Drawings 626A4-18-107 Final .pdf
PDF 45 MB Posted
- Solicitation number
- 36C24921B0001
About this file
This document provides details for a federal contract opportunity to renovate the Whole Health Clinic at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. Project #626A4-18-107 involves furnishing all labor, materials, equipment, and supervision necessary to prepare the site for building operations as required by the drawings and specifications. The solicitation number is 36C24921B0001 and bids must be submitted by November 9, 2020 at 10:00 AM Central Time to the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The contractor will be responsible for completely preparing the site for construction activities according to the provided drawings and specifications for the Whole Health Clinic renovation.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
HFR DESIGN, INC.
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
RENOVATE FOR WHOLE HEALTH CLINIC
ALVIN C. YORK VAMC
3400 LEBANON PIKE
MURFREESBORO, TN 37129
4-30-2019
F
IN
A L
B
ID
D O
C U
M E
N T
S -3
-2
FINAL BID DOCUMENTS
HFR Project No: 2018130
WEB: www.hfrdesign.com
FAX: 615.370.8530
PHONE: 615.370.8500
CITY/STATE/ZIP: BRENTWOOD, TN 37027
ADDRESS: 214 CENTERVIEW DRIVE, STE 300
EMAIL: bcrump@hfrdesign.com
ENGINEER: BRIAN CRUMP
STRUCTURAL
ENGINEER:
HFR DESIGN
WEB: www.hfrdesign.com
FAX: 615.370.8530
PHONE: 615.370.8500
CITY/STATE/ZIP: BRENTWOOD, TN 37027
ADDRESS: 214 CENTERVIEW DRIVE, STE 300
EMAIL: llutche@hfrdesign.com
DESIGNER: LEONARD LUTCHE
INTERIOR
DESIGNER:
HFR DESIGN
WEB: www.atriaxgroup.com
PHONE: 828.315.9962
CITY/STATE/ZIP: HICKORY, NC 28601
ADDRESS: 102 3RD AVENUE NE
EMAIL: ed.henson@atriaxgroup.com
PROJ. ARCHITECT: ED HENSON
ARCHITECT: ATRIAX, PLLC.
PROJECT NUMBER: 2018130
WEB: www.hfrdesign.com
FAX: 615.370.8530
PHONE: 615.370.8500
CITY/STATE/ZIP: BRENTWOOD, TN 37027
ADDRESS: 214 CENTERVIEW DRIVE, STE 300
EMAIL: llutche@hfrdesign.com
PROJ. MANAGER: LEONARD LUTCHE
EMAIL: rfranks@hfrdesign.com
PROJ. ARCHITECT: RON FRANKS
ARCHITECT: HFR DESIGN
PROJECT NUMBER: 626A4-18-107
WEB: www.tennesseevalley.va.gov
PHONE: 615.867.6000
CITY/STATE/ZIP: Murfreesboro, TN 37129
ADDRESS: 3400 Lebanon Road
EMAIL: hans.johnson2@va.gov
CONTACT PERSON: HANS JOHNSON
OWNER: ALVIN C. YORK VA MEDICAL CENTER
PROJECT CONTACT LIST
WEB: www.tlc-engineers.com
FAX: 615.297.4554
PHONE: 615.297.4554
CITY/STATE/ZIP: Brentwood, TN 37027
ADDRESS: 12 Cadillac Drive; Suite 150
EMAIL: gerald.versluys@tlc-eng.com
ELECTRICAL: GERALD VERSLUYS
EMAIL: gerald.versluys@tlc-eng.com
TECHNOLOGY: GERALD VERSLUYS
EMAIL: steve.kemp@tlc-eng.com
PLUMBING: STEVE KEMP
EMAIL: steve.kemp@tlc-eng.com
MECHANICAL: STEVE KEMP
MECHANICAL,
PLUMBING, &
ELECTRICAL
ENGINEERS:
TLC ENGINEERING SOLUTIONS
PROJECT CONTACTS (CONT)
NEGATIVE AIR PRESSURE MACHINE NOTES:
1. PROVIDE A TEMPORARY NEGATIVE AIR MACHINE FOR CONSTRUCTION
AREA. MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE
ADJACENT SPACES AT A MINIMUM OF -0.03" W.C. PROVIDE TEMPORARY
DUCT BARRIER PARTITIONS.
FAN CRITERIA:
MODEL: HEPA-AIRE PAS1200HC
CFM: 800 CFM
HP/V/P: .25/120/1
2. PROVIDE TEMPORARY EXHAUST FROM HEPA UNIT TO DISCHARGE OUT
EXISTING WINDOW, PROVIDE PLYWOOD OVER WINDOW OPENING WITH
OPENING AND DUCT COLLAR FOR CONNECTION TO FLEX DUCT FROM
NEGATIVE AIR MACHINE. PROVIDE WITH DISCONNECTIVE MEANS AND FAN
GUARDS. PROVIDE AS MANY TEMPORARY NEGATIVE AIR MACHINES AS
REQUIRED TO MAINTAIN MINIMUM NEGATIVE PRESSURE REQUIREMENT.
3. PROVIDE INCLINED MANOMETER GAGE WITH RANGE FROM 0.00" TO 0.1"
W.C. MAINTAIN A MINIMUM OF -0.03" W.C. IN CONSTRUCTION AREA.
REFERENCE FACILITY ICRA PLAN FOR ADDITIONAL INFORMATION.
12" METAL FLEX
DUCT (TYP.)
MANOMETER
(SEE NOTE 3) NEGATIVE AIR PRESSURE
MACHINE (SEE NOTE 1)
REMOVE EXISTING WINDOW
AND INSTALL TEMPORARY
PLYWOOD WITH OPENING AND
DUCT COLLAR FOR FLEX DUCT
CONNECTION. PROVIDE
WEATHER TIGHT SEAL.
DEMOLITION WORK SPACE OUTSIDE
WINDOW TAG
ELEVATION TAG
GYPSUM BOARD
EARTH
CONCRETE
CONC. MASONRY UNITS
STEEL SECTION
FINISH WOOD
BATT INSULATION
GRAVEL FILL
DOOR TAG
HANDICAP ACCESSIBLE
SECTION INDICATOR
SHEET NUMBER
ENLARGED PLAN NUMBER
NOTE: THE DIRECTION OF THE SECTION INDICATOR'S
FLAG MAY REFLECT AN "OPPOSITE HAND" OR
"MIRRORED VIEW" OF BUILDING AND WALL SECTIONS
EQUIPMENT TAG
AA
CALLOUT
# / A ##.##
EIFS INSULATION BOARD
# / A ##.##
# / A ##.##
0000-000
EXIST DEMO NEW
BLDG. 1 phase 1
BLDG. 2 phase 2
BLDG. 9 phase 1
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs
\a tr a y lo r\ D e s k to p \R e v it P ro je c ts
\M b o ro
V A
R e n o v a ti o n -2 a tr a y lo r.
rv t
/2
/2
:3
:3
P
M
4-30-2019
626A4-18-107
GI 01.01
RENOVATE FOR WHOLE HEALTH
CLINIC
GENERAL DATA
DRAWN
BY:
HFR Project No: 2018130
FINAL BID DOCUMENTS
SYMBOL LEGEND
MED. MEDICAL
MED. CAB. MEDICAL CABINET
MFR. MANUFACTURER
MGMT. MANAGEMENT
MH MANHOLE
MIN. MINIMUM
MIR. MIRROR
MISC. MISCELLANEOUS
MR/S MIRROR WITH SHELF
MTD. MOUNTED
MTL. METAL
N.I.C. NOT IN CONTRACT
NOM. NOMINAL
O.C. ON CENTER
O.D. OVERFLOW DRAIN
O.F.O.I. OWNER FURNISHED / OWNER
INSTALLED
OPER. OPERATIONS
OPNG. OPENING
OPP. OPPOSITE
P.P.G. POLISHED PLATE GLASS
P.R.V. POWER ROOF VENTILATOR
P.T. PRESSURE TREATED
PART'N(S) PARTITION(S)
PLAS. PLASTER
PLAS. LAM. PLASTIC LAMINATE
PLYWD. PLYWOOD
PREP. PREPARATION
PREV. PREVENTIVE
PROF. PROFESSIONAL
PTD PAPER TOWEL DISPENSER
Q.T. QUARRY TILE
R. RADIUS
R.D. ROOF DRAIN
R.O. ROUGH OPENING
RECEPT. RECEPTION
RECOV. RECOVERY
REF. REFRIGERATOR
REF. REFER, REFERENCE
REINF. REINFORCING, REINFORCED
REQ'D REQUIRED
RM. ROOM
S SEALANT
S.&R. SHELF AND ROD
S.S. STAINLESS STEEL
SAN. SANITARY
SB SPLASHBLOCK
SCHED. SCHEDULE
SD SOAP DISH
SEC. SECTION, SECRETARY
SGNL. SIGNAL
SHLVG. SHELVING
SIM. SIMILAR
SPECS. SPECIFICATIONS
SS SANITARY SEWER
STD. STANDARD
STL. STEEL
STO. STORAGE
STRUCT. STRUCTURAL
SYS. SYSTEM
T./TOIL./TL
T.
TOILET
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TB TOWEL BAR
TBL. TABLE
TECH. TECHNICIAN
TEL. TELEPHONE
THK. THICK
THKNS. THICKNESS
TPH TOILET PAPER HOLDER
TRAIN. TRAINING
TRANS. TRANSFORMER
TREAT. TREATMENT
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
UNEXP. UNEXPOSED
VEST. VESTIBULE
W.H.F.E. WALL HUNG FIRE
EXTINGUISHER
W/ WITH
WC/W.C. WATER CLOSET
WD. WOOD
WP. WATERPROOF(ING)
A.F.F. ABOVE FINISHED FLOOR
A.F.S. AT FINISHED SLAB
ADD'L ADDITIONAL
ADJ. ADJUSTABLE
ADMIN. ADMINISTRATION
ALUM. ALUMINUM
APPROX. APPROXIMATE
ASST. ASSISTANT
B.W. BOTTOM OF THE WALL
B/B BALLED & BURLAPPED
BR. BARE ROOT
BRKT. BRACKET
BRKTS. BRACKETS
C CALK
C'SNK. COUNTERSUNK
C.B. CATCH BASIN
C.F.C.I. CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
C.J. CONTROL JOINT
C.M.U. CONCRETE MASONRY UNIT
CAB. CABINET
CLG. CEILING
CLO. CLOSET
CNTR. COUNTER
COL. COLUMN
COMP. COMPUTER
CONC. CONCRETE
CONF. CONFERENCE
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
DIA. DIAMETER
DIAG. DIAGONAL
DIM. DIMENSION
DIR. DIRECTOR
DISP. DISPENSER
DS DOWNSPOUT
DTL. DETAIL
DWGS. DRAWINGS
EA. EACH
ELEC. ELECTRICAL
ELEV. ELEVATION
ENCL. ENCLOSURE
EQUIP. EQUIPMENT
EXIST. EXISTING
EXP. JT. EXPANSION JOINT
EXT. EXTERIOR
F.D. FLOOR DRAIN
F.E.C. FIRE EXTINGUISHER CABINET
F.F.E. FINISH FLOOR ELEVATION
FDS FOLD DOWN SEAT
FH FIRE HYDRANT
FIN. FINISH
FL. FLOOR
FOB FACE OF BRICK
FTG. FOOTING
FZR. FREEZER
G.B. GRAB BAR
GA. GAUGE
GAL. GALLON
GALV. GALVANIZED
GEN. GENERAL
GYP. GYPSUM
GYP. BD. GYPSUM BOARD
H.B. HOSE BIBB
H.M. HOLLOW METAL
HCM HANDICAPPED MIRROR
HD. HEAD
HRDBD HARDBOARD
I.D. INSIDE DIAMETER
INFO. INFORMATION
INSUL. INSULATION
INT. INTERIOR
INV. INVERT
JT. JOINT
KIT. KITCHEN
LAB. LABORATORY
LAV. LAVATORY
LKR. LOCKER
M.O. MASONRY OPENING
MACH. MACHINE
MAINT. MAINTENANCE
MAT'L MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
GENERAL ABBREVIATIONS
● ALL OTHER NON-STRUCTURAL COMPONENTS WITHIN THE HVAC, MECHANICAL, PLUMBING, AND
ELECTRICAL SYSTEMS ARE ASSIGNED AN IMPORTANCE FACTOR OF 1.0 AND ARE ELIGIBLE FOR THE LATERAL BRACING EXEMPTIONS LISTED IN ASCE 7 SECTION 9.6. THE EXEMPTIONS APPLY TO SPECIFIC SMALLER SIZES OF PIPING AND DUCTWORK AND LESS HEAVY EQUIPMENT. NON-EXEMPT PORTIONS OF THESE SYSTEMS SHALL STILL BE LATERALLY BRACED. SYSTEMS WITH AN IMPORTANCE FACTOR OF 1.0
ARE CONSIDERED BY THE CODE TO BE NOT CRITICAL FOR THE CONTINUED OPERATION OF THE
FACILITY.
COMPONENTS WITH AN IMPORTANCE FACTOR OF 1.0:
● STORM SEWER SERVING CRITICAL CARE AREAS.
● SANITARY SEWER SERVING CRITICAL CARE AREAS.
● STEAM SYSTEM.
● HEATING HOT WATER SYSTEM.
● DOMESTIC HOT WATER SYSTEM.
● FIRE ALARM SYSTEM.
● EMERGENCY POWER DISTRIBUTION SYSTEMS INCLUDING ASSOCIATED GENERATOR, TRANSFER
SWITCHES, BUS DUCTS, SWITCHBOARDS, CONDUIT, AND TRANSFORMERS.
● GENERATOR ENGINE EXHAUST.
● DUCTWORK CARRYING RADIOACTIVE AGENTS AND INFECTIOUS ISOLATION AIR.
● MEDICAL GAS PIPING AND EQUIPMENT.
● FIRE SPRINKLERS AND EQUIPMENT.
● NATURAL GAS PIPING.
● FUEL OIL PIPING AND EQUIPMENT.
COMPONENTS WITH AN IMPORTANCE FACTOR OF 1.5:
3. ASSIGNED SEISMIC USE GROUP OR BUILDING DESIGN CATEGORY AS DEFINED IN THE IBC:
2. THE TERM "WITHSTAND" MEANS "THE SYSTEM WILL REMAIN IN PLACE WITHOUT SEPARATION OF ANY PARTS WHEN SUBJECTED TO THE SEISMIC FORCES SPECIFIED AND THE SYSTEM WILL BE FULLY OPERATIONAL
AFTER THE SEISMIC EVENT."
1. COMPONENTS SHALL WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS DETERMINED ACCORDING TO
ASCE/SEI 7.
NON-STRUCTURAL SEISMIC NOTES
14. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL LOCAL AND STATE CONSTRUCTION PERMITS.
13. CONTRACTOR SHALL NOT DISRUPT OR LIMIT THE FACILITY'S LIFE SAFETY PLAN AND SYSTEM.
12. SEISMIC: NON-STRUCTURAL COMPONENTS SHALL WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS
DETERMINED ACCORDING TO ASCE/SEI 7. PROVIDE ENGINEERED SUPPORTS PER SEISMIC
CLASSIFICATION AND ASCE/SEI 7 REQUIRMENTS.
11. CODES: COMPLY WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES.
10. SUPPORT / BLOCKING: PROVIDE SUPPORT FOR NEW WORK. IF HANGERS, BACKERS, OR OTHER SUPPORTS ARE NOT DETAILED, NOTED, OR SPECIFIED, CONTRACTOR SHALL SUBMIT A VIABLE SUPPORT DETAIL TO THE ARCHITECT FOR APPROVAL. ALL BLOCKING SHALL BE METAL (U.N.O.) ALL WOOD
BLOCKING, WHERE SPECIFIED, SHALL BE FIRE RETARDANT (U.N.O.)
9. MAINTAIN RATINGS: MAINTAIN FIRE / SMOKE RATINGS OF EXISTING PARTITIONS AND BARRIERS.
8. SHUTDOWNS / DOWNTIME: CONTRACTOR SHALL MAKE EVERY EFFORT TO MINIMIZE DOWNTIME
ASSOCIATED WITH SCHEDULED SHUTDOWNS. COORDINATE WITH OWNER.
7. COORDINATE TRADES: GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATION BETWEEN
TRADES. MECHANICAL DUCTWORK & EQUIPMENT SHALL HAVE PRIORITY OVER OTHER DISCIPLINES (FOR INSTALLATION & ROUTING). COORDINATE UTILITIES, SO THEY ARE INSTALLED IN AN ORDERLY AND
UNIFORM MANNER.
6. PROTECT / RESTORE: PROTECT EXISTING ITEMS, EQUIPMENT, FINISHES, ETC., TO REMAIN. REPAIR / REPLACE / RESTORE CONDITIONS THAT ARE DAMAGED OR DISTURBED AS A RESULT OF DEMOLITION OR
NEW WORK.
5. UTILITIES: UTILITIES AND SYSTEMS IN AREAS OUTSIDE THE CONSTRUCTION LIMITS SHALL REMAIN (U.N.O.).
4. COORDINATE NEW ITEMS: EXACT LOCATIONS OF ALL EQUIPMENT, DEVICES / OUTLETS, FIXTURES, CASEWORK, MOUNTS, AND ROUTING OF UTILITIES SHALL BE COORDINATED WITH AND APPROVED BY THE
OWNER.
3. DO NOT SCALE DRAWINGS.
2. VERIFY CONDITIONS: INVESTIGATE THE SITE AND VERIFY EXISTING CONDITIONS (BOTH EXPOSED AND
CONCEALED) PRIOR TO PRICING THE JOB.
1. DIAGRAMMATIC DRAWINGS: THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE DRAWINGS
REPRESENT THE INTENT OF THE PROJECT WORK.
GENERAL PROJECT NOTES
PROPOSED: NO CHANGE
PARKING: 2% OF PARKING SPACES OR 1/25 > OR 2/26-50
ACCESSIBILITY: ALL PUBLIC AREAS - ADAAG, ANSI
J. HANDICAPPED ACCESSIBILITY REQUIREMENTS:
ROOF CONSTRUCTION: 1.5 HR
FLOOR CONSTRUCTION: 2 HR
NON-BEARING WALLS & PARTITIONS (INTERIOR): 0 HR
NON-BEARING WALLS & PARTITIONS (EXTERIOR) 0 HR
BEARING WALLS (INTERIOR): 3 HR
BEARING WALLS (EXTERIOR): 3 HR
STRUCTURAL FRAME: 3 HR
I. FIRE PROTECTION REQUIREMENTS (IBC TABLE 601 & NFPA A.8.2.1.2):
DEAD ENDS: 20 FEET MAX IBC [CODE REF]
CORR. FIRE RATING OCCUPANCY: 0 HRS (SPRINKLERED) IBC [CODE REF]
CORRIDORS: WIDTH 96 IN IBC [CODE REF]
MAX EGRESS: DISTANCE: 200 FT (SPRINKLERED) IBC [CODE REF]
EGRESS WIDTH: 0.2 PER OCCUPANT DOORS (OTHER) IBC [CODE REF]
H. EXIT REQUIREMENTS:
NOTE: REFER TO PLAN FOR INDIVIDUAL SPACE OCCUPANCY LOADS
LOCKER ROOMS 50 GSF / OCCUPANT
SLEEPING AREAS 120 GSF / OCCUPANT
ACCESSORY STORAGE &
MECH SPACES
300 GSF / OCCUPANT
OP TREATMENT AREAS 100 GSF / OCCUPANT
IP TREATMENT AREAS 240 GSF / OCCUPANT
WAITING, CONF., &
SEMINAR AREAS
15 GSF / OCCUPANT
OFFICE AREAS 100 GSF / OCCUPANT
AREA DESCRIPTION LOAD FACTOR TOTAL AREA OCCUPANTS
G. OCCUPANT LOAD:
PROPOSED HEIGHT:
EXISTING HEIGHT:
PROPOSED AREA:
EXISTING AREA:
ALLOWED AREA: UNLIMITED NFPA CH. [CODE REF]
ALLOWED HEIGHT: UNLIMITED IBC [CODE REF]
F. BUILDING HEIGHT & AREA:
SEISMIC DESIGN CAT:
SITE CLASSIFICATION:
OCCUPANCY CAT:
S1 = Sd1 =
Ss = Sds =
SITE CLASSIFICATION:
E. SEISMIC ZONE:
NFPA 2018: [TYPE II (2,2,2) - FULLY SPRINKLED] NFPA CH. [CODE REF]
IBC 2012: [TYPE IA - FULLY SPRINKLED] IBC [CODE REF]
D. CONSTRUCTION TYPE:
NFPA 2018: [HEALTHCARE OCCUPANCY] NFPA CH. [CODE REF]
IBC 2012: INSTITUTIONAL HEALTHCARE OCCUPANCY - I2 IBC [CODE REF]
C. OCCUPANACY:
615-893-3750
MURFREESBORO, TN 37113-1139
111 WEST VINE STREET
CITY OF MURFREESBORO
615-7417190
NASHVILLE, TN 37243-1162
500 JAMES ROBERTSON PARKWAY
TENNESSEE STATE FIRE MARSHAL'S OFFICE (SFMO)
B. AUTHORITIES HAVING JURISDICTION (AHJ):
2009 ICC ANSI 117.1 - ACCESSIBLE AND USABLE BUILDING AND FACILITIES
2008 NATIONAL ELECTRIC CODE (NEC)
2012 INTERNATIONAL FUEL GAS CODE
2012 INTERNATIONAL MECHANICAL CODE (IMC)
2012 INTERNATIONAL PLUMBING CODE (IPC)
2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2012 INTERNATIONAL FIRE CODE (IFC)
2012 INTERNATIONAL BUILDING CODE (IBC)
CITY OF MURFREESBORO
2010 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTH CARE FACILITIES
2010 ADA AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES WITH 2002...
2012 INTERNATIONAL FUEL GAS CODE
2011 NATIONAL ELECTRIC CODE (NEC)
2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2015 INTERNATIONAL MECHANICAL CODE (IMC)
2015 INTERNATIONAL PLUMBING CODE (IPC)
2015 INTERNATIONAL FIRE CODE (IFC)
2012 LSC - NFPA - 101 LIFE SAFETY CODE
2012 INTERNATIONAL BUILDING CODE (IBC)
STATE OF TENNESSEE
A. APPLICABLE STATUTES:
DESCRIPTION: RENOVATIONS TO BUILDING 1, 4TH FLOOR SIM. LAB, WORK ROOM, AND STORAGE.
BUILDING 2, GROUND FLOOR NEW WHOLE HEALTH CLINIC. BUILDING 9, GROUND FLOOR
NEW PT RESOURCE CENTER.
LOCATION: VAMC-ALVIN C. YORK, MURFREESBORO, TN
PROJECT: RENOVATE FOR WHOLE HEALTH CLINIC
PLAN REVIEW DATA DRAWING INDEX
SHEET # SHEET NAME C
D REVISIONS
07 - MECHANICAL
M-MH-01 LEGENDS, NOTES, AND SYMBOLS ●
M-MD-01 B1 - 4TH FLOOR - MECHANICAL DEMOLITION ●
M-MD-02 B2 - GROUND FLOOR - MECHANICAL DEMOLITION ●
M-MD-03 B2 - GROUND FLOOR - MECHANICAL DEMOLITION ●
M-MD-04 B9 - GROUND FLOOR - MECHANICAL DEMOLITION ●
M-MH-02 B1 - 4TH FLOOR - NEW DUCTWORK ●
M-MH-03 B2 - GROUND FLOOR - NEW DUCTWORK ●
M-MH-04 B2 - 1ST FLOOR - NEW DUCTWORK AND PIPING ●
M-MP-01 B2 - GROUND FLOOR - NEW PIPING ●
M-MP-02 B2 - GROUND FLOOR - NEW PIPING ●
M-MH-05 B2 - ROOF - NEW ●
M-MH-06 B9 - GROUND FLOOR - NEW DUCTWORK ●
M-MH-07 SCHEDULES ●
M-MH-08 SCHEDULES ●
M-MH-09 MECHANICAL DETAILS ●
M-MH-10 MECHANICAL DETAILS ●
M-MH-11 MECHANICAL DETAILS ●
M-MH-12 MECHANICAL DETAILS ●
M-MI-01 MECHANICAL CONTROLS ●
M-MI-02 MECHANICAL CONTROLS ●
08 - PLUMBING
P-PI-01 PLUMBING LEGENDS & NOTES ●
P-PI-02 PLUMBING SCHEDULES ●
P-PI-03 PLUMBING DETAILS ●
P-PD-01 BLDG 2 GROUND FLOOR - PLUMBING DEMOLITION ●
P-PP-01 BLDG 2 GROUND FLOOR - GRAVITY - NEW WORK -
UNDERGROUND
P-PP-02 BLDG 2 FIRST FLOOR - GRAVITY - NEW WORK ●
P-PP-03 BLDG 1 FOURTH FLOOR - GRAVITY - NEW WORK ●
P-PP-04 BLDG 2 GROUND FLOOR - PRESSURE - NEW WORK ●
P-PP-05 BLDG 1 FOURTH FLOOR - PRESSURE - NEW WORK ●
P-PP-06 BLDG 2 ROOF PLAN - PLUMBING - NEW WORK ●
P-PW-01 PLUMBING RISERS ●
09 - ELECTRICAL
E-EI-01 ELECTRICAL LEGEND & NOTES ●
E-EI-02 ELECTRICAL PANEL SCHEDULES ●
E-EI-03 ELECTRICAL PANEL SCHEDULES ●
E-EI-04 ELECTRICAL DETAILS ●
E-EI-05 ELECTRICAL DETAILS ●
E-ED-01 BUILDING #2 - GROUND FLOOR - DEMOLITION - ELECTRICAL ●
E-ED-02 BUILDING #9 - GROUND FLOOR - DEMOLITION - ELECTRICAL ●
E-ED-03 BUILDING #1 -4TH FLOOR - DEMOLITION - ELECTRICAL ●
E-EP-00 BUILDING #2 - GROUND FLOOR - NEW WORK - OVERALL ●
E-EP-01 BUILDING #2 - GROUND FLOOR - NEW WORK - POWER ●
E-EP-02 BUILDING #2 - ROOF PLAN - NEW WORK - POWER ●
E-EP-03 BUILDING #9 - GROUND FLOOR - NEW WORK - POWER ●
E-EP-04 BUILDING #1 - 4TH FLOOR - NEW WORK - POWER ●
E-EL-01 BUILDING #2 - GROUND FLOOR - NEW WORK - LIGHTING ●
E-EL-02 BUILDING #9 - GROUND FLOOR - NEW WORK - LIGHTING ●
E-EL-03 BUILDING #1 - 4TH FLOOR - NEW WORK - LIGHTING ●
E-EY-01 BUILDING #2 - GROUND FLOOR - NEW WORK - FIRE ALARM ●
E-EY-02 BUILDING #9 GROUND FLOOR - NEW WORK - FIRE ALARM ●
E-EY-03 BUILDING #1 - 4TH FLOOR - NEW WORK - FIRE ALARM ●
10 - FIRE PROTECTION
F-FI-01 FIRE PROTECTION LEGENDS, DETAILS & NOTES ●
F-FD-01 BLDG. 2 GROUND FLOOR - FIRE PROTECTION - DEMOLITION ●
F-FD-02 BLDG. 9 GROUND FLOOR - FIRE PROTECTION - DEMOLITION ●
F-FD-03 BLDG. 1 FOURTH FLOOR - FIRE PROTECTION - DEMOLITION ●
F-FX-01 BLDG 2 GROUND FLOOR - FIRE PROTECTION - NEW WORK ●
F-FX-02 BLDG 9 GROUND FLOOR - FIRE PROTECTION - NEW WORK ●
F-FX-03 BLDG 1 - FOURTH FLOOR - FIRE PROTECTION - NEW WORK ●
11 - TECHNOLOGY
T-TJ-01 LEGENDS, NOTES, AND SYMBOLS ●
T-TD-01 B1 - 4TH FLOOR - TECHNOLOGY DEMOLITION ●
T-TD-02 B2 - GROUND FLOOR - TECHNOLOGY DEMOLITION ●
T-TD-03 B9 - GROUND FLOOR - TECHNOLOGY DEMOLITION ●
T-TJ-02 B1 - 4TH FLOOR - NEW TECHNOLOGY ●
T-TJ-03-A B2 - GROUND FLOOR - NEW TECHNOLOGY ●
T-TJ-03-B B2 - GROUND FLOOR - CABLE ROUTING - NEW TECHNOLOGY ●
T-TJ-04 B9 - GROUND FLOOR - NEW TECHNOLOGY ●
T-TJ-05 TECHNOLOGY DETAILS ●
DRAWING INDEX
SHEET # SHEET NAME C
D REVISIONS
00 - GENERAL
GI 01.01 GENERAL DATA ●
GI 01.10 WALL TYPE DETAILS ●
GI 01.20 ACCESSIBILITY DETAILS ●
GI 02.01A BLDG. 2 - GROUND FLOOR LIFE SAFETY PLAN ●
GI 02.02A BLDG. 9 - GROUND FLOOR LIFE SAFETY PLAN ●
GI 02.04 BLDG. 1 - 4TH FLOOR LIFE SAFETY PLAN ●
03 - DEMOLITION
AD 01.01A BLDG. 2- GROUND FLOOR DEMOLITION PLAN ●
AD 01.01B BLDG. 2 - GROUND FLOOR RCP - DEMOLITION ●
AD 01.02A BLDG. 9 - GROUND FLOOR DEMOLITION PLAN ●
AD 01.04 BLDG. 1 - 4TH FLOOR DEMOLITION PLAN ●
04 - ARCHITECTURAL
A 01.01A BLDG. 2 - GROUND FLOOR PLAN - NOTED ●
A 01.01B BLDG. 2 GROUND FLOOR PLAN - DIMENSIONED ●
A 01.02A BLDG. 9 - GROUND FLOOR PLAN ●
A 01.03A BLDG. 2 - 1ST FLOOR PLAN ●
A 01.04 BLDG 1 - 4TH FLOOR PLAN ●
A 02.01 ENLARGED PLANS ●
A 03.01 DOOR SCHEDULE AND DETAILS ●
A 03.02 DOOR AND WINDOW DETAILS ●
A 08.01 MISC. DETAILS ●
A 08.02 MISC DETAILS ●
A 08.03 MISC. DETAILS ●
A 09.01 INTERIOR ELEVATIONS ●
A 09.02 INTERIOR ELEVATIONS ●
A 10.01 CASEWORK ELEVATIONS ●
A 10.02 CASEWORK DETAILS ●
A 11.01A BLDG. 2 - GROUND FLOOR REFLECTED CEILING PLAN ●
A 11.02A BLDG. 9 - GROUND FLOOR REFLECTED CEILING PLAN ●
A 11.03A BLDG. 2 - 1ST FLOOR REFLECTED CEILING PLAN ●
A 11.04 BLDG. 1 - 4TH FLOOR REFLECTED CEILING PLAN ●
A 13.05A BLDG. 2 - ROOF PLAN ●
A 13.05B ROOF DETAILS ●
A 13.05C 3D VIEWS ●
05 - INTERIOR DESIGN
IN 01.01A BLDG. 2 - GROUND FLOOR FINISH PLAN ●
IN 01.02A BLDG. 9 - GROUND FLOOR FINISH PLAN ●
IN 01.03A BLDG. 2 - 1ST FLOOR FINISH PLAN ●
IN 01.04 BLDG. 1 - 4TH FLOOR FINISH PLAN ●
IN 01.05 INTERIOR FLOOR PATTERNS AND DETAILS ●
06 - STRUCTURAL
SS 02.01 ROOF FRAMING PLAN - BLDG. #2 ●
NOT TO SCALE
VICINITY PLAN
NOT TO SCALE
NEGATIVE AIR MACHINE
10. REFER TO DEMOLITION SHEETS AD 01.01A AND AD 01.02A FOR LOCATION AND EXTENTS OF TEMPORARY
DUST/CONSTRUCTION PARTITION (KEYNOTE 2.04).
9. DUST BARRIERS BETWEEN DEMOLITION / CONSTRUCTION ZONE AND OCCUPIED AREAS ARE TO EXTEND
ABOVE CEILING AND SEALED TO UNDERSIDE OF STRUCTURE ABOVE. RESULTING TEMPORARY
CONSTRUCTION SHALL MEET 1HR FIRE BARRIER REQUIREMENTS U.N.O.
8. PROVIDE STICKY MATS AT ALL CONSTRUCTION ENTRANCES AND REPLACE ON REGULAR BASIS TO
ENSURE DEBRIS IS NOT TRANSFERRED FROM CONSTRUCTION SIDE OF BARRIER TO CLEAN
(NON-CONSTRUCTION) SIDE OF BARRIER.
7. SITE SHALL BE INSPECTED BY OWNER'S INFECTION CONTROL OFFICER UPON COMPLETION OF BARRIERS
AND PRIOR TO START OF CONSTRUCTION.
6. PROVIDE REQUIRED TEMPORARY DUST BARRIERS, BARRICADES, INFECTION CONTROL MEASURES PER
THE COMPLETED RISK ASSESSMENT, ETC. TO PROTECT PERSONNEL AND ADJACENT SPACES.
5. WET MOP WORK AREA THOROUGHLY WITH DISINFECTANT UPON COMPLETION OF PROJECT.
4. INSTALL HEPA FILTERED NEGATIVE AIR MACHINE TO RUN 24 HOURS PER DAY UNTIL CONSTRUCTION IS
COMPLETED.
3. CONSTRUCTION DEBRIS SHALL BE TRANSPORTED IN A WHEELED TILT TRUCK WITH DOME LID AT A MIN.
2. AIR QUALITY MONITOR TESTING SHALL BE PERFORMED BEFORE THE START OF CONSTRUCTION, PERIODICALLY DURING THE CONSTRUCTION PROCESS, AND AT COMPLETION OF CONSTRUCTION.
1. REFER TO INFECTION CONTROL RISK ASSESSMENT PERFORMED BY FACILITIES INFECTION CONTROL
OFFICER FOR SPECIFIC ICRA LEVEL & REQUIREMENTS
GENERAL ICRA NOTES
No. Date Description
1 6/20/2019 Addendum 1
HIGHER PRIORITY
(HIGHEST)
(LOWEST)NON-RATED PARTITION
ONE HOUR FIRE BARRIER
ONE HOUR FIRE / SMOKE BARRIER
TWO HOUR FIRE BARRIER
TWO HOUR FIRE / SMOKE BARRIER
WALL PRIORITY LEGEND
LOWER PRIORITY
PLAN
NON-RATED SMOKE PARTITION
1HR FIRE BARRIER
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
U465
45 - 49
1HR
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"1HR FIRE BARRIER"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: 45 MIN
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 25 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF
20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN
ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND
WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO FURRING CHANNELS,
WALLBOARD IS ATTACHED WITH 1" LONG TYPE S SCREWS AT 12" O.C.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL
FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH
INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.
7. ACOUSTICAL SEALANT.
8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION
FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.
PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS
REQUIRED TO RECEIVE JOINT SEALANT.
9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
7/
8" M
IN
SMOKETIGHT PARTITION
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
45 - 49
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"NON-RATED SMOKETIGHT"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: SM
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 25 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED
BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT
STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND
SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT
ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. ACOUSTICAL SEALANT.
7. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
V A
R
IE
S
NON-RATED PARTITION
16" O.C.
SECTION
PLAN
DESCRIPTION:
2 43
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
45 - 49
N.T.S.
ABOVE CEILING ID (STENCIL):
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
OPENINGS: --
V A
R
IE
S
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 25 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED
BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT
STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND
SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT
ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. ACOUSTICAL SEALANT.
1/ 4"
M
IN
1. Floor, Side and Ceiling Runners — "J" - shaped runner, min 4 in. deep, with unequal legs of 1 in. and 2 in., fabricated from min 24 MSG (min 20 MSG when Item 4A, 4B or 7 are used) galv steel. Runners positioned with short leg toward finished side of wall. Runners attached to structural supports with steel fasteners located not greater than 2 in. from ends and not greater than 24 in. OC. "E" - shaped studs (Item 2A) may be used as side runners in place of "J" - shaped runners.
2. Steel Studs — "E" - shaped studs installed back to back. "E" - shaped studs secured together with steel screws spaced a maximum 12 in. OC. Fabricated from min 25 MSG galv steel, min 4 in. deep, with one leg 1 in. long and two legs 3/4 in. long. Shorter legs 1 in. apart to engage gypsum liner panels. Cut to lengths 3/8 to 1/2 in. less than floor to ceiling heights.
3. Gypsum Board* — Gypsum liner panels, nom 1 in. thick, 24 in. or 600 mm (for metric spacing) wide. Panels cut 1 in. less in length than floor to ceiling height. Vertical edges inserted in "H" portion of "C-H" studs or the gap between the two 3/4 in. legs of the "E" studs. Free edge of end panels attached to long leg of vertical "J" - runners with 1-5/8 in.
long Type S steel screws spaced not greater than 12 in. OC. When wall height exceeds liner panel length, liner panel may be butted to extend to the full height of the wall.
Horizontal joints need not be backed by steel framing. In System I, butt joints in liner panels are staggered min 36 in. Butt joints backed with 6 in. by 22 in. strips of 3/4 in. thick gypsum wallboard (Item 4). Wallboard strips centered over butt joints and secured to liner panels with six 1-1/2 in. long Type G steel screws, three screws along the 22 in.
dimension at the top and bottom of the strips.
CANADIAN GYPSUM COMPANY — Type SLX UNITED STATES GYPSUM CO — Type SLX USG MEXICO S A DE C V — Type SLX
4. Gypsum Board* — Gypsum panels, with beveled, square or tapered edges, nom 3/4 in. thick, 48 in. or 1200 mm wide, applied vertically or horizontally, secured with 1-1/4 in.
long Type S steel screws spaced 8 in. OC along vertical edges and 12 in. OC in the field when installed vertically or 8 in. OC along the vertical edges and in the field when installed horizontally. Horizontal joints need not be backed by steel framing. Screws along side joints offset 4 in. Requires min 4 in. deep framing per Items 1, 2 and 3. Requires min 3 in.
thick mineral wool batts per Item 6.
CANADIAN GYPSUM COMPANY — Types IP-X3, or ULTRACODE UNITED STATES GYPSUM CO — Types IP-X3, or ULTRACODE USG MEXICO S A DE C V — Types IP-X3, or ULTRACODE
5. Joint Tape and Compound — (Not Shown) Systems: A,B,C,E,F,G,H,I Joints on outer layers of gypsum boards (Item 4 and 4A) covered with paper tape and joint compound.
Paper tape and joint compound may be omitted when gypsum boards are supplied with square edges. Exposed screw heads covered with joint compound.
*Bearing the UL Classification Mark
SYSTEM B - 2 HR.
2 HR SHAFTWALL
PLAN: DESCRIPTION:
UL DESIGN #:
STC RATING:FIRE RATING:
U415
45 - 492 HR
24" O.C.
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
OPENINGS: --
INTERIOR WALL TYPE LEGEND
NOTE: REF GENERAL INTERIOR WALL NOTES, WALL
CONSTRUCTION & PRIORITY DETAILS, AND FIREWALL DETAILS
FOR ADDITIONAL INFORMATION. NOT ALL WALLS WILL BE
TAGGED. REFERENCE SECTIONS, DETAILS, & PLAN NOTES FOR
UNIQUE OR SPECIAL CONDITIONS.
6D
WALL
PRIORITY
WALL TYPE
_A 3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES
_B
NOTE: NOT ALL WALL TYPES ARE USED - REF FLOOR PLANS AND ENLARGED FLOOR
PLANS
3 5/8" MTL. STUD W/ 5/8" GYPSUM BOARD ON (1) SIDE
_C
_D
_E 7/8" MTL FURRING CHANNELS W/ 5/8" GYPSUM BOARD ON (1) SIDE
_G
6" MTL STUD W/ 5/8" GYPSUM BOARD ON BOTH SIDES
2 1/2" MTL STUD W/ 5/8" GYPSUM BOARD ON (1) SIDE
SHAFTWALL - 4" MTL STUDS W/ 2 LAYERS OF TYPE X 3/4" GYPSUM
BOARD ON 1 SIDE AND 1" SHAFT LINER ON THE OTHER REF. WALL
TYPE DETAILS GI 01.10
_F 1 5/8" MTL STUD W/ 5/8" GYPSUM BOARD ON (1) SIDE
EXISTING PARTITION
NEW HALF WALL PARTITION
NEW 1-HR. RATED FIRE PARTITION
(PRIORITY 2)
NEW TEMPORARY PARTITION
EXISTING SMOKE RESISTANT PARTITION
EXISTING ONE HOUR FIRE BARRIER
EXISTING TWO HOUR FIRE BARRIER
PARTITION TO BE DEMOLISHED
WALL LEGEND
NEW SMOKE PARTITION
(PRIORITY 3)
NOTE: REF. SHEET G01.02 FOR WALL TYPE DETAILS
NEW PARTITION
(PRIORITY 4)
STEEL FLOOR AND CEILING CHANNELS.
2 1/2" MTL. STUDS @ 16" O.C.
NOT USED
LINE OF EXISTING WALL.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
NOT USED.
CEMENT BOARD - 5/8" THICK.
3 1/8"
STEEL FLOOR AND CEILING CHANNELS.
3 5/8" MTL. STUDS @ 16" O.C.
NOT USED
LINE OF EXISTING WALL.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
NOT USED.
CEMENT BOARD - 5/8" THICK.
4 1/4"
T O
/2
1/
4"
STEEL FLOOR AND CEILING CHANNELS.
3-5/8" MTL. STUDS @ 16" O.C.
SOUND ATTENUATION BATT INSUL. - 3-1/2"
GLASS FIBER BATTS IN STUD CAVITY.
TYPE X - GYPSUM WALLBOARD - 5/8" THICK.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
74 7/8"
4 7/8" THICK
GYPSUM ASSOCIATION #XXX
XXX STC
STEEL FLOOR AND CEILING CHANNELS.
6" MTL. STUDS @ 16" O.C.
SOUND ATTENUATION BATT INSUL. - 3-1/2"
GLASS FIBER BATTS IN STUD CAVITY.
TYPE X - GYPSUM WALLBOARD - 5/8"
THICK.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
1-5/8" SCREWS 8" O.C. @ EA. STUD.
CEMENT BOARD - 5/8" THICK.
7 1/4"
4 7/8" THICK
GYPSUM ASSOCIATION #XXX
XXX STC
NOT USED
7/8" METAL FURRING CHANNELS @ 24"
O.C.
NOT USED
LINE OF EXISTING WALL.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
NOT USED.
TYPE ' X' GYP. BOARD - 5/8" THICK.
1 1/2"
STEEL FLOOR AND CEILING CHANNELS.
1 5/8" MTL. STUDS @ 16" O.C.
NOT USED
LINE OF EXISTING WALL.
JOINT TREATMENT.
ACOUSTICAL SEALANT.
FLOOR SLAB OR ROOF DECK ASSEMBLY.
NOT USED.
TYPE ' X' GYP. BOARD - 5/8" THICK.
2 1/4"
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs
\l lu tc h e
\D o c u m e n ts \M b o ro V
A R e n o v a ti o n -2
L
L u tc h e
.r v t
/2
/2
:2
:2
P
M
4-30-2019
626A4-18-107
GI 01.10
RENOVATE FOR WHOLE HEALTH
CLINIC
WALL TYPE DETAILS
Author
HFR Project No: 2018130
FINAL BID DOCUMENTS
● USE SEMI-GLOSS PAINT.
● LOCATE NOT MORE THAN 12'-0" O.C. ON CORRIDOR SIDES OF PARTITIONS, AND WITH A LEAST ONE MESSAGE PER ROOM ON ROOM SIDE OF PARTITION, AND WITHIN 15'-0" OF THE END OF EACH WALL.
● STENCIL MESSAGE SIMILAR TO: "SMOKE PARTITION" OR "1-HR FIRE BARRIER."
● IDENTIFY PARTITIONS ABOVE CEILINGS ON BOTH SIDES OF PARTITIONS EXCEPT WITHIN SHAFTS IN RED
LETTERS NOT LESS THAN 4" HIGH WITH AT LEAST A 3/8" STROKE.
12. FIRE AND SMOKE PARTITION / BARRIER IDENTIFICATION:
11. PENETRATIONS IN WALLS SHALL BE SEALED AS REQUIRED BY THE WALL RATING PER AN APPROVED UL
DESIGN.
10. GYPBOARD PANELS SHALL BE PLACED A MINIMUM OF 1/4" ABOVE FLOOR AND SHALL BE CUT WITHIN 1/4" MAX TOLERANCE TO SHAPE OF DECK OR STRUCTURE ABOVE. GAPS BETWEEN PANELS SHALL BE <1/4".
● PROVIDE DEFLECTION AND BRIDGING CLIPS.
● MAINTAIN CLEARANCE UNDER STRUCTURAL BUILDING MEMBERS TO AVOID DEFLECTION TRANSFER TO
STUDS. PROVIDE EXTENDED LEG CEILING RUNNERS.
9. DO NOT TRANSFER DEFLECTION FROM STRUCTURAL BUILDING MEMBERS TO STUDS. CONTRACTOR'S
OPTION, PROVIDE EITHER OF THE FOLLOWING:
8. EXTEND ALL WALL CONSTRUCTION TO THE DECK ABOVE AND SEAL U.N.O.
7. INSTALL ACOUSTICAL GASKETS AT FLOOR AND CEILING TRACK LOCATIONS.
6. PROVIDE ACOUSTICAL INSULATION FULL HEIGHT IN ALL WALLS U.N.O.
5. STAGGER JOINTS ON OPPOSITE SIDES OF PARTITIONS.
4. ALL FRAMING SHALL BE 20 GA U.N.O.
● PROVIDE FIRE RATED IMPACT RESISTANT GYPBOARD 4'-0"H ON ALL WALLS IN PATIENT ROOMS, 4'-0"H AT ALL EQUIPMENT ALCOVES AND ROOMS NOT SCHEDULED TO RECEIVE RIGID WALL PROTECTION, AND
ADDITIONAL LOCATIONS AS NOTED ON DRAWINGS. (IMPACT RESISTANT GYPBOARD SHALL TAKE
PRIORITY AT LOCATIONS INDICATED TO RECEIVE GLASS FIBER FACED GYPSUM PANELS.)
● PROVIDE FIRE RATED GLASS FIBER FACED GYPSUM PANELS ON INTERIOR SURFACE OF EXTERIOR WALLS, TOILET ROOMS, JANITOR'S CLOSETS, MECHANICAL SPACES, AND WITHIN 4'-0" OF WATER...
● ALL GYPBOARD SHALL BE 5/8" TYPE 'X' U.N.O.
3. GYPBOARD REQUIREMENTS:
2. TOILET WETWALLS AND PATIENT ROOM HEADWALLS SHALL BE 6" METAL STUDS
1. ALL WALLS SHALL BE 3-5/8" METAL STUD AT 16"0.C. MAX U.N.O.
REFERENCE WALL TYPE DETAILS, PLANS, AND SPECIFICATIONS.
GENERAL WALL NOTES
NOT TO SCALE
2 1HR FIRE BARRIER
NOT TO SCALE
3 SMOKETIGHT PARTITION
NOT TO SCALE
4 NON-RATED PARTITION
NOT TO SCALE
1 2-HR SHAFT WALL
7 TYPE DTYPE B
TYPE A TYPE C 6 TYPE E
12 TYPE F
GENERAL NOTES
1. THIS IS DIAGRAMMATIC IN NATURE AND SHOWS GENERIC
CONDITIONS. SEE FLOOR PLANS FOR ACTUAL CONDITIONS.
2. MAINTAIN NOTED CLEARANCES AT ALL DOORS.
MIN
18"
M
IN
(A)
FRONT APPROACH, PULL SIDE
M
IN
(B)
FRONT APPROACH, PUSH SIDE
M
IN
(C)
FRONT APPROACH, PUSH SIDE,
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
MIN
12" MIN
36"
M
IN
(D)
HINGE APPROACH, PULL SIDE
M
IN
(F)
HINGE APPROACH, PUSH SIDE
MIN
42"
M
IN
(E)
HINGE APPROACH, PULL SIDE
MIN
22" 48
M
IN
(G)
HINGE APPROACH, PUSH SIDE,
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
MIN
22"
MIN
24"
M
IN
(H)
LATCH APPROACH, PULL SIDE
MIN
24"
M
IN
(I)
LATCH APPROACH, PULL SIDE,
DOOR PROVIDED WITH
CLOSER
M
IN
(J)
LATCH APPROACH, PUSH SIDE
MIN
24" 48
M
IN
(K)
LATCH APPROACH, PUSH SIDE,
DOOR PROVIDED WITH CLOSER
MIN
24"
MIN
18"
M
IN
(A)
PULL SIDE
X > 8"
MANEUVERING CLEARANCES AT RECESSED
DOORS AND GATES
MANEUVERING CLEARANCES AT MANUAL
SWINGING DOORS AND GATES
(B)
PUSH SIDE
M
IN
X > 8"
(C)
PUSH SIDE, DOOR PROVIDED
WITH BOTH CLOSER AND
LATCH
M
IN
X > 8"
MIN
12"
DOORS IN SERIES AND GATES IN SERIES
(A)
48" MIN
(B)
48" MIN
(C)
48" MIN
(BACK)(SIDE CONTROL WALL) (SIDE)
T .O
. S E
A T
SOME ITEMS MAY NOT BE APPLICABLE
HCWV
GB/U GB/U
CONTROL
AREA
GB-24
GB-24
GB-42
HCT
GB-12
DF
HCDF
MIRROR
TPD
TB-18
FPDL
URINAL SCREEN
EXTEND MIN 18"
FROM WALL
BCS
PTD-WR
GB-18
C L P
U
LL
H A
N D
LE
C L F
LU
S
H C
O N
T R
O L
GB-18 INSULATED
SUPPLY AND
DRAIN LINES
TPD
C L F
LU
S
H C
O N
T R
O L
M A
X
M A
X
M A
X
M A
X
M A
X
M
IN
T O
S P
O U
T
M A
X
M
IN
M A
X H
.C . H
T
M
A X
MIN
13 1/2"
TO PLAN)
(REFER
AMBULATORY
36"W (±1")
60"D MIN
59"D MIN: FLOOR MNT WC
66" WIDE
56"D MIN: WALL HUNG WC
17" ±1"
H E
IG
H
T
S T
A N
D A
R D
S U
R F
A C
E
M A
X T
O R
E F
LE
C
T
IV
E
25"MAX
17"MIN
MIN
30"
MIN
60"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G
M A
X
6" MAX
MIN
30" 36" 36"
1"
1"
18"
36"
18"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G 6"
M A
X
1"
M
IN
T O
O U
T
LE
T
M
IN
M A
X
15" MIN
T O
S P
O U
T
M A
X
C O
N T
R O
LS
M A
X T
O
M
IN
30" MIN
MIN
12"
9"
MAX
12"
MIN
24"
MAX
24"
MIN
24"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G 3"
-6
4" MAX
G R
IP
S
U R
F A
C E
T .O
1"
42" MIN
MAX
12"
40" ±1"
S U
R F
A C
E
M A
X T
O R
E F
LE
C
T
IV
E
18" OR 24"
H .C
. H T
M A
X
(FRONT) (SIDE)
M A
X
M
IN
TO PLAN)
(REFER
M
IN9"
CLEAR
30" MIN
4" MAX 32" MIN 32" MIN
1"
4" MAX
1"
(BACK) (CONTROL WALL)
GB/L
CURTAIN
ROD
CONTRO
L AREA
M
IN
M A
X
FLUSH
VALVE
M A
X
6" MAX
36" MIN
60" MIN±1"
17"
GB-36
CLEAR
15" MIN
CLEAR
15" MIN
8" (±1")
M A
X
T O
S P
O U
T
C O
N T
R O
LS
H C
A C
C E
S S
IB
LE
"54
MIN
15"
M A
X
CONTROL
AREA
MAX
15"
M
IN
CONTROL
AREA, IF
SEAT
PROVIDED
PROVIDED
27" MAX
IF SEAT
M A
X
M
IN6" MAX
PTD
M A
X
M A
X
C O
N T
R O
LS
M A
X
SD
M A
X
5" MAX 42
M A
X
C O
N T
R O
LS
EHD EHD-HF
C O
N T
R O
LS
C O
N T
R O
LS
C O
N T
R O
LS
UNOBSTRUCTED ITEMS
MAX
24". 44
M A
X
C O
N T
R O
LS
PAPER TOWEL
DISPENSER & WASTE
RECEPTACLE (PTD-WR)
C O
N T
R O
LSFPDR
PAPER
TOWEL
DISPENSER
(PTD)
ELECTRIC
HAND DRYER
(EHD)
ELECTRIC
HAND DRYER -
HANDS FREE
(EHD-HF)
SOAP
DISPENSER
(SD)
MIN
15" 5" MAX
FEMININE
PRODUCT
DISPENSER
(FNDR)
M A
X
FEMININE
PRODUCT
DISPOSAL UNIT
(FNDL)
SD (ONLY) SD, PTD, EHD
OR EHD-HF
BACK WALL
MOUNTED
OBSTRUCTED ITEMS
SIDE WALL
MOUNTED
H.C.
TELEPHONE
(HCT)
DRINKING
FOUNTAIN
(DF)
H.C.
DRINKING
FOUNTAIN
(HCDF)
(FRONT) (SIDE)
TOILET PAPER
DISPENSER
(TPD)
TOWEL BAR
18" MIN
(TB-18)
BABY CHANGING STATION
(BCS)
TYPICAL PARTITION SPACING
(RE: ENLARGED PLANS FOR ACTUAL DIM'S & SPEC'S FOR ACTUAL TYPE OF PARTITIONS)
18" ±1
MIN
12".
MIN
24".
G R
IP
S
U R
F A
C E
T .O
HC WATER CLOSET
(HCWC)
GRAB BAR
42" (GB-42)
(SIDE) (FRONT)
GRAB BAR
18" (GB-18)
GRAB BAR
36" (GB-36)
M
IN
54" MIN
HC LAVATORY
(SIDE) (FRONT)
COAT HOOK
(CH)
(FRONT) (SIDE)
(FRONT)
MIRROR WITH OR
WITHOUT SHELF
(MIR/S-18X36)
(MIR-18X36)
(MIR/S-24X36)
(MIR-24X36)
(CONTROL)
GRAB BAR
18" (GB-18)
HC BATHTUB
(HCBT)
NOTE: BATHTUBS SHALL DELIVER
WATER THAT IS 120 DEGREES MAX.
GRAB BAR
24" (GB-24)
(BACK) (HEAD)
GRAB BAR
12" (GB-12)
M
IN
S U
R F
A C
E
T .O
G
R
IP
P
IN
G
REMOVABLE IN-TUB
SEAT MIN 15"-16"
MAX DEEP
ROLL IN SHOWER
(RS)
CONT. "U" SHAPED GRAB
BAR (GB/U)
MAX
6"
MAX
6"
GB/L
CONT. "L" SHAPED GRAB BAR
(GB/L)
TRANSFER SHOWER
(TS)
(SIDE)
(CONTROLS ON ANY WALL
IF NO SEAT IS PROVIDED)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs
\l lu tc h e
\D o c u m e n ts \M b o ro V
A R e n o v a ti o n -2
L
L u tc h e
.r v t
/2
/2
:2
:3
P
M
4-30-2019
626A4-18-107
GI 01.20
RENOVATE FOR WHOLE HEALTH
CLINIC
ACCESSIBILITY DETAILS
Author
HFR Project No: 2018130
FINAL BID DOCUMENTS
NOT TO SCALE
ACCESSIBLE DOOR CLEARANCES
NOT TO SCALE
TYPICAL TOILET FIXTURE AND ACCESSORY MOUNTING REQUIREMENTS
FEC
F E
C
FEC
C=18015'-0"
POINT OF EGRESS
TRAVEL DISTANCE
POINT OF DECISION
FIRE EXTINGUISHER CABINET
FIRE ALARM PULL
EGRESS CAPACITY (EXIT WIDTH/.2)
LINE OF TRAVEL
F
FEC
EXIT EXIT LOCATION
ROOM NAME
ROOM #
AREA
OCCUPANT LOAD
ROOM TAG
LIFE SAFETY LEGEND
FIRE EXTINGUISHERFE
EXIT SIGN (SINGLE SIDED)
EXIT SIGN WITH DIRECTIONAL ARROWFIRE ALARM VISUAL ALARMF
FIRE ALARM AUDIO/VISUAL ALARMF
FIRE ALARM ANNUNCIATOR PANELFAA
FIRE ALARM CONTROL PANELFACP
SMOKE DETECTORD
EXISTING PARTITION
NEW HALF WALL PARTITION
NEW 1-HR. RATED FIRE PARTITION
(PRIORITY 2)
NEW TEMPORARY PARTITION
EXISTING SMOKE RESISTANT PARTITION
EXISTING ONE HOUR FIRE BARRIER
EXISTING TWO HOUR FIRE BARRIER
PARTITION TO BE DEMOLISHED
WALL LEGEND
NEW SMOKE PARTITION
(PRIORITY 3)
NOTE: REF. SHEET G01.02 FOR WALL TYPE DETAILS
NEW PARTITION
(PRIORITY 4)
CORRIDOR
B2-G31
CORRIDOR
B2-G30
CORRIDOR
B2-G27
CORRIDOR
B2-G29
STAIR
B2-G10
MECH.
B2-G09
ACUPUNCTURE
EXAM
B2-G37
EXAM
/CONS. /PT. /
CHIRO 1
B2-G38
EXAM
/CONS. /PT. /
CHIRO 2
B2-G39
FLEX PT
EXAM/ GEN.
PURPOSE
B2-G40
GROUP
EXERCISE
B2-G41
PT/EXAM
B2-G52
PT/EXAM
B2-G53
PT/EXAM
B2-G55
PT/EXAM
B2-G54
LOUNGE/CONF.
B2-G57
SOILED
B2-G51
SUPPLY
B2-G56
TLT/DRESS
B2-G44
ACU./
TRTMT 2
B2-G42
TLT
B2-G58
TLT
B2-G59
WAITING
B2-G35
CHIRO.
/TRTMT 4
B2-G45
CHIRO.
/TRTMT 3
B2-G46
CHIRO. /
TRTMT 2
B2-G47
CHIRO./
TRTMT 1
B2-G48
BIO. /FB.
/STRESS
RED.
B2-G49
ACU./
TRTMT 1
B2-G43
CLEAN
STORAGE
B2-G50
STAIR
B2-G16
RECEPTION
/WORK
B2-G36
C O
R R
ID
O
R
B -G
B
CORRIDOR
B2-G35A
C O
R R
ID
O
R
B -G
D
PASSAGE
B2-G35E
CORRIDOR
B2-G35C
STAIR
B2-G34
MECH.
B2-G20
DATA
B2-G20B
ELEC. SWITCH
GEAR
B2-G18
MAS
RECORDS/
SHRED
B2-G19
ELEC.
B2-G22
ELEC.
B2-G22A
SUPPLY
SERVICES
(FULL GAS
BOTTLE
STOR.)
B2-G23
DELIVERY
B2-G23A
ELEC. POWER
DIST.
B2-G24
STORAGE
B2-G24ACONTAMINATED
STORAGE
B2-G25
MECH.
B2-G21
TELE.
B2-G20A
KITCHEN
STOR.
B2-G08E
FEMALE
LOCKER
B2-G08C
KITCHEN
STOR.
B2-G02
ELEVATOR
LOBBY
B2-G01
STAIR
B2-G04
OFFICE
B2-G06E
OFFICE
B2-G06D
OFFICE
B2-G06A
OFFICE
B2-G06B
MALE TLT.
B2-G08A
FEMALE TLT.
B2-G08D
BREAK ROOM
B2-G08B
MALE LOCKER
B2-G08
AGENT
CASHIER
B2-G07C
TRAVEL
B2-G07
CORRIDOR
B2-G06
STOR.
B2-G06C
OFFICE
B2-G06F
HAC
B2-G06G
OFFICE
B2-G06H
ELEC.
B2-G11A
QUEING
B2-G07B
NURSING
B2-G11G
NEW PT C&P
EXAM
B2-G12A
NEW PT EXAM
B2-G12B
NEW PT
ACCESS
CLINIC
B2-G12
WAITING
B2-G12I
BUSINESS
OFFICE
B2-G15C
STAIR
B2-G13
NF SERVICE
B2-G12H
OFFICE
B2-G12G
WORK
B2-G12D
OFFICE
G35IIIII
CLASSROOM
B2-G12C
DIABETES
NURSE
B2-G12E
CHIEF
OUTPATIENT
SERVICES
B2-G11D
OIF/OEF
B2-G12K
RELEASE OF
INFO.
B2-GG15A
OIF/OEF
TRANSITION
PAT. ADV.
B2-G12J
COAT ROOM
B2-G15
BUSINESS
OFFICE
B2-G15D
STAIR
B2-G33
CONNECTOR
B2-G33A CONNECTOR
B2-G34A
OUTPATIENT
SERVICES
B2-G11
OFFICE
B2-G11C
OFFICE
B2-G11E
OFFICE
B2-G11B
OFFICE
B2-G11F
CORRIDOR
B2-G32
VCS STOR.
B2-G24B
WAITING
B2-G07A
ALCOVE
B2-G06I
ELEVATOR
B2-G03
ELEVATOR
B2-G05
STOR.
B2-G23C
STOR.
B2-G23D
STORAGE
B2-G23B
STORAGE
B2-G23E
EMERGENCY
GEN.
B2-G35Y
CONNECTOR
B2-G27A
MECH. SPACE
B2-G25A
EXIT
EXITEXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT EXIT
2012 IBC - SECTION 713.4-
2-HR FIRE RATING FOR STAIRS AND
SHAFTS IF 4 STORIES OR MORE
CONNECTED. IF 3 STORIES OR LESS
CONNECTED, 1-HR FIRE RATED.
97' - 6" TO EXIT
140' - 0" TO EXIT
2012 NFPA 101 - SEC. 19.2.3.4 -
ANY REQUIRED AISLE, CORRIDOR, OR
RAMP SHALL BE NOT LESS THAN 48 INCHES
IN CLEAR WIDTH SERVING AS MEANS OF
EGRESS FROM PATIENT SLEEPING ROOMS,
UNLESS OTHERWISE PERMITTED BY ONE
OF THE FOLLOWING:
2012 NFPA - SEC. 19.2.3.4(1) -
AISLES, CORRIDORS, AND RAMPS IN
ADJUNCT AREAS NOT INTENDED FOR THE
HOUSING, TREATMENT, OR USE OF
INPATIENTS SHALL BE NOT LESS THAN. 44
INCHES IN CLEAR AND UN-OBSTRUCTED
WIDTH.
2012 IBC - TABLE 1018.2
MINIMUM CORRIDOR WIDTH IS 44 INCHES
BECAUSE NO BED MOVEMENT IN
CORRIDORS AND NO OUT-PATIENTS
INCAPABLE OF SELF PRESERVATION WILL
BE OCCURING IN THE SUITE.
BUILDING 1:
2 @ 48" = (2)(48) / .2 = 480
TOTAL EXIT CAPACITY = 480
EXIT CAPACITY:
OCCUPANCY LOAD FACTORS:
BUILDING 2 GROUND FLOOR:
BUSINESS = 4,790 NSF (100 NSF/OCC)
= 47 OCCUPANTS
TOTAL OCCUPANT LOAD = 47
BUSINESS OCCUPANCY HATCH
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C U s e rs
\a tr a y lo r\ D e s k to p \R e v it P ro je c ts
\M b o ro
V A
R e n o v a ti o n -2 a tr a y lo r.
rv t
/2
/2
:4
:2
P
M
4-30-2019
626A4-18-107
GI 02.01A
RENOVATE FOR WHOLE HEALTH
CLINIC
BLDG. 2 - GROUND FLOOR LIFE SAFETY
PLAN
Author
HFR Project No: 2018130
FINAL BID DOCUMENTS
4. REMOVE EXISTING ANNEALED OR OTHERWISE NON-SAFETY-RATED GLASS FROM EXISTING DOORS, SIDELIGHTS, AND OTHER HAZARDOUS LOCATIONS SCHEDULED TO REMAIN WITHIN PROJECT AREA. IN NON-RATED OPENINGS, PROVIDE NEW TEMPERED GLASS TO MATCH ORIGINAL DESIGN. IN RATED OPENINGS, PROVIDE NEW IMPACT-RESISTANT, FIRE-RATED GLASS TO MATCH ORIGINAL CONFIGURATION, RATED NO LESS THAN
SURROUNDING WALL CONSTRUCTION.
3. EXIT PATHS SHALL BE MAINTAINED CLEAR OF EQUIPMENT, MATERIALS AND DEBRIS AND SHALL BE MARKED WITH
APPROVED EXIT SIGNS VISIBLE AT ALL TIMES.
2. TEMPORARY PARTITIONS REQ'D FOR DUST OR INFECTION CONTROL SHALL BE CONSTRUCTED TO MAINTAIN EXISTING FIRE BARRIER REQUIREMENTS. WHERE TEMPORARY PARTITIONS MUST INCLUDE DOORS FOR CONSTRUCTION ACCESS OR LIFE SAFETY EGRESS, INSTALL DOOR ASSEMBLIES EQUAL IN RATING TO THE CONSTRUCTION BEING PENETRATED WITH POSITIVE LATCHING HARDWARE AND EXIT DEVICES (PANIC BARS)
WHERE REQ'D.
1. ALL EXISTING PARTITIONS INDICATED TO REMAIN SHALL BE UPGRADED TO RATING NOTED IF THEY OCCUR ON OR IN A SMOKE COMPARTMENT WITHIN CONSTRUCTION AREA. EXTENT OF UPGRADE SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, EXTENDING PARTITIONS TO UNDERSIDE OF DECK, INSTALLING BLOW-OUT PATCHES, RECONSTRUCTING INTERSECTIONS AT OTHER PARTITIONS, INSTALLING UL APPROVED FIRESTOP SYSTEM AT WALL PENETRATIONS, RE-INSTALLING FIRE AND/OR FIRE/SMOKE DAMPERS, INSTALLING FIVE-SIDED ENCLOSURES OF RECESSED ITEMS, INSTALLING ADDITIONAL FRAMING, AND INSTALLING 12” WIDE STRIPS OF G.W.B OVER JOINTS NOT OFFSET FROM OPPOSING SIDE. AT CONTRACTOR'S OPTION, PARTITION MAY BE COMPLETELY STRIPPED AND REBUILT. ALL SERVICES WITHIN PARTITION MUST BE MAINTAINED AND FINISHES
RESTORED REGARDLESS OF COURSE OF ACTION.
RENOVATION WORK
15. REFER TO THE CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION RELATED TO LIFE SAFETY
CONSTRUCTION AND APPROVED UL ASSEMBLIES.
● PROVIDE WET-CHEMICAL TYPE, CLASS K WALL-HUNG FIRE EXTINGUISHERS THROUGHOUT KITCHENS.
LOCATE SO THAT A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET OF TRAVEL FROM ANY PIECE OF
COOKING EQUIPMENT BELOW HOOD WILL BE PROVIDED.
● PROVIDE CLEAN AGENT TYPE FIRE EXTINGUISHERS WITH UL RATING OF 1A:10B:C IN EACH DATA CENTER, MRI ROOM, AND MRI CONTROL ROOM. LOCATE SO THAT A MAXIMUM OF 75 FEET OF TRAVEL FROM ANY
SPACE WILL BE PROVIDED.
● PROVIDE DRY CHEMICAL, ABC TYPE FIRE EXTINGUISHERS WITH UL RATING OF 4A:60B:C IN ALL
MECHANICAL SPACES.
● PROVIDE MULTI-PURPOSE, DRY CHEMICAL, ABC TYPE FIRE EXTINGUISHERS WITH UL RATING OF 4A:60B:C THROUGHOUT THE ENTIRE BUILDING. LOCATE SO THAT A MAXIMUM OF 75 FEET OF TRAVEL FROM ANY
SPACE WILL BE PROVIDED.
14. FIRE EXTINGUISHER LOCATIONS: PROVIDE AS SHOWN ON PLANS AND AS INDICATED, WHICHEVER IS MORE
RESTRICTIVE. CABINETS SHALL BE FULLY RECESSED (U.N.O.):
13. DOORS, WINDOWS, AND OTHER OPENINGS SHALL BE RATED EQUAL TO THAT OF THE CONSTRUCTION BEING PENETRATED. PROVIDE POSITIVE LATCHING AT RATED DOOR ASSEMBLIES. GLAZING SHALL BE FIRE RATED EQUAL TO THE WALL CONSTRUCTION AND INSTALLED IN AN EQUALLY RATED FRAMING SYSTEM, TESTED AS AN
ASSEMBLY. WIRE GLASS IS NOT PERMITTED.
12. WHERE FIRE RATED WALL ASSEMBLIES OCCUR IN PROXIMITY TO STEEL BEAMS OR JOINTS WITH INADEQUATE DIMENSION TO INSTALL SCREWS, PROVIDE STUD FRAMING AROUND THE BEAM OR JOIST IN ACCORDANCE WITH U.L. DESIGN N-501 WITH LAYERS OF G.W.B. EQUAL IN NUMBER TO THE WALL ASSEMBLY CONSTRUCTION.
11. WHERE PARTITIONS MUST BE CONNECTED TO STRUCTURE FOR SUPPORT, INSTALL 20 GUAGE GALVANIZED METAL Z-CLIPS SPACED AS REQ'D, BUT NOT MORE THAN 2'-0” O.C. PRIOR TO APPLICATION OF FIREPROOFING.
10. WHERE DEVICES, CABINETS, OR ACCESSORIES GREATER THAN 16 SQ. IN. ARE INDICATED IN RATED CONSTRUCTION, PROVIDE A FIVE-SIDED G.W.B. ENCLOSURE CONSTRUCTED OF LAYERS OF G.W.B. EQUAL IN
NUMBER TO THE CONSTRUCTION BEING PENETRATED.
9. WHERE DEVICES ARE INDICATED IN RATED CONSTRUCTION, THE MAXIMUM ALLOWABLE AREA OF INDIVIDUAL U.L.
LISTED BACKBOXES PERMITTED IN THE WALL IS 16 SQ. IN. WITH MAXIMUM AGGREGATE AREA OF 100 SQ. IN PER 100 SF OF WALL AREA. BACKBOXES ON OPPOSITE FACES OF RATED WALLS SHALL BE OFFSET A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. WHEN PENETRATIONS EXCEED THE ALLOWABLE AREAS, DEVICES SHALL BE PROVIDED WITH A FIVE-SIDED G.W.B. ENCLOSURE OR UL LISTED INTUMESCENT FIRE PUTTY.
8. PROVIDE ENCLOSURE AND ACCESS PANEL AT EACH FIRE PROTECTION INSPECTION TEST VALVE. DO NOT LOCATE VALVES AND PIPES IN EXTERIOR WALLS. PROVIDE PAINTED STEEL ACCESS PANELS IN WALLS &
CEILINGS EQUAL IN RATING TO THE CONSTRUCTION BEING INSTALLED IN.
7. INSTALL METALLIC SLEEVES AROUND LOW VOLTAGE CABLES THAT PENETRATE THE WALL, AND SEAL AROUND
THE SLEEVE AND INSIDE THE SLEEVE WITH AN APPROVED SEALANT.
6. INSTALL G.W.B.