Drawings 24-33.pdf
PDF 26 MB Posted
- Solicitation number
- 36C24921B0011
About this file
This federal presolicitation notice is for the replacement of a 750kW emergency generator at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project number is 6115--Project 621-19-123 and has an estimated value between $500,000 and $1,000,000. The NAICS code is 238210 and the small business size standard is $16.5 million. The solicitation is expected to be posted on June 28, 2021 and close on July 28, 2021. This is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. Offerors must be listed in the CVE database and SAM, and the awarded contractor must submit evidence of VETS4212 enrollment. The contracting officer is Diana Grube and questions must be submitted in writing to her email with the project information in the subject line before the solicitation is issued.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24921B0011 0002.pdf | ||
| 36C24921B0011 0001.docx | DOCX document | |
| Building 116 Lead and Asbestos Survey Results.pdf | ||
| RFI Form - 750kW Emergency Gen.pdf | ||
| Drawings 11-17.pdf | ||
| Specs 621-19-123 Replace Emerg Generator Bldg 116 - Bid Documents .pdf | ||
| EMR.pdf | ||
| WD TN20210111 dated 1-1-2021.pdf | ||
| Drawings 18-23.pdf | ||
| Header - List of Attachments.txt | TXT text file | |
| 36C24921B0011_1.docx | DOCX document | |
| Drawings 1-10.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
ES-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - SPECIFICATIONS
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
A. NFPA 70 NATIONAL ELECTRICAL CODE, 2020 EDITION
B. NFPA 99 HEALTH CARE FACILITIES CODE, 2021 EDITION
C. NFPA 101 LIFE SAFETY CODE, 2021 EDITION
D. NFPA 110 EMERGENCY AND STANDBY POWER SYSTEMS, 2019 EDITION
E. NFPA 780 STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, 2020 EDITION
F. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%
FULL.
3. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT, CLEARANCE FOR RECESSED LUMINAIRES, AND CORRECT ROUGH-IN LOCATIONS OF
ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL
DESCRIPTIONS INDICATED.
5. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.
6. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE NEUTRAL CONDUCTORS AS INDICATED HEREIN. MULTIPLE BRANCH CIRCUITS IN ONE
RACEWAY REQUIRE ONLY ONE EQUIPMENT GROUNDING CONDUCTOR.
7. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DEMOLISHED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DEMOLISHED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AT NO ADDITIONAL
COST TO THE OWNER.
8. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER. SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE
EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.
9. REFER TO SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
10. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK THAT SHALL BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND
SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
11. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK THAT SHALL BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE
CONTRACTOR'S RESPONSIBILITY.
12. ALL CONDUCTORS SHALL BE COPPER.
13. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY
MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
14. PROVIDE LABELS ON ALL RECEPTACLES, LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED
CEILING WHICH MAY BE HANDWRITTEN WITH AN INDELIBLE MARKER.
15. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.
16. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME EMERGENCY POWER (ARTICLE 700 LOADS) IS "ON LINE" SHALL NOT EXCEED 10 SECONDS. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME LEGALLY REQUIRED (ARTICLE 701) POWER IS "ON LINE" AND SHALL NOT BE NO MORE THAN 60 SECONDS. FROM THE TIME NORMAL POWER IS LOST UNTIL THE TIME OPTIONAL STANDBY POWER (ARTICLE 702 LOADS) IS "ON LINE" AND SHALL BE NO LESS THAN 60 SECONDS BUT NO MORE THAN 120 SECONDS.
ELECTRICAL ABBREVIATIONS
A or AMP
AC
ACC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
COR
CP
CPT
CRAC
CRI
CT
CU
CWP
D
DC
DF
DH
DHWCP
DISC
DOAS
DPDT
DPST
DSCU
DSHP
DSS
DUH
DWBP
DX
E or EMER
EC
EF
ELEC
EMEW
EMH
EMSH
EMT
EPA
EQUIP
ERU
ERV
ESEW
EUH
EWC
EWH
EX or EXIST
EXP
F
FACP
FCU
FLEX
FWE
G or GND
GFCI
GFGI
GRC
GUH
GWH
H or HT
HAC
HOA
HP
HT
HVU
HWCP
HWP
HWRP
HWSP
HWUH
HZ
AMPERE(S)
AIR COMPRESSOR or AIR CURTAIN or
ALTERNATING CURRENT
AIR COOLED CHILLER
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP
CIRCUIT
COMMUNICATIONS MANHOLE
CONTRACTING OFFICER'S REPRESENTATIVE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER or COOLING TOWER
COPPER
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATER or DEHUMIDIFIER
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM
DOUBLE POLE DOUBLE THROW
DOUBLE POLE SINGLE THROW
DUCTLESS SPLIT CONDENSING UNIT
DUCTLESS SPLIT HEAT PUMP
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DUCT UNIT HEATER
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION COOLING COIL
EMERGENCY
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
EMERGENCY EYEWASH
ELECTRICAL MANHOLE
EMERGENCY SHOWER
ELECTRICAL METALLIC TUBING
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY UNIT
ENERGY RECOVERY VENTILATOR
EMERGENCY SHOWER / EYEWASH
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXISTING
EXPLOSION PROOF
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED CONTRACTOR
INSTALLED or GROUND FAULT CIRCUIT
INTERRUPTER
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER or HEAT PUMP
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP
HEATING WATER PUMP
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP
HOT WATER UNIT HEATER
HERTZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCMIL
KEF
KH
KV
KVA
KVAR
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB
MCC
MGB
MH
MIN
MLO
MOD
MRS
MT or MTD N
NC
NEC
NEMA
NESC
NFPA
NL
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UG
UH
UIO
UL
UTP
V
VA
VAR
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WP
WSHP
XFMR
Z
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT AMPERES
KILOVOLT AMPERES REACTIVE
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOTOR RATED SWITCH
MOUNT or MOUNTED
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL ELECTRICAL SAFETY CODE
NATIONAL FIRE PROTECTION ASSOCIATION
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
PRIMARY INDUCTION UNIT (VAV TERMINAL UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNDERGROUND
UNIT HEATER
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VOLT AMPERES REACTIVE
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WEATHERPROOF
WATER SOURCE HEAT PUMP
TRANSFORMER
IMPEDANCE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :0
P
M
ES-001
ELECTRICAL GENERAL NOTES &
ABBREVIATIONS
MAY 14, 2021 WSP TED
BID DOCUMENTS
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 125 FT AND
GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 190 FT AND
GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH LESS THAN 300 FT AND
GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G, 3/4"C.
NOTES:
1. 'E' NEXT TO A DEVICE INDICATES THE DEVICE IS EXISTING TO
REMAIN. 'D' NEXT TO A DEVICE INDICATES IT IS TO BE
DEMOLISHED.
2. ALL EXISTING EQUIPMENT IS SHOWN IN THIN LINEWORK. ALL
DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
Revisions: Date:
1/2
B
W
S B
M
M
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
A
AE
M
X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNT AT 96" ABOVE FINISHED FLOOR.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
EMERGENCY LIGHT UNIT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
REMOTE HEAD OR FLOOD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
WALL WASH DOWNLIGHT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POLE MOUNTED LUMINAIRE. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POST-TOP OR BOLLARD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER,
(CIRCUIT BREAKER SIZE/ POLES/ NEMA
ENCLOSURE)
DRY TYPE TRANSFORMER
METER
ELECTRONIC METER
SURFACE MOUNTED PANELBOARD. DASHED BOX
INDICATES WORKING ACCESS REQUIRED BY
CODE.
RECESSED MOUNTED PANELBOARD. DASHED
BOX INDICATES WORKING ACCESS REQUIRED
BY CODE.
DISTRIBUTION PANELBOARD. DASHED BOX
INDICATES WORKING ACCESS REQUIRED BY
CODE.
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
PULL OR JUNCTION BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE
DROP CEILING
EMERGENCY POWER OFF SWITCH
CR
ST
TR
M
R
P2A-1,3,5
WIRING DEVICES
4-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
SLIDE DIMMER, MOUNT 48" ABOVE FINISHED
FLOOR
MOTOR RATED DISCONNECT SWITCH WITH
THERMAL OVERLOADS, SINGLE POLE SINGLE
THROW, MOUNT ON UNIT, UNLESS INDICATED
OTHERWISE.
WALL MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
WALL MOUNTED, DUAL TECHNOLOGY VACANCY
SWITCH, MOUNT 48" ABOVE FINISHED FLOOR
LOW VOLTAGE ON/OFF WALL SWITCH, WALL
MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE
DIMMER CONTROL WITH DIMMABLE FIXTURES
INTEGRAL WITH SWITCH.
BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT
48" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
WHITE NOISE ROTARY VOLUME CONTROL;
MOUNT 48" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE.
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
CEILING MOUNTED DUAL TECHNOLOGY
VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
WIRING
CIRCUIT HOMERUN TO PANELBOARD. P2A-1,3,5,
ADJACENT TO ARROW, INDICATES HOMERUN
CIRCUITS 1, 3, AND 5 IN PANEL P2A. MARKS
ACROSS RACEWAY INDICATE THE NUMBER OF
PHASE CONDUCTORS AND NEUTRALS IN
RACEWAY. NEUTRAL CONDUCTORS ARE
INDICATED BY LONGER HASHMARKS. NO MARKS
ACROSS RACEWAY INDICATES 2#12
CONDUCTORS AND 1#12 GROUND CONDUCTOR.
CONDUCTOR SIZE #12 UNLESS INDICATED
OTHERWISE.
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UNLESS INDICATED
OTHERWISE
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
LADDER TYPE CABLE TRAY (SIZE AS INDICATED
ON PLAN)
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"
ABOVE FINISHED FLOOR (TO CENTERLINE OF
DEVICE) OR 6" ABOVE COUNTERTOP (TO
BOTTOM OF DEVICE) OR 4" ABOVE BACKSPLASH
(TO BOTTOM OF DEVICE)
DUPLEX GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE NEMA 5-20R, MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE NEMA 5-20R, MOUNT 48" ABOVE
FINISHED FLOOR (TO CENTERLINE OF DEVICE)
OR 6" ABOVE COUNTERTOP (TO BOTTOM OF
DEVICE) OR 4" ABOVE BACKSPLASH (TO BOTTOM
OF DEVICE)
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SPLIT YOKE, DUPLEX RECEPTACLE NEMA 5-20R
WITH ONE CONTROLLED AND ONE NON-
CONTROLLED RECEPTACLE. MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
SPLIT YOKE, DUPLEX RECEPTACLE NEMA 5-20R
WITH ONE CONTROLLED AND ONE NON-
CONTROLLED RECEPTACLE. MOUNT 48" ABOVE
FINISHED FLOOR (TO CENTERLINE OF DEVICE)
OR 6" ABOVE COUNTERTOP (TO BOTTOM OF
DEVICE) OR 4" ABOVE BACKSPLASH (TO BOTTOM
OF DEVICE)
SPLIT YOKE, DUPLEX GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE NEMA 5-20R WITH
ONE CONTROLLED AND ONE NON-CONTROLLED
RECEPTACLE. MOUNT 18" ABOVE FINISHED
FLOOR, UNLESS INDICATED OTHERWISE
SPLIT YOKE, DUPLEX GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE NEMA 5-20R, WITH
ONE CONTROLLED AND ONE NON-CONTROLLED
RECEPTACLE. MOUNT 48" ABOVE FINISHED
FLOOR (TO CENTERLINE OF DEVICE) OR 6"
ABOVE COUNTERTOP (TO BOTTOM OF DEVICE)
OR 4" ABOVE BACKSPLASH (TO BOTTOM OF
DEVICE)
DOUBLE-DUPLEX GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE, NEMA 5-20R,
MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" ABOVE
FINISHED FLOOR
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR.
WALL SWITCH, AC TYPE, SPST, MOUNT 48"
ABOVE FINISHED FLOOR
WALL SWITCH, AC TYPE, DPDT, MOUNT 48"
ABOVE FINISHED FLOOR
3-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
ELECTRICAL LEGEND
D
M
LV
OS
DS
PE
5-30R
EWC
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND ROD TEST WELL
BARE COPPER GROUND CONDUCTOR, 1/0 UNLESS
INDICATED OTHERWISE.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SCHEMATIC
PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)
CONTROL RELAY COIL
SHUNT TRIP COIL
TIME DELAY RELAY COIL
MOTOR STARTER COIL
S W
S
S
S
S
S
S
S
VS
DE
F
G
H
P
J
V S
O S
G
G4
LP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :0
P
M
ES-002
ELECTRICAL LEGEND
MAY 14, 2021 WSP TED
BID DOCUMENTS
NOTE:
1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
SSS
S
S
PC
F A
T C
S M
S M
S M
S M
S M
S M
S M
1 2
B
A
EXISTING-TO-REMAIN
LIGHTING PANEL WITH
CONTACTOR PANEL ABOVE
EXISTING-TO-REMAIN
PHOTOCELL
EXISTING-TO-REMAIN
EXTERIOR LIGHTING MANUAL
OVERRIDE SWITCH
EMERGENCY
GENERATOR
ELECTRICAL
D D
D D
D D
D D
D D
D D D D
D D
D
D D
D D
D D
D D
D
D
D
D
D
1 2
B
A
+48"
+48"
+48"
+48"
W P
+48"
+48"
EXISTING-TO-BE-
RELOCATED
DISCONNECT SWITCH
FOR EXH-116-1
EXISTING-TO-BE-
RELOCATED
COMBINATION STARTER &
DISCONNECT SWITCH FOR
UNIT HEATER-116-2
EXISTING-TO-BE-
RELOCATED METERING
SYSTEM
EXISTING-TO-REMAIN
FIRE ALARM PANELS
EXISTING-TO-REMAIN
LIGHTING PANEL WITH
CONTACTOR PANEL ABOVE
EXISTING-TO-REMAIN
'AUTOMATIC TRANSFER
SWITCHBOARD'
EXISTING-TO-REMAIN
PANEL 'GBEP'
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
MOTORIZED DAMPERS
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
EUH-11
EXISTING-TO-BE-
DEMOLISHED DAY TANK
AND FUEL PUMPING
SYSTEM
EXISTING-TO-BE-
DEMOLISHED REMOTE
RADIATOR
EXISTING-TO-BE-
DEMOLISHED DISCONNECT
FOR REMOTE RADIATOR
EXISTING-TO-BE-
DEMOLISHED ENGINE
GENERATOR SET
EXISTING-TO-BE-
DEMOLISHED BATTERY
CHARGER
EXISTING-TO-BE-
DEMOLISHED GENERATOR
CONTROL PANEL
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
MOTORIZED DAMPERS
EXISTING-TO-REMAIN
PANEL 'DPELS'
EXISTING-TO-REMAIN
PANEL 'DPEC'
EXISTING-TO-REMAIN
PANEL 'DPEE'
ELECTRICAL
EMERGENCY
GENERATOR
N O
R M
A L
M
IN
D
IS
T
A
T S
A T
S A
T S
D
IS
T
E M
E R
M
A
IN
E
E
E
E
E
R
E
E
E
E
EXISTING-TO-BE-
DEMOLISHED
EMERGENCY POWER
OFF SWITCH.
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
MOTORIZED DAMPERS
EXISTING-TO-BE-RELOCATED
RECEPTACLE. SEE SHEET
ES-101 FOR NEW LOCATION.
5R R
PHOTO KEY LEGEND
DIRECTION PHOTO WAS TAKEN
NOTES PHOTO LOCATION
PHOTO DETAIL NUMBER
REFERENCE SHEET ES-501 FOR PHOTOS
B1
B3
B5
D5
D3
D1
A1
T R
U E
N
PLAN
NORTH
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :1
P
M
ESD101
ELECTRICAL DEMOLITION PLANS
MAY 14, 2021 WSP TED
BID DOCUMENTS
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS
& LEGEND.
2. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND, UNLESS EXPLICITLY
DIMENSIONED, INDICATE APPROPRIATE LOCATIONS OF FIXTURES, APPARATUS,
EQUIPMENT AND RACEWAYS. CHANGES IN THE LOCATION, AND OFFSETS, OF
WORK OF OTHER TRADES, SHALL BE MADE DURING THE PREPERATION OF
COORDINATION DRAWINGS AND PRIOR TO INITIAL INSTALLATION, WITHOUT
ADDITIONAL COST.
3. ASSUME EQUIPMENT FOR DEMOLITION HAS LEAD-CONTAINING AND ASBESTOS-
CONTAINING MATERIALS WHICH SHALL BE HANDLED IN ACCORDANCE WITH
STATE AND FEDERAL REGULATIONS, AND THE SPECIFICATIONS CONTAINED
HEREIN. THE RECENT SURVEY PERFORMED CAN BE REQUESTED FROM THE
CONTRACTING OFFICER'S REPRESENTATIVE FOR USE AS "FOR INFORMATION
ONLY."
4. LOCATIONS OF MOTORS, STARTERS, EQUIPMENT AND APPARATUS AS
INDICATED ON THE DRAWINGS ARE APPROXIMATE; CONNECTIONS SHALL BE
MADE TO SUCH EQUIPMENT AS ACTUALLY INSTALLED.
5. PROVIDE ACCESS TO EQUIPMENT AND APPARATUS REQUIRING OPERATION,
SERVICE OR MAINTENANCE THROUGHOUT THE LIFE OF THE SYSTEM.
6. SWITCHBOARDS, PANELBOARDS, VARIABLE FREQUENCY DRIVES,
TRANSFORMERS, AND STARTERS SHALL BE INSTALLED SUCH THAT THE
WORKING SPACE IN FRONT, REAR AND/OR SIDE (WHERE REAR AND/OR SIDE
ACCESS IS REQUIRED TO WORK ON EQUIPMENT) IS CLEAR OF PIPING,
DUCTWORK, OR MECHANICAL EQUIPMENT. DIMENSIONS OF THE WORKING
SPACE SHALL BE A MINIMUM DEPTH OF 36" HORIZONTALLY, THE WIDTH OF THE
EQUIPMENT OR 30", WHICHEVER IS GREATER, AND THE HEIGHT OF THE
EQUIPMENT OR 78", WHICHEVER IS GREATER.
7. SCHEDULE AND PHASE WORK, AND PROVIDE TEMPORARY SERVICE AND
CONNECTIONS, AS INDICATED IN SECTION 01 00 00 GENERAL REQUIREMENTS.
8. THE EXISTING INSTALLATION SHALL REMAIN AS IS EXCEPT AS OTHERWISE
INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. PERFORM WORK TO TIE
IN THE NEW WORK WITH THE EXISTING WORK AND TO ADAPT THE EXISTING
WORK TO THE CHANGES IN THE BUILDING AND SYSTEMS.
9. REMOVE EQUIPMENT, APPARATUS, AND EXPOSED WIRING AND RACEWAYS
RENDERED USELESS DUE TO CHANGES.
10.REMOVE ALL LUMINAIRES AND EXIT SIGNS.
11.EXISTING-TO-BE-REMOVED BATTERY UNITS SHALL BE TURNED OVER TO THE
CONTRACTING OFFICER'S REPRESENTATIVE. ALL OTHER ITEMS THAT ARE
EXISTING-TO-BE-REMOVED SHALL BECOME THE PROPERTY OF THE
CONTRACTOR AND BE REMOVED FROM THE SITE AND DISPOSED OF IN
ACCORDANCE WITH STATE AND FEDERAL REGULATIONS.
12.MATERIAL AND EQUIPMENT WHICH HAS BEEN REMOVED AND NOT ACCEPTED
BY THE CONTRACTING OFFICER'S REPRESENTATIVE SHALL BECOME THE
PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE.
13.EXISTING ELECTRICAL EQUIPMENT, INCLUDING LAMPS AND BALLASTS,
REMOVED AND NOT REUSED SHALL BE HANDLED AND DISPOSED OF IN
ACCORDANCE WITH APPLICABLE STATE AND FEDERAL REGULATIONS.
14.MATERIAL AND EQUIPMENT WHICH HAS BEEN REMOVED SHALL NOT BE USED
IN THE NEW WORK, EXCEPT AS SPECIFIED HEREIN.
15.WHERE EXISTING RACEWAYS AND EQUIPMENT ARE INDICATED ON THE
DRAWINGS, SIZE AND LOCATION SHALL BE VERIFIED PRIOR TO BIDDING.
16.PROVIDE CIRCUIT CONTINUITY FOR EXISTING WIRING DEVICES AND
EQUIPMENT OUTSIDE THE RENOVATION AREA SERVED FROM OR THROUGH
THE RENOVATION AREA.
17.REMOVE THE EXISTING EMERGENCY POWER SUPPLY AND INSTALL A NEW
EMERGENCY POWER SUPPLY AS SPECIFIED HEREIN AND AS INDICATED ON
THE DRAWINGS.
18.SLEEVES LEFT OPEN BY REMOVAL OF CONDUIT OR RACEWAYS SHALL BE CUT
FLUSH WITH THE FINISHED SLAB, AND FILLED WITH GROUT FLUSH WITH SLAB.
19.CONCEALED RACEWAYS IN MASONRY WALLS RENDERED USELESS BY
REVISIONS SHALL BE CUT FLUSH WITH WALL SURFACE AND SEALED WITH
GROUT.
20.WHERE EXISTING MECHANICAL EQUIPMENT IS REMOVED, REMOVE ELECTRICAL
WIRING, RACEWAYS, SWITCHES AND STARTERS ASSOCIATED WITH THE
EQUIPMENT.
21.WHERE EXISTING MECHANICAL EQUIPMENT IS MODIFIED OR RELOCATED,
MODIFY THE ELECTRICAL CONNECTIONS TO THE EQUIPMENT TO ADAPT IT TO
ITS NEW FUNCTION OR LOCATION.
KEYNOTES:
1. DEMOLISH ALL EXISTING LUMINAIRES IN THIS SPACE. EXISTING
BRANCH CIRCUIT AND SWITCH WIRING SHALL REMAIN.
RECONNECT NEW LUMINAIRES TO EXISTING BRANCH CIRCUIT
WIRING.
2. DEMOLISH LUMINAIRE AND BRANCH CIRCUIT WIRING BACK TO
THE SOURCE. REMOVE ANY RECEPTACLES USED FOR PLUG-
AND-CORD CONNECTED LUMINAIRES.
3. DEMOLISH EXISTING EXTERIOR LUMINAIRE. EXISTING BRANCH
CIRCUIT SWITCH WIRING SHALL REMAIN. RECONNECT NEW
LUMINAIRE(S) TO EXISTING OUTLET BOX AND BRANCH CIRCUIT
WIRING.
4. DEMOLISH EXISTING EXIT SIGN. EXISTING BRANCH CIRCUIT
WIRING SHALL REMAIN. RECONNECT NEW EXIT SIGN(S) TO
EXISTING OUTLET BOX AND BRANCH CIRCUIT WIRING.
5. EXISTING VEEDER ROOT TLS-300 TANK GAUGE AND LEAK
DETECTION UNIT IS EXISTING-TO-REMAIN. PROTECT SYSTEM
DURING CONSTRUCTION AND DEMONSTRATE OPERATION
UPON SUBSTANTIAL COMPLETION OF THE PROJECT.
SCALE: 1/4" = 1'-0"F1
DEMOLITION LIGHTING PLAN
SCALE: 1/4" = 1'-0"F5
DEMOLITION POWER PLAN
SCALE: = 1'-0"
0 4 84
1/4"
RISER DIAGRAM LEGEND
INDIVIDUALLY
MOUNTED CIRCUIT
BREAKER; TRIP AND
POLE SIZE AS
INDICATED.
PANELBOARD; MAIN
CIRCUIT BREAKER,
CIRCUIT BREAKERS AS
SCHEDULED.
INDIVIDUALLY
MOUNTED MOTOR
STARTER OR VARIABLE
FREQUENCY DRIVE;
NEMA SIZE AS
INDICATED.
AUTOMATIC TRANSFER
SWITCH; SIZE AS
INDICATED.
TRANSFORMER; SEE
TRANSFORMER
SCHEDULE, PRIMARY &
SECONDARY FEEDER
SIZE, AND GROUNDING
ELECTRODE
INFORMATION.
FUSED DISCONNECT;
FRAME, POLE, AND
FUSE SIZE AS
INDICATED.
NOTE: NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
PANELBOARD; MAIN
LUGS ONLY, CIRCUIT
BREAKERS AS
SCHEDULED.
MOTOR, HORSEPOWER
AS INDICATED.
FEEDER; CONDUIT AND
WIRE SIZE AS
INDICATED BY FEEDER
MARK.
NON-FUSED
DISCONNECT; FRAME
AND POLE SIZE AS
INDICATED.
SITELEVEL 1EMERGENCY
ELECTRICAL
ROOM
EXTERIOR
XFMR
'XAD'
DEMO
A
/3 P
V F
D
A
/3 P
/4 A
DEMO
A
/3 P
EXISTING
TO-BE-DEMOLISHED
REMOTE RADIATOR
EXISTING
TO-BE-DEMOLISHED
SKID-MOUNTED ENGINE
GENERATOR SET
EXISTING
XFMR
'XAD'
A
/3 P
V F
D
A
/3 P
/4 A
EXISTING
A
/3 P
EXISTING SERVICE
TRANSFORMER
208Y/120 V
3 PH, 4W
EXISTING
PANEL
'DPEE'
EXISTING
PANEL
'DPELS'
EXISTING
PANEL
'DPEC'
EXISTING
PANEL
'GBEP'
EXISTING SITE
LIGHTING
PANEL
EXISTING
FEEDER TO
BLDG 69
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
2,500AT
2,500AF
2,500AT
2,500AF
225A/3P 400A/3P
EXISTING-TO-REMAIN
'ATS' SWITCHBOARD
EXISTING
FEEDER TO
BLDG 116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :1
P
M
ESD601
ELECTRICAL DEMOLITION RISER DIAGRAM
MAY 14, 2021 WSP TED
BID DOCUMENTS
SCALE: NOT TO SCALEF1
DEMOLITION RISER DIAGRAM
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS
& LEGEND.
SSS
S
S
PC
F A
T C
S M
S M
S M
S M
S M
J
J S M
J
1 2
B
A
EXISTING-TO-REMAIN
LIGHTING PANEL WITH
CONTACTOR PANEL ABOVE
EXISTING-TO-REMAIN
PHOTOCELL
EXISTING-TO-REMAIN
EXTERIOR LIGHTING MANUAL
OVERRIDE SWITCH
F
FE
F
FE
F
FE
F
FE
F
FE
F
F
FE
F
FE FE
F
FE
F
FEFFE
X
OO
EMERGENCY
GENERATOR
ELECTRICAL
O
O
1 1
X
1 2
B
A
RELOCATED DISCONNECT
SWITCH FOR EXH-116-1
RELOCATED METERING
SYSTEM
EXISTING-TO-REMAIN
FIRE ALARM PANEL
EXISTING-TO-REMAIN LIGHTING
PANEL WITH CONTACTOR PANEL
ABOVE
EXISTING-TO-REMAIN 'AUTOMATIC
TRANSFER SWITCHBOARD'
EXISTING-TO-REMAIN
PANEL 'GBEP'
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
EUH-11
EXISTING-TO-REMAIN
PANEL 'DPELS'
EXISTING-TO-REMAIN
PANEL 'DPEC'
EXISTING-TO-REMAIN
PANEL 'DPEE'
+48"
+48"
+48"
+48"
W P
+48"
ELECTRICAL
EMERGENCY
GENERATOR
N O
R M
L
M
IN
D
IS
T
A
T S
A T
S A
T S
D
IS
T
E M
E R
M
A
IN
E
E
E
E
E
E
E
NEW EMERGENCY
POWER OFF SWITCH FOR
ENGINE GENERATOR
SET. PROVIDE CLASS 2
WIRING TO GENERATOR
CONTROLLER AS
REQUIRED BY THE
MANUFACTURER.
E
NEW ENGINE
GENERATOR SET
E
R +48"
RELOCATED
DISCONNECT
SWITCH FOR
EXH-116-2
RELOCATED
DUPLEX
OUTLET
NEW GENERATOR QUICK
CONNECT TAP BOX MOUNTED
ON A UNISTRUT FRAME. SEE
DETAIL F5/ES-501.
NEW 750 kVA DRY-TYPE
TRANSFORMER IN
NEMA 3R ENCLOSURE
NEW MANUAL TRANSFER
SWITCHBOARD
(TYPICAL)
10' - 0"
NEW
GROUND
RING
PROVIDE NEW GROUNDING
CONNECTIONS AS INDICATED ON
SHEET ES-602
NEW GROUNDING BAR
SEE DETAIL C7/ES-501 FOR
PENETRATION
EXISTING GROUNDING ELECTRODE.
TRIM AND RECONNECT AS
INDICATED ON SHEET ES-602
FROM
XFMR
LUGS
OUT
FROM
GEN
SET
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
MOTORIZED DAMPERS -
CONNECT NEW DAMPERS TO
EXISTING DISCONNECT.
EXISTING-TO-REMAIN
DISCONNECT SWITCH FOR
MOTORIZED DAMPERS -
CONNECT NEW DAMPERS
TO EXISTING DISCONNECT.
PROVIDE PROTECTIVE
BOLLARDS AS INDICATED IN
DETAIL F1/ES-501. TYPICAL
OF 3.
NEW DAY-TANK
WP
WP GBEP-37
GBEP-10
GBEP-11,13
R
RELOCATED COMBINATION
STARTER & DISCONNECT
SWITCH FOR UNIT HEATER
116-2
R
GBEP-39
SEE DETAIL E4/S-301 FOR
EXTERIOR EQUIPMENT PAD
DETAIL CONSTRUCTION. SEE
SHEET F7/CS101 FOR
DIMENSIONED LOCATION OF
EQUIPMENT PAD.
T R
U E
N
PLAN
NORTH
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :0
P
M
ES-101
ELECTRICAL FLOOR PLANS
MAY 14, 2021 WSP TED
BID DOCUMENTS
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS &
LEGEND.
2. REFER TO ES-611 FOR LUMINAIRE SCHEDULE.
3. REFER TO SHEET ES-611 FOR MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO SHEET CS101 FOR EXACT LOCATION OF EXTERIOR EQUIPMENT.
KEYNOTES:
1. CONNECT NEW LUMINAIRES TO BRANCH CIRCUIT WIRING AND CONTROLS OF
EXISTING LUMINAIRES IN THIS SPACE.
2. PROVIDE 120V CONNECTION FOR BATTERY CHARGER.
3. PROVIDE 208V CONNECTION FOR 9kW BLOCK HEATER. BRANCH CIRCUIT
WIRING SHALL BE 2 #4, 1 #10 G., 1" C.
4. PROVIDE 120V CONNECTION FOR DAY TANK.
5. PROVIDE 120V CONNECTION FOR SPACE HEATER.
6. CONNECT NEW EXIT SIGN AHEAD OF LOCAL SWITCHING. PROVIDE AN
ADDITIONAL PHASE CONDUCTOR IN BRANCH CIRCUIT WIRING AS REQUIRED.
SCALE: 1/4" = 1'-0"F1
LIGHTING PLAN
SCALE: 1/4" = 1'-0"F5
POWER PLAN
SCALE: = 1'-0"
0 4 84
1/4"
LENGTH AS REQUIRED
APPROXIMATELY 14"
M
IN
IM
U
M
WIDTH OF QUICK
CONNECT TAP BOX
2'-0"
2'-0"4'-0"
3'-0"
EMBEDMENT
2' DIAMETER MINIMUM
6"
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 36" SHALL BE INSTALLED WITH A CENTER SUPPORT
ROD. SUPPORT RODS SHALL NOT BE GREATER THAN 18" APART.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES FOR
ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
CONDUIT CLAMP. SIZE AS
REQUIRED
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
LOCKING SQUARE WASHER
& LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
WASHER & LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
LOCKING
SQUARE WASHER
& LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL
F7 CONDUIT TRAPEZE MOUNTING DETAIL
SCALE: NOT TO SCALE
BRACES
12 GAUGE 1.5"
SQUARE
GALVANIZED STEEL
CHANNEL
STANCHION AND
BRACES
0.25" x 1.5" WELDED
GALVANIZED STEEL
CORNER BRACE
WELD ALL AROUND
F5 EQUIPMENT MOUNTING DETAIL
SCALE: NOT TO SCALE
F1 BOLLARD DETAIL
SCALE: NOT TO SCALE
TRANSFORMER/SWITCHGEAR PLAN VIEW
ROUNDED CONCRETE CAP,
FORMED IN FIELD
CONCRETE FILLED 6"
DIAMETER GALVANIZED
STEEL PIPE PAINTED
SAFETY YELLOW
CONCRETE FOOTING
FINISHED GRADE
FINISHED GRADE
FINISHED FLOOR
1" METAL CONDUIT
SEAL WALL PENETRATION
CONDUIT BODY
BUILDING WALL
1" GRC
BOND EACH END OF
CONDUIT TO
GROUND CABLE
GROUND ROD
CONDUIT
GROUNDING
BUSHING
4/0 BARE COPPER
2' MIN.
6' MAX.
M
IN
M A
X
TO EXISTING GROUNDING
ELECTRODE
EXOTHERMIC WELD
GROUND BAR
#4/0 BARE COPPER CONDUCTOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :0
P
M
ES-501
ELECTRICAL DETAILS
MAY 14, 2021 WSP TED
BID DOCUMENTS
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
SCALE: NOT TO SCALEC7
GROUNDING ELECTRODE CONNECTION DETAIL
SCALE: NOT TO SCALEB1
EXTERIOR VIEW
SCALE: NOT TO SCALEB3
EXISTING METERING ASSEMBLY
SCALE: NOT TO SCALEB5
SPACE BEHIND SWITCHBOARD
SCALE: NOT TO SCALED5
EXISTING GROUNDING ELECTRODE
SCALE: NOT TO SCALED1
EXISTING VEEDER-ROOT SYSTEM
SCALE: NOT TO SCALED3
EXISTING UNIT HEATER
RISER DIAGRAM LEGEND
INDIVIDUALLY
MOUNTED CIRCUIT
BREAKER; TRIP AND
POLE SIZE AS
INDICATED.
PANELBOARD; MAIN
CIRCUIT BREAKER,
CIRCUIT BREAKERS AS
SCHEDULED.
INDIVIDUALLY
MOUNTED MOTOR
STARTER OR VARIABLE
FREQUENCY DRIVE;
NEMA SIZE AS
INDICATED.
TRANSFER SWITCH;
SIZE AS INDICATED.
TRANSFORMER; SEE
TRANSFORMER
SCHEDULE, PRIMARY &
SECONDARY FEEDER
SIZE, AND GROUNDING
ELECTRODE
INFORMATION.
FUSED DISCONNECT;
FRAME, POLE, AND
FUSE SIZE AS
INDICATED.
NOTE: NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
PANELBOARD; MAIN
LUGS ONLY, CIRCUIT
BREAKERS AS
SCHEDULED.
MOTOR, HORSEPOWER
AS INDICATED.
FEEDER; CONDUIT AND
WIRE SIZE AS
INDICATED BY FEEDER
MARK.
NON-FUSED
DISCONNECT; FRAME
AND POLE SIZE AS
INDICATED.
SITELEVEL 1EMERGENCY
ELECTRICAL
ROOM
EXTERIOR
EXISTING
XFMR
'XAD'
A
/3 P
V F
D
A
/3 P
/4 A
EXISTING
A
/3 P
EXISTING SERVICE
TRANSFORMER
208Y/120 V
3 PH, 4W
EXISTING
PANEL
'DPEE'
EXISTING
PANEL
'DPELS'
EXISTING
PANEL
'DPEC'
EXISTING
PANEL
'GBEP'
EXISTING SITE
LIGHTING
PANEL
EXISTING
FEEDER TO
BLDG 69
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
800AT
800AF
2,500AT
2,500AF
2,500AT
2,500AF
225A/3P 400A/3P
EXISTING-TO-REMAIN
'ATS' SWITCHBOARD
EXISTING
FEEDER TO
BLDG 116
75 75
FUTURE
XFMR
'XAD'
A
/3 P
V F
D
A
/3 P
/4 A
FUTURE
A
/3 P
NEW
XFMR
'XAD'
A
/3 P
V F
D
A
/3 P
/4 A
NEW
A
/3 P
T750P
480:208 750kVA
XFMR
NEW 750kW
208/120VSKID-MOUNTED
ENGINE GENERATOR SET
,0
A
L U
G S
,0
A
/3 P
TO
LOAD
BANK
SPD SPD
1,200A, 480V
GENERATOR
QUICK-CONNECT TAP
BOX - NEMA 3R
ENCLOSURE, PAD
MOUNTED OR
MOUNTED ON A
UNISTRUT FRAME.
NEW 3,000A
MANUAL
TRANSFER
SWITCHBOARD
3,000AT
3,000AF
K
3,000AT
3,000AF
K
3000T750S
,0
A
M L O
EXTERIOR PAD - SEE
DETAIL E4/S-301.
GENERATOR PAD -
SEE DETAIL C1 &
E1/S-301.
INTERIOR
HOUSEKEEPING PAD
- SEE DETAIL
D4/S-301.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :0
P
M
ES-601
ELECTRICAL RISER DIAGRAM & SCHEDULES
MAY 14, 2021 WSP TED
BID DOCUMENTS
SCALE: NOT TO SCALEF1
ELECTRICAL RISER DIAGRAM
FEEDER SCHEDULE
FEEDER TAG COPPER FEEDER
20 4#12 & 1#12G, 1/2"C.
25 4#10 & 1#10G, 3/4"C.
30 4#10 & 1#10G, 3/4"C.
35 4#8 & 1#10G, 1"C.
40 4#8 & 1#10G, 1"C.
45 4#6 & 1#10G, 1"C.
50 4#6 & 1#10G, 1"C.
60 4#4 & 1#10G, 1-1/4"C.
70 4#4 & 1#8G, 1-1/4"C.
80 4#2 & 1#8G, 1-1/2"C.
90 4#2 & 1#8G, 1-1/2"C.
100 4#1 & 1#8G, 2"C.
110 4#1 & 1#6G, 2"C.
125 4#1 & 1#6G, 2"C.
150 4-1/0 & 1#6G, 2"C.
175 4-2/0 & 1#6G, 2"C.
200 4-3/0 & 1#6G, 2-1/2"C.
225 4-4/0 & 1#4G, 2-1/2"C.
250 4-250 KCMIL & 1#4G, 3"C.
300 4-350 KCMIL & 1#4G, 3"C.
350 4-500 KCMIL & 1#2G, 4"C.
400 4-500 KCMIL & 1#2G, 4"C.
450 TWO 2-1/2-INCH CONDUITS, EACH
WITH FOUR 4/0 AND ONE #2G
500 TWO 3-INCH CONDUITS, EACH WITH
FOUR 250 KCMIL AND ONE #2G
600 TWO 3-INCH CONDUITS, EACH WITH
FOUR 350 KCMIL AND ONE #1G
700 TWO 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
800 TWO 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
1000 THREE 4-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 2/0G
1200 FOUR 3-INCH CONDUITS, EACH WITH
FOUR 350 KCMIL AND ONE 3/0G
1600 FIVE 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 4/0G
2000 SIX 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 250KCMIL G
2500 SEVEN 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 350KCMIL G
3000 NINE 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 350KCMIL G
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
TRANSFORMER FEEDER SCHEDULE
FEEDER
TAG PRIMARY FEEDER
FEEDER
TAG SECONDARY FEEDER
GROUNDING
ELECTRODE
CONDUCTOR
T15P 3#10 & 1#10G, 1/2"C. T15S 4#6 & 1#10G, 1"C. #8G
T30P 3#6 & 1#10G, 3/4"C. T30S 4#1 & 1#8G, 1-1/2"C. #6G
T45P 3#4 & 1#8G, 1"C. T45S 4-1/0 & 1#6G, 2"C. #6G
T75P 3#1 & 1#6G, 1-1/2"C. T75S 4-250 KCMIL & 1#4G, 2-1/2"C. #2G
T112.5P 3-2/0 & 1#6G, 2"C. T112.5S 4-500 KCMIL & 1#2G, 3"C. 1/0G
T150P 3-4/0 & 1#4G, 2"C. T150S TWO 2-1/2-INCH CONDUITS, EACH
WITH FOUR 250 KCMIL AND ONE #2G
1/0G
T225P 3-500 KCMIL & 1#2G, 3"C. T225S TWO 3-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 1/0G
2/0G
T300P TWO 2-INCH CONDUITS, EACH WITH
THREE 4/0 AND ONE #2G
T300S THREE 3-1/2-INCH CONDUITS, EACH
WITH FOUR 500 KCMIL AND ONE 2/0G
4/0G
T500P TWO 3-INCH CONDUITS, EACH WITH
THREE 500 KCMIL AND ONE 1/0G
T500S FIVE 3-1/2-INCH CONDUITS, EACH WITH
FOUR 500 KCMIL AND ONE 250 KCMIL G
350 KCMIL G
T750P FOUR 3-INCH CONDUITS, EACH
WITH THREE 350 KCMIL AND ONE
3/0G
T750S EIGHT 3-1/2-INCH CONDUITS, EACH
WITH FOUR 500 KCMIL AND ONE 3/0 G
350 KCMIL G
KEYNOTES:
1. PROVIDE KEY INTERLOCK BETWEEN GENERATOR (PRIMARY) SOURCE AND
GENERATOR QUICK CONNECTION (ALTERNATE SOURCE) TO PREVENT
INADVERTENT CONNECTION OF BOTH SOURCES TO THE TRANSFER
SWITCH. PROVIDE KEY LOCKS FOR EACH DISCONNECT WITH ONLY ONE
KEY. INSERT KEY INTO THE PRIMARY SOURCE LOCK TO ALLOW IT TO BE
CLOSED AND THE GENERATOR TO FEED THE AUTOMATIC TRANSFER
SWITCH. THE KEY SHALL BECOME CAPTIVE WHILE THIS SWITCH IS CLOSED
AND CAN ONLY BE RELEASED BY OPENING THE SWITCH. IN ORDER TO
CONNECT THE TEMPORARY GENERATOR, THE KEY SHALL BE REMOVED
FROM THE PRIMARY SWITCH. THE KEY SHALL THEN BE INSERTED INTO
THE LOCK OF THE ALTERNATE SOURCE DISCONNECT SWITCH. THE KEY
SHALL REMAIN CAPTIVE WHILE ALTERNATE SOURCE DISCONNECT SWITCH
IS CLOSED.
SCALE: NOT TO SCALE SCALE: NOT TO SCALE
MIN. 20'
MIN 2"
2"
4"
1" 1" 1"2"
1 1/2" TYP
1" 5/8"
2'-0" MIN
N
NEW MAIN ELECTRICAL
ROOM GROUND BAR. SEE
DETAIL B4/ES-602.
EXISTING SYSTEM BONDING
JUMPER
EXISTING SWITCHBOARD
'ATS' GROUND BUS
REMOVABLE LINK
MAIN BONDING JUMPER
EXISTING SWITCHBOARD
'ATS' NEUTRAL BUS
EXISTING SWITCHBOARD
'ATS'CONTINUOUS GROUNDING
ELECTRODE CONDUCTOR; 1
#4/0 IN 1" METAL CONDUIT.
UNSPLICED GROUNDING
ELECTRODE CONDUCTOR
SHALL TERMINATE AT
GROUND RING.
EQUIPMENT BONDING
JUMPER (TYPICAL)
EXOTHERMIC WELD
(TYPICAL)
MAIN ELECTRICAL ROOM
GROUND RING (SEE SHEET
ES-101 FOR LOCATION)
GROUND RING; NOT LESS
THAN #2 AWG BARE
COPPER (TYPICAL)
GROUND ROD (TYPICAL)
E X
P O
S E
D I N
T E
R
IO
R S
T R
U C
T U
R A
L S
T E
E L
EXISTING SERVICE
TRANSFORMER
EXISTING GROUNDED
SERVICE CONDUCTOR.
GROUNDING ELECTRODE
CONDUCTOR (SUPPLY SIDE
BONDING JUMPER); 1 #4/0 IN
1" METAL CONDUIT
NEW GENERATOR
METAL CONDUITS
NOT
ELECTRICALLY
CONTINUOUS
SHALL HAVE
JUMPER (TYPICAL)
FOUNDATION IN DIRECT
CONTACT WITH EARTH
#4 AWG OR LARGER
BARE COPPER
CONDUCTOR OR STEEL
REINFORCING BAR OR
ROD NOT LESS THAN 1/2"
DIAMETER
EXOTHERMIC WELD
EXISTING GROUNDING
ELECTRODE
CONCRETE-ENCASED GROUNDING ELECTRODE
(UFER GROUND)
PROVIDE A CONCRETE ENCASED GROUNDING
ELECTRODE AND SUPPLEMENTAL ELECTRODES IN
ACCORDANCE WITH NFPA 70 ARTICLE 250.52(3) TO
PROVIDE A GROUNDING RESISTANCE OF 25 OHMS OR
LESS. ALL GROUND CONNECTIONS TO CONCRETE
ENCASED ELECTRODE SHALL REMAIN ACCESSIBLE.
1 #6 IN METAL CONDUIT
EXISTING
FIRE ALARM
CONTROL
PANEL
BONDING JUMPER; 1 #4/0 IN
1" METAL CONDUIT
GROUND ROD
EXOTHERMIC WELD
GROUNDING ELECTRODE
CONDUCTOR; 1 #4/0 IN 1"
METAL CONDUIT. (TYPICAL)
GROUND RING
PROVIDE A GROUND RING TO PROVIDE A GROUNDING
RESISTANCE OF 25 OHMS OR LESS IN ACCORDANCE
WITH NFPA 70 ARTICLE 250.52(4). ALL GROUND
CONNECTIONS TO GROUND RINGS SHALL REMAIN
ACCESSIBLE. GROUND RODS SHALL BE NO LESS THAN 6'
APART AND NO LESS THAN 30" BELOW GRADE. PROVIDE
TEST WELLS WHERE INDICATED ON THE DRAWINGS.
WATER PIPE GROUNDING ELECTRODE
PROVIDE A GROUNDING ELECTRODE
CONNECTION IN ACCORDANCE WITH NFPA 70
ARTICLE 250.52(1) TO A METAL
UNDERGROUND WATER PIPE. CONNECTION
SHALL BE MADE WITH A GROUND CLAMP
WITHIN 5' OF WATER PIPE ENTRANCE INTO
BUILDING AND AHEAD OF ANY VALVE,
CONNECTOR, OR METERING DEVICE. TO
MAINTAIN 10' OF ELECTRICAL CONTINUITY OF
UNDERGROUND WATER PIPE ELECTRODE,
PROVIDE BONDING JUMPERS AROUND
INSULATED JOINTS, FILTERING DEVICE AND
METERING EQUIPMENT. SIZE BONDING
JUMPER IN ACCORDANCE WITH NFPA 70
TABLE 250.12(C)(1).
METAL SUPPORT STRUCTURE GROUNDING ELECTRODE
PROVIDE A GROUNDING ELECTRODE CONNECTION TO
EXPOSED STRUCTURAL STEEL IN ACCORDANCE WITH
NFPA 70 ARTICLE 250.52(2). SIZE BONDING JUMPER IN
ACCORDANCE WITH NFPA 70 TABLE 250.102(C)(1).
EXOTHERMIC WELD TO
GROUND ROD (TYPICAL)
GROUNDING ELECTRODE
CONDUCTOR; 1 #4/0 IN 1"
METAL CONDUIT
B1
DRY-TYPE TRANSFORMER GROUNDING DETAIL
1/4" DIAMETER
MOUNTING HOLES
(TYPICAL OF 4)
BASE CLAMP/
BRACKET
3/8" DIAMETER HOLE
(TYPICAL OF 6)
3/8" x 5/8" HEX
HEAD BOLT
3/8" LOCK WASHER & 3/8"
FLAT WASHER
3/8" FLAT WASHER &
3/8" LOCK WASHER
1/4" THICK
COPPER BAR
1/4" DIAMETER HOLE
(TYPICAL OF 8)
GENERAL NOTES:
1. ALL HARDWARE SHALL BE STAINLESS
STEEL.
2. PROVIDE 1 MOUNTING POINT PER 12" OF
BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
SECTION
STEEL EXPANSION
ANCHOR
INSULATOR
1/4" THICK COPPER BAR
3/8" x 5/8" HEX
HEAD BOLT
B4
GROUND BAR DETAIL
PROVIDE GROUNDING
ELECTRODE CONDUCTOR
TO GENERATOR QUICK
CONNECT TAP BOX; 1 #4/0
IN 1" NONMETALLIC
CONDUIT
FLOOR LEVEL
4 WIRES
H2 X3 H1
5 WIRES
X0 X2 H3 X1
TYPICAL PANELBOARD
A B C
A B C
MAIN
BREAKER
NOTES
1. TRANSFORMER BONDING STRAP, IF NOT PROVIDED BY
THE TRANSFORMER MANUFACTURER, SHALL BE THE
SAME SIZE AS THE SYSTEM BONDING JUMPER IN
ACCORDANCE WITH NFPA 70, TABLE 250.102(C)(1).
2. PROVIDE A BONDING BUSHING AND EQUIPMENT BONDING
JUMPER AT THE CONDUIT TERMINATION. JUMPER SHALL
BE THE SAME SIZE AS THE GROUNDING ELECTRODE
CONDUCTOR CONTAINED IN THE CONDUIT.
3. PROVIDE A BONDING CLAMP AT THE TERMINATION OF
THE GROUNDING ELECTRODE CONDUCTOR TO THE
ELECTRODE.
BOND GROUNDING ELECTRODE TO THE
NEAREST ELECTRICAL RISER GROUND BAR,
THE STEEL FRAME OF THE BUILDING WHERE
PROVEN TO BE SUITABLY GROUNDED OR TO
THE METALLIC WATER PIPE WITHIN 5' FROM
THE POINT OF ENTRANCE INTO THE
BUILDING (NFPA 70 ARTICLE 250-30(A)).
TRANSFORMER
WINDING
FROM
TRANSFORMER
PRIMARY
SOURCE
GROUND BUS
GROUND BUS
BONDED TO
ENCLOSURE
BONDING BUSHING
WITH BONDING
JUMPER
NEUTRAL BUS
INSULATED FROM
PANEL
NEUTRAL (WHITE)
CONCRETE
HOUSEKEEPING PAD
GROUND PAD
SYSTEM BONDING
JUMPER
EQUIPMENT
BONDING JUMPER
BOND EXHAUST FLUE TO
LIGHTNING PROTECTION
ROOF CONDUCTOR WITH UL
LISTED PIPE BONDING CLAMP
EXISTING CLASS I ROOF
LIGHTNING PROTECTION
CONDUCTOR
NEW EXHAUST FLUE -
SPECIFIED IN DIVISION 23
CLASS I BONDING
CONDUCTOR - SIZED IN
ACCORDANCE WITH
NFPA-780, 2020 EDITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :1
P
M
ES-602
ELECTRICAL GROUNDING RISER DIAGRAM &
DETAILS
MAY 14, 2021 WSP TED
BID DOCUMENTS
SCALE: NOT TO SCALEF5
GROUNDING RISER DIAGRAM
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
SCALE: NOT TO SCALEF1
GENERATOR EXHAUST FLUE GROUNDING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :1
P
M
ES-611
ELECTRICAL LUMINAIRE & EQUIPMENT
SCHEDULES
MAY 14, 2021 WSP TED
BID DOCUMENTS
LUMINAIRE SCHEDULE
FIXTURE DESCRIPTION LAMP
NOMINAL
LUMENS CRI CCT VOLTAGE WATTAGE MOUNTING MANUFACTURER NOTES
F 4' UTILITY STRIP LUMINAIRE WITH
WHITE FINISH. PROVIDE CHAIN
HANGERS AND WIRE GUARD.
LED 4000 80+ 4000 K 120 V 31 W PENDANT MOUNT 11'-0" AFF TO BOTTOM
OF FIXTURE, UNLESS OTHERWISE NOTED
DAY-BRITE - FSS
EATON METALUX - SNLED
COLUMBIA - LCL
FE SAME AS TYPE 'F' EXCEPT WITH
EMERGENCY BATTERY BACKUP
LED 4000 80+ 4000 K 120 V 31 W
O WALL PACK LED 9000 80+ 4000 K 120 V 72 W WALL MOUNT AT EXISTING LUMINAIRE
OUTLET BOX, UNLESS OTHERWISE NOTED
PHILIPS STONCO - WPM
EATON LUMARK - WP
HUBBELL OUTDOOR - WGH
X EXIT SIGN WITH EMERGENCY
BATTERY BACKUP
LED N/A 80+ N/A 120 V 5 W WALL/CEILING, AS INDICATED ON THE
DRAWINGS
CHLORIDE LIGHTING - 55L
DUAL LITE - SE
EMERGI-LITE - PRESTIGE
HE WILLIAMS - EXIT
LIGHTALARMS - GALAXY
SURE-LITES - CX
NOTES:
1. WIRE EXIT SIGNS AHEAD OF ALL LOCAL SWITCHING.
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
MECHANICAL EQUIPMENT SCHEDULE
UNIT VOLTAGE
NUMBER
OF POLES KVA MCA HP STARTER DISCONNECT FEEDER SIZE PANEL CIRCUIT LOCATION NOTES
DAY TANK 120 V 1 0.86 kVA 9 A 1/3 BY DIVISION 22 N/A 2#12 & 1#12G - 3/4"C GBEP 7 EMERGENCY GENERATOR 200 1
NOTES:
1. ALL CONDUCTORS FOR MECHANICAL EQUIPMENT SHALL BE COPPER.
30" 30" 30"
90"
91.5"
MAGNUM ATS
EMERGENCY MAIN NORMAL MAIN
4 POLE
B6 EXISTING ATS SWITCHBOARD ELEVATION
SCALE: NOT TO SCALE
MAGNUM ATS
4 POLE
MAGNUM ATS
4 POLE
D6 NEW MANUAL TRANSFER SWITCHBOARD ELEVATION
SCALE: NOT TO SCALE
ERMS
K1
ERMS
K1
SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7
DETAILED ELEVATION BASED
ON SQUARE D. WORST CASE
EQUIPMENT DIMENSIONS ARE
110" X 38" X 91.5".
OPEN OPEN
TRIP CLOSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
NON SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
REPLACE 750kW EMERGENCY
GENERATOR BUILDING 116
VAMC MOUNTAIN HOME, TN
621-19-123
B
IM
/1
V
A
-1
-1
B ld g
G e n e ra to r/
V
A B ld g M
E P
F
P v .r v t
/1
/2
:3 :1
P
M
ES-621
ELECTRICAL SWITCHBOARD SCHEDULES &
ELEVATIONS
MAY 14, 2021 WSP TED
BID DOCUMENTS
SHEET NOTES:
1. REFER TO ES-001 & ES-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
EXISTING SWITCHBOARD
'ATS'
A ARC-FAULT CIRCUIT INTERRUPTOR (AFCI)
G GROUND FAULT CIRCUIT INTERRUPTOR (GFCI)
H PROVIDE RED CIRCUIT BREAKER WITH HANDLE
CLAMP DEVICE
S SHUNT TRIP BREAKER
E EXISTING-TO-REMAIN
N NEW BREAKER IN EXISTING SPACE
M PROVIDE CT FOR METERING SYSTEM AND CONNECT
TO METER INDICATED ON THE METERING SCHEDULE
PANELBOARD SCHEDULE NOTE LEGEND:
NEW MANUAL TRANSFER
SWITCHBOARD
1. EXISTING-TO-REMAIN EATON AUTOMATIC TRANSFER SWITCHBOARD (GO# LAT0006321-001).
2. PROVIDE NEW TYPE 1 INTERNAL SURGE PROTECTIVE DEVICE. 7X CHASSIS MOUNTED SPD UNIT - SPD SERIES 250kA SPD, POWER XPERT SPD WITH SURGE COUNTER (DISCONNECT
INCLUDED). SPD CAT# SPD250208Y4C
NOTES:
15 EXISTING MAIN CIRCUIT BREAKER (UTILITY) 3 2500 A 2500 A 0.00 kVA SECTION 7
14 NEW SPD (N) 3 60 A 60 A 0.00 kVA SECTION 6
13 EXISTING SPACE -- -- -- 0.00 kVA --
12 EXISTING BUILDING 69 3 400 A 400 A 0.00 kVA SECTION 6
11 EXISTING PANEL 'DPEC' ATS (E) 3 800 A 800 A 0.00 kVA SECTION 5
10 EXISTING PANEL 'DPEC' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 4
9 EXISTING PANEL 'DPELS' ATS (E) 3 800 A 800 A 0.00 kVA SECTION 4
8 EXISTING PANEL 'DPELS' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 4
7 EXISTING PANEL 'DPEE' ATS (E) 3 800 A 800 A 10.47 kVA SECTION 3
6 EXISTING PANEL 'DPEE' ATS (N) 3 800 A 800 A 0.00 kVA SECTION 3
5 EXISTING SPACE -- -- -- 0.00 kVA --
4 NEW SPD (E) 3 60 A 60 A 0.00 kVA SECTION 2
3 EXISTING SPACE -- -- -- 0.00 kVA --
2 EXISTING BUILDING 116 3 225 A 225 A 0.00 kVA SECTION 2
1 EXISTING MAIN CIRCUIT BREAKER (EMERGENCY) 3 2500 A 2500 A 0.00 kVA SECTION 1
CKT CIRCUIT DESCRIPTION # OF POLES FRAME SIZE TRIP RATING LOAD REMARKS
ENCLOSURE: NEMA 1
MOUNTING: FLOOR WIRES: 4 MAINS RATING: 2500 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: 2500 A MCB
LOCATION: ELECTRICAL 100 VOLTS: 208Y/120 A.I.C. RATING: 65,000 A
EXISTING SWITCHBOARD: ATS
1. EATON…
This is the start of the file's text. The full file is on GovTribe.