Drawings 24-33.pdf

PDF 26 MB Posted

Attached to
6115--Project 621-19-123 - Replace 750kW Emer Gen. in Bldg. 116
Solicitation number
36C24921B0011
Issued by

About this file

This federal presolicitation notice is for the replacement of a 750kW emergency generator at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project number is 6115--Project 621-19-123 and has an estimated value between $500,000 and $1,000,000. The NAICS code is 238210 and the small business size standard is $16.5 million. The solicitation is expected to be posted on June 28, 2021 and close on July 28, 2021. This is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. Offerors must be listed in the CVE database and SAM, and the awarded contractor must submit evidence of VETS4212 enrollment. The contracting officer is Diana Grube and questions must be submitted in writing to her email with the project information in the subject line before the solicitation is issued.

View the file

Other files

File Type Posted
36C24921B0011 0002.pdf PDF
36C24921B0011 0001.docx DOCX document
Building 116 Lead and Asbestos Survey Results.pdf PDF
RFI Form - 750kW Emergency Gen.pdf PDF
Drawings 11-17.pdf PDF
Specs 621-19-123 Replace Emerg Generator Bldg 116 - Bid Documents .pdf PDF
EMR.pdf PDF
WD TN20210111 dated 1-1-2021.pdf PDF
Drawings 18-23.pdf PDF
Header - List of Attachments.txt TXT text file
36C24921B0011_1.docx DOCX document
Drawings 1-10.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NAMING CONVENTION

ES-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - SPECIFICATIONS

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

ELECTRICAL GENERAL NOTES:

1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:

A. NFPA 70 NATIONAL ELECTRICAL CODE, 2020 EDITION

B. NFPA 99 HEALTH CARE FACILITIES CODE, 2021 EDITION

C. NFPA 101 LIFE SAFETY CODE, 2021 EDITION

D. NFPA 110 EMERGENCY AND STANDBY POWER SYSTEMS, 2019 EDITION

E. NFPA 780 STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, 2020 EDITION

F. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.

2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%

FULL.

3. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT, CLEARANCE FOR RECESSED LUMINAIRES, AND CORRECT ROUGH-IN LOCATIONS OF

ELECTRICAL CONNECTIONS.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL

DESCRIPTIONS INDICATED.

5. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.

6. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE NEUTRAL CONDUCTORS AS INDICATED HEREIN. MULTIPLE BRANCH CIRCUITS IN ONE

RACEWAY REQUIRE ONLY ONE EQUIPMENT GROUNDING CONDUCTOR.

7. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DEMOLISHED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DEMOLISHED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AT NO ADDITIONAL

COST TO THE OWNER.

8. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER. SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE

EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.

9. REFER TO SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.

10. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK THAT SHALL BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

11. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK THAT SHALL BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE

CONTRACTOR'S RESPONSIBILITY.

12. ALL CONDUCTORS SHALL BE COPPER.

13. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY

MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.

14. PROVIDE LABELS ON ALL RECEPTACLES, LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED

CEILING WHICH MAY BE HANDWRITTEN WITH AN INDELIBLE MARKER.

15. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.

16. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME EMERGENCY POWER (ARTICLE 700 LOADS) IS "ON LINE" SHALL NOT EXCEED 10 SECONDS. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME LEGALLY REQUIRED (ARTICLE 701) POWER IS "ON LINE" AND SHALL NOT BE NO MORE THAN 60 SECONDS. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME OPTIONAL STANDBY POWER (ARTICLE 702 LOADS) IS "ON LINE" AND SHALL BE NO LESS THAN 60 SECONDS BUT NO MORE THAN 120 SECONDS.

ELECTRICAL ABBREVIATIONS

A or AMP

AC

ACC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

COR

CP

CPT

CRAC

CRI

CT

CU

CWP

D

DC

DF

DH

DHWCP

DISC

DOAS

DPDT

DPST

DSCU

DSHP

DSS

DUH

DWBP

DX

E or EMER

EC

EF

ELEC

EMEW

EMH

EMSH

EMT

EPA

EQUIP

ERU

ERV

ESEW

EUH

EWC

EWH

EX or EXIST

EXP

F

FACP

FCU

FLEX

FWE

G or GND

GFCI

GFGI

GRC

GUH

GWH

H or HT

HAC

HOA

HP

HT

HVU

HWCP

HWP

HWRP

HWSP

HWUH

HZ

AMPERE(S)

AIR COMPRESSOR or AIR CURTAIN or

ALTERNATING CURRENT

AIR COOLED CHILLER

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CHILLER

CHILLED WATER CIRCULATING PUMP

CHILLED WATER PUMP

CHILLED WATER SUPPLY PUMP

CIRCUIT

COMMUNICATIONS MANHOLE

CONTRACTING OFFICER'S REPRESENTATIVE

CONDENSATE PUMP

CONTROL POWER TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER or COOLING TOWER

COPPER

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATER or DEHUMIDIFIER

DOMESTIC HOT WATER CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR SYSTEM

DOUBLE POLE DOUBLE THROW

DOUBLE POLE SINGLE THROW

DUCTLESS SPLIT CONDENSING UNIT

DUCTLESS SPLIT HEAT PUMP

DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DUCT UNIT HEATER

DOMESTIC WATER BOOSTER PUMP

DIRECT EXPANSION COOLING COIL

EMERGENCY

EMPTY CONDUIT

EXHAUST FAN

ELECTRICAL

EMERGENCY EYEWASH

ELECTRICAL MANHOLE

EMERGENCY SHOWER

ELECTRICAL METALLIC TUBING

EFFECTIVE PROJECTED AREA

EQUIPMENT

ENERGY RECOVERY UNIT

ENERGY RECOVERY VENTILATOR

EMERGENCY SHOWER / EYEWASH

ELECTRIC UNIT HEATER

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXISTING

EXPLOSION PROOF

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED CONTRACTOR

INSTALLED or GROUND FAULT CIRCUIT

INTERRUPTER

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GALVANIZED RIGID STEEL CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER or HEAT PUMP

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER CIRCULATING PUMP

HEATING WATER PUMP

HOT WATER RECIRCULATION PUMP

HEATING WATER SUPPLY PUMP

HOT WATER UNIT HEATER

HERTZ

IDS

IMC

IRH

J OR JB

K

KAIC

KCMIL

KEF

KH

KV

KVA

KVAR

KW

KWHR

L

LA

LAN

LAV

LTG

MAU

MAX

MCA

MCB

MCC

MGB

MH

MIN

MLO

MOD

MRS

MT or MTD N

NC

NEC

NEMA

NESC

NFPA

NL

NO

NTS

P

PA

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

RECP

RF

RH

RMC

RMS

RTU

RVNR

SA

SCCR

SD

SF

S/N

SP

SPD

SPDT

SPEC

SPST

SWBD

SWGR

TMGB

TOL

TP

TYP

U

UG

UH

UIO

UL

UTP

V

VA

VAR

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WP

WSHP

XFMR

Z

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE INTERRUPTING CAPACITY

THOUSAND OF CIRCULAR MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT AMPERES

KILOVOLT AMPERES REACTIVE

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOTOR RATED SWITCH

MOUNT or MOUNTED

NEUTRAL

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL ELECTRICAL SAFETY CODE

NATIONAL FIRE PROTECTION ASSOCIATION

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

PRIMARY INDUCTION UNIT (VAV TERMINAL UNIT)

PAD MOUNTED TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RECEPTACLE

RETURN FAN

RADIANT HEATERS (ELECTRIC)

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SURGE ARRESTOR

SHORT CIRCUIT CURRENT RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE THROW

SPECIFICATIONS

SINGLE POLE SINGLE THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNDERGROUND

UNIT HEATER

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VOLT AMPERES REACTIVE

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT FLOW SYSTEM

WATTS or WIRE

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WEATHERPROOF

WATER SOURCE HEAT PUMP

TRANSFORMER

IMPEDANCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :0

P

M

ES-001

ELECTRICAL GENERAL NOTES &

ABBREVIATIONS

MAY 14, 2021 WSP TED

BID DOCUMENTS

NOTE:

1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS

PROJECT.

WIRE SIZE FOR ALL 120V, 20A CIRCUITS,UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 75 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 125 FT AND

GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 190 FT AND

GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 300 FT AND

GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G, 3/4"C.

NOTES:

1. 'E' NEXT TO A DEVICE INDICATES THE DEVICE IS EXISTING TO

REMAIN. 'D' NEXT TO A DEVICE INDICATES IT IS TO BE

DEMOLISHED.

2. ALL EXISTING EQUIPMENT IS SHOWN IN THIN LINEWORK. ALL

DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

Revisions: Date:

1/2

B

W

S B

M

M

2/60/40/1

60/40/3/3R

40/3/3R

CB

T

M

EM

J J

J

A

AE

M

X

C

D a b

LUMINAIRES

LUMINAIRE AND OUTLET BOX. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

LUMINAIRE AND OUTLET BOX WIRED FOR

MULTILEVEL SWITCHING, LOWER CASE LETTER

INDICATES SWITCHLEG DESTINATION.

LUMINAIRE AND OUTLET BOX, WITH PROVISIONS

FOR EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED EXIT SIGN AND

OUTLET BOX. PROVIDE NUMBER OF ARROWS

AND FACES INDICATED. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNT AT 96" ABOVE FINISHED FLOOR.

RECESSED OR PENDANT MOUNTED LUMINAIRE

AND OUTLET BOX. LETTER INDICATES LUMINAIRE

TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED LUMINAIRE AND

OUTLET BOX WITH PROVISIONS FOR

EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

EMERGENCY LIGHT UNIT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

REMOTE HEAD OR FLOOD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

WALL WASH DOWNLIGHT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POLE MOUNTED LUMINAIRE. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POST-TOP OR BOLLARD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

EQUIPMENT

MOTOR, HORSEPOWER AS INDICATED

MOTORIZED DAMPER

3-POLE COMBINATION MAGNETIC MOTOR

STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/

NEMA ENCLOSURE) NF = NONFUSED

DISCONNECT SWITCH, (SWITCH AMPS/ FUSE

SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-

FUSED

INDIVIDUALLY MOUNTED CIRCUIT BREAKER,

(CIRCUIT BREAKER SIZE/ POLES/ NEMA

ENCLOSURE)

DRY TYPE TRANSFORMER

METER

ELECTRONIC METER

SURFACE MOUNTED PANELBOARD. DASHED BOX

INDICATES WORKING ACCESS REQUIRED BY

CODE.

RECESSED MOUNTED PANELBOARD. DASHED

BOX INDICATES WORKING ACCESS REQUIRED

BY CODE.

DISTRIBUTION PANELBOARD. DASHED BOX

INDICATES WORKING ACCESS REQUIRED BY

CODE.

EQUIPMENT AS INDICATED

CEILING OR WALL MOUNTED JUNCTION BOX

PULL OR JUNCTION BOX

CEILING MOUNTED BLUE LIGHT SYSTEM

ROTATING BEACON

WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE

DROP CEILING

EMERGENCY POWER OFF SWITCH

CR

ST

TR

M

R

P2A-1,3,5

WIRING DEVICES

4-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

SLIDE DIMMER, MOUNT 48" ABOVE FINISHED

FLOOR

MOTOR RATED DISCONNECT SWITCH WITH

THERMAL OVERLOADS, SINGLE POLE SINGLE

THROW, MOUNT ON UNIT, UNLESS INDICATED

OTHERWISE.

WALL MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

WALL MOUNTED, DUAL TECHNOLOGY VACANCY

SWITCH, MOUNT 48" ABOVE FINISHED FLOOR

LOW VOLTAGE ON/OFF WALL SWITCH, WALL

MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE

DIMMER CONTROL WITH DIMMABLE FIXTURES

INTEGRAL WITH SWITCH.

BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT

48" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

WHITE NOISE ROTARY VOLUME CONTROL;

MOUNT 48" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE.

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

CEILING MOUNTED DUAL TECHNOLOGY

VACANCY SENSOR

CEILING MOUNTED DAYLIGHT SENSOR

PHOTOELECTRIC CELL

WIRING

CIRCUIT HOMERUN TO PANELBOARD. P2A-1,3,5,

ADJACENT TO ARROW, INDICATES HOMERUN

CIRCUITS 1, 3, AND 5 IN PANEL P2A. MARKS

ACROSS RACEWAY INDICATE THE NUMBER OF

PHASE CONDUCTORS AND NEUTRALS IN

RACEWAY. NEUTRAL CONDUCTORS ARE

INDICATED BY LONGER HASHMARKS. NO MARKS

ACROSS RACEWAY INDICATES 2#12

CONDUCTORS AND 1#12 GROUND CONDUCTOR.

CONDUCTOR SIZE #12 UNLESS INDICATED

OTHERWISE.

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

PLUG-IN BUSWAY, UNLESS INDICATED

OTHERWISE

SURFACE METAL RACEWAY OR MULTIOUTLET

ASSEMBLY AS INDICATED

LADDER TYPE CABLE TRAY (SIZE AS INDICATED

ON PLAN)

WIRING DEVICES

SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE.

DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"

ABOVE FINISHED FLOOR (TO CENTERLINE OF

DEVICE) OR 6" ABOVE COUNTERTOP (TO

BOTTOM OF DEVICE) OR 4" ABOVE BACKSPLASH

(TO BOTTOM OF DEVICE)

DUPLEX GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE NEMA 5-20R, MOUNT 18" ABOVE

FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE NEMA 5-20R, MOUNT 48" ABOVE

FINISHED FLOOR (TO CENTERLINE OF DEVICE)

OR 6" ABOVE COUNTERTOP (TO BOTTOM OF

DEVICE) OR 4" ABOVE BACKSPLASH (TO BOTTOM

OF DEVICE)

DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 18" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE

SPLIT YOKE, DUPLEX RECEPTACLE NEMA 5-20R

WITH ONE CONTROLLED AND ONE NON-

CONTROLLED RECEPTACLE. MOUNT 18" ABOVE

FINISHED FLOOR, UNLESS INDICATED

OTHERWISE.

SPLIT YOKE, DUPLEX RECEPTACLE NEMA 5-20R

WITH ONE CONTROLLED AND ONE NON-

CONTROLLED RECEPTACLE. MOUNT 48" ABOVE

FINISHED FLOOR (TO CENTERLINE OF DEVICE)

OR 6" ABOVE COUNTERTOP (TO BOTTOM OF

DEVICE) OR 4" ABOVE BACKSPLASH (TO BOTTOM

OF DEVICE)

SPLIT YOKE, DUPLEX GROUND FAULT CIRCUIT

INTERRUPTER RECEPTACLE NEMA 5-20R WITH

ONE CONTROLLED AND ONE NON-CONTROLLED

RECEPTACLE. MOUNT 18" ABOVE FINISHED

FLOOR, UNLESS INDICATED OTHERWISE

SPLIT YOKE, DUPLEX GROUND FAULT CIRCUIT

INTERRUPTER RECEPTACLE NEMA 5-20R, WITH

ONE CONTROLLED AND ONE NON-CONTROLLED

RECEPTACLE. MOUNT 48" ABOVE FINISHED

FLOOR (TO CENTERLINE OF DEVICE) OR 6"

ABOVE COUNTERTOP (TO BOTTOM OF DEVICE)

OR 4" ABOVE BACKSPLASH (TO BOTTOM OF

DEVICE)

DOUBLE-DUPLEX GROUND FAULT CIRCUIT

INTERRUPTER RECEPTACLE, NEMA 5-20R,

MOUNTED CONCEALED BEHIND ELECTRIC

WATER COOLER

FLOOR BOX WITH DUPLEX RECEPTACLE NEMA

5-20R. PROVIDE FIRE RATED POKE THRU

DEVICES ON ALL FLOORS ABOVE GROUND

LEVEL.

SPECIAL RECEPTACLE, NEMA TYPE AS

INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,

UNLESS INDICATED OTHERWISE

CEILING BOX WITH DUPLEX RECEPTACLE, NEMA

5-20R

RECEPTACLE WP = IN-USE WEATHER PROOF

SUBSCRIPTS TR = TAMPER RESISTANT

TV = TELEVISION, MOUNT AT 60" ABOVE

FINISHED FLOOR

AFCI = ARC FAULT CIRCUIT INTERRUPTER

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR.

WALL SWITCH, AC TYPE, SPST, MOUNT 48"

ABOVE FINISHED FLOOR

WALL SWITCH, AC TYPE, DPDT, MOUNT 48"

ABOVE FINISHED FLOOR

3-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

ELECTRICAL LEGEND

D

M

LV

OS

DS

PE

5-30R

EWC

LIGHTNING PROTECTION

3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG

GROUND ROD TEST WELL

BARE COPPER GROUND CONDUCTOR, 1/0 UNLESS

INDICATED OTHERWISE.

4/0 BARE COPPER GROUND CONDUCTOR

LIGHTNING PROTECTION SYSTEM AIR TERMINAL

LIGHTNING PROTECTION ROOF CONDUCTOR

ELECTRICAL CONNECTION

SCHEMATIC

PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)

CONTROL RELAY COIL

SHUNT TRIP COIL

TIME DELAY RELAY COIL

MOTOR STARTER COIL

S W

S

S

S

S

S

S

S

VS

DE

F

G

H

P

J

V S

O S

G

G4

LP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :0

P

M

ES-002

ELECTRICAL LEGEND

MAY 14, 2021 WSP TED

BID DOCUMENTS

NOTE:

1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

SSS

S

S

PC

F A

T C

S M

S M

S M

S M

S M

S M

S M

1 2

B

A

EXISTING-TO-REMAIN

LIGHTING PANEL WITH

CONTACTOR PANEL ABOVE

EXISTING-TO-REMAIN

PHOTOCELL

EXISTING-TO-REMAIN

EXTERIOR LIGHTING MANUAL

OVERRIDE SWITCH

EMERGENCY

GENERATOR

ELECTRICAL

D D

D D

D D

D D

D D

D D D D

D D

D

D D

D D

D D

D D

D

D

D

D

D

1 2

B

A

+48"

+48"

+48"

+48"

W P

+48"

+48"

EXISTING-TO-BE-

RELOCATED

DISCONNECT SWITCH

FOR EXH-116-1

EXISTING-TO-BE-

RELOCATED

COMBINATION STARTER &

DISCONNECT SWITCH FOR

UNIT HEATER-116-2

EXISTING-TO-BE-

RELOCATED METERING

SYSTEM

EXISTING-TO-REMAIN

FIRE ALARM PANELS

EXISTING-TO-REMAIN

LIGHTING PANEL WITH

CONTACTOR PANEL ABOVE

EXISTING-TO-REMAIN

'AUTOMATIC TRANSFER

SWITCHBOARD'

EXISTING-TO-REMAIN

PANEL 'GBEP'

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

MOTORIZED DAMPERS

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

EUH-11

EXISTING-TO-BE-

DEMOLISHED DAY TANK

AND FUEL PUMPING

SYSTEM

EXISTING-TO-BE-

DEMOLISHED REMOTE

RADIATOR

EXISTING-TO-BE-

DEMOLISHED DISCONNECT

FOR REMOTE RADIATOR

EXISTING-TO-BE-

DEMOLISHED ENGINE

GENERATOR SET

EXISTING-TO-BE-

DEMOLISHED BATTERY

CHARGER

EXISTING-TO-BE-

DEMOLISHED GENERATOR

CONTROL PANEL

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

MOTORIZED DAMPERS

EXISTING-TO-REMAIN

PANEL 'DPELS'

EXISTING-TO-REMAIN

PANEL 'DPEC'

EXISTING-TO-REMAIN

PANEL 'DPEE'

ELECTRICAL

EMERGENCY

GENERATOR

N O

R M

A L

M

IN

D

IS

T

A

T S

A T

S A

T S

D

IS

T

E M

E R

M

A

IN

E

E

E

E

E

R

E

E

E

E

EXISTING-TO-BE-

DEMOLISHED

EMERGENCY POWER

OFF SWITCH.

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

MOTORIZED DAMPERS

EXISTING-TO-BE-RELOCATED

RECEPTACLE. SEE SHEET

ES-101 FOR NEW LOCATION.

5R R

PHOTO KEY LEGEND

DIRECTION PHOTO WAS TAKEN

NOTES PHOTO LOCATION

PHOTO DETAIL NUMBER

REFERENCE SHEET ES-501 FOR PHOTOS

B1

B3

B5

D5

D3

D1

A1

T R

U E

N

PLAN

NORTH

KEY PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :1

P

M

ESD101

ELECTRICAL DEMOLITION PLANS

MAY 14, 2021 WSP TED

BID DOCUMENTS

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS

& LEGEND.

2. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND, UNLESS EXPLICITLY

DIMENSIONED, INDICATE APPROPRIATE LOCATIONS OF FIXTURES, APPARATUS,

EQUIPMENT AND RACEWAYS. CHANGES IN THE LOCATION, AND OFFSETS, OF

WORK OF OTHER TRADES, SHALL BE MADE DURING THE PREPERATION OF

COORDINATION DRAWINGS AND PRIOR TO INITIAL INSTALLATION, WITHOUT

ADDITIONAL COST.

3. ASSUME EQUIPMENT FOR DEMOLITION HAS LEAD-CONTAINING AND ASBESTOS-

CONTAINING MATERIALS WHICH SHALL BE HANDLED IN ACCORDANCE WITH

STATE AND FEDERAL REGULATIONS, AND THE SPECIFICATIONS CONTAINED

HEREIN. THE RECENT SURVEY PERFORMED CAN BE REQUESTED FROM THE

CONTRACTING OFFICER'S REPRESENTATIVE FOR USE AS "FOR INFORMATION

ONLY."

4. LOCATIONS OF MOTORS, STARTERS, EQUIPMENT AND APPARATUS AS

INDICATED ON THE DRAWINGS ARE APPROXIMATE; CONNECTIONS SHALL BE

MADE TO SUCH EQUIPMENT AS ACTUALLY INSTALLED.

5. PROVIDE ACCESS TO EQUIPMENT AND APPARATUS REQUIRING OPERATION,

SERVICE OR MAINTENANCE THROUGHOUT THE LIFE OF THE SYSTEM.

6. SWITCHBOARDS, PANELBOARDS, VARIABLE FREQUENCY DRIVES,

TRANSFORMERS, AND STARTERS SHALL BE INSTALLED SUCH THAT THE

WORKING SPACE IN FRONT, REAR AND/OR SIDE (WHERE REAR AND/OR SIDE

ACCESS IS REQUIRED TO WORK ON EQUIPMENT) IS CLEAR OF PIPING,

DUCTWORK, OR MECHANICAL EQUIPMENT. DIMENSIONS OF THE WORKING

SPACE SHALL BE A MINIMUM DEPTH OF 36" HORIZONTALLY, THE WIDTH OF THE

EQUIPMENT OR 30", WHICHEVER IS GREATER, AND THE HEIGHT OF THE

EQUIPMENT OR 78", WHICHEVER IS GREATER.

7. SCHEDULE AND PHASE WORK, AND PROVIDE TEMPORARY SERVICE AND

CONNECTIONS, AS INDICATED IN SECTION 01 00 00 GENERAL REQUIREMENTS.

8. THE EXISTING INSTALLATION SHALL REMAIN AS IS EXCEPT AS OTHERWISE

INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. PERFORM WORK TO TIE

IN THE NEW WORK WITH THE EXISTING WORK AND TO ADAPT THE EXISTING

WORK TO THE CHANGES IN THE BUILDING AND SYSTEMS.

9. REMOVE EQUIPMENT, APPARATUS, AND EXPOSED WIRING AND RACEWAYS

RENDERED USELESS DUE TO CHANGES.

10.REMOVE ALL LUMINAIRES AND EXIT SIGNS.

11.EXISTING-TO-BE-REMOVED BATTERY UNITS SHALL BE TURNED OVER TO THE

CONTRACTING OFFICER'S REPRESENTATIVE. ALL OTHER ITEMS THAT ARE

EXISTING-TO-BE-REMOVED SHALL BECOME THE PROPERTY OF THE

CONTRACTOR AND BE REMOVED FROM THE SITE AND DISPOSED OF IN

ACCORDANCE WITH STATE AND FEDERAL REGULATIONS.

12.MATERIAL AND EQUIPMENT WHICH HAS BEEN REMOVED AND NOT ACCEPTED

BY THE CONTRACTING OFFICER'S REPRESENTATIVE SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE.

13.EXISTING ELECTRICAL EQUIPMENT, INCLUDING LAMPS AND BALLASTS,

REMOVED AND NOT REUSED SHALL BE HANDLED AND DISPOSED OF IN

ACCORDANCE WITH APPLICABLE STATE AND FEDERAL REGULATIONS.

14.MATERIAL AND EQUIPMENT WHICH HAS BEEN REMOVED SHALL NOT BE USED

IN THE NEW WORK, EXCEPT AS SPECIFIED HEREIN.

15.WHERE EXISTING RACEWAYS AND EQUIPMENT ARE INDICATED ON THE

DRAWINGS, SIZE AND LOCATION SHALL BE VERIFIED PRIOR TO BIDDING.

16.PROVIDE CIRCUIT CONTINUITY FOR EXISTING WIRING DEVICES AND

EQUIPMENT OUTSIDE THE RENOVATION AREA SERVED FROM OR THROUGH

THE RENOVATION AREA.

17.REMOVE THE EXISTING EMERGENCY POWER SUPPLY AND INSTALL A NEW

EMERGENCY POWER SUPPLY AS SPECIFIED HEREIN AND AS INDICATED ON

THE DRAWINGS.

18.SLEEVES LEFT OPEN BY REMOVAL OF CONDUIT OR RACEWAYS SHALL BE CUT

FLUSH WITH THE FINISHED SLAB, AND FILLED WITH GROUT FLUSH WITH SLAB.

19.CONCEALED RACEWAYS IN MASONRY WALLS RENDERED USELESS BY

REVISIONS SHALL BE CUT FLUSH WITH WALL SURFACE AND SEALED WITH

GROUT.

20.WHERE EXISTING MECHANICAL EQUIPMENT IS REMOVED, REMOVE ELECTRICAL

WIRING, RACEWAYS, SWITCHES AND STARTERS ASSOCIATED WITH THE

EQUIPMENT.

21.WHERE EXISTING MECHANICAL EQUIPMENT IS MODIFIED OR RELOCATED,

MODIFY THE ELECTRICAL CONNECTIONS TO THE EQUIPMENT TO ADAPT IT TO

ITS NEW FUNCTION OR LOCATION.

KEYNOTES:

1. DEMOLISH ALL EXISTING LUMINAIRES IN THIS SPACE. EXISTING

BRANCH CIRCUIT AND SWITCH WIRING SHALL REMAIN.

RECONNECT NEW LUMINAIRES TO EXISTING BRANCH CIRCUIT

WIRING.

2. DEMOLISH LUMINAIRE AND BRANCH CIRCUIT WIRING BACK TO

THE SOURCE. REMOVE ANY RECEPTACLES USED FOR PLUG-

AND-CORD CONNECTED LUMINAIRES.

3. DEMOLISH EXISTING EXTERIOR LUMINAIRE. EXISTING BRANCH

CIRCUIT SWITCH WIRING SHALL REMAIN. RECONNECT NEW

LUMINAIRE(S) TO EXISTING OUTLET BOX AND BRANCH CIRCUIT

WIRING.

4. DEMOLISH EXISTING EXIT SIGN. EXISTING BRANCH CIRCUIT

WIRING SHALL REMAIN. RECONNECT NEW EXIT SIGN(S) TO

EXISTING OUTLET BOX AND BRANCH CIRCUIT WIRING.

5. EXISTING VEEDER ROOT TLS-300 TANK GAUGE AND LEAK

DETECTION UNIT IS EXISTING-TO-REMAIN. PROTECT SYSTEM

DURING CONSTRUCTION AND DEMONSTRATE OPERATION

UPON SUBSTANTIAL COMPLETION OF THE PROJECT.

SCALE: 1/4" = 1'-0"F1

DEMOLITION LIGHTING PLAN

SCALE: 1/4" = 1'-0"F5

DEMOLITION POWER PLAN

SCALE: = 1'-0"

0 4 84

1/4"

RISER DIAGRAM LEGEND

INDIVIDUALLY

MOUNTED CIRCUIT

BREAKER; TRIP AND

POLE SIZE AS

INDICATED.

PANELBOARD; MAIN

CIRCUIT BREAKER,

CIRCUIT BREAKERS AS

SCHEDULED.

INDIVIDUALLY

MOUNTED MOTOR

STARTER OR VARIABLE

FREQUENCY DRIVE;

NEMA SIZE AS

INDICATED.

AUTOMATIC TRANSFER

SWITCH; SIZE AS

INDICATED.

TRANSFORMER; SEE

TRANSFORMER

SCHEDULE, PRIMARY &

SECONDARY FEEDER

SIZE, AND GROUNDING

ELECTRODE

INFORMATION.

FUSED DISCONNECT;

FRAME, POLE, AND

FUSE SIZE AS

INDICATED.

NOTE: NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

PANELBOARD; MAIN

LUGS ONLY, CIRCUIT

BREAKERS AS

SCHEDULED.

MOTOR, HORSEPOWER

AS INDICATED.

FEEDER; CONDUIT AND

WIRE SIZE AS

INDICATED BY FEEDER

MARK.

NON-FUSED

DISCONNECT; FRAME

AND POLE SIZE AS

INDICATED.

SITELEVEL 1EMERGENCY

ELECTRICAL

ROOM

EXTERIOR

XFMR

'XAD'

DEMO

A

/3 P

V F

D

A

/3 P

/4 A

DEMO

A

/3 P

EXISTING

TO-BE-DEMOLISHED

REMOTE RADIATOR

EXISTING

TO-BE-DEMOLISHED

SKID-MOUNTED ENGINE

GENERATOR SET

EXISTING

XFMR

'XAD'

A

/3 P

V F

D

A

/3 P

/4 A

EXISTING

A

/3 P

EXISTING SERVICE

TRANSFORMER

208Y/120 V

3 PH, 4W

EXISTING

PANEL

'DPEE'

EXISTING

PANEL

'DPELS'

EXISTING

PANEL

'DPEC'

EXISTING

PANEL

'GBEP'

EXISTING SITE

LIGHTING

PANEL

EXISTING

FEEDER TO

BLDG 69

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

2,500AT

2,500AF

2,500AT

2,500AF

225A/3P 400A/3P

EXISTING-TO-REMAIN

'ATS' SWITCHBOARD

EXISTING

FEEDER TO

BLDG 116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :1

P

M

ESD601

ELECTRICAL DEMOLITION RISER DIAGRAM

MAY 14, 2021 WSP TED

BID DOCUMENTS

SCALE: NOT TO SCALEF1

DEMOLITION RISER DIAGRAM

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS

& LEGEND.

SSS

S

S

PC

F A

T C

S M

S M

S M

S M

S M

J

J S M

J

1 2

B

A

EXISTING-TO-REMAIN

LIGHTING PANEL WITH

CONTACTOR PANEL ABOVE

EXISTING-TO-REMAIN

PHOTOCELL

EXISTING-TO-REMAIN

EXTERIOR LIGHTING MANUAL

OVERRIDE SWITCH

F

FE

F

FE

F

FE

F

FE

F

FE

F

F

FE

F

FE FE

F

FE

F

FEFFE

X

OO

EMERGENCY

GENERATOR

ELECTRICAL

O

O

1 1

X

1 2

B

A

RELOCATED DISCONNECT

SWITCH FOR EXH-116-1

RELOCATED METERING

SYSTEM

EXISTING-TO-REMAIN

FIRE ALARM PANEL

EXISTING-TO-REMAIN LIGHTING

PANEL WITH CONTACTOR PANEL

ABOVE

EXISTING-TO-REMAIN 'AUTOMATIC

TRANSFER SWITCHBOARD'

EXISTING-TO-REMAIN

PANEL 'GBEP'

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

EUH-11

EXISTING-TO-REMAIN

PANEL 'DPELS'

EXISTING-TO-REMAIN

PANEL 'DPEC'

EXISTING-TO-REMAIN

PANEL 'DPEE'

+48"

+48"

+48"

+48"

W P

+48"

ELECTRICAL

EMERGENCY

GENERATOR

N O

R M

L

M

IN

D

IS

T

A

T S

A T

S A

T S

D

IS

T

E M

E R

M

A

IN

E

E

E

E

E

E

E

NEW EMERGENCY

POWER OFF SWITCH FOR

ENGINE GENERATOR

SET. PROVIDE CLASS 2

WIRING TO GENERATOR

CONTROLLER AS

REQUIRED BY THE

MANUFACTURER.

E

NEW ENGINE

GENERATOR SET

E

R +48"

RELOCATED

DISCONNECT

SWITCH FOR

EXH-116-2

RELOCATED

DUPLEX

OUTLET

NEW GENERATOR QUICK

CONNECT TAP BOX MOUNTED

ON A UNISTRUT FRAME. SEE

DETAIL F5/ES-501.

NEW 750 kVA DRY-TYPE

TRANSFORMER IN

NEMA 3R ENCLOSURE

NEW MANUAL TRANSFER

SWITCHBOARD

(TYPICAL)

10' - 0"

NEW

GROUND

RING

PROVIDE NEW GROUNDING

CONNECTIONS AS INDICATED ON

SHEET ES-602

NEW GROUNDING BAR

SEE DETAIL C7/ES-501 FOR

PENETRATION

EXISTING GROUNDING ELECTRODE.

TRIM AND RECONNECT AS

INDICATED ON SHEET ES-602

FROM

XFMR

LUGS

OUT

FROM

GEN

SET

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

MOTORIZED DAMPERS -

CONNECT NEW DAMPERS TO

EXISTING DISCONNECT.

EXISTING-TO-REMAIN

DISCONNECT SWITCH FOR

MOTORIZED DAMPERS -

CONNECT NEW DAMPERS

TO EXISTING DISCONNECT.

PROVIDE PROTECTIVE

BOLLARDS AS INDICATED IN

DETAIL F1/ES-501. TYPICAL

OF 3.

NEW DAY-TANK

WP

WP GBEP-37

GBEP-10

GBEP-11,13

R

RELOCATED COMBINATION

STARTER & DISCONNECT

SWITCH FOR UNIT HEATER

116-2

R

GBEP-39

SEE DETAIL E4/S-301 FOR

EXTERIOR EQUIPMENT PAD

DETAIL CONSTRUCTION. SEE

SHEET F7/CS101 FOR

DIMENSIONED LOCATION OF

EQUIPMENT PAD.

T R

U E

N

PLAN

NORTH

KEY PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :0

P

M

ES-101

ELECTRICAL FLOOR PLANS

MAY 14, 2021 WSP TED

BID DOCUMENTS

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS &

LEGEND.

2. REFER TO ES-611 FOR LUMINAIRE SCHEDULE.

3. REFER TO SHEET ES-611 FOR MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO SHEET CS101 FOR EXACT LOCATION OF EXTERIOR EQUIPMENT.

KEYNOTES:

1. CONNECT NEW LUMINAIRES TO BRANCH CIRCUIT WIRING AND CONTROLS OF

EXISTING LUMINAIRES IN THIS SPACE.

2. PROVIDE 120V CONNECTION FOR BATTERY CHARGER.

3. PROVIDE 208V CONNECTION FOR 9kW BLOCK HEATER. BRANCH CIRCUIT

WIRING SHALL BE 2 #4, 1 #10 G., 1" C.

4. PROVIDE 120V CONNECTION FOR DAY TANK.

5. PROVIDE 120V CONNECTION FOR SPACE HEATER.

6. CONNECT NEW EXIT SIGN AHEAD OF LOCAL SWITCHING. PROVIDE AN

ADDITIONAL PHASE CONDUCTOR IN BRANCH CIRCUIT WIRING AS REQUIRED.

SCALE: 1/4" = 1'-0"F1

LIGHTING PLAN

SCALE: 1/4" = 1'-0"F5

POWER PLAN

SCALE: = 1'-0"

0 4 84

1/4"

LENGTH AS REQUIRED

APPROXIMATELY 14"

M

IN

IM

U

M

WIDTH OF QUICK

CONNECT TAP BOX

2'-0"

2'-0"4'-0"

3'-0"

EMBEDMENT

2' DIAMETER MINIMUM

6"

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 36" SHALL BE INSTALLED WITH A CENTER SUPPORT

ROD. SUPPORT RODS SHALL NOT BE GREATER THAN 18" APART.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES FOR

ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

CONDUIT CLAMP. SIZE AS

REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

LOCKING SQUARE WASHER

& LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

WASHER & LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

LOCKING

SQUARE WASHER

& LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

F7 CONDUIT TRAPEZE MOUNTING DETAIL

SCALE: NOT TO SCALE

BRACES

12 GAUGE 1.5"

SQUARE

GALVANIZED STEEL

CHANNEL

STANCHION AND

BRACES

0.25" x 1.5" WELDED

GALVANIZED STEEL

CORNER BRACE

WELD ALL AROUND

F5 EQUIPMENT MOUNTING DETAIL

SCALE: NOT TO SCALE

F1 BOLLARD DETAIL

SCALE: NOT TO SCALE

TRANSFORMER/SWITCHGEAR PLAN VIEW

ROUNDED CONCRETE CAP,

FORMED IN FIELD

CONCRETE FILLED 6"

DIAMETER GALVANIZED

STEEL PIPE PAINTED

SAFETY YELLOW

CONCRETE FOOTING

FINISHED GRADE

FINISHED GRADE

FINISHED FLOOR

1" METAL CONDUIT

SEAL WALL PENETRATION

CONDUIT BODY

BUILDING WALL

1" GRC

BOND EACH END OF

CONDUIT TO

GROUND CABLE

GROUND ROD

CONDUIT

GROUNDING

BUSHING

4/0 BARE COPPER

2' MIN.

6' MAX.

M

IN

M A

X

TO EXISTING GROUNDING

ELECTRODE

EXOTHERMIC WELD

GROUND BAR

#4/0 BARE COPPER CONDUCTOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :0

P

M

ES-501

ELECTRICAL DETAILS

MAY 14, 2021 WSP TED

BID DOCUMENTS

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

SCALE: NOT TO SCALEC7

GROUNDING ELECTRODE CONNECTION DETAIL

SCALE: NOT TO SCALEB1

EXTERIOR VIEW

SCALE: NOT TO SCALEB3

EXISTING METERING ASSEMBLY

SCALE: NOT TO SCALEB5

SPACE BEHIND SWITCHBOARD

SCALE: NOT TO SCALED5

EXISTING GROUNDING ELECTRODE

SCALE: NOT TO SCALED1

EXISTING VEEDER-ROOT SYSTEM

SCALE: NOT TO SCALED3

EXISTING UNIT HEATER

RISER DIAGRAM LEGEND

INDIVIDUALLY

MOUNTED CIRCUIT

BREAKER; TRIP AND

POLE SIZE AS

INDICATED.

PANELBOARD; MAIN

CIRCUIT BREAKER,

CIRCUIT BREAKERS AS

SCHEDULED.

INDIVIDUALLY

MOUNTED MOTOR

STARTER OR VARIABLE

FREQUENCY DRIVE;

NEMA SIZE AS

INDICATED.

TRANSFER SWITCH;

SIZE AS INDICATED.

TRANSFORMER; SEE

TRANSFORMER

SCHEDULE, PRIMARY &

SECONDARY FEEDER

SIZE, AND GROUNDING

ELECTRODE

INFORMATION.

FUSED DISCONNECT;

FRAME, POLE, AND

FUSE SIZE AS

INDICATED.

NOTE: NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

PANELBOARD; MAIN

LUGS ONLY, CIRCUIT

BREAKERS AS

SCHEDULED.

MOTOR, HORSEPOWER

AS INDICATED.

FEEDER; CONDUIT AND

WIRE SIZE AS

INDICATED BY FEEDER

MARK.

NON-FUSED

DISCONNECT; FRAME

AND POLE SIZE AS

INDICATED.

SITELEVEL 1EMERGENCY

ELECTRICAL

ROOM

EXTERIOR

EXISTING

XFMR

'XAD'

A

/3 P

V F

D

A

/3 P

/4 A

EXISTING

A

/3 P

EXISTING SERVICE

TRANSFORMER

208Y/120 V

3 PH, 4W

EXISTING

PANEL

'DPEE'

EXISTING

PANEL

'DPELS'

EXISTING

PANEL

'DPEC'

EXISTING

PANEL

'GBEP'

EXISTING SITE

LIGHTING

PANEL

EXISTING

FEEDER TO

BLDG 69

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

800AT

800AF

2,500AT

2,500AF

2,500AT

2,500AF

225A/3P 400A/3P

EXISTING-TO-REMAIN

'ATS' SWITCHBOARD

EXISTING

FEEDER TO

BLDG 116

75 75

FUTURE

XFMR

'XAD'

A

/3 P

V F

D

A

/3 P

/4 A

FUTURE

A

/3 P

NEW

XFMR

'XAD'

A

/3 P

V F

D

A

/3 P

/4 A

NEW

A

/3 P

T750P

480:208 750kVA

XFMR

NEW 750kW

208/120VSKID-MOUNTED

ENGINE GENERATOR SET

,0

A

L U

G S

,0

A

/3 P

TO

LOAD

BANK

SPD SPD

1,200A, 480V

GENERATOR

QUICK-CONNECT TAP

BOX - NEMA 3R

ENCLOSURE, PAD

MOUNTED OR

MOUNTED ON A

UNISTRUT FRAME.

NEW 3,000A

MANUAL

TRANSFER

SWITCHBOARD

3,000AT

3,000AF

K

3,000AT

3,000AF

K

3000T750S

,0

A

M L O

EXTERIOR PAD - SEE

DETAIL E4/S-301.

GENERATOR PAD -

SEE DETAIL C1 &

E1/S-301.

INTERIOR

HOUSEKEEPING PAD

- SEE DETAIL

D4/S-301.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :0

P

M

ES-601

ELECTRICAL RISER DIAGRAM & SCHEDULES

MAY 14, 2021 WSP TED

BID DOCUMENTS

SCALE: NOT TO SCALEF1

ELECTRICAL RISER DIAGRAM

FEEDER SCHEDULE

FEEDER TAG COPPER FEEDER

20 4#12 & 1#12G, 1/2"C.

25 4#10 & 1#10G, 3/4"C.

30 4#10 & 1#10G, 3/4"C.

35 4#8 & 1#10G, 1"C.

40 4#8 & 1#10G, 1"C.

45 4#6 & 1#10G, 1"C.

50 4#6 & 1#10G, 1"C.

60 4#4 & 1#10G, 1-1/4"C.

70 4#4 & 1#8G, 1-1/4"C.

80 4#2 & 1#8G, 1-1/2"C.

90 4#2 & 1#8G, 1-1/2"C.

100 4#1 & 1#8G, 2"C.

110 4#1 & 1#6G, 2"C.

125 4#1 & 1#6G, 2"C.

150 4-1/0 & 1#6G, 2"C.

175 4-2/0 & 1#6G, 2"C.

200 4-3/0 & 1#6G, 2-1/2"C.

225 4-4/0 & 1#4G, 2-1/2"C.

250 4-250 KCMIL & 1#4G, 3"C.

300 4-350 KCMIL & 1#4G, 3"C.

350 4-500 KCMIL & 1#2G, 4"C.

400 4-500 KCMIL & 1#2G, 4"C.

450 TWO 2-1/2-INCH CONDUITS, EACH

WITH FOUR 4/0 AND ONE #2G

500 TWO 3-INCH CONDUITS, EACH WITH

FOUR 250 KCMIL AND ONE #2G

600 TWO 3-INCH CONDUITS, EACH WITH

FOUR 350 KCMIL AND ONE #1G

700 TWO 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 1/0G

800 TWO 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 1/0G

1000 THREE 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 2/0G

1200 FOUR 3-INCH CONDUITS, EACH WITH

FOUR 350 KCMIL AND ONE 3/0G

1600 FIVE 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 4/0G

2000 SIX 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 250KCMIL G

2500 SEVEN 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 350KCMIL G

3000 NINE 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 350KCMIL G

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

TRANSFORMER FEEDER SCHEDULE

FEEDER

TAG PRIMARY FEEDER

FEEDER

TAG SECONDARY FEEDER

GROUNDING

ELECTRODE

CONDUCTOR

T15P 3#10 & 1#10G, 1/2"C. T15S 4#6 & 1#10G, 1"C. #8G

T30P 3#6 & 1#10G, 3/4"C. T30S 4#1 & 1#8G, 1-1/2"C. #6G

T45P 3#4 & 1#8G, 1"C. T45S 4-1/0 & 1#6G, 2"C. #6G

T75P 3#1 & 1#6G, 1-1/2"C. T75S 4-250 KCMIL & 1#4G, 2-1/2"C. #2G

T112.5P 3-2/0 & 1#6G, 2"C. T112.5S 4-500 KCMIL & 1#2G, 3"C. 1/0G

T150P 3-4/0 & 1#4G, 2"C. T150S TWO 2-1/2-INCH CONDUITS, EACH

WITH FOUR 250 KCMIL AND ONE #2G

1/0G

T225P 3-500 KCMIL & 1#2G, 3"C. T225S TWO 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 1/0G

2/0G

T300P TWO 2-INCH CONDUITS, EACH WITH

THREE 4/0 AND ONE #2G

T300S THREE 3-1/2-INCH CONDUITS, EACH

WITH FOUR 500 KCMIL AND ONE 2/0G

4/0G

T500P TWO 3-INCH CONDUITS, EACH WITH

THREE 500 KCMIL AND ONE 1/0G

T500S FIVE 3-1/2-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 250 KCMIL G

350 KCMIL G

T750P FOUR 3-INCH CONDUITS, EACH

WITH THREE 350 KCMIL AND ONE

3/0G

T750S EIGHT 3-1/2-INCH CONDUITS, EACH

WITH FOUR 500 KCMIL AND ONE 3/0 G

350 KCMIL G

KEYNOTES:

1. PROVIDE KEY INTERLOCK BETWEEN GENERATOR (PRIMARY) SOURCE AND

GENERATOR QUICK CONNECTION (ALTERNATE SOURCE) TO PREVENT

INADVERTENT CONNECTION OF BOTH SOURCES TO THE TRANSFER

SWITCH. PROVIDE KEY LOCKS FOR EACH DISCONNECT WITH ONLY ONE

KEY. INSERT KEY INTO THE PRIMARY SOURCE LOCK TO ALLOW IT TO BE

CLOSED AND THE GENERATOR TO FEED THE AUTOMATIC TRANSFER

SWITCH. THE KEY SHALL BECOME CAPTIVE WHILE THIS SWITCH IS CLOSED

AND CAN ONLY BE RELEASED BY OPENING THE SWITCH. IN ORDER TO

CONNECT THE TEMPORARY GENERATOR, THE KEY SHALL BE REMOVED

FROM THE PRIMARY SWITCH. THE KEY SHALL THEN BE INSERTED INTO

THE LOCK OF THE ALTERNATE SOURCE DISCONNECT SWITCH. THE KEY

SHALL REMAIN CAPTIVE WHILE ALTERNATE SOURCE DISCONNECT SWITCH

IS CLOSED.

SCALE: NOT TO SCALE SCALE: NOT TO SCALE

MIN. 20'

MIN 2"

2"

4"

1" 1" 1"2"

1 1/2" TYP

1" 5/8"

2'-0" MIN

N

NEW MAIN ELECTRICAL

ROOM GROUND BAR. SEE

DETAIL B4/ES-602.

EXISTING SYSTEM BONDING

JUMPER

EXISTING SWITCHBOARD

'ATS' GROUND BUS

REMOVABLE LINK

MAIN BONDING JUMPER

EXISTING SWITCHBOARD

'ATS' NEUTRAL BUS

EXISTING SWITCHBOARD

'ATS'CONTINUOUS GROUNDING

ELECTRODE CONDUCTOR; 1

#4/0 IN 1" METAL CONDUIT.

UNSPLICED GROUNDING

ELECTRODE CONDUCTOR

SHALL TERMINATE AT

GROUND RING.

EQUIPMENT BONDING

JUMPER (TYPICAL)

EXOTHERMIC WELD

(TYPICAL)

MAIN ELECTRICAL ROOM

GROUND RING (SEE SHEET

ES-101 FOR LOCATION)

GROUND RING; NOT LESS

THAN #2 AWG BARE

COPPER (TYPICAL)

GROUND ROD (TYPICAL)

E X

P O

S E

D I N

T E

R

IO

R S

T R

U C

T U

R A

L S

T E

E L

EXISTING SERVICE

TRANSFORMER

EXISTING GROUNDED

SERVICE CONDUCTOR.

GROUNDING ELECTRODE

CONDUCTOR (SUPPLY SIDE

BONDING JUMPER); 1 #4/0 IN

1" METAL CONDUIT

NEW GENERATOR

METAL CONDUITS

NOT

ELECTRICALLY

CONTINUOUS

SHALL HAVE

JUMPER (TYPICAL)

FOUNDATION IN DIRECT

CONTACT WITH EARTH

#4 AWG OR LARGER

BARE COPPER

CONDUCTOR OR STEEL

REINFORCING BAR OR

ROD NOT LESS THAN 1/2"

DIAMETER

EXOTHERMIC WELD

EXISTING GROUNDING

ELECTRODE

CONCRETE-ENCASED GROUNDING ELECTRODE

(UFER GROUND)

PROVIDE A CONCRETE ENCASED GROUNDING

ELECTRODE AND SUPPLEMENTAL ELECTRODES IN

ACCORDANCE WITH NFPA 70 ARTICLE 250.52(3) TO

PROVIDE A GROUNDING RESISTANCE OF 25 OHMS OR

LESS. ALL GROUND CONNECTIONS TO CONCRETE

ENCASED ELECTRODE SHALL REMAIN ACCESSIBLE.

1 #6 IN METAL CONDUIT

EXISTING

FIRE ALARM

CONTROL

PANEL

BONDING JUMPER; 1 #4/0 IN

1" METAL CONDUIT

GROUND ROD

EXOTHERMIC WELD

GROUNDING ELECTRODE

CONDUCTOR; 1 #4/0 IN 1"

METAL CONDUIT. (TYPICAL)

GROUND RING

PROVIDE A GROUND RING TO PROVIDE A GROUNDING

RESISTANCE OF 25 OHMS OR LESS IN ACCORDANCE

WITH NFPA 70 ARTICLE 250.52(4). ALL GROUND

CONNECTIONS TO GROUND RINGS SHALL REMAIN

ACCESSIBLE. GROUND RODS SHALL BE NO LESS THAN 6'

APART AND NO LESS THAN 30" BELOW GRADE. PROVIDE

TEST WELLS WHERE INDICATED ON THE DRAWINGS.

WATER PIPE GROUNDING ELECTRODE

PROVIDE A GROUNDING ELECTRODE

CONNECTION IN ACCORDANCE WITH NFPA 70

ARTICLE 250.52(1) TO A METAL

UNDERGROUND WATER PIPE. CONNECTION

SHALL BE MADE WITH A GROUND CLAMP

WITHIN 5' OF WATER PIPE ENTRANCE INTO

BUILDING AND AHEAD OF ANY VALVE,

CONNECTOR, OR METERING DEVICE. TO

MAINTAIN 10' OF ELECTRICAL CONTINUITY OF

UNDERGROUND WATER PIPE ELECTRODE,

PROVIDE BONDING JUMPERS AROUND

INSULATED JOINTS, FILTERING DEVICE AND

METERING EQUIPMENT. SIZE BONDING

JUMPER IN ACCORDANCE WITH NFPA 70

TABLE 250.12(C)(1).

METAL SUPPORT STRUCTURE GROUNDING ELECTRODE

PROVIDE A GROUNDING ELECTRODE CONNECTION TO

EXPOSED STRUCTURAL STEEL IN ACCORDANCE WITH

NFPA 70 ARTICLE 250.52(2). SIZE BONDING JUMPER IN

ACCORDANCE WITH NFPA 70 TABLE 250.102(C)(1).

EXOTHERMIC WELD TO

GROUND ROD (TYPICAL)

GROUNDING ELECTRODE

CONDUCTOR; 1 #4/0 IN 1"

METAL CONDUIT

B1

DRY-TYPE TRANSFORMER GROUNDING DETAIL

1/4" DIAMETER

MOUNTING HOLES

(TYPICAL OF 4)

BASE CLAMP/

BRACKET

3/8" DIAMETER HOLE

(TYPICAL OF 6)

3/8" x 5/8" HEX

HEAD BOLT

3/8" LOCK WASHER & 3/8"

FLAT WASHER

3/8" FLAT WASHER &

3/8" LOCK WASHER

1/4" THICK

COPPER BAR

1/4" DIAMETER HOLE

(TYPICAL OF 8)

GENERAL NOTES:

1. ALL HARDWARE SHALL BE STAINLESS

STEEL.

2. PROVIDE 1 MOUNTING POINT PER 12" OF

BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

SECTION

STEEL EXPANSION

ANCHOR

INSULATOR

1/4" THICK COPPER BAR

3/8" x 5/8" HEX

HEAD BOLT

B4

GROUND BAR DETAIL

PROVIDE GROUNDING

ELECTRODE CONDUCTOR

TO GENERATOR QUICK

CONNECT TAP BOX; 1 #4/0

IN 1" NONMETALLIC

CONDUIT

FLOOR LEVEL

4 WIRES

H2 X3 H1

5 WIRES

X0 X2 H3 X1

TYPICAL PANELBOARD

A B C

A B C

MAIN

BREAKER

NOTES

1. TRANSFORMER BONDING STRAP, IF NOT PROVIDED BY

THE TRANSFORMER MANUFACTURER, SHALL BE THE

SAME SIZE AS THE SYSTEM BONDING JUMPER IN

ACCORDANCE WITH NFPA 70, TABLE 250.102(C)(1).

2. PROVIDE A BONDING BUSHING AND EQUIPMENT BONDING

JUMPER AT THE CONDUIT TERMINATION. JUMPER SHALL

BE THE SAME SIZE AS THE GROUNDING ELECTRODE

CONDUCTOR CONTAINED IN THE CONDUIT.

3. PROVIDE A BONDING CLAMP AT THE TERMINATION OF

THE GROUNDING ELECTRODE CONDUCTOR TO THE

ELECTRODE.

BOND GROUNDING ELECTRODE TO THE

NEAREST ELECTRICAL RISER GROUND BAR,

THE STEEL FRAME OF THE BUILDING WHERE

PROVEN TO BE SUITABLY GROUNDED OR TO

THE METALLIC WATER PIPE WITHIN 5' FROM

THE POINT OF ENTRANCE INTO THE

BUILDING (NFPA 70 ARTICLE 250-30(A)).

TRANSFORMER

WINDING

FROM

TRANSFORMER

PRIMARY

SOURCE

GROUND BUS

GROUND BUS

BONDED TO

ENCLOSURE

BONDING BUSHING

WITH BONDING

JUMPER

NEUTRAL BUS

INSULATED FROM

PANEL

NEUTRAL (WHITE)

CONCRETE

HOUSEKEEPING PAD

GROUND PAD

SYSTEM BONDING

JUMPER

EQUIPMENT

BONDING JUMPER

BOND EXHAUST FLUE TO

LIGHTNING PROTECTION

ROOF CONDUCTOR WITH UL

LISTED PIPE BONDING CLAMP

EXISTING CLASS I ROOF

LIGHTNING PROTECTION

CONDUCTOR

NEW EXHAUST FLUE -

SPECIFIED IN DIVISION 23

CLASS I BONDING

CONDUCTOR - SIZED IN

ACCORDANCE WITH

NFPA-780, 2020 EDITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :1

P

M

ES-602

ELECTRICAL GROUNDING RISER DIAGRAM &

DETAILS

MAY 14, 2021 WSP TED

BID DOCUMENTS

SCALE: NOT TO SCALEF5

GROUNDING RISER DIAGRAM

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

SCALE: NOT TO SCALEF1

GENERATOR EXHAUST FLUE GROUNDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :1

P

M

ES-611

ELECTRICAL LUMINAIRE & EQUIPMENT

SCHEDULES

MAY 14, 2021 WSP TED

BID DOCUMENTS

LUMINAIRE SCHEDULE

FIXTURE DESCRIPTION LAMP

NOMINAL

LUMENS CRI CCT VOLTAGE WATTAGE MOUNTING MANUFACTURER NOTES

F 4' UTILITY STRIP LUMINAIRE WITH

WHITE FINISH. PROVIDE CHAIN

HANGERS AND WIRE GUARD.

LED 4000 80+ 4000 K 120 V 31 W PENDANT MOUNT 11'-0" AFF TO BOTTOM

OF FIXTURE, UNLESS OTHERWISE NOTED

DAY-BRITE - FSS

EATON METALUX - SNLED

COLUMBIA - LCL

FE SAME AS TYPE 'F' EXCEPT WITH

EMERGENCY BATTERY BACKUP

LED 4000 80+ 4000 K 120 V 31 W

O WALL PACK LED 9000 80+ 4000 K 120 V 72 W WALL MOUNT AT EXISTING LUMINAIRE

OUTLET BOX, UNLESS OTHERWISE NOTED

PHILIPS STONCO - WPM

EATON LUMARK - WP

HUBBELL OUTDOOR - WGH

X EXIT SIGN WITH EMERGENCY

BATTERY BACKUP

LED N/A 80+ N/A 120 V 5 W WALL/CEILING, AS INDICATED ON THE

DRAWINGS

CHLORIDE LIGHTING - 55L

DUAL LITE - SE

EMERGI-LITE - PRESTIGE

HE WILLIAMS - EXIT

LIGHTALARMS - GALAXY

SURE-LITES - CX

NOTES:

1. WIRE EXIT SIGNS AHEAD OF ALL LOCAL SWITCHING.

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

MECHANICAL EQUIPMENT SCHEDULE

UNIT VOLTAGE

NUMBER

OF POLES KVA MCA HP STARTER DISCONNECT FEEDER SIZE PANEL CIRCUIT LOCATION NOTES

DAY TANK 120 V 1 0.86 kVA 9 A 1/3 BY DIVISION 22 N/A 2#12 & 1#12G - 3/4"C GBEP 7 EMERGENCY GENERATOR 200 1

NOTES:

1. ALL CONDUCTORS FOR MECHANICAL EQUIPMENT SHALL BE COPPER.

30" 30" 30"

90"

91.5"

MAGNUM ATS

EMERGENCY MAIN NORMAL MAIN

4 POLE

B6 EXISTING ATS SWITCHBOARD ELEVATION

SCALE: NOT TO SCALE

MAGNUM ATS

4 POLE

MAGNUM ATS

4 POLE

D6 NEW MANUAL TRANSFER SWITCHBOARD ELEVATION

SCALE: NOT TO SCALE

ERMS

K1

ERMS

K1

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7

DETAILED ELEVATION BASED

ON SQUARE D. WORST CASE

EQUIPMENT DIMENSIONS ARE

110" X 38" X 91.5".

OPEN OPEN

TRIP CLOSE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

NON SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

REPLACE 750kW EMERGENCY

GENERATOR BUILDING 116

VAMC MOUNTAIN HOME, TN

621-19-123

B

IM

/1

V

A

-1

-1

B ld g

G e n e ra to r/

V

A B ld g M

E P

F

P v .r v t

/1

/2

:3 :1

P

M

ES-621

ELECTRICAL SWITCHBOARD SCHEDULES &

ELEVATIONS

MAY 14, 2021 WSP TED

BID DOCUMENTS

SHEET NOTES:

1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

EXISTING SWITCHBOARD

'ATS'

A ARC-FAULT CIRCUIT INTERRUPTOR (AFCI)

G GROUND FAULT CIRCUIT INTERRUPTOR (GFCI)

H PROVIDE RED CIRCUIT BREAKER WITH HANDLE

CLAMP DEVICE

S SHUNT TRIP BREAKER

E EXISTING-TO-REMAIN

N NEW BREAKER IN EXISTING SPACE

M PROVIDE CT FOR METERING SYSTEM AND CONNECT

TO METER INDICATED ON THE METERING SCHEDULE

PANELBOARD SCHEDULE NOTE LEGEND:

NEW MANUAL TRANSFER

SWITCHBOARD

1. EXISTING-TO-REMAIN EATON AUTOMATIC TRANSFER SWITCHBOARD (GO# LAT0006321-001).

2. PROVIDE NEW TYPE 1 INTERNAL SURGE PROTECTIVE DEVICE. 7X CHASSIS MOUNTED SPD UNIT - SPD SERIES 250kA SPD, POWER XPERT SPD WITH SURGE COUNTER (DISCONNECT

INCLUDED). SPD CAT# SPD250208Y4C

NOTES:

15 EXISTING MAIN CIRCUIT BREAKER (UTILITY) 3 2500 A 2500 A 0.00 kVA SECTION 7

14 NEW SPD (N) 3 60 A 60 A 0.00 kVA SECTION 6

13 EXISTING SPACE -- -- -- 0.00 kVA --

12 EXISTING BUILDING 69 3 400 A 400 A 0.00 kVA SECTION 6

11 EXISTING PANEL 'DPEC' ATS (E) 3 800 A 800 A 0.00 kVA SECTION 5

10 EXISTING PANEL 'DPEC' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 4

9 EXISTING PANEL 'DPELS' ATS (E) 3 800 A 800 A 0.00 kVA SECTION 4

8 EXISTING PANEL 'DPELS' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 4

7 EXISTING PANEL 'DPEE' ATS (E) 3 800 A 800 A 10.47 kVA SECTION 3

6 EXISTING PANEL 'DPEE' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 3

5 EXISTING SPACE -- -- -- 0.00 kVA --

4 NEW SPD (E) 3 60 A 60 A 0.00 kVA SECTION 2

3 EXISTING SPACE -- -- -- 0.00 kVA --

2 EXISTING BUILDING 116 3 225 A 225 A 0.00 kVA SECTION 2

1 EXISTING MAIN CIRCUIT BREAKER (EMERGENCY) 3 2500 A 2500 A 0.00 kVA SECTION 1

CKT CIRCUIT DESCRIPTION # OF POLES FRAME SIZE TRIP RATING LOAD REMARKS

ENCLOSURE: NEMA 1

MOUNTING: FLOOR WIRES: 4 MAINS RATING: 2500 A

SUPPLY FROM: PHASES: 3 MAINS TYPE: 2500 A MCB

LOCATION: ELECTRICAL 100 VOLTS: 208Y/120 A.I.C. RATING: 65,000 A

EXISTING SWITCHBOARD: ATS

1. EATON…