Drawings.pdf
PDF 2 MB Posted
- Attached to
- Discovery HVAC
- Solicitation number
- RFP - BRSP - 240000000551
- Issued by
- Berrien County, Bergland CDP, Michigan
About this file
This document contains information related to the Discovery HVAC contract opportunity for Berrien County, Michigan. The project involves the HVAC replacement at the Discovery Academy facility in Berrien Springs, Michigan. The work includes demolition of existing rooftop units, installation of new rooftop units, ductwork, and related mechanical and electrical work. The drawings and specifications provide details on the required equipment, materials, and scope of work. The project requires the contractor to obtain all necessary permits and inspections, and complete the work in a professional manner according to relevant codes and standards. Shop drawings must be submitted for review, and the contractor is responsible for start-up, training, and warranties.
The contract documents do not specify pricing terms, set asides, incumbents, or funding details. However, they do outline requirements for the contractor, including safety responsibilities, coordination with other trades, and maintaining proper documentation. The successful contractor will be required to provide a one-year warranty covering all labor and materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project Manual.pdf | ||
| Invitation to Bid.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE: ARCHITECT:
C A
R M
I D E
S
IG
N G
R O
U P
210 E. MAIN STREET; P.O. BOX 487
NILES, MICHIGAN 49120
P: 269.663.5073
OWNER: PROJECT LOCATION: DRAWING INDEX: AREA MAP:
ENGINEER:
A u to d e s k D o c s /2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C R
E P
L A
C E
M E
N T
/2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C M
E P
.r v t
/3
/2
:4
:0
P M
.1
DECEMBER 1, 2023
BERRIEN SPRINGS PUBLIC SCHOOLS
DISCOVERY ACADEMY HVAC REPLACEMENT
D E
C E
M B
E R
B E
R R
IE
N
S P
R
IN
G S
P U
B L
IC
S C
H O
O L S
D
IS
C O
V E
R Y
A C
A D
E M
Y H
V A
C R
E P
L A
C E
M E
N T
FOR CONSTRUCTION
1 Sylvester Ave, Berrien Springs, MI 49103
G000 COVER SHEET
M000 MECHANICAL SYMBOLS AND GENERAL NOTES
M001 MECHANICAL SPECIFICATIONS
M310 FIRST FLOOR SHEET METAL PLAN
M701 MECHANICAL SCHEDULES & DETAILS
BERRIEN SPRINGS PUBLIC SCHOOLS 1 SYLVESTER AVE
BERRIEN SPRINGS, MI 49103
MECHANICAL ABBREVIATION LIST
ABBREVIATION DESCRIPTION
AAV
ACC
ACCU
AD
AFF
AFMS
AG
AHU
ALT
AMP
APD
ASHRAE
ASR
AUX
BAS
BCU
BDD
BFF
BFP
BHP
BOD
BOP
BTU
BTUH
C
CAP
CAV
CB
CC
CD
CD
CFCI
CFH
CFM
CH
CHW
CHWR
CHWS
CLG
CNDS
CNDS (__#)
CO
CO2
CONT
CONTR
CONV
COP
CP
CRU
CSS
CT
CUH
CW
CWF
DA
DAT
DB
DDC
DEG
DFU
DIA
DMPR
D/N
DN
DNZ
DS
DT
DTC
DWH
DWG
[E]
EXIST
EA
EA
EA
EAT
ECUH
EDB
EER
EEW/S
EEW
EF
EFF
EHC
EJ
EL
ELEC
EMS
ESP
EUH
EWB
EWC
EWT
EXH
FP
°F
F&B
F&T
FA
FCU
AUTOMATIC AIR VENT
AIR COOLED CONDENSER
AIR COOLED CONDENSER UNIT
ACCESS DOOR
ABOVE FINISHED FLOOR
AIRFLOW MEASURING STATION
ABOVE GRADE
AIR HANDLING UNIT
ALTERNATE
AMPERE
AIR PRESSURE DROP
AMERICAN SOCIETY OF HEATING, REFRIGERATION
AND AIR-CONDITIONING ENGINEERS
AUTOMATIC SPRINKLER RISER
AUXILIARY
BUILDING AUTOMATION SYSTEM
BLOWER COIL UNIT
BACK DRAFT DAMPER
BELOW FINISHED FLOOR
BACKFLOW PREVENTER
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
COMMON
CAPACITY
CONSTANT AIR VOLUME
CATCH BASIN
COOLING COIL
COLD DECK
CONDENSATE DRAIN
CONTRACTOR FURNISHED, CONTRACTOR
INSTALLED
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
COOLING
CONDENSATE
CONDENSATE (SPECIFIC PSIG)
CLEAN OUT
CARBON DIOXIDE
CONTINUATION OR CONTINUED
CONTRACTOR
CONVECTOR
COEFFICIENT OF PERFORMACE
CIRCULATING PUMP
CONDENSATE RETURN UNIT
CLINICAL SERVICE SINK
COOLING TOWER
CABINET UNIT HEATER
DOMESTIC COLD WATER
DOMESTIC COLD WATER FILTERED
DISCHARGE AIR
DISCHARGE AIR TEMPERATURE
DRY BULB
DIRECT DIGITAL CONTROL
DEGREE
DRAINAGE FIXTURE UNITS
DIAMETER
DAMPER
DAY/NIGHT
DOWN
DOWNSPOUT NOZZLE
DUCT SILENCER
DRAIN TILE
DRAIN TILE CONNECTION
DOMESTIC WATER HEATER
DRAWING
EXISTING
EXISTING
EXHAUST GRILLE OR REGISTER
EACH
EXHAUST AIR
ENTERING AIR TEMPERATURE
ELECTRIC CABINET UNIT HEATER
ENTERING DRY BULB
ENERGY EFFICIENCY RATIO
EMERGENCY EYE WASH / SHOWER
EMERGENCY EYE WASH
EXHAUST FAN
EFFICIENCY
ELECTRIC HEATING COIL
EXPANSION JOINT
ELEVATION
ELECTRICAL
EMERGENCY SHOWER
EXTERNAL STATIC PRESSURE
ELECTRIC UNIT HEATER
ENTERING WET BULB
ELECTRIC WATER COOLER
ENTERING WATER TEMPERATURE
EXHAUST
FIRE PROTECTION
DEGREEES FAHRENHEIT
FACE AND BYPASS
FLOAT AND THERMOSTATIC
FACE AREA
FAN COIL UNIT
ABBREVIATION DESCRIPTION
MECHANICAL SYMBOL LIST
PIPING SYMBOLS
FD
FFD
FH
FHC
FHR
FHV
FLA
FLR
FM
FMS
FPM
FP
FS
FSE
FT
FTR
FW
FV
G
GA
GAL
GH
GRH
GPH
GPM
H
HB
HC
HD
HEPA
HL
HOA
HO
HP
HP
HPL
HR
HTG
HV
HVAC
HW
HW(__)
HWR
HX
HZ
IAQ
ID
IE
IH
IN
IR
IW
JC
JP
KW
KWH
LAT
LAB
LAV
LBS
LDB
LD
LL
LPC
LPS
LPS(__#)
LRA
LWB
LWT
MA
MAT
MAU
MAX
MBH
MCA
MCC
MECH
MEZZ
MFR
MH
MIN
MISC
MMBH
M/S
MTD
MTR
MV
NC
NC
NCTC
NCTO
NFWH
NFPA
NOTC
NOTO
NIC
NO
NOM
NPCW
FLOOR DRAIN
FUNNEL FLOOR DRAIN
FIRE HYDRANT
FIRE HOSE CABINET
FIRE HOSE RACK
FIRE HOSE VALVE
FULL LOAD AMPS
FLOOR
FLOW METER
FLOW MEASURING STATION
FEET PER MINUTE
FIRE PUMP
FLOOR SINK
FOOD SERVICE EQUIPMENT
FEET
FINNED TUBE RADIATION
FOOT WASH
FACE VELOCITY
NATURAL GAS
GAUGE
GALLON
GROUND HYDRANT
GRAVITY RELIEF HOOD
GALLONS PER HOUR
GALLONS PER MINUTE
HYDROGEN
HOSE BIBB
HEATING COIL
HOT DECK
HIGH EFFICIENCY PARTICULATE ARRESTANCE
HIGH LIMIT
HAND/OFF/AUTO
HUB OUTLET
HEAT PUMP
HORSEPOWER
HEAT PUMP LOOP
HOUR
HEATING
HEATING VENTILATING
HEATING, VENTILATING, AIR CONDITIONING
DOMESTIC HOT WATER
DOMESTIC HOT WATER (SPECIFIC TEMP °F)
DOMESTIC HOT WATER RETURN
HEAT EXCHANGER
HERTZ
INDOOR AIR QUALITY
INSIDE DIAMETER
INVERT ELEVATION
INTAKE HOOD
INCHES
INFRARED HEATER
INDIRECT WASTE
JANITOR'S CLOSET
JOCKEY PUMP
KILOWATT
KILOWATT-HOUR
LEAVING AIR TEMPERATURE
LABRATORY
LAVATORY
POUNDS
LEAVING DRY BULB
LINEAR DRAIN
LOW LIMIT
LOW PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE STEAM (SPECIFIC PSIG)
LOCKED ROTOR AMPS
LEAVING WET BULB
LEAVING WATER TEMPERATURE
MIXED AIR
MIXED AIR TEMPERATURE
MAKE-UP AIR UNIT
MAXIMUM
THOUSAND BRITISH THERMAL UNITS PER HOUR
MEDICAL COMPRESSED AIR
MINIMUM CIRCUIT AMPACITY
MOTOR CONTROL CENTER
MECHANICAL
MEZZANINE
MANUFACTURER
MANHOLE
MINIMUM
MISCELLANEOUS
MILLION BRITISH THERMAL UNITS PER HOUR
MOTOR STARTER
MOUNTED
MOTOR
MANUAL AIR VENT
NOISE CRITERIA
NORMALLY CLOSED
NORMALLY CLOSED TIMED CLOSED
NORMALLY CLOSED TIMED OPEN
NON-FREEZE WALL HYDRANT
NATIONAL FIRE PROTECTION AGENCY
NORMALLY OPEN TIMED CLOSED
NORMALLY OPEN TIMED OPEN
NOT IN CONTRACT
NORMALLY OPEN
NOMINAL
NON POTABLE COLD WATER
ABBREVIATION DESCRIPTION
O
OA
OAT
OBD
OC
OD
OED
OFCI
OFOI
OL
ORC
ORD
OS&Y
OV
OWS
PACU
PBD
PC
PD
PNL
PPM
PRESS
PRV
PSAN
PSI
PSIA
PSIG
(R)
R
RA
RAT
RCP
RD
REQD
REF
RF
RH
RL
RLFA
RPM
RS
RTU
SA
SA
SA
SAN
SAN (GREASE)
SAT
SECT
SF
SH
SK
SMR
SMS
SP
SPEC
SPKLR
SQFT
S/S
SS
ST
STD
STK
ST
ST (OF)
S/W
SW
TA
TC
TC
TCP
TD
TEMP
TEMP
TH
THA
THR
THR
THS
TSP
TU
TV
TYP
UH
UL
UNO
UR
UV
V
V
VAC
VAV
VB
VD
VOL
VFC
VTR
VTU
VUV
W
W&V
WB
WC
WC
WG
WPD
WT
XFMR
OXYGEN
OUTSIDE AIR
OUTSIDE AIR TEMPERATURE
OPPOSED BLADE DAMPER
ON CENTER/CENTER TO CENTER
OUTSIDE DIAMETER
OPEN ENDED DUCT
OWNER FURNISHED, CONTRACTOR INSTALLED
ONWER FURNISHED, OWNER INSTALLED
OVERLOAD
OVERFLOW RAIN CONDUCTOR
OVERFLOW ROOF DRAIN
OUTSIDE SCREW AND YOKE
OUTLET VELOCITY
OPERATOR WORKSTATION
PACKAGED AIR CONDITIONING UNIT
PARALLEL BLADE DAMPER
PUMPED CONDENSATE
PRESSURE DROP (FEET OF WATER)
PANEL
PARTS PER MILLION
PRESSURE
PRESSURE REDUCING VALVE
PUMPED SANITARY
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH - ABSOLUTE
POUNDS PER SQUARE INCH - GAUGE
RELOCATED
RETURN GRILLE OR REGISTER
RETURN AIR
RETURN AIR TEMPERATURE
RADIANT CEILING PANEL
ROOF DRAIN
REQUIRED
ROOF EXHAUST FAN
RETURN FAN
RELATIVE HUMIDITY
REFRIGERANT LIQUID
RELIEF AIR
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
ROOFTOP UNIT
SUPPLY AIR DIFFUSER OR GRILLE
SOUND ATTENUATOR
SUPPLY AIR
SANITARY WASTE
SANITARY WASTE - GREASE
SUPPLY AIR TEMPERATURE
SECTION
SUPPLY FAN
SHOWER
SINK
SNOW MELT RETURN
SNOW MELT SUPPLY
STATIC PRESSURE
SPECIFICATION
SPRINKLER
SQUARE FOOT/SQUARE FEET
START/STOP
SERVICE SINK
STORM
STANDARD
STACK
STORM
STORM (OVERFLOW)
SUMMER/WINTER
SWITCH
TRANSFER AIR GRILLE
TEMPERATURE CONTROL
TEMPERING COIL
TEMPERATURE CONTROL PANEL
TRENCH DRAIN
TEMPERATURE
TEMPORARY
TERMINAL HEATING
TOTAL HEAT ABSORBED
TERMINAL HEATING RETURN
TOTAL HEAT REJECTED
TERMINAL HEATING SUPPLY
TOTAL STATIC PRESSURE
TERMINAL UNIT
TURNING VANES
TYPICAL
UNIT HEATER
UNDERWRITER'S LABORATORY
UNLESS NOTED OTHERWISE
URINAL
UNIT VENTILATOR
VALVE
VENT
VACUUM
VARIABLE AIR VOLUME
VACUUM BREAKER
VOLUME DAMPER (MANUALLY ADJUSTABLE)
VOLUME
VARIABLE FREQUENCY CONTROLER
VENT THROUGH ROOF
VENTURI TERMINAL UNIT
VERTICAL UNIT VENTILATOR
WASTE
WASTE AND VENT
WET BULB
WATER CLOSET
WATER COLUMN
WATER GAUGE
WATER PRESSURE DROP
WEIGHT
TRANSFORMER
SYMBOL DESCRIPTION
AIR VENT - AUTOMATIC
AIR VENT - MANUAL
BACKFLOW PREVENTER
CATCH BASIN
CIRCULATING PUMP
CLEAN OUT - IN FLOOR
CLEAN OUT - FLANGE
DIRECTION OF FLOW
DIRECTION OF PITCH - DOWN
FINNED TUBE RADIATION
FIRE PROTECTION - SIAMESE CONNECTION - FREE STANDING
FIRE PROTECTION - SIAMESE CONNECTION - WALL MOUNTED
FIRE PROTECTION - SPRINKLER HEAD, CONCEALED
FIRE PROTECTION - SPRINKLER HEAD, PENDANT
FIRE PROTECTION - SPRINKLER HEAD, UPRIGHT
FIRE PROTECTION - SPRINKLER HEAD, SIDEWALL
FLOOR DRAIN
FLOOR DRAIN - ELEVATION
FLOOR DRAIN - FUNNEL
FLOOR DRAIN - FUNNEL, ELEVATION
FLOW MEASURING DEVICE (FOR TEST AND BALANCING)
FLOW SWITCH
HOSE BIBB
MANHOLE
OPEN SITE DRAIN
PIPE - ANCHOR
PIPE - CAP OR PLUG
PIPE - ELBOW DOWN
PIPE - ELBOW UP
PIPE - EXPANSION JOINT OR COMPENSATOR
PIPE - FLANGE
PIPE - HOSE AND BRAID FLEXIBLE CONNECTION
PIPE - GUIDE
PIPE - TEE DOWN
PIPE - TEE UP
PIPE - UNION
PRESSURE AND TEMPERATURE TEST PLUG
PRESSURE GAUGE AND COCK
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
ROOF/OVERFLOW DRAIN
STEAM TRAP - FLOAT AND THERMOSTATIC
STRAINER
STRAINER WITH VALVE AND BLOW-OFF
THERMOMETER
TRAP
VALVE - ANGLE
VALVE - BALL
VALVE - BALANCE (i.e. BALANCE VALVE TO 0.5 GPM)
VALVE - BUTTERFLY
VALVE - COMINATION BALANCE & FLOW MEASURING
VALVE - CHECK
VALVE - SPRING CHECK
VALVE - GAS (MANUAL)
VALVE - GLOBE
VALVE - ISOLATION
VALVE - NEEDLE
VALVE - OS&Y
VALVE - PLUG
VALVE - PRESSURE REGULATING
VALVE - PRESSURE REDUCING
VALVE - PRESSURE RELIEF
VALVE - PRESSURE & TEMPERATURE RELIEF
VENT THROUGH ROOF
WALL HYDRANT
DUCTWORK SYMBOLS
SYMBOL DESCRIPTION
AIR TERMINAL UNIT
AIR TERMINAL UNIT WITH HEATING COIL
DAMPER - HORIZONTAL FIRE (EXISTING, NEW)
DAMPER - HORIZONTAL FIRE / SMOKE (EXISTING, NEW)
DAMPER - SMOKE (EXISTING, NEW)
DAMPER - VERTICAL FIRE (EXISTING, NEW)
DAMPER - VERTICAL FIRE / SMOKE (EXISTING, NEW)
DAMPER - BACK DRAFT
DAMPER - VOLUME (MANUALLY ADJUSTABLE)
DIFFUSER - BLANK OFF
DIFFUSER - LINEAR SLOT
DIFFUSER - SQUARE OR RECTANGULAR
DUCT CROSS SECTION - SUPPLY
DUCT CROSS SECTION - RETURN
DUCT CROSS SECTION - EXHAUST
DUCT - FLEXIBLE CONNECTION
DUCT - FLEXIBLE DUCT
DUCT TAKE-OFF - ROUND CONICAL
DUCT TAKE-OFF - RECTANGULAR WITH SHOE TAP
ELBOW - RECTANGULAR WITH TURNING VANES
ELBOW - RECTANGULAR/ ROUND SMOOTH RADIUS
ELBOW DOWN - RECTANGULAR
ELBOW DOWN - ROUND
ELBOW UP - RECTANGULAR
ELBOW UP - ROUND
HEATING COIL
INCLINED DROP IN DIRECTION OF AIRFLOW
INCLINED RISE IN DIRECTION OF AIRFLOW
INTAKE OR RELIEF HOOD
REGISTER - RETURN OR EXHAUST
REGISTER - RETURN WITH BOOT
REGISTER - TRANSFER GRILLE
ROOF EXHAUST FAN
DOUBLE LINE DUCTWORK SYMBOLS
SYMBOL DESCRIPTION
DUCT TAKE-OFF - RECTANGULAR WITH SHOE TAP
DUCT TAKE-OFF - ROUND CONICAL
ELBOW - RECTANGULAR WITH TURNING VANES
ELBOW - RECTANGULAR SHORT RADIUS WITH SPLITTER VANES
ELBOW - ROUND
ELBOW - RECTANGULAR SMOOTH RADIUS
ELBOW DOWN - RECTANGULAR
ELBOW DOWN - ROUND
ELBOW UP - RECTANGULAR
ELBOW UP - ROUND
HEATING COIL
INCLINED DROP IN DIRECTION OF AIRFLOW
INCLINED RISE IN DIRECTION OF AIRFLOW
TRANSITION - CONCENTRIC
TRANSITION -ECCENTRIC
D
R
AV
MV
BFP
CO
CO
FS
HB
MH
P/T
VTR
WH
TU-101
TU-101
BDD
D
R
0.5
0.5 (i.e. BALANCE VALVE TO 0.5 GPM)
DAMPER - MOTORIZEDM
PIPE - RUBBER FLEXIBLE CONNECTION
FLOW METER
FM
TEMPERATURE CONTROL - PARTIAL SYMBOLS LIST
SYMBOL DESCRIPTION
CO2 CARBON DIOXIDE SENSOR
CO
DPT
FM
CARBON MONOXIDE SENSOR
DIFFERENTIAL PRESSURE TRANSMITTER
FLOW METER
GUARD FOR STAT OR SENSOR
HUMIDISTAT OR HUMIDITY SENSOR
(AS DEFINED ON TC DRAWINGS)
SYMBOL DESCRIPTION
OCCUPANCY SENSOR
PT PRESSURE TRANSMITTER
STATIC PRESSURE SENSOR OR PROBE
VALVE - 2 WAY CONTROL VALVE
VALVE - 3 WAY CONTROL VALVE
THERMOSTAT OR TEMPERATURE SENSOR
(AS DEFINED ON TC DRAWINGS)
T
OS
SP
H
NOTE: LIST OF ADDITIONAL SYMBOLS & ABBREVIATIONS ASSOCIATED WITH
TEMPERATURE CONTROLS ARE IDENTIFIED ON TC DRAWINGS.
NOTE: SOME SYMBOLS AND ABBREVIATIONS
SHOWN MAY NOT APPLY TO THIS PROJECT.
DATE
210 E. MAIN STREET; P.O. BOX 487
NILES, MICHIGAN 49120
P: 269.663.5073
THE INFORMATION ON THIS SHEET IS
THE PROPERTY OF CARMI design group inc. AND MAY NOT BE REPRODUCED
WITHOUT WRITTEN CONSENT FROM
CARMI design group inc.
Copyright 2023 ©
PROJECT #
ISSUEDNO. DATE
A u to d e s k D o c s /2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C R
E P
L A
C E
M E
N T
/2 .1
C D
G B
S P
S D
IS
C
O V
E R
Y H
V A
C M
E P
.r v t
/3
/2
:4
:0
P M
DISCOVERY
ACADEMY HVAC
REPLACEMENT
DECEMBER 1, 2023
BERRIEN SPRINGS
PUBLIC SCHOOLS
1 Sylvester Ave, Berrien Springs, MI 49103
23.112
MECHANICAL
SYMBOLS AND
GENERAL
NOTES
M000
FOR CONSTRUCTION
MECHANICAL SPECIFICATIONS
1. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE
IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED. INSTALLER
SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND
DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE PIPING, VALVES, TRAPS, GAUGES, CONTROLS, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND
LOCAL CODES.
2. ALL WORK AND EQUIPMENT PROVIDED AND PERFORMED ON THIS PROJECT SHALL COMPLY WITH ALL
APPLICABLE LAWS, CODES, ETC OF ANY AND ALL AUTHORITIES HAVING JURISDICTION INCLUDING, BUT NOT
LIMITED TO: MICHIGAN MECHANICAL CODE - 2015, MICHIGAN PLUMBING CODE - 2015, MICHIGAN BUILDING
CODE - 2015, MICHIGAN UNIFORM ENERGY CODE (ASHRAE 90.1-2013). THE LOCAL FIRE MARSHAL, UNDERWRITERS LABORATORIES, IRI, FM, NATIONAL ELECTRICAL CODE, LOCAL HEALTH DEPARTMENT, OSHA, MIOSHA. ANY MODIFICATIONS REQUIRED BY ANY OF THE ABOVE SHALL BE MADE AT NO ADDITIONAL
COST TO THE OWNER. WHERE THE CONTRACT DOCUMENTS EXCEED THE CODE REQUIREMENTS, THE
CONTRACT DOCUMENTS SHALL BE FOLLOWED. DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE
SUBMITTED TO THE ENGINEER FOR REVIEW BEFORE INSTALLATION.
3. CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
4. JOBSITE SAFETY IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL HAVE ON SITE A
QUALIFIED FOREMAN OVERSEEING ALL ASPECTS OF THE CONSTRUCTION. THE ARCHITECT AND ENGINEER
ARE NOT RESPONSIBLE FOR JOBSITE SAFETY.
5. ANY HOISTS, LIFTS, OR SPECIAL EQUIPMENT REQUIRED TO SAFELY COMPLETE THE PROJECT SHALL BE
PROVIDED BY THE CONTRACTOR UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.
6. THE BID SHALL INCLUDE ALL LABOR AND MATERIALS ESSENTIAL TO PROVIDE A COMPLETE AND
FUNCTIONING SYSTEM AS DESCRIBED IN THE CONTRACT DOCUMENTS, EVEN THOUGH EVERY ITEM
INVOLVED IS NOT PARTICULARLY MENTIONED. SUCH MATERIALS SHALL INCLUDE PIPING, VALVES, TRAPS, GAUGES, CONTROLS, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND LOCAL CODES. IN
CASES OF DOUBT AS TO WORK INTENDED THE CONTRACTOR SHALL REQUEST SUPPLEMENTARY
INFORMATION AT LEAST FIVE(5) DAYS PRIOR TO BIDDING. ONCE CONTRACT IS AWARDED ANY DISPUTES AS
TO THE INTENT OF THE DESIGN SHALL BE RESOLVED AS DIRECTED BY THE ENGINEER AND NO ADDITIONAL
COST TO THE OWNER.
7. CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL EQUIPMENT AND MATERIALS WITH ALL OTHER
TRADES.
8. CONTRACTOR SHALL NOT PROCEED WITH ANY WORK FOR WHICH ADDITIONAL COMPENSATION IS
EXPECTED WITHOUT A WRITTEN CHANGE-ORDER SIGNED BY THE ENGINEER. ADDITIONAL COMPENSATION
WILL NOT BE GIVEN WITHOUT A SIGNED, WRITTEN, CHANGE-ORDER. CHANGE-ORDER FORMS MAY BE
REQUESTED FROM THE ENGINEER OR CONTRACTOR MAY USE THEIR OWN FORM. CHANGE-ORDER MUST
INCLUDE DESCRIPTION OF CHANGE, REASON FOR CHANGE, AND COST BREAKDOWN SHOWING ITEMIZED
MATERIAL COSTS, LABOR TIME AND RATE AND SEPARATELY LISTED OH&P. OH&P FOR CHANGE ORDERS
SHALL NOT EXCEED 10%.
9. A SET OF AS-BUILT DOCUMENTS SHALL BE KEPT ON THE JOB SITE, ACCESSIBLE TO ALL TRADES.
CONTRACTOR SHALL MAINTAIN THE AS-BUILT DRAWINGS DAILY INDICATING ANY DEVIATIONS FROM THE
CONTRACT DOCUMENTS. CONTRACTOR SHALL MAINTAIN COMMUNICATION WITH ALL OTHER TRADES AND
REVIEW AS-BUILT DOCUMENTS OF ALL TRADES ON A REGULAR BASIS. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING WITH ALL TRADES DURING CONSTRUCTION AND FOR NOTIFYING THE
ENGINEER OF ANY CHANGES THAT WILL NEED TO BE MADE AS SOON AS THEY ARE IDENTIFIED.
10. ALL PRODUCTS AND MATERIALS USED SHALL BE NEW AND "BEST OF ITS KIND." PRODUCTS AND MATERIALS
SHALL BE PROTECTED FROM CONSTRUCTION AND WEATHER DAMAGE. CONTRACTOR SHALL NOT INSTALL
ANY COMPONENT THAT IS DAMAGED, DIRTY, OR SHOWS ANY SIGNS OF CORROSION.
11. THE CONTRACTOR IS RESPONSIBLE, AT HIS OWN COST, FOR WAREHOUSING OF MATERIAL AND EQUIPMENT
TO BE INSTALLED ON THIS PROJECT. COORDINATE WITH THE BUILDING OWNER AND/OR GENERAL
CONTRACTOR FOR SPACE AVAILABLE ON THE JOB SITE FOR MATERIAL STORAGE.
12. SHOP DRAWINGS SHALL BE SUBMITTED FOR THE ITEMS LISTED BELOW WITHIN 2 WEEKS OF AWARD OF
CONTRACT AND A MINIMUM OF 2 WEEKS PRIOR TO INSTALLATION. CONTRACTOR SHALL NOT ORDER
EQUIPMENT UNTIL SHOP DRAWINGS HAVE BEEN PROCESSED BY THE ENGINEER. SHOP DRAWINGS SHALL
BE REVIEWED BY THE CONTRACTOR AND GENERAL CONTRACTOR PRIOR TO BEING SUBMITTED TO THE
ENGINEER. INCLUSION IN SHOP DRAWINGS DOES NOT AUTHORIZE A DEVIATION FROM THE REQUIREMENTS
OF THE SPECIFICATIONS. ALL SHOP DRAWINGS SHALL HAVE LISTED ON THE COVER SHEET ANY AND ALL
PRODUCTS OR MATERIALS THAT DEVIATE FROM SPECIFICATIONS. DETERMINATION OF "EQUAL" SHALL BE
MADE BY ENGINEER. AT A MINIMUM SHOP DRAWINGS SHALL BE SUBMITTED FOR: ALL AIR HANDLING
EQUIPMENT, DUCT SEALANTS, MOTORIZED DAMPERS, GRILLES / LOUVERS / DIFFUSERS.
13. AT PROJECT COMPLETION PROVIDE TO THE BUILDING OWNER THREE(3) BOUND SETS TO INCLUDE ALL O&M
MANUALS FOR EQUIPMENT INSTALLED, BALANCE REPORTS AND COPIES OF ALL MANUFACTURER
WARRANTIES. CONTRACTOR SHALL COMPLETE ANY WARRANTY REGISTRATION CARDS NECESSARY FOR
MANUFACTURER WARRANTIES.
14. CONTRACTOR SHALL PROVIDE A ONE (1) YEAR WARRANTY FOR ALL WORK PERFORMED. THIS INSTALLERS
WARRANTY SHALL COVER ALL MATERIAL AND EQUIPMENT NOT COVERED BY A MANUFACTURER
WARRANTY AND ALL LABOR. THIS WARRANTY SHALL ALSO COVER INSTALLER ERROR OR DAMAGE.
15. ALL WORK ON THIS PROJECT SHALL BE EXECUTED IN A GOOD, WORKMAN LIKE MANNER USING MECHANICS
SKILLED IN THEIR RESPECTIVE TRADES. NO ALLOWANCE WILL BE GIVEN FOR POOR WORKMANSHIP. ANY
INSTALLATION THAT IS OF INSUFFICIENT QUALITY SHALL BE REPLACED BY THE CONTRACTOR AT NO COST
TO THE OWNER.
16. WORK SITE IS TO BE LEFT IN A NEAT AND ORDERLY CONDITION AT THE END OF EACH WORK SHIFT.
17. CONTRACTOR SHALL COORDINATE WITH THE OWNER ANY OWNER FURNISHED EQUIPMENT. CONTRACTOR
SHALL RECEIVE ANY OWNER FURNISHED ITEMS WHEN DELIVERED TO THE JOB SITE AND SHALL BE
RESPONSIBLE FOR THE ITEMS ONCE RECEIVED.
18. CONTRACTOR SHALL REVIEW ARCHITECTURAL DRAWINGS FOR LOCATIONS OF SLAB-TO-SLAB PARTITIONS, FIRE RATED PARTITIONS AND FIRE RATED FLOORS. ALL PENETRATION OF SLAB-TO-SLAB PARTITIONS
SHALL BE SEALED AIR TIGHT. ALL PENETRATIONS OF FIRE RATED PARTITIONS OR FLOORS SHALL BE
PROVIDED WITH A FIRE RATED DAMPER AND ACCESS DOOR. DAMPER SHALL HAVE A RATING APPROPRIATE
FOR THE ASSEMBLY PENETRATED.
19. PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE SEALED USING CODE APPROVED, LABORATORY
TESTED AND LABELED SEALANTS FOR A FIRE RESISTANCE RATING EQUAL TO OR GREATER THAN THE
ASSEMBLY PENETRATED.
20. CONTRACTOR SHALL VERIFY LOCATION OF CEILING MOUNTED DIFFUSERS AND GRILLES WITH
ARCHITECTURAL CEILING PLAN PRIOR TO INSTALLATION.
21. ALL DUCT SIZES SHOWN ON THE DRAWINGS ARE TO ESTABLISH TOTAL DUCT AREA REQUIRED. IF DUCT
SIZES NEED TO BE CHANGED OR DUCTS BE REROUTED TO INSTALL THE DUCTS THROUGH JOISTS, ABOVE
CEILINGS, BELOW STEEL, ETC., CHANGES SHALL BE DONE AT NO EXTRA COST TO THE OWNER. THE
CONTRACTOR SHALL CHECK WITH THE ARCHITECT/ENGINEER BEFORE CHANGING ANY SIZES.
22. NEW DUCTWORK, PIPING, AND CONDUIT SHALL BE INSTALLED AS HIGH AS POSSIBLE. CONTRACTOR SHALL
COORDINATE DUCTWORK, PIPING AND CONDUITS WITH LIGHTING FIXTURES, CEILING CONSTRUCTION, STRUCTURE AIR DISTRIBUTION EQUIPMENT, ETC., AND SHALL BE OFF-SET AS REQUIRED.
23. ALL NEW RECTANGULAR DUCTWORK SHALL BE 1" W.G. CONSTRUCTION OF LOCK FORMING GALVANIZED
STEEL IN ACCORDANCE WITH FIGURES 3-1 THRU 3-56 AND TABLE 3-2 OF THE SMACNA GUIDELINES ("DUCT
MANUAL AND SHEET METAL CONSTRUCTION FOR VENTILATION AND AIR CONDITIONING SYSTEMS" MOST
RECENT EDITION.) SNAP LOCK LONGITUDINAL SEAMS AND DRAWBAND JOINT CONNECTIONS ARE NOT
ACCEPTABLE. (LOW PRESSURE ROUND RUN-OUT DUCTS MAY BE SNAP LOCK LONGITUDINAL SEAM WITH
SCREW/RIVET JOINT CONNECTIONS).
24. DUCTWORK SHALL BE HUNG AS HIGH AS POSSIBLE FROM BUILDING STRUCTURE. CONDUITS, PIPES, CEILINGS OR ANY OTHER ITEMS SHALL NOT BE HUNG FROM DUCTWORK. PROVIDE ALL FITTINGS ELBOWS, DAMPERS, OFF-SETS, ETC. FOR COMPLETE DUCTWORK INSTALLATION. ALL ELBOWS SHALL BE GORED
RADIUS ELBOWS (PLEATED NOT ALLOWED) UNLESS SQUARE ELBOWS ARE SHOWN ON PLANS. ALL SQUARE
ELBOWS SHALL HAVE TURNING VANES.
25. VOLUME DAMPERS SHALL BE INSTALLED AS SHOWN ON PLANS, AND AT ALL BRANCH TAKE-OFFS.
26. ALL DUCTWORK SHALL BE SEALED USING IRON GRIP (NO SUBSTITUTIONS) AND SHALL MEET THE MICHIGAN
UNIFORM ENERGY CODE (ASHRAE 90.1-2007) DUCT SEAL LEVEL "A" (TABLE 6.4.4.2A). SEAL LEVEL "A" SHALL
BE USED FOR ALL DUCT TYPES AND PRESSURE CLASSES.
27.
ALL EXTERIOR DUCTWORK SHALL BE THERMADUCT, PREFABRICATED EXTERIOR DUCT SYSTEM.
28. USE PVC COATED GALVANIZED STEEL FOR UNDERGROUND DUCTS AND INSTALL IN ACCORDANCE WITH THE
MANUFACTURER'S REQUIREMENTS. REPAIR DAMAGE TO PVC COATINGS WITH MANUFACTURER'S
RECOMMENDED MATERIALS. DUCTS IN CONCRETE SLABS SHALL BE ROUND AND ENCASED IN AT LEAST 2”
OF CONCRETE. USE A VIBRATOR TO FILL VOIDS IN CONCRETE. SLOPE ALL UNDERGROUND DUCT BACK
TOWARD UNIT. PROVIDE DUCT ACCESS DOOR.
29. FLEXIBLE DUCT CONNECTIONS SHALL BE MADE BY APPLYING DUCT SEALER TO INSIDE OF FLEXIBLE DUCT
AND OUTSIDE OF HARD DUCT COLLAR. ADHESIVE SHALL BE CHEMICALLY COMPATIBLE WITH MATERIALS IN
CONTACT WITH IT. THE ENDS OF DUCTS SHALL BE TRIMMED SQUARELY PRIOR TO INSTALLATION. COLLARS
AND SLEEVES SHALL BE INSERTED INTO FLEXIBLE DUCT A MINIMUM OF 1” BEFORE FASTENING. SLIDE FLEX
DUCT OVER COLLAR AND TAPE WITH THREE WRAPS OF DUCT TAPE AROUND JOINT AND SEAL WITH
STAINLESS STEEL CLAMPS OVER OUTSIDE OF TAPE.
A. HIGH PRESSURE: INSTALL AT INLET CONNECTIONS OF TERMINAL UNITS. MAXIMUM DEVELOPED
LENGTH OF FLEX DUCT SHALL BE 3'-0”. USE METAL DUCTS AND FITTINGS TO REACH WITHIN 3'-0”
OF TERMINAL UNIT.
B. LOW PRESSURE: INSTALL WHERE INDICATED ON DRAWINGS AND BE A MAXIMUM OF 5'-0” IN
LENGTH. USE METAL DUCT AND FITTINGS TO REACH WITHIN 5'-0” OF DIFFUSER.
30. FLEXIBLE DUCTS SHALL BE USED FOR ALIGNMENT PURPOSES ONLY. MAXIMUM OFFSET 1” PER FOOT
LENGTH. NO ELBOWS USING FLEXIBLE DUCTS WILL BE ALLOWED. DUCTS SHOULD NOT BE COMPRESSED.
THE SPECIFICATIONS HEREIN, SHALL NOT SUPERSEDE THE APPLICATION CONTINGENCIES DICTATED BY
THE FLEXIBLE DUCT MANUFACTURER IF THOSE ARE MORE STRINGENT.
31. ALL PIPING TO BE INSTALLED PERPENDICULAR TO STRUCTURE LINES UNLESS OTHERWISE NOTED ON
DRAWINGS. ALL PIPING TO BE NEATLY SPACED WITH RISERS AND DROPS PLUMB AND TRUE. MINIMUM
SPACING SHALL HAVE 1" CLEAR BETWEEN PIPING (INCLUDING FITTINGS) AFTER INSULATION. PIPING SHALL
NOT OBSTRUCT ACCESS TO EQUIPMENT,VALVES, FILTERS, ETC.
32. ALL PIPING TO BE INSTALLED CONCEALED EXCEPT WHERE NOTED ON PLANS. DO NOT INSTALL PIPING
BELOW SLABS EXCEPT WHERE NOTED ON PLANS. DO NOT CONCEAL PIPING UNTIL INSPECTED AND TESTED.
PNEUMATIC TESTING OF ALL PIPING IS REQUIRED.
33. ALL PIPING THAT PENETRATES CONCRETE SLABS OR MASONRY WALLS SHALL BE PROVIDED WITH A PIPE
SLEEVE WITH AN I.D. MINIMUM 1" LARGER THAN O.D. OF PIPE. SLEEVES SHALL PROTRUDE 2" AFF AND FLUSH
WITH WALL SURFACE. IF PIPE SLEEVES ARE NOT POURED-IN-PLACE, GROUT SECURELY TO WALL OR SLAB.
SEAL SPACE BETWEEN PIPE AND SLEEVE. USE FIRE RATED SEALANT WHERE REQUIRED.
34. PROVIDE ALL PIPING OFF-SETS AS REQUIRED FOR COORDINATION WITH STRUCTURE, DUCTWORK, CONDUITS, ETC.
35. INSTALL PIPE ANCHORS WHERE REQUIRED OR AS SHOWN ON PLANS. INSTALL PIPE ROLLERS WHERE
REQUIRED OR SHOWN ON PLANS. INSTALL GUIDES AT ALL EXPANSION JOINTS, EXPANSION LOOPS OR
WHERE REQUIRED.
36. FLEXIBLE CONNECTORS, EXPANSION AND VIBRATION CONTROL DEVICES AND FITTING SHALL BE OF AN
APPROVED TYPE.
37. ALL PIPING, VALVES AND HYDRONIC EQUIPMENT SHALL BE LABELED WITH ENGRAVED TAGS OR PLACARDS
WITH LETTERING ONE INCH(1") TALL (MINIMUM).
38. CLOSE NIPPLES SHALL NOT BE PERMITTED. USE ONLY SHOULDER NIPPLES.
39. REDUCERS FOR PUMPS OR CONTROL VALVES SHALL BE INSTALLED ABUTTING THE INLET/OUTLET OF THE
VALVE OR PUMP.
40. USE ECCENTRIC REDUCING FITTINGS OR COUPLINGS WHERE REQUIRED TO PREVENT THE POCKETING OF
LIQUIDS.
41. PROVIDE UNION OR FLANGE AT PIPE CONNECTIONS TO COILS, EQUIPMENT, ETC. AND AT LOCATIONS SHOWN
ON PLANS OR IN DETAILS. PROVIDE UNION OR FLANGE BETWEEN EQUIPMENT AND CONTROL VALVES.
42. PROVIDE PEET'S PLUGS (PT PLUGS) AT THE INLET AND OUTLET OF ALL HYDRONIC EQUIPMENT WHERE
THERMOMETERS ARE NOT SHOWN.
43. PROVIDE DIELECTRIC UNIONS BETWEEN FERROUS AND NON FERROUS PIPE AND FITTINGS.
44. PIPE INSULATION SHALL BE PER ASHRAE 90.1-2013. MINIMUM 1" FIBERGLASS INSULATION (2LB, FIRE/SMOKE 25/50) ON ALL HYDRONIC PIPING. STEAM HEATING PIPING SYSTEM SYSTEMS WITH 1½” THICK
FIBERGLASS INSULATION (1½” DIAMETER AND UNDER) OR 2” THICK (OVER 1½” DIAMETER). 251°-350° FLUID
TEMPERATURE: INSULATE STEAM HEATING PIPING SYSTEM SYSTEMS WITH 2½” THICK FIBERGLASS
INSULATION (1½” DIAMETER AND UNDER) OR 3” THICK (OVER 1½” DIAMETER). 140°-200° FLUID
TEMPERATURE: INSULATE CONDENSATE HEATING PIPING SYSTEMS WITH 1” THICK FIBERGLASS INSULATION
(4” DIAMETER AND UNDER). 201°-250° FLUID TEMPERATURE: INSULATE CONDENSATE HEATING PIPING
SYSTEM WITH 1½” THICK FIBERGLASS INSULATION (1½” DIAMETER AND UNDER) OR 2” THICK (OVER 1½”
DIAMETER).
45. THERMOSTATS SHALL BE INSTALLED AS SHOWN ON PLANS. TYPICAL HEIGHT FOR MOUNTING SHALL BE 48"
AFF TO BOTTOM OF T-STAT, UNLESS OTHERWISE NOTED. DO NOT INSTALL T-STAT WITHIN TWO(2) FEET OF
DIMMING LIGHT SWITCH. INDICATED SHALL BE MEASURED AND BALANCED TO WITHIN 10% OF THE FLOW
VALUES INDICATED ON THE DRAWINGS. FAN RPMS, AND VOLUME DAMPERS SHALL BE ADJUSTED AS
REQUIRED TO ACHIEVE FLOW BALANCE. NEBB OR AABC CERTIFIED BALANCE REPORTS SHALL BE
SUBMITTED TO THE ENGINEER AT THE COMPLETION OF THE PROJECT. THE COST OF THE BALANCING
SHALL BE INCLUDED IN THE MECHANICAL CONTRACTOR BID.
46. ALL AUTOMATIC TEMPERATURE CONTROLS ARE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.
47. CONTRACTOR SHALL NOT CUT, DRILL OR POWDER NAIL INTO ANY EXISTING OR NEW STRUCTURAL MEMBER
OR ASSEMBLY WITHOUT PRIOR WRITTEN AUTHORIZATION FROM A LICENSED STRUCTURAL ENGINEER AND
THE BUILDING OWNER. THIS INCLUDES CORE DRILLING ANY CONCRETE WALL OR FLOOR SLAB.
48. ALL MECHANICAL EQUIPMENT SHALL BE HUNG OR SUPPORTED WITH VIBRATION ISOLATING HANGERS OR
PADS. NO VIBRATION SHALL BE TRANSMITTED TO THE STRUCTURE.
49. COMBUSTION AIR INTAKE AND EXHAUST FLUES SHALL HAVE 10'-0" HORIZONTAL OR 3'-0" VERTICAL
SEPARATION.
50. PROVIDE UL LISTED FIRE DAMPERS AT PENETRATIONS OF FIRE RATED WALLS AND CEILINGS.
51. A MANUFACTURER'S AUTHORIZED REPRESENTATIVE SHALL PROVIDE START-UP SUPERVISION AND
TRAINING OF OWNER'S PERSONNEL IN THE PROPER OPERATION AND MAINTENANCE OF ALL EQUIPMENT.
52. GAS PIPING SYSTEM SHALL CONFORM TO THE REQUIREMENTS OF NFPA 54 - NATIONAL FUEL GAS CODE
AND INTERNATIONAL FUEL GAS CODE.
53. GAS PIPING ABOVE GRADE AND OUTSIDE THE BUILDING GAS PIPING IS TO BE PAINTED BLACK.
54. COORDINATE VOLTAGE AND PHASE OF EACH PIECE OF EQUIPMENT WITH ELECTRICAL CONTRACTOR
BEFORE ORDERING.
DATE
210 E. MAIN STREET; P.O. BOX 487
NILES, MICHIGAN 49120
P: 269.663.5073
THE INFORMATION ON THIS SHEET IS
THE PROPERTY OF CARMI design group inc. AND MAY NOT BE REPRODUCED
WITHOUT WRITTEN CONSENT FROM
CARMI design group inc.
Copyright 2023 ©
PROJECT #
ISSUEDNO. DATE
A u to d e s k D o c s /2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C R
E P
L A
C E
M E
N T
/2 .1
C D
G B
S P
S D
IS
C
O V
E R
Y H
V A
C M
E P
.r v t
/3
/2
:4
:0
P M
DISCOVERY
ACADEMY HVAC
REPLACEMENT
DECEMBER 1, 2023
BERRIEN SPRINGS
PUBLIC SCHOOLS
1 Sylvester Ave, Berrien Springs, MI 49103
23.112
MECHANICAL
SPECIFICATIONS
M001
ELECTRICAL SPECIFICIATION
1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
2. ALL WORK SHALL BE PERFORMED IN ACCORDINANCE WITH THE MICHIGAN ELECTRICAL CODE.
3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY
FUNCTIONAL ELECTRICAL SERVICE.
4. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.
5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT.
B. CONDUCTORS.
C. WIRING DEVICES INCLUDING COVERPLATES.
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.
E. POWER METERS.
7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.
8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
9. PROVIDE LAMACOID LABELS FOR:
A. DISCONNECT SWITCHES.
10. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:
A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS: RIGID GALVANIZED STEEL.
C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.
D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.
11. IT IS UNDERSTAND AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT
PARTICULARLY MENTIONED. INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A
COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL
DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND LOCAL CODES.
RTU-1
RTU-2
RTU-3
EXIST. GAS METER
EXISTING BIG RM S UNIT
EXISTING WEST CLASSROOM UNIT
EXISTING BIG RM N UNIT
EXIST. GAS METER
DATE
210 E. MAIN STREET; P.O. BOX 487
NILES, MICHIGAN 49120
P: 269.663.5073
THE INFORMATION ON THIS SHEET IS
THE PROPERTY OF CARMI design group inc. AND MAY NOT BE REPRODUCED
WITHOUT WRITTEN CONSENT FROM
CARMI design group inc.
Copyright 2023 ©
PROJECT #
ISSUEDNO. DATE
A u to d e s k D o c s /2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C R
E P
L A
C E
M E
N T
/2 .1
C D
G B
S P
S D
IS
C
O V
E R
Y H
V A
C M
E P
.r v t
/3
/2
:4
:0
P M
DISCOVERY
ACADEMY HVAC
REPLACEMENT
DECEMBER 1, 2023
BERRIEN SPRINGS
PUBLIC SCHOOLS
1 Sylvester Ave, Berrien Springs, MI 49103
23.112
FIRST FLOOR
SHEET METAL
PLAN
M310
MECHANICAL KEYED NOTES
1 UNIT SHALL BE INSTALLED ON A 36" CURB ON NEW CONCRETE HOUSEKEEPING PAD.
2 EXTERIOR DUCTWORK SHALL BE PREINSULATED DUCTWORK SYSTEM BASED ON
THERMADUCT. MATCH EXISTING DUCT SIZES, ROUTE AND OFFSET AS NECESSARY FOR
UNIT LOCATIONS.
3 REMOTE POWERED EXHAUST
4 DUCT WORK SHALL CONTINUE AND TIE-IN TO EXISTING INTERNAL DUCTWORK
5 CONNECT EXISTING CIRCUIT TO UNIT MOUNTED NON-FUSED DISCONNECT.
6 PROVIDE WEED BARRIER AND 5" OF CRUSHED GRAVEL WITHIN EQUIPMENT SERVICE AREA.
7 BLACK STEEL LANDSCAPE EDGING
1/4" = 1'-0"
MECHANICAL PLAN1/4" = 1'-0"
MECHANICAL DEMOLITION PLAN
MECHANICAL DEMOLITION KEYED NOTES
1 EXISTING RELIEF TO BE DEMOLISHED
2 EXISTING DUCTWORK TO BE DEMOLISHED
3 DISCONNECT EXISTING ELECTRICAL CONNECTION TO MECHANICAL UNIT.
DEMOLISH EXISTING UNIT MOUNTED DISCONNECT.
4 REMOVE EXISTING RTU, EQUIPMENT PAD, EXTERIOR SHEET METAL,
CONTROLS, GAS PIPING AND ALL ASSOCIATED ACCESSORIES.. PREPARE
LOCATION FOR NEW WORK
5 REMOVE ALL EXISTING STONE, WEEDS, AND DEBRIS FROM WITHIN
EQUIPMENT SERVICE AREA DOWN 5 INCHES. PREPARE FOR NEW WORK.
DIRT LEG
GRADE
MOUNTED
RTU
SHUT-OFF VALVE
PRESSURE REGULATOR PIPE
VENT OUTLET WITH
DOWNTURN ELBOW
UNION
CONNECT TO EXISTING GAS
CONDENSATE TRAP
AND DRAIN TO GRADE
36" CURB FURNISHED BY
UNIT MANUFACTURER
RETURN AIR
SUPPLY AIR
DUCT
CONCRETE HOUSEKEEPING PAD
3' - 0"
2"
8" 8"
M
IN
F
IE
L
D V
E R
IF
Y
(2) #5 CONTINUOUS
#5 @ 16" O.C.
COMPACTED STONE FILL
4,000 PSI CONCRETE PAD
6x6 W2.9xW2.9 W.W.M.
HOUSEKEEPING PAD SHALL MATCH UNIT CURB DIMENSIONS PLUS 6" IN ALL DIRECTIONS
DATE
210 E. MAIN STREET; P.O. BOX 487
NILES, MICHIGAN 49120
P: 269.663.5073
THE INFORMATION ON THIS SHEET IS
THE PROPERTY OF CARMI design group inc. AND MAY NOT BE REPRODUCED
WITHOUT WRITTEN CONSENT FROM
CARMI design group inc.
Copyright 2023 ©
PROJECT #
ISSUEDNO. DATE
A u to d e s k D o c s /2
.1
C
D G
B
S P
S D
IS
C
O V
E R
Y H
V A
C R
E P
L A
C E
M E
N T
/2 .1
C D
G B
S P
S D
IS
C
O V
E R
Y H
V A
C M
E P
.r v t
/3
/2
:4
:0
P M
DISCOVERY
ACADEMY HVAC
REPLACEMENT
DECEMBER 1, 2023
BERRIEN SPRINGS
PUBLIC SCHOOLS
1 Sylvester Ave, Berrien Springs, MI 49103
23.112
MECHANICAL
SCHEDULES &
DETAILS
M701
VENTILATION ESTIMATE
SERVED BY NAME NUMBER SPACE TYPE
PEOPLE VENTILATION AREA VENTILATION
MINIMUM
OUTDOOR
AIRFLOW
(CFM)
AIR
DISTRIBUTION
EFFECTIVENESS
SYSTEM
VENTILATION
EFFICIENCY
ADJUSTED
OUTDOOR
AIRFLOW
(CFM)
ACTUAL
OUTDOOR AIR
(CFM)
OCCUPANCY UNIT
NUMBER OF
PEOPLE
OUTDOOR AIR PER
PERSON
(CFM/PERSON)
PERSON
OUTDOOR
AIRFLOW
(CFM)
OUTDOOR AIR PER
AREA (CFM/SF)
AREA (SF)
AREA
OUTDOOR
AIRFLOW
(CFM)
RTU-1 WRITING LAB 104 Classroom/Lecture/Training Number of people 13 10 130 0.12 546 66 196 0.8 1 244 245
RTU-1 CLASSROOM 103 Classroom/Lecture/Training Number of people 20 10 200 0.12 546 66 266 0.8 1 332 335
RTU-1: 2 461 576
RTU-2 MEN'S 107 Restrooms Number of people 0 0 0 0.00 56 0 0 0.8 1 0 0
RTU-2 WOMEN'S 109 Restrooms Number of people 0 0 0 0.00 56 0 0 0.8 1 0 0
RTU-2 CHASE 108 Electrical/Mechanical Number of people 0 0 0 0.06 21 1 1 0.8 1 2 5
RTU-2 CORRIDOR 106 Corridor/Transition Number of people 0 0 0 0.06 183 11 11 0.8 1 14 15
RTU-2 ROOM 117 Classroom/Lecture/Training Number of people 4 10 40 0.12 102 12 52 0.8 1 65 65
RTU-2 ROOM 116 Classroom/Lecture/Training Number of people 5 10 50 0.12 133 16 66 0.8 1 83 85
RTU-2 LAB AREA 105 S Classroom/Lecture/Training Number of people 17 10 170 0.12 1358 163 333 0.8 1 416 420
RTU-2: 7 463 579
RTU-3 ROOM 112 Restrooms Number of people 0 0 0 0.00 56 0 0 0.8 1 0 0
RTU-3 ROOM 113 Restrooms Number of people 0 0 0 0.00 82 0 0 0.8 1 0 0
RTU-3 ROOM 114 Classroom/Lecture/Training Number of people 0 10 0 0.12 15 2 2 0.8 1 2 5
RTU-3 VEST 101 Corridor/Transition Number of people 0 0 0 0.06 61 4 4 0.8 1 5 5
RTU-3 ROOM 111 Classroom/Lecture/Training Number of people 2 10 20 0.12 47 6 26 0.8 1 32 35
RTU-3 ROOM 115 Classroom/Lecture/Training Number of people 4 10 40 0.12 108 13 53 0.8 1 66 70
RTU-3 LAB AREA 105 N Classroom/Lecture/Training Number of people 18 10 180 0.12 1357 163 343 0.8 1 429 430
RTU-3: 7 427 534
ROOFTOP UNIT SUMMARY SCHEDULE
MARK MANUFACTURER MODEL
ARRANGEMENT/IN
STALLATION
GROSS TOTAL
CAPACITY
OUTDOOR AIR
INTAKE FLOW
SUPPLY
AIRFLOW
RATE
SUPPLY FAN SYSTEM SUPPLY FAN MOTOR COOLING DESIGN COOLING COIL HEATING DESIGN GAS HEAT SIZE
GAS BURNER
RATINGS
MINIMUM EFFICIENCY
PRODUCT
WEIGHT MCA MOCP
SYSTEM
VOLTAGE PHASETESP SIZE EDB EWB LDB LWB EAT LAT
1ST STAGE
INPUT BTU/H
2ND STAGE
INPUT BTU/H FUEL TYPE
RTU-1, RTU-2, & RTU-3 TRANE 4YCZ6060C1115A MOUNT ON CURB 60000.0 Btu/h 570 1950 CFM 1.00 in-wg 1 hp 84 69 56 °F 55 °F 35 °F 83 °F 92000.0 Btu/h 115000.0 Btu/h NG Cooling: 11.4 EER, 15.1 SEER 676.00 lbf 45 A 60 A 240 V 1
NOTES:
1. HINGED ACCESS PANELS WITH 2-IN MERV 13.
2. NON-FUSED DISCONNECT SWITCH & POWERED 15A CONVENIENCE OUTLET.
3. DOWNFLOW LOW LEAK ECONOMIZER DB WITH BR
4. PROVIDE WITH RETURN AIR DUCT DETECTORS.
5. PROVIDE WITH 36" INSULATED CURB FURNISHED BY UNIT MANUFACTURER.
6. PROVIDE WITH MICROMETL POWERED EXHAUST MODEL PCC-IMP2LCA-D-1VH ON RTU-1.
7. PROVIDE NEW PROGRAMMABLE THERMOSTAT. LOCATE IN SAME LOCATION AS EXISTING.
SCALE: NONEM701
1 GAS PIPING CONNECTION FOR ROOFTOP EQUIPMENT DETAIL
SCALE: NONEM701
2 HORIZONTAL DISCHARGE GROUND MOUNT UNIT
SCALE: NONEM701
3 CONCRETE PAD DETAIL
File details come from the government source that posted it. Updated .