Drawing 2.pdf

PDF 100 KB Posted

Attached to
Lenel Access Control System Federal contract opportunity
Solicitation number
FA282322Q0016
Issued by
Department of the Air Force Materiel Command Test Center

View the file

Other files for this federal contract opportunity

Other files attached to Lenel Access Control System, newest first.
File Type Posted
Solicitation Amendment - FA282322Q00160001.pdf PDF
Solicitation Amendment FA282322Q00160001 SF 30.pdf PDF
Wage Determination.pdf PDF
Site Visit.pdf PDF
Drawing 1.pdf PDF
Solicitation - FA282322Q0016.pdf PDF
SSJ_Redacted.pdf PDF
SOW 4.1.22.pdf PDF
Request Base Access.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNSECURE SIDE SECURE SIDE

CEILING

FLOOR

J

B M

3/4" C WITH 2-#18 CONTROL WIRES TO

ROOM INDICATED ON PLAN FOR USER

INTERLOCK SYSTEM (IF INDICATED)

UNSECURE SIDE SECURE SIDE

CEILING

FLOOR

J

CR EL

B M

3/4" C EMPTY W. PULL ROPE TO

LOCATION SHOWN ON PLAN FOR

ACCESS CONTROL PANEL

3/4" C WITH 2-#18 CONTROL WIRES TO

ROOM INDICATED ON PLAN FOR USER

INTERLOCK SYSTEM (IF INDICATED)

120V POWER (AS REQUIRED FOR

HARDWARE). SEE POWER PLANS

J

3/4" CONDUIT

SLEEVE THRU

WALL

4X4 JUNCTION BOX

EXTERIOR WALL

SEE ARCHITECTURAL

ELEVATIONS

3/4"C TO

COMMUNICATIONS

ROOM

' A

FG

CAMERA HOUSING

AND CAMERA ARE

GFGI

CAP CONDUIT

EG

LI

N

AI

R

FO

RC

E

BA

SE

, F

LO

RI

DA

AD

VA

N C

ED

M

U N

IT

IO

N S

TE

C

H N

O

LO

G Y

C O

M

PL

EX

P

H

AS

E

II

PR

O

JE

C

T N

O . F

TF

A0

M

O

BI

LE

D

IS

TR

IC

T

M O

BI

LE

, A

LA

BA

M

A

Mobile District

US Army Corps of Engineers ®

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

N O

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

SHEET

IDENTIFICATION

1 2 3 4 5

D

C

B

A

FILE:

DATE:

W

AR

D P

AR

KW

AY

KA

N

SA

S C

IT

Y, M O

BU

RN

S

M cD

O

NN

EL

L

D

ES

IG

N

ED

B

Y:

D R

AW

N

B Y:

SB

M

T

BY

PL

O

T

SC

AL

E:

SI

ZE

" x

4"

FI

LE

N

AM

E:

C

KD

B Y:

PL

O

T D

AT

E:

D

AT

E:

SO

LI

C

IT

AT

IO

N N

U M

BE

R

PR

O

JE

C

T N

U M

BE

R

C

AD

D C

O D

E:

W

8-

-R

-0

FT

FA

M

EF

FTFA043000

JU

N

E, JU

N

E, 6/22/2020 3:00:15 PM

As in dic at ed

P.

O

'G

OR

M

AN

A.

S

NE

TH

EN

C.

P

LU

M M

ER

12276401-EY5010050

-0

1-

EY

01-EY501

SE

C

U R

IT

Y

D

ET

AI

LS

ST

AN

D

AR

D D

ET

AI

LS

NTSSCALE:C1 1.1 - ALARM SINGLE DOOR

NTSSCALE:C3 1.2 - ALARM/ACCESS SINGLE DOOR

NTSSCALE:A1 EXTERIOR CAMERA ROUGH-IN

GENERAL NOTES:

1. BMS SWITCHES SHALL BE UL 634 LEVEL 2 HIGH SECURITY TYPE.

FOR DOORS INDICATED WITH CONNECTIONS TO USER PROVIDED

SAFETY INTERLOCK SYSTEM, PROVIDE BMS WITH DUAL OUTPUT

CONTACTS.

ALL BMS SWITCHES BEING INSTALLED INTERIOR TO A CLASS II

HAZARDOUS LOCATION SHALL BE INSTALLED PER NEC AND SHALL

BE SUITABLE AS AN INTRINSICALLY SAFE APARATUS. ALL

CONNECTIONS TO THE BMS (BY OTHERS) SHALL UTILIZE

INTRINSICALLY SAFE SYSTEMS.

2.

CEILING

FLOOR

UNSECURE SIDE SECURE SIDE

B M

B M

JJ 3/4" C WITH 2-#18 CONTROL

WIRES TO ROOM INDICATED

ON PLAN FOR USER

INTERLOCK SYSTEM (IF

INDICATED). FOR BUILDING

05 STORAGE BUNKER,

ROUTE TO IDS PANEL

ENCLOSURE

CEILING

FLOOR

UNSECURE SIDE SECURE SIDE

JJ

B M

B M

CR EL

HINGESET

3/4" C EMPTY W. PULL

ROPE TO LOCATION

SHOWN ON PLAN FOR

ACCESS CONTROL

PANEL

3/4" C WITH 2-#18 CONTROL

WIRES TO ROOM INDICATED ON

PLAN FOR USER INTERLOCK

SYSTEM (IF INDICATED)

120V POWER (AS REQUIRED FOR

HARDWARE). SEE POWER PLANS

J

FLOOR

B M

J

3/4" C EMPTY W. PULL ROPE TO

LOCATION SHOWN ON PLAN FOR

ACCESS CONTROL PANEL

3/4" C WITH 2-#18 CONTROL WIRES TO

ROOM INDICATED ON PLAN FOR USER

INTERLOCK SYSTEM (IF INDICATED)

EG

LI

N

AI

R

FO

RC

E

BA

SE

, F

LO

RI

DA

AD

VA

N C

ED

M

U N

IT

IO

N S

TE

C

H N

O

LO

G Y

C O

M

PL

EX

P

H

AS

E

II

PR

O

JE

C

T N

O . F

TF

A0

M

O

BI

LE

D

IS

TR

IC

T

M O

BI

LE

, A

LA

BA

M

A

Mobile District

US Army Corps of Engineers ®

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

N O

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

SHEET

IDENTIFICATION

1 2 3 4 5

D

C

B

A

FILE:

DATE:

W

AR

D P

AR

KW

AY

KA

N

SA

S C

IT

Y, M O

BU

RN

S

M cD

O

NN

EL

L

D

ES

IG

N

ED

B

Y:

D R

AW

N

B Y:

SB

M

T

BY

PL

O

T

SC

AL

E:

SI

ZE

" x

4"

FI

LE

N

AM

E:

C

KD

B Y:

PL

O

T D

AT

E:

D

AT

E:

SO

LI

C

IT

AT

IO

N N

U M

BE

R

PR

O

JE

C

T N

U M

BE

R

C

AD

D C

O D

E:

W

8-

-R

-0

FT

FA

M

EF

FTFA043000

JU

N

E, JU

N

E, 6/22/2020 3:00:16 PM

1/ 2"

'-0

P.

O

'G

OR

M

AN

A.

S

NE

TH

EN

C.

P

LU

M M

ER

12276401-EY5020050

-0

1-

EY

01-EY502

SE

C

U R

IT

Y

D

ET

AI

LS

ST

AN

D

AR

D D

ET

AI

LS

NTSSCALE:C1 2.1 - ALARM DOUBLE DOOR

NTSSCALE:C3 2.2 - ALARM/ACCESS DOUBLE DOOR

NTSSCALE:A1 3.1 - ALARM OVERHEAD DOOR

GENERAL NOTES:

1. BMS SWITCHES SHALL BE UL 634 LEVEL 2 HIGH SECURITY TYPE.

FOR DOORS INDICATED WITH CONNECTIONS TO USER PROVIDED

SAFETY INTERLOCK SYSTEM, PROVIDE BMS WITH DUAL OUTPUT

CONTACTS.

ALL BMS SWITCHES BEING INSTALLED INTERIOR TO A CLASS II

HAZARDOUS LOCATION SHALL BE INSTALLED PER NEC AND SHALL

BE SUITABLE AS AN INTRINSICALLY SAFE APARATUS. ALL

CONNECTIONS TO THE BMS (BY OTHERS) SHALL UTILIZE

INTRINSICALLY SAFE SYSTEMS.

2.