Addendum 3
4 MB Posted
- Attached to
- WEST TOWN SCHOOL HVAC AND PLUMBING UPGRADES
- Solicitation number
- 22-FAC-017
- Issued by
- Douglas County, Georgia
About this file
This is Addendum 3 to the West Town School HVAC and Plumbing Upgrades contract opportunity in Georgia. The project involves replacement of heating and air conditioning systems and plumbing fixtures at West Town Elementary School located at 1113 University Avenue. The scope of work encompasses all labor, material, and equipment required to complete the specified HVAC and plumbing upgrades as detailed in the bid documents.
The addendum file provided does not contain specific details regarding pricing terms, set-asides, response or due dates, site visit requirements, bidder conferences, award dates, contract term, renewal options, funding sources, or other salient contractual information. To obtain comprehensive details about these elements, reference to the complete bid documents and primary addendum should be consulted.
Text of this file
West Town Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia
Addendum No. 3- Page 1 of 3
ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210
ADDENDUM NUMBER: THREE DATED: June 15, 2022
To: All contract bidders of record.
This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.
CHANGES TO SPECIFICATIONS
1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS
A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:
“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two
(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:
1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.
2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.
3. Exit Light/Emergency Light (one in each classroom at egress).
4. Computer Hub/Switch. Connect to nearest IDF in the main building.
5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.
6. Wireless Access Point (one in each classroom). Connect to hub/switch.
7. Intercom Speaker (one in each classroom). Bogen model number
MB8TSL(VR) or approved equal.
8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.
9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.
10. ADA Accessible Rest Room (one in each classroom).
11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.
12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height
13. One Set of Steps and One ADA Ramp.
14. Above ground septic tank, which will include weekly pumping service.
15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).
16. Above ground septic tank, which will include weekly pumping service.
Addendum No. 3- Page 2 of 3
17. Modular Classroom Distributers:
a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;
(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.
b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,
(770) 366-3356, wendy.grenske@mobilemodular.com”
2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS
A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.
3. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION
UNITS
A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:
“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”
CHANGES TO DRAWINGS
1. SHEET T100 - TITLE SHEET
A. Delete Sheet T100 in its entirety and replace with Sheet T100, revised 06/15/2022, included herewith.
2. SHEET MD101 - MECHANICAL DEMO PLAN -BUILDING 3000
B. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.
3. SHEET MD102 - MECHANICAL DEMO PLAN - BUILDING 3010 & 3020
A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.
4. SHEET M101 - MECHANICAL NEW WORK PLAN -BUILDING 3000
A. Delete Sheet M101 in its entirety and replace with Sheet M101, revised 06/15/2022, included herewith.
5. SHEET M504 - MECHANICAL/STRUCTURAL DETAILS
A. Add Sheet M504 Mechanical/Structural Details dated 06/15/2022, included herewith.
Addendum No. 3- Page 3 of 3
6. SHEET E001- ELECTRICAL OVERALL PLAN
A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.
7. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND
A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised 06/15/2022, included herewith.
END OF ADDENDUM #3
West Town Elementary School Revised June 15, 2022
ACOUSTICAL PANEL CEILINGS 095113 - 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.
2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
ACOUSTICAL PANEL CEILINGS 095113 - 2
B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.
Do not proceed with installation of ceilings until deficiencies have been corrected.
1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.
2. Before notifying Architect, complete the following in areas to receive ceilings:
a. Installation of lighting fixtures, powered for operation.
b. Installation, insulation, and leak and pressure testing of water piping systems.
c. Installation of air-duct systems.
d. Installation of air devices.
e. Installation of mechanical system control-air tubing.
f. Installation of ceiling support framing.
C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.
B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)
A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.
ACOUSTICAL PANEL CEILINGS 095113 - 3
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.
2. Pattern: E.
C. Color: White.
D. LR: Not less than 0.90.
E. NRC: Not less than 0.95.
F. Humidity/Sag Resistance: Humiguard Plus.
G. Edge/Joint Detail: Square edge.
H. Thickness: 5/8 inch.
I. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Clean Room VL
2. CertainTeed Corp.; Performa, Vinyrock
3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.
2. Pattern: As indicated by manufacturer’s designation.
C. Color: White.
D. LR: Not less than 0.78.
E. CAC: Not less than 38.
F. Edge/Joint Detail: Square.
G. Thickness: 1/2 inch.
H. Modular Size: 24 by 24 inches.
ACOUSTICAL PANEL CEILINGS 095113 - 4
2.5 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.
2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation
B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Steel cold-rolled sheet.
5. Cap Finish: Painted white.
2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard
2. CertainTeed Corp.; Classic Environmental Stab
3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA
ACOUSTICAL PANEL CEILINGS 095113 - 5
B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:
Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. Face Design: Flat, flush.
3. Face Finish: Painted white.
2.8 METAL EDGE MOLDINGS AND TRIM
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation.
B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.
1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.
2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.
3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.
B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
ACOUSTICAL PANEL CEILINGS 095113 - 6
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.
3.3 INSTALLATION
A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.
7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.
8. Do not attach hangers to steel deck tabs.
9. Do not attach hangers to steel roof deck. Attach hangers to structural members.
10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.
11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.
ACOUSTICAL PANEL CEILINGS 095113 - 7
C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.
D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.
1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.
2. Do not use exposed fasteners, including pop rivets, on moldings and trim.
E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.
F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.
1. Arrange directionally patterned acoustical panels as follows:
a. Install panels in a basket-weave pattern.
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.
3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.
3.4 CLEANING
A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
END OF SECTION 095113
ACOUSTICAL PANEL CEILINGS 095113 - 8
THIS PAGE INTENTIONALLY LEFT BLANK
D A
D E
BLECKLEY LAURENS
CHATHAM
EFFINGHAM
IRWIN
BERRIEN
LOWNDESGRADY
SE
M
IN
OL
E
DECATUR
EARLY
MILLER
BAKER
THOMAS
BROOKS
COLQUITT
MITCHELL
COOK
TIFT
SCHLEY
TERRELL
DOUGHERTY
WEBSTER
RANDOLPH
QUITMAN
CLAY
CALHOUN
CHATTAHOOCHEE
STEWART
MARION
WILCOX
CRISP
WORTH
LEE
TURNER
DOOLY
MACON
SUMTER
HOUSTON
PULASKI
McINTOSH
PIERCE
CHARLTON
LA
NI
ER
CLINCH
ECHOLS
ATKINSON
WARE
CAMDEN
BRANTLEY
GLYNN
TOOMBS
APPLING
COFFEE
BEN HILL
TELFAIR
DAVIS
JEFF
WHEELER
DODGE
TREUTLEN
M
ON
TG
OM
ER
Y
LONG
WAYNE
LIBERTY
BULLOCH
EVANS
CANDLER
TATTNALL
BRYAN
DAWSON FRANKLIN
CLARKE
OCONEE
PUTNAM
BALDWIN
TWIGGS
HENRY
FA
YE
TT
E
PIKE
UPSON
SPALDING
M
ER
IW
ET
HER
HARRIS
MUSCOGEE
TALBOT
COWETA
HEARD
TROUP
PEACH
CRAWFORD
TAYLOR
BIBB
MONROE
LAMAR
BUTTS
JASPER
JONES
CHEROKEE
FULTON
PAULDING
HARALSON
CARROLL
DOUGLAS
BARTOWFLOYD
POLK
COBB
NEWTON
DEKALB
CL
AY
TO
N
ROCKD
AL
E
WALTON
MORGAN
GWINNETT
FORSYTH
JACKSON
HALL BANKS
BARROW
M cD
U F
F
IE
JEFFERSON
EMANUEL
WASHINGTON
WILKINSON
JOHNSON
HANCOCK
WARREN
GLASCOCK
JENKINS
SCREVEN
RICHMOND
BURKE
COLUMBIA
OGLETHORPE
WILKES
TALIAFERROGREENE
LINCOLN
ELBERT
HART
MADISON
RABUN
STEPHENS
FANNIN
PICKENS
GILMER
WHITF
IELD
GORDON
C H
AT
TO
O G
A
WALKER M
U
R R
A Y
CATOOSA
UNION
LUMPKIN
WHITE
HABERSHAM
TOWNS
BACON
DOUGHERTY
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION
GA DOE ID #: 5062
T100
TITLE SHEET
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
WEST TOWN ELEMENTARY SCHOOL - HVAC &
PLUMBING UPGRADES
1113 UNIVERSITY ST, ALBANY, GA 31707
T100 TITLE SHEET
C100 SITE PLAN
A100 CONSTRUCTION PHASING PLAN
A200 ARCHITECTURAL CEILING PLAN - OVERALL
MD100 MECHANICAL DEMO PLAN - OVERALL
MD101 MECHANICAL DEMO PLAN - BUILDING 3000
MD102 MECHANICAL DEMO PLAN - BUILDING 3010 & 3020
M100 MECHANICAL NEW WORK PLAN - OVERALL
M101 MECHANICAL NEW WORK PLAN - BUILDING 3000
M102 MECHANICAL NEW WORK PLAN - BUILDING 3010 & 3020
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M504 MECHANICAL/STRUCTURAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES
P101 PLUMBING FLOOR PLAN - BUILDING 3000
P102 PLUMBING FLOOR PLANS - BUILDING 3010 & 3020
E001 ELECTRICAL OVERALL PLAN
ED101 ELECTRICAL DEMOLITION PLAN - BUILDING 3000
ED102 ELECTRICAL DEMOLITION PLAN - BUILDING 3010 & 3020
E201 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3000
E202 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3010 & 3020
E801 ELECTRICAL SCHEDULES AND LEGEND
GA DOE ID#: 5062
No. Description Date
2 ADDENDUM #3 06/15/22
1 1
6 6
15 4 4
4 4
3 3 3 3 3 3 3 3 3
33333333
3RD CLASSROOM
4TH CLASSROOM 4TH CLASSROOM 4TH CLASSROOM 4TH COMPUTER LAB 5TH CLASSROOM 5TH CLASSROOM
5TH CLASSROOM5TH CLASSROOM
2ND CLASSROOM 2ND CLASSROOM
2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM
K-1 CLASSROOM
KITCHENDISHWASH
DRY STOR.
OFFICE
CAFETERIA
STAGE
COPIER & SUPPLY
DRESSING
OFFICE
WORK ROOM
PRINCIPAL
VAULT
OFFICE
LOBBY
ASSIST. PRINCIPAL
WAITING
COUNSELOR
COUNSELOR
3RD CLASSROOM
K COMPUTER LAB 1ST CLASSROOM
3RD CLASSROOM
BOYS TLT.
GIRLS TLT
WORK RM.
JAN. STOR.
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED.
SPECIAL ED.
READING
STOR.
BOYS TLT.
GIRLS TLT.
WORK RM. TESTING
9 9
MECH.
Room
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
MD101
MECHANICAL DEMO PLAN -
BUILDING 3000
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3000
NOTES: (THIS SHEET ONLY)
10 . REMOVE EXISTING RANGE HOOD EXHAUST FAN ON ROOF.
11 . EXISTING KITCHEN RANGE HOOD TOO REMAIN.
12 . REMOVE EXISTING UNIT HEATER.
13 . REMOVE EXISTING DUCT HEATER. SEE ELECTRICAL DRAWINGS FOR CIRCUIT DEMO.
14 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF APPLICABLE.
15 . REMOVE EXISTING ROOFTOP AIR CONDITIONER CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL. SALVAGE BIPOLAR
IONIZATION UNIT AND TURN OVER TO OWNER.
16 . REMOVE EXISTING EXISTNG DUCTWORK. GRILLES TO REMAIN FOR RESUSE.
17 . EXISTING DISHWASHE EXHAUST FAN TO REMAIN.
18 . REMOVE EXISTING DUCTWORK AND GRILLES BACK TO SCOPE OF WORK SYMBOL. PATCH AND SEAL OPENING IN DUCT AIR TIGHT.
REINSULATE AS NEEDED.
19 . REMOVE EXISTING ROOF VENTILATOR TO REMAIN. CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL.
20 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK, SUPPORTS, AND ELECTRICAL CIRCUIT.
1 . REMOVING EXISTING CEILING HEATER.
2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF WORK SYMBOL.
3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT
FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
4 . REMOVE EXISTING ROOFTOP PACKAGE UNIT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP SAME LOCATION. SEE NEW WORK DRAWINGS FROM REPLACEMENT OF UNIT.
5 . REMOVE EXISTING HEAT PUMP ON ROOF FROM THIS APPROXIMATE LOCATION. REMOVE ANY ASSOCIATED REFRIGERANT PIPES (ON ROOF AND INSIDE BUILDING). EQUIPMENT SUPPORT RAILS TO REMAIN FOR REUSE. ROOF PIPE BOX SHALL DEMOED AND ROOF
OPENING WILL BE USED FOR A NEW PIPE BOX. SEE NEW WORK DRAWINGS FOR PIPE BOX
6 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.
7 . EXISTING ROOF VENTILATOR TO REMAIN.
8 . REMOVE EXISTING RANGE HOOD SUPPLY FAN ON ROOF.
9 . REMOVE EXISTING AIR HANDLING UNIT FROM THIS APPROXIMATE LOCATION. REMOVE EXISTING SUPPLY AND RETURN DUCT FROM AIR HANDLING UNIT UP TO THE SCOPE OF WORK SYMBOL. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW WORK DRAWING FOR NEW AIR HANDLING UNIT AND DUCTWORK.
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
TT TT
P.E. OFFICE
GYM
FOYER
BOYS TLT.
GIRLS TLT.
STOR.
UTILITY CLOSET
EXTENDED DAY
1 1
3 3 3 3
3 3 3 3 3
PRODUCTION
A.V. STOR.
MUSIC
MEDIA
OFFICE
WORK RM.
MEETING
ART
ART STOR. KILN
K-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOM
STOR.
P.E. STOR.
BOYS
JAN.
GIRLS
TLT.
TEACHER TLT.
TLT. TLT.
TLT.
IDF
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
MD102
MECHANICAL DEMO PLAN -
BUILDING 3010 & 3020
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"2 MECHANICAL DEMO PLAN - BUILDING 3020
NOTES: (THIS SHEET ONLY)
1 . REMOVING EXISTING CEILING HEATER. SEE NEW WORK FOR REPLACEMENT.
2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF
WORK SYMBOL.
3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
4 . REMOVE EXISTING WALL HEATER. SEE NEW WORK FOR REPLACEMENT.
5 . EXISTING KILN EXHAUST DUCT AND WALL CAP TO REMAIN.
6 . EXISTING LOUVER TO REMAIN.
7 . EXISTING LOUVER AND EXHAUST FAN TO REMAIN.
8 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF
APPLICABLE.
9 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP, ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION SHOWN. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN
NEW PACKAGED HEAT PUMP SAME LOCATION.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3010
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
3RD CLASSROOM 4TH CLASSROOM
4TH CLASSROOM
4TH CLASSROOM
4TH COMPUTER LAB 5TH CLASSROOM
5TH CLASSROOM
5TH CLASSROOM5TH CLASSROOM
2ND CLASSROOM 2ND CLASSROOM
2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM
1ST CLASSROOM
1ST CLASSROOM1ST CLASSROOM
K-1 CLASSROOM
KITCHEN
DISHWASH
DRY STOR.
OFFICE
CAFETERIA
STAGE
COPIER & SUPPLY
DRESSING
OFFICE
WORK ROOM
PRINCIPAL
VAULT
OFFICE
LOBBY
ASSIST. PRINCIPAL
WAITING
COUNSELOR
COUNSELOR
3RD CLASSROOM
K COMPUTER LAB
1ST CLASSROOM
3RD CLASSROOM
BOYS TLT. GIRLS TLT
WORK RM.
JAN. STOR.
SPEECH SPECIAL ED.
RESOURCE SPECIAL
ED.
SPECIAL ED.
READING
STOR.
213.8 SF
BOYS TLT. GIRLS TLT.
WORK RM. TESTING
Room
MECH.
TLT.
TLT.
ELEC.
JAN.
WHHP-1 WHHP-2 WHHP-3 WHHP-4 WHHP-5 WHHP-6 WHHP-7 WHHP-8 WHHP-9
WHHP-10
WHHP-11
WHHP-12WHHP-13WHHP-14
WHHP-15
WHHP-16WHHP-17WHHP-18WHHP-19
EF-6
EF-8
EF-7
EF-9
RTU-4
RTU-6 RTU-7
RTU-8
RTU-9
RTU-10
RTU-11
RTU-12
RTU-13
RTU-1 RTU-2
EF-1
EF-2
EF-4 EF-5
EF-11EF-12
EF-14
EF-15
EF-16
EF-17
ECH-2
ECH-2
ECH-3
ECH-1
EF-18
EF-19
8 8
3 3 3 3 3
33333333
EF-10
OAU-1
OAU-2
PARENT CENTER
BOOK STOR.
BOOK STOR.
KEF-1
KSF-1 KSF-2
HP-1
HP-2
AHU-2
AHU-1
A2
A2
A2
A2
A2
150A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
14 14
DFCU-1
A1
A1
6"ø
6"ø
12"ø20"x12" 10"ø18"x12"
8"ø
8"ø
8"ø8"ø8"ø8"ø8"ø8"ø8"ø
DOU-1
750 750
12"ø 12"ø 10"ø10"ø
CC CC
CC CC
MM MM
MM
MM
MM
MM
T
PTHP-1
PTHP-3
A1
DFCU-2
500500
150300
DCU-2
EA - 300 CFM
EA - 300 CFM EA - 450 CFM
EA - 450 CFM
225225
TT TT TT TT
TTTTTTTT
MM
MM
ECH-8 ECH-9
ECH-10ECH-11
200 200
RTU-3
TT TT TT TT TT TT TT
TT
TT
TTTTTTTTTTTTTTTT
50 50
A2
12 12 12 12 12 12 12 12
121212121212121212
CC
CC
CC
T
16"x12"
"x
TT
TT
R
R
1" D
1" D
TT
18 18 18 18 18 18 18
18 18 18 18 18 18 18 18
TT 18
TT
R
3/4" D
A2
A2
A1
A1
6"ø
A1
A1
A1
6"ø
TT
TT
TT
18 TT
18 TT 18 TT
D
28(TYP)
28(TYP)
D
3/4" D
6"ø
3/4" D
3/4" D
3/4" D
3/4" D
3/4" D
28"x12"
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
M101
MECHANICAL NEW WORK
PLAN - BUILDING 3000
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - BUILDING 3000
NOTES: (THIS SHEET ONLY)
20 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..
21 . PIPE BOX LOCATED IN SAME PLACE AS EXISTING PIPE BOX. SEE PIPE BOX DETAIL. USE ROOF CURB ADAPTER AS NEEDED. SEE ROOF CURB ADAPTER DETAIL.
22 . CONDENSATE PIPE TO DISCHARGE INTO EXISTING CONDENSATE DRAINE LINE. BEFORE CONNECTING TO EXISTING PIPE, CONTRACTOR SHALL ENSURE EXISTING LINE IS
FREE OF DEBRIS OR ANY BLOCKAGE.
23 . REPAIR EXISTING DUCT COVERING TO FIT UP TO NEW UNIT. MATCH EXISTING DUCT COVER.
24 . ROOF MOUNTED DUCTLESS CONDENSING UNIT. SEE DUCTLESS UNIT ATOP EQUIPMENT SUPPORT RAIL DETAIL.
25 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.
26 . DUCTLESS CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
27 . ROUTE CONDENSATE FROM WALL UNIT UP THROUGH PIPE BOX AND DISCHARGE ON ROOF.
28 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.
29 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO DISCHARGE AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH OAU AND ROUTED TO THE NEAREST GUTTER AS SHOWN. INSURE THAT DRAIN PIPING DOES NOT BLOCK OAU ACCESS PANELS. DO NOT ROUTE DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE DRAIN TRAP DETAIL AND CONDENSATE ROOF SUPPORT DETAIL(S).
30 . DISCHARGE CONDENSATE ON ROOF AFTER P-TRAP.
31 . APPROXIMATE LOCATION AND SEPERATION OF JOISTS. FEILD VERFIY EXACT LOCATIONS AND CONDITIONS PRIOR TO INSTALLING THE UNIT. SEE M504 FOR STRUCTURAL
REINFORCEMENT PLANS.
32 . MAIN DDC PANEL MOUNTED ON WALL.
1 . NEW CEILING HEATER IN EXISTING GRID.
2 . NEW CEILING MOUNTED EXHAUST FAN CONNECTED TO EXITING DUCTWORK WITH FLEXIBLE DUCT OF SIZE INDICATED.
3 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO CONNECT NEW WHHP TO EXISTING DUCTWORK
IN CHASE.
4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ATOP ROOF CURB ADAPTER
6 . CENTRIFUGAL ROOF MOUNTED EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEEDED.
7 . KITCHEN HOOD EXHAUST FAN. MOUNTED ON ROOF CURB ADAPTER.
8 . KITCHEN HOOD SUPPLY FAN. MOUNTED ON ROOF CURB ADAPTER.
9 . EXISTING KITCHEN HOOD.
10 . HORIZONTAL AIR HANDLER SUSPENDED FROM CEILING IN SAME LOCATION AS OLD AIR HANDLE.
11 . NEW HEAT PUMP MOUNTED ON EXISITNG ROOF SUPPORTS IN THIS APPROXIMATE LOCATION.
12 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE AS NECESSARY TRANSITIONS AND OFFSETS TO MAKE CONNECTION.
13 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CUSTOM STRUCTURAL LARGE BASE ROOF CURB. SEE M504 FOR STRUCTURAL SHEETS S-1 & S-2 FOR STRUCTURAL DRAWINGS
FOR STRUCTURE REINFORCEMENT. SEE LARGE BASE ROOF CURB WITH CURB ADAPTER DETAIL.
14 . CONNECTION SIZE SUPPLY DUCT TRANSITIONS IN ELBOW FOR CONNECTION TO EXISTING 24" X 24" SUPPLY DUCTWORK AT APPROXIMATE LOCATION SHOWN. FIELD VERIFY EXISTING DUCTWORK DIMENSIONS. PROVIDE FITTINGS AND OFFSETS AS REQURIED TO MAKE CONNECTION.
15 . NEW RETURN DUCT CONNECTS TO EXISTING RETURN PLENUM AT THIS APPROXIMATE LOCATION.
16 . PACKAGED TERMINAL HEAT PUMP MOUNTED IN PLACE OF OLD.
17 . EXISTING TO REMAIN.
18 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..
19 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
No. Description Date
2 ADDENDUM #3 06/15/22
NOTES: (THIS DETAIL ONLY)
1. MATERIAL: 18 GA. GALVANIZED STEEL.
2. FULLY WELDED.
3. FULLY INSULATED: 1", 1.5# INSULATION.
4. 1" X 4" PRESSURE TREATED WOOD NAILER.
5. UNIT TIE DOWN/LIFTING LUG.
6. PROVIDE 2 PIECES, BASE CURB AND ADAPTER.
7. ALL ROOF CURBS SHALL BE PLACED IN LOCATIONS AS SHOWN ON SHEET M101. SEE
S-1 AND S-2 ON M504 FOR ALL SECTIONS AND DETAILS FOR PLACEMENT.
8. CURB SHALL BE BY ALADDIN METAL PRODUCTS OR MGM PRODUCTS.
9. SEE SHEET M101 FOR NOTES REGARDING SUPPLY DROP. ALL DIMENSIONS SHALL BE
FIELD VERIFIED.
TOP BASE WIDTH/LENGTH OF CURB SHALL
SPECIFICALLY MATCH THE EXACT DIMENSIONS
OF THE ROOFTOP UNIT BEING INSTALLED.
ALSO SUPPLY CONNECTION SHALL
MATCH UP EXACTLY TO SPECIFIC MODEL
OF ROOFTOP UNIT.
INSULATED DECK PAN
THIS DIMENSION IS APPROXIMATE AND SHOULD BE
FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES
SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE
STRUCT. DRAWINGS ON M504. OVERALL CURB
DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.
CONTRACTOR SHALL VERIFY 24" WILL
ALLOW 12" MIN. ABOVE ROOF AS SHOWN.
BACK CURB
1" X 4"
NAILER
ADAPTER
2" BASE FLANGE OUT (FULL
PERIMETER)
LINE OF ROOF
12" MIN. ABOVE ROOF FINISH LEVEL
TOP VIEW
SIDE VIEWEND VIEW
12' 0"4' 4.5" +/-
THIS DIMENSION IS APPROXIMATE AND SHOULD BE
FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES
SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE
STRUCT. DRAWINGS ON M504. OVERALL CURB
DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
M504
MECHANICAL/STRUCTURAL
DETAILS
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
06/13/2022
HHP
JA3
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
NOT TO SCALE
LARGE BASE CURB WITH CURB ADAPTER
No. Description Date
2 ADDENDUM #3 06/15/22
1 PROVIDE A NEMA 3R 24"X24"X8" LOCKABLE LOW VOLTAGE SYSTEM CABINET FOR
MOBILE CLASSROOM SYSTEMS CABLING EXTENSION. INSTALL CABINET ON STANCHION
AT 24" ABOVE FINISHED GRADE. COORDINATE EXACT LOCATION WITH THE OWNER.
2 PROVIDE TWO (2) 3" CONDUITS WITH PULL ROPES FROM THE TELEPHONE BACKBOARD
(TEL) TO THE CABINET SPECIFIED IN NOTE 7 ABOVE. PROVIDE THE FOLLOWING CABLES
AS SPECIFIED FROM THE CABINET TO THE LOCATION INDICATED:
A. 48 PAIR INTERCOM CABLE AND 12 STRAND FIBER OPTIC CABLE IN 11/2" INNERDUCT
TO INTERCOM CABINET (MIC) THROUGH TEL.
B. 12 STRAND FIBER OPTIC CABLE TO MDF RACK.
C. 24 PAIR TELEPHONE CABLE.
PROVIDE SURGE SUPPRESSION FOR ALL COPPER CABLES ENTERING THE BUILDING.
ROUTE CABLES CONCEALED ABOVE ACCESSIBLE CEILINGS INSIDE THE BUILDING.
LEAVE MIN. 10' OF SLACK CABLES COILED AT EACH END. MAKE ALL CONNECTIONS.
3 CONTRACTOR SHALL PROVIDE AND INSTALL DATA NETWORK AND INTERCOM SYSTEM
EXTENSION INCLUDING ALL CONNECTIVITY AND ELECTRONIC EQUIPMENT TO THE
CONTRACTOR PROVIDED MODULAR CLASSROOMS. ROUTE SPECIFIED SYSTEM CABLES
FROM THE LOCKABLE LOW VOLTAGE SYSTEM CABINET TO EACH MODULAR
CLASSROOM. PROVIDE FIBER OPTIC CABLE FROM THE MODULAR CLASSROOM IDF
CORE SWITCH LOCATION TO EACH MODULAR CLASSROOM FOR DATA NETWORK
BACKBONE AND CONNECTIVITY AS SPECIFIED. PROVIDE INTERCOM SYSTEM
EXTENSION CABLES, COMPONENTS, SPEAKER, AND CONNECTIVITY TO THE MAIN
BUILDING INTERCOM SYSTEM VIA THE SPECIFIED MULTI-ZONE INTERCOM EXTENSION
PANEL. THE INTERCOM SYSTEM EXTENSION SHALL ALLOW EMERGENCY TONE
ANNUNCIATION FROM THE MAIN BUILDING INTERCOM SYSTEM. MAKE ALL
CONNECTIONS.
4 GENERAL: MODULAR CLASSROOMS ARE BEING PROVIDED BY THE CONTRACTOR PRIOR TO
THE START OF CONSTRUCTION. THE CONTRACTOR WILL REMOVE THESE CLASSROOMS
NEAR COMPLETION OF CONSTRUCTION. THE QUANTITY OF MODULAR CLASSROOM
UNITS IS SHOWN ON THIS SHEET. CONTRACTOR SHALL PROVIDE ALL POWER
SERVICE CONNECTIONS TO EACH UNIT. CONTRACTOR SHALL PROVIDE TEMPORARY
POWER SERVICE BY COORDINATING WITH THE POWER UTILITY COMPANY. OWNER SHALL PAY
ALL METER FEES AND SHALL PAY FOR UTILITY USAGE FOR ALL MODULAR UNITS FOR THE
DURATION OF THE PROJECT. PROVIDE 120/240V, 1PH, 150A SERVICE INCLUDING SECONDARY
CONDUCTORS FROM THE UTILITY COMPANY TRANSFORMERS, WEATHERHEADS, METER
SOCKETS, CONNECTION TO MODULAR CLASSROOM SERVICE PANEL, GROUNDING, RACEWAYS,
AND ETC FOR EACH MODULAR CLASSROOM.
5 GENERAL: CONTRACTOR SHALL PROVIDE AN EXIT UNIT COMBO BY LITHONIA, LHQM
LED R, OR EQUAL IN EACH MODULAR CLASSROOM. MOUNT THIS EXIT UNIT COMBO
ABOVE ONE OF THE EXIT DOORS INSIDE THE MODULAR CLASSROOMS AS SHOWN ON
THE ARCHITECTURAL DRAWINGS. CONNECT THIS UNIT TO THE UN-SWITCHED LIGHTING
CIRCUIT IN THE SPACE WITH 2#12, #12G CONDUCTORS IN 1/2" CONDUIT. MAKE ALL
CONNECTIONS. THE QUANTITY OF MODULAR CLASSROOM UNITS IS SHOWN ON THIS SHEET.
A. SECURE ALL EXISTING INTERIOR AND EXTERIOR LIGHT FIXTURES
AND EXIT SIGNS IN THE BUILDING, INCLUDING CIRCUIT
CONDUCTORS, CONDUITS, AND SWITCHES ETC. UNLESS NOTED
OTHERWISE.
B. DISCONNECT POWER FROM ALL MECHANICAL EQUIPMENT
SHOWN ON THE DEMOLITION DRAWINGS UNLESS OTHERWISE
NOTED, INCLUDING ROOF TOP UNITS, EXHAUST FANS, WALL
HEATERS, AIR HANDLERS, WATER SOURCE HEAT PUMPS,
COOLING TOWERS, BOILERS, UNIT VENTILATORS AND ETC. ALL
ELECTRICAL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS
OTHERWISE NOTED.
C. ALL EXISTING COMPUTER DATA OUTLETS, CABLES, AND
RACEWAYS SHALL REMAIN. ALL EXISTING COMPUTER DATA
OUTLETS, CABLES, AND RACEWAYS THAT ARE ASSOCIATED
WITH THE EXISTING MDF'S AND IDF'S TO REMAIN SHALL REMAIN
UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PROTECTION OF EXISTING DATA
OUTLETS AND ALL ASSOCIATED DATA NETWORKING ELECTRONIC
EQUIPMENT DURING DEMOLITION AND RENOVATIONS OF ALL
AREAS.
D. ALL EXISTING FIRE ALARM SYSTEM DEVICES INCLUDING SMOKE
DETECTORS, HORNS, STROBES, PULL STATIONS, PANELS AND
ETC. SHALL REMAIN IN THEIR ENTIRETY UNLESS NOTED
OTHERWISE.
E. ALL EXISTING INTERCOM SYSTEM COMPONENTS INCLUDING
WALL AND CEILING SPEAKERS, HANDSETS, PUSH BUTTONS,
CLOCKS, CABLES, AND RACEWAYS SHALL REMAIN IN THEIR
ENTIRETY.
F. ALL EXISTING CEILING MOUNTED EQUIPMENT AD DEVICES FOR
VIDEO SURVEILLANCE, INTRUSION DETECTION / SECURITY, AND
WIRELESS DATA NETWORK SYSTEMS SHALL BE SECURED AND
REINSTALLED IN NEW CEILINGS PER ARCHITECTURAL DRAWINGS
UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO THIS EQUIPMENT DURING
CONSTRUCTION. ANY EXISTING DAMAGED EQUIPMENT SHALL BE
REPORTED TO THE ENGINEER AND OWNER PRIOR TO
COMMENCEMENT OF WORK. CONTRACTOR SHALL COORDINATE
AIMING OF EACH SECURITY CAMERA TOUCHED AS PART OF THIS
PROJECT WITH OWNER. DURING REINSTALLATION OWNER’S REP
SHALL VERIFY FIELD OF VIEW IS ACCEPTABLE. CONTRACTOR
SHALL NOTIFY OWNER 7 DAYS IN ADVANCE OF INSTALLATION SO
OWNER’S REPRESENTATIVES MAY BE SCHEDULED TO BE
AVAILABLE ON SITE.
G. ALL EXISTING AUDIO- VISUAL COMPONENTS AND CABLING IN
CONFERENCE ROOMS INCLUDING THE PROJECTORS, SPEAKERS,
AUDIO ENHANCEMENT SYSTEM, TV TUNERS, AND CONNECTIVITY
SHALL REMAIN AND BE REINSTALLED. PROTECT, SECURE, AND
CLEAN THESE COMPONENTS DURING CONSTRUCTION. REINSTALL
THIS EQUIPMENT IN NEW CEILINGS AND NEW CEILING
ENCLOSURES. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
DAMAGE TO THIS EQUIPMENT DURING CONSTRUCTION. ANY
EXISTING DAMAGED EQUIPMENT SHALL BE REPORTED TO THE
ARCHITECT AND OWNER PRIOR TO COMMENCEMENT OF WORK.
H. ALL EXISTING ELECTRICAL CIRCUITS FOR TELEPHONE, INTERCOM,
TV, SECURITY, AND VIDEO SURVEILLANCE SHALL BE MAINTAINED IN
THE OCCUPIED AREAS DURING CONSTRUCTION UNLESS NOTED
OTHERWISE.CONTRACTOR IS CAUTIONED THAT NOT ALL OF THE
EXISTING LOW VOLTAGE SYSTEM CABLING IS IN CONDUIT.
I. ALL EXISTING VIDEO SURVEILLANCE SYSTEM CAMERAS AND
RECORDER HEAD- END EQUIPMENT INCLUDING NVR, MONITORS AND
CABLES SHALL REMAIN. SECURE, PROTECT, AND RE- MOUNT
EXISTING IP VIDEO SURVEILLANCE CAMERAS IN NEW CEILING TILES.
J. ALL EXISTING WIRELESS DATA NETWORK ACCESS POINTS SHALL
REMAIN. THIS CONTRACTOR SHALL SECURE, PROTECT, AND
REINSTALL ALL EXISTING ACCESS POINTS AND ASSOCIATED
CIRCUITRY ENTIRELY.
K. CEILING MOUNTED LIGHT FIXTURES IN THE AREAS OF MECHANICAL
EQUIPMENT DEMOLITION AND INSTALLATION SHALL BE
TEMPORARILY SECURED TO STRUCTURE, PROTECTED, AND
REINSTALLED IN NEW OR EXISTING CEILINGS PER MECHANICAL
DRAWINGS UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO LIGHT FIXTURES DURING
CONSTRUCTION.
2 3
GENERAL NOTES: (MODULAR CLASSROOMS)
(CEILING REMOVAL)GENERAL NOTES:
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
GA DOE ID #: 5062
E001
ELECTRICAL OVERALL PLAN
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
CTS
KAB
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
SCALE: 1/16" = 1'-0"
Electrical Overall Plan
1 . APPROXIMATE LOCATION OF EXISTING FIRE ALARM PANEL (SECUTRON MODEL MR-2400)
2 . APPROXIMATE LOCATION OF EXISTING INTERCOM SYSTEM HEAD END (BOGEN MULTICOM 2000)
3 . APPROXIMATE LOCATION OF EXISTING DATA MAIN DISTRIBUTION FRAME (MDF)
4 . GENERAL: HATCHED AREAS SHOW LOCATIONS WHERE CEILING TILE AND GRID ARE BEING REMOVED FOR DEMOLITION AND REPLACEMENT OF HVAC EQUIPMENT. SEE GENERAL NOTES THIS SHEET FOR
ADDITIONAL WORK.
NOTES: (THIS SHEET ONLY)
No. Description Date
1 ADDENDUM #3 6/15/22
1. CONTRACTOR SHALL REPLACE 80 EXISTING CEILING MOUNTED INTERCOM
SPEAKERS WITH NEW AS PART OF THIS PROJECT. IT IS THE INTENT OF
THE OWNER TO REPLACE ALL CEILING MOUNTED INTERCOM
SPEAKERS BUILDING WIDE WITH NEW. NEW SPEAKER PROVIDED BY THIS
CONTRACTOR SHALL BE BOGEN #ACD2X2U OR APPROVED EQUAL.
CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF DEMOLISHED
SPEAKERS AND MOUNTING HARDWARE.
GENERAL NOTES:
(INTERCOM SYSTEM)
J
ATS
J
M
R
C
FACTORY INSTALLED PIGTAIL
INSUL. BUSHING (TYP)
TO 120 VAC
PROVIDE IN-WALL JUNCTION BOX
WITH STAINLESS STEEL COVER
PLATE AND HOLE FOR CABLE
BUT SPLICE
BUTT SPLICE BY DIV. 16 MADE
INSIDE IN-WALL BOX
DUPLEX OUTLET
HARD CEILING 1' X 1' REMOVABLE ACCESS
PANEL (TYPICAL)
OBTAIN STD. &
HANDICAP SINK
MTG. HEIGHT FROM
DIV. 15 " ROUGH-IN"
DRAWING
1/2"MIN, 2"MAX
BENEATH LOWER
EDGE OF SINK
1/2"C IN WALL BY DIV. 16
FOR LOW VOLTAGE
(ONE PER LAV.)
120/24 VAC XFMR
BY DIV. 15
FIELD INSTALLED
MIN.18-2 PLENUM
RATED CABLE UP
TO XFMR IIN CELL
CAVITY BY DIV.16
MAXIMUM OF 1 LAVORATORIES, TOILET
OR URINAL PER XFMR/J BOX
(PER OWNER'S REQUEST)
SCALE: NONE
TYPICAL ELECTRIC FAUCET, TOILET OR URINAL SENSOR DETAIL
ELECTRICAL LEGEND
CONVENIENCE OUTLETS
SPECIAL PURPOSE OUTLET- WALL, CEILING
DUPLEX OUTLET- WALL, CEILING
ELECTRICAL PANELS- SEE SCHEDULE AND RISERS
SIMPLEX
JUNCTION BOX- WALL, CEILING
ONE SECTION PANEL
TWO SECTION PANEL
THREE SECTION PANEL
TRANSFORMER
AUTO TRANSFER SWITCH
GENERAL EQUIPMENT
CIRCUITS
RACEWAY IN CEILING OR WALL
ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN
HOMERUN - ONE ARROW PER CIRCUIT
RACEWAY UNDER FLOOR OR SLAB
EXPOSED RACEWAY
FLEXIBLE RACEWAY
CONDUIT - UP, DOWN
CABLE TRAY
MOTOR CONTROLLER
STARTER / DISCONNECT
ENCLOSED CIRCUIT BREAKER
DISCONNECT (SEE DRAWING FOR F= FUSED, NR= NON-FUSED)
PUSH BUTTON
SINGLE POLE, MOTOR RATED
CONTACTOR
RELAY
NOTE
IG = ISOLATED GROUND
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 5062
E801
ELECTRICAL SCHEDULES
AND LEGEND
2021200
W E
S T
T O
W N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
05/20/2022
CTS
KAB
U
N
IV
E R
S
IT
Y S
T
A L
B A
N Y
G
A
No. Description Date
1 ADDENDUM #3 6/15/22
| ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210 |
| ADDENDUM NUMBER: THREE DATED: June 15, 2022 |
| CHANGES TO SPECIFICATIONS |
| CHANGES TO DRAWINGS |
| 095113 - Acoustical Panel Ceilings_06152022.pdf |
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section includes acoustical panels and exposed suspension systems for ceilings. |
| 1.3 ACTION SUBMITTALS |
| A. Product Data: For each type of product. |
| 1.4 CLOSEOUT SUBMITTALS |
| A. Maintenance Data: For finishes to include in maintenance manuals. |
| 1.5 MAINTENANCE MATERIAL SUBMITTALS |
| A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| 1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2. |
| 2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1. |
| 1.6 DELIVERY, STORAGE, AND HANDLING |
| A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, tempe... |
| B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content. |
| C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way. |
| 1.7 FIELD CONDITIONS |
| A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained ... |
| B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed. Do not proceed with installation of ceilings until deficiencies hav... |
| 1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation. |
| 2. Before notifying Architect, complete the following in areas to receive ceilings: |
| a. Installation of lighting fixtures, powered for operation. |
| b. Installation, insulation, and leak and pressure testing of water piping systems. |
| c. Installation of air-duct systems. |
| d. Installation of air devices. |
| e. Installation of mechanical system control-air tubing. |
| f. Installation of ceiling support framing. |
C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.
| PART 2 - PRODUCTS |
| 2.1 PERFORMANCE REQUIREMENTS |
| A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. |
| 1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials. |
| 2. Smoke-Developed Index: 450 or less. |
| 2.2 ACOUSTICAL PANELS, GENERAL |
| A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer. |
| B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated. |
| C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type. |
| 2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS) |
| A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following: |
| 1. Armstrong World Industries, Inc. |
| 2. CertainTeed Corp. |
| 3. USG Interiors, Inc. |
| B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows: |
| 1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted. |
| 2. Pattern: E. |
| C. Color: White. |
| D. LR: Not less than 0.90. |
| E. NRC: Not less than 0.95. |
| F. Humidity/Sag Resistance: Humiguard Plus. |
| G. Edge/Joint Detail: Square edge. |
| H. Thickness: 5/8 inch. |
| I. Modular Size: 24 by 24 inches. |
| 2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS) |
| A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following: |
| 1. Armstrong World Industries, Inc.; Clean Room VL |
| 2. CertainTeed Corp.; Performa, Vinyrock |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus |
| B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows: |
| 1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile. |
| 2. Pattern: As indicated by manufacturer’s designation. |
| C. Color: White. |
| D. LR: Not less than 0.78. |
| E. CAC: Not less than 38. |
| F. Edge/Joint Detail: Square. |
| G. Thickness: 1/2 inch. |
| H. Modular Size: 24 by 24 inches. |
| 2.5 METAL SUSPENSION SYSTEMS, GENERAL |
| A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M. |
| 1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated. |
| B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements: |
| 1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper. |
| 2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire. |
| 2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings> |
| A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer: |
| 1. Armstrong World Industries, Inc. |
| 2. CertainTeed Corp. |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation |
| B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating desig... |
| 1. Structural Classification: Intermediate-duty system. |
| 2. End Condition of Cross Runners: Override (stepped) type. |
| 3. Face Design: Flat, flush. |
| 4. Cap Material: Steel cold-rolled sheet. |
| 5. Cap Finish: Painted white. |
| 2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings> |
| A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following: |
| 1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard |
| 2. CertainTeed Corp.; Classic Environmental Stab |
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| Bid Invitation | — | |
| Addendum 1 | — | |
| Addendum 4 | — | |
| DRAWINGS | — | |
| Award Information | — | |
| Addendum 2 | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .