SHALL BE PHASED. SEE SPECIFICATION SECTION 011100.
13. THE EXISTING FIRE ALARM AND INTRUSION DETECTION SYSTEMS SHALL STAY OPERATIONAL UNTIL THE NEW FIRE ALARM AND INTRUSION DETECTION SYSTEMS ARE OPERATIONAL. COORDINATE ANY DOWN TIME WITH THE CONTRACTING OFFICER.
14. IN GENERAL, INSTALL NEW FIRE ALARM AND INTRUSION DETECTION DEVICES IN SAME LOCATION AS EXISTING TO REDUCE
THE NEED TO PROVIDE PATCHING AND PAINTING.
15. INTRUSION DETECTION DEVICES AND FIRE ALARM DEVICES SHALL BE MOUNTED VIA SCREWS AS RECOMMENDED BY MANUFACTURER. COORDINATE EXACT MOUNTING REQUIREMENTS WITH CONTRACTING OFFICER PRIOR TO INSTALLATION.
16. COORDINATE NETWORK CONFIGURATION AND CONNECTIONS WITH THE CONTRACTING OFFICER PRIOR TO INSTALLATION.
NETWORK SHALL BE CONFIGURED TO PERFORM SYSTEM FUNCTIONS AS OUTLINED WITHIN THE CONSTRUCTION
DOCUMENTS.
17. WHERE INDICATED ON PLANS, PROVIDE DOOR POSITION SWITCHES FOR EACH DOOR LEAF WHETHER IT IS A SINGLE OR
DOUBLE DOOR.
18. REFER TO FIRE ALARM, SECURITY, AND NETWORK RISER DIAGRAMS AND DETAILS ON SHEETS E22 FOR ADDITIONAL
INFORMATION.
19. EXISTING FIRE SPRINKLER SYSTEMS IN THE FOLLOWING BUILDINGS: VISITOR CENTER AND GARFIELD HOUSE. PROVIDE REMOVAL OF EXISTING FIRE ALARM SYSTEM INTERFACE WIRING AND CONNECTION OF NEW FIRE ALARM SYSTEM INTERFACE WIRING IN A TIMELY MANNER. AFTER RECONNECTION HAVE THE FIRE SPRINKLER SYSTEMS TESTED AND CERTIFIED BY A LICENSED FIRE SPRINKLER CONTRACTOR AND PROVIDE WRITTEN REPORT TO CONTRACTING OFFICER.
20. WHERE ADDITIONAL NEW BREAKER(S) ARE CALLED OUT TO BE PROVIDED IN EXISTING PANELS, BUT POLE SPACE IS NOT AVAILABLE, CONSOLIDATE EXISTING CIRCUITS TO MAKE SPACE AVAILABLE. COORDINATE WITH CONTRACTING OFFICER.
21. PROVIDE A FIBER OPTIC INTERFACE DEVICE IN EACH BUILDING FOR THE NEW FIRE ALARM CONTROL PANEL AND INTRUSION ALARM PANEL SO THAT THE FIRE ALARM SYSTEM IS NETWORKED TOGETHER BETWEEN BUILDINGS AND SO THAT THE
INTRUSION ALARM SYSTEM IS NETWORKED TOGETHER BETWEEN BUILDINGS.
22. IN THE VISITOR CENTER PROVIDE A WORK STATION TO MONITOR FIRE ALARM PANELS IN ALL BUILDINGS. WORK STATION TO INCLUDE PERSONAL COMPUTER, MONITOR, KEYBOARD, MOUSE, WIRING, PROGRAMMING, AND TRAINING. LOCATE IN
STORAGE ROOM 202. REFER TO DETAIL.
23. IN THE VISITOR CENTER PROVIDE A WORK STATION TO MONITOR INTRUSION ALARM PANELS IN ALL BUILDINGS. WORK STATION TO INCLUDE PERSONAL COMPUTER, MONITOR, KEYBOARD, WIRING, PROGRAMMING AND TRAINING. LOCATE IN
STORAGE ROOM 202. REFER TO DETAIL
GENERAL NOTES
CARBON MONOXIDE DETECTOR
ELECTRICAL SYMBOLS
FIBER OPTIC CABLE
("#" INDICATES NUMBER OF STRANDS
"T" INDICATES TYPE AND
"X" INDICATES CABLE NAME)
COMBINATION DATA/AV FLOOR OUTLET
("#" INDICATES DEVICE TYPE IN SCHEDULE)
CABLE SLACK
("X" INDICATES SLACK LENGTH)
CABLE PROTECTOR
("XXX" INDICATES NUMBER OF PROTECTORS)
WIRELESS RECEIVER
WIRELESS REPEATER
UNSHIELDED TWISTED PAIR COPPER CABLE -
"C" INDICATES CATEGORY NUMBER
"#" INDICATES NUMBER OF PAIRS
"G" INDICATES AWG, "X" INDICATES CABLE NAME
CROSS-CONNECT FIELD
SPLICE
MECHANICAL TERMINATION OF CABLE
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
TELECOMMUNICATIONS
#-T X
XXX
X C-#-G X
COMMUNICATIONS OUTLET CEILING COMMUNICATIONS OUTLET FLOOR COMMUNICATIONS OUTLET
MUTOA - MULTI-USER TELECOMMUNICATIONS
OUTLET ASSEMBLYSPECIAL SERVICES COMMUNICATIONS OUTLET
WIRELESS ACCESS POINT
("#" INDICATES QUANTITY OF ANTENNAS)
AV
AV GEAR BOX, REFER TO
SCHEMATICS AND SPECS
GROUND BAR
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PATHWAYS
CONDUIT SLEEVE WITH BUSHINGS DISTRIBUTION RINGS
WALL MOUNT TELECOMMUNICATIONS EQUIPMENT J-HOOK STYLE CABLE HANGERS CABLE TRAY DROP OUT
CABLE TRAY
("#" INDICATES TRAY DIMENSIONS)
CABLE RUNWAY
("#" INDICATES TRAY DIMENSIONS)
CABLE TRAY - SOLID BOTTOM
("#" INDICATES TRAY DIMENSIONS)
CABLE TRAY - WALL MOUNTED
("#" INDICATES TRAY DIMENSIONS)
EQUIPMENT RACK
("#" INDICATES RACK NO. AND FRONT OF RACK)#
FIRE ALARM AUTOMATIC SMOKE DETECTOR FIRE SPRINKLER VALVE TAMPER SWITCH
WIRELESS FIRE ALARM SMOKE DETECTOR FIRE SPRINKLER FLOW SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM AUTOMATIC WALL SMOKE DETECTOR CEILING FIRE ALARM HORN AND LIGHT COMBINATION
(# INDICATES CANDELA RATING)
FIRE ALARM CONTROL PANEL
FIRE ALARM AUTOMATIC CEILING HEAT DETECTOR
WIRELESS FIRE ALARM HEAT DETECTOR
FIRE ALARM MANUAL STATION
FIRE ALARM CONTROL MODULE
CEILING FIRE ALARM LIGHT
(# INDICATES CANDELA RATING)
WALL FIRE ALARM LIGHT
(# INDICATES CANDELA RATING)
SAMPLING TUBE TYPE SMOKE DETECTOR
FIRE ALARM MAGNETIC DOOR HOLDER
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
FIRE DETECTION AND ALARM
F
F CM
F MM
F
F #
F
F #
F
F FAA
FACP
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SUBSCRIPTS
SUBSCRIPT "E" ADDED TO ANY SYMBOL
INDICATES EXISTING
SUBSCRIPT "PD" ADDED TO ANY FLOOR OUTLET
INDICATES PEDESTAL MOUNTED
SUBSCRIPT "K" ADDED TO ANY SYMBOL
INDICATES KEY OPERATED
SUBSCRIPT "WG" ADDED TO ANY SYMBOL
INDICATES WIRE GUARD
SUBSCRIPT "P" ADDED TO ANY SYMBOL
INDICATES PILOT LIGHT
SUBSCRIPT "AC" ADDED TO ANY SYMBOL INDICATES ABOVE COUNTER. LOCATE CENTER OF DEVICE 4" ABOVE COUNTER SURFACE OR WHERE PRESENT, 4" ABOVE BACKSPLASH.
WHERE INDICATED ADJACENT TO LAVATORY WITHOUT COUNTER, LOCATE CENTER OF DEVICE 8" ABOVE RIM OF LAVATORY.
EP
E
PD
AC
K
WG
P
RT WP
SUBSCRIPT "RT" APPLIED TO ANY SYMBOL
INDICATES RAIN TIGHT NEMA 3R
OR EQUIVALENT
SUBSCRIPT "WP" APPLIED TO ANY SYMBOL
INDICATES WEATHERPROOF NEMA TYPE 4
OR EQUIVALENT
SUBSCRIPT "EP" APPLIED TO ANY SYMBOL
INDICATES EXPLOSION PROOF,
CLASS, GROUP AND DIVISION AS NOTED
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SECURITY
WALL MOUNT MOTION SENSOR
CEILING MOUNT MOTION SENSOR
WIRELESS WALL MOUNT MOTION DETECTOR
WIRELESS CEILING MOUNT MOTION DETECTOR
POINT OF CONNECTION FOR 120VAC BY
ELECTRICAL CONTRACTOR
GLASS BREAK SENSOR
INTERCOM STATION
("S" SUBSTATION, "M" MASTER STATION)
JUNCTION BOX FOR SPECIALTY SECURITY SENSOR
DOME CAMERA
("#" INDICATES NUMBER IN SPECIFICATIONS)
SECURITY KEYPAD DEVICE
REMOTE ANNUNCIATOR DEVICE
DOOR LOCK POWER SUPPLY
PTZ DOME CAMERA
("#" INDICATES NUMBER IN SCHEDULE)
SECURITY EQUIPMENT CABINET(S), TYPE AND
QUANTITY MAY VARY FROM WALL MOUNTED,
FREE STANDING RACKS, OR EXTERIOR RATED,
REFER TO DETAILS
KEY SWITCH
REQUEST TO EXIT DEVICE
("M" MOTION SENSOR, "P" PUSH BUTTON)ACCESS CONTROL DEVICE LOCATION
"M" INDICATES MULLION MOUNT
DOOR POSITION SWITCH
WIRELESS DOOR POSITION SWITCH
AUTOMATIC OPERATOR CONNECTION POINT
('G' GATE, 'D' DOOR)
SECURITY PUSH BUTTON - ("P" INDICATES
PANIC ALARM)
M
P
J S
IC S,M
GB
E
G,D
PS
RA
KP
KS
RQE M,P
SEC
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
LIGHTING AND POWER
BRANCH CIRCUIT EXPOSED
BRANCH CIRCUIT -
CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT - CONCEALED IN FLOOR
(UNDERGROUND IF EXTERIOR)
SPECIAL PURPOSE HOMERUN AS INDICATED
HOMERUN TO PANEL (NUMBER OF ARROWS
INDICATES NUMBER OF CIRCUITS)
CIRCUIT DOWN
SIMPLEX RECEPTACLE
CORD AND PLUG
PULL BOX
CEILING MOUNTED DUPLEX RECEPTACLE
POLE LUMINAIRE(S)
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
ABOVE GRADE FIXTURE
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
LIGHTING PANEL - FLUSH MOUNTED
TRANSFORMER
ENCLOSED CIRCUIT BREAKER
SAFETY SWITCH
(FUSED UNLESS OTHERWISE NOTED)
WALL MOUNTED JUNCTION BOX
JUNCTION BOX
("F" INDICATES FLOOR, "C" INDICATES CEILING)
T
PB J
J XCIRCUIT BREAK
CIRCUIT UP
CONDUIT STUB OUT
STRIP LIGHT
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
LIGHTING PANEL - SURFACE MOUNTED
SINGLE POLE SWITCH
G,T,U
DUPLEX RECEPTACLE
"G" SUBSCRIPT INDICATES GFCI, "T" SUBSCRIPT
INDICATES TAMPER RESISTANT TYPE, "U" SUBSCRIPT
INDICATES COMBINATION USB CHARGING STATION
SYMBOLS INDICATED HERE AND NOT USED IN THE
CONTRACT DOCUMENTS DO NOT APPLY TO THIS
PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
FIRE ALARM MONITOR MODULE
FIRE ALARM HORN AND LIGHT COMBINATION
P
R
CO
GATEWAYF
WIRELESS FIRE ALARM MANUAL STATION R RESIDENTIAL BATTERY SMOKE DETECTOR
FS FIRE ALARM LOW FREQUENCY SOUNDER
H20 WATER DETECTOR
THE PARK SHALL HAVE FIRST SALVAGE RIGHTS TO ALL DEVICES AND EQUIPMENT REMOVED.
REMOVE FIRE ALARM AND INTRUSION ALARM CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS BACK TO THE
SOURCE.
ABANDON CONCEALED CONDUITS INSIDE WALLS.
COORDINATE AND SCHEDULE FIRE ALARM SYSTEM AND INTRUSION ALARM SYSTEM OUTAGES WITH THE PARK AND
CONTRACTING OFFICER.
COORDINATE DEMOLITION WITH THE PARK AND CONTRACTING OFFICER. ALLOW THE PARK TO OCCUPY THE SPACE.
REMOVE EXISTING FIRE ALARM DEVICES, INTRUSION ALARM DEVICES, AND WIRING. SEE PROJECT MANUAL AND NEW WORK
DRAWINGS.
THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS. FIRE ALARM AND INTRUSION ALARM SYSTEM SERVING BUILDINGS NOT UNDER CONSTRUCTION SHALL REMAIN ACTIVE UNTIL THOSE AREAS
ARE TURNED OVER TO THE CONTRACTOR FOR CONSTRUCTION.
REMOVE DEMOLISHED ITEMS FROM PROJECT SITE. PROPERLY DISPOSE OF ITEMS.
1.
2.
3.
4.
5.
6.
8.
7.
DEMOLITION DRAWINGS INDICATE EXISTING FIRE ALARM AND EXISTING INTRUSION ALARM EQUIPMENT AND EXISTING DEVICES WHICH ARE TO BE REMOVED. REMOVE INDICATED ITEMS AND ASSOCIATED ITEMS SUCH AS PARTYLINE EVENT TRANSCEIVER (PET) PANELS, OTHER ASSOCIATED EQUIPMENT, ABANDONED PANELS/EQUIPMENT BOXES AND CONDUITS NOT INDICATED BUT WHICH MUST BE REMOVED TO ACCOMMODATE REMODELING. SEE PROJECT MANUAL "WORK IN
EXISTING BUILDINGS" FOR ADDITIONAL INFORMATION.
9.
DEMOLITION NOTES
F
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
1.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
XX
ED1
SITE PLAN - ELECTRICAL
DEMOLITION
SITE PLAN - ELECTRICAL DEMOLITON
SCALE: 1" = 30'-0"
30 60 90 120 150
XX
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X X
XX
X
X
X
X X
X X
X X
X X
X
WINDMILL
CAMPAIGN
OFFICE
GARFIELD
HOME
M
EN
TO
R
AVE.
VISITOR
CENTER
TENANT
HOUSE
COMFORT
STATION
CHICKEN
COOP
MAIN
GATE
VISITOR
PARKING
HISTORIC LANE (BROWN ASPHALT)
HISTORIC LANE (BROWN ASPHALT)
ASPH
ALT W
ALKIN
G
TR
AIL
MAINTENANCE
BLDG.
GRAINERY
HORSE
BARN
ED3
ED3
ED4
ED4
ED5
ED5
ED8
ED8
ED8
ED8
ED2
ED2
ED7
ED6
ED6
ED6
ED10
ED10
ED9
ED9
ED10
UP
UP
1ST FLR XREF R 45' FOR BSMT
F
STAIR
STAIR
RECEPTION
SALES
VESTIBULE
RR
JAN.
EXHIBIT
SPRINKLER
SERVICE
LOBBY
EXHIBIT
EXHIBIT
EXHIBIT
ELEC
101B
AUDITORIUM
EXHIBIT
F
F
F
F
F F
1 (TYP)
2 (TYP)
(TYP)
(TYP)
(TYP)
(TYP)
XXXXXXXX
1ST FLR XREF 45' R FOR BSMT
DN
DN
ADMIN.
OFFICE
LOUNGE
STORAGE
STORAGE.
ELEC.
CLOSET
STAIR
STAIR
HALL
201A
F
F
F
3 (TYP)
4(TYP)
1 (TYP)
5 6
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
2.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
VISITOR CENTER FIRST FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
FLAG NOTES
XX
ED2
VISITOR CENTER
FLOOR PLANS -
ELECTRICAL DEMOLITION
ED2
VISITOR CENTER SECOND FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
ED2
1 REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
5 REMOVE EXISTING FIRE ALARM CONTROL PANEL.
6 REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
BASEMENT
BOILER
PIT
HALL
CRAWL
ELEV.
EQUIP.
CELLAR
HALL
AREAWAY
F F
CO
KP
FA
CP
3 (TYP)
(TYP)
1 (TYP)
F
F
PARLOR
RECEPTION
HALL
CLOSET
BEDROOM
ANTEROOM
DINING
ROOM
BEDROOM
VEST
CLO
VEST
101HALL
HALL
PANTRY
EXHIBITS
12 1
LAUNDRY
PANTRY
EXHIBITS
ENTRY
HALL
LAV
114 TLT
F
WPF
YELLOW
WP
YE
LL
OW
WP
WP
F
KP
F
ML
FA
A
FF
F
4 (TYP)
(TYP)
(TYP)
(TYP)
(TYP)
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
3.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
MAIN HOUSE BASEMENT FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
MAIN HOUSE MAIN FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
FLAG NOTES
XX
ED3
MAIN HOUSE
FLOOR PLANS -
ELECTRICAL DEMOLITION
ED3
ED3
1 REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
5 REMOVE EXISTING FIRE ALARM CONTROL PANEL.
6 REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
PIT
AutoCAD SHX Text
%%UCRAWL
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
%%UELEV.
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
LIFT
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
BEDROOM
HALL
HALL
HALL
HALL
HALL
ALCOVE
BEDROOM
BEDROOM
CLO
CLO
CLO
VAULT
LIBRARY
BEDROOM
CLO
BATH
CLO
CLO
CLO
BEDROOM
OFFICE
BEDROOM
CLO
CLO
BEDROOM
F F F
1(TYP)
(TYP)
3(TYP)
TANK
MECH
MECH
MECH
HALL
HALL
WATER
TANK
BEDROOM
BEDROOM
CLO
ALCOVE
CLO
F
F
21(TYP)
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
4.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
MAIN HOUSE SECOND FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
MAIN HOUSE THIRD FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
FLAG NOTES
XX
ED4
MAIN HOUSE
FLOOR PLANS -
ELECTRICAL DEMOLITION
ED4
ED4
1 REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
%%UELEV
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
1 (TYP)3 (TYP)
IN ATTIC
F
ATTIC ACCESS
4 (TYP)
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
5.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
CAMPAIGN HQ
MAIN FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
CAMPAIGN HQ
CRAWL SPACE PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
FLAG NOTES
XX
ED5
CAMPAIGN HQ
FLOOR PLANS - ELECTRICAL
DEMOLITION
ED5
ED5
REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
5 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
6 REMOVE EXISTING FIRE ALARM CONTROL PANEL.
7 REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
RM.1
RM.2
RM.3
RM.4
RM.5
RM.6
STAIR
S1
RM.21
STAIR
S1
RM.22
RM.23
RR
LAUNDRY
RM.
STAIR
S0
FURNACE
RM.
CRAWL
SPACE
F
F
F
6 5
1(TYP)
1 (TYP)
(TYP)
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
6.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
TENANT HOUSE FIRST FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
TENANT HOUSE BASEMENT FLOOR PLAN -
ELECTRICAL DEMOLITON
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
FLAG NOTES
XX
ED6
TENANT HOUSE
FLOOR PLANS -
ELECTRICAL DEMOLITION
ED6
ED6
TENANT HOUSE SECOND FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
ED6
1 REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
5 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
6 REMOVE EXISTING FIRE ALARM CONTROL PANEL.
7 REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
F 3 (TYP)
2 (TYP)
MEN
WOMEN
(TYP)
F
F
WP4
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 8p m
ED
7.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
FLAG NOTES
XX
ED7
COMFORT STATION
FLOOR PLAN - ELECTRICAL
DEMOLITION
COMFORT STATION
FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
ED7
REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING CONCEALED
CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 EXISTING AMBER WARNING LIGHT _______.
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 9p m
ED
8.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
WINDMILL GROUND FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
FLAG NOTES
XX
ED8
WINDMILL
FLOOR PLANS -
ELECTRICAL DEMOLITION
ED8
WINDMILL SECOND FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
ED8
WINDMILL THIRD FLOOR PLAN -
ELECTRICAL DEMOLITON
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
ED8
WINDMILLFOURTH FLOOR PLAN -
ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
ED8
REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
REMOVE EXISTING FIRE ALARM CONTROL PANEL.
REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
LOFT
F F 25
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 9p m
ED
9.d wg js an ch ez
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
FLAG NOTES
XX
ED9
GRAINERY
FLOOR PLANS - ELECTRICAL
DEMOLITION
GRAINERY
MAIN FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
GRAINERY
UPPER FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
ED9
ED9
REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
5 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
6 REMOVE EXISTING FIRE ALARM CONTROL PANEL.
7 REMOVE EXISTING INTRUSION ALARM CONTROL PANEL.
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
HORSE
STALL
HORSE
STALL
TACK
ROOM
COMMON
CO
(TYP)
F
F7 2
F
1 (TYP)
HAY
LOFT
MAINTENANCE
F F
4(TYP)
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 9p m
ED
.dw g jsa nc he z
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
HORSE BARN
MAIN FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
HORSE BARN
LOFT FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
XX
ED
MAINTENANCE BLDG & HORSE
BARN FLOOR PLANS -
ELECTRICAL DEMOLITION
MAINTENANCE BLDG
MAIN FLOOR PLAN - ELECTRICAL DEMOLITON
SCALE: 1/4" = 1'-0"
2 6 8 124 16 20
ED10
ED10
ED10
FLAG NOTES
1 REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
2 REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
3 REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
4 REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING
CONCEALED CONDUIT TO REMAIN.
5 REMOVE EXISTING FIRE ALARM MANUAL PULL STATION.
6 REMOVE EXISTING FIRE ALARM / INTRUSION ALARM CONTROL PANEL.
7 REMOVE EXISTING REMOTE FIRE ALARM ANNUNCIATOR PANEL.
AutoCAD SHX Text
UP
XX
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X X
XX
X
X
X
X X
X X
X X
X X
X
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
12/01/2023
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
XX
DESIGN DEVELOPMENT
XX
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2023C
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239956
No ve mb er
, 2
2:3 9p m
E1
.dw g jsa nc he z
INSTALL NEW INTRUSION & FIRE ALARM SYSTEM
JAMES A. GARFIELD NHS
MENTOR, OHIO
487/80010
319395
XX
E1 SITE PLAN - ELECTRICAL
SITE PLAN - ELECTRICAL
SCALE: 1" = 30'-0"
30 60 90 120 150
WINDMILL
CAMPAIGN
OFFICE
GARFIELD
HOME
M
EN
TO
R
AVE.
VISITOR
CENTER
TENANT
HOUSE
COMFORT
STATION
CHICKEN
COOP
MAIN
GATE
VISITOR
PARKING
HISTORIC LANE (BROWN ASPHALT)
HISTORIC LANE (BROWN ASPHALT)
ASPH
ALT W
ALKIN
G
TR
AIL
MAINTENANCE
BLDG.
GRAINERY
HORSE
BARN
CONDUIT SCHEDULE FIBER OPTIC AND COPPER CABLE SCHEDULE REMARKS
EXISTING UNDERGROUND CONDUIT
REFER TO FIBER OPTIC DIAGRAM AND SPECIFICATION SECTION 271323 FOR
CONNECTIVITY AND CABLING INFORMATION
1, 2, 3
EXISTING UNDERGROUND CONDUIT FIRE ALARM COPPER CABLES 2, 3
EXISTING UNDERGROUND CONDUIT FIRE ALARM AND…