DRAWINGS 3.pdf
PDF 27 MB Posted
- Solicitation number
- PE-65700-NONST-2026-000000093
- Issued by
- Fayette County, Georgia
About this file
This is a technical drawings document (Drawing 3.pdf) for the Taxiway Bravo West Relocation project at Richard B. Russell Regional Airport in Floyd County, Georgia. The drawings provide comprehensive installation and construction specifications for airfield lighting and guidance sign infrastructure, including detailed vault plans, junction can details, in-pavement light fixture installations, and guidance sign foundations. The project encompasses multiple components including conduit installations with counterpoise grounding systems, base can installations at various depths, light fixtures with isolation transformers, and directional guidance signs positioned along taxiway routes. The drawings specify precise elevation requirements, material specifications (including PVC conduits, copper grounding components, galvanized steel elements, and concrete encasement), and installation sequences across three major steps: subgrade preparation and initial installation, concrete encasement and pavement integration, and final fixture and pavement ring installation.
The technical specifications require strict adherence to FAA Advisory Circular 150/5345-46 standards and include detailed requirements for grounding systems utilizing exothermic welds, #6 bare copper counterpoise wire, and 3/4-inch by 10-foot copper-clad steel ground rods. Installation procedures mandate survey verification of locations, elevation recordings at multiple stages, and inspections by the Responsible Project Representative (RPR) prior to continuation of work. The contractor assumes responsibility for furnishing all spacer rings, maintaining proper bolt torque settings using calibrated torque wrenches, protecting finished pavement surfaces from staining, and correcting any deficiencies caused by weather events or installation procedures at contractor expense. The guidance sign schedule identifies multiple sign locations along Taxiway A and Taxiway B with specific circuit numbers, FAA sizes and styles, module quantities, and station/offset coordinates for installation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DRAWINGS 2.pdf | ||
| Bid 26_022 Richard B_ Russell Taxiway Bravo W.pdf | ||
| DRAWINGS 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAULT PLAN
FINISHED SURFACE
1. CONNECTION TO GROUND RODS SHALL BE MADE USING EXOTHERMIC WELDS.
2. COUNTERPOISE SHALL BE INSTALLED 4" MINIMUM ABOVE THE CABLE OR
CONDUIT AND AS REQUIRED BY BELOW.
3. LOCATION OF THE COUNTERPOISE SHALL BE CALCULATED TO ENSURE THAT THE
CABLES AND/OR CONDUITS TO BE PROTECTED ARE WITHIN A 45° ZONE OF
PROTECTION BELOW THE COUNTERPOISE.
NOTES FOR CONDUIT NOT PARALLEL TO PAVEMENT:
4"
MIN.
2"
45°
CONE
3/4" X 10' GROUND
ROD MIN, (TYP)
EXOTHERMIC WELD
COUNTERPOISE
DUCT
2" PVC SCH 40
CONDUIT (TYP.)
SAND BACKFILL
" M
IN
3" M
IN
4"
M
IN
3" MIN
8" M
IN BACKFILL WITH
SUITABLE COMPACTED
MATERIAL REMOVED
FROM THE TRENCH
DETECTABLE TAPE SEE
L-110 OF THE
SPECIFICATIONS
CONDUIT SPACER
#6 AWG BARE COPPER
COUNTERPOISE WIRE
FINISHED GRADE
SECTION A-A SECTION B-B
0.
5" T
EX
T
(T
YP
≈ 2.0625" DIA
BRASS MARKER
SURV-KAP #M/M-B2 FLAT
TOP OR APPROVED
EQUAL
≈ 0.6875" DIA
2.
5"
0.
SEE NOTE 1
FINISHED SURFACE
OR PAVEMENT
3" M
IN
+0 .0
0" -0
.0
5"
1"
2.25" A A
B
B
CIRCUIT ID,
SEE NOTE 4
ELEVATION VIEW
INDIVIDUAL
JUNCTION CAN ID
JUNCTION CAN
PLAZA #
6" 2.
5"
N O
R
TH
JCP-1E
A-A
N O
R
TH
JCP#1
1' - 9"
3' - 6"
1' - 9" 1' - 9"
JUNCTION CAN IDENTIFICATION MARKER,
CONTRACTOR SHALL USE 3" MANUFACTURED
LETTERS AND DEPRESS LETTERS INTO WET
CONCRETE FOR A STROKE DEPTH OF 1/2"
3' - 6"
1' - 9"
XXX
VERTICAL SECTION VIEW
PLAN VIEW
2" DIAMETER BRASS CIRCUIT IDENTIFICATION
MARKER, SEE CIRCUIT IDENTIFICATION BRASS
MARKER DETAIL FOR ADDITIONAL
INFORMATION
2' - 6"
1" CHAMFER AROUND PERIMETER
CONCRETE ENCASEMENT AROUND JUNCTION CAN
16" DIAM, 24" DEEP, L-867 BASE CAN WITH GASKET
AND 1/2" GALVANIZED COVER PLATE WITH
COUNTER BORE HOLES FOR BOLTS
3/4" x 10' COPPER-CLAD STEEL GROUND
ROD
COMPACTED BACKFILL AROUND JUNCTION CAN
EXCAVATION WITH 4" TOPSOIL, SEEDING, AND
MULCHING PER SPECIFICATIONS
NEOPRENE GROMMET
1" PVC DRAIN PIPE WITH NEOPRENE
GROMMET AT BOTTOM OF BASE CAN
6" BASE OF #57 CRUSHED AGGREGATE
#6 SOLID BARE COPPER COUNTERPOISE, BOND TO
BASE CAN VIA BASE CAN GROUND LUG CLAMP
#6 BARE COPPER CONDUCTOR FROM
GROUND LUG CLAMP TO GROUND ROD,
EXOTHERMIC WELD TO GROUND ROD
2" PVC CONDUIT WITH PVC END BELLS AT BASE CAN
ENTRANCE, EXTEND ALL UNUSED CONDUITS 12" MIN
BEYOND CONCRETE ENCASEMENT AND CAP, TYP
4"
4"
SECTION A-A SECTION B-B
PLAN VIEW
12'' DIAMETER, 24'' DEEP L-867 LIGHT BASE CAN
1/2" ± 1/4" SLOPED TO DRAIN
LIGHT FIXTURE MOUNTING PLATE WITH 3/8" SS BOLTS
LIGHT FIXTURE STEM, SEE LIGHT FIXTURE AND BASE
CAN SCHEDULE FOR FIXTURE TYPE INFORMATION
FRANGIBLE COUPLING
6" CONCRETE ENCASEMENT AROUND BASE CAN
1" PVC DRAIN PIPE WITH NEOPRENE
GROMMET AT BOTTOM OF BASE CAN
#6 SOLID BARE COPPER COUNTERPOISE, BOND TO
BASE CAN VIA BASE CAN GROUND LUG CLAMP
#6 BARE COPPER CONDUCTOR FROM
GROUND LUG CLAMP TO GROUND ROD,
EXOTHERMIC WELD TO GROUND ROD
2" PVC CONDUIT WITH PVC END BELLS AND
NEOPRENE GROMMET AT BASE CAN ENTRANCE
3/4" x 10' COPPER-CLAD STEEL
GROUND ROD 6" MIN BELOW GRADE
6" BASE OF #57 CRUSHED AGGREGATE
6' EQUIPMENT GROUND TO GROUND LUG
PER LIGHT FIXTURE MANUFACTURER'S
INSTALLATION INSTRUCTIONS
L-823 PRIMARY CONNECTOR (TYP)
ISOLATION TRANSFORMER ON CONCRETE BRICK
L-823 SECONDARY CONNECTOR (STYLE 8)
5 KV AIRFIELD LIGHTING CABLE
ELEVATED AIRFIELD LIGHTING FIXTURE, SEE SPECIFICATION
L-125 FOR ADDITIONAL INFORMATION REGARDING FIXTURE
TYPE, ILLUMINATION SOURCE (QUARTZ OR LED) AND HEIGHT
CABLE TAG (TYP)
IN-PAVEMENT FIXTURE, SEE SPECIFICATION L-125
FOR ADDITIONAL INFORMATION ON FIXTURE TYPE
AND ILLUMINATION SOURCE (QUARTZ OR LED)
6' EQUIPMENT GROUND TO GROUND LUG
PER LIGHT FIXTURE MANUFACTURER'S
INSTALLATION INSTRUCTIONS
L-823 PRIMARY CONNECTOR (TYP)
ISOLATION TRANSFORMER ON CONCRETE BRICK
L-823 SECONDARY CONNECTOR
5 KV AIRFIELD LIGHTING CABLE
ANTI-ROTATION FINS
CABLE TAG (TYP)
L-823 PRIMARY CONNECTOR (TYP)
ISOLATION TRANSFORMER ON
CONCRETE BRICK
5 KV AIRFIELD LIGHTING CABLE
GUIDANCE SIGN L-867 BASE CAN
L-823 EXTENSION CORD TO SIGN POWER
LEG, 8' MIN LENGTH
L-823 SECONDARY CONNECTOR (TYP)
CABLE TAG (TYP)
REMOVE ALL LOOSE MATERIAL AND PLATE TAMP EXISTING
SUBGRADE PRIOR TO PLACEMENT OF AGGREGATE
NOTES:
1. IF BASE CAN EXCAVATION IS LEFT OPEN DURING A RAIN EVENT, THE SUBGRADE MUST BE INSPECTED BY THE RPR PRIOR TO CONTINUATION OF WORK. IF THE SUBGRADE OR ANY OTHER MATERIAL IS COMPROMISED BY THE RAIN, ADDITIONAL STEPS WILL BE TAKEN TO CORRECT ANY DEFICIENCIES
NOTED AT THE EXPENSE OF THE CONTRACTOR.
LIGHT IDENTIFICATION
TAG(TYP) LIGHT IDENTIFICATION
TAG(TYP)
LIGHT IDENTIFICATION
TAG(TYP)
BLUE RETROREFLECTIVE TAPE
OVER WHITE POST
MARKER POLE ANCHOR
COUPLING WITH INTERNAL
HINGE
GALVANIZED STEEL SOIL
ANCHOR
36" DIA. CORE-DRILL
C O
R E-
D R
IL
L
D
EP
TH
S
EE
N
O
TE
STEP 2
1. PREPARE SUBGRADE, INSTALL #6 BARE COPPER COUNTERPOISE CABLE AND GROUND ROD.
INSTALL REBAR CAGE AND BOND WITH A #6 AWG BARE COPPER GROUND WIRE TO
EXTERNAL GROUND LUG ON BASE CAN WITH AN EXOTHERMIC WELD. INSTALL BASE CAN
AND CONNECT TO CONDUIT. PRIOR TO POURING CONCRETE ENCASEMENT, INSTALL A JIG
TO STABILIZE THE BASE CAN SECTIONS DURING CONCRETE PLACEMENT, AND PLACE
CONCRETE ENCASEMENT. THE CONTRACTOR SHALL RECORD THE STATION AND ELEVATION
OF MUD PLATE AND PROVIDE THIS INFORMATION TO THE OWNER.
2. POUR P-610 CONCRETE AROUND NEW BASE CAN AND CONDUIT. VIBRATE CONCRETE TO
ELIMINATE ANY VOIDS.
3. PRIOR TO PAVEMENT OVERLAY OPERATIONS, THE CONTRACTOR SHALL RECORD THE
STATION AND ELEVATION OF CENTER POINT OF THE BASE CAN MUD PLATE AND PROVIDE
THIS INFORMATION TO THE OWNER.
4. IF BASE CAN EXCAVATION IS LEFT OPEN DURING A RAIN EVENT, THE SUBGRADE MUST BE
INSPECTED BY THE RPR PRIOR TO CONTINUATION OF WORK. IF THE SUBGRADE OR ANY
OTHER MATERIAL IS COMPROMISED BY THE RAIN, ADDITIONAL STEPS WILL BE TAKEN TO
CORRECT ANY DEFICIENCIES NOTED AT THE EXPENSE OF THE CONTRACTOR.
ELEVATION
STEP 1
1. REVIEW AREA PLANS AND LOCATE EXISTING LIGHT LOCATIONS
BY SURVEY. CONFIRM LOCATIONS WITH RPR PRIOR TO CORING
EXISTING BASE CAN AND PAVEMENT.
2. CORE DRILL A 36" DIAMETER HOLE TO REMOVE EXISTING
ASPHALT AND BASE AT A DETERMINED DEPTH THAT ALLOWS A
MINIMUM OF 6" OF CONCRETE BENEATH THE BASE CAN AND 6"
OF P-209 BENEATH THE CONCRETE. REMOVE AND
DISPOSE OF THE CORE.
3. IF REQUIRED, COMPACT EXISTING SUBGRADE. ANY DEBRIS OR
MATERIAL THAT FALLS INTO THE CORE SHALL BE REMOVED
PRIOR TO INSTALLATION OF THE BASE CAN.
ELEVATION
STEP 3
1. AFTER PAVEMENT OVERLAY OPERATIONS HAVE BEEN COMPLETED, PILOT
CORE TO FIND MUD PLATE CENTER POINT INDENT BEFORE 13-1/2"
CORE-DRILLING. CORE-DRILL THE PAVEMENT.
2. INSTALL TOP SECTION, LIGHT FIXTURE, AND PAVEMENT RING. AS REQUIRED TO
MEET FINAL GRADE, PROVIDE ADDITIONAL SPACER RINGS (MAX 3/8" THICK TO
1/16" MIN THICK). NO MORE THAN 2 SPACER RINGS (MAX 3/8" THICK EACH)
SHALL BE USED TO ACHIEVE FINAL GRADE. POUR THE P-605, TO FILL THE VOID
BETWEEN THE TOP CAN SECTION AND THE PAVEMENT TO 3/4" BELOW
SURFACE GRADE. THE REMAINING VOID SHALL BE FILLED WITH P-605.
THE HEIGHT OF THE L-868 EXTENSION SHALL BE DETERMINED AS FOLLOWS:
1. RECORD FINAL ELEVATION OF THE TOP AND AT THE MIDPOINT OF THE MUD
PLATE AFTER THE BOTTOM SECTION OF THE BASE CAN HAS BEEN INSTALLED.
2. RECORD FINAL ELEVATION OF THE PAVEMENT DIRECTLY ABOVE THE MIDPOINT
OF THE MUD PLATE AFTER THE PAVEMENT IS COMPLETELY INSTALLED.
ELEVATION
6" GDOT ASPHALT SURFACE COURSE
PROPOSED 12"
CRUSHED
AGGREGATE BASE
COURSE
EXISTING SUBGRADE
#57 STONE 6"
DEEP
GROUND LUG ON
INTERIOR AND
EXTERIOR
OF CAN
3/4" X 10' COPPER-CLAD
STEEL GROUND ROD
REBAR CAGE
NEOPRENE GROMMET AT
CAN ENTRANCE AND
BELL END ON CONDUIT
INSIDE OF CAN (TYP.)
5/8 " THICK PLYWOOD SHIPPING
COVER TO REMAIN UNTIL
CONCRETE HAS FULLY CURED
P-610 CONCRETE
ENCASEMENT 6"
3"
#6 BARE COPPER
COUNTERPOISE WIRE
L-868B BASE CAN,
12" DIA., DEPTH AS REQUIRED
FOR CONDUIT CONNECTION
13-1/2"
CORE-DRILL
L-850C IN-PAVEMENT RUNWAY EDGE LIGHT,
ON L-868B BASE CAN EXTENSION, 3/4" THICK
FLANGE RING WITH PAVEMENT DAM,
PROVIDE SPACER RINGS AS REQUIRED TO
MEET FINAL GRADE.
SEE DETAIL 2, THIS SHEET
#6 STRANDED COPPER,
GREEN BONDING JUMPER
WITH 6' OF SLACKPROPOSED 6" ASPHALT
12" (TYP.)
LIGHT FIXTURE
STAINLESS STEEL BOLTS COMPLIANT WITH ASTM F593C,
SHALL BE DUAL-COATED WITH CERAMIC METALLIC BASE
COAT AND FLUROPOLYMER TOP COAT WITH INTEGRATED
2-PART WASHER. PINK IN COLOR AS MANUFACTURED BY
MCB OR APPROVED EQUAL, COMPLIANT WITH AC
150/5345-42 (LATEST EDITION), AND EB #83A
5/ 8"
1/8"
3/ 4"
3/ 4"
SEAL BETWEEN SPACER
AND CONCRETE WITH
SEALANT PER P-605.
FLANGE RING WITH PAVEMENT DAM AND
O RING GROOVE, SHEET NOTE 1
L-868, SIZE B, CLASS I BASE
TOP EDGE OF BASE PLATE OR
LIGHT FIXTURE SHALL BE
0" TO 1/16" BELOW PAVEMENT
GRADE AT LOWEST ELEVATION
.5" (MIN.)
TWY
B(TYP.)
TWY B
(TYP.)
PROPOSED 12"
CRUSHED
AGGREGATE BASE
COURSE
EXISTING SUBGRADE
PROPOSED 6" ASPHALT
SHEET NOTES:
1. THE FLANGE RING WITH PAVEMENT DAM IS DESIGNED AS A NOMINAL 3/4"
THICKNESS FOR THE FLANGE RING PORTION. THE FLANGE RING MAY BE REQUIRED
TO BE THINNER OR THICKER DEPENDING ON BASE CAN INSTALLATION AND PAVING
TECHNIQUES. THE CONTRACTOR SHALL BE RESPONSIBLE TO MEASURE AND
DETERMINE THE EXACT REQUIRED THICKNESS OF EACH INDIVIDUAL SPACER RING
REQUIRED TO PUT THE AIRFIELD LIGHTING FIXTURE AT THE CORRECT ELEVATION,
AZIMUTH AND ROTATION PER FAA ADVISORY CIRCULAR 150/5345-46 LATEST
EDITION. A MAXIMUM OF THREE RINGS (SPACER, BEVEL OR FLANGE RING) MAY BE
STACKED TOGETHER WITH A MAXIMUM HEIGHT OF 2-3/16". THE CONTRACTOR'S BID
PRICE SHALL INCLUDE FURNISHING AND INSTALLING ALL SPACER RINGS. BASE
CANS, SPACER RINGS AND FLANGE RING SHALL BE GALVANIZED WITH GROOVE
FOR O-RING, EPOXY COATING NOT REQUIRED.
2. THE P-605 SEALER SHALL FILL THE VOID TO WITHIN 0.125" OF THE TOP EDGE OF
THE CONCRETE RING AT THE LOWEST CONCRETE ELEVATION. ANY OVER POURS
SHALL BE REPLACED BY THE CONTRACTOR AT THEIR EXPENSE.
3. IMMEDIATELY AFTER THE HOLES ARE CORED IN THE CRUSHED AGGREGATE BASE
COURSE, THE BASE CANS SHALL BE INSTALLED AND THE P-610 PLACED SO AS TO
PREVENT WATER FROM ENTERING THE STABILIZED SUBGRADE.
4. BEFORE PAVING MAY PROCEED, THE CONTRACTOR SHALL DEMONSTRATE TO THE
RPR BY SURVEY THAT THE BASE CANS ARE AT THE CORRECT ELEVATION, AZIMUTH
AND ROTATION AND THAT THE PROPER CLEARANCE EXISTS BETWEEN THE BASE
CAN AND THE PAVING TRAIN.
5. THE FINISHED PAVEMENT SURFACE SHALL BE PROTECTED FROM FOREIGN
SUBSTANCES WHICH WOULD CAUSE STAINING, I.E.. OIL, P-605, ETC. THE
CONTRACTOR SHALL IMMEDIATELY CLEAN ALL SPILLS AND CORRECT/CLEAN ANY
STAINED SURFACES AT THE CONTRACTORS EXPENSE.
6. USE ACETATE RESISTANT, CONDUCTIVE SEALANT BETWEEN ADAPTER/SPACER
RINGS. ALSO, USE BETWEEN ADAPTER/SPACER RING AND BASE CAN. DO NOT
INSTALL EXCESSIVE AMOUNTS OF SEALANT. THE SEALANT SHALL NOT ACT A
BARRIER BETWEEN THE SPACER RING(S) AND BASE CAN AND ADAPTER RING AND
FLANGE RING. METAL TO METAL CONTACT SHALL BE MAINTAINED BETWEEN THE
BASE CAN, SPACER RING(S) AND ADAPTER RING AND FLANGE RING.
7. THE FIXTURE MOUNTING BOLTS SHALL EXTEND THROUGH THE BASE CAN
MOUNTING FLANGE INTO THE BASE CAN A MINIMUM OF 1/2". THE BOLTS SHALL
HAVE ENOUGH THREAD LENGTH SO THEY DO NOT SHOULDER OUT BEFORE THE
FIXTURE IS SECURELY TIGHTENED. THE BOLTS SHALL BE TORQUE PER THE
MANUFACTURERS RECOMMENDATIONS. THE BOLTS SHALL BE SUPPLIED WITH CEC
LOCK WASHERS.
8. ALL BOLTS USED FOR L-868 BASE CANS SHALL BE OF THE SAME MANUFACTURER
AND TYPE. BOLT TORQUE SETTINGS SHALL BE SUBMITTED TO THE ENGINEER FOR
REVIEW PRIOR TO INSTALLATION OF NEW BOLTS. IN-PAVEMENT FIXTURE BOLTS
ARE ONE-TIME USE ONLY. NEVER REUSE THE BOLTS OR LOCKING WASHERS FOR
IN-PAVEMENT LIGHT FIXTURES. TORQUE ALL BOLTS TO THE TORQUE VALUE
SPECIFIED BY THE FIXTURE MANUFACTURER WITH A CALIBRATED TORQUE
WRENCH. DO NOT USE IMPACT WRENCHES, THEY ARE NOT DESIGNED FOR THE
LOW BOLT TORQUES REQUIRED FOR IN-PAVEMENT LIGHT FIXTURES.
REMOVE ALL LOOSE MATERIAL AND PLATE
TAMP EXISTING SUBGRADE PRIOR TO
PLACEMENT OF AGGREGATE
VARIES BY MODULE COUNT
SECTION "A - A"
GUIDANCE SIGN NOTES
1. 2" GALVANIZED FLANGE, ATTACH TO SIGN FOUNDATION WITH BOLTS AS
SPECIFIED IN SIGN MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. 3/4" PVC SLEEVE FOR GROUND WIRE, COORDINATE LOCATION WITH
GUIDANCE SIGN EXTERNAL GROUND LUG, GROUT AFTER GROUND
WIRE INSTALLATION.
3. SIGN POWER LEG, SEE "SIGN POWER LEG DETAIL" AT TOP RIGHT OF
SHEET FOR ADDITIONAL INFORMATION.
4. 2" CONDUIT WITH MANUFACTURED ELBOW FROM BASE CAN TO TOP
SURFACE OF SIGN FOUNDATION, COORDINATE CONDUIT TYPE (PVC OR
RGS) WITH SIGN MANUFACTURER'S INSTALLATION INSTRUCTIONS,
PROVIDE ADAPTERS AND COUPLINGS AS REQUIRED.
5. COUNTERPOISE ASSOCIATED WITH INCOMING CONDUIT TO GUIDANCE
SIGN SHALL NOT BE BONDED TO GUIDANCE SIGN BASE CAN.
TERMINATE INCOMING COUNTERPOISE, VIA EXOTHERMIC WELD, TO
DEDICATED 3/4" x 10' COPPER CLAD STEEL GROUND ROD.
6. THE DETAILS SHOWN ON THIS SHEET, PLUS ANY ADDITIONAL
REQUIREMENTS ASSOCIATED WITH THE GUIDANCE SIGN
MANUFACTURER'S INSTALLATION INSTRUCTIONS, SHALL BE
CONSIDERED INCIDENTAL TO THE GUIDANCE SIGN PAY ITEM.
SIGN POWER LEG DETAIL
XX-XX
SECTION "B - B"
2' - 0"
B
A A
PLAN VIEW
5' - 6"
B
10"
SEE NOTE 1
SEE NOTE 2
#6 BARE COPPER CONDUCTOR FROM
BASE CAN EXTERNAL GROUND LUG
CLAMP TO GROUND ROD, EXOTHERMIC
WELD TO GROUND ROD
3/4" x 10' COPPER-CLAD STEEL
GROUND ROD 6" MIN BELOW GRADE
#6 BARE COPPER GROUND FORM
GUIDANCE SIGN EXTERNAL
GROUND LUG FROM GROUND LUG,
EXOTHERMIC WELD TO GROUND
ROD
#6 BARE COPPER GROUND, BOND TO
REBAR WITH UL LISTED MECHANICAL
CONNECTOR AND EXOTHERMIC
WELD TO GROUND ROD
GUIDANCE SIGN
EXTERNAL GROUND
LUG
SIGN TETHER, TYP
SEE NOTE 4
SEE NOTE 3
REFERENCE POINT FOR SITING
LOCATION OF GUIDANCE SIGN
FRANGIBLE COUPLING
CABLE CLAMP
L-823 EXTENSION CORD, 8' MIN LENGTH
TO SIGN POWER LEG
MOUNTING FLANGE
L-823 CORDSET
TERMINATE INCOMING CONDUIT FROM
BASE CAN FLUSH WITH SIGN
FOUNDATION
BOTTOM OF GUIDANCE SIGN FRAME
TOP SURFACE OF SIGN FOUNDATION
PROVIDE 1/4" SLOPE PER
FOOT TO DRAIN
12" DIA, 24" DEEP, L-867 BASE CAN WITH
GASKET AND 1/2" GALVANIZED COVER
PLATE WITH COUNTER BORE HOLES
FOR BOLTS. SEE GUIDANCE SIGN
ELECTRICAL CONNECTIONS DETAIL
FOR ADDITIONAL INFORMATION
6" CONCRETE ENCASEMENT AROUND
BOTTOM AND SIDES OF BASE CAN
1" PVC DRAIN PIPE WITH NEOPRENE
GROMMET AT BOTTOM OF BASE CAN
6" BASE OF #57 CRUSHED AGGREGATE
GUIDANCE SIGN SHALL INCLUDE AN
"ON/OFF" SWITCH WITH WEATHER
PROOF COVER TO DE-ENERGIZE SIGN
DURING MAINTENANCE
GUIDANCE SIGN IDENTIFICATION TAG
REFERENCE POINT FOR SITING
LOCATION OF GUIDANCE SIGN
REBAR, SEE PLAN VIEW FOR
ADDITIONAL INFORMATION
1" CHAMFER AROUND PERIMETER OF
SIGN FOUNDATION
COMPACTED BACKFILL AROUND SIGN
WITH TOPSOIL, SEEDING, AND
MULCHING PER SPECIFICATIONS
EXTEND ALL UNUSED CONDUITS 12" BEYOND
MAINTENANCE PAD AND SEAL WITH PVC CAP,
TYP
#6 BARE COPPER CONDUCTOR FROM BASE CAN
EXTERNAL GROUND LUG CLAMP TO GROUND ROD,
EXOTHERMIC WELD TO GROUND ROD
3/4" x 10' COPPER-CLAD STEEL
GROUND ROD 6" MIN BELOW GRADE
#6 BARE COPPER GROUND FORM
GUIDANCE SIGN EXTERNAL GROUND LUG
FROM GROUND LUG, EXOTHERMIC WELD
TO GROUND ROD
#6 BARE COPPER GROUND, BOND TO REBAR
WITH UL LISTED MECHANICAL CONNECTOR AND
EXOTHERMIC WELD TO GROUND ROD
#4 VERTICAL REBAR, PROVIDE 3" OF CONCRETE
COVERAGE BETWEEN CAN AND REBAR, TYP OF 6
#3 HORIZONTAL REBAR RINGS, 18" DIA SPACED AT
8" O.C. VERTICALLY, PROVIDE 3" OF CONCRETE
COVERAGE BETWEEN CAN AND REBAR, TYP
2" PVC CONDUIT WITH PVC END BELLS AND
NEOPRENE GROMMET AT BASE CAN
ENTRANCES, TYP
GRID OF #3 REBAR AT 12" O.C. EACH WAY
MAINTAIN 3" OF COVERAGE CONCRETER
BETWEEN OUTER REBAR AND EDGE OF
MAINTENANCE PAD
OUTLINE OF BOTTOM OF GUIDANCE SIGN FRAME
DEPTH OF REBAR REINFORCEMENT
TO BE 5" FROM TOP OF FOUNDATION
TOP OF FOUNDATION
SHALL BE 1" ABOVE
GRADE MAX
1. CABLES SHALL NOT BE PLACED LESS THAN 24-INCHES DEEP IN ANY ONE
TRENCH. CABLES WITH DIFFERENT VOLTAGE RATINGS SHALL NOT BE INSTALLED
IN THE SAME TRENCH. THREE FEET OF CABLE SLACK SHALL BE PROVIDED ON
BOTH SIDES OF THE FIXTURE.
2. UNIT DUCT SHALL BE TERMINATED BEFORE THE L-823 CONNECTORS AND
SEALED WITH HEAT SHRINK AS SPECIFIED.
ARE OPPER
GROUND ONDUTOR
EXISTING CONCRETE
ENCASED DUCT
NEW CONCRETE
ENCASED DUCT
SIGN PANELS
TYPE COLOR LEGEND SYMBOL
L-858L YELLOW INSCRIPTION AND BORDER ON BLACK BACKGROUND
L-858R WHITE INSCRIPTION WITH BLACK BORDER ON RED BACKGROUND
L-858Y BLACK INSCRIPTION ON YELLOW BACKGROUND
L-858B WHITE INSCRIPTION ON BLACK BACKGROUND
SIGN PANEL TO REMAIN N/A
SIGN PANEL TO BE REMOVED N/A
16R-34L
A
A5
A
S1
PROPOSED GUIDANCE SIGN SCHEDULE
SIGN #
LEGEND ARROW DIRECTION
CIRCUIT NO. FAA SIZE FAA STYLE QTY. OF
MODULES
LOCATION REFERENCE
DRAWING
FRONT BACK FRONT BACK STATION OFFSET
- TWY A 2 3 3 1420+31.92 144.8122
- 3 1420+49.18 99.41
- 3 1421+78.82 99.41
- - 1401+99.86 46.59
- 1424+06.90 -53.02
- 1423+34.22 48.37
270° | 90° - 1419+09.30 -37.49
B -
B1 7 B1
A7-25 A
AA 7-25
19 - 1B B
R/W 7/25
R/W 7/25
R/W 7/25
R/W 1/19
TWY B
TWY B
EL-203
EL-203
EL-203
EL-201
EL-203
EL-203
EL-203
A
AB
AB
270° | 90°
270° | 90°
1. CONTRACTOR SHALL STAKE OUT SIGN REFERENCE POINT FOR RPR PRIOR TO
INSTALLATION OF SIGN FOUNDATION. COST SHALL BE INCIDENTAL TO
INSTALLATION OF SIGNS.
270° - 1419+49.85 88.6523 R/W 1/19 1 EL-203B - 2 3
NEW OR
RELOCATED
RELOCATED
NEW
RELOCATED
RELOCATED
RELOCATED
RELOCATED
NEW
RELOCATED