This is Addendum 3 to the West Town School HVAC and Plumbing Upgrades contract opportunity in Georgia. The project involves replacement of heating and air conditioning systems and plumbing fixtures at West Town Elementary School located at 1113 University Avenue. The scope of work encompasses all labor, material, and equipment required to complete the specified HVAC and plumbing upgrades as detailed in the bid documents.

The addendum file provided does not contain specific details regarding pricing terms, set-asides, response or due dates, site visit requirements, bidder conferences, award dates, contract term, renewal options, funding sources, or other salient contractual information. To obtain comprehensive details about these elements, reference to the complete bid documents and primary addendum should be consulted.

Text of this file

West Town Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia

Addendum No. 3- Page 1 of 3

ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210

ADDENDUM NUMBER: THREE DATED: June 15, 2022

To: All contract bidders of record.

This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.

CHANGES TO SPECIFICATIONS

1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS

A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:

“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two

(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:

1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.

2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.

3. Exit Light/Emergency Light (one in each classroom at egress).

4. Computer Hub/Switch. Connect to nearest IDF in the main building.

5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.

6. Wireless Access Point (one in each classroom). Connect to hub/switch.

7. Intercom Speaker (one in each classroom). Bogen model number

MB8TSL(VR) or approved equal.

8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.

9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.

10. ADA Accessible Rest Room (one in each classroom).

11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.

12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height

13. One Set of Steps and One ADA Ramp.

14. Above ground septic tank, which will include weekly pumping service.

15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).

16. Above ground septic tank, which will include weekly pumping service.

Addendum No. 3- Page 2 of 3

17. Modular Classroom Distributers:

a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;

(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.

b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,

(770) 366-3356, wendy.grenske@mobilemodular.com”

2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS

A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.

3. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION

UNITS

A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:

“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”

CHANGES TO DRAWINGS

1. SHEET T100 - TITLE SHEET

A. Delete Sheet T100 in its entirety and replace with Sheet T100, revised 06/15/2022, included herewith.

2. SHEET MD101 - MECHANICAL DEMO PLAN -BUILDING 3000

B. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.

3. SHEET MD102 - MECHANICAL DEMO PLAN - BUILDING 3010 & 3020

A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.

4. SHEET M101 - MECHANICAL NEW WORK PLAN -BUILDING 3000

A. Delete Sheet M101 in its entirety and replace with Sheet M101, revised 06/15/2022, included herewith.

5. SHEET M504 - MECHANICAL/STRUCTURAL DETAILS

A. Add Sheet M504 Mechanical/Structural Details dated 06/15/2022, included herewith.

Addendum No. 3- Page 3 of 3

6. SHEET E001- ELECTRICAL OVERALL PLAN

A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.

7. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND

A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised 06/15/2022, included herewith.

END OF ADDENDUM #3

West Town Elementary School Revised June 15, 2022

ACOUSTICAL PANEL CEILINGS 095113 - 1

SECTION 095113 - ACOUSTICAL PANEL CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes acoustical panels and exposed suspension systems for ceilings.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1.4 CLOSEOUT SUBMITTALS

A. Maintenance Data: For finishes to include in maintenance manuals.

1.5 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.

2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.

C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.

1.7 FIELD CONDITIONS

A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.

ACOUSTICAL PANEL CEILINGS 095113 - 2

B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.

Do not proceed with installation of ceilings until deficiencies have been corrected.

1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.

2. Before notifying Architect, complete the following in areas to receive ceilings:

a. Installation of lighting fixtures, powered for operation.

b. Installation, insulation, and leak and pressure testing of water piping systems.

c. Installation of air-duct systems.

d. Installation of air devices.

e. Installation of mechanical system control-air tubing.

f. Installation of ceiling support framing.

C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.

2. Smoke-Developed Index: 450 or less.

2.2 ACOUSTICAL PANELS, GENERAL

A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.

B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.

C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.

2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)

A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.

ACOUSTICAL PANEL CEILINGS 095113 - 3

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.

2. Pattern: E.

C. Color: White.

D. LR: Not less than 0.90.

E. NRC: Not less than 0.95.

F. Humidity/Sag Resistance: Humiguard Plus.

G. Edge/Joint Detail: Square edge.

H. Thickness: 5/8 inch.

I. Modular Size: 24 by 24 inches.

2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Clean Room VL

2. CertainTeed Corp.; Performa, Vinyrock

3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.

2. Pattern: As indicated by manufacturer’s designation.

C. Color: White.

D. LR: Not less than 0.78.

E. CAC: Not less than 38.

F. Edge/Joint Detail: Square.

G. Thickness: 1/2 inch.

H. Modular Size: 24 by 24 inches.

ACOUSTICAL PANEL CEILINGS 095113 - 4

2.5 METAL SUSPENSION SYSTEMS, GENERAL

A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.

1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.

B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:

1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.

2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.

2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>

A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation

B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. End Condition of Cross Runners: Override (stepped) type.

3. Face Design: Flat, flush.

4. Cap Material: Steel cold-rolled sheet.

5. Cap Finish: Painted white.

2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard

2. CertainTeed Corp.; Classic Environmental Stab

3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA

ACOUSTICAL PANEL CEILINGS 095113 - 5

B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:

Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. Face Design: Flat, flush.

3. Face Finish: Painted white.

2.8 METAL EDGE MOLDINGS AND TRIM

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation.

B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.

1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.

2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.

3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.

B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

ACOUSTICAL PANEL CEILINGS 095113 - 6

3.2 PREPARATION

A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.

6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.

7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.

8. Do not attach hangers to steel deck tabs.

9. Do not attach hangers to steel roof deck. Attach hangers to structural members.

10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.

11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

ACOUSTICAL PANEL CEILINGS 095113 - 7

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.

1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.

2. Do not use exposed fasteners, including pop rivets, on moldings and trim.

E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.

F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.

1. Arrange directionally patterned acoustical panels as follows:

a. Install panels in a basket-weave pattern.

2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.

3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.

3.4 CLEANING

A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

END OF SECTION 095113

ACOUSTICAL PANEL CEILINGS 095113 - 8

THIS PAGE INTENTIONALLY LEFT BLANK

D A

D E

BLECKLEY LAURENS

CHATHAM

EFFINGHAM

IRWIN

BERRIEN

LOWNDESGRADY

SE

M

IN

OL

E

DECATUR

EARLY

MILLER

BAKER

THOMAS

BROOKS

COLQUITT

MITCHELL

COOK

TIFT

SCHLEY

TERRELL

DOUGHERTY

WEBSTER

RANDOLPH

QUITMAN

CLAY

CALHOUN

CHATTAHOOCHEE

STEWART

MARION

WILCOX

CRISP

WORTH

LEE

TURNER

DOOLY

MACON

SUMTER

HOUSTON

PULASKI

McINTOSH

PIERCE

CHARLTON

LA

NI

ER

CLINCH

ECHOLS

ATKINSON

WARE

CAMDEN

BRANTLEY

GLYNN

TOOMBS

APPLING

COFFEE

BEN HILL

TELFAIR

DAVIS

JEFF

WHEELER

DODGE

TREUTLEN

M

ON

TG

OM

ER

Y

LONG

WAYNE

LIBERTY

BULLOCH

EVANS

CANDLER

TATTNALL

BRYAN

DAWSON FRANKLIN

CLARKE

OCONEE

PUTNAM

BALDWIN

TWIGGS

HENRY

FA

YE

TT

E

PIKE

UPSON

SPALDING

M

ER

IW

ET

HER

HARRIS

MUSCOGEE

TALBOT

COWETA

HEARD

TROUP

PEACH

CRAWFORD

TAYLOR

BIBB

MONROE

LAMAR

BUTTS

JASPER

JONES

CHEROKEE

FULTON

PAULDING

HARALSON

CARROLL

DOUGLAS

BARTOWFLOYD

POLK

COBB

NEWTON

DEKALB

CL

AY

TO

N

ROCKD

AL

E

WALTON

MORGAN

GWINNETT

FORSYTH

JACKSON

HALL BANKS

BARROW

M cD

U F

F

IE

JEFFERSON

EMANUEL

WASHINGTON

WILKINSON

JOHNSON

HANCOCK

WARREN

GLASCOCK

JENKINS

SCREVEN

RICHMOND

BURKE

COLUMBIA

OGLETHORPE

WILKES

TALIAFERROGREENE

LINCOLN

ELBERT

HART

MADISON

RABUN

STEPHENS

FANNIN

PICKENS

GILMER

WHITF

IELD

GORDON

C H

AT

TO

O G

A

WALKER M

U

R R

A Y

CATOOSA

UNION

LUMPKIN

WHITE

HABERSHAM

TOWNS

BACON

DOUGHERTY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION

GA DOE ID #: 5062

T100

TITLE SHEET

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

HHP

JA3

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

WEST TOWN ELEMENTARY SCHOOL - HVAC &

PLUMBING UPGRADES

1113 UNIVERSITY ST, ALBANY, GA 31707

T100 TITLE SHEET

C100 SITE PLAN

A100 CONSTRUCTION PHASING PLAN

A200 ARCHITECTURAL CEILING PLAN - OVERALL

MD100 MECHANICAL DEMO PLAN - OVERALL

MD101 MECHANICAL DEMO PLAN - BUILDING 3000

MD102 MECHANICAL DEMO PLAN - BUILDING 3010 & 3020

M100 MECHANICAL NEW WORK PLAN - OVERALL

M101 MECHANICAL NEW WORK PLAN - BUILDING 3000

M102 MECHANICAL NEW WORK PLAN - BUILDING 3010 & 3020

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M503 MECHANICAL DETAILS

M504 MECHANICAL/STRUCTURAL DETAILS

M601 MECHANICAL SCHEDULES

M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES

P101 PLUMBING FLOOR PLAN - BUILDING 3000

P102 PLUMBING FLOOR PLANS - BUILDING 3010 & 3020

E001 ELECTRICAL OVERALL PLAN

ED101 ELECTRICAL DEMOLITION PLAN - BUILDING 3000

ED102 ELECTRICAL DEMOLITION PLAN - BUILDING 3010 & 3020

E201 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3000

E202 ELECTRICAL NEW WORK POWER PLAN - BUILDING 3010 & 3020

E801 ELECTRICAL SCHEDULES AND LEGEND

GA DOE ID#: 5062

No. Description Date

2 ADDENDUM #3 06/15/22

1 1

6 6

15 4 4

4 4

3 3 3 3 3 3 3 3 3

33333333

3RD CLASSROOM

4TH CLASSROOM 4TH CLASSROOM 4TH CLASSROOM 4TH COMPUTER LAB 5TH CLASSROOM 5TH CLASSROOM

5TH CLASSROOM5TH CLASSROOM

2ND CLASSROOM 2ND CLASSROOM

2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM1ST CLASSROOM

K-1 CLASSROOM

KITCHENDISHWASH

DRY STOR.

OFFICE

CAFETERIA

STAGE

COPIER & SUPPLY

DRESSING

OFFICE

WORK ROOM

PRINCIPAL

VAULT

OFFICE

LOBBY

ASSIST. PRINCIPAL

WAITING

COUNSELOR

COUNSELOR

3RD CLASSROOM

K COMPUTER LAB 1ST CLASSROOM

3RD CLASSROOM

BOYS TLT.

GIRLS TLT

WORK RM.

JAN. STOR.

SPEECH SPECIAL ED.

RESOURCE SPECIAL

ED.

SPECIAL ED.

READING

STOR.

BOYS TLT.

GIRLS TLT.

WORK RM. TESTING

9 9

MECH.

Room

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5062

MD101

MECHANICAL DEMO PLAN -

BUILDING 3000

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

HHP

JA3

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3000

NOTES: (THIS SHEET ONLY)

10 . REMOVE EXISTING RANGE HOOD EXHAUST FAN ON ROOF.

11 . EXISTING KITCHEN RANGE HOOD TOO REMAIN.

12 . REMOVE EXISTING UNIT HEATER.

13 . REMOVE EXISTING DUCT HEATER. SEE ELECTRICAL DRAWINGS FOR CIRCUIT DEMO.

14 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF APPLICABLE.

15 . REMOVE EXISTING ROOFTOP AIR CONDITIONER CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL. SALVAGE BIPOLAR

IONIZATION UNIT AND TURN OVER TO OWNER.

16 . REMOVE EXISTING EXISTNG DUCTWORK. GRILLES TO REMAIN FOR RESUSE.

17 . EXISTING DISHWASHE EXHAUST FAN TO REMAIN.

18 . REMOVE EXISTING DUCTWORK AND GRILLES BACK TO SCOPE OF WORK SYMBOL. PATCH AND SEAL OPENING IN DUCT AIR TIGHT.

REINSULATE AS NEEDED.

19 . REMOVE EXISTING ROOF VENTILATOR TO REMAIN. CAP EXISTING ROOF CURB. SEE ROOF CURB CAP DETAIL.

20 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK, SUPPORTS, AND ELECTRICAL CIRCUIT.

1 . REMOVING EXISTING CEILING HEATER.

2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF WORK SYMBOL.

3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT

FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.

4 . REMOVE EXISTING ROOFTOP PACKAGE UNIT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP SAME LOCATION. SEE NEW WORK DRAWINGS FROM REPLACEMENT OF UNIT.

5 . REMOVE EXISTING HEAT PUMP ON ROOF FROM THIS APPROXIMATE LOCATION. REMOVE ANY ASSOCIATED REFRIGERANT PIPES (ON ROOF AND INSIDE BUILDING). EQUIPMENT SUPPORT RAILS TO REMAIN FOR REUSE. ROOF PIPE BOX SHALL DEMOED AND ROOF

OPENING WILL BE USED FOR A NEW PIPE BOX. SEE NEW WORK DRAWINGS FOR PIPE BOX

6 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

7 . EXISTING ROOF VENTILATOR TO REMAIN.

8 . REMOVE EXISTING RANGE HOOD SUPPLY FAN ON ROOF.

9 . REMOVE EXISTING AIR HANDLING UNIT FROM THIS APPROXIMATE LOCATION. REMOVE EXISTING SUPPLY AND RETURN DUCT FROM AIR HANDLING UNIT UP TO THE SCOPE OF WORK SYMBOL. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW WORK DRAWING FOR NEW AIR HANDLING UNIT AND DUCTWORK.

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

2 ADDENDUM #3 06/15/22

TT TT

P.E. OFFICE

GYM

FOYER

BOYS TLT.

GIRLS TLT.

STOR.

UTILITY CLOSET

EXTENDED DAY

1 1

3 3 3 3

3 3 3 3 3

PRODUCTION

A.V. STOR.

MUSIC

MEDIA

OFFICE

WORK RM.

MEETING

ART

ART STOR. KILN

K-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOMK-1 CLASSROOM

STOR.

P.E. STOR.

BOYS

JAN.

GIRLS

TLT.

TEACHER TLT.

TLT. TLT.

TLT.

IDF

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5062

MD102

MECHANICAL DEMO PLAN -

BUILDING 3010 & 3020

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

HHP

JA3

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

1/8" = 1'-0"2 MECHANICAL DEMO PLAN - BUILDING 3020

NOTES: (THIS SHEET ONLY)

1 . REMOVING EXISTING CEILING HEATER. SEE NEW WORK FOR REPLACEMENT.

2 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND ASSOCIATED DUCTWORK UP TO SCOPE OF

WORK SYMBOL.

3 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.

4 . REMOVE EXISTING WALL HEATER. SEE NEW WORK FOR REPLACEMENT.

5 . EXISTING KILN EXHAUST DUCT AND WALL CAP TO REMAIN.

6 . EXISTING LOUVER TO REMAIN.

7 . EXISTING LOUVER AND EXHAUST FAN TO REMAIN.

8 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SALVAGE BIPOLAR IONIZATION UNIT IF

APPLICABLE.

9 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP, ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION SHOWN. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR REINSTALLATION IN

NEW PACKAGED HEAT PUMP SAME LOCATION.

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - BUILDING 3010

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

2 ADDENDUM #3 06/15/22

3RD CLASSROOM 4TH CLASSROOM

4TH CLASSROOM

4TH CLASSROOM

4TH COMPUTER LAB 5TH CLASSROOM

5TH CLASSROOM

5TH CLASSROOM5TH CLASSROOM

2ND CLASSROOM 2ND CLASSROOM

2ND CLASSROOM2ND CLASSROOM2ND CLASSROOM1ST CLASSROOM

1ST CLASSROOM

1ST CLASSROOM1ST CLASSROOM

K-1 CLASSROOM

KITCHEN

DISHWASH

DRY STOR.

OFFICE

CAFETERIA

STAGE

COPIER & SUPPLY

DRESSING

OFFICE

WORK ROOM

PRINCIPAL

VAULT

OFFICE

LOBBY

ASSIST. PRINCIPAL

WAITING

COUNSELOR

COUNSELOR

3RD CLASSROOM

K COMPUTER LAB

1ST CLASSROOM

3RD CLASSROOM

BOYS TLT. GIRLS TLT

WORK RM.

JAN. STOR.

SPEECH SPECIAL ED.

RESOURCE SPECIAL

ED.

SPECIAL ED.

READING

STOR.

213.8 SF

BOYS TLT. GIRLS TLT.

WORK RM. TESTING

Room

MECH.

TLT.

TLT.

ELEC.

JAN.

WHHP-1 WHHP-2 WHHP-3 WHHP-4 WHHP-5 WHHP-6 WHHP-7 WHHP-8 WHHP-9

WHHP-10

WHHP-11

WHHP-12WHHP-13WHHP-14

WHHP-15

WHHP-16WHHP-17WHHP-18WHHP-19

EF-6

EF-8

EF-7

EF-9

RTU-4

RTU-6 RTU-7

RTU-8

RTU-9

RTU-10

RTU-11

RTU-12

RTU-13

RTU-1 RTU-2

EF-1

EF-2

EF-4 EF-5

EF-11EF-12

EF-14

EF-15

EF-16

EF-17

ECH-2

ECH-2

ECH-3

ECH-1

EF-18

EF-19

8 8

3 3 3 3 3

33333333

EF-10

OAU-1

OAU-2

PARENT CENTER

BOOK STOR.

BOOK STOR.

KEF-1

KSF-1 KSF-2

HP-1

HP-2

AHU-2

AHU-1

A2

A2

A2

A2

A2

150A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

14 14

DFCU-1

A1

A1

6"ø

6"ø

12"ø20"x12" 10"ø18"x12"

8"ø

8"ø

8"ø8"ø8"ø8"ø8"ø8"ø8"ø

DOU-1

750 750

12"ø 12"ø 10"ø10"ø

CC CC

CC CC

MM MM

MM

MM

MM

MM

T

PTHP-1

PTHP-3

A1

DFCU-2

500500

150300

DCU-2

EA - 300 CFM

EA - 300 CFM EA - 450 CFM

EA - 450 CFM

225225

TT TT TT TT

TTTTTTTT

MM

MM

ECH-8 ECH-9

ECH-10ECH-11

200 200

RTU-3

TT TT TT TT TT TT TT

TT

TT

TTTTTTTTTTTTTTTT

50 50

A2

12 12 12 12 12 12 12 12

121212121212121212

CC

CC

CC

T

16"x12"

"x

TT

TT

R

R

1" D

1" D

TT

18 18 18 18 18 18 18

18 18 18 18 18 18 18 18

TT 18

TT

R

3/4" D

A2

A2

A1

A1

6"ø

A1

A1

A1

6"ø

TT

TT

TT

18 TT

18 TT 18 TT

D

28(TYP)

28(TYP)

D

3/4" D

6"ø

3/4" D

3/4" D

3/4" D

3/4" D

3/4" D

28"x12"

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5062

M101

MECHANICAL NEW WORK

PLAN - BUILDING 3000

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

HHP

JA3

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - BUILDING 3000

NOTES: (THIS SHEET ONLY)

20 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..

21 . PIPE BOX LOCATED IN SAME PLACE AS EXISTING PIPE BOX. SEE PIPE BOX DETAIL. USE ROOF CURB ADAPTER AS NEEDED. SEE ROOF CURB ADAPTER DETAIL.

22 . CONDENSATE PIPE TO DISCHARGE INTO EXISTING CONDENSATE DRAINE LINE. BEFORE CONNECTING TO EXISTING PIPE, CONTRACTOR SHALL ENSURE EXISTING LINE IS

FREE OF DEBRIS OR ANY BLOCKAGE.

23 . REPAIR EXISTING DUCT COVERING TO FIT UP TO NEW UNIT. MATCH EXISTING DUCT COVER.

24 . ROOF MOUNTED DUCTLESS CONDENSING UNIT. SEE DUCTLESS UNIT ATOP EQUIPMENT SUPPORT RAIL DETAIL.

25 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.

26 . DUCTLESS CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.

27 . ROUTE CONDENSATE FROM WALL UNIT UP THROUGH PIPE BOX AND DISCHARGE ON ROOF.

28 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.

29 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO DISCHARGE AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH OAU AND ROUTED TO THE NEAREST GUTTER AS SHOWN. INSURE THAT DRAIN PIPING DOES NOT BLOCK OAU ACCESS PANELS. DO NOT ROUTE DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE DRAIN TRAP DETAIL AND CONDENSATE ROOF SUPPORT DETAIL(S).

30 . DISCHARGE CONDENSATE ON ROOF AFTER P-TRAP.

31 . APPROXIMATE LOCATION AND SEPERATION OF JOISTS. FEILD VERFIY EXACT LOCATIONS AND CONDITIONS PRIOR TO INSTALLING THE UNIT. SEE M504 FOR STRUCTURAL

REINFORCEMENT PLANS.

32 . MAIN DDC PANEL MOUNTED ON WALL.

1 . NEW CEILING HEATER IN EXISTING GRID.

2 . NEW CEILING MOUNTED EXHAUST FAN CONNECTED TO EXITING DUCTWORK WITH FLEXIBLE DUCT OF SIZE INDICATED.

3 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS REMOVED WHHP. PROVIDE TRANSITIONS AS REQUIRED TO CONNECT NEW WHHP TO EXISTING DUCTWORK

IN CHASE.

4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ATOP ROOF CURB ADAPTER

6 . CENTRIFUGAL ROOF MOUNTED EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEEDED.

7 . KITCHEN HOOD EXHAUST FAN. MOUNTED ON ROOF CURB ADAPTER.

8 . KITCHEN HOOD SUPPLY FAN. MOUNTED ON ROOF CURB ADAPTER.

9 . EXISTING KITCHEN HOOD.

10 . HORIZONTAL AIR HANDLER SUSPENDED FROM CEILING IN SAME LOCATION AS OLD AIR HANDLE.

11 . NEW HEAT PUMP MOUNTED ON EXISITNG ROOF SUPPORTS IN THIS APPROXIMATE LOCATION.

12 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE AS NECESSARY TRANSITIONS AND OFFSETS TO MAKE CONNECTION.

13 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CUSTOM STRUCTURAL LARGE BASE ROOF CURB. SEE M504 FOR STRUCTURAL SHEETS S-1 & S-2 FOR STRUCTURAL DRAWINGS

FOR STRUCTURE REINFORCEMENT. SEE LARGE BASE ROOF CURB WITH CURB ADAPTER DETAIL.

14 . CONNECTION SIZE SUPPLY DUCT TRANSITIONS IN ELBOW FOR CONNECTION TO EXISTING 24" X 24" SUPPLY DUCTWORK AT APPROXIMATE LOCATION SHOWN. FIELD VERIFY EXISTING DUCTWORK DIMENSIONS. PROVIDE FITTINGS AND OFFSETS AS REQURIED TO MAKE CONNECTION.

15 . NEW RETURN DUCT CONNECTS TO EXISTING RETURN PLENUM AT THIS APPROXIMATE LOCATION.

16 . PACKAGED TERMINAL HEAT PUMP MOUNTED IN PLACE OF OLD.

17 . EXISTING TO REMAIN.

18 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..

19 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..

GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.

No. Description Date

2 ADDENDUM #3 06/15/22

NOTES: (THIS DETAIL ONLY)

1. MATERIAL: 18 GA. GALVANIZED STEEL.

2. FULLY WELDED.

3. FULLY INSULATED: 1", 1.5# INSULATION.

4. 1" X 4" PRESSURE TREATED WOOD NAILER.

5. UNIT TIE DOWN/LIFTING LUG.

6. PROVIDE 2 PIECES, BASE CURB AND ADAPTER.

7. ALL ROOF CURBS SHALL BE PLACED IN LOCATIONS AS SHOWN ON SHEET M101. SEE

S-1 AND S-2 ON M504 FOR ALL SECTIONS AND DETAILS FOR PLACEMENT.

8. CURB SHALL BE BY ALADDIN METAL PRODUCTS OR MGM PRODUCTS.

9. SEE SHEET M101 FOR NOTES REGARDING SUPPLY DROP. ALL DIMENSIONS SHALL BE

FIELD VERIFIED.

TOP BASE WIDTH/LENGTH OF CURB SHALL

SPECIFICALLY MATCH THE EXACT DIMENSIONS

OF THE ROOFTOP UNIT BEING INSTALLED.

ALSO SUPPLY CONNECTION SHALL

MATCH UP EXACTLY TO SPECIFIC MODEL

OF ROOFTOP UNIT.

INSULATED DECK PAN

THIS DIMENSION IS APPROXIMATE AND SHOULD BE

FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES

SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE

STRUCT. DRAWINGS ON M504. OVERALL CURB

DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.

CONTRACTOR SHALL VERIFY 24" WILL

ALLOW 12" MIN. ABOVE ROOF AS SHOWN.

BACK CURB

1" X 4"

NAILER

ADAPTER

2" BASE FLANGE OUT (FULL

PERIMETER)

LINE OF ROOF

12" MIN. ABOVE ROOF FINISH LEVEL

TOP VIEW

SIDE VIEWEND VIEW

12' 0"4' 4.5" +/-

THIS DIMENSION IS APPROXIMATE AND SHOULD BE

FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES

SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE

STRUCT. DRAWINGS ON M504. OVERALL CURB

DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 5062

M504

MECHANICAL/STRUCTURAL

DETAILS

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

06/13/2022

HHP

JA3

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

NOT TO SCALE

LARGE BASE CURB WITH CURB ADAPTER

No. Description Date

2 ADDENDUM #3 06/15/22

1 PROVIDE A NEMA 3R 24"X24"X8" LOCKABLE LOW VOLTAGE SYSTEM CABINET FOR

MOBILE CLASSROOM SYSTEMS CABLING EXTENSION. INSTALL CABINET ON STANCHION

AT 24" ABOVE FINISHED GRADE. COORDINATE EXACT LOCATION WITH THE OWNER.

2 PROVIDE TWO (2) 3" CONDUITS WITH PULL ROPES FROM THE TELEPHONE BACKBOARD

(TEL) TO THE CABINET SPECIFIED IN NOTE 7 ABOVE. PROVIDE THE FOLLOWING CABLES

AS SPECIFIED FROM THE CABINET TO THE LOCATION INDICATED:

A. 48 PAIR INTERCOM CABLE AND 12 STRAND FIBER OPTIC CABLE IN 11/2" INNERDUCT

TO INTERCOM CABINET (MIC) THROUGH TEL.

B. 12 STRAND FIBER OPTIC CABLE TO MDF RACK.

C. 24 PAIR TELEPHONE CABLE.

PROVIDE SURGE SUPPRESSION FOR ALL COPPER CABLES ENTERING THE BUILDING.

ROUTE CABLES CONCEALED ABOVE ACCESSIBLE CEILINGS INSIDE THE BUILDING.

LEAVE MIN. 10' OF SLACK CABLES COILED AT EACH END. MAKE ALL CONNECTIONS.

3 CONTRACTOR SHALL PROVIDE AND INSTALL DATA NETWORK AND INTERCOM SYSTEM

EXTENSION INCLUDING ALL CONNECTIVITY AND ELECTRONIC EQUIPMENT TO THE

CONTRACTOR PROVIDED MODULAR CLASSROOMS. ROUTE SPECIFIED SYSTEM CABLES

FROM THE LOCKABLE LOW VOLTAGE SYSTEM CABINET TO EACH MODULAR

CLASSROOM. PROVIDE FIBER OPTIC CABLE FROM THE MODULAR CLASSROOM IDF

CORE SWITCH LOCATION TO EACH MODULAR CLASSROOM FOR DATA NETWORK

BACKBONE AND CONNECTIVITY AS SPECIFIED. PROVIDE INTERCOM SYSTEM

EXTENSION CABLES, COMPONENTS, SPEAKER, AND CONNECTIVITY TO THE MAIN

BUILDING INTERCOM SYSTEM VIA THE SPECIFIED MULTI-ZONE INTERCOM EXTENSION

PANEL. THE INTERCOM SYSTEM EXTENSION SHALL ALLOW EMERGENCY TONE

ANNUNCIATION FROM THE MAIN BUILDING INTERCOM SYSTEM. MAKE ALL

CONNECTIONS.

4 GENERAL: MODULAR CLASSROOMS ARE BEING PROVIDED BY THE CONTRACTOR PRIOR TO

THE START OF CONSTRUCTION. THE CONTRACTOR WILL REMOVE THESE CLASSROOMS

NEAR COMPLETION OF CONSTRUCTION. THE QUANTITY OF MODULAR CLASSROOM

UNITS IS SHOWN ON THIS SHEET. CONTRACTOR SHALL PROVIDE ALL POWER

SERVICE CONNECTIONS TO EACH UNIT. CONTRACTOR SHALL PROVIDE TEMPORARY

POWER SERVICE BY COORDINATING WITH THE POWER UTILITY COMPANY. OWNER SHALL PAY

ALL METER FEES AND SHALL PAY FOR UTILITY USAGE FOR ALL MODULAR UNITS FOR THE

DURATION OF THE PROJECT. PROVIDE 120/240V, 1PH, 150A SERVICE INCLUDING SECONDARY

CONDUCTORS FROM THE UTILITY COMPANY TRANSFORMERS, WEATHERHEADS, METER

SOCKETS, CONNECTION TO MODULAR CLASSROOM SERVICE PANEL, GROUNDING, RACEWAYS,

AND ETC FOR EACH MODULAR CLASSROOM.

5 GENERAL: CONTRACTOR SHALL PROVIDE AN EXIT UNIT COMBO BY LITHONIA, LHQM

LED R, OR EQUAL IN EACH MODULAR CLASSROOM. MOUNT THIS EXIT UNIT COMBO

ABOVE ONE OF THE EXIT DOORS INSIDE THE MODULAR CLASSROOMS AS SHOWN ON

THE ARCHITECTURAL DRAWINGS. CONNECT THIS UNIT TO THE UN-SWITCHED LIGHTING

CIRCUIT IN THE SPACE WITH 2#12, #12G CONDUCTORS IN 1/2" CONDUIT. MAKE ALL

CONNECTIONS. THE QUANTITY OF MODULAR CLASSROOM UNITS IS SHOWN ON THIS SHEET.

A. SECURE ALL EXISTING INTERIOR AND EXTERIOR LIGHT FIXTURES

AND EXIT SIGNS IN THE BUILDING, INCLUDING CIRCUIT

CONDUCTORS, CONDUITS, AND SWITCHES ETC. UNLESS NOTED

OTHERWISE.

B. DISCONNECT POWER FROM ALL MECHANICAL EQUIPMENT

SHOWN ON THE DEMOLITION DRAWINGS UNLESS OTHERWISE

NOTED, INCLUDING ROOF TOP UNITS, EXHAUST FANS, WALL

HEATERS, AIR HANDLERS, WATER SOURCE HEAT PUMPS,

COOLING TOWERS, BOILERS, UNIT VENTILATORS AND ETC. ALL

ELECTRICAL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS

OTHERWISE NOTED.

C. ALL EXISTING COMPUTER DATA OUTLETS, CABLES, AND

RACEWAYS SHALL REMAIN. ALL EXISTING COMPUTER DATA

OUTLETS, CABLES, AND RACEWAYS THAT ARE ASSOCIATED

WITH THE EXISTING MDF'S AND IDF'S TO REMAIN SHALL REMAIN

UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE

RESPONSIBLE FOR THE PROTECTION OF EXISTING DATA

OUTLETS AND ALL ASSOCIATED DATA NETWORKING ELECTRONIC

EQUIPMENT DURING DEMOLITION AND RENOVATIONS OF ALL

AREAS.

D. ALL EXISTING FIRE ALARM SYSTEM DEVICES INCLUDING SMOKE

DETECTORS, HORNS, STROBES, PULL STATIONS, PANELS AND

ETC. SHALL REMAIN IN THEIR ENTIRETY UNLESS NOTED

OTHERWISE.

E. ALL EXISTING INTERCOM SYSTEM COMPONENTS INCLUDING

WALL AND CEILING SPEAKERS, HANDSETS, PUSH BUTTONS,

CLOCKS, CABLES, AND RACEWAYS SHALL REMAIN IN THEIR

ENTIRETY.

F. ALL EXISTING CEILING MOUNTED EQUIPMENT AD DEVICES FOR

VIDEO SURVEILLANCE, INTRUSION DETECTION / SECURITY, AND

WIRELESS DATA NETWORK SYSTEMS SHALL BE SECURED AND

REINSTALLED IN NEW CEILINGS PER ARCHITECTURAL DRAWINGS

UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE

RESPONSIBLE FOR ANY DAMAGE TO THIS EQUIPMENT DURING

CONSTRUCTION. ANY EXISTING DAMAGED EQUIPMENT SHALL BE

REPORTED TO THE ENGINEER AND OWNER PRIOR TO

COMMENCEMENT OF WORK. CONTRACTOR SHALL COORDINATE

AIMING OF EACH SECURITY CAMERA TOUCHED AS PART OF THIS

PROJECT WITH OWNER. DURING REINSTALLATION OWNER’S REP

SHALL VERIFY FIELD OF VIEW IS ACCEPTABLE. CONTRACTOR

SHALL NOTIFY OWNER 7 DAYS IN ADVANCE OF INSTALLATION SO

OWNER’S REPRESENTATIVES MAY BE SCHEDULED TO BE

AVAILABLE ON SITE.

G. ALL EXISTING AUDIO- VISUAL COMPONENTS AND CABLING IN

CONFERENCE ROOMS INCLUDING THE PROJECTORS, SPEAKERS,

AUDIO ENHANCEMENT SYSTEM, TV TUNERS, AND CONNECTIVITY

SHALL REMAIN AND BE REINSTALLED. PROTECT, SECURE, AND

CLEAN THESE COMPONENTS DURING CONSTRUCTION. REINSTALL

THIS EQUIPMENT IN NEW CEILINGS AND NEW CEILING

ENCLOSURES. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY

DAMAGE TO THIS EQUIPMENT DURING CONSTRUCTION. ANY

EXISTING DAMAGED EQUIPMENT SHALL BE REPORTED TO THE

ARCHITECT AND OWNER PRIOR TO COMMENCEMENT OF WORK.

H. ALL EXISTING ELECTRICAL CIRCUITS FOR TELEPHONE, INTERCOM,

TV, SECURITY, AND VIDEO SURVEILLANCE SHALL BE MAINTAINED IN

THE OCCUPIED AREAS DURING CONSTRUCTION UNLESS NOTED

OTHERWISE.CONTRACTOR IS CAUTIONED THAT NOT ALL OF THE

EXISTING LOW VOLTAGE SYSTEM CABLING IS IN CONDUIT.

I. ALL EXISTING VIDEO SURVEILLANCE SYSTEM CAMERAS AND

RECORDER HEAD- END EQUIPMENT INCLUDING NVR, MONITORS AND

CABLES SHALL REMAIN. SECURE, PROTECT, AND RE- MOUNT

EXISTING IP VIDEO SURVEILLANCE CAMERAS IN NEW CEILING TILES.

J. ALL EXISTING WIRELESS DATA NETWORK ACCESS POINTS SHALL

REMAIN. THIS CONTRACTOR SHALL SECURE, PROTECT, AND

REINSTALL ALL EXISTING ACCESS POINTS AND ASSOCIATED

CIRCUITRY ENTIRELY.

K. CEILING MOUNTED LIGHT FIXTURES IN THE AREAS OF MECHANICAL

EQUIPMENT DEMOLITION AND INSTALLATION SHALL BE

TEMPORARILY SECURED TO STRUCTURE, PROTECTED, AND

REINSTALLED IN NEW OR EXISTING CEILINGS PER MECHANICAL

DRAWINGS UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE

RESPONSIBLE FOR ANY DAMAGE TO LIGHT FIXTURES DURING

CONSTRUCTION.

2 3

GENERAL NOTES: (MODULAR CLASSROOMS)

(CEILING REMOVAL)GENERAL NOTES:

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5062

E001

ELECTRICAL OVERALL PLAN

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

CTS

KAB

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

SCALE: 1/16" = 1'-0"

Electrical Overall Plan

1 . APPROXIMATE LOCATION OF EXISTING FIRE ALARM PANEL (SECUTRON MODEL MR-2400)

2 . APPROXIMATE LOCATION OF EXISTING INTERCOM SYSTEM HEAD END (BOGEN MULTICOM 2000)

3 . APPROXIMATE LOCATION OF EXISTING DATA MAIN DISTRIBUTION FRAME (MDF)

4 . GENERAL: HATCHED AREAS SHOW LOCATIONS WHERE CEILING TILE AND GRID ARE BEING REMOVED FOR DEMOLITION AND REPLACEMENT OF HVAC EQUIPMENT. SEE GENERAL NOTES THIS SHEET FOR

ADDITIONAL WORK.

NOTES: (THIS SHEET ONLY)

No. Description Date

1 ADDENDUM #3 6/15/22

1. CONTRACTOR SHALL REPLACE 80 EXISTING CEILING MOUNTED INTERCOM

SPEAKERS WITH NEW AS PART OF THIS PROJECT. IT IS THE INTENT OF

THE OWNER TO REPLACE ALL CEILING MOUNTED INTERCOM

SPEAKERS BUILDING WIDE WITH NEW. NEW SPEAKER PROVIDED BY THIS

CONTRACTOR SHALL BE BOGEN #ACD2X2U OR APPROVED EQUAL.

CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF DEMOLISHED

SPEAKERS AND MOUNTING HARDWARE.

GENERAL NOTES:

(INTERCOM SYSTEM)

J

ATS

J

M

R

C

FACTORY INSTALLED PIGTAIL

INSUL. BUSHING (TYP)

TO 120 VAC

PROVIDE IN-WALL JUNCTION BOX

WITH STAINLESS STEEL COVER

PLATE AND HOLE FOR CABLE

BUT SPLICE

BUTT SPLICE BY DIV. 16 MADE

INSIDE IN-WALL BOX

DUPLEX OUTLET

HARD CEILING 1' X 1' REMOVABLE ACCESS

PANEL (TYPICAL)

OBTAIN STD. &

HANDICAP SINK

MTG. HEIGHT FROM

DIV. 15 " ROUGH-IN"

DRAWING

1/2"MIN, 2"MAX

BENEATH LOWER

EDGE OF SINK

1/2"C IN WALL BY DIV. 16

FOR LOW VOLTAGE

(ONE PER LAV.)

120/24 VAC XFMR

BY DIV. 15

FIELD INSTALLED

MIN.18-2 PLENUM

RATED CABLE UP

TO XFMR IIN CELL

CAVITY BY DIV.16

MAXIMUM OF 1 LAVORATORIES, TOILET

OR URINAL PER XFMR/J BOX

(PER OWNER'S REQUEST)

SCALE: NONE

TYPICAL ELECTRIC FAUCET, TOILET OR URINAL SENSOR DETAIL

ELECTRICAL LEGEND

CONVENIENCE OUTLETS

SPECIAL PURPOSE OUTLET- WALL, CEILING

DUPLEX OUTLET- WALL, CEILING

ELECTRICAL PANELS- SEE SCHEDULE AND RISERS

SIMPLEX

JUNCTION BOX- WALL, CEILING

ONE SECTION PANEL

TWO SECTION PANEL

THREE SECTION PANEL

TRANSFORMER

AUTO TRANSFER SWITCH

GENERAL EQUIPMENT

CIRCUITS

RACEWAY IN CEILING OR WALL

ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN

HOMERUN - ONE ARROW PER CIRCUIT

RACEWAY UNDER FLOOR OR SLAB

EXPOSED RACEWAY

FLEXIBLE RACEWAY

CONDUIT - UP, DOWN

CABLE TRAY

MOTOR CONTROLLER

STARTER / DISCONNECT

ENCLOSED CIRCUIT BREAKER

DISCONNECT (SEE DRAWING FOR F= FUSED, NR= NON-FUSED)

PUSH BUTTON

SINGLE POLE, MOTOR RATED

CONTACTOR

RELAY

NOTE

IG = ISOLATED GROUND

GFCI = GROUND FAULT CIRCUIT INTERRUPTER

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 5062

E801

ELECTRICAL SCHEDULES

AND LEGEND

2021200

W E

S T

T O

W N

E L

E M

E N

T A

R Y

S C

H O

O L

H

V A

C

P L

U M

B

IN

G U

P G

R A

D E

S

05/20/2022

CTS

KAB

U

N

IV

E R

S

IT

Y S

T

A L

B A

N Y

G

A

No. Description Date

1 ADDENDUM #3 6/15/22

ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210
ADDENDUM NUMBER: THREE DATED: June 15, 2022
CHANGES TO SPECIFICATIONS
CHANGES TO DRAWINGS
095113 - Acoustical Panel Ceilings_06152022.pdf
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.
2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, tempe...
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained ...
B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed. Do not proceed with installation of ceilings until deficiencies hav...
1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.
2. Before notifying Architect, complete the following in areas to receive ceilings:
a. Installation of lighting fixtures, powered for operation.
b. Installation, insulation, and leak and pressure testing of water piping systems.
c. Installation of air-duct systems.
d. Installation of air devices.
e. Installation of mechanical system control-air tubing.
f. Installation of ceiling support framing.

C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.

PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.
B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)
A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.
2. Pattern: E.
C. Color: White.
D. LR: Not less than 0.90.
E. NRC: Not less than 0.95.
F. Humidity/Sag Resistance: Humiguard Plus.
G. Edge/Joint Detail: Square edge.
H. Thickness: 5/8 inch.
I. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Clean Room VL
2. CertainTeed Corp.; Performa, Vinyrock
3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.
2. Pattern: As indicated by manufacturer’s designation.
C. Color: White.
D. LR: Not less than 0.78.
E. CAC: Not less than 38.
F. Edge/Joint Detail: Square.
G. Thickness: 1/2 inch.
H. Modular Size: 24 by 24 inches.
2.5 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.
2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation
B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating desig...
1. Structural Classification: Intermediate-duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Steel cold-rolled sheet.
5. Cap Finish: Painted white.
2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard
2. CertainTeed Corp.; Classic Environmental Stab

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
Bid Invitation —