Drawings 561-25-125 Replace Pumps for Chillers.pdf

PDF 6 MB Posted

Attached to
Y1DA--Project # 561-25-125 Replace Pumps for Chillers at the East Orange VAMC
Solicitation number
36C24226B0006_1
Issued by

About this file

These are design and construction drawings for a U.S. Department of Veterans Affairs (VA) project to replace pumps for chillers at the East Orange VA Medical Campus located at 385 Tremont Avenue in East Orange, New Jersey. The project number is 561-25-125 and involves replacing existing condenser water pumps (CWP-1, CWP-3) and chilled water pumps (CHP-1) with new pumps, along with associated Variable Frequency Drives (VFDs) and electrical modifications. The engineering work is being performed by Miller-Remick LLC, a Service-Disabled Veteran-Owned Small Business, with the project issued for bid and marked as fully sprinklered. The drawings include detailed mechanical and electrical plans for demolition, piping, power connections, and control systems, with specific notes about maintaining facility operations during construction and coordinating work with existing systems.

The technical scope includes removing existing vertical deep well condenser water pumps and chilled water pumps, installing new pumps with inertia bases, modifying electrical connections by splicing and extending existing power feeders to new wall-mounted VFDs, and bypassing existing pump starters in the Motor Control Center (MCC) so they function only as circuit breaker disconnecting means. The project requires careful coordination with facility personnel to minimize disruption, with specific instructions to schedule work during off-peak hours and ensure all systems remain operational. The design incorporates detailed flow diagrams, control sequences, and notes about integrating new equipment with the existing Building Automation System (BAS).

View the file

Other files

File Type Posted
36C24226B0006 0001 IFB Amend.pdf PDF
36C24226B0006_1 IFB-.pdf PDF
852.219-75 Limitation on Subcontracting.pdf PDF
36C24226B0006_1 IFB.pdf PDF
Buy American Certificate.pdf PDF
wages.pdf PDF
Specs 561-25-125 Replace Pumps for Chillers.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

m C

A 0

" 0 m ti m

N

C

N

.c u m

'" ~ 0 E

N N

D tj- N co N I r---

I r---

"" " "D m L

-.c u L

0 -m Q_

E Q_

'" u Q_

'" Q'

E 0 Cl

'" '" .c 1/)

L u

I '" m .c [l_

;c E .a

1/)

C

'" L L u I

"D u

I F /" m

"' C

" 0 L

I tj-m L

.c u

'" "' C L m w N

I

"' "' tj-

I "' "' tj- [l_

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

NO. DESCRIPTION DATE

VA FORM 08-6231

' 3B5 Tremont Avenue

Veteraris Affairs P-'11 Medlta l Ci:!lltt!r ...

"LOCATION MAP" OR "SITE PLAN"

SCALE: NTS

CONSULTANT

2 3

4 5 6 7

REPLACE PUMPS FOR CHILLERS

DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 561-25-125

GIOOI

GI002

M-001

MD101

MP102

MP103

M-501

M-601 M-801

GENERAL

VA EAST ORANGE CAMPUS

385 TREMONT AVE

EAST ORANGE, NJ 07018

DRAWING INDEX

COVER SHEET & DRAWING INDEX E-001

E-002

ED101

ICRAPLAN AND CONSTRUCTION ACCESS PATHWAY -GROUND FLOOR

ELECTRICAL

ABBREVII\TIONS & SYMBOLS

ELECTRICAL NOTES

DEMOLITION PLAN

EP101 POWER PLAN

MECHANICAL

ABBREVL'\TIONS. NOTES AND SYMBOLS

DEMOLITION PLAN

PIPING PLAN & ELEVATION GROUND FLOOR

PIPING PLAN GROUND FLOOR

DETAILS

FLOW DII\GRAMS

CONTROLS FLOW DIAGRAMS

ENGINEER OF RECORD MILLER-REMICK LLC

PROFESSIONAL ENGINEER Office of

Construction and Facilities Management

Drawing TiUe

COVERSHEET

Miller-Remick LLC ~ ..... ) M.E.P. & Structural Engineering rsavoss \ A SeNice Disabled Veteran Owned :-,_ J Small Business • •v•

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

MR PROJECT NO: 0499-0120

VA

U.S. Department of Veterans Affairs

Approved: Project Director

BUILDING KEY PLAN

SCALE: NTS

Phase

ISSUED FOR BID

FULLY SPRINKLERED

PLAN

NORTH

EB

ACTUAL

NORTH

D t:j ~~~~ -... %1

L

KEYPLAN

Project Title

EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

DD

D

D

0 0

0 0

0 0

0 0

PLAN

NORTH

EBTUAL

NORTH

Project Number

561-25-125 Building Number

Location I Drawing Number

VA EAST ORANGE CAMPUS _

Issue Date

2025-07-16

Checked

LM r;J GI001

A

B

C

D

E

F

.,. ~c.., jj ~o

A

C

= u w

"' -0

E s,- 'f!

D <.D N

"' N I r--- I r---

O> ,, w L u L 0 -w o_

E o_

"' u o_

"' De:

E N L?

/" -"' "' = V)

L u

I "' w = o_

0 --"E' .D

V)

C

"' L L u I

"D u

F I w O> C -,, L

D I s,-w L

"' -:c u

"' O> C L

0 -w w N

I a, a, -a-

"i D

I a, a, s,- (L

1 2 3 4 5 6

CONSTRUCTION PATH 4 5 6

A\------+~~~~~~~~~F~~~~~~(--t~~~~~~~~~~~~~~~~~~~~~--++-~A

B-136 I.V.

3TORAGE

OFFICE

B-134

B

STAIR5

B-S5

ELEC.CLO.

B-E-105

B-137A

PROCESS

STORES

STORAGE

LINEN

ROOM

B-1340

CLOSET

B-134A

CORRIDOR

B-133

CORRIDOR

B-137C

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. CONSULTANT

NO. DESCRIPTION DATE

VA FORM 08-6231

1 2

' ' B ~rr-------r=--,::=---=;:r- 1 T B

C >--t-----,...--

E

WALK-IN

COOLER

B-12BA

F

WALK-IN

COOLER

B-128B

B-128C

WALK IN

REFRIG

I i

J

0 MECHANICAL

ROOM

B-128

, I k- - --- --- --- --- --- i - - --- --- --- --- - r~r

' ' J l J

I ' ' I - I

I - -

REFRIG

B-118

CORR.

B-117 r SUPERVISOR

FOOD

SERVICE

I w I

I I

-f--

' ' ( B-116 / B-114

GENERAL

STORAGE I

' MECHANICA L'

ROOM I B-128

I I w - I I I I I_ -

0 0

UTILITY

SHOP

B-119C

MECHANICAL

ROOM

B-128D

------~' '~~ C..,C99~=========,r'/ L__ ~------, ~

REFRIG

B-119 REFRIG

B-120

STORAGE

FOOD

SERVICE

B-115

STAIR6

Br__.-11,--------l)

FL:

7.__

I I I

ICRA,

CONSTRUCTION ACTIVITY "TYPE C"

RISK LEVEL "MEDIUM"

CLASS 0 111"

B-110

KITCHEN

n

CORR.-._____

B-113 \

II )< B-112 L/ SUPERVISOR

DIET.

OFFICE

I

B-111

CHIEF

DIETETICS

OFFICE

C

I 0 E

' F

I r

X ,. 1 ; I~~ ,i.l!-~_

.~ND CONSTRUCTION ACCESS PATHWAY - GROUND FLOOR

ENGINEER OF RECORD

Miller-Remick LLC E, ..... ) M.E.P. & structural Engineering lsrn,oss \ A Service Disabled Veteran Owned \ ../, Small Business • :v:

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

MR PROJECT NO: 0499-0120

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Office of Construction and Facilities Management

VA U,S, Department of Veterans Affairs

B-401

IRM

CLOSET

Drawing Title

/I I

ICRA PLAN AND CONSTRUCTION

ACCESS PATHWAY

GROUND FLOOR

Approved: Project Director

CRAWL S

CRAWL S

I I

Phase

9 10

GENERAL SHEET NOTES:

1. WORK THIS DRAWING WITH SPECIFICATIONS 013526 AND THE INFECTION PREVENTION

AND CONTROL CONSTRUCTION/RENOVATION/MAINTENANCE PERMIT.

© SHEET KEYNOTES:

I. SEAL DOOR THAT LEADS TO KITCHEN FROM MECHANICAL ROOM B-128D

LEGEND:

VZZ/~/21

CONSTRUCTION PATH

PLASTIC BARRIER

CONSTRUCTION AREA

KEYPLAN

0 0

0 0

0 0

0 0

PLAN

NORTH

EBTUAL

NORTH

Project Tltle Project Number

561-25-125

ISSUED FOR BID

EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

Building Number

FULLY SPRINKLERED

ILocv~"EAST ORANGE CAMPUS I Drawing Number

Issue Date

2025-07-16

~F°I GI002

A

B

C

D

"' 0 ,Q C

A 0

II

.5

N

C

N

D

E

F

= u w

E

N m N D

"' N I r--

I r--m

" D

'" L w ·-= u

L

0 -o_

E o_ w u o_ w ct'.

= cn L w u

D D I

·" C = u w

I

CD

w

= o_

"" E _o en C w L L u I

D u

I m C

" 0 L

D I tj-

L w

= u w

"' C L w D N

D I m m tj-j;

D

I m m tj- D o_

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

NO. DESCRIPTION DATE

VA FORM 08-6231

MECHANICAL ABBREVIATIONS

(A) ABANDONED

A/E ARCHITECT/ENGINEER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR COOLED CONDENSING UNIT

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AJFTER FILTER

AFF ABOVE FINISHED FLOOR

AFMO AIR FLOW MEASURING DEVICE

AHU AIR HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AV AUTOMATIC AIR VENT

B BOILER

BAS BUILDING AUTOMATION SYSTEM

BD SLOWDOWN

BOD BACKDRAFT DAMPER

BBR BASE BOARD RADLI\TOR

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BTO BOTTOM TAKE-OFF

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

cc COOLING COIL

CD CEILING DIFFUSER

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CU FT CUBIC FEET

CH CHILLER

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

Cl CAST IRON co CARBON MONOXIDE co CLIEAN OUT

CO:, CARBON DIOXIDE

COMP AIR COMPRESSOR

COR CONTRACTING OFFICER REPRESENTATIVE

COP COEFFICIENT OF PERFORMANCE

GP CONDENSATE PUMP

CSG CLIEAN STEAM GENERATOR

CT COOLING TOWER

cu CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

cw COLD WATER (POTABLE) cwcc CHILLED WATER COOLING COIL

CWR CONDENSING WATER RETURN

cws CONDENSING WATER SUPPLY

(D) DEMOLISH

Db DECIBELS

DB DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DP DEW POINT TEMPERATURE

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

(E) EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EAV EXHAUST AIR VALVE

ECC ENGINEERING CONTROL CENTER

ECM ELECTRICALLY COMMUTATED MOTOR

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILILE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EJ EXPANSION JOINT

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EWT ENTERING WATER TEMPERATURE

EX EXISTING

EXH EXHAUST

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SD COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FD FIRE DAMPER

FF FINAL FILTER

FLR DR FLOOR DR

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

H HUMIDIFIER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HCU HEATING & COOLING UNIT

HD HEAD

HOA HAND/OFF /AUTOMATIC

HP HORSEPOWER

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

CONSULTANT

3 4

HX HEAT EXCHANGER

HZ HERTZ

1/0 INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ID INSIDE DIAMETER

IN INCHES

IN HG HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTERGRATED PART LOAD VALUE

IRH INTRARED HEATER

kW KILOWATT kWH KILOWATT HOUR

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

MAT MIXED AIR TEMPERATURE

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MIN MINIMUM

MOD MOTOR OPERATED DAMPER

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MV MANUAL AIR VENT

(N) NEW

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NO NORMALLY OPEN

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTDOOR AIR

OBD OPPOSED BLADE DAMPER

OD OUTSIDE DIAMETER

OED OPEN END DUCT

p PUMP

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRT PRESSURE REDUCING TERMINAL

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH - ABSOLUTE

PSIG POUNDS PER SQUARE INCH - GAGE

(R) RELOCATE

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

RAV RETURN AIR VALVE

RCP RADIANT CEILING PANEL

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SAV SUPPLY AIR VALVE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCI SPINAL CODE INJURY

SD SMOKE DETECTOR

SF SUPPLY FAN

SHC STEAM HEATING COIL

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SQ IN SQUARE INCH (INCHES)

SRV SAFETY RELIEF VALVE

ss STAINLESS STEEL

SSF SIDE STREAM FILTER

ST STEAM TRAP

SWHX STEAM TO WATER HEAT EXCHANGER

(T) TEMPORARY

TAB TESTING, ADJUSTING, & BALANCING

TCV TEMPERATURE CONTROL VALVE

TDH TOTAL DYNAMIC HEAD

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

V VALVE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL BALANCING)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

w WATTS

WAG WASTE ANESTHESIA GAS

WB WET-BULB (TEMPERATURE)

WC WATER COLUMN

WCCH WATER COOLED CHILLER

wccu WATER COOLED CONDENSING UNIT

WG WATER GAGE

WMS WIRE MESH SCREEN

WPD WATER SIDE PRESSURE DROP

3 4

CONTROLS SYMBOLS

BACNET COMMUNICATIONS

ENGINEERING CONTROL CENTER (BAS)

HAND SWITCH (HAND-OFF-AUTO SWITCH)

START-STOP

VARIABLE FREQUENCY DRIVE

DRAWING SYMBOLS

0 KEY NOTE SYMBOL

@ DETAIL NUMBER

x!x --- DRAWING NUMBER WHERE

DRAWN

&-- SECTION LETTER

X;X DRAWING NUMBER WHERE

SHOWN

BUILDING NO. WHERE

~ EQUIPMENT IS LOCATED.

~HEAT EXCHANGER NUMBER

"'- EQUIPMENT ABBREVIATION

(HEAT EXCHANGER)

/ ITEM (TERMINAL UNIT SHOWN)

TU 42 I / ITEM NUMBER (TERMINAL UNIT

NO. 1)

SERVED BY AIR HANDLER

UNIT NO. 42

0 POINT OF DISCONNECTION

8 POINT OF CONNECTION -

NEW TO EXISTING

- - 1 HOUR RATED PARTITION _ , , _

2 HOUR RATED PARTITION

----- SMOKE RATED PAIRTTION

ENGINEER OF RECORD

Miller-Remick LLC M.E.P. & Structural Engineering J A Service Disabled Veteran Owned 'i SmalJ Business

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (858)429-4000

FAX: (858)429-51)()2

MR PROJECT NO: 0499-0120

PIPING SYMBOLS

T

---;·I--;--

---1[81--;--

---11Z1r---

---11Jlr---

0--"-{

-----lllll]f---iv £wv 9;

----1@1---

,.,,,, V ..._,. ®

Gil ►◄ - • i.

-----l><J--11><1f-

--,: ~:t---

------j):(J-i1><1f-

--111>----

----<Ki">---

VI<(;~----

--t><)----[

------iN--ls;J;

I' f-

--~f---

------j~-

-----l~-

------j~-

---i;/:>t---

-----l:tJ,,_1 --

-----l~--

---1r-<( -

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

DIRECTION OF PIPE PITCH (DOWN)

DIRECTION OF FLOW

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45' OR 90'

BOTTOM CONNECTION, 45' OR 90'

CAIPPED OUTLET

RISE OR DROP IN PIPE

UNION

FLANGE

PIPE UP

PIPE DOWN

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

FLOAT & THERMOSTATIC TRAP SET

INCLUDING PIPING ACCESSORIES SEE DETAIL

THERMOSTATIC TRAIP SET INCLUDING PIPING

ACCESSORIES SEE DETAIL

THERMOMETER

PRESSURE GAGE

FLEXIBLE CONNECTION

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

EXHAUST HEAD

SAFETY RELIEF VENT WEATHER CAP

QUICK-COUPLE HOSE CONNECTOR

HUMIDISTAT

THERMOSTAT

STATIC PRESSURE SENSOR

DIFFERENTIAL PRESSURE SENSOR

PUMP

REFRIGERANT SIGHT GLASS

HUMIDIFIER

BACKFILOW PREVENTER

VALVE - NORMALLY CLOSED

GATE VALVE - THREADED/FLANGED

GATE VALVE WITH GLOBE VALVE BYPASS

GLOBE VALVE - THREADED/FLANGED

BUTTERFLY VALVE

BALL VALVE

ISOLATION VALVE IN RISER

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE & HOSE

CONNECTION)

WYE STRAINER WITH VALVED DRAIN AND

QUICK-COUPLE HOSE CONNECTOR

ANGLE GLOBE VALVE

MODULATING CONTROL VALVE

MODULATING CONTROL BUTTERFLY VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

PRESSURE REDUCING VALVE (PRV)

RELIEF VALVE (STEAM OR HYDRONIC)

VACUUM BREAKER

AUTOMATIC BALANCING CONTROL VALVE

CIRCUIT SETTER VALVE

WATER BALANCE DEVICE

TRIPLE DUTY VALVE (ISOLATION, BALANCE,

& CHECK)

PLUG VALVE

FLOAT-OPERATED CONTROL VALVE

Office of Construction and Facilities Management

VA U.S. Department of Veterans Affairs

7 8

HVAC NOTES AND CONDITIONS:

1. CONTRACTOR SHALL TEST ADJUST & BALANCE THE COMPLETED SYSTEM. ALL

BALANCING WORK SHALL BE DONE UNDER THE DIRECT SUPERVISION OF AN MBC

OR NEBB-QUALIFIED SUPERVISOR WHO SHALL CERTIFY THE RESULTS.

2. TEST, ADJUST AND BALANCE WORK WILL DEMONSTRATE THAT ALL SYSTEMS

OPERATE AS THEY WERE INTENDED TO. UPON COMPLETION OF THE WORK A

WRITTEN TEST AND BALANCE REPORT WILL BE SUBMITTED TO THE OWNER. FORMS

AND PROCEDURES UTILIZED FOR THIS WORK WILL BE AS PROPOSED BY THE MBC

OR OTHER NATIONALLY RECOGNIZED ORGANIZATION ACCEPTABLE TO THE OWNER.

PIPING SYMBOLS

Drawing Title

A

BO

--- BWS --

___ CBD ---

CF

---- CHR ---

CHS

--- CTIPD --

___ CTPS ---

CW

---- CWR ---

CWS

D

--- FOR --

___ FOS ---

---FWPD---

---FWPS---

G

--- G(I) ---

---- GCR ----

GCS

---- GHR ---

GHS

---- GRR ----

GRS

---- HPR ---

___ HPS --

---- HWR ---

___ HWS --

---- LPR ----

LPS

---- MPR ---

___ MPS --

MW

--- OFL --

PC

--- RHG --

RL

RS

SW

V

MECHANICAL

COMPRESSED AIR

BOILER BLOWOFF

BOILER WATER SAMPLE

CONTINUOUS SLOWDOWN

CHEMICAL FEED

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE TRANSFER PUMP DISCHARGE

CONDENSATE TRANSFER PUMP SUCTION

COLD WATER (CITY WATER)

CONDENSER WATER RETURN (TO TOWER)

CONDENSER WATER SUPPLY (FROM TOWER)

DRAIN LINE

FUEL OIL RETURN

FUEL OIL SUPPLY

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

NATURAL GAS MAIN FUEL

NATURAIL GAS IGNITER FUEL

CHILLED GLYCOL WATER RETURN

CHILLED GLYCOL WATER SUPPLY

GLYCOL WATER HEATING RETURN

GLYCOL WATER HEATING SUPPLY

GLYCOL WATER RUN-AROUND RETURN

GLYCOL WATER RUN-AROUND SUPPLY

HIGH PRESSURE STEAM CONDENSATE RETURN

HIGH PRESSURE STEAM (61 PSIG AND ABOVE)

HOT WATER HEATING RETURN

HOT WATER HEATING SUPPLY

LOW PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 60 PSIG)

MAIKE-UP WATER

OVERFLOW

CONDENSATE PUMP DISCHARGE

REFRIGERANT HOT GAS

REFRIGERANT LIQUID

REFRIGERANT SUCTION

SOFTENED WATER

VENT LINE

NEW PIPE

EXISTING PIPE

DEMOLISH PIPE

Phase

9 10

GENERAL NOTES AND CONDITIONS

1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED BY THE OWNER AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN TEAM FOR THE PURPOSE OF ENGINEERING DESIGN. EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS EXISTING.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING INSTALLATION OR FABRICATION WORK.

1. 1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW THE PLANS AND SPECIFICATIONS, AS WELL AS ALL RELATED PROJECT PLANS AND SPECIFICATIONS FROM OTHER DISCIPLINES, TO BECOME FAMILIAR WITH

THE FULL PROJECT SCOPE AND COORDINATED RESPONSIBILITIES.

1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE DRAWINGS, OR IN THE SPECIFICATIONS, CONSULT THE ENGINEER FOR NECESSARY CLARIFICATIONS, AND CONFORM TO THOSE CLARIFICATIONS INSOFAR AS THEY ARE CONSISTENT WITH THE ORIGINAL DRAWINGS AND SPECIFICATIONS. IN NO CASE SHALL WORK PROCEED

IN UNCERTAINTY.

1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE INTENT OF THE ORIGINAL DESIGN. COORDINATE ANY MODIFICATIONS WITH THE ENGINEER AND OWNER PRIOR TO STARTING WORK IN

AREAS AFFECTED.

1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT SITE PRIOR TO

STARTING WORK.

1.5. DO NOT SCALE DRAWINGS.

2. BIDDERS ARE TO VISIT THE SITE ANO FAMILIARIZE THEMSELVES AS THE NATURE AND SCOPE OF THE WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE AND ENSURE THAT ALL ALTERNATE PRICING INFORMATION NOTED WITHIN THE CONSTRUCTION DOCUMENTS HAVE BEEN INCLUDED WITHIN THE ORIGINAL BID SUBMISSION. LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED, OR FOR ANY DIFFICULTIES ENCOUNTERED WHICH COULJD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT

BE ACCEPTED.

3. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING OBSERVED, PAIRTCULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE EMPLOYED DIRECTLY AND INDIRECTLY ON THE PREMISES, AND THE OWNER'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY BE

REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED.

3.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES, APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH GIVE PROPER AND UNDERSTANDABLE WARNING TO PERSONS WITH REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION WITH THE WORK.

4. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK WHICH COULJD REQUIRE ADDITIONAL MECHANICAL/PLUMBING WORK, AND ITEMS THAT ARE NOT INDICATED

ON THE DRAWINGS.

5. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION. IN PARTICULAR, THE WORK WILL BE IN ACCORDANCE WITH THE LATEST EDITION OF [THE INTERNATIONAL BUILDING CODE, ALL ITS SUBPARTS AND AMENDMENTS INVOKED BY THE STATE AND/OR AUTHORITY HAVING JURISDICTION AT THE LOCATION OF THE PROJECT] [NFPA 90A, NFPA 96, NFPA 99 AND NFPA 101 ].

6. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE). INDUSTRY STANDARDS, AND IN CONFORMANCE WITH THE

MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS.

7. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUfvAILENT. SUBSTITUTED EQUIPMENT

OR MATERIALS SHALL NOT BE INSTALLED UNTIL GWEN WRITTEN AIPPRCVAL BY THE OWNER.

8. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF

PRCVISIONS INCLUDED IN THESE CONDITIONS.

9. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTON, AND UPON SUBSTANTIAL COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH, SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD STRUCTURES, AND OTHER MATERLI\LS OR EQUIPMENT THAT WAS REQUIRED IN CONNECTION

WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF.

10. THOSE PERFORMING WORK AS A CONTRACTOR MUST EXAMINE SUBSTRATES AND CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE OWNER IN WRITING, OF CONDITIONS DETRIMENTAL TO THE PRCPER AND TIMELY COMPLETION OF THE WORK. COMMENCEMENT OF WORK BY A TRADE ON A SURFACE OR CONSTRUCTION SHALL IMPLY ACCEPTANCE OF SUCH SURFACE OR CONSTRUCTION. DO NOT PROCEED WITH

INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.

11. THE CONTRACTOR SHALL SECURE ALL PERMITS AND APPLICATIONS AND PAY ANY AND ALL FEES AS REQUIRED.

THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES AND CERTIFICATES OF INSPECTION REQUIRED BY THE AUTHORITIES HAVING JURISDICTION. DELIVER ALL PERMITS, CERTIFICATES AND APPROVALS TO THE OWNER AGENT PRIOR TO FINAL ACCEPTANCE OF THE WORK. THE CONTRACTOR MUST FILE NECESSARY DRAWINGS, PREPARE DOCUMENTS AND MAKE APPLICATIONS FOR EACH REQUIRED PERMIT AND INSPECTON, PRIOR TO COMMENCING

WORK TO AVOID DELAYS DURING CONSTRUCTION.

12. AS DIRECTED BY THE OWNER, ALL EXISTING EQUIPMENT AND MATERIAL IN USABLE CONDITION THAT IS REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER, OR HANDLED AS INSTRUCTED BY THE OWNER, BE DISPOSED OF BY THE CONTRACTOR. ALL MATERIALS DEEMED FOR REMOVAL SHALL BE RECYCLED WHENEVER POSSIBLE, IN ACCORDANCE WITH THE REQUIREMENTS SET FORTH WITHIN DIVISION 1 OF THE SPECIFICATIONS.

13. CONTRACTOR IS TO PROVIDE ALL REQUIRED SCAFFOLJDING, LADDERS, RIGGING, HOISTING AND ALL OTHER

EQUIPMENT REQUIRED FOR THE INSTALLATION OF THEIR WORK.

14. ESTABLISH PASSAGE CLEARANCES REQUIRED TO DELIVER, INSTALL AND ERECT ALL REQUIRED EQUIPMENT. IF STRUCTURES, EQUIPMENT AND SYSTEMS MUST BE ALTERED TO PROVIDE PASSAGE OF EQUIPMENT, THE CONTRACTOR SHALL RESTORE STRUCTURES, EQUIPMENT AND SYSTEMS TO THEIR ORIGINAL CONDITION AT THE CONTRACTOR'S EXPENSE; INCLUDING REMOVING AND REPLACEMENT OF ALL CEILING AS REQUIRED TO COMPLETE

THE WORK.

15. EXCAVATION FOR UNDER SLAB OR UNDERGROUND INSTALLATION OF CONDUITS SHALL BE APPROACHED WITH EXTREME CAUTION SO AS NOT TO DAMAGE EXISTING UNDERGROUND PIPING, WIRING AND CONDUITS.

PIPING NOTES:

1. CONTRACTOR TO INSTALL HIGH POINT VENTS AT ALL SYSTEM HIGH POINTS AND LOW POINT DRAINS AT SYSTEM

LOW POINTS. VENTS AND DRAINS ARE REQUIRED TO FACILITATE SYSTEM DRAINING AND VENTING DURING TESTING

AND START-UP.

2. UNIONS SHALL BE INSTALLED AT ALL EQUIPMENT. THE USE OF DIELECTRIC UNIONS MUST BE INSTALLED IN AREAS WHERE JOINING OF DISSIMILAR METALS (IE CARBON STEEL TO COPPER OR BRONZE, ETC.). THIS IS TO FACILITATE PIPING REMOVAL AND REASSEMBLY FOR FUTURE MAINTENANCE WORK AND/OR PREVENT GALVANIC

CORROSION.

3. CONTRACTOR SHALL PROPERLY BRACE, ANCHOR, AND SUPPORT ALL PIPING, VALVES ETC. UNLESS SHOWN OTHERWISE, ALL PIPE HANGERS AND SUPPORTS SHALL BE DESIGNED, MANUFACTURED AND INSTALLED PER MSS

SP-58, MSS SP-69 AND MSS SP-89.

4. ALL PIPES THAT PASS THROUGH EXTERIOR WALLS SHALL BE SLEEVED AND MADE WEATHER TIGHT.

5. ALL PIPING AND VALVES MUST BE PROPERLY IDENTIFIED AND LABELED PER ANSI 13.1, ENTITLED "SCHEME FOR THE IDENTIFlCATION OF PIPING SYSTEMS". ALL VALVES MUST BE IDENTIFIED AND TAGGED WITH WEATHERPROOF

TAGS.

6. ALL PIPES OR TUBING WHICH PASS THROUGH RATED AND NON-RATED WALLS, FLOORS AND FOUNDATION WALLS, SHALL PASS THROUGH A SCHEDULE 40 CARBON STEEL PIPE SLEEVE. SLEEVES WHICH PASS THROUGH MASONRY SHALL BE GALVANIZED COATED. ALL SLEEVES SHALL BE INSTALLED FLUSH ON BOTH SIDES OF WALL

PENETRATION.

NON RATED WALL: THE SLEEVE SHALL BE SIZED TO ALLOW FREE PASSAGE OF INSULATED AND NON-INSULATED

PIPES AND TUBING.

RATED WALL: PIPES WHICH PASS THROUGH FlRE-RATED WALLS & FLOOR SHALL USE THE APPROPRIATE CODE APPROVED, TESTED AND INSTALLATION METHOD OF SEALING WHILE MAINTAINING THE INTEGRITY OF THE WALL'S

FIRE RATING(S).

EXTENSION WALLS & FOUNDATION WALLS: PIPES WHICH PASS THROUGH EXTENSION WALLS OR FOUNDATION

WALLS SHALL BE SEALED AND MADE WATERTIGHT.

7. ALL VALVES SHALL BE ACCESSIBLE IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE ACCESS DOORS AND

COORDINATE THE GENERAL CONTRACTOR.

Project Title Project Number

561-25-125

ABBREVIATIONS, NOTES AND SYMBOLS ISSUED FOR BID

EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

Building Number

Approved: Project Director

FULLY SPRINKLERED

ILoc~~nEAST ORANGE CAMPUS I Drawing Number

:;:l•=•=ue::::;::D=a1=e====::::;-;:::I ~=:==:==:::;-;:11D~ra=w=n==:::;1

2025-07-16 RHD

M-001

7 8 9 10

A

B

C

D

MECHANICAL

ROOM

B-128

STAIR 6

B-S6

UTILITY

SHOP

B-119C

LINEN

ROOM

B-134D

MECHANICAL

ROOM

B-128

OFFICE

B-134

TOILET

B-134B

CLOSET

B-134A

STAIR 5

B-S5

SHAFT 8

ELEC. CLO.

B-E-105

CLOSET

B-135

CORRIDOR

B-137C

CORRIDOR

B-133

WALK-IN

COOLER

B-128A

WALK-IN

COOLER

B-128B

MECHANICAL

ROOM

B-128D

REFRIG

B-119

REFRIG

B-118

REFRIG

B-120

CORR.

B-117

CORR.

B-113

STORAGE

FOOD

SERVICE

B-115

SUPERVISOR

FOOD

SERVICE

B-116

MECHANICAL

DEMOLITION PLAN

MD101

RHDLM

PLAN

NORTH

ACTUAL

NORTH

KEYPLAN

NO. DESCRIPTION DATE

PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F m 5 a,'--'--,-, " g :c q- ..........,~ le -"' m ~o co N I n

I ro

C, -CL

"' 0

CL

C

Q_

E "' D

-D -D

C

= 0

I w

"' w

= Q_

0 -"' E .D C, (/) -C

"' L L C, u I

" 0 u

I w 0, C

" 2 D

I sj i" = u

-w w N

I a, a, sj-

'i

B-136 I.V.

3TORAGE

I

IHf---1

I y

II

\: u -

LJ~

B-137A

PROCESS -STORES -

I STORAGE

- ,ca

ACCESS TO THE CONSTRUCYION AREA IS

RESTRICTED THROUGH THESE DOORS.

COORDINATED WITH THE VA FOR

CONSTRUCTION ACCESS.

B

C

RETAINING WALL

n u

I

I

(E) 1-CT-3

(E) 1-CT-2

(E) 1-CT-1

(E) 1-WCC-1

n

I

I '

(E) CWP-4

I 1jl I I j I I I I I ' I' I I

(E) 1-CH-2

""~'-----\:n'.-==-!j-+-____ (D) CWP 1 'J '"

110_!__!

. 1..1 -

J

0---+~--+---tfu

I I -/ :c----::~~' :

I I H __ ....., jCE) 1-CHP-4

I I I~ I , '-,-I- 0

1 1 lol

---,-1 +-11 H -

I ioc:L " I I - 12•,-□ J I wl'-1--"'~ I

(E) 1-CH

lgal - !

I:' I 1:-:::r- - ~

1'1 I I w

I I , , i:=u,·,-w I I L_ __ __,

(E) 1-CHP-6

,----- - - -, (E) CHILLED

F

1 r---1 --,I I WATER BUILDING

I . . PUMPS

1---------ll--l----'-' -':--==~ -~----

1 (E) 1-CHP-9 -J

I

I

B-128C

WALK IN

REFRIG

i L

I I

, (E) 1-CHP-8

(E) BAS

USER

INTERFACE

I (@) ALL 8" PIPING TRIM

- ~ 4 • LOW THE ELBOW SEE

, - ~ !DETAIL 2/M-501 AND , ( l ._j (E) PUMP;~ 7 ._,, .. ~ 601 FLOW DIAGRAM D10ALL 6 PIP ,NG TRIM CHANGEOVER ~ Le " gL,QW-d ~E- el.ElOW SEE h\3 VALVE DETAI i:" 21M= 501 AND\::/ / / I

M-601 FLOW DIAGRAM ~ / / _

(E) PUMP

CHANGEOVER

VALVE

(E) 6" CHS

IV ~

~ y ;;,,i~

,I I .,, ~ ..d ,°;?i~~~~'=,;'"7 tc (D) CHP-1 (D) CWP-2 (E) CWP-3

L----f-c)--tl~I [] lT. K ____ _,, ,---7----,-----1

D ~ - -- _J }-'-I~>- I= E'RiiJ- ,'V 17 'II---,-~,-~ ' --~f,,,ilf'i!=~II L

(E)1-CH-4° 0 (E) SSR-1 _ ~ -(E) CT VFD

~(E) MAKE-UP

WATER SYSTEM

FROM (E) BFP

I I r-H-1--(E) MCC

I

I

\D): l'µT2"7'1PWG TRIM 0 1/ /

BELOW THE ELBOW SEE

DETAIL 4/M-501 AND

M;-601 FLO~ DIAGRAM

CWP 2

I / _.b-t~laad __

NECT-'

I

CWP-4

FL:

B-110

KITCHEN

n

B-114

GENERAL

STORAGE

L./ SUPERVISOR

I )< B-112

DIET.

OFFICE

B-111

CHIEF

DIETETICS

OFFICE

I 1 MECHANICAL DEMOLITION PLAN

, _ _____,, 1 SCALE: 1 /8" - 1'-0"

E

""'~ DVOSB \

I . •"'

-++--++--< B

-++--++--< C

.d'f---+tt-+--0

----+-it+---{ E

--t-tt-'-t----i F

I r

I

X B-401 X IRM

CLOSET

I ~I .II\ \ /I I

CRAWL SI

CRAWL SI

I I

GENERAL SHEET NOTES:

1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS, GENERAL NOTES &

SYMBOLS.

0 SHEET KEYNOTES:

1. DEMOLISH VERTICAL DEEP WELL CONDENSER WATER PUMP, CWP-1

2. DEMOLISH VERTICAL DEEP WELL CONDENSER WATER PUMP, CWP-3

3. DEMOLISH CHILLED WATER PUMP CHP-1 AND INERTIA BASE THAT SERVES O.R.

CHILLER.

4. DEMOLISH WATER PUMP CWP-2 AND INERTIA BASE THAT SERVES AS A SPARE FOR

THE D.R. CHILLED WATER SYSTEM AND CONDENSER SYSTEM.

CONSTRUCTION NOTES:

IF POSSIBLE DEMOLITION AND INSTALLATION OF THE O.R. PUMPS SHALL BE

EXECUTED WHEN THE OAT IS BELOW 40F. IF A SHUTDOWN IS REQUIRED

PLEASE COORDINATE wrrH THE VA FACILITY

Cj ~

DD

0 0

0 0

0 0

0 0

EB

i VA I□□ -;:L':::====================::..'::::==========================================================-===========--------------'======================:'..'::::===============-=======::::'..'::====:'..'::::============:'J VA FORM 08-6231

B-128

MECHANICAL

ROOM

B-128

REFRIG

B-119

REFRIG

B-118

REFRIG

B-120

CORR.

B-117

CORR.

B-113

STORAGE

FOOD

SERVICE

B-115

SUPERVISOR

FOOD

SERVICE

B-116

MECHANICAL

PIPING PLAN & ELEVATION

GROUND FLOOR

MP102

RHDLM

PLAN

NORTH

ACTUAL

NORTH

KEYPLAN

NO. DESCRIPTION DATE

PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

-0 Q m C

II

.5 ~o a• ~"' m e ,s

= 0 w

" -0

E

:a, CL

N N r---- -.. -D en N I n I ro w o_

E o_

- '" 0 o_

'" CY

C 0 = 0

'" 2

N D

CL

:a, C 0 = 0

'" :a, I w

"' w

= CL

C

"' L L u I

" 0 u

I w

CT>

C

" 2 D

I sj i"

= u

'" CT>

C

0 -w w N

I m m sj-

"i D

I m m sj-

CL

VA FORM 08-6231

V

I ~

I ~-t=---

"' I u + --w -j r- ---\ f---;D ~ --'rr

"' I u

• ~ -w

I

I I

I I I I I I

I I I I I "' I I I I

I I I u1 I l~I I

I I 151

I ' I I f- --j I I

___J l_L

Ir I

"' I I u1 +I 51 - I

I I L':

r;::

I

I _j

C I I '

I I

II I I

I I

~(E)10"o

~ (E)1-WCCH-2

= . . . . . ~ I m

I: : I / - - I -

I I -(E)10"o

' I I I 8 \ I e------------1

I H

I h '-

- (E)10" CHS I\ '- ~ _j j I m I

( I 0 0 , 1111 I~) :(,, I 1111

H 11:J II ~ - 0

0 - (E)1 WCCH 3 ~~ I I -- -1 .

I I I I

- (E)10"o

I " ,Ji~ I I L - \ I r"~ _ ,, __ -i~~-~ H

I I I '-

I I I ~

I I I I I I I \ H H I I I I I I I ~ l - r - -

-::l I ' . I - (E)10" CHS li'sl 1i's1 1i's1 H I Io I l"o I lol ·- ',l tt I,,,) 8 I ,;:_I I ,;:_I I ,;:_I (E)10" CHR - ::JI w w w

1-1 1-1 1-1

(E) SAFETY RAIL_/ I I I I I I

I I I I I I I (

I I I I I I (E) RAMP DN )

J I I J

I I 10·• i '----- J I I I I ~

I I I I I I

-- ci_,e I I I I

IE 1 -CHP-4 I I

I r " I I c:\ ~ I I

" _,:s 'I I I -

I

I - - -

I I I I -l == ,-71 - 11r_, '--- Cl JIL a I I I

: ii I I r-n ~1 --- - - -µ

( I I I I

1 (E) 1-CHP-5 I I

-12"0- I ~ fI - I l I E ~

:-4--'

I- -

,- I

(E)1-CHP-6

L... - ...L-_::1/'

I I I j 1 MECHANICAL SCALE: 1/4" - l'-0"

- 1- \

GENERAL SHEET NOTES: - -

' +- A - - - - - - -

I

1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS, GENERAL NOTES &

SYMBOLS.

r--:, I I I I'\

-(E)12" CWS I

B ,_ -r ' I/ -

I © SHEET KEYNOTES: I //

' ' 1 ' CONTRACTOR TO VERIFY THE SUMP HEIGHT AND WATER LEVEL AND PROVIDE THIS

(E)12" CWR- &I ( ' ' 6 INFORMATION TO THEIR PUMP VENDOR. SEE ELECTRICAL DRAWINGS FOR VFD ' '

LOCATIONS.

I " I . . . . . - I/

(E)12" CWR- - ~

(E)1-WCCH-1 =

I I ·" Q N 'N - -

I

~ - C e. '- ~ , -' I '

I I & •

(E) CWP-4 N ---

h (E)12" CWS- □ l

- 00 (E)12" CWS- I f-- -

I a. C ,'-- -

- :--c I t' ·{ ~

I (E)12" CWR- ~I -

(E)12" CWR I t,;"-:-1 t-:----:< I ~,_...._~ \

'= 000 ;y ~ u\ 0 -- -- --v ~ 7 1 1

(E) CWP-2

L J {N)~c,. / j T\

\ c,., L lJ

(N) 12" PIPING TRIM BELOW THE (N)

ELBOW; SEE DETAIL 4/M-501 (E) VFD FOR (E) DISCONNECT 1-CWP-3 1

' AND M-601 FLOW DIAGRAM CWP-2 FOR CWP-4

~~~0~" s':'~l~GET:~M4,~~~~1THE I AND M-601 FLOW DIAGRAM

I I -I- ~I I 0 - -

- ~ I t I E - - - - -- -

( B-114

GENERAL

STORAGE

Jl I

) B-112

PIPING PLAN - GROUND FLOOR

• • ~ ~- DD

"- DT

DD

C

. . j e "- 0 0 . . =

0 ' 0 0 -~ s ~

,e- .• 0- 0 - ,__ .. L~~lf - 0

I ' ~.ITT1: : f . 0 -~ .

.~L~

• -.. .'Er. ': : 0

I 0 .

0 1, 0 m • • • 0 - 0 0

• 0 f ! __.J

I r-" J '

H DD

-~ I □□

EB

I I

I I E

"'"~ 8DVOSB \ ,

VA I I□□

STAIR 6

B-S6

UTILITY

SHOP

B-119C

MECHANICAL

ROOM

B-128D

B-12

MECHANICAL

PIPING PLAN

GROUND FLOOR

MP103

RHDLM

PLAN

NORTH

ACTUAL

NORTH

KEYPLAN

NO. DESCRIPTION DATE

PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F m 5 a,'--'--,-, " g :c q- ..........,~ le -"' m ~o

-D

"' N I n I ro w Q_

E Q_

- '" 0 Q_

'" cc

C .c

'" 2 n D -[l_

C .c

I w

"' w .c o_

-C

"' L L u I

" 0 u

I w 0, C

" 2 D

I sj i" '" .c u

'" 0, C

0 -w w D N

I a, a, sj-

'i

1 --------7 (E) CHILLED

I ----------WATER BUILDING

i I I i PUMPS

I I

(E)< ) _ 1-CHP-8

(E) BAS

USER

INTERFACE

(N) B" PIPING T~I~ BELOW THE

ELBOW; SEE DETAI~ 2/M-501

AND M-601 FLO DIAGRAM '-"

(N) 6" PIPING TRIM BELOW THE

ELBOW; SEE DETAIL 2/M-501

AND M-601 FLOW DIAGRAM"-"

I

I

(NJL__ __ _,Y""Y'-f'-~',----1----',\·-----------~

0(r-~---CH-P--1~) ~ \ (E) 8" CHR

(E) 8" CHS

(E) ELECTRICAL ~

CONNECTION

lYP

'--- (E) 6" CHS

ON INERTIA BASE r,;:::;:,o:::

(E) 8" CWR (;i _ f--- \

(E) 8" CHR >-- '---' I

trr1 l

• -'N (E) CWP-3

_,.,,.-(E) B cws,( 1-CWP-2 > 0

ON INERTIA BASE

Im ,___, j

(E) 1-WCCH-4

- ~ G -.

( I

(E) SSR -

\' I l I

( I I°/

MECHANICAL PIPING PLAN - GROUND FLOOR

I 1 , SCALE: 1/4" ~ 1'-o·

-0 (9

(E)

MCC

I

I

L/

GENERAL SHEET NOTES:

1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS, GENERAL NOTES &

SYMBOLS.

(j) SHEET KEYNOTES:

1. SEE ELECTRICAL DRAWINGS FOR VFD LOCATIONS.

I

• • Cj □ □

"- "T j

? "- 0 0

0 '

0 0

~~-ri • -,e- 0- 0 -,,,. s . .

If - e----· • t:~

' -~.rm: : . 0

,,. l

~L~:

~ 0 0 -.. 0

I

01, m • • • 0 - 0 0

0 0 __,J I r-" J .

-~ I □□

EB

I I

E

'""~ DVOSB \

I . •"'

;:=============;;:==========;:==========;:=I =====;I i VA I I□□ -;:L':::====================::..'::::==========================================================--===========-------------'======================:'..'::::===============--=======::::'..'::====:'..'::::============:'J VA FORM 08-6231

DETAILS AND SCHEDULE

M-501

LMLM

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

FLOW DIAGRAMS

M-601

LMLM

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

Q

• C u .S

Q

• C

~o

I

-fi C 1" ~o

I co w Q_ w

"' m E 0, D

LJ...

_Q

C w L L u I

"O u

I m

"' C

D

I -tj

.c u

'" 0, C m w N

I

"' "' -tj-

"i

TO OR

SUITES

TO BLDG

T

(El( 1-CT-2 ) (El--< I-CT-I )

! ~' r1g ,g ,g I ' ~ ~ ~ I (E) T T T I v, ( CH P-9 ) I f-----------, I f-----------, I f-----------i ~ o I ~-~--~ I ~-~--~ I 0 'i3' : I I I (E)

~--12· cws----------~-----------------~-~

: ( CHP-8 ) ~-----------------I------{}~---------------~

I ,. L---Jtl---------------___! ___ 7 I

: (E) • ~ : 16" CHS : 14" CHS I 11-2"-CWRL---L}~---------------~12" CWR

I O" CHS-< t, 6---12" CWR " '--_q,-______ " <D-I ( CHP-7 ) I 10 CHS-<> I 10 CHS I

I I I I

~----------------- 9_ ~ :UI -" ~I - ~j

! (E) BYPASS (E) ~~-- ' -, ~<;;: (E) - ' -: ~1 E - ' - .~1

•0 (1-WCCH-2) ~<fl (1-WCCH-3) ~<fl, j ( (i-WCCH-1) ~Q, j ... ~I.__ - -= -- -=1--

~---12· CHR ---~-----------10" CHR---------1- -- ----- -------- _J : o-12" CWS

I (G~~- I I I (1-CHP-4) j ,------------10" CHR- - -------- ___________ _j

I I I I I 1 I I ~-,----------~

L ___ 12" CHR---~-----------10" CHR---------:- __ J

t (E)(I-CHP-5) :

"' I I o I

12· cws

~12" CWSJ ----J,'.

EXISTING '!'' ,, '

v, ,,, EXISTING

N I

- I L---------e----------- 10" CHR--------J

(Nl .--,./

(N\ I -CWP-3 )

(El

NEW (1-CWP-1) CWP-2 - -

(El

CWP-4 NEW -

(E)(_I--C-H-P--6-) - - -- ~

- " " - " e, 1- --------r-------- -7

,-------~--~ L _____________________ _J

0 ~~~~~~R WATER FLOW DIAGRAM

NOTES:

I. SEE DETAIL 4 ON M-501 FOR PUMP

INSTALLATION AND PIPING

COMPONENTS.

(El SUMP TANK

(El--

\ I-CT-I )

400 TON

FROM OR

SUITES

' rr ~ ~ ~3·-r 1f--g ___ ~ ~----------------1--1---.---_--rll/' f-W~ I

6" CHS --<P t-6" CHR

I

8" CWS -<I> ¢,---8" CWR I ::,,,_

I I NC

I I I

' I I I I I I

I I L _____ _

,------- -----iVl-

1,'@ " □ ! -<S f-s" s" "' ~ o a"

1\:= (':;;~~7 I .. /J .--,. / .--,. /1 r""=C::::::::,,,-;"i f' (3 "" : NEW "----' I "....Y "----' I

CONDENSER F''"'C I l I "-~ ""G-;~" ! " o, ! " 'o):

L~-~~~']'l __ _j (E\ I -WCCH-4) Li !ij ~ ~ f-- Li !ij ~ \ii -

(N (-1--C-H-P--1~) (N)( 1 -CWP-2 )

o-s·

(El CWP-3

I 2 OR COOLING WATER FLOW DIAGRAM

SCALE: NONE

NOTES:

1. SEE DETAIL 2 ON M-501 FOR PUMP

INSTALLATION AND PIPING COMPONENTS.

2. NEW PUMP 1 -CWP-2 IS SPARE PUMP.

FROM (El

WATER

TREATMENT

SYSEM P/TE-

'I>- 8"

I

(E) SIDESTREAM

FILTER 1-SSR-1

P/TE-

GENERAL SHEET NOTES:

1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS, GENERAL NOTES &

SYMBOLS,

2. REFER TO DRAWING M-501 FOR DETAILS.

I I

::==============;::==========;:==========;l;:========;I i VA I ID□ -;:L':::=================='===::'..::::==========================================================='-'===========-------------=======================:.================='-'=======~====:.======'--'========:J VA FORM 08-6231

CONTROLS FLOW DIAGRAMS

M-801

LMLM

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

Q

• C

~o

I

-fi C ~ s;r ~~

1" ~o

,n N

I n

I ro ro

I

C V L L u I

"O u I m

"' C

" 2

I -st i" V

.c u V

"' C m w N

I m m -a-

"i

TO OR

SUITES

FROM OR

SUITES

TO BLDG

T , ! s~ (E) V-6 J ~ (E) V-8 J ~ (E) V-9 J ~ I (E) T~ T~ T~ I !fl ( CH P-9 ) ! f---------, I f---------, I f----------< de " = f-----~ I f-----~ I

13 • '64 : ! !

! (E< CHP-8 ) ~ _ ---- _ ~2~ cw5_ _______ I ____ ---1'.f'~(E)_ ~5_ ___ -- ______ -~

I L ---1'.f'~)_v~ - -- --- - - -- _ _!_ - - 7 I : 0 15" cHs 1 14• cHs----- L ___ L---1'.f'~(E)_ v-7_ ____________ J

(E) I I b--12" CWR

I '---------10" CHS------~

I < CHP-7 ) l I :

: ----------------(E) :PASS ~ ~'I ~ ~'! ~ 1~1

l _ ~ ~-- >- - ~i? >- ~ ~~?

I ~--- =-- U (El(1-wcCH-1) <.0 Q, (El<1-wcCH-2) Q__Q (Eb-wccH-3) Q__Q ~ ~1--I- -=1 L- ---- =1 ~ I I I I I I I I

II (E) v-1oo-;!, ±{] (E) V-1 (E) V-11 o-;:, ±{] (E) V-2 (E) V-12 o-;:, , 2..[J (E) V-3 T T T

I I I I

~---12" CHR---~-----------10" CHR---------:- ________________ J :

I (E) ___ I I P----12" cws

: (1-CHP-4) ! ,------------10" CHR---------------------J

I I I ---1 -----------12· cws -------------

BA~ET 1" ' t-------,'/r------, t (E)( 1-CHP-

) SST HS VFD ECC 1 1:t------t--'ll'.t-----------1_ ,, ' er I u 0

I

I I

t. -

(E) " -- CWP-2 - -t-7 ,,_ - -

~---------~---------- 10" CHR--------_J

(E) ---

I ~t------- ~ "---------r l~----~'--~

( 1-CHP-6 )

SST HS

L---------------------~ (0

(N) ___ (E) SUMP TANK (N) CWP 4

(1-CWP-1) (-1--C-W-P--3-) -

DIAGRAM

© SHEET KEYNOTES:

1. ADD NEW PUMPS 1-CWP-1 AND 1-CWP-3 TO EXISTING CONTROL SYSTEM.

COORDINATE WITH BAS CONTRACTOR.

NEW CONDENSER PUMPS 1-CWP-1, AND 1-CWP-3 FLOWS SHALL BE SET BY THE

TESTING, ADJUSTING, & BALANCING (TAB) CONTRACTOR VIA THE VARIABLE FREQUENCY

DRIVE (VFD).

-2"

(E)--

\, 1-CT-1 )

400 TON

----,[If

NC

H /'r-------~------------+"+---,'., "e------~ NC ,,, q,-5" ,t,-s"

VFD ECG

FROM (E)

WATER

TREATMENT

SYSEM P/TE-

ECC VFD

P/TE-

( p-8"

----- <>-..:'B::.."----c::--"r~I ____ I _____ _,,

(E) CWP-3

I 2 : !R2;;;;lON O.R. CHILLED WATER FLOW DIAGRAM

© SHEET KEYNOTES:

2. AOD NEW PUMPS 1-CHP-1 AND 1-CWP-2 TO EXISTING CONTROL SYSTEM.

COORDINATE WITH THE BAS CONTRACTOR

NEW PUMPS 1-CHP-1, AND 1-CWP-2 FLOWS SHALL BE SET BY THE TESTING,

ADJUSTING, & BALANCING (TAB) CONTRACTOR VIA THE VARLI.BLE FREQUENCY DRIVE

(VFD).

f-r- -

(E) SIDESTREAM

FILTER 1-SSR-1

E

'""~ DVOSB \

I . _..,, ,v, HS SST

CONDENSER PUMP CONTROL

A. CONCURRENT WITH THE INITIAL START OF THE SECONDARY CHILLED WATER

PUMP, OPEN THE PRIMARY CHILLED AND CONDENSER WATER ISOLATION VALVE

OF THE LEAD CHILLER. AJFTER THE VALVE END SWITCH PROVES THE VALVE IS

OPEN, START THE LEAO CHILLED AND CONDENSER WATER PUMPS AND

INCREASE THEIR SPEED AT THE RATE THAT WOULD ATTAIN FULL SPEED IN ONE

MINUTE,

B. THE LEAD CHILLED WATER AND CONDENSER WATER PUMPS ARE TO ATTAIN, AS

A MINIMUM, THE SPEED NECESSARY TO GENERATE THE MINIMUM CHILLED

WATER AND CONDENSER WATER FLOW THROUGH THE CHILLER. THE SPEED OF

THE PRIMARY CHILLED WATER PUMP SPEED IS, IF NECESSARY, TO BE FURTHER

INCREASED SO THAT THE FLOW THROUGH THE LEAD CHILLER EQUALS THE

FlLOW OF THE SECONDARY DISTRIBUTION.

C, UPON THE CHILLER PROVIDED CONDENSER WATER AND CHILLED WATER FLOW

PROVING SWITCHES ESTABLISHING SUFFICIENT FLOW, THE CHILLER STARTS AND

IS CONTROLLED UNDER THE CHILLER'S OWN CONITROL SYSTEM.

D. THE CHILLER BACNET COMMUNICATIONS CAPACllY VALUE IS TO BE USED TO

STAGE THE NUMBER OF CHILLERS OPERATING, IF ONE OR TWO CHILLERS ARE

OPERATING AND THE CAPACllY OF THE INDMDUAL OPERATING CHILLERS REACHES 80% (0.8) OF FULL CAPACllY, THE CONTROLS ARE TO CALL FOR AN

ADDITIONAL CHILLER TO BE BROUGHT ON LINE.

E. THE CONDENSER WATER PUMP'S SPEED WILL BE MODULATED TO ATTAIN THE

FlLOW, AS MEASURED BY THE FLOW METERS AT THE OPERATING CHILLER(S)

WITH THE LOWEST FLOW.

F. AFTER TWO MINUTES OF CHILLER OPERATION WHEN THE LEAD CHILLER IS

STAJRTED OR DURING NORMAL OPERATION OF THE PLANT ANO AJFTER START UP

OF AN ADDITIONAL CHILLER, THE CAPACllY OF THE CONDENSER WATER PUMPS

ARE TO BE MODULATED TO MAINTAIN CHILLER CONDENSER WATER FLOW

REQUIREMENTS DESCRIBED ABOVE,

FAULT HANDLING:

A. CHILLED WATER AND CONDENSER WATER PUMPS - FAULT SHALL BE DETECTED

BY THE VFD COMMUNICATING THROUGH THE BACNET COMMUNICATIONS THAT

THE VFD HAS FAULTED OR THE AMPS DRAW OF THE PUMP IS LOW. THE

SYSTEM SHALL REPLACE THE MALFUNCTIONING PUMP WITH THE NEXT IN LINE

LAG PUMP. ALL CONTROL SIGNALS SHALL BE TRANSFERRED TO THAT PUMP. AN

ALARM IS TO BE DISPLAYED AT THE ECC.

ECC HS SST

PRIMARY/CONDENSER O,R, PUMP CONTROL

A. AT CHILLER PLANT STAJRT UP, CONCURRENT WITH THE INITIAL START OF THE

PRIMARY CHILLED WATER PUMP, OPEN THE CONDENSER WATER ISOLATION

VALVE OF THE LEAD CHILLER. AFTER THE VALVE END SWITCH PROVES THE

VALVE IS OPEN, START THE LEAD CONDENSER WATER PUMP AND INCREASE ITS

SPEED TO FULL SPEED AT A THE RATE THAT WOULD ATTAJN FULL SPEED IN

ONE MINUTE.

B. UPON THE CHILLER PROVIDED CONDENSER WATER AND CHILLED WATER FLOW

PROVING SWITCHES ESTABLISHING SUFFICIENT FlLOW, THE CHILLER STARTS AND

IS CONTROLLED UNDER THE CHILLER'S OWN CONTROL SYSTEM.

FAULT HANDLING:

A. CHILLED WATER AND CONDENSER WATER PUMPS - FAULT SHALL BE DETECTED

BY THE VFD COMMUNICATING THROUGH THE BACNET COMMUNICATIONS THAT

THE VFD HAS FAULTED OR THE AMPS DRAW OF THE PUMP IS LOW, THE

SYSTEM SHALL REPLACE THE MALFUNCTIONING PUMP WITH THE NEXT IN LINE

LAG PUMP. ALL CONTROL SIGNALS SHALL BE TRANSFERRED TO THAT PUMP, AN

ALARM IS TO BE DISPLAYED AT THE ECC.

GENERAL SHEET NOTES:

1. THE DIAGRAM OF THE CENTRAL CHILLED WATER DISTRIBUTION WAS DERIVED

FROM THE EXISTING BAS GRAPHIC, FlELD VERIFY ARRANGEMENT AND

EQUIPMENT/VALVE TAGGING IN THE FIELD, IN COORDINATION WITH THE CONTROL

SYSTEMS INTEGRATOR.

2, ADD EXISTING PUMPS TO EXISTING CONTROL SYSTEM, COORDINATE WITH VA AND

THE EXISTING CONITROL CONTRACTOR AND FOLLOW EXISTING SEQUENCE OF

OPERATION.

3. THE FACILllY'S CONTROL SYSTEM INTEGRATOR (CSI) MUST BE CONTRACTED

UNDER THIS PROJECT FOR ADDITIONS TO THE EXISTING BAS. THE EXISTING

CONTROL REPRESENTATIVE FOR THE PROJECT AREA IS:

AJNSWORTH (FORMERLY DELTA CONTOLS, INC.)

10 CENTRE DRIVE

MONROE, N.J. 08831

ATTN: SIMON ZHOU

OFFICE #: 908-635-2985

I I

:c==============;:c==========;:==========;l;:========;I i VA I ID□ -;:L':::=================='===::'..::::==========================================================='-'===========-------------=======================:'..'::::================'-'=======~====:'..'::::====-'========:J VA FORM 08-6231

ELECTRICAL

ABBREVIATIONS & SYMBOLS

E-001

MJRMJR

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0120

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

ISSUED FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC

REPLACE PUMPS

FOR CHILLERS

VA EAST ORANGE CAMPUS

561-25-125

Project Director

2025-07-16

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

:,a [L co N r---

"' N I

I r---

L

.c u

"' u

I w

• C:

"' w

I r-- "' w .c [L

.D

" 0 u I

.c u

"' CT>

C

0 -w w N

I a, a, scj-

VA FORM 08-6231

ELECTRICAL ABBREVIATIONS:

1PH

1P 2/C 3/C

3PH

4/C 4W

A/C UNIT

A/E

AAP

AC

ACC

ADDL

ADJ

ADO

A, t,,C t,,F t,,G

AH

AHJ

AIC

ALT

AMB OR A

AMP

ARCH

ASC

AT

ATS

AUTO

AV

BAT

BC

BFF

BIL

BLDG

BPIP

BRKR

BYP

C

CAB

CALC

CAP

CAT

CATV

CCR

CCTV

cd

CD

CF

CF/Cl

CF/0I

CFE

CHW

CHWP

CKT

CKT BRKR

CLF

CLG

CMU

COAX

COMM

COMPT

CONC

CONT

CONTR

COORD

CPT

CRI

CT

CTV

cu

CU FT

CUR

DB

DC

DCP

DEG C

DEG F

DEMO

DIAG

DISC

DISTR

DISTR PNL

DMM

DMR SW

ON

DPDT

DPST

DRSW

OS

DWG

(E)

EC

EG

EGC

EL

ELEC

ELEV

EMCP

EMER

EMI

EMT

ENCL

EPO

EPRF

(ER)

ESMT

EWC

EWH

EXIST

DEVICE MOUNTED ABOVE STD HEIGHT

SINGLE -PHASE

SINGLE POLE

TWO-CONDUCTOR

THREE-CONDUCTOR

THREE-PHASE

FOUR-CONDUCTOR

FOUR-WIRE

AIR CONDITIONING UNIT

ARCHITECT/ENGINEER

ALARM ANNUNCIATOR PANEL

ALTERNATING CURRENT OR ARMORED CABLE

ACCESSIBLE

ADDITIONAL

ADJACENT, ADJOINING

AUTOMATIC DOOR OPENER

AMPERE FRAME OR AMP FUSE

ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE FAULT

CURRENT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AMPERE HOUR

AUTHORITY HAVING JURISDICTION

AMPERE INTERRUPTING CAPACITY

ALTERNATE

AMBIENT

AMPERE

ARCHITECT

AMPS SHORT CIRCUIT

AMPERE TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUDIO VISUAL

BATTERY

BARE COPPER

BOARD

BELOW FINISH FLOOR

BASIC INSULATION LEVEL

BUILDING

BOILER PLANT INSTRUMENTATION PANEL

BREAKER

BY PASS

CONDUIT

CABINET

CALCULATE

CAPACITY

CATALOG

COMMUNITY ANTENNA TELEVISION

CONTROL CONTACTOR

CLOSED CIRCUIT TELEVISION

CANDELA

CONSTRUCTION DOCUMENTS

CONTRACTOR FURNISHED

CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CONTRACTOR FURNISHED/OWNER INSTALLED

CONTRACTOR FURNISHED EQUIPMENT

CHILLED WATER

CHILLED WATER PUMP

CIRCUIT

CIRCUIT BREAKER

CURRENT LIMITING FUSE

CEILING

CONCRETE MASONRY UNIT

COAX CABLE

COMMUNICATION

COMPARTMENT

CONCRETE

CONTINUE

CONTRACTOR

COORDINATE

CONTROL POWER TRANSFORMER

COLOR RENDERING INDEX

CURRENT TRAINSFORMER

CABLE TELEVISION

COPPER

CUBIC FEET

CURRENT

DECIBEL OR DIRECT BURIAL

DIRECT CURRENT

DIMMER CONTROL PANEL

DEGREES CELSIUS

DEGREES FAHRENHEIT

DEMOLITION

DIAGRAM

DISCONNECT

DISTRIBUTION

DISTRIBUTION PANEL

DIGITAL MULTIMETER

DIMMER SWITCH

DOWN

DOUBLE POLE, DOUBLE THROW

DOUBLE POLE, SINGLE THROW

DOOR SWITCH

DISCONNECT SWITCH

DRAWING

EXISTING TO REMAIN

ELECTRICAL CONTRACTOR

EQUIPMENT GROUND

ELECTRICAL GROUNDING CONDUCTOR

ELEVATION

ELECTRIC OR ELECTRICAL

ELEVATOR

EMERGENCY MONITORING CONTROL PANEL

EMERGENCY

ELECTROMAGNETIC INTERFERENCE

ELECTRICAL METALLIC TUBING

ENCLOSURE

EMERGENCY POWER OFF

EXPLOSION PROOF

EXISTING TO BE RELOCATED

EASEMENT

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXISTING

FA

FMP

FABL

FABX

FACP

FATC

FC

Fl

FIXT

FLA

FLEX

FLT

FLUOR

FLUOR FIX

FOUTT

FP

FT

FU SW

FVNR

FVR

G OR GNO

GEN

GFCI

GIB

HID

HOA

HP

HT

HZ

IESNA

IMC

INCAND

IR

IWH

J-BOX

kV kVA kVAH kVAR kW kWH kWHM

LED

LF

LM

LP

LPS

LRA

LTCP

LT

LTG

LTG PNL

LTNG

LV

MATV

MAX

MC

MCA

MCB

MCC

MOP

MECH

MG

MH

MIN

MOCP

MLO

MT

MTD

MTG

MTS

MV

MVA

MW

(N)

NA

NEC

NEMA

NEUT OR N

NFPA

NIC

NL

NO

NS

NTS

OC

OD

OL

p

PA

PB

PBPU

PCB

PEC

PED

PEM

PEND

PF

PH

PNL

POD

PT

PTRV

PVC

PWR

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM BELL

FIRE ALARM BOX

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

FOOT CAIN OLE

FILM ILLUMINATOR

FIXTURE

FULL LOAD AMPS

FLEXIBLE METALLIC CONDUIT

FLOODLIGHT

FLUORESCENT

FLUORESCENT FIXTURE

TELEPHONE FLOOR OUTLET

FIRE PROTECTION

FEET OR FOOT

FUSED SWITCH

FULL VOLTAGE NON-REVERSING

FULL VOLTAGE REVERSING

GROUND OR GENERATOR

GENERATOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND TERMINAL BOX

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTOMATIC

HORSEPOWER

HEIGHT

HERTZ

ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

INTERMEDIATE METAL CONDUIT

INCANDESCENT

INFRARED

INSTANTANEOUS WATER HEATER

JUNCTION BOX

KILOVOLT

KILOVOLT AMPERE

KILOVOLT AMPERE PER HOUR

KILOVOLT AMPERE REACTIVE

KILOWATT

KILOWATT HOUR

KILOWATT HOUR METER

LIGHT EMITTING DIODE

LINEAR FEET (FOOT)

LUMEN

LIGHT POLE

LOW PRESSURE SODIUM

LOCKED ROTOR AMPS

LOCAL TEMPERATURE CONTROL PANEL

LIGHT

LIGHTING

LIGHTING PAINEL

LIGHTNING

LOW VOLTAGE

MASTER AINTENNA TELEVISION SYSTEM

MAXIMUM

METAL-CLAD

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MECHANICAL

MOTOR GENERATOR

MANHOLE

MINIMUM

MAXIMUM OVERCURRENT…