Asbestos Survey 7 8 9.pdf

PDF 719 KB Posted

Attached to
Z2DA--36C249-21-AP-4235 - 626A4-17-101 - Renovate Bathrooms
Solicitation number
36C24922B0003
Issued by

About this file

This document contains drawings and notes from an asbestos survey of buildings 8, 9, and their mechanical systems at the TVHS Alvin C. York Campus. The drawings identify the location and extent of asbestos-containing materials such as pipe insulation, floor tiles, mastics, transite panels, fire doors, and duct connectors. Notes indicate additional asbestos may be concealed and presume the presence of asbestos in certain materials.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Veterans Health Administration VISN 9 to renovate bathrooms at the campus between $500,000 and $1 million. The drawings and notes provide necessary information on existing asbestos-containing materials to properly scope and price the renovation work for the solicited contract.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONNECTING

CORRIDOR 2/9

DATE: OCTOBER 2009

SCALE: NTS

10 New England Business Center Drive, Suite 105 Andover, MA 01810

TF: (800) 659-1202

PH: (978) 688-3736

FAX: (978) 688-5494

www.efiglobal.com

TVHS, ALVIN C. YORK CAMPUS

ACM LOCATION DRAWING

BLDG #9, GROUND FLOOR

NOTES

1. ASBESTOS-CONTAINING PIPE & PIPE

FITTING INSULATION MAY BE

CONCEALED BEHIND WALLS, ABOVE

CEILINGS & WITHIN MECHANICAL

CHASES.

2. PRESUMED ASBESTOS-CONTAINING

TRANSITE PANELS MAY BE PRESENT

BEHIND RADIATORS WITHIN THE

BUILDING.

3. ASBESTOS-CONTAINING BLACK TAR

COATING IS PRESENT ON FIBERGLASS

PIPE & DUCT INSULATION

THROUGHOUT BUILDING.

4. PRESUMED ASBESTOS-CONTAINING

FIRE DOORS & ELEVATOR DOORS ARE

PRESENT THROUGHOUT BUILDING.

LEGEND

= ASBESTOS-CONTAINING PIPE

INSULATION

= ASBESTOS-CONTAINING

FLOOR TILE & ASSOCIATED

MASTIC

= ASBESTOS-CONTAINING PIPE

FITTING INSULATION

DATE: OCTOBER 2009

SCALE: NTS

10 New England Business Center Drive, Suite 105 Andover, MA 01810

TF: (800) 659-1202

PH: (978) 688-3736

FAX: (978) 688-5494

www.efiglobal.com

TVHS, ALVIN C. YORK CAMPUS

ACM LOCATION DRAWING

BLDG #9, 1ST FLOOR

NOTES

1. ASBESTOS-CONTAINING PIPE & PIPE

FITTING INSULATION MAY BE

CONCEALED BEHIND WALLS, ABOVE

CEILINGS & WITHIN MECHANICAL

CHASES.

2. PRESUMED ASBESTOS-CONTAINING

TRANSITE PANELS MAY BE PRESENT

BEHIND RADIATORS WITHIN THE

BUILDING.

3. ASBESTOS-CONTAINING BLACK TAR

COATING IS PRESENT ON FIBERGLASS

PIPE & DUCT INSULATION

THROUGHOUT BUILDING.

4. PRESUMED ASBESTOS-CONTAINING

FIRE DOORS & ELEVATOR DOORS ARE

PRESENT THROUGHOUT BUILDING.

LEGEND

= ASBESTOS-CONTAINING PIPE

INSULATION

= ASBESTOS-CONTAINING

FLOOR TILE & ASSOCIATED

MASTIC

10 New England Business Center Drive, Suite 105 Andover, MA 01810

TF: (800) 659-1202

PH: (978) 688-3736

FAX: (978) 688-5494

www.efiglobal.com

TVHS, ALVIN C. YORK CAMPUS

ACM LOCATION DRAWING

BLDG #9, 2ND FLOOR

NOTES

1. ASBESTOS-CONTAINING PIPE & PIPE

FITTING INSULATION MAY BE

CONCEALED BEHIND WALLS, ABOVE

CEILINGS & WITHIN MECHANICAL

CHASES.

2. PRESUMED ASBESTOS-CONTAINING

TRANSITE PANELS MAY BE PRESENT

BEHIND RADIATORS WITHIN THE

BUILDING.

3. ASBESTOS-CONTAINING BLACK TAR

COATING IS PRESENT ON FIBERGLASS

PIPE & DUCT INSULATION

THROUGHOUT BUILDING.

4. PRESUMED ASBESTOS-CONTAINING

FIRE DOORS & ELEVATOR DOORS ARE

PRESENT THROUGHOUT BUILDING.

LEGEND

= ASBESTOS-CONTAINING PIPE

INSULATION

= ASBESTOS-CONTAINING

FLOOR TILE & ASSOCIATED

MASTIC

NOTES

SCALE: NTS

10 New England Business Center Drive, Suite 105 Andover, MA 01810

TF: (800) 659-1202

PH: (978) 688-3736

FAX: (978) 688-5494

www.efiglobal.com

TVHS, ALVIN C. YORK CAMPUS

ACM LOCATION DRAWING

BLDG #9, 3RD FLOOR

LEGEND

= ASBESTOS-CONTAINING

CLOTH DUCT CONNECTOR

10 New England Business Center Drive, Suite 105 Andover, MA 01810

TF: (800) 659-1202

PH: (978) 688-3736

FAX: (978) 688-5494

www.efiglobal.com

TVHS, ALVIN C. YORK CAMPUS

ACM LOCATION DRAWING

BLDG #8, GROUND FLOOR

NOTES

1. ASBESTOS-CONTAINING PIPE &

PIPE FITTING INSULATION MAY BE

CONCEALED BEHIND WALLS, ABOVE

CEILINGS & WITHIN MECHANICAL

CHASES.

2. PRESUMED

ASBESTOS-CONTAINING FIRE DOORS

& ELEVATOR DOORS ARE PRESENT

THROUGHOUT BUILDING.

3. PRESUMED

ASBESTOS-CONTAINING TRANSITE

PANELS MAY BE PRESENT BEHIND

RADIATORS.

4. ASBESTOS-CONTAINING THERMAL

SYSTEMS INSULATION DEBRIS &

CONTAMINATED SOIL ARE PRESENT

THROUGHOUT THE BUILDING STEAM

TUNNELS (SEE STEAM TUNNEL

DRAWING).