Drawings 945CM3002 Columbaria Burial Expansion Phase 2 at Cheyenne NC.pdf
PDF 24 MB Posted
- Solicitation number
- 36C78624B0034
About this file
This document appears to be a set of drawings for the Columbaria Burial Expansion Phase 2 project at the Cheyenne National Cemetery, under Solicitation Number 36C78624B0034. The project is being conducted by the Department of Veterans Affairs National Cemetery Administration. The drawings provide detailed specifications for the expansion of the columbaria at the cemetery. Key details include the project number (945CM3002), the location (Cheyenne, WY), and the scope of work for the burial expansion project. This document does not contain information about response dates, award dates, pricing terms, set asides, or other salient contractual details, as it appears to be solely a set of technical drawings for the construction project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78624B0034 0002.docx | DOCX document | |
| 36C78624B0034 0001.docx | DOCX document | |
| FAR 52219 28 POST AWARD SMALL BUSINESS PROGRAM REREPRESENTATION SEP 2023.docx | DOCX document | |
| Limitations on Subcontracting Certificate.docx | DOCX document | |
| 36C78624B0034_1.docx | DOCX document | |
| Specifications 945CM3002 Columbaria Burial Expansion Phase 2 at Cheyenne NC.pdf | ||
| IFB Cost Estimate Worksheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION MAP
SCALE: NTS
SITE LOCATION AND ACCESS MAP
SCALE: NTS
PROJECT TEAM
FIRM PANEL
SCALE: NTS
CHEYENNE NC
COVER
G-001
N
SHEET INDEX
SHEET
NO.
DRAWING
NO. SHEET TITLE
1 G-001 COVERSHEET
DEPARTMENT OF VETERANS AFFAIRS
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL EXPANSION, PHASE 2
NCA PROJECT NO. 945CM3002
8611 HILDRETH RD, CHEYENNE, WY 82009
N
CODE OF CONDUCT
1. BURIAL CEREMONIES WILL BE SCHEDULED THROUGHOUT THE COURSE OF THIS PROJECT. COORDINATE
DAILY ACTIVITIES WITH THE CEMETERY DIRECTOR OR HIS APPROVED REPRESENTATIVE TO
ACCOMMODATE SCHEDULED INTERNMENTS. CONTRACTOR SHALL OBTAIN THE SCHEDULE DAILY FOR THREE DAYS IN ADVANCE FOR SERVICES PRIOR TO THE CLOSE OF BUSINESS EACH DAY. ALLOWABLE
WORK TO BE DETERMINED BY THE CEMETERY DIRECTOR.
2. BECAUSE OF THE SENSITIVE NATURE OF THE CEMETERY SITE, CONTRACTOR SHALL MAINTAIN EACH WORK AREA IN A CLEAN AND ORDERLY APPEARANCE. TRASH AND WASTE MATERIALS SHALL BE STORED IN APPROVED CONTAINERS AND ROUTINELY DISPOSED OFF-SITE. CLEANUP SHALL BE REQUIRED AT THE
END OF EACH DAY AND/OR MORE FREQUENTLY AS REQUIRED.
3. THE CONTRACTORS STAFF AND SUBCONTRACTORS STAFF SHALL NOT: DRESS IN SLEEVELESS SHIRTS OR SHORT PANTS, WEAR CLOTHING WITH INAPPROPRIATE LOGOS, PLAY MUSIC, TALK LOUD, PLACE
PERSONAL ITEMS ON HEADSTONES, LEAN AGAINST OR SIT ON HEADSTONES.
4. THE EFFECT OF WORK ON PUBLIC ACCESS SHALL BE MINIMAL AND SHALL BE COORDINATED WITH THE
CEMETERY DIRECTOR. ANY ALTERED PUBLIC TRAFFIC ROUTES SHALL BE WELL DEFINED WITH
PROFESSIONALLY MADE SIGNAGE AND/OR OTHER APPROVED CONVENTIONAL METHODS.
5. DO NOT WORK UPON NOR STORE ANY MATERIALS ON OCCUPIED COLUMBARIUM WALLS. ALL EFFORT
WILL BE MADE TO MAINTAIN DISTANCE FROM OCCUPIED COLUMBARIUM WALLS.
1. TOPOGRAPHIC INFORMATION PROVIDED BY SURVEY PERFORMED BY STEIL SURVEYING SERVICES. THE
GENERAL CONTRACTOR SHALL VERIFY ALL SURVEY INFORMATION.
2. THE BASIS OF BEARINGS FOR THE SURVEY IS THE WYOMING STATE PLANE COORDINATES, EAST ZONE, NAD83-2011, US SURVEY FEET. ELEVATIONS NAVD88.
3. CHEYENNE NATIONAL CEMETERY IS LOCATED IN ZONE X "AREA OF MINIMAL FLOODING" PER FEMA FLOOD
MAP 56021C1067F EFFECTIVE DATE JANUARY 17, 2007.
4. THE EXISTING UNDERGROUND UTILITIES SHOWN HEREON ARE BASED UPON AVAILABLE INFORMATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF ALL UTILITIES PRIOR TO BEGINNING ANY WORK. IF UTILITIES OTHER THAN THOSE SHOWN HEREIN ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY AND TAKE APPROPRIATE MEASURES TO
PROTECT THE LINE(S) AND ENSURE CONTINUED SERVICE. DAMAGE CAUSED TO EXISTING UTILITIES BY THE CONTRACTOR SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
THE CONTRACTOR SHALL VERIFY THE CONNECTION POINTS OF NEW UTILITIES TO EXISTING UTILITIES
PRIOR TO BEGINNING CONSTRUCTION.
5. THE CONTRACTOR SHALL INSTALL TREE PROTECTION BARRICADES PRIOR TO BEGINNING EARTHWORK
OPERATIONS.
6. THE CONTRACTOR SHALL NOTIFY THE COR IF UNSUITABLE MATERIAL IS DISCOVERED PRIOR TO
BEGINNING ANY REMOVAL OPERATION. (SEE SPECIFICATION SECTION 31.20.00)
7. THE CONTRACTOR SHALL STABILIZE ALL DISTURBED AREA WITH SOD OR MULCH, NOT SHOWN FOR ASPHALT OR CONCRETE, WITHIN LIMITS OF DEMOLITION AND PROPOSED WORK. THIS INCLUDES
STAGING AREA AND LAYDOWN AREAS.
8. CONTRACTOR SHALL GRADE ALL DISTURBED AREAS TO DRAIN FOR POSITIVE FLOW PRIOR TO FINAL
APPROVAL.
9. THE DESIGN ADEQUACY AND SAFETY OF ALL BRACING, SHORING AND TEMPORARY SUPPORTS, ETC. IS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
10. IN PERFORMING CONSTRUCTION OBSERVATION VISITS TO THE JOB SITE, THE ENGINEER SHALL HAVE NEITHER CONTROL OVER NOR RESPONSIBILITY FOR THE CONTRACTOR'S MEANS, METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES IN PERFORMING THE WORK.
11. THE CONTRACTOR'S MEANS, METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES IN PERFORMING THE WORK IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR, WHO IS ALSO RESPONSIBLE FOR COMPLYING WITH ALL HEALTH AND SAFETY PRECAUTIONS AS REQUIRED BY ANY REGULATORY AGENCY.
12. THERE SHALL BE AT ALL TIMES, WHEN WORK IS BEING DONE, A COMPETENT PERSON WHO IS APPRISED OF THE CONDITION AND PROGRESS OF ALL AREAS OF WORK ON SITE. THIS COMPETENT PERSON SHALL BE ABLE TO SPEAK FOR AND ACT IN THE BEHALF OF THE CONTRACTOR. HE SHALL BE AWARE AND KNOWLEDGEABLE OF ALL THE SAFETY CONCERNS ON THE JOB SITE. HE SHALL BE EMPOWERED TO
IMMEDIATELY AND EFFECTIVELY MITIGATE THE ACTIONS OF ANY WORKMAN ON SITE.
13. CONTRACTOR SHALL PREPARE AND SUBMIT A WELDING PLAN TO THE COR PRIOR TO PERFORMING ANY FIELD WELDING SHOULD IT BE REQUIRED. FOLLOWING APPROVAL ALL WELDS SHALL BE PERFORMED IN
ACCORDANCE WITH THE APPROVED PLAN. WELDING PLAN SHALL LIST CERTIFIED WELDERS THE
CONTRACTOR INTENDS TO USE.
14. CONTRACTOR SHALL PREPARE AND SUBMIT A SWPPP PER SPECIFICATIONS.
GENERAL NOTES
ARCHITECT / ENGINEER
VALI COOPER INTERNATIONAL, LLC
DENVER, CO 80249
CONTACT: JORDAN VANDERMEER
JORDAN.VANDERMEER@VALIINT.COM
720-799-1035
SURVEYOR
STEIL SURVEYING SERVICES
CHEYENNE, WY 82001
CONTACT: JEFFREY JONES
JEFF@STEILSURVEY.COM
307-634-7273
VA COR
CONTACT: DIMASALANG JUNIO
DIMASALANG.JUNIO@VA.GOV
202.213.5171
LANDSCAPE ARCHITECT
PLAND COLLABORATIVE
ALBUQUERQUE, MN
CONTACT: BRIAN VERARDO
BVERARDO@PLANDCOLLAB.COM
505-268-2266
N
G-101
V-101
C-101
CONSTRUCTION ACCESS, STAGING & FENCING PLAN
CD101
OVERALL TOPOGRAPHICAL SURVEY
DEMOLITION PLAN
SITE PLAN
LI501
IRRIGATION PLAN
IRRIGATION DETAILS
HILDRETH RD
EROSION AND SEDIMENTATION CONTROL PLAN
A-101 A-102
COLUMBARIUM WALL PLANS AND ELEVATIONS
ALEXANDRIA NC
GC101
LP101 PLANTING PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
POLO RANCH RD
HOWARD LN R
O
U N
D T
O P
R D
H
IL
D R
ET
H
R D
CHEYENNE NC
CHEYENNE NC
C-503 DETAILS - GRAVESITE
JVSF
A-501 A-502
COMMITTAL SHELTER FLOOR PLANS SECTIONS AND DETAILS
COLUMBARIUM &SEAL WALL DETAILS
COLUMBARIUM DETAILS - 1
S-101 STRUCTURAL DETAILS
C-502 DETAILS - SITE
C-402
ENLARGED - GRADING & DRAINAGE PLAN
C-401
ENLARGED - SITE PLAN
LI101
INTERNMENT SUMMARY
SECTION # PPC IGC NICHE
Sec 1 4'x4' 338 Sec 2 4'x4' 300 Sec 3 4'x4' 290 Sec 6 3'x8' 612 Columbarium 640
TOTAL 612 928 640
C-403
ENLARGED - GRADING & DRAINAGE PLAN
C-102 HORIZONTAL CONTROL & FOUNDATION ELEVATION PLAN
C-501 DETAILS - SITE
E-401 ELECTRICAL SITE PLAN
LD101 LANDSCAPE DEMOLITION PLAN
C-404
ENLARGED - SITE PLAN
C-504 DETAILS - GRAVESITE
C-505 DETAILS - FLOWER WATER STATIONS
S-001 GENERAL NOTES, ABBREVIATIONS AND LEGENDS28
A-503
SIGN DETAILSA-504
COLUMBARIUM DETAILS - 2
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
02/27/2024
A-103 GRAVESITE NUMBERING PLAN
G-101
CONSTRUCTION ACCESS,
STAGING AND FENCING PLAN
0 0 0
ON SAFETY
ZERO
Department of Veterans Affairs
PAINTED BORDER
MEMBER BLACK ENAMEL
2" X 4" FRAME AND BRACES
IN SAME PLANE
METAL FACE
STRETCH METAL FACE
TIGHT, TURN OVER FRAME
AND SECURE WITH FLAT
HEAD DEFORMED NAILS
LETTERING TO BE
HELVETICA STYLE 5"
HIGH
METAL FACE WHITE
ENAMEL
LETTERING TO BE
HELVETICA STYLE 3"
HIGH TO BE CENTERED
HORIZONTALLY
2" X 4" FRAME AND
BRACE IN BACK
LETTERING TO BE
HELVETICA STYLE 2" HIGH
TO BE CENTERED
HORIZONTALLY
LETTERING TO BE
HELVETICA STYLE 1-1/2"
HIGH TO BE CENTERED
HORIZONTALLY
4" X 4" POSTS
PAINTED WHITE
BORDER MEMBER
PAINTED BLACK
BACKGROUND TO BE
PAINTED WHITE
LETTERING TO BE
HELVETICA STYLE 1"
HIGH TO BE CENTERED
HORIZONTALLY
LETTERING TO BE
HELVETICA STYLE 1-1/2"
HIGH TO BE CENTERED
HORIZONTALLY
SURROUNDING BORDER TO
BE BLUE
CENTER TO BE WHITE
8'-8"
6'-6"
6"
1-1/2" 3" 5" 2" 5" 5" 3" 2"
1-1/2"
4'-0" MIN.
3"
6"
9"
6"
3" 2" 3"
6"
ALL LETTERING TO BE
PAINTED BLACK WITH
EXCEPTION OF PROJECT
TITLE WHICH IS TO BE BLUE
NOTE:
ANY SEAM IN METAL TO BE
FLAT SEAM - SEAMS TO BE
HORIZONTAL AND OCCUR
BETWEEN LINES OF
LETTERING.
SECTION ON CENTER
4'-0"
BRACING SEE
CONSTRUCTION SIGN
SECTION DETAIL
C7/A-509
3'-0"
VARIES
3'-0"
BLUE
BLUE OUTLINE WITH
WHITE INTERIOR
BLUE
WHITE
RED
RED
2"
2"
PROVIDE (3) SETS OF
REMOVABLE NUMERALS
PAINTED ON 1/8" TEMPERED
HARDBOARD
2"
1-3/4"
2"
WOOD STRIPS
BRACING
4" X 4" POST IF SIGN IS
INSTALLED ON GRADE
FIN. GRADE
SCALE: NTS
SAFETY SIGNC8
SCALE: NTS
PROJECT SIGNF6
VARIES;
AVERAGE 3'-0"
LEGEND AND SYMBOLS
CONSTRUCTION STAGING AREA
CONSTRUCTION FENCE
ACCESS / HAUL ROUTE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
CONCRETE WASHOUT AREA
CONSTRUCTION ENTRANCE
KEYED NOTES
1. SAFETY SIGN, SEE DETAIL C8 THIS SHEET.
2. PROJECT SIGN, SEE DETAIL F6 THIS SHEET.
ACCESS/HAUL
ROUTE
REMOVE AND REPLACE EXISTING
FENCE PANELS AS NECESSARY FOR
CEMETERY ACCESS. INSTALL
LOCKABLE ACCESS GATE
CONSTRUCTION
STAGING AREA
1 2
CONTRACTOR SHALL PLACE PORTABLE
RESTROOMS INSIDE OF STAGING AREA.
CONTRACTOR SHALL RESTORE ALL
DISTURBED AREAS TO ORIGINAL
NATIVE GRASSES AFTER THE
COMPLETION OF THE PROJECT.
TEMPORARY SHELTER:
1. CONTRACTOR SHALL PROVIDE A TEMPORARY SHELTER
DURING ACTIVITIES THAT PREVENT SERVICES FROM
BEING PERFORMED AT THE EXISTING SHELTER.
1.1. SHELTER SHALL BE A MINIMUM OF 14'X14'.
1.2. CONTRACTOR SHALL BE RESPONSIBLE FOR
ADEQUATELY SECURING SHELTER.
2. CONTRACTOR SHALL COORDINATE THE TEMPORARY
SHELTER LOCATION WITH CEMETERY STAFF.
3. CONTRACTOR SHALL PROVIDE A FUNCTIONING SOUND
SYSTEM FOR THE TEMPORARY SHELTER CONSISTING OF
THE FOLLOWING:
3.1. 4-OHM WEATHER RESISTANT SPEAKERS (OWI TRP470
OR APPROVED EQUAL).
3.2. TAPS PLAYER (MACKENZIE LABORATORIES MINIMAC 2
OR APPROVED EQUAL)
3.3. POWER TO ALLOW OPERATION FOR AT LEAST TWO
HOURS .
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
02/26/2024
ACCESS GATES:
ACCESS TO THE STAGING AREA IS PROVIDED THROUGH
AGRICULTURAL RESEARCH PROPERTY (ARS). THE
CONTRACTOR SHALL PROVIDE THE FOLLOWING TO PREVENT
PUBLIC ACCESS ON ARS PROPERTY DURING CONSTRUCTION.
1. DOUBLE PADLOCK ON THE EXISTING DOUBLE GATE
1.1. ONE LOCK WILL BE FOR ARS USE AND THE OTHER
FOR CONTRACTOR USE
1.2. ACCESS GATE SHALL BE LOCKED AT ALL TIMES
THAT THE CONTRACTOR IS NOT PRESENT.
2. GATE SHALL BE CLOSED WHEN APPROPRIATE DURING
CONSTRUCTION HOURS TO DETER PUBLIC ACCESS.
3. INSTALL TWO HIGH VISIBILITY CONSTRUCTION SIGNS
(30"X30" MIN) STATING "CONSTRUCTION AREA - NO
ENTRY" ON BOTH SIDES OF THE ROADWAY.
4. SHOULD THE PUBLIC ACCESS THE ARS OWNED
PROPERTY, THE CONTRACTOR SHALL INSTALL A
SECONDARY DOUBLE GATE AND FENCING BEYOND THE
CONSTRUCTION ACCESS POINT TO PREVENT PUBLIC
ACCESS AT NO ADDITIONAL COST TO THE
GOVERNMENT.
CONSTRUCTION
ENTRANCE
ACCESS GATES, SEE NOTES THIS SHEET
30" X 30" HIGH VISIBILITY "CONSTRUCTION
AREA - NO ACCESS" SIGNS
CONSTRUCTION FENCING
PER SPECIFICATIONS
-2 .0
-2 .1
-2 .3
-2 .0
-2 .0
%-2 .0
-2 .0
-2
.3
-2 .2
-2 .0
INV:6231.10
INV:6231.23
INV: MATCH EX. INV: MATCH EX. INV: MATCH EX.
EROSION AND SEDIMENTATION
CONTROL PLANS
GC101
0 20 40
1 INCH = 20 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
KEYED NOTES
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
DEMOLITION LEGEND AND SYMBOLS
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
SILT FENCING
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
CONSTRUCTION FENCING
1. SILT FENCE, SEE DETAIL THIS SHEET.
2. CONSTRUCTION FENCING WITH PRIVACY FABRIC PER
SPECIFICATIONS.
3. CONSTRUCTION ENTRANCE, SEE DETAIL THIS SHEET.
4. CONCRETE WASHOUT AREA, SEE DETAIL THIS SHEET.
4' M
IN
2.
5'
M
IN
1.
5'
M
IN
6' MAX. O.C.
2"
6"
EXISTING GROUND
2"X4" WOOD STUDS
FILTER FABRIC SILT FENCE
(TYPE A)
8oz NON WOVEN
HARD SURFACE
PUBLIC ROAD
COARSE AGGREGATE
N.S.A. R-2 (1.5" - 3.5")
CONSTRUCTION EXIT
GEOTEXTILE UNDERLINER
CONCRETE
WASHOUT
LETTERS A MINIMUM OF 5" IN
HEIGHT
CONCRETE WASHOUT SIGN DETAIL
STAKE (TYP.)
STRAW BALE (TYP.)
10' MIN.
VA
R
IE
S
' M
IN
PLAN
TYPE "ABOVE GRADE"
WITH STRAW BALES
BINDING WIRE
STRAW BALE
STAPLES 18" DIA. 4" STAPLE
(2 PER BALE)
NATIVE MATERIAL
(OPTIONAL)
WOOD OR
METAL STAKES
(2 PER BALE)
SECTION B-B
NOTES:
1. ACTUAL LAYOUT DETERMINED IN FIELD.
2. INSTALL CONCRETE WASHOUT SIGN (24"X24", MINIMUM) WITHIN 30' OF THE
TEMPORARY CONCRETE WASHOUT FACILITY.
3. TEMPORARY WASHOUT AREA MUST BE AT LEAST 50' FROM A STORM
DRAIN, CREEK BANK OR PERIMETER CONTROL.
4. CLEAN OUT CONCRETE WASHOUT AREA WHEN 50% FULL.
5. THE KEY TO FUNCTIONAL CONCRETE WASHOUTS IS WEEKLY
INSPECTIONS, ROUTINE MAINTENANCE, AND REGULAR CLEAN OUT.
6. SILT FENCE SHALL BE INSTALLED AROUND
PERIMETER OF CONCRETE WASHOUT AREA
EXCEPT FOR THE SIDE UTILIZED FOR ACCESSING
THE WASHOUT.
7. A ROCK CONSTRUCTION ENTRANCE MAY BE
NECESSARY ALONG ONE SIDE OF THE WASHOUT
TO PROVIDE VEHICLE ACCESS.
IMPERVIOUS LINER
5' RADIUS
CONSTRUCTION ENTRANCE
CONCRETE WASHOUT AREA
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
02/27/2024
FM
UD UD UD UD UD
UDUDUDUDUD
UD
CO
CO
CO
OVERALL TOPOGRAPHICAL
SURVEY
V-101
0 20 40
1 INCH = 20 FEET
JVSF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration Design and
Construction Service U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCIProject Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
CERTIFICATE OF SURVEYOR
FENCING
COMMITTAL SHELTER
COLUMARIUM WALL
IGC SECTION
FENCING
PPC SECTION
GRAVEL ROAD
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
UD UD UD UD UD
UDUDUDUDUD
UD
CO
CO
CO
DEMOLITION PLAN
CD101
0 20 40
1 INCH = 20 FEET
KEYED NOTES
DEMO EXISTING SIDEWALK
1. REMOVE EXISTING SIDEWALK.
2. REMOVE EXISTING CURB & GUTTER.
3. REMOVE EXISTING MONUMENT CONCRETE BASE AND
FOUNDATION. CONTRACTOR SHALL STORE MONUMENT
DURING REPAIR.
4. RELOCATE EXISTING PUMP CONTROL PANEL, SEE SHEET
C-101.
5. REMOVE & REPLACE EXISTING WET WELL LID.
6. RELOCATE EXISTING GATE SENSOR AS NEEDED FOR
SIDEWALK INSTALLATION.
7. REMOVE EXISTING STOP SIGN.
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
DEMO CURB AND GUTTER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
SAW CUT AT EXISTING
EXPANSION JOINT
SAW CUT AT EXISTING
EXPANSION JOINT
SAW CUT AT EXISTING
EXPANSION JOINT
SAW CUT AT EXISTING
EXPANSION JOINT
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
5.73'
SITE PLAN
C-101
0 20 40
1 INCH = 20 FEET
SIDEWALK
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
CURB AND GUTTER
JVSF
ADA RAMP W/ DETECTABLE
WARNING
ELECTRICAL PULL BOX
2 2 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration Design and
Construction Service U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCIProject Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
SEE SHEET C-401, C-403,
ARCHITECTURAL SHEETS AND
LANDSCAPING SHEETS
SEE SHEET C-402, C-404 AND ARCHITECTURAL SHEETS
75' SETBACK
EXPANSION JOINT
CONTROL JOINT
SECTION 10
EXISTING IGC
SECTION 9
EXISTING PPC
SE
C
TI
O
N
SE
C
TI
O
N
SECTION 6
3x8 PPC
612 BURIALS
SECTION 1
4X4 IGC
338 BURIALS
SEE SHEET C-402 & C-404SEE SHEET C-402 & C-404
SEE SHEET C-402, C-404 AND ARCHITECTURAL SHEETS
SECTION 2
4X4 IGC
300 BURIALS
SECTION 3
4X4 IGC
300 BURIALS
TWO COLUMBARIUM WALLS
320 NICHES EACH
KEYED NOTES
1. RELOCATED CONTROL PANEL, SEE ELECTRICAL PLANS.
2. IGC SECTION, SEE ARCHITECTURAL PLANS.
3. NO PARKING SIGN, SEE ARCHITECTURAL PLANS.
4. DO NOT ENTER SIGN, SEE ARCHITECTURAL PLANS.
5. STOP SIGN, SEE ARCHITECTURAL PLANS.
ALL WORK SHOWN IN THIS AREA IS
TO BE COMPLETED AS A PART OF A
SEPARATE CONTRACT
SEE ARCHITECTURAL SHEETS
AND LANDSCAPING SHEETS
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
UD UD UD UD UD
UDUDUDUDUD
UD
CO
CO
CO
101 102
103 104 105 106
113 114
316 317
320 321
323 324 325
501 502 503 504 505 506
507 508
CONTROL POINTS
POINT
NORTHING
247,479.86
247,515.86
247,518.94
247,554.94
247,557.94
247,593.94
247,479.32
247,515.30
247,518.32
247,554.32
EASTING
728,424.89
728,424.58
728,432.54
728,432.23
728,432.25
728,431.94
728,360.88
728,360.57
728,360.54
728,360.23
CONTROL POINTS
POINT
NORTHING
247,557.32
247,593.31
247,478.69
247,514.68
247,517.76
247,553.76
247,556.76
247,592.76
247,489.17
247,489.55
EASTING
728,360.25
728,359.94
728,288.88
728,288.57
728,296.54
728,296.23
728,296.26
728,295.94
728,479.62
728,523.61
CONTROL POINTS
POINT
NORTHING
247,561.18
247,561.56
247,631.18
247,631.57
247,693.16
247,693.55
247,755.17
247,755.56
247,817.16
247,817.54
EASTING
728,479.00
728,523.00
728,478.16
728,522.39
728,477.62
728,521.84
728,477.10
728,521.32
728,476.55
728,520.77
CONTROL POINTS
POINT
NORTHING
247,873.17
247,873.55
247,478.43
247,517.43
247,556.43
247,595.43
247,477.88
247,516.83
247,555.87
247,594.87
EASTING
728,476.31
728,520.30
728,432.90
728,432.56
728,432.21
728,431.94
728,368.91
728,368.57
728,368.23
728,367.94
CONTROL POINTS
POINT
NORTHING
247,477.32
247,516.32
247,555.32
247,594.32
247,489.19
247,629.18
247,633.18
247,753.18
247,757.17
247,873.17
EASTING
728,304.91
728,304.57
728,304.23
728,303.94
728,476.10
728,473.90
728,473.87
728,472.83
728,472.80
728,471.81
CONTROL POINTS
POINT
NORTHING
247,476.98
247,593.98
EASTING
728,439.39
728,438.46
HORIZONTAL CONTROL &
FOUNDATION ELEVATION
PLAN
C-102
0 10 20
1 INCH = 10 FEET
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
GRID MONUMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
TOP OF FOUNDATION: 6246.49TOP OF FOUNDATION: 6246.12
TOP OF FOUNDATION
SCALE: NTS
FOUNDATION ELEVATION LOCATIONF9
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
SECTION MARKER
FM
FM
UD UD UD UD UD UD UD UD UD UD UD
UDUDUDUDUDUDUDUD
UDUD
CO
CO
ENLARGED - SITE PLAN
C-401
0 10 20 30
SIDEWALK
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
CURB AND GUTTER
JVSF
ADA RAMP W/ DETECTABLE
WARNING
EXPANSION JOINT
CONTROL JOINT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
1 INCH = 10 FEET
KEYED NOTES
1. CONCRETE SIDEWALK, SEE DETAIL B6/C-501.
2. EXPANSION JOINT, SEE DETAIL B2/C-501.
3. CONTROL JOINT, SEE DETAIL C2/C-501.
4. FLOWER WATER STATION WITH FLORAL VASE AND TRASH
RECEPTACLE, SEE SHEET C-505.
5. NEW WET WELL LID, SEE WET WELL LID NOTES BELOW.
6. ELECTRICAL PULL BOX, SEE E-401.
7. PPC SECTION, SEE ARCHITECTURAL PLANS.
WET WELL LID NOTES:
1. CONTRACTOR SHALL REMOVE AND REPLACE THE
EXISTING FIBERGLASS LID WITH THE FOLLOWING:
1.1. LID SHALL BE CONSTRUCTED OF ALUMINUM OR
STAINLESS STEEL.
1.2. LID SHALL HAVE A MINIMUM LOAD RATING OF 300 PSF.
1.3. LID SHALL BE INSTALLED ON THE EXISTING 24"
DIAMETER WET WELL.
1.4. COVER SHALL BE LOCKABLE. (FLUSH MOUNTED)
1.5. HINGES SHALL BE STAINLESS STEEL.
1.6. LID SHALL BE POWDER COATED. CONTRACTOR
SHALL SUBMIT COLOR SAMPLE TO NCA FOR WRITTEN
APPROVAL PRIOR TO PAINTING.
1.7. ADJACENT GRADE SHALL BE FLUSH WITH LID.
5.00'MATCH EXISTING
RADIUS
2 TYP. 3 TYP.
5.00' TYP.
ALL JOINTS
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
CO
5.73'
ENLARGED - SITE PLAN
C-402
0 5 10
1 INCH = 5 FEET
KEYED NOTES
SIDEWALK
1. CONCRETE SIDEWALK, SEE DETAIL B6/C-501.
2. CURB & GUTTER, SEE DETAIL C9/C-501.
3. ADA RAMP, SEE DETAIL B9/C-501.
4. EXPANSION JOINT, SEE DETAIL B2/C-501.
5. CONTROL JOINT, SEE DETAIL C2/C-501.
6. VALLEY GUTTER, SEE DETAIL F9/C-501.
7. REPLACE CONCRETE AT THE BASE OF THE BIVOUAC OF
THE DEAD PLAQUE, SEE DETAIL F4/C-501.
8. REPLACE DAMAGED RECEPTACLES, SEE GENERAL NOTES
THIS SHEET.
9. CONSTRUCTION JOINT, SEE DETAIL C6/C-501.
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
CURB AND GUTTER
JVSF
ADA RAMP W/ DETECTABLE
WARNING
8.00'
3 @ E.Q. SPACING 3 @ E.Q. SPACING 3 @ E.Q. SPACING 3 @ E.Q. SPACING
2.00' TYP. 2.00'
5.00'
6.00'
TRANSITIONOVER 5.00'
ARC LENGTH 38.00'
5.00'
4 TYP.
4 TYP. 4 TYP.4 TYP. 5 TYP.5 TYP.
5 TYP.
5 TYP.
EXPANSION JOINT
CONTROL JOINT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
SCALE: 1" = 5'
NORTH ADA RAMP SITE PLANC6
SCALE: 1" = 5'
SOUTH ADA RAMP SITE PLANB2
SCALE: 1" = 5'
COMMITTAL SHELTER SITE PLAND2
SCALE: 1" = 5'
COLUMBARIUM SITE PLANF5
9 TYP.
4 TYP.
CONTRACTOR SHALL MATCH
EXISTING JOINTING SCHEME
GENERAL NOTES:
1. CONTRACTOR SHALL REPLACE THE DAMAGED
RECEPTACLES (2) AND RE-SECURE THEM AS REQUIRED
ON THE BACKSIDE OF THE COMMITTAL SHELTER.
CONSTRUCTION JOINT
5 TYP.
5 TYP.
3.33 TYP.
5.00' TYP.
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
RENG INE ER
02/27/2024
±26.0'
±4.5'
±4.5'
±26.0'
32.65' TYP.
146.27'
5.90'
1.95' 1.95' 3.95'
FM
FM
UD UD UD UD UD UD UD UD UD UD UD
UDUDUDUDUDUDUDUD
UDUD
CO
CO
-2 .0
-2 .1
-2 .3
-2 .0
-2 .0
-2 .0
-2 .0
-2 .3
-2 .2
-2 .0
FG:6245.03
EG:6243.75
FG:6244.92
EG:6242.62
FG:6245.00
EG:6242.44
FG:6245.00
EG:6242.02
FG:6242.20
EG:6241.86
FG:6242.28
EG:6242.08
FG:6242.10
EG:6242.90
FG:6242.41
EG:6242.41
FG:6244.93
EG:6242.86
FG:6242.16
EG:6242.25
INV:6231.10
INV:6231.23
INV: MATCH EX. INV: MATCH EX. INV: MATCH EX.
ENLARGED - GRADING &
DRAINAGE PLAN
C-403
0 20 40
1 INCH = 60 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
KEYED NOTES
4" PERFORATED
UNDERDDRAIN
1. 4" PERFORATED UNDERDRAIN, SEE DETAIL SHEET C-503.
2. CLEANOUT, SEE DETAIL A2/C-503.
3. PPC INFILTRATION TRENCH, SEE DETAIL D6/C-502
4. CONNECT TO EXISTING UNDERDRAIN.
5. CONNECT TO EXISTING WET WELL.
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
CLEANOUT
2 2
4 4
INFILTRATION TRENCH
-2.00%
-2.00%
FG:XXXX
EG:XXXX
FINISHED GRADE
EXISTING GRADE
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
FG:6245.28
FG:6245.62 FG:6245.63
FG:6245.46 FG:6245.47
FG:6245.63 FG:6245.66
FG:6245.79 FG:6245.82 FG:6246.00 FG:6245.98
FG:6245.82 FG:6245.83
FG:6246.16
FG:6246.00
FG:6245.28
FG:6245.45
FG:6246.02
CO
ENLARGED - GRADING &
DRAINAGE PLAN
C-404
0 5 10
1 INCH = 5 FEET
KEYED NOTES
1. TAPERED END SECTION, SEE DETAIL D2/C-502.
2. 4" PERFORATED PVC, SEE ARCHITECTURAL DETAILS.
3. GRAVEL STRIP CLEANOUT, SEE DETAIL B9/C-502.
4. TURF CLEANOUT, SEE DETAIL F5/C-503.
5. 6" PERFORATED PVC INFILTRATION TRENCH, SEE DETAIL
B2/C-502.
6. 4" PVC DOWNSPOUT EXTENSION AT 2% MINIMUM SLOPE,
SEE DETAIL F2/C-502.
7. 6" POP-UP EMITTER, SEE DETAIL D9/C-502.
SEE SURVEY SHEETS FOR EXISTING CONDITIONS LEGEND
LEGEND AND SYMBOLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
SCALE: 1" = 5'
NORTH ADA RAMP GRADING PLANC6
SCALE: 1" = 5'
SOUTH ADA RAMP GRADING PLANB2
SCALE: 1" = 5'
COMMITTAL SHELTER DRAINAGE PLAND2
SCALE: 1" = 5'
COLUMBARIUM GRADING AND DRAINAGE PLANF5
MATCH EXISTINGMATCH EXISTING
MATCH EXISTINGMATCH EXISTING
TRANSITION TO VALLEY GUTTER
-8.33%
MATCH EXISTING
TRANSITION TO VALLEY GUTTER
MATCH EXISTING
-2.00%
-8.33%
-2 .0
0%
MATCH EXISTING
-2.00%
-2.00%
-2.00%
-0.50% -0.50% -0.50%
2 2
1 1 33
FG:XXXX FINISHED GRADE
MATCH EXISTING
GRADES AND
SLOPES
M
ATC
H
EX.
MATCH EX.
25'
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
DETAILS - SITE
C-501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
1/4" RADIUS
AT EDGES
4" MIN.
5"
4"
SCALE: NTS
CONCRETE SIDEWALKB6
SCARIFY, MOISTURE
CONDITION AND RECOMPACT
12" OF SUBGRADE BENEATH
ALL NEW FLATWORK.
4" COMPACTED
AGGREGATE BASE
4200 PSI CONCRETE W/
FIBER REINFORCEMENT PER
SPECIFICATIONS
JVSF
MATCH EXISTING FINISH.
EXPANSION JOINT FILLER
WITH SEALANT
GENERAL NOTES:
1. JOINT SHALL TOOLED.
2. MAXIMUM JOINT SPACING SHALL BE 10' O.C.
3. JOINT DEPTH TO BE 1/4 OF PAVEMENT
THICKNESS
SCALE: NTS
CONTROL JOINT (TYP.)C2
SCALE: NTS
EXPANSION JOINT (TYP.)B2
PAINT AND GREASE
END OF DOWELS
SMOOTH DOWEL 58" DIA.
@ 18" O.C. 5" 5"
TOOLED JOINT WITH 14" R
GENERAL NOTES:
1. INSTALL MASON SAND ON TOP OF SEALANT BEFORE
SEALANT CURES.
2. ALL EXPANSION JOINTS ARE TO HAVE A 1/4" TOOLED
RADIUS.
3. CONTRACTOR SHALL USE EXPANSION JOINT TO TIE
INTO ALL EXISTING WORK WHERE SHOWN ON PLANS.
SEALANT IS TO BE ROUNDED AS SHOWN
CONCRETE
PAVEMENT
1/4" R
SCALE: NTS
CONSTRUCTION JOINT (TYP.)C6
PAINT AND GREASE
END OF DOWELS
SMOOTH
DOWEL 58" DIA.
5" 5"
GENERAL NOTES:
1. ALL CONSTRUCTION
JOINTS ARE TO HAVE A
1/4" TOOLED RADIUS.
1/4" R
8.
M
AX
2" 71
2"
MATCH EXISTING
6"
2"
1/4" R 1/4" R
24"
4"
LANDSCAPE/PAVEMENT
PER PLAN
SCALE: NTS
MOUNTABLE CURB AND GUTTERC9
GENERAL NOTES:
1. CONTRACTOR SHALL USE
EXPANSION JOINTS WHEN JOINING
TO ALL EXISTING WORK.
2. CONTROL JOINTS INTERVALS SHALL
MATCH EXISTING ONSITE
CONDITIONS.
5'
2'
5'
24" MOUNTABLE CURB
SEE PLANS
TRUNCATED DOMES SHALL HAVE
INTEGRATED COLOR (YELLOW) BRICK
PAVERS AND SHALL BE WET OR MORTAR
SET PER MANUFACTURER WRITTEN
INSTRUCTIONS
SCALE: NTS
ADA RAMPB9
2.0%
THE PERIMETER
JOINT IS TO BE AN
EXPANSION JOINT
CONCRETE PER
SPECIFICATION 32 05 23
SCALE: NTS
BIVOUAC OF THE DEAD (BOD) PLAQUEF4
EXISTING GRANITE PEDESTAL
ISOMETRIC
EXISTING GRANITE
PEDESTAL
EXPANSION JOINT W/
DOWELS PER DETAIL B2
THIS SHEET.
#4 REBAR AT 12" C.C.
FINISH GRADE
Slope
ELEVATION
FOOTING. CONTRACTOR TO
MATCH EXISTING DIMENSIONS
VINYL PIN, TYPICAL
(4 TOTAL)
DRAINAGE FILL, 12"
DEPTH
1'-6"
7" 2'
12"
2'-8"
CONCRETE FOOTING
Slope
VALLEY GUTTER
2" 71
2"
2"
1/4" R 1/4" R
24"
4"
LANDSCAPE/PAVEMENT
PER PLAN
SCALE: NTS
VALLEY GUTTERF9
-2.0%
CONCRETE PER
SPECIFICATION 32 05 23
TRANSITION TO
VALLEY GUTTER
-2.0%
#4 BAR CONTINUOUS
#4 BAR CONTINUOUS
ISOMETRIC VIEW
EXPANSION JOINT
SHALL BE PLACED
AROUND THE
PERIMETER OF THE
RAMP
8.3 3%
MAX.
4" COMPACTED
AGGREGATE BASE
4" COMPACTED
AGGREGATE BASE
GENERAL NOTES:
1. CONTRACTOR SHALL USE
EXPANSION JOINTS OR
CONSTRUCTION JOINTS WHEN
JOINING TO ALL EXISTING WORK.
2. ALL REPLACEMENT FLATWORK
SHALL HAVE ITS UNDISTURBED
SUBGRADE COMPACTED PER
SPECIFICATIONS. SCARIFICATION IS
NOT REQUIRED.
GENERAL NOTES:
1. CONTRACTOR SHALL USE
EXPANSION JOINTS WHEN JOINING
TO ALL EXISTING WORK.
2. CONTROL JOINTS INTERVALS SHALL
MATCH EXISTING ONSITE
CONDITIONS.
SCARIFY, MOISTURE
CONDITION AND RECOMPACT
12" OF SUBGRADE BENEATH
PLAQUE.
3'-8"
2' -8
2'-7"
APPROXIMATE
FOOTING
DIMENSIONS
PLAN VIEW
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
DETAILS - SITE
C-502
SCALE: NTS
GUTTER INFILTRATION TRENCHB2
FINISH GRADE
UNDISTURBED SOIL
6" PVC PERFORATED UNDERDRAIN
PIPE @0.5% SLOPE, MIN. 36" MIN.
24"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer JVSF
CLEANOUT PLUG
(MALE PIPE THREAD) CLEANOUT ADAPTOR (FEMALE
PIPE THREAD)DECORATIVE GRAVEL
#57 STONE
INSTALL PLASTIC PLUG
W/ 'O' RING FOR END OF LINE
SECTION
4"Ø PERFORATED PVC
PVC WYE
FILTER FABRIC
SCALE: NTS
GRAVEL STRIP CLEANOUTB9
NTS
STORM SEWER BEDDINGB5
STORM SEWER
PIPE
NOTES:
1. ALL TRENCH EXCAVATION SHALL
BE IN ACCORDANCE WITH OSHA
REQUIREMENTS.
COMPACTED BACKFILL,
SEE SPECIFICATION 31 20
00 FOR COMPACTION
REQUIREMENTS
FINISHED SURFACE VARIES, SEE PLANS
COMPACTED BEDDING PER
SPECIFICATION 31 20 00
EQ
EQ
COMPACTED BACKFILL,
SEE SPECIFICATION 31 20
00 FOR COMPACTION
REQUIREMENTS
SCALE: NTS
PPC INFILTRATION TRENCHD6
BACKSLOPE TO
CONFORM TO
O.S.H.A. REGULATIONS
FINISH GRADE
UNDISTURBED SOIL
COMPACTED ON-SITE SOIL
VERTICAL TRENCH WALLS
W/ SHORING TO CONFORM
TO O.S.H.A. REGULATIONS
WARNING TAPE
2" ABOVE FABRIC
4" PVC OR HDPE PERFORATED
UNDERDRAIN PIPE @0.5% SLOPE, MIN.
2"
24" MIN.
2'
90° PVC ELBOW
6" PERFORATED PVC
6" NDS POLYOLEFIN POP-UP DRAINGE
EMITTER WITH U.V. INHIBITOR, OR
APPROVED EQUAL.
SCALE: NTS
POP-UP DRAIN EMITTERD9
AASHTO #57 STONE WRAPPED
IN 8 OZ/SY NON WOVEN
GEOTEXTILE FABRIC
AASHTO #57 STONE WRAPPED
IN 8 OZ/SY NON WOVEN
GEOTEXTILE FABRIC
18"
5"4" PVC
SLOPED TO MATCH
SURROUNDING GRADE
SCALE: NTS
TAPERED END SECTIOND2
9" MIN.
9" MIN.
REMOVABLE RODENT GUARD
WARNING TAPE 2"
ABOVE FABRIC
4200 PSI CONCRETE PER
SPECIFICATIONS
TOP SOIL PER SPECIFICATIONS
TOP SOIL & TURF SOD PER SPECIFICATIONS
TOP SOIL AND TURF SOD PER SPECIFICATIONS
NTS
DOWNSPOUT EXTENSIONF2
4" SOLID PVC
NOTES:
1. ALL TRENCH EXCAVATION SHALL
BE IN ACCORDANCE WITH OSHA
REQUIREMENTS.
2. WHERE DAYLIGHTING IS
REQUIRED, CONTRACTOR SHALL
START 4" PVC WITH 12" OF COVER
AND DAYLIGHT ACCORDINGLY.
COMPACTED BACKFILL,
SEE SPECIFICATION 31 20
00 FOR COMPACTION
REQUIREMENTS
FINISHED SURFACE VARIES, SEE PLANS
COMPACTED BEDDING PER
SPECIFICATION 31 20 00
12" MIN.
COMPACTED BACKFILL,
SEE SPECIFICATION 31 20
00 FOR COMPACTION
REQUIREMENTS
PVC RISER AS NEEDED
#4 REBAR
#4 REBAR
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
SFTM
DETAILS - GRAVESITES
C-503
PLUG END OF PIPE
UNLESS CONTINUOUS
WYE BRANCH
45° ELBOW
4" SOLID PVC.
4 INCHES OF COMPACTED
DRAINAGE FILL -
SPEC SECTION 312000
6" MIN. 4"
M
IN
CAST IRON CLEANOUT
FRAME & COVER, FLUSH
WITH FINISHED GRADE (NO
VERBIAGE ON CAP)
RECESSED 4" PVC CLEANOUT WITH PLUG
6" PVC ENCASEMENT PIPE 6"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
TOPSOIL PER
SPECIFICATIONS
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
PRE-CAST CONC.
POST:
7 1/2"x7 1/2" x 3'-0" W/
1" CHAMFER AT ALL
EXPOSED CORNERS
AND 3/8" RECESS
AREA (ALL 4 SIDES):
CAST W/ (3) #3 REBAR
EQUALLY SPACED,
MEDIUM SAND BLAST
FINISH.
6"
8 1/4"
1' -6
8" 7"
3" 1"
7 1/2"
3/
4"
3 3/4"
FINISHED GRADE
PRE-CAST CONCRETE
COLLAR, SEE PLAN
VIEW
1/8" ALUMINUM SIGN
PANEL, ALL 4 SIDES OF
POST. SEE SIGN PANEL
PLAN/ SECTION.
R7/8"
SCALE: 1 1/2" = 1'-0"
SIGN PANEL ENLARGEMENT
SCALE: 3/4" = 1'-0"
TOP COLLAR PLAN/ SECTION
2' -0
2'-0"
1/
2"
8 1/2"
POST
NO SEALANT
BETWEEN POST
AND COLLAR.
TO FLOAT ON
GRAVEL BASE
3"
1" 1/2" CHAMFER 4
SIDES, TOP ONLY
1/4" Ø HOLES. SECURE W/ (2)
3/8" Ø x 3" S.S. BOLT AND
EXPANSION SHIELD.
1/
4"
1/8" THICK ALUMINUM SIGN
PANEL. PANEL SHALL BE
COLORED VA STANDARD
BRONZE WITH VA STANDARD
WHITE
SECTION
PLAN
GENERAL NOTES:
1. LOCATE SECTION MARKERS AT LOCATION
SHOWN ON PLAN, PARALLEL AND
PERPENDICULAR TO HEADSTONE DIRECTION.
2. SHOULD THE SECTION MARKER NOT MATCH
THE EXISTING ON-SITE SECTION MARKERS,
THE CONTRACTOR SHALL MATCH THE
EXISTING.
3' -0
APPROVE TEXT FOR SECTIONS WITH
CEMETERY AND COTR. PRIOR TO
ORDERING THIS PRODUCT.
2' -6
6" DEPTH AGGREGATE
DRAINAGE FILL
GRAVESITE GRID MONUMENT
1" MIN
MONUMENT MARKER
CONCRETE BASE
MONUMENT MARKER (PROTECT
VISIBLE SURFACES DURING
PLACEMENT INTO CONCRETE)
1'-0" LENGTH OF #6 REBAR FIRMLY
SECURED TO MONUMENT MARKERS;
SET INTO CONCRETE MONUMENT
BASE
SMOOTH-TROWEL FINISH TOP
SURFACE ENSURING POSITIVE
DRAINAGE
8" PVC PIPE FILLED WITH 3.500 PSI
CAST IN PLACE CONCRETE AT 28
DAYS
GAP AROUND PVC PIPE AND
SURROUNDING EARTH SHALL
BE FILLED WITH CONCRETE TO
WITHIN 4" OF FINISH GRADE
COMPACTED APPROVED FILL
OR NATIVE EARTH
ISOMETRIC VIEW
PLAN
3 1/4
NOTE:
ALL LAWNS AND IRRIGATION LINES
WITHIN THE BURIAL SECTIONS
SHALL BE INSTALLED AND
ACCEPTED PRIOR TO MONUMENT
BASE PLACEMENT. ALL LAWNS AND
IRRIGATION LINES DAMAGED
DURING INSTALLATION SHALL BE
REPAIRED AT CONTRACTOR'S
EXPENSE.
8" DIA.
SET FLUSH WITH FINISH GRADE
4' -0
CL
MONUMENT MARKER
Na t iona l Cemetery
Graves i t e Gr i d Monum en t
CROSS HAIRS MUST FALL
WITHIN 3/4" OF THE
CENTER OF THE MARKER
OR THE ENTIRE
MONUMENT MUST BE
MOVED
3 1/4" DIAMETER FORGED
ALUMINUM DOMED TOP
MONUMENT MARKER WITH
PLASTIC INSULATOR WITH
HEX SOCKET TO RECEIVE
REBAR
FIELD INCISED CROSS
HAIRS ON CAP; CROSS
HAIRS SHALL BE PARALLEL
AND PERPENDICULAR TO
THE GRAVESITE
GRIDLINES AND PRECISE
TO ±0.005'
REQUIRED TEXT ENGRAVED
ON CAP, TYPICAL
3 1/4"
PLASTIC INSERT
1/
2INTEGRAL MAGNET
DOMED TOP
PLAN
SECTION
N.T.S.
GRAVESITE GRID MONUMENTC3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
SCALE: 3/4"=1'-0"
SECTION MARKERE5
N.T.S.
MONUMENT MARKERC7
DETAILS - GRAVESITES
C-504
JVSF
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
0 5'
1/4 INCH = 1 FOOT
10'1'
N.T.S
FLORAL WATERING STATION DETAILSF4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet of 30
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
POWDER COATING
COLOR: VS BRONZE
CUSTOM PLAQUES & DECALS
SECURITY
LID IS SECURED WITH VINYL COATED GALVANIZED STEEL AIRCRAFT CABLE. CABLE IS
LOOPED AROUND ATTACHMENT BRACKETS AND CRIMPED IN PLACE.
LIDS
1. STANDARD WITH TAPERED FORMED LID (AS SHOWN).
2. PROVIDE HINGED SOLID COVER LID WITH HANDLE. LID HINGE TO BE PLACED A 1/3
CHORD POSITION ON LID. HINGE TO BE STAINLESS STEEL PIANO STYLE. PROVIDE SS
HANDLE.
NOTES:
1. DRAWING NOT TO SCALE. DO NOT SCALE DRAWINGS.
2. ALL FABRICATED METAL COMPONENTS ARE STEEL SHOTBLASTED, ETCHED, PHOSPHATIZED, PREHEATED, AND ELECTROSTATICALLY POWDER-COATED WITH T.G.I.C. POLYESTER POWDER COATINGS. PRODUCTS ARE FULLY CLEANED AND PRETREATED, PREHEATED AND COATED WHILE HOT TO FILL CREVICES AND BUILD COATING FILM. COATED PARTS ARE THEN FULLY CURED TO COATING MANUFACTURER'S SPECIFICATIONS. THE THICKNESS OF THE RESULTING FINISH COAT AVERAGES 8-10 MILS (200-250 MICRONS).
3. PRODUCT MUST BE PERMANENTLY AFFIXED TO THE GROUND SLAB AT ALL FOUR LEGS.
4. STAINLESS STEEL ANCHOR BOLTS TO BE PROVIDED BY CONTRACTOR
5. HOT DIP GALVANIZE BEFORE POWDER COATING. SEE WRITTEN SPECIFICATIONS FOR DETAILS.
6. ALL SPECIFICATIONS ARE SUBJECT TO CHANGE. CONTACT MANUFACTURER FOR DETAILS.
7. THIS PRODUCT IS SHIPPED FULLY ASSEMBLED.
8. CONTRACTOR SHALL SURVEY EXISTING FLORAL STATION AND MATCH INSTALLATION.
PROVIDE AND INSTALL PRESSURE SENSITIVE
VINYL OUTDOOR DECALS. THE TEXT 'VASES'
SHALL BE APPLIED TO ALL SOLID HINGED LIDS.
THE TEST 'TRASH' SHALL BE APPLIED TO ALL
PERIMETER RINGS OF THE OPEN STYLE LIDS.
CONFIRM LAYOUT AND SIZE OF LETTERS WITH
COTR.
TOTAL OF (1) SUPPLIED IN PHASE 1.
TRASH RECEPTACLE:
IRONSITES® SERIES LITTER RECEPTACLE,
MODEL NO. S-42, (36-GALLON CAPACITY).
COLOR BRONZE, OR APPROVED EQUAL.
SUPPLIED BY: VICTOR STANLEY
P.O. BOX DRAWER 330 - DUNKIRK, MD 20754
TEL (301) 855-8300 - FAX (410) 257-7579
www.victorstanley.com
FLOWER VASE RECEPTACLE:
IRONSITES® SERIES LITTER RECEPTACLE,
MODEL NO. S-424, (36-GALLON CAPACITY)
WITH HINGED LID. COLOR BRONZE, OR
APPROVED EQUAL.
SUPPLIED BY:
VICTOR STANLEY
P.O. BOX DRAWER 330 - DUNKIRK, MD 20754
TEL (301) 855-8300 - FAX (410) 257-7579
www.victorstanley.com
SECTION VIEW
CONCRETE PAD
CONTRACTOR PROVIDED AND
INSTALLED TRASH CONTAINER
PLAN VIEW
CONTRACTOR
PROVIDED AND
INSTALLED FLORAL
VASE RECEPTACLE
1'-5" 1'-6"
7'-5 1/2"
3' -2
/4
PRECAST POST SEE DETAIL THIS SHEET
TRASH CONTAINER
SEE ISOMETRIC THIS SHEET
WATER LINE (BELOW) -
SEE IRRIGATION
PLANS
ALUMINUM PANEL
BLUE BACKGROUND
WHITE LETTERS RED/
WHITE SYMBOL
6"
1/
2"
1' -4
6"
2' -4
2' -0
DO
NOT
DRINK
4" 1"
3"
1" 1"
VALVE BOX MINIMUM 6" BEHIND
CONCRETE SLAB
CONNECTION TO NON-POTABLE
WATER SOURCE
1' -4
3/4"
WHITE
TEXT
4"
4' -0
TOP OF
CONCRETE PAD
2'-4 1/8"
2'-4 1/8"
2' -1
3/
5' -0
PRESSURE REDUCING VALVE:
SEE IRRIGATION SHEETS
FLORAL VASE
RECEPTACLE
SEE ISOMETRIC THIS
SHEET
SPACE LABEL 4
TIMES EQUALLY
AROUND RING
SPACE LABEL 4
TIMES EQUALLY
AROUND RING
2'-3 1/4" 2'-2 1/4"
FAUCET: HAWS 6252EHLF,
AS SPECIFIED
SAWED CONTRACTION
JOINT (ABOVE)
4" AGGREGATE BASE
4 11/16"
1"
3/8" RECESS
(BELOW),
ALL SIDES
ARCHITECTURAL
PRE-CAST POST;
LIGHT SANDBLAST FINISH
3' -5
/2
1' -1
/4
1'-1 3/4"
STONE
M
AT
C H
E
XI
ST
IN
G
FW
S
36-GALLON CAPACITY HIGH
DENSITY PLASTIC LINER
(WEIGHT NOT TO EXCEED 6 LBS.)
SITS ON 3/8" x 3" SUPPORT BARS
3/8" x 1"
VERTICAL
STEEL BARS
19"
1/4" x 2-1/2"
HORIZONTAL
SOLID STEEL
BAND
5/8" SOLID
STEEL TOP
RING
LEVELING FEET WITH
A 3/8" DIAMETER
THREADED STEEL
SHAFT
3/4" SQUARE
CENTER
ANCHOR
BOLT HOLE
Ø 28-1/8"Ø 28-1/8"
DETAILS - FLOWER WATER
STATION
C-505
JVSF
4" RADIUS AT ALL EDGES
CONCRETE SIDEWALK
PER DETAIL B6/C-501
No. 44593
PROFESSIONAL
REGISTERED
JORDAN D. VANDERMEE
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE
O O
O O
O O
O O
O
OOOOOOOOOOOOOOOOOOOOOOOOOOOOO
W
UD UD UD
PPPP
P P
P
PPPPPPPPPPPPPPP
P
P P
P
P
UDUDUD
U D
U D
FM
FM
CO
CO
CO
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE
O O
O O
O O
O O
O
OOOOOOOOOOOOOOOOOOOOOOOOOOOOO
W
UD UD UD
PPPP
P P
P
PPPPPPPPPPPPPPP
P
P P
P
P
UDUDUDUD UD UD
U D
U D U
D U
D
FM
FM
CO
CO
CO
RSC
1.0 1.0
1.0 1.0
1.0
1.0 1.0
1.0 1.0
4.0 4.0
4.0
212121212121212121
2121212121212121
SECTION 6
SECTION 7
SECTION 8
SECTION 9
51 51
01 01
01 01
01 01
01010101
01 01
SECTION 10
VF
D
WP
1.0 1.0
1.0 1.0
1.0
1.0 1.0
1.0 1.0
3.0 4.0
4.0 4.08.0
8.0 8.0
4.0
8.0 8.0
8.0 4.0
2.04.0
4.0
4.0
TYP TYP TYP
TYP
TYP
TYP TYP
TYP
2.02.0 4.0
TYP
51 51
CODE DESCRIPTION
GD-01 THE CONTRACTOR SHALL FILL AND COMPACT ALL VOIDS
CREATED BY DEMOLITION WORK WITH CLEAN BACKFILL
MATERIAL WHICH SHALL BE APPROVED BY COR PRIOR TO
BACKFILL OPERATIONS.
GD-02 THE CONTRACTOR SHALL PROTECT EXISTING UTILITIES
FROM DAMAGE. ANY DAMAGE TO EXISTING UTILITIES SHALL
BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL COST
TO THE GOVERNMENT.
GD-03 THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL
EXISTING UTILITY LINES PRIOR TO DEMOLITION,
CONSTRUCTION, AND TRENCHING.
GD-04 THE CONTRACTOR SHALL TAKE ALL NECESSARY
PRECAUTIONS TO ENSURE NO DAMAGE OCCURS TO
EXISTING STRUCTURES, TREES, AND PAVEMENT TO REMAIN
AND ITEMS TO BE SALVAGED. ANY DAMAGE TO ITEMS TO
REMAIN OR TO BE SALVAGED RESULTING FROM
CONSTRUCTION OPERATIONS SHALL BE REPAIRED AND/OR
REPLACED AT NO ADDITIONAL COST TO THE GOVERNMENT.
GD-05 ALL AREAS ADJACENT TO THE SITE SHALL BE MAINTAINED IN
A CLEAN CONDITION, MUD AND DUST FREE AT ALL TIMES.
GD-06 PRIOR TO DEMOLITION OPERATIONS, THE CONTRACTOR
SHALL BE REQUIRED TO DOCUMENT ALL EXISTING
CONDITIONS DIRECTLY ADJACENT TO THE PROJECT AREA
AND THE CONDITION OF ANY EXISTING ITEMS TO REMAIN
WITHIN THE PROJECT AREA. CONTRACTOR SHALL PROVIDE
DOCUMENTATION TO THE COR BEFORE PROCEEDING WITH
ANY WORK.
IRRIGATION DEMOLITION GENERAL NOTES
XX
IRRIGATION LEGEND
EXISTING REMOTE CONTROL VALVE TO REMAIN
EXISTING REMOTE CONTROL VALVE TO BE RELOCATED
EXISTING TURF ROTOR/SPRAY HEAD TO REMAIN
EXISTING TURF ROTOR/SPRAY HEAD TO BE REMOVED
EXISTING MAIN LINE TO REMAIN, SIZE: 2"
EXISTING LATERAL TO REMAIN, SIZE VARIES
EXISTING LATERAL LINE TO BE REMOVED TO EXTENTS SHOWN
EXISTING QUICK COUPLER TO REMAIN
EXISTING BACKFLOW PREVENTER TO REMAIN
EXISTING CONTROLLER TO REMAIN
EXISTING RAIN SENSOR TO REMAIN
EXISTING VARIABLE FREQUENCY DRIVE (VFD)
EXISTING PRESSURE TANK
EXISTING WELL WITH SUBMERSIBLE WELL PUMP.
EXISTING METAL ENCLOSURE ON CONCRETE PAD TO REMAIN
RS
C
VFD
WP
CODE DESCRIPTION QTY
D-01 REMOVE EXISTING TURFGRASS - SEE PLANTING PLAN FOR 6,481 SF
FUTURE IMPROVEMENTS
D-02 EXISTING IRRIGATION HEAD TO REMAIN - CONTRACTOR
SHALL PRESERVE AND PROTECT DURING CONSTRUCTION
ACTIVITY
D-03 REMOVE EXISTING IRRIGATION HEAD AND RETURN TO
CEMETERY STAFF
D-04 CUT AND REMOVE PVC LATERAL LINES AND FITTINGS TO
LIMITS SHOWN FOR CONNECTION TO NEW HEADS AND
LATERALS - SEE IRRIGATION PLAN LI101. PROTECT EXISTING
LATERALS TO REMAIN FROM DAMAGE OR FILLING WITH DIRT
OR DEBRIS.
D-05 REMOVE LATERAL LINES, FITTINGS, AND ASSOCIATED HEADS
FOR ENTIRE ZONE
D-06 REMOVE REMOTE CONTROL VALVE ASSEMBLY, INCLUDING
ALL PIPING, FITTINGS, AND VALVE BOX TO THE SERVICE TEE
AND CAP ANY SERVICE TEES NOT RECEIVING NEW REMOTE
CONTROL VALVES. CUT AND LABEL WIRE FOR REUSE - SEE
IRRIGATION PLAN LI101. PULL ANY UNUSED WIRES BACK TO
THE NEAREST VALVE BOX AND CLEARLY LABEL FOR FUTURE
USE.
D-07 EXISTING IRRIGATION POINT OF CONNECTION, CONTROLLER,
BACKFLOW PREVENTER, ISOLATION VALVE AND OTHER
EQUIPMENT TO REMAIN
D-08 LOCATE EXISTING SPARE WIRES (TWO PER EACH. LOCATION
INDICATED), CUT, SPLICE IN EXISTING VALVE BOX, AND RUN
TO NEW VALVE LOCATION - SEE LI101.
D-09
COLUMN RISER, AND VARIABLE FREQUENCY DRIVE (VFD) AND
REPLACE - SEE LI101 AND SPECIFICATIONS FOR NEW
EQUIPMENT.
IRRIGATION DEMOLITION KEYED NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
CHEYENNE NATIONAL CEMETERY
CONSTRUCT COLUMBARIA, BURIAL
EXPANSION, PHASE 2
CHEYENNE, WY
945CM3002
N/A Project Manager/ COR
02/27/2024Revisions: Date:
DJ Junio Department of Veterans Affairs, NCA
Phone:
Email: Dimasalang.junio@va.gov Sheet
BID DOCUMENTS
VCI Project Management Construction Management Engineering
56 Louis Prima Drive, Suite B, Covington LA 70433 504.684.4408; Jordan Vandermeer
LANDSCAPE AND IRRIGATION
DEMOLITION PLAN
LD101
BV ER/KA
of 3017
Jordan Vandermeer Snapshot
OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE
O O
O O
O O
O O
O
OOOOOOOOOOOOOOOOOOOOOOOOOOOOO
W
UD UD UD
PPPP
P P
P
PPPPPPPPPPPPPPP
P
P P
P
P
UDUDUD
U D
U D
FM
FM
CO
CO
CO
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
OEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOEOE
O O
O O
O O
O O
O
OOOOOOOOOOOOOOOOOOOOOOOOOOOOO
W
UD UD UD
PPPP
P P
P
PPPPPPPPPPPPPPP
P
P P
P
P
UDUDUDUD UD UD
U D
U D U
D U
D
FM
FM
CO
CO
CO
RSC
SECTION 3
SECTION 6
SECTION 7
SECTION 8
SECTION 9 SECTION 10
SECTION 2SECTION 1
VF
D
WP
WELL CAPACITY/YIELD TESTING:
CONTRACTOR SHALL PERFORM DRAW DOWN TESTING ON THE EXISTING WELL TO ESTABLISH
THE PRODUCTION CAPACITY/YIELD TO VERIFY IF THE WELL CAN PROVIDE AN ADEQUATE
WATER SUPPLY (50GPM) FOR THE PHASE 2 EXPANSION PROJECT AND TO DETERMINE
APPROPRIATE DEPTH OF NEW SUBMERSIBLE PUMP. CONTRACTOR SHALL RUN DRAW DOWN
TEST UNTIL AND ONE HOUR AFTER WELL LEVEL WATER STABILIZES. WATER LEVELS SHALL BE
MEASURED AT REGULAR TIME INTERVALS DURING THE DURATION OF THE ENTIRE TEST. WELL
PRODUCTION TEST RESULTS SHALL BE SUBMITTED TO THE COR FOR REVIEW PRIOR TO
PROCEEDING WITH ANY WORK ON THE IRRIGATION SYSTEM. IF THE WELL CAPACITY IS
INADEQUATE TO SUPPORT THE PHASE 2 EXPANSION, CONTRACTOR WILL RECEIVE DIRECTION
FROM COR REGARDING SYSTEM MODIFICATIONS THAT MAY BE REQUIRED.
CONTRACTOR SHALL REMOVE THE EXISTING 5HP SUMBERSIBLE PUMP, 1-1/4” STAINLESS
STEEL DROP/RISER PIPE, AND PITLESS ADAPTER AND REPLACE WITH A NEW 7.5 HP
SUBMERSIBLE PUMP, 2” SCH. 40,304 STAINLESS STEEL DROP/RISER PIPE, AND 2” BRASS
PITLESS ADAPTER. PUMP SHALL BE SET AT DEPTH AS DETERMINED BY RESULTS OF DRAW
DOWN TEST. POWER FOR NEW PUMP MOTOR SHALL BE SUPPLIED BY EXISTING SINGLE
PHASE, 240V CIRCUIT CONNECTED TO EXISTING PUMP. PUMP SHALL BE GOULDS WATER
TECHNOLOGY MODEL #45GS75 OR APPROVED EQUAL SUBMERSIBLE PUMP WITH 4”, 7.5 HP,
SINGLE PHASE MOTOR AND 2” NPT DISCHARGE.
CONTRACTOR SHALL REMOVE THE EXISTING PENTEK VARIABLE FREQUENCY DRIVE (VFD)
LOCATED INSIDE OF THE EXISTING METAL ENCLOSURE AND REPLACE WITH MITSUBISHI
MODEL FR-F820-00490-E3N6 VFD. POWER FOR NEW VFD SHALL BE SUPPLIED BY EXISITNG
POWER SUPPLY CONNECTED TO EXISTING VFD. CONTROL WIRING SHALL BE INSTALLED AS
REQUIRED BETWEEN NEW PUMP MOTOR AND NEW VFD. VFD SHALL BE PROGRAMMED TO
PROVIDE CONSTANT PRESSURE OF 100PSI FOR FLOWS BETWEEN 20GPM AND 50GPM.
ALL POWER AND CONTROL WIRING SHALL BE INSTALLED IN ELECTRICAL CONDUIT IN
ACCORDANCE…
This is the start of the file's text. The full file is on GovTribe.