This file summary outlines renovation requirements for bathrooms at a Veterans Affairs facility. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is soliciting bids for project number 626A4-17-101 to renovate bathrooms. The construction magnitude is estimated between $500,000 and $1,000,000. Interested parties should respond to solicitation number 36C24922B0003 by the specified deadline to be considered for the award, which is expected to be issued for this project requiring bathroom renovations at a Veterans Affairs medical center.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

626A4-17-101 Renovate Bathrooms

Eliminate the following work from the project:

1. All work in Building 1

2. All Work in Building 5

3. All work associated with room G-02 in Building 9

Addendum - Replace all push plates for all automatic door openers applicable to this project with touchless type.

Basis of design - BEA 4-3/4 inch square Model #10MS21HS1

2. Facility Standard - T & S Brass B-1141-2VL15CR4 with Chigago Faucets thermostatic mixing valve 131-CFMABRCF -

A R CH W A Y

C C - 5 /7

C O RR I DO R 4 /5

C O NN E C TI NG

C C -5 /6

5"

P-420

P-115

P-201

P-420 P-420 P-420

P-201

P-115

P-115

P-115

P-115

P-115

P-420 P-524

SAN

5"5"

4" 4"

2"

4"

FD-C

FD-C

2" 2"

2" BELOW SLAB

4"

WCO

WCO

WCOWCO

P-609

P-420

P-115

P-201

P-420 P-420 P-420

P-201

P-115

P-115

P-115

P-115

P-115

P-420 P-524

3/4" 1"

FD-C

FD-C

1/2"

3/4"

1/2"

P-609

WATER

LINES ARE

ABOVE

CEILING

WATER

LINES ARE

ABOVE

CEILING

WATER

LINES ARE

ABOVE

CEILING

WATER

LINES ARE

ABOVE

CEILING

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

F

E

D

C

B

A

VA FORM 08-6231

AS SHOWN

16-337

RENOVATE BATHROOMS -

ALVIN C. YORK VA MEDICAL

CENTER MURFREESBORO, TN

626A4-17-101

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

G G

AS INDICATED

DECEMBER 18, 2017

VAMC MURFREESBORO CAMPUS

3400 LEBANON RD,

MURFREESBORO, TN 37129

JEFF SEABORN

www.acg-pa.com

919-858-7420

Raleigh, NC

Indianapolis, IN

Pittsburgh, PA

Virginia Beach, VA

Atlanta, GA

Fort Collins, CO

SHEET KEY NOTES

SMHSPG

P-102

BUILDING 5

ENLARGED PLUMBING DEMOLITION

AND NEW WORK PLANS

KEY PLAN

SCALE: N.T.S.

AREA OF

WORK

1. DEMOLISH PLUMBING FIXTURE, CAP SANITARY LINE, AND DEMOLISH WATER

LINE TO LOCATION INDICATED AND CAP.

2. PROVIDE FAUCET. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

3. PROVIDE WATER CLOSET. ROUTE SANITARY AND DOMESTIC WATER TO

FIXTURE.

4. PROVIDE URINAL. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

5. PROVIDE DOUBLE COMPARTMENT KITCHEN SINK. ROUTE SANITARY AND

DOMESTIC WATER TO FIXTURE.

6. PROVIDE NEW FLOOR DRAIN PIPED TO EXISTING SANITARY AS INDICATED.

PROVIDE PRESSURE TRAP PRIMER ABOVE CEILING WITH ISOLATION VALVE.

PROVIDE LABEL ON CEILING TO IDENTIFY THE LOCATION FOR MAINTENANCE.

SHEET NOTES

1. SLEEVE ALL PENETRATIONS, FIRESTOP OR SEAL AS REQUIRED.

2. UNLESS NOTED OTHERWISE, THE SIZE OF FIXTURE RUNOUTS IS TO BE WHAT

IS LISTED IN THE PLUMBING FIXTURE SCHEDULE.

3. DOMESTIC WATER AND SANITARY PIPES ARE BELOW SLAB OR IN WALL AND

VENT PIPES ARE ABOVE CEILING UNLESS NOTED OTHERWISE.

4. SEAL NEW AND EXISTING PIPE PENETRATIONS THROUGH FLOOR WATER

TIGHT.

ASBESTOS NOTE

1. OBTAIN ACM REPORT FROM COR BEFORE PERFORMING WORK. NOTIFY COR

WHEN ACM IS ENCOUNTERED THEN REMOVE ACCORDING TO METHODS

INDICATED IN THE SPECIFICATIONS.

WALL LEGEND

3 ADDENDUM NO. 3 TRAP PRIMERS 11/27/2019

P-115

P-420

P-420

P-115

1"

1"

WATER

LINES ARE

UNDER

SLAB

CO

1/2" DCW & DHW

WATER

LINES ARE

UNDER

SLAB

WATER LINES ARE UNDER SLAB

3/4" DHW

2" DCW

WASTE LINES

ARE UNDER SLAB

EXISTING VENT

P-115 P-201

P-420

P-115 P-201

P-201

P-420

1"

FD-C

1"

1"

1/2" DCW & DHW

WATER

LINES ARE

UNDER

SLAB

WATER

LINES ARE

UNDER

SLAB

WASTE

LINES ARE

UNDER

SLAB

U P

D N

U P

D N

P-115 P-201

P-420

P-115 P-201

P-201

P-420

4" SAN

2" V

FD-C

2" V

2" SAN

2" SAN

2" V

WCO

WASTE LINES

ARE UNDER SLAB

4" SAN

EXISTING VENT

P-115

P-420

P-420

P-115

2" V

4"

4"

2"

WASTE

LINES ARE

UNDER

SLAB

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

F

E

D

C

B

A

VA FORM 08-6231

AS SHOWN

16-337

RENOVATE BATHROOMS -

ALVIN C. YORK VA MEDICAL

CENTER MURFREESBORO, TN

626A4-17-101

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

G G

AS INDICATED

DECEMBER 18, 2017

VAMC MURFREESBORO CAMPUS

3400 LEBANON RD,

MURFREESBORO, TN 37129

JEFF SEABORN

www.acg-pa.com

919-858-7420

Raleigh, NC

Indianapolis, IN

Pittsburgh, PA

Virginia Beach, VA

Atlanta, GA

Fort Collins, CO

SMHSPG

P-103

BUILDING 7

ENLARGED PLUMBING DEMOLITION AND

NEW WORK PLANS

KEY PLAN

SCALE: N.T.S.

AREA OF

WORK

SHEET KEY NOTESSHEET KEY NOTES

1. DEMOLISH PLUMBING FIXTURE, CAP SANITARY LINE, AND DEMOLISH WATER

LINE TO LOCATION INDICATED AND CAP.

2. PROVIDE FAUCET. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

3. PROVIDE WATER CLOSET AND HEAVY DUTY CARRIER. ROUTE SANITARY AND

DOMESTIC WATER TO FIXTURE.

4. PROVIDE URINAL. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

5. PROVIDE WATER CLOSET. ROUTE SANITARY AND DOMESTIC WATER TO

FIXTURE.

6. ROUTE NEW 1" DCW LINE FROM MAIN IN PIPE BASEMENT.

7. PROVIDE NEW FLOOR DRAIN PIPED TO EXISTING SANITARY AS INDICATED.

PROVIDE PRESSURE TRAP PRIMER ABOVE CEILING WITH ISOLATION VALVE.

PROVIDE LABEL ON CEILING TO IDENTIFY THE LOCATION FOR MAINTENANCE.

8. DEMOLISH ABANDONED PIPE TO MAIN IN CRAWL SPACE.

9. EXISTING WATER LINES TO REMAIN.

SHEET NOTES

1. SLEEVE ALL PENETRATIONS, FIRESTOP OR SEAL AS REQUIRED.

2. UNLESS NOTED OTHERWISE, THE SIZE OF FIXTURE RUNOUTS IS TO BE WHAT

IS LISTED IN THE PLUMBING FIXTURE SCHEDULE.

3. DOMESTIC WATER AND SANITARY PIPES ARE BELOW SLAB OR IN WALL AND

VENT PIPES ARE ABOVE CEILING UNLESS NOTED OTHERWISE.

4. SEAL NEW AND EXISTING PIPE PENETRATIONS THROUGH FLOOR WATER

TIGHT.

ASBESTOS NOTE

1. OBTAIN ACM REPORT FROM COR BEFORE PERFORMING WORK. NOTIFY COR

WHEN ACM IS ENCOUNTERED THEN REMOVE ACCORDING TO METHODS

INDICATED IN THE SPECIFICATIONS.

WALL LEGEND

2 HOUR FIREWALL

P-114

P-420

P-114

SAN

SAN

2"

6"

5"

4"

P-201

P-115

P-420

FD-C

4"

2"

SAN

SAN

2"

6"

5"

4"

C O NN E C TI NG

C O RR I DO R -8 /9

C O NN E C TI NG

C O RR I DO R -7 /8

P-201

P-115

P-420

SAN

6"

6" 5"

4" SAN

CO

FD-C

4" SAN

2" V

2" V

WCO

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

F

E

D

C

B

A

VA FORM 08-6231

AS SHOWN

16-337

RENOVATE BATHROOMS -

ALVIN C. YORK VA MEDICAL

CENTER MURFREESBORO, TN

626A4-17-101

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

G G

AS INDICATED

DECEMBER 18, 2017

VAMC MURFREESBORO CAMPUS

3400 LEBANON RD,

MURFREESBORO, TN 37129

JEFF SEABORN

www.acg-pa.com

919-858-7420

Raleigh, NC

Indianapolis, IN

Pittsburgh, PA

Virginia Beach, VA

Atlanta, GA

Fort Collins, CO

SMHSPG

P-104

BUILDING 8

ENLARGED PLUMBING DEMOLITION AND

NEW WORK PLANS

KEY PLAN

SCALE: N.T.S.

AREA OF

WORK

SHEET KEY NOTESSHEET KEY NOTES

1. DEMOLISH PLUMBING FIXTURE, CAP SANITARY LINE, AND DEMOLISH WATER

LINE TO LOCATION INDICATED AND CAP.

2. PROVIDE FAUCET. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

3. PROVIDE WATER CLOSET AND HEAVY DUTY CARRIER. ROUTE SANITARY AND

DOMESTIC WATER TO FIXTURE.

4. PROVIDE URINAL. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

5. PROVIDE NEW FLOOR DRAIN PIPED TO EXISTING SANITARY AS INDICATED.

PROVIDE PRESSURE TRAP PRIMER ABOVE CEILING WITH ISOLATION VALVE.

PROVIDE LABEL ON CEILING TO IDENTIFY THE LOCATION FOR MAINTENANCE.

SHEET NOTES

1. SLEEVE ALL PENETRATIONS, FIRESTOP OR SEAL AS REQUIRED.

2. UNLESS NOTED OTHERWISE, THE SIZE OF FIXTURE RUNOUTS IS TO BE WHAT

IS LISTED IN THE PLUMBING FIXTURE SCHEDULE.

3. DOMESTIC WATER AND SANITARY PIPES ARE BELOW SLAB OR IN WALL AND

VENT PIPES ARE ABOVE CEILING UNLESS NOTED OTHERWISE.

4. SEAL NEW AND EXISTING PIPE PENETRATIONS THROUGH FLOOR WATER

TIGHT.

ALTERNATE NOTES*

2 OMIT BUILDING 8 WOMEN G12 RENOVATION

ASBESTOS NOTE

1. OBTAIN ACM REPORT FROM COR BEFORE PERFORMING WORK. NOTIFY COR

WHEN ACM IS ENCOUNTERED THEN REMOVE ACCORDING TO METHODS

INDICATED IN THE SPECIFICATIONS.

WALL LEGEND

2 ADDENDUM NO. 2 SCOPE CHANGES 01/21/2019

4"

2"

P-420 P-420

P-114

P-114 P-114

P-115

P-420

P-201

FD-C

WCO

P-115 P-420

C O RR I DO R - 8/9

C O NN E C TI NG

C O NN E C TI NG

C O RR I DO R 2 /9

P-115

P-420

P-201

SAN

4" SAN

FD-C

CO

2" V

WCO

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

F

E

D

C

B

A

VA FORM 08-6231

AS SHOWN

16-337

RENOVATE BATHROOMS -

ALVIN C. YORK VA MEDICAL

CENTER MURFREESBORO, TN

626A4-17-101

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

G G

AS INDICATED

DECEMBER 18, 2017

VAMC MURFREESBORO CAMPUS

3400 LEBANON RD,

MURFREESBORO, TN 37129

JEFF SEABORN

www.acg-pa.com

919-858-7420

Raleigh, NC

Indianapolis, IN

Pittsburgh, PA

Virginia Beach, VA

Atlanta, GA

Fort Collins, CO

SMHSPG

P-105

BUILDING 9

ENLARGED PLUMBING DEMOLITION AND

NEW WORK PLANS

SHEET KEY NOTESSHEET KEY NOTES

1. DEMOLISH PLUMBING FIXTURE, CAP SANITARY LINE, AND DEMOLISH WATER

LINE TO LOCATION INDICATED AND CAP.

2. PROVIDE FAUCET. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

3. PROVIDE WATER CLOSET. ROUTE SANITARY AND DOMESTIC WATER TO

FIXTURE.

4. PROVIDE URINAL. ROUTE SANITARY AND DOMESTIC WATER TO FIXTURE.

5. PROVIDE NEW FLOOR DRAIN PIPED TO EXISTING SANITARY AS INDICATED.

PROVIDE PRESSURE TRAP PRIMER ABOVE CEILING WITH ISOLATION VALVE.

PROVIDE LABEL ON CEILING TO IDENTIFY THE LOCATION FOR MAINTENANCE

6. PIPE CHASE CONTAINS KNOWN ACM.

SHEET NOTES

AREA OF

WORK

1. SLEEVE ALL PENETRATIONS, FIRESTOP OR SEAL AS REQUIRED.

2. UNLESS NOTED OTHERWISE, THE SIZE OF FIXTURE RUNOUTS IS TO BE WHAT

IS LISTED IN THE PLUMBING FIXTURE SCHEDULE.

3. DOMESTIC WATER AND SANITARY PIPES ARE BELOW SLAB OR IN WALL AND

VENT PIPES ARE ABOVE CEILING UNLESS NOTED OTHERWISE.

4. SEAL NEW AND EXISTING PIPE PENETRATIONS THROUGH FLOOR WATER

TIGHT.

ALTERNATE NOTES*

3 OMIT BUILDING 9 WOMEN G17 RENOVATION*

KEY PLAN

SCALE: N.T.S.

ASBESTOS NOTE

1. OBTAIN ACM REPORT FROM COR BEFORE PERFORMING WORK. NOTIFY COR

WHEN ACM IS ENCOUNTERED THEN REMOVE ACCORDING TO METHODS

INDICATED IN THE SPECIFICATIONS.

WALL LEGEND

2 ADDENDUM NO. 2 SCOPE CHANGES 01/21/2019