DRAWINGS
11 MB Posted
- Attached to
- WEST TOWN SCHOOL HVAC AND PLUMBING UPGRADES
- Solicitation number
- 22-FAC-017
- Issued by
- Douglas County, Georgia
About this file
This file contains architectural and engineering drawings for the West Town Elementary School HVAC and Plumbing Upgrades project located at 1113 University Street, Albany, Georgia. The project includes comprehensive replacement of heating, ventilation, air conditioning systems, and plumbing fixtures across three buildings (3000, 3010, and 3020) at the school campus. The scope encompasses demolition of existing mechanical equipment including wall-hung heat pumps, rooftop units, fan coil units, exhaust fans, and associated ductwork, followed by installation of new equipment including Carrier rooftop packaged units, Bard wall-hung heat pumps, Greenheck exhaust fans, ductless fan coil units, air handling units, ceiling heaters, and packaged terminal heat pumps. The project is organized into four construction phases designed to maintain occupancy of the school during renovation. Plumbing work includes replacement of water closets, urinals, lavatories, sinks, water coolers, and associated fixtures throughout the buildings. Electrical work involves disconnecting and reconnecting power circuits to all mechanical equipment, with existing panels retained for reuse. The drawings include mechanical demolition plans, new work plans, equipment schedules detailing capacities and specifications, piping and ductwork details, and general notes addressing contractor responsibilities including refrigerant recovery from existing R-22 systems.
The project involves extensive coordination requirements including field verification of existing conditions, temporary wall installation to separate work areas from occupied student spaces, coordination with utility companies for temporary power service to modular classroom units, protection of existing data, fire alarm, intercom, and security systems, and careful sequencing to avoid conflicts with structural members and other building systems. The contractor must provide modular classroom units to house displaced students during each construction phase, with no more than eight classrooms relocated per phase. Temporary domestic cold water piping connections are required for the modular units. Equipment removal includes recovery of R-22 refrigerant with cylinders returned to the owner for processing, and salvage of existing bipolar ionization units for reinstallation in new equipment. The project specifications reference standard SMACNA construction details for ductwork, ASHRAE 62.1 indoor air quality procedures for outdoor air requirements, and manufacturer installation instructions for all equipment. Cost details, bid dates, contract award dates, and project timeline information are not included in this drawing set.
Text of this file
D A
D E
BLECKLEY LAURENS
CHATHAM
EFFINGHAM
IRWIN
BERRIEN
LOWNDESGRADY
SE
MI
NO
LE
DECATUR
EARLY
MILLER
BAKER
THOMAS
BROOKS
COLQUITT
MITCHELL
COOK
TIFT
SCHLEY
TERRELL
DOUGHERTY
WEBSTER
RANDOLPH
QUITMAN
CLAY
CALHOUN
CHATTAHOOCHEE
STEWART
MARION
WILCOX
CRISP
WORTH
LEE
TURNER
DOOLY
MACON
SUMTER
HOUSTON
PULASKI
McINTOSH
PIERCE
CHARLTON
LA
NIE
R
CLINCH
ECHOLS
ATKINSON
WARE
CAMDEN
BRANTLEY
GLYNN
TOOMBS
APPLING
COFFEE
BEN HILL
TELFAIR
DAVIS
JEFF
WHEELER
DODGE
TREUTLEN
M
ON
TG
OM
ER
Y
LONG
WAYNE
LIBERTY
BULLOCH
EVANS
CANDLER
TATTNALL
BRYAN
DAWSON FRANKLIN
CLARKE
OCONEE
PUTNAM
BALDWIN
TWIGGS
HENRY
FA
YE
TT
E
PIKE
UPSON
SPALDING
M
ER
IW
ET
HER
HARRIS
MUSCOGEE
TALBOT
COWETA
HEARD
TROUP
PEACH
CRAWFORD
TAYLOR
BIBB
MONROE
LAMAR
BUTTS
JASPER
JONES
CHEROKEE
FULTON
PAULDING
HARALSON
CARROLL
DOUGLAS
BARTOWFLOYD
POLK
COBB
NEWTON
DEKALB
CL
AY
TO
N
ROCKD
AL
E
WALTON
MORGAN
GWINNETT
FORSYTH
JACKSON
HALL BANKS
BARROW
M cD
U F
FI
E
JEFFERSON
EMANUEL
WASHINGTON
WILKINSON
JOHNSON
HANCOCK
WARREN
GLASCOCK
JENKINS
SCREVEN
RICHMOND
BURKE
COLUMBIA
OGLETHORPE
WILKES
TALIAFERROGREENE
LINCOLN
ELBERT
HART
MADISON
RABUN
STEPHENS
FANNIN
PICKENS
GILMER
WHITF
IELD
GORDON
C H
AT
TO
O G
A
WALKER M
U
R R
AY
CATOOSA
UNION
LUMPKIN
WHITE
HABERSHAM
TOWNS
BACON
DOUGHERTY
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION
GA DOE ID #: 5062
T100
TITLE SHEET
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
WEST TOWN ELEMENTARY SCHOOL - HVAC &
PLUMBING UPGRADES
1113 UNIVERSITY ST, ALBANY, GA 31707
T100 TITLE SHEET
C100 SITE PLAN
A100 CONSTRUCTION PHASING PLAN
A200 ARCHITECTURAL CEILING PLAN - OVERALL
MD100 MECHANICAL DEMO PLAN - OVERALL
MD101 MECHANICAL DEMO PLAN - BUILDING 3000
MD102 MECHANICAL DEMO PLAN - BUILDING 3010 & 3020
M100 MECHANICAL NEW WORK PLAN - OVERALL
M101 MECHANICAL NEW WORK PLAN - BUILDING 3000
M102 MECHANICAL NEW WORK PLAN - BUILDING 3010 & 3020
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES
P101 PLUMBING FLOOR PLAN - BUILDING 3000
P102 PLUMBING FLOOR PLANS - BUILDING 3010 & 3020
E001 ELECTRICAL OVERALL PLAN
ED101 ELECTRICAL DEMOLITION PLAN - BUILDING 3000
ED102 ELECTRICAL DEMOLITION PLAN - BUILDING 3010 & 3020
E201 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3000
E202 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3010 & 3020
E801 ELECTRICAL SCHEDULES AND LEGEND
No. Description Date
GA DOE ID#: 5062
U N
IV
E
R S
IT
Y
S T
U N
IV
E
R S
IT
Y
S T
TEMPORARY PORTABLE CLASSROOM
TEMPORARY PORTABLE CLASSROOM
GENERAL NOTE: LOCATIONS OF CLASSROOM TRAILERS IS
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF
EXISTING STORM DRAINS, FENCING, SIDEWALKS, PLAYGROUNDS,
DRIVES, ETC. AND CAREFULLY COORDINATE PLACEMENT OF
CLASSROOMS TO AVOID CONFLICT AND MAINTAIN REQUIRED
CLEARANCES.
EXISTING PLAYGROUND
EXISTING PLAYGROUND
EXISTING PLAYGROUND
2" DCW 2" DCW
D C
W
1 1/2" DCW
1 1/2" DCW
1 1/2" DCW
1 1/2" DCW
1 1/2" DCW
CONTRACTOR SHALL COORDINATE WITH OWNER FOR
TEMPORARY CONNECTION OF 2" DOMESTIC COLD WATER
PIPING TO EXISTING IN THIS APPROXIMATE LOCATION.
EXISTING COVERED W
ALKW
AY
EXISTING COVERED WALKWAY
EXISTING PAVED PARKING LOT
E X
IS
T
IN
G
C O
V E
R E
D
W A
L K
W A
Y
EXISTING COVERED
WALKWAY
EXISTING CONCRETE PAD
EXISTING TREE
EXISTING TREE
D C
W
D C
W
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
C101
SITE PLAN
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
04/22/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/16" = 1'-0"1 SITE PLAN
PHASE 2
PHASE 1
PHASE 3
PHASE 4
PHASE 1
PHASE 1
PHASE 2
1(TYP.)
MUSIC
PRODUCTION
A.V. STOR.
MEDIA
OFFICE
WORK RM.
MEETING
ART
ART STOR.
KILN
K-1 CLASSROOM
K-1 CLASSROOMK-1 CLASSROOM
K-1 CLASSROOM
P.E. STOR.
STOR.
BOYS
GIRLS
JAN.
TLT.
TLT.
TEACHER TLT.
TLT.
TLT.
IDF
Room
DRY STOR.
OFFICE
KITCHEN
DISHWASH
CAFETERIA
COPIER & SUPPLY
DRESSING
OFFICE
PRINCIPAL
OFFICE
WORK ROOM
VAULT
MECH.
TLT.
K-1 CLASSROOM
BOOK STOR. PARENT CENTER BOOK STOR.
3RD CLASSROOMK COMPUTER LAB
1ST CLASSROOM 3RD CLASSROOM
3RD CLASSROOM
1ST CLASSROOM
1ST CLASSROOM
4TH CLASSROOM
COUNSELOR
COUNSELOR
ASSIST. PRINCIPAL
WAITING
1ST CLASSROOM
1ST CLASSROOM
2ND CLASSROOM
2ND CLASSROOM
2ND CLASSROOM
2ND CLASSROOM 5TH CLASSROOM 5TH CLASSROOM
5TH CLASSROOM
5TH CLASSROOM2ND CLASSROOM
READING
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED. SPECIAL ED.
4TH COMPUTER LAB
4TH CLASSROOM
4TH CLASSROOM
WORK RM.
TESTING
STOR.WORK RM.JAN. STOR.
GIRLS TLT GIRLS TLT.
BOYS TLT.
BOYS TLT.
JAN.
ELEC. LOBBY
STAGE
P.E. OFFICE
BOYS TLT.
GIRLS TLT.
STOR. EXTENDED DAY
UTILITY CLOSET
FOYER
GYM
TLT.Room
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
A100
CONSTRUCTION PHASING
PLAN
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
04/22/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/16" = 1'-0"1 CONSTRUCTION PHASING PLAN
1 . ADJUST TEMPORARY WALLS AS REQUIRED TO MAINTAIN SEPARATION FROM
WORK AREAS AND OCCUPIED STUDENT AREAS. ACCESS TO EXIT DOORS SHALL
BE MAINTAINED AT ALL TIMES.
2 . PROVIDE TEMPORARY WALL (MIN 6' TALL) TO SEPARATE WORK AREAS FROM
OCCUPIED AREAS BASED ON PHASING. PROVIDE DOORS AS REQUIRED FOR
ACCESS TO WORK AREA. PROVIDE PROTECTION FOR EXISTING FLOORING,
WALLS, ETC. TO PREVENT DAMAGE TO EXISTING ITEMS DURING INSTALLATION /
REMOVAL OF TEMPORARY WALL.
3 . ADJUST TEMPORARY WALLS AS REQUIRED TO ALLOW ACCESS TO RESTROOMS
WHILE MAINTAINING SEPARATION OF WORK AREAS FROM OCCUPIED STUDENT
AREAS.
NOTES: (THIS SHEET ONLY)
GENERAL NOTE: THERE WILL BE 4 MODULAR CLASSROOM BUILDINGS WITH (2) CLASSROOMS PER MODULAR UNIT ON THIS SITE PROVIDED BY THE CONTRACTOR. NO MORE THAN 8 CLASSROOMS MAY BE MOVED TO MODULAR UNITS FOR
EACH PHASE. PHASES SHOWN HEREIN ARE SUGGESTED PHASES AND MAY BE CHANGED DUE TO CONSTRUCTION TIMELINES, CONSTRUCTION SCHEDULES, EQUIPMENT LEAD TIMES, UNFORESEEN CIRCUMSTANCES ENCOUNTERED
DURING THE CONSTRUCTION PROCESS OR FURTHER COORDINATION WITH OWNER. VERIFY ALL PHASING, TEMPORARY
WALL/PARTITION INSTALLATION AND/OR SCHEDULING PRIOR TO COMMENCEMENT OF WORK.
No. Description Date
GENERAL NOTE: PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE WITH OWNER TO REMOVE ALL PERSONAL ITEMS FROM SPACES AFFECTED BY DEMOLITION. CONTRACTOR SHALL PROTECT EXISTING CASEWORK, FURNITURE, FLOORING, WALLS, CEILINGS, ETC. NOT ABLE TO BE REMOVED. AT THE END OF CONSTRUCTION, CONTRACTOR SHALL REMOVE ALL PROTECTIVE COVERS AND WIPE DOWN AND CLEAN ALL SURFACES AFFECTED BY
DUST, DIRT, CONSTRUCTION DEBRIS, ETC.
GENERAL NOTE: REMOVAL OF CEILINGS REQUIRED FOR REMOVAL OF
EXISTING EXHAUST FANS LOCATED ABOVE RESTROOMS NOT SHOWN.
SEE MECHANICAL DRAWINGS FOR LOCATIONS OF ITEMS LOCATED
ABOVE CEILINGS THAT MAY REQUIRE REMOVAL OF CEILING TILES.
DEMO EXISTING CEILING TILE &
GRID AS REQUIRED AND REPLACE
WITH NEW CEILING TILE & GRID
DEMO EXISTING CEILING TILE &
REPLACE WITH NEW CEILING TILE
CEILING HATCH LEGEND
(NO HATCH) EXISTING CEILING TILE
& GRID TO REMAIN
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
A200
ARCHITECTURAL CEILING
PLAN - OVERALL
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
3/32" = 1'-0"1 ARCHITECTURAL CEILING PLAN - OVERALL
MD101
MD102
MD102
TOILETS
ADDED?
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
MD100
MECHANICAL DEMO PLAN -
OVERALL
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
3/32" = 1'-0"1 MECHANICAL DEMO PLAN - OVERALL
1 1
6 6
15 4 4
4 4
3 3 3 3 3 3 3 3 3
33333333
3RD CLASSROOM
4TH CLASSROOM 4TH CLASSROOM 4TH CLASSROOM 4TH COMPUTER LAB 5TH CLASSROOM 5TH CLASSROOM
5TH CLASSROOM5TH CLASSROOM
2ND CLASSROOM 2ND CLASSROOM
2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM
K-1 CLASSROOM
KITCHENDISHWASH
DRY STOR.
OFFICE
CAFETERIA
STAGE
COPIER & SUPPLY
DRESSING
OFFICE
WORK ROOM
PRINCIPAL
VAULT
OFFICE
LOBBY
ASSIST. PRINCIPAL
WAITING
COUNSELOR
COUNSELOR
3RD CLASSROOM
K COMPUTER LAB 1ST CLASSROOM
3RD CLASSROOM
BOYS TLT.
GIRLS TLT
WORK RM.
JAN. STOR.
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED.
SPECIAL ED.
READING
STOR.
BOYS TLT.
GIRLS TLT.
WORK RM. TESTING
9 9
MECH.
Room
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
MD101
MECHANICAL DEMO PLAN -
BUILDING 3000
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3000
NOTES: (THIS SHEET ONLY)
10 . REMOVE EXISTING RANGE HOOD EXHAUST FAN ON ROOF.
11 . EXISTING KITCHEN RANGE HOOD TOO REMAIN.
12 . REMOVE EXISTING UNIT HEATER.
13 . REMOVE EXISTING DUCT HEATER. SEE ELECTRICAL DRAWINGS FOR CIRCUIT DEMO.
14 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF APPLICABLE.
15 . REMOVE EXISTING ROOFTOP AIR CONDITIONER CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL. SALVAGE BIPOLAR
IONIZATION UNIT AND TURN OVER TO OWNER.
16 . REMOVE EXISTING EXISTNG DUCTWORK. GRILLES TO REMAIN FOR RESUSE.
17 . EXISTING DISHWASHE EXHAUST FAN TO REMAIN.
18 . REMOVE EXISTING DUCTWORK AND GRILLES BACK TO SCOPE OF WORK SYMBOL. PATCH AND SEAL OPENING IN DUCT AIR TIGHT.
REINSULATE AS NEEDED.
19 . REMOVE EXISTING ROOF VENTILATOR TO REMAIN. CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL.
20 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK, SUPPORTS, AND ELECTRICAL CIRCUIT.
1 . REMOVING EXISTING CEILING HEATER.
2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF WORK SYMBOL.
3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT
FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
4 . REMOVE EXISTING ROOFTOP PACKAGE UNIT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP SAME LOCATION. SEE NEW WORK DRAWINGS FROM REPLACEMENT OF UNIT.
5 . REMOVE EXISTING HEAT PUMP ON ROOF FROM THIS APPROXIMATE LOCATION. REMOVE ANY ASSOCIATED REFRIGERANT PIPES (ON ROOF AND INSIDE BUILDING). EQUIPMENT SUPPORT RAILS TO REMAIN FOR REUSE. ROOF PIPE BOX SHALL DEMOED AND ROOF
OPENING WILL BE USED FOR A NEW PIPE BOX. SEE NEW WORK DRAWINGS FOR PIPE BOX
6 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.
7 . EXISTING ROOF VENTILATOR TO REMAIN.
8 . REMOVE EXISTING RANGE HOOD SUPPLY FAN ON ROOF.
9 . REMOVE EXISTING AIR HANDLING UNIT FROM THIS APPROXIMATE LOCATION. REMOVE EXISTING SUPPLY AND RETURN DUCT FROM AIR HANDLING UNIT UP TO THE SCOPE OF WORK SYMBOL. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW WORK DRAWING FOR NEW AIR HANDLING UNIT AND DUCTWORK.
No. Description Date
GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF
WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL
UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING
WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).
CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT
REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY
CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS
HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR
PROCESSING.
TT TT
P.E. OFFICE
GYM
FOYER
BOYS TLT.
GIRLS TLT.
STOR.
UTILITY CLOSET
EXTENDED DAY
1 1
3 3 3 3
3 3 3 3 3
PRODUCTION
A.V. STOR.
MUSIC
MEDIA
OFFICE
WORK RM.
MEETING
ART
ART STOR. KILN
K-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOM
STOR.
P.E. STOR.
BOYS
JAN.
GIRLS
TLT.
TEACHER TLT.
TLT. TLT.
TLT.
IDF
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
MD102
MECHANICAL DEMO PLAN -
BUILDING 3010 & 3020
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"2 MECHANICAL DEMO PLAN - BUILDING 3020
NOTES: (THIS SHEET ONLY)
1 . REMOVING EXISTING CEILING HEATER. SEE NEW WORK FOR REPLACEMENT.
2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF
WORK SYMBOL.
3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
4 . REMOVE EXISTING WALL HEATER. SEE NEW WORK FOR REPLACEMENT.
5 . EXISTING KILN EXHAUST DUCT AND WALL CAP TO REMAIN.
6 . EXISTING LOUVER TO REMAIN.
7 . EXISTING LOUVER AND EXHAUST FAN TO REMAIN.
8 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF
APPLICABLE.
9 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP, ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION SHOWN. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN
NEW PACKAGED HEAT PUMP SAME LOCATION.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3010
No. Description Date
GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF
WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL
UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING
WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).
CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT
REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY
CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS
HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR
PROCESSING.
M101
M102
M102
3RD CLASSROOM
4TH CLASSROOM
4TH CLASSROOM
4TH CLASSROOM
4TH COMPUTER LAB
5TH CLASSROOM
5TH CLASSROOM5TH CLASSROOM2ND CLASSROOM2ND CLASSROOM
2ND CLASSROOM
2ND CLASSROOM
1ST CLASSROOM
1ST CLASSROOM
1ST CLASSROOM
1ST CLASSROOM
K-1 CLASSROOM
K COMPUTER LAB 3RD CLASSROOM
3RD CLASSROOM1ST CLASSROOM
BOYS TLT. BOYS TLT.
GIRLS TLT.GIRLS TLT
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED.
SPECIAL ED.
5TH CLASSROOM2ND CLASSROOM
READING
TESTING
WORK RM.
STOR.
JAN. STOR.
PARENT CENTER
BOOK STOR.
BOOK STOR.
CAFETERIA STAGE
KITCHEN
DRY STOR.
OFFICE
DISHWASH
WORK ROOM
COPIER & SUPPLY
VAULT
PRINCIPAL
OFFICE
OFFICE
LOBBY
ASSIST. PRINCIPAL
WAITING
COUNSELOR COUNSELOR
ART
ART STOR. KILN
MEETING
WORK RM.
OFFICE
MEDIAMUSIC
PRODUCTION
A.V. STOR.
P.E. STOR.
STOR.
BOYS
GIRLS
JAN.
K-1 CLASSROOM K-1 CLASSROOM K-1 CLASSROOM K-1 CLASSROOMTLT.
IDF
TLT.
TLT.
TLT.
TEACHER TLT.
MECH.
TLT.
ELEC.
JAN.
P.E. OFFICE FOYER
BOYS TLT.
GIRLS TLT.
STOR.
UTILITY CLOSET
EXTENDED DAY
GYM
EF-24
EF-25
EF-26
EF-14
EF-15
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
M100
MECHANICAL NEW WORK
PLAN - OVERALL
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
3/32" = 1'-0"1 MECHANICAL NEW WORK PLAN - OVERALL
3RD CLASSROOM 4TH CLASSROOM 4TH CLASSROOM 4TH CLASSROOM
4TH COMPUTER LAB 5TH CLASSROOM
5TH CLASSROOM
5TH CLASSROOM5TH CLASSROOM
2ND CLASSROOM 2ND CLASSROOM
2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM
K-1 CLASSROOM
KITCHEN
DISHWASH
DRY STOR.
OFFICE
CAFETERIA
STAGE
COPIER & SUPPLY
DRESSING
OFFICE
WORK ROOM
PRINCIPAL
VAULT
OFFICE
LOBBY
ASSIST. PRINCIPAL
WAITING
COUNSELOR
COUNSELOR
3RD CLASSROOM
K COMPUTER LAB
1ST CLASSROOM
3RD CLASSROOM
BOYS TLT. GIRLS TLT
WORK RM.
JAN. STOR.
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED.
SPECIAL ED.
READING
STOR.
213.8 SF
BOYS TLT. GIRLS TLT.
WORK RM. TESTING
Room
MECH.
TLT.
TLT.
ELEC.
JAN.
WHHP-1 WHHP-2 WHHP-3 WHHP-4 WHHP-5 WHHP-6 WHHP-7 WHHP-8 WHHP-9
WHHP-10
WHHP-11
WHHP-12WHHP-13WHHP-14
WHHP-15
WHHP-16WHHP-17WHHP-18WHHP-19
EF-6
EF-8
EF-7
EF-9
RTU-4
RTU-6 RTU-7
RTU-8
RTU-9
RTU-10
RTU-11
RTU-12
RTU-13
RTU-1 RTU-2
EF-1
EF-2
EF-4 EF-5
EF-11EF-12
EF-14
EF-15
EF-16
EF-17
ECH-2
ECH-2
ECH-3
ECH-1
EF-18
EF-19
8 8
3 3 3 3 3
33333333
EF-10
OAU-1
OAU-2
PARENT CENTER
BOOK STOR.
BOOK STOR.
KEF-1
KSF-1 KSF-2
HP-1
HP-2
AHU-2
AHU-1
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
14 14
DFCU-1
A1
A1
6"ø
6"ø
12"ø20"x12" 10"ø18"x12"
8"ø
8"ø
8"ø8"ø8"ø8"ø8"ø8"ø8"ø
DOU-1
750 750
12"ø 12"ø 10"ø10"ø
CC CC
CC CC
MM MM
MM
MM
MM
MM
T
PTHP-1
PTHP-3
A1
DFCU-2
500500
150300
DCU-2
EA - 300 CFM
EA - 300 CFM EA - 450 CFM
EA - 450 CFM
225225
TT TT TT TT
TTTTTTTT
MM
MM
ECH-8 ECH-9
ECH-10ECH-11
200 200
RTU-3
TT TT TT TT TT TT TT
TT
TT
TTTTTTTTTTTTTTTT
50 50
A2
12 12 12 12 12 12 12 12
121212121212121212
CC
CC
CC
T
16"x12"
"x
TT
TT
R
R
1" D
1" D
TT
18 18 18 18 18 18 18
18 18 18 18 18 18 18 18
TT 18
TT 18
R
3/4" D
A2
A2
A1
A1
6"ø
A1
A1
A1
6"ø
TT
TT
TT
18 TT
18 TT 18 TT
D
28(TYP)
28(TYP)
D
3/4" D
6"ø
3/4" D
3/4" D
3/4" D
3/4" D
3/4" D
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
M101
MECHANICAL NEW WORK
PLAN - BUILDING 3000
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - BUILDING 3000
NOTES: (THIS SHEET ONLY)
20 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..
21 . PIPE BOX LOCATED IN SAME PLACE AS EXISTING PIPE BOX. SEE PIPE BOX DETAIL. USE ROOF CURB ADAPTER AS NEEDED. SEE ROOF CURB ADAPTER DETAIL.
22 . CONDENSATE PIPE TO DISCHARGE INTO EXISTING CONDENSATE DRAINE LINE. BEFORE CONNECTING TO EXISTING PIPE, CONTRACTOR SHALL ENSURE EXISTING LINE IS
FREE OF DEBRIS OR ANY BLOCKAGE.
23 . REPAIR EXISTING DUCT COVERING TO FIT UP TO NEW UNIT. MATCH EXISTING DUCT COVER.
24 . ROOF MOUNTED DUCTLESS CONDENSING UNIT. SEE DUCTLESS UNIT ATOP EQUIPMENT SUPPORT RAIL DETAIL.
25 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.
26 . DUCTLESS CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
27 . ROUTE CONDENSATE FROM WALL UNIT UP THROUGH PIPE BOX AND DISCHARGE ON ROOF.
28 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.
29 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO DISCHARGE AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH OAU AND ROUTED TO THE NEAREST GUTTER AS SHOWN. INSURE THAT DRAIN PIPING DOES NOT BLOCK OAU ACCESS PANELS. DO NOT ROUTE DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE DRAIN TRAP DETAIL AND CONDENSATE ROOF SUPPORT DETAIL(S).
30 . DISCHARGE CONDENSATE ON ROOF AFTER P-TRAP.
1 . NEW CEILING HEATER IN EXISTING GRID.
2 . NEW CEILING MOUNTED EXHAUST FAN CONNECTED TO EXITING DUCTWORK WITH FLEXIBLE DUCT OF SIZE INDICATED.
3 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO CONNECT NEW WHHP TO EXISTING DUCTWORK
IN CHASE.
4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ATOP ROOF CURB ADAPTER
6 . CENTRIFUGAL ROOF MOUNTED EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEEDED.
7 . KITCHEN HOOD EXHAUST FAN. MOUNTED ON ROOF CURB ADAPTER.
8 . KITCHEN HOOD SUPPLY FAN. MOUNTED ON ROOF CURB ADAPTER.
9 . EXISTING KITCHEN HOOD.
10 . HORIZONTAL AIR HANDLER SUSPENDED FROM CEILING IN SAME LOCATION AS OLD AIR HANDLE.
11 . NEW HEAT PUMP MOUNTED ON EXISITNG ROOF SUPPORTS IN THIS APPROXIMATE LOCATION.
12 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE AS NECESSARY TRANSITIONS AND OFFSETS TO MAKE CONNECTION.
13 . 100% OUTSIDE AIR UNIT MOUNTED ATOP ROOF CURB. SEE ROOF CURB DETAIL - NEW CURB ON EXISTING ROOF.
14 . CONNECTION SIZE SUPPLY DUCT TRANSITIONS IN ELBOW FOR CONNECTION TO EXISTING 24" X 24" SUPPLY DUCTWORK AT APPROXIMATE LOCATION SHOWN. FIELD VERIFY EXISTING DUCTWORK DIMENSIONS. PROVIDE FITTINGS AND OFFSETS AS REQURIED TO MAKE CONNECTION.
15 . NEW RETURN DUCT CONNECTS TO EXISTING RETURN PLENUM AT THIS APPROXIMATE LOCATION.
16 . PACKAGED TERMINAL HEAT PUMP MOUNTED IN PLACE OF OLD.
17 . EXISTING TO REMAIN.
18 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..
19 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..
No. Description Date
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
PRODUCTION
A.V. STOR.
MUSIC
MEDIA
OFFICE
WORK RM.
MEETING
ART
ART STOR. KILN
K-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOM
STOR.
P.E. STOR.
237.07 SF
BOYS
JAN.
GIRLS TLT.
TEACHER TLT.
TLT.
TLT.
TLT.
IDF
WHHP-20WHHP-22WHHP-23
WHHP-24 WHHP-25 WHHP-26 WHHP-27 WHHP-28
WHHP-29
EF-21
EF-23
EF-22
EF-26
EF-25
EF-24EF-27
EF-28
EF-13
550 550
550 500
300 400400
400400
3 3 3 3
3 3 3 3
3ECH-5
ECH-4
ECH-6
ECH-7
OAU-3
A2
A2
A2
A2
A2
A2
A2
A2
WHHP-21
50 50
CC
CCCC
CC
MM
MM
MM MM
MM
DFCU-3
DCU-3
TT
6 6 6 6
8"ø
8"ø
8"ø 8"ø
8"ø
8"ø
16"ø
14"ø 12"ø
8"ø 8"ø
TT
133/4" D
R
16TT TT TT TT
TT
TTTTTT
TT
TT
16 16 16
161616
MVD
1" D
14"x16"
"ø
14"ø
A2
6"ø A2
6"ø
F.D. F.D.
F.D.
P.E. OFFICE
GYM
FOYER
BOYS TLT.
GIRLS TLT.
STOR. UTILITY CLOSET
EXTENDED DAY
EWH-2
EWH-1
EF-20
EF-3
PTHP-2
MM
MM
RTU-15RTU-14
ECH-12
NOTES: (THIS SHEET ONLY)
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
M102
MECHANICAL NEW WORK
PLAN - BUILDING 3010 & 3020
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - BUILDING 3010
1/8" = 1'-0"2 MECHANICAL NEW WORK PLAN - BUILDING 3020
1 . NEW CEILING HEATER IN EXISTING GRID.
2 . NEW CEILING MOUNTED EXHAUST FAN CONNECTED TO EXITING DUCTWORK WITH FLEXIBLE DUCT OF SIZE INDICATED.
3 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO CONNECT NEW WHHP TO EXISTING DUCTWORK IN CHASE.
4 . 100% OUTDSIDE AIR UNIT MOUNTED ON CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL. SEE PAD MOUNTED EXTERIOR METAL DUCT HOOD DETAIL.
5 . OA DUCT RISES IN STORAGE ROOM TO ATTIC. ROUTE OA DUCT ABOVE CORRIDOR FIRE RATED ASSEMBLY
6 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE ASS NECESSARY TRANSITIONS AND OFFSETS TO MAKE CONNECTION.
7 . PACKAGED TERMINAL HEAT PUMP MOUNTED IN PLACE OF OLD.
8 . ELECTRIC WALL HEATER REPLACEMENT. FEILD VERIFY EXACT LOCATION OF EXISTING.
9 . CONNECT NEW DUCTWORK TO EXISTING DUCTWORK. PROVIDE TRANSITIONS/OFFSETS AS REQUIRED TO MAKE NEW CONNECTION TO EXISTING DUCTWORK. SEE
10 . GROUND MOUNTED HORIZONTAL DISCHARGE PACKAGED HEAT PUMP MOUNTED ON CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL. SEE PAD MOUNTED GYM RTU EXTERIOR METAL DUCT HOOD DETAIL. PROVIDE TRANSITIONS/OFFSETS AS NEED TO MAKE DUCT CONNECTION.
11 . ROUTE CONDENSATE PIPING UNDERNEATH RETURN DUCT AND THROUGH EXTERNAL COVER. INSTALL THE CONDENSATE TRAP OUTSIDE OF THE COVERING. DO NOT INSTALL TRAP BETWEEN SUPPLE
AND RETURN DUCT. DISCHARGE ON PAD.
12 . NEW DUCTLESS CONDENSING UNIT MOUNTED ON WALL BRACKET. MOUNT UNIT AS HIGH AS POSSIBLE ON WALL. MAINTAIN MANUFACTURERS CLEARANCES.
13 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.
14 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..
15 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..
16 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..
17 . 100% OUTDSIDE AIR UNIT CONDENSATE TO DISCHARGE OFF THE EDGE OF PAD.
18 . TAP EXISTING DUCT FOR HALLWAY SUPPLY DUCT.
19 . INSTALL 6' TALL CHAINLINK FENCE AROUND EQUIPMENT YARD IN ACCORDANCE TO SPECIFICATIONS. INSTALL 3'GATE IN FENCE FOR SERVICE ACCESS.
No. Description Date
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
MAIN ROUND TRUNK DUCT
2 3/16" DUCT WRAP INSULATION FOR
SUPPLY AND RETURN DUCT
OPENING IN SIDE OF RECTANGULAR SHEET METAL
DUCT SHALL BE CUT WITH DRILL-CUTTER OR TIN
SNIPS. DIAMETER OF OPENING SHALL MATCH INNER
DIAMETER OF FOAM GASKET OR DIAMETER
RECOMMENDED BY TAKEOFF MANUFACTURER
DUCT
DUCT MASTICSHEET METAL SCREWS ON 6" CENTERS
FOAM GASKET
EXTERIOR VAPOR BARRIER (ONLY) SECURED
TO FITTING WITH NYLON "ZIP STRIP" BAND
SECURE INNER DUCT TO FITTING WITH NYLON
ZIP STRIP BAND IN ADDITION TO NYLON
STRIPBAND. SEAL INNER CORE TO DUCT.
FLEXIBLE DUCTWORK
90° SADDLE TAKEOFF COLLAR DAMPER AND THERMA-SEAL
GASKET FLANGE AND DAMPER HANDLE STANDOFF, SIMILAR TO
CROWN PRODUCT MODEL #314-DSO
FOR SUPPLY/RETURN DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR
HANDLE) WITH 2 3/16" DUCT WRAP. SEAL WITH VAPOR PROOF MASTIC AND CLOTH
FABRIC OVERLAPPING ESCUTCHEON AND DUCT WRAP FSK JACKET TO PREVENT
PASSAGE OF SMOKE.
20 GAUGE GALVANIZED SHEET METAL COVER
SEAL AND CAULK ALL JOINTS WATERTIGHT
A S
R E
Q U
IR
E
D
AS REQUIRED
SHEET METAL COVER ATOP ANGLE IRON
CONTINUOUS INSULATION
LAG SCREWS TO CURB ON MAXIMUM 16" CENTERS
EXISTING ROOF CURB TO REMAIN FOR REUSE
EXISTING ROOF AND DECK
PLAN VIEW
ELEVATION VIEW
CONTRACTOR SHALL FIELD VERIFY
EXACT CURB DIMENSIONS PRIOR
TO FABRICATING CURB CAP.
3" X 3" X ¼" ANGLE IRON FULLY WELDED
(PROVIDE CENTER ANGLE AT MIDSPAN
FOR ALL CURBS LARGER THAN 8 SQ. FT.)
NOTE: ALL ITEMS IN THIS DETAIL ARE NEW UNLESS NOTED OTHERWISE.
CURB CAP IS TO BE CONSTRUCTED OF 3" X 3" X ¼" ANGLE IRON
MEMBERS, MITERED OR BUTTED AS SHOWN AND WELDED TOGETHER.
COVER ENTIRE FRAME WITH 20 GA. GALVANIZED SHEET METAL. SEAL
AND CAULK ALL SEAMS WATERTIGHT. LINE ENTIRE UNDERSIDE WITH 1 ½"
RIGID FIBERGLASS INSULATION. SECURE TO EXISTING CURB WITH
GALVANIZED LAG SCREWS ON 16" CENTERS.
PROVIDE 1" WIDE CLOSED CELL
ELASTOMERIC (ARMAFLEX) TAPE
AROUND FULL PERIMETER OF
CURB TO SEAL COVER TO CURB.
PROVIDE BACKERBOARD IN ANY GAPS
AND SEAL AIR TIGHT WITH SILICONE
CAULK AROUND FULL PERIMETER
AT POINT WHERE ANGLE IRON OVERLAPS
CURB.
CEILING, BY ARCHITECTURAL
SQUARE TO ROUND TRANSITION (WHERE ELBOW CONNECTS TO SQUARE
NECK DIFFUSERS). PROVIDE ROUND TO ROUND TRANSITION WHERE GRILLE
NECK SIZE DIFFERS FROM CONNECTING DUCT SIZE (EITHER LARGER OR
SMALLER). INSULATE ON SUPPLY DUCTS.
3 GORE ADJUSTABLE ELBOW. INSULATE
ON SUPPLY DUCTS.
NYLON ZIP STRIP ON OUTER VAPOR BARRIER.
ENSURE INSULATION IS PULLED DOWN WITH
VAPOR BARRIER SO NO DUCTWORK IS
UNINSULATED.
NOTE: DETAIL IS TYPICAL FOR ALL FLEX DUCT RUNOUTS TO DIFFUSERS
STAINLESS STEEL DRAWBAND
ON INNER DUCT
FLEX DUCT
INSULATION BLANKET ON TOP
OF SUPPLY DIFFUSERS
CEILING DIFFUSER
J
POWER WIRING AND CONDUIT BY ELECTRICAL
PROVIDE "KNOCK OUT" AND GROMMET
FOR POWER CABLE
ROOF CURB. SEE ROOF CURB DETAIL.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE. (PROVIDE
ADJUSTABLE SHEAVE FOR ALL BELT DRIVE)
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
EXHAUST FAN
FACTORY FURNISHED DAMPER TRAY TO SUPPORT
BACK DRAFT DAMPER AND PROVIDE DUCT
ATTACHMENT.
FULL PERIMETER ANGLE IRON FRAMING BENEATH
CURB BY STRUCTURAL.
SECURE DUCT TO ROOF STRUCTURE WITH SHEET
METAL ON 4 SIDES. DUCT SHALL NOT BE
SUPPORTED BY DAMPER TRAY.
EXHAUST DUCT UP FROM BELOW
EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT
UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/
CURB SIZE.
MINIMUM 1 1/4" CLEARANCE FOR CONDUIT
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE
J
POWER WIRING AND CONDUIT BY ELECTRICAL
PROVIDE "KNOCK OUT" AND GROMMET
FOR POWER CABLE
ROOF CURB. SEE ROOF CURB DETAIL.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE.
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
UPBLAST EXHAUST FAN
FACTORY FURNISHED DAMPER TRAY TO SUPPORT
BACK DRAFT DAMPER AND PROVIDE DUCT
ATTACHMENT.
FULL PERIMETER ANGLE IRON FRAMING BENEATH
CURB BY STRUCTURAL.
SECURE DUCT TO ROOF STRUCTURE WITH SHEET
METAL ON 4 SIDES. DUCT SHALL NOT BE
SUPPORTED BY DAMPER TRAY.
EXHAUST DUCT UP FROM BELOW
EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT
UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/
CURB SIZE.
MINIMUM 1 1/4" CLEARANCE FOR CONDUIT
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE GALVANIZED BIRD SCREEN
SECURE CURB CAP TO CURB WITH ANCHORS ON
MAXIMUM 12" CENTERS (MINIMUM 2 ANCHORS
EACH SIDE)
GRADE
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
3000 PSI CONCRETE
1" CHAMFER
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2" MINIMUM
EXTERIOR CONCRETE PAD
FLOOR
1" CHAMFER
ANCHOR (TYPICAL OF 4)
INTERIOR CONCRETE PAD
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2"
3000 PSI CONCRETE
1½"
3"
UNION
AC UNIT
DRAIN CONNECTION
DRAIN PIPE SHALL BE AT LEAST
THE SAME DIAMETER AS THE NIPPLE
ON THE DRAIN PAN CONNECTION
OPEN END NIPPLE
SEE DRAWINGS FOR
PIPE REQUIRED MATERIAL
SLOPE AS REQUIRED
IN SPECIFICATIONS
PIPE NIPPLE
6"
FRONT VIEW
4"
SIDE VIEW
V A
R
IE
S
CONDENSATE PIPE,
VERIFY SIZE (TYP)
UV - STABILIZED, EDPM ADJUSTABLE RUBBER PIPE
SUPPORT, VERIFY PIPE DIAMETER BEING SUPPORTED.
SPACED ON MAXIMUM 8 FT. CENTERS AND 24" OF
FITTINGS (ERICO CADDY PYRAMID RPSE - TYPICAL)
INSTALL CONDENSATE PIPE AT THE LOWEST
POSSIBLE ELEVATION TO REDUCE TOP
HEAVY PIPE AND TO REDUCE TIPPING OVER
BUT TO MAINTAIN SPECIFIED SLOPE.
GENERAL: THIS CONDENSATE SUPPORT SHALL BE USED WITH DRAIN ELEVATIONS ABOVE ROOF OF 7" OR LESS. CONDENSATE ELEVATIONS ABOVE 8" SHALL USE ERICO CADDY PYRAMID ST ADJUSTABLE
STRUT SUPPORT OR EQUAL BY MIRO.
OPENING IN SIDE OF RECTANGULAR
SHEET METAL DUCT SHALL BE CUT
WITH DRILL CUTTER (NOT TIN SNIPS).
DIAMETER OF OPENING SHALL MATCH
INNER DIAMTER OF FOAM GASKET.
DUCT
DUCT MASTIC
FOAM GASKET
SHEET METAL SCREWS
ON 4" CENTERSDUCT
2" DUCT WRAP INSULATION FOR SUPPLY DUCT
EXTERIOR VAPOR BARRIER (ONLY) SECURED TO
FITTING WITH NYLON "ZIP-STRIP" BAND
FLEXIBLE DUCTWORK
BELLMOUTH OR 45° FITTING WITH DAMPER
FOR SUPPLY DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR HANDLE)
WITH 2" DUCTWRAP SEALED WITH VAPOR PROOF MASTIC AND CLOTH FABRIC
OVERLAPPING ESCUTCHEON AND DUCT WRAP FSK JACKET TO PREVENT PASSAGE
OF SMOKE.
PROVIDE OPTIONAL EXTENDED NECK SHAFT
FOR INSULATED DUCTS TO CLEAR INSULATION THICKNESS
SECURE INNER DUCT TO FITTING WITH 1/2" STAINLESS STEEL
DRAW BAND. CONTRACTOR SHALL NOT UTILIZE NYLON "ZIP-
STRIP" BAND TO SECURE INNER DUCT TO FITTING.
AIR
NOTE: SINGLE BI-POLAR IONIZATION UNIT SHOWN. INSTALLATION SIMILAR WHEN
MULTIPLE UNITS ARE INSTALLED IN ONE HVAC UNIT, EXCEPT 24V WIRING FROM
HVAC UNIT'S TERMINAL SIDE SHALL FEED CONTRACTOR FURNISHED TERMINAL
STRIP, WHICH SHALL THEN FEED POWER TO MULTIPLE UNITS. CONTRACTOR
FURNISHED TERMINAL STRIP SHALL BE ELECTRICALLY ISOLATED FROM THE HVAC
UNIT CASING AND ALL OTHER METAL COMPONENTS.
SECURE WITH SCREWS IN LOCATION THAT
WILL NOT DAMAGE HVAC EQUIPMENT OR
ASSOCIATED REFRIGERANT PIPE, WIRING
OR OTHER COMPONENTS
NEEDLEPOINT ELECTRODES. ENSURE UNIT IS
ORIENTED AND INSTALLED SO THAT AIR FLOW
PASSES BETWEEN ELECTRODES (INSTALL
PERPENDICULAR TO AIRFLOW). MAINTAIN
MANUFACTURER'S DISTANCE FROM NEEDLES
TO METAL SURFACE TO PREVENT ARCING.
FACTORY
FURNISHED
24VAC WIRING
BI-POLAR UNIT. SEE SCHEDULE FOR QUANTITY.
SEE ENLARGED DRAWING BELOW.
LED CONFIRMING IONIZATION OPERATION
B.A.S. CONTACTS TO ALLOW OWNER TO MONITOR STATUS.
MONITORING IS NOT INCLUDED IN THIS PROJECT.
BI-POLAR IONIZATION UNIT MOUNTED INSIDE UNIT DOWNSTREAM OF
FILTER IN SUPPLY AIRSTREAM IN LOCATION APPROVED BY HVAC
EQUIPMENT MANUFACTURER AND BI-POLAR MANUFACTURER
(FAN)
(24V POWER)
G
R
Y
W
C
O
CONNECT TO FAN AND 24V POWER TERMINALS ON 24 VAC
TERMINAL STRIP IN HVAC EQUIPMENT. ADDITIONAL GENERIC
TERMINALS ARE SHOWN FOR SYMBOLIC PURPOSES AND
ACTUAL TERMINALS WILL VARY BASED ON TYPE OF
EQUIPMENT.
PROVIDE ADDITIONAL WIRING (AS REQUIRED) IF FACTORY FURNISHED
WIRING WILL NOT REACH 24VAC TERMINAL STRIP. PROVIDE WIRE NUTS
AND ELECTRICAL TAPE AT JOINT. MATCH WIRE GAUGE OF
MANUFACTURER'S WIRING.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
M501
MECHANICAL DETAILS
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
NOT TO SCALE
90° SADDLE TAP TAKEOFF FITTING DETAIL
NOT TO SCALE
CAP AT EXISTING CURB
NOT TO SCALE
CEILING GRILLE DUCT CONNECTION DETAIL
NOT TO SCALE
CENTRIFUGAL DOWN BLAST EXHAUST FAN DETAIL
NOT TO SCALE
CENTRIFUGAL UPBLAST EXHAUST FAN DETAIL (CHECK)
NOT TO SCALE
CONCRETE EQUIPMENT PAD DETAIL
NOT TO SCALE
CONDENSATE DRAIN TRAP DETAIL
NOT TO SCALE
CONDENSATE PIPE SUPPORT ON ROOF DETAIL
NOT TO SCALE
BELLMOUTH AND 45° TAKEOFF FITTING DETAIL
No. Description Date
NOT TO SCALE
COMPACT BI-POLAR IONIZATION UNIT DETAIL
PROVIDE INSULATED HOUSING WHERE SCHEDULED
DUCT
AIRFLOW
PARALLEL BLADE BACKDRAFT DAMPER
SQUARE ACCESS PANEL FOR DAMPER ACTUATOR ACCESS
ACCESS PANEL (BOTH SIDES)
MOUNTING BRACKETS (TYP)
HANGING VIBRATION ISOLATORS. SEE SPECS FOR TYPE.
THREADED ROD
SUPPLEMENTAL ANGLE IRON FRAMING
DOUBLE NUTS
DOUBLE NUTS
DUCT
MOTOR. SEE SPECS FOR TYPE.
NOTE: BELT DRIVE FAN SIMILAR, EXCEPT MOTOR
OUTISDE OF FAN CASING, AND WITH INSULATED
MOTOR COVER WHERE SPECIFIED.
DUCT MOUNTING COLLAR (TYP INLET AND OUTLET). PROVIDE
1/2" X 1/2" WELDED WIRE GALVANIZED INLET GUARD FOR
NON-DUCTED INLET APPLICATIONS AS SCHEDULED.
MAINTAIN MINIMUM 2.5 TIMES WHERE DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND OUTLET OF FAN BEFORE
ELBOW, TRANSITION, DAMPER, ETC.
PROVIDE MOTORIZED DAMPER WITH INTERNAL ACTUATOR WHERE
SCHEDULED. DAMPER VOLTAGE SHALL MATCH FAN VOLTAGE.
FLEXIBLE DUCT
CONNECTION (TYP)
GALVANIZED MOTOR COVER
WHERE SCHEDULED
BACKWARD
INCLINED WHEEL
MAINTAIN MINIMUM 2.5 TIMES
WHEEL DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND
OUTLET OF FAN BEFORE ELBOW,
TRANSITION, DAMPER, ETC.
FACTORY INSTALLED NEMA-1
DISCONNECT SWITCH
FACTORY WIRED FROM MOTOR
TO DISCONNECT SWITCH
WELD SIDE ANGLE CLIP TO PAN (TYP OF 4)
TO CORNERS. SUSPEND WITH 3/8"
THREADED ROD. DO NOT BLOCK ACCESS
TO CONTROLLER.
PAN SHALL BE MIN. 18 GAUGE
GALVANIZED STEEL
2"
3/4" NIPPLE WELDED
TO PAN
PIPE 3/4" PAN DRAIN TO LOCATION
SHOWN ON DRAWINGS. SLOPE
PAN TO THIS SIDE.
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
18 GAUGE GALVANIZED SHEET METAL COVER FACTORY
FABRICATED BY EQUIPMENT SUPPORT MANUFACTURER
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.AS REQUIRED
RAISED CHANNEL SUPPORT FOR
MOUNTING OF HEAT PUMPS (TYP).
CHANNELS TO BE FACTORY
FABRICATED INTO COVER.
COORDINATE SPACING OF SUPPORT CHANNELS
WITH DIMENSIONS OF HEAT PUMPS BEING
INSTALLED ATOP PLATFORM. SEE PLANS
FOR UNIT LAYOUT.
ROOF CURB. SEE ROOF CURB DETAIL.COORDINATE LENGTH OF PLATFORM
REQUIRED WITH UNIT LAYOUT INDICATED
ON PLANS
ISOMETRIC VIEW
HEAT PUMP UNIT. SEE PLANS FOR SIZING AND LAYOUT.
SECURE HEAT PUMP
TO SUPPORT CHANNEL.
LAG SCREWS TO CURB ON
MAXIMUM 16" CENTERS.
ROOF CURB. SEE
ROOF CURB DETAIL.
PROVIDE FACTORY FURNISHED
INTERNAL SUPPORT CHANNELS
AS REQUIRED TO SUPPORT
WEIGHT OF HEAT PUMP UNITS.
ROOF DECK SHALL BE
CONTINUOUS UNDER CURB.
6" (MIN.)
FRONT VIEW
PRESSURE TREATED WOOD NAILER
SHEET METAL SCREW IN SIDE OF
COUNTER FLASHING (TYP)
18 GAUGE GALVANIZED STEEL
COUNTER FLASHING
SHEET METAL SCREW (TYP)
18 GAUGE STEEL BASE SECTION
FIELD INSTALLED INSULATION
INTEGRAL 18 GAUGE
GALVANIZED
STEEL BASE PLATE
FIELD INSTALLED CANT
ROOF DECK CONTINUOUS
BENEATH SUPPORT RAIL
SEE ARCHITECTURAL DRAWINGS FOR SPECIFIC
DETAILS CONCERNING ROOF CONSTRUCTION,
FLASHING, ANCHORS, BLOCKING,
ROOF DECK TYPE, ETC.
C U
R B
H E
IG
H
T
S T
Y
LE
A
S T
Y
LE
B
S T
Y
LE
C
2" MAX.
1" 1"
FOLDING BLADE STATIC RATED FIRE DAMPER
IN TYPE 'B' FRAME (EXCEPT TYPE 'A' SHALL BE
USED AT SIDEWALL REGISTERS AND NON-DUCTED
TRANSFER OPENING). DYNAMIC RATED DAMPERS
SHALL BE USED WHERE SPECIFICALLY SHOWN
ON DRAWINGS
ATTACH FIRE DAMPER TO SLEEVE IN
ACCORDANCE WITH MANUFACTUER'S
UL INSTALLATION INSTRUCTIONS
FACTORY FURNISHED ROUND OR OVAL
TRANSITION WITH BLADE STACK OUT
OF AIR STREAM
ROUND AND OVAL FIRE DAMPER
INSTALLATION SIMILAR
DUCT (WHERE APPLICABLE)
SLEEVE LENGTH SHALL BE DETERMINED BY CONTRACTOR TO
BE WITHIN MINIMUM AND MAXIMUM DISTANCE FROM
WALL/FLOOR AS REQUIRED BY MANUFACTUER
NOTE: INSTALLATION SHALL CONFORM TO THE FIRE
DAMPERS MANUFACTURER'S "UL" INSTALLATION
INSTRUCTIONS
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
THICKNESS RATING, AND MATERIAL OF
CONSTRUCTION FROM ARCHITECTURAL DRAWINGS,
AND USE THIS INFORMATION TO SELECT FIRE
DAMPER AND FIRE DAMPER ACCESSORIES.
PROVIDE MINIMUM OVERLAP ALL AROUND AS REQUIRED BY
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS
CLEARANCE (TYPICAL) AS REQUIRED BY MANUFACTURER'S
UL INSTALLATION INSTRUCTIONS
165° FUSIBLE LINK
DUCT TO SLEEVE CONNECTION SHALL BE AN APPROVED
TYPE AS LISTED IN THE MANUFACTURER'S UL INSTALLATION
INSTRUCTIONS. PROVIDE DUCT SEALANT APPROVED BY
FIRE DAMPER MANUFACTURER.
PROVIDE ACCESS PANEL FOR RECTANGULAR DUCTS. FOR ROUND DUCTS,
DOOR SIZE SHALL BE AS NOTED IN SPECIFICATIONS. FOR FLOOR
PENETRATIONS ACCESS PANEL SHALL BE ABOVE FLOOR.
FACTORY PROVIDED SLEEVE. SLEEVE LENGTH AND GAUGE SHALL
BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
FACTORY PROVIDED RETAINING ANGLES. ANGLE SIZE AND GAUGE
SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
GROUT
1" ABOVE FLOOR; FLUSH FOR WALLS
SCHEDULE 10 (MINIMUM)
STEEL PIPE
CONDUIT OR PIPING
PIPING INSULATION AS SPECIFIED.
PIPE INSULATION SHALL BE CONTINUOUS
THRU PENETRATION.
SEAL BETWEEN SLEEVE AND PIPING WITH FIRE RESISTANT
SEALANT OF SUFFICIENT THICKNESS TO MAINTAIN WALL'S
OR FLOOR FIRE RATING (1" MINIMUM THICKNESS). IF WALL
IS NOT FIRE RATED, PROVIDE CAULKING IN LIEU OF FIRE
RESISTANT SEALANT. SEALANT IS ONLY REQUIRED ON
ONE SIDE OF WALL, UNLESS REQUIRED BY MANUFACTURER
ON BOTH SIDES.
FIBERGLASS BATTS PACKED BETWEEN SLEEVE
AND PIPE (OR PIPE INSULATION ON INSULATED PIPE)
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
CONSTRUCTION TYPE (MASONRY, CONCRETE,
BRICK AND CMU, ETC.) AND THICKNESS.
INSIDE
UNINSULATED REFRIGERANT LIQUID PIPE
REFRIGERANT PIPE DROPS
IN WALL AS REQUIRED
INSULATED REFRIGERANT
SUCTION PIPE
20 GAUGE GALVANIZED
STEEL SHEET METAL SLEEVE
TERMINATE SLEEVE
FLUSH WITH WALL
OUTSIDE
PIPE PENETRATES WALL
NEAR GRADE LEVEL
EXTERIOR PAINTABLE SILICON CAULK.
PAINT TO MATCH EXTERIOR. EXTERIOR WALL. SEE ARCHITECTURAL PLANS
FOR CONSTRUCTION
FIRE RESISTANT FOAM OF APPROPRIATE
THICKNESS TO MAINTAIN WALL'S FIRE RATING
(1" MINIMUM THICKNESS)
DIA. -",
(SEE PLANS)
3"
DIM. + ?"
DIM. + ?"
3"
PAINT INTERIOR OF BOX MATTE BLACK.1
2 MINIMUM 26 GAUGE GALV. SHEET METAL.
4 ADAPTER MAY BE FABRICATED BY CONTRACTOR OR PROVIDED BY CROWN
PRODUCTS MODEL #666 ADAPTER OR EQUAL.
PROVIDE 1/2" DUCT LINER ON RETURN DUCT
APPLICATIONS AND NO LINER ON EXHAUST APPLICATION.
NOTES: (THIS DETAIL ONLY)
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE
AROUND PERIMETER OF DUCT EACH SIDE
OF WALL. ANCHOR TO WALL WITH
EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL
OPENING.
ELEVATION SECTION
NOTE: DETAIL IS SIMILAR FOR
UNINSULATED DUCTS. SEE
SPECIFICATION FOR REQUIRED
INSULATION THICKNESS.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC
OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET TO
PREVENT PASSAGE OF SMOKE.
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE AROUND
PERIMETER OF DUCT EACH SIDE OF WALL.
ANCHOR TO WALL WITH EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK
JACKET.INSULATION IS CONTINUOUS
THROUGH WALL OPENING.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH
FABRIC OVERLAPPING ANGLE AND DUCT WRAP
FSK JACKET TO PREVENT PASSAGE OF SMOKE.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
M502
MECHANICAL DETAILS
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
NOT TO SCALE
CENTRIFUGAL INLINE FAN DETAIL
NOT TO SCALE
CONDENSATE AUXILIARY DRAIN PAN DETAIL
NOT TO SCALE
EQUIPMENT SUPPORT PLATFORM DETAIL (HP)
NOT TO SCALE
EQUIPMENT SUPPORT RAIL DETAIL
NOT TO SCALE
FIRE DAMPER DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL - REFRIGERANT PIPE THRU EXTERIOR WALL
NOT TO SCALE
RECTANGULAR TO ROUND FLAT ADAPTER
NOT TO SCALE
DUCT PENETRATION THRU WALL DETAIL
INSIDEOUTSIDE
GRADE
EXTERIOR 22 GAUGE HOOD SHALL BE PAINT GRIP SHEET
METAL. ALL JOINTS AND SEAMS SHALL BE STANDARD
SMACNA CONSTRUCTION, AND SEALED NEATLY AND
WATERTIGHT. PAINT EXTERIOR DUCTWORK WITH 2 COATS
OF ENAMEL PAINT. VERIFY COLOR WITH ENGINEER.
HVAC
UNIT CAULK FULL WIDTH.
SEAL WEATHERTIGHT.
TURN CONNECTING DUCT UPWARD WITH 2"
FLANGE ON RTAC CONNECTION. CAULK FULL
PERIMETER OF DUCT.
1 LAYER OF EXTERIOR 2" THICK ARMACELL CLOSED
CELL ELASTOMERIC INSULATION OVER SUPPLY AND
RETURN DUCTWORK. FIBERGLASS INTERNAL DUCT
LINER OR EXTERNAL DUCT WRAP/BOARD IS NOT
ALLOWED ON THE DUCT. FINISH INSULATION WITH 2
COATS OF ARMACELL ARMAFLEX FINISH AND
EMBOSSED ALUMINUM COVER.
SEE PLANS FOR DUCT CONTINUATION.
NOTE: THE DUCT ROUTING SHOWN BETWEEN THE HVAC UNIT AND THE EXTERIOR WALL IS
SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,
OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.
CONCRETE EQUIPMENT PAD. SEE
CONCRETE EQUIPMENT PAD DETAIL.
22 GAUGE 3 SIDED METAL DUCT HOOD BETWEEN HVAC UNIT AND
EXTERIOR WALL. EXTEND BOTH SIDES OF SHEET METAL COVER TO
CONCRETE PAD. FLANGE DUCT 2" AT CONCRETE PAD AND PROVIDE
WEATHERTIGHT SEALS AT CONNECTION POINTS.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO EXTERIOR
WALL AND OVERLAPPING FLANGE OF COVER
NOTE: BASIS OF DESIGN CONDENSATE DRAIN IS LOCATED BETWEEN SUPPLY AND RETURN
DUCT CONNECTIONS. ROUTE CONDENSATE TO EXTERIOR OF HOOD AND PROVIDE P-TRAP
AT EXTERIOR OF HOOD IN AN ACCESSIBLE LOCATION. SEE CONDENSATE DRAIN TRAP
DETAIL.
2" MIN. UPWARD TURNED FLANGE. CAULK
FULL WIDTH OF FLANGE.
DUCT
SEE PLANS FOR DUCT CONTINUATION.
DUCT
FIELD VERIFY EXISTING DUCT
OPENING DIMENSIONS.
INSIDEOUTSIDE
GRADE
EXTERIOR 22 GAUGE HOOD SHALL BE PAINT GRIP
SHEET METAL. ALL JOINTS AND SEAMS SHALL BE
STANDARD SMACNA CONSTRUCTION, AND SEALED
NEATLY AND WATERTIGHT. PAINT EXTERIOR
DUCTWORK WITH 2 COATS OF ENAMEL PAINT.
VERIFY COLOR WITH ENGINEER.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO RTAC AND
OVERLAPPING FLANGE OF COVER
HVAC
UNIT
CAULK FULL WIDTH
CAULK FULL WIDTH OF FLANGE
TURN CONNECTING DUCT UPWARD WITH 2"
FLANGE ON RTAC CONNECTION. CAULK FULL
PERIMETER OF DUCT.
1 LAYER OF EXTERIOR 2" THICK ARMACELL CLOSED
CELL ELASTOMERIC INSULATION. FIBERGLASS
INTERNAL DUCT LINER OR EXTERNAL DUCT
WRAP/BOARD IS NOT ALLOWED ON THE DUCT. FINISH
INSULATION WITH 2 COATS OF ARMACELL ARMAFLEX
FINISH AND EMBOSSED ALUMINUM COVER.
SEE PLANS FOR DUCT CONTINUATION.
NOTE: THE DUCT ROUTING SHOWN BETWEEN THE HVAC UNIT AND THE EXTERIOR WALL IS
SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,
OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.
CONCRETE EQUIPMENT PAD. SEE
CONCRETE EQUIPMENT PAD DETAIL.
22 GAUGE 3 SIDED METAL DUCT HOOD BETWEEN HVAC UNIT
AND EXTERIOR WALL. EXTEND BOTH SIDES OF SHEET METAL
COVER TO CONCRETE PAD. FLANGE DUCT 2" AT CONCRETE
PAD AND PROVIDE WEATHERTIGHT SEALS AT CONNECTION
POINTS. SLOPE HOOD TO PREVENT WATER POOLING ON
TOP OF HOOD.
22 GAUGE METAL COUNTER FLASHING FULL
WIDTH OF DUCT ANCHORED TO EXTERIOR
WALL AND OVERLAPPING FLANGE OF COVER
NOTE: DO NOT ENCLOSE CONDENSATE DRAIN CONNECTION IN SHEET METAL HOOD. SEE
DRAWINGS FOR CONDENSATE ROUTING.
2" MIN. UPWARD TURNED FLANGE. CAULK
FULL WIDTH OF FLANGE.
LIGHT
RETURN
DUCT
22 GAUGE PAINT GALV GRIP GALVANIZED FLASHING. PAINT
FLASHING TO MATCH WHAC COLOR. FLASHING SHALL EXTEND
UP 4". CAULK AND SEAL WATERTIGHT AT FLASHING OVERLAP
FLASHING OVER WHAC'S INTEGRAL VERTICAL FLASHING.
WALL HUNG HEAT PUMP (WHHP)
INTEGRAL SLOPED TOP
EXISTING EXTERIOR WALL. FIELD
VERIFY EXACT CONSTRUCTION.
INTEGRAL DISCONNECT SWITCH
INTEGRAL VINYL DRAIN TUBING BY EQUIPMENT
MANUFACTURER. PVC TUBING SHALL BE
INSERTED INTO VINYL TUBING
STAINLESS STEEL HOSE CLAMP
3/4" PAINTED SCHEDULE 80 PVC DRAIN PIPE
PIPE CLAMP SECURED TO WALL
ON MAX 18" CENTERS
HEAVY DUTY STEEL RETURN GRILLE.
CONDENSATE LINE DOWN WALL AT GRADE.
AT GRADE, ELBOW PIPE AWAY FROM
BUILDING.
ROUTE DUCT HARD AGAINST
WALL AS POSSIBLE.
PROVIDE 1" LINER FROM UNIT CONNECTION
THRU BOTH ELBOWS TO LOCATION SHOWN.
REMAINDER OF SUPPLY DUCT SHALL BE
EXTERNALLY INSULATED WITH 2 3/16" DUCT
WRAP.
EXACT MOUNTING HEIGHT OF WHAC UNIT ABOVE GRADE / FINISHED
FLOOR VARIES BASED ON EXISTING CONDITIONS. WHERE POSSIBLE,
MAINTAIN MINIMUM 12" FROM BOTTOM OF WHAC TO GRADE.
SEE
INSERT
ROUTE DUCT HARD AGAINST
WALL AS POSSIBLE.
NEW ARCHITECTURAL CHASE TO CONCEAL
DUCT. SEE ARCH DRAWINGS FOR DETAILS.
WALL CURB TO ALLOW INSTALLATION OF NEW
WHHP IN SAME LOCATION AS EXISTING WHHP.
CAULK FULL LENGTH, BOTH SIDES AND TOP OF
UNIT. COLOR SHALL MATCH EXTERIOR WALL.
1" DUCT LINER INSIDE ALL RETURN DUCT.
PROVIDE CLOSED CELL EPDM ADHESIVE BACKED WEATHER
STRIPPING AROUND FULL PERIMETER OF UNIT PRIOR TO
MOUNTING AGAINST WALL TO SERVE AS INSECT AND
INFILTRATION BARRIER.
FILTER ACCESS PANEL
INTERNALLY MOUNTED BI-POLAR
IONIZATION UNIT
8" A.F.F. TO B.E. GRILLE
SOUND TRAP ELBOW
BRICK AND BLOCK WALL
FILTER IN INTEGRAL FILTER RACK
3" X 3" X 1/4" STRUCTURAL ANGLE. PAINT EXPOSED ANGLE
WITH TWO COATS OF PANT TO MATCH BUILDING COLOR
SUPPLY DUCTWORK
EXISTING INSULATION ON
CHICKEN WIRE SUPPORT
SYSTEM.
CEILINGTRANSITION IN RISE FROM
UNIT CONNECTION SIZE TO
SIZE SHOWN ON PLAN
ELECTRIC HEAT
SPACE ABOVE CEILING IS EXTREMELY LIMITED.
OFFSET DUCTWORK HORIZONTALLY AS
REQUIRED TO AVOID CONFLICT WITH LIGHT
FIXTURES. ENSURE DUCT INSULATION IS NOT
COMPRESSED MORE THAN 25%.
NOTE: DETAIL IS SIMILAR FOR UNINSULATED DUCTS.
CAULK AROUND FULL PERIMETER OF ESCUTCHEON
EACH SIDE OF WALL.
3" WIDE (MINIMUM) GAUGE SHEET METAL ESCUTCHEON
AROUND PERIMETER OF DUCT EACH SIDE OF WALL.
ANCHOR TO WALL WITH EXPANSION ANCHOR.
DUCT
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL OPENING.SEAL WITH VAPOR PROOF MASTIC AND
CLOTH FABRIC OVERLAPPING
ESCUTCHEON AND DUCT
WRAP FSK JACKET TO PREVENT
PASSAGE OF SMOKE.
NOTE: THIS DETAIL IS APPLICABLE TO CONCEALED ROUND, FLAT OVAL,
AND SPIRAL DUCTWORK. THIS DETAIL IS NOT APPLICABLE TO THE
INSTALLATION OF EXPOSED NON-RECTANGULAR DUCTWORK. SEE
SPECIFICATIONS FOR REQUIRED INSULATION THICKNESS
ELEVATION
SECTION
MASONRY WALL SHOWN. INSTALLATION REQUIREMENTS
ARE THE SAME FOR GYP BOARD WALLS.
SEAL WITH FSK TAPE OVERLAPPING ESCUTCHEON AND DUCT
WRAP FSK JACKET TO PREVENT PASSAGE OF SMOKE.
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL
OPENING.
3" WIDE (MINIMUM) 22 GAUGE SHEET METAL
ESCUTCHEON AROUND PERIMETER OF DUCT EACH
SIDE OF WALL. ANCHOR TO WALL WITH EXPANSION
ANCHOR .ENSURE ESCUTCHEON WIDTH IS
SUFFICIENT TO CONCEAL EDGES OF WALL OPENING.
CAULK AROUND FULL PERIMETER OF ESCUTCHEON
EACH SIDE OF WALL.
PROCEDURE:
1. SAW CUT BED JOINT IN BRICK TO INSTALL ANGLE.
2. INSTALL ANGLE - BEAR 8" AT JAMB.
3. SAW CUT BED JOINT IN CMU TO INSTALL ANGLE.
4. GROUT JAMBS SOLID.
5. INSTALL ANGLE - BEAR 8" AT JAMB.
6. REMOVE MASONRY AS REQUIRED.
EXISTING BRICK
¼" THICK X 11" WIDE
STEEL PLATE SPANNING
FULL WIDTH OF OPENING.
4 x 4 x 3/8 ANGLE IRON
EXISTING CMU
4 x 4 x 3/8 ANGLE IRON
3/16
NOTE: EXISTING BRICK AND BLOCK WALL
CONSTRUCTION SHOWN. SIMILAR FOR OTHER WALL
CONSTRUCTIONS.
EXISTING ROOF
RE-WORK ROOFING FOR INSTALLATION
OF NEW ROOF CURB IN ACCORDANCE WITH
ROOF MANUFACTURER'S BOND REQUIREMENTS.
C U
R B
H E
IG
H
T
EQUIPMENT
GASKET SEALER
PRESSURE
TREATED
WOOD NAILER
RIGID INSULATION
METAL ROOF CURB
LAG BOLT
PRESSURE TREATED BLOCKING
AS REQUIRED TO MATCH INSULATION
THICKNESS.
DUCT
ANCHOR TO DECK
ROOF DECK TO EXTEND
BENEATH ENTIRE ROOF CURB,
COORDINATE DUCT OPENING
LOCATION WITH MECH. UNIT
FULL PERIMETER STRUCTURAL STEEL FRAMING
UNDER ROOF CURB.
EXISTING METAL DECK
5/16" X 1/2" (MINIMUM) HEX HEAD
SCREWS ON 18" CENTERS. PROVIDE
MINIMUM 2 SCREWS PER SIDE.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
M503
MECHANICAL DETAILS
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
NOT TO SCALE
PAD MOUNTED GYM RTU EXTERIOR METAL DUCT HOOD DETAIL
NOT TO SCALE
PAD MOUNTED EXTERIOR METAL DUCT HOOD DETAIL
NOT TO SCALE
WALL HUNG AIR CONDITIONER - DUCTED SUPPLY DETAIL
NOT TO SCALE
NON-RECTANGULAR DUCT PENETRATION THRU WALL DETAIL
No. Description Date
NOT TO SCALE
LINTEL DETAIL AT EXISTING WALL
NOT TO SCALE
ROOF CURB DETAIL - NEW CURB ON EXISTING ROOF
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
M601
MECHANICAL SCHEDULES
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
EXHAUST FANS
TAG GREENHECK MODEL NUMBER CFM APPROX. E.S.P. (IN.W.G.) FAN RPM MOTOR HP SONES NOTES
EF-1 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-2 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-3 SP-80-VG 75 0.375 935 80W 0.5 2:3:4:5
EF-4 G-090-VG 300 0.3 1,135 1/10 4.7 1:3:4:5:6
EF-5 G-095-VG 450 0.3 1,174 1/6 5.4 1:3:4:5:6
EF-6 SP-A390-VG 225 0.5 1,274 1/15 5.2 2:3:4:5
EF-7 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-8 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-9 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-10 SP-A390-VG 110 0.5 1,274 1/15 5.2 2:3:4:5
EF-11 G-095-VG 450 0.3 1,174 1/6 5.4 1:3:4:5:6
EF-12 G-090-VG 300 0.3 1,135 1/10 4.7 1:3:4:5:6
EF-13 CSP-A510-VG 375 0.5 1,217 92W 1.1 2:3:4:5
EF-14 SP-A390-VG 225 0.5 1,274 1/15 5.2 2:3:4:5
EF-15 SP-80-VG 65 0.5 935 - 0.5 2:3:4:5
EF-16 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-17 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-18 SP-80-VG 75 0.375 935 6 - 2:3:4:5
EF-19 CSP-A510-VG 500 0.5 500 156W 1.4 2:3:4:5
EF-20 SP-80-VG 75 0.375 935 80W 0.5 2:3:4:5
EF-21 SP-A390-VG 150 0.5 1,222 29W 4.0 2:3:4:5
EF-22 SP-80-VG 75 0.375 768 80W 1.0 2:3:4:5
EF-23 SP-80-VG 75 0.375 768 80W 1.0 2:3:4:5
EF-24 SP-80-VG 75 0.375 768 80W 1.0 2:3:4:5
EF-25 SP-80-VG 75 0.375 768 80W 1.0 2:3:4:5
EF-26 SP-80-VG 75 0.375 768 80W 1.0 2:3:4:5
EF-27 SP-80-VG 40 0.5 935 6W 0.3 2:3:4:5
EF-28 SP-A390-VG 225 0.5 1,274 1/15 5.2 2:3:4:5
KEF-1 CUE-240-VG 6,200 0.5 809 2 17.1 4:8
KSF-1 SAF-112 2,480 0.5 779 3/4 15.2 4:7
KSF-2 SAF-112 2,480 0.5 779 3/4 15.2 4:7
DUCTLESS FAN COIL UNITS
TAG
CARRIER MODEL
NUMBER
TOTAL COOLING MBH SENSIBLE COOLING
CAPACITY (MBH)
TOTAL
SUPPLY CFM
HEATING CAPACITY MBH APPROX. E.S.P.
(IN.W.G.)
BLOWER
MOTOR WATTS
NOTES
RATED MIN. RATED MIN
DFCU-1 40MBCQ48 48 9.0 38.4 1175 50.0 10.0 - 270 1:2:3:4
DFCU-2 40MHHC12 12 4.8 9 305 - - - 20 2:3:4:5:6
DFCU-3 40MHHC12 12 4.8 9 305 - - - 20 2:3:4:5:6
DUCTLESS CONDENSING UNITS/HEAT PUMPS
TAG
CARRIER MODEL
NUMBER
TOTAL COOLING MBH HEATING CAPACITY MBH MINIMUM AMBIENT
COOLING TEMP. °F
NOTES
RATED MIN. RATED MIN.
DOU-1 38MBRQ48 48 9.0 50.0 10.0 40 1:2:3:4:5:6:7
DCU-2 38MHRBC12 12 4.8 - - 40 1:2:3:4:5:6:7:8
DCU-3 38MHRBC12 12 4.8 - - 40 1:2:3:4:5:7:8:9
ROOFTOP/PACKAGED UNITS
TAG
CARRIER
MODEL
NUMBER
TOTAL
COOLING MBH
SENSIBLE
COOLING MBH
TOTAL
SUPPLY CFM
O.A. CFM
HEATING
OUTPUT MBH
AUX. HEAT KW
APPROX.
E.S.P.
(IN.W.G.)
MINUMUM STAGES
COOLING ENTERING
CONDITIONS
MINIMUM
AMBIENT
COOLING TEMP
NOTES
COOLING HEATING E.A.T. D.B. °F E.A.T. W.B. °F
RTU-1 50GCQM04 33.8 26.9 1,200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-2 50GCQM04 33.8 26.9 1,200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-3 50GCQM05 45.2 35.8 1600 150 28.7 12.0 0.5 2 2 77.0 63.6 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-4 50GCQM05 45.2 35.8 1600 150 28.7 12.0 0.5 2 2 77.0 63.6 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-6 50GCQM04 33.8 26.9 1200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-7 50GCQM36 33.8 26.9 1,200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-8 50GCQM04 33.8 26.9 1200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-9 50GCQM04 33.8 26.9 1200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-10 50GCQM04 33.8 26.9 1200 150 24.1 8.1 0.5 2 2 77.6 64.2 40 1:2:3:4:5:6:7:8:9:10:11:12:14
RTU-11 50GCQM05 45.2 35.8 1600…
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| Bid Invitation | — | |
| Addendum 1 | — | |
| Addendum 4 | — | |
| Award Information | — | |
| Addendum 3 | — | |
| Addendum 2 | — |